System Sensor B404BT Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
B404BT Plug-in Detector Base
1-800-SENSOR2, FAX: 630-377-6495
Specifications
Base Diameter: 6.2 inches (15.7 cm) Base Height: 1.1 inches (2.9cm) Weight: 0.6 lb. (260 g) Mounting: 4-inch square box without plaster ring. Minimum depth–1.5 inches
4-inch octagon box. Minimum depth–1.5 inches
Operating Temperature Range: 0° to 49°C (32° to 120°F) Operating Humidity Range: 10% to 93% Relative Humidity
Electrical Ratings – includes base and detector
System Voltage: 24 VAC/DC, 60 Hz Relay Contact Ratings Resistive or Inductive (60% power factor) load Form A: 2.0A @ 30VAC/DC Form C: 2.0A @ 30VAC/DC
0.6A @ 110VDC
1.0A @ 125VAC (If used, the RA400 Remote Annunciator and RTC operates within the specified detec-
tor system voltage.) Start-up Time: 36.0 Seconds maximum (After 60 second reset)
A Division of Pittway
Before Installing
Please thoroughly read System Sensor’s manual I56-407, Guide for Proper Use of System Smoke Detectors. This manual provides detailed information on detector spacing, placement, zoning, wiring, and special applications, and is available at no charge from System Sensor.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with this base must be tested and maintained regularly following NFPA 72 re­quirements. The detector used with this base should be cleaned at least once a year.
General Description
The B404BT detector base is designed for use with Sys­tem Sensor model 2451 and 2451TH photoelectronic and 1451 ionization detector heads. The capability of plug­ging these detectors into a variety of special bases makes them more versatile than equivalent direct-wired models. Refer to the System Sensor catalog for other available plug-in bases. The B404BT base is intended for use in 4-wire systems with terminals provided for re­mote annunicator and relay connections.
Power
Wire leads are provided for 24 VAC/DC power operation.
D450-10-00 1 I56-530-03
Base Terminals
No. Function 1 Remote Annunciator (+) 2 Test Coil (+) 3 Not used 4 Remote Annunciator (-) 5 RTC (-) 6 N.O. Supervisory Relay 7 N.O Form A Contacts 8 N.O. Alarm Relay 9 N.O. Form A 10 C. Initiation 11 C. Contacts 12 N.O. Alarm Relay 13 N.C. Form C 14 C. Auxiliary Contacts
Mounting
The detector base mounts directly to 4-inch octagon boxes and 4-inch square boxes. To mount the base, remove the decorative ring by rotating it in either direction to unhook the snaps before separating the ring from the base. Use the screws supplied with the junction box to attach the base to the box through the appropriate mounting slots in the base.
}
}
}
Figure 1. Base Terminals
Figure 2. Mounting Base to Box
Position the decorative ring around the base and rotate it in either direction until the ring snaps into place (see Figure 2).
Installation Guidelines
All wiring must be installed in compliance with the Na­tional Electrical Code, all applicable local codes, and any special requirements of the authority having jurisdiction, using the proper wire size. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring er­rors. Improper connections can prevent a system from re­sponding properly in the event of a fire.
For signal wiring (the wiring between interconnected detectors), it is recommended that the wire be no smaller than 16 gauge (1.5 square mm), and that two­or three-conductor wire be no smaller than 18 gauge (1.0 square mm). For best performance, alarm loop con­ductors should be installed in separate grounded con­duit or shielded cable to protect the alarm loop from extraneous electrical interference.
SHORTING SPRING
SNAP ON DECORATIVE RING
SCREWS (NOT SUPPLIED)
DETECTOR BASE
BOX (NOT SUPPLIED)
Smoke detectors and alarm systems control panels have specifications for allowable loop resistance. Consult the control panel manufacturer’s specifications for the total loop resistance allowed for the particular model control panel being used before wiring the detector loops.
D450-10-00 2 I56-530-03
A78-1175-01
R
Figure 3. Typical Wiring Diagram for 24VAC rms/DC Detector Systems
W
APA451
N
W N
APA451
RELEASING DEVICE
14
13
12
24 VACrms/DC
11
CONTROL
PANEL
24 VACrms/DC
BLACK LEADS TRANSFORMER PRIMARY
ALARM INITIATION LOOP
4
3
2
5
1
6
10
7
9
8
NOTE: ABOVE DIAGRAM SHOWS NFPA REQUIRED WIRING OF SUPERVISED
SYSTEMS. SCHEMATIC SHOWN BELOW FOR REFERENCE.
SUPERVISORY RELAY
CONTROL
PANEL
ALARM RELAY
Wiring Instructions
NOTE: Refer to the manufacturer’s instructions for releas-
ing device wiring.
NOTE: To ensure that electrical connections are super-
vised, do NOT loop wires under terminals 8, 9, 10, and 11. Cut the wire at each terminal.
RELEASING
3
2
6
7
SUPERVISORY RELAY
ALARM RELAY
4
5
1
10
9
8
DEVICE
14
13
12
11
EOL
SPECIFIED BY PANEL MANUFACTURE
EOL
SPECIFIED BY PANEL MANUFACTURER
A78-1577-09
shorting spring since it reengages as the detector head is turned into the base, completing the circuit
Tamper-resistance Feature
This detector base also includes an optional tamper-resis­tant feature that when activated prevents removal of the detector without the use of a tool.
To make electrical connections, strip approximately 3/8" (1 cm) insulation from the end of each wire, slide the bare
To make the base tamper resistant, simply break off the tab
on the base (see Figure 4A), before installing the detector. wire end under the clamping plate, and tighten the clamp­ing plate screw. Use the strip gauges molded into the in­side and underside of the base for ease of wiring to terminals 1 and 4, and to terminals 6 through 14, respec­tively.
To remove the detector from the base after it has been
made tamper resistant, insert a small screwdriver (see Fig-
ure 4B) into the small hole and press the plastic lever away
from the detector. Rotate the detector counterclockwise
and remove. The zone wiring of the detector base should be checked
before installing the smoke detector heads. The base con­tains a built-in shorting spring to make this possible. After the detector base is wired and mounted to an electrical box,
NOTE: Head removal after activating the tamper-resis-
tance feature first requires removal of the decora­tive ring.
position the shorting spring against terminal 3. This tem­porary connection energizes the supervisory relay and per­mits the wiring of the loop to be checked for continuity.
After all detector bases have been mounted, wired, and the wiring checked, install the detector heads. The shorting spring in the base automatically disengages when the de­tector head is removed from the base. DO NOT remove the
D450-10-00 3 I56-530-03
Figure 4A. Activating Tamper-Resistance Feature Figure 4B. Removing Detector Head from Base
BREAK TAB AT
PLASTIC LEVER
DOTTED LINE BY TWISTING TOWARD CENTER OF BASE.
The Limitations of Property Protection Smoke Detectors
The smoke detector used with this base is designed to activate and ini­tiate emergency action, but will do so only when it is used in conjunction
with an authorized fire alarm system. This detector must be installed in accordance with NFPA standard 72.
Smoke detectors will not work without power. AC or DC powered smoke detectors will not work if the power supply is cut off.
Smoke detectors will not sense fires which start where smoke does not reach the detectors. Smoldering fires typically do not generate a lot of
heat which is needed to drive the smoke up to the ceiling where the smoke detector is usually located. For this reason, there may be large de­lays in detecting a smoldering fire with either an ionization type detector or a photoelectric type detector. Either one of them may alarm only after flaming has initiated which will generate the heat needed to drive the smoke to the ceiling.
Smoke from fires in chimneys, in walls, on roofs or on the other side of a closed door(s) may not reach the smoke detector and alarm it. A detector cannot detect a fire developing on another level of a building quickly or at all. For these reasons, detectors shall be located on every level and in
every bedroom within a building.
Smoke detectors have sensing limitations, too. Ionization detectors and
photoelectric detectors are required to pass fire tests of the flaming and
USE SMALL-BLADED SCREWDRIVER TO PUSH PLASTIC LEVER IN DIRECTION OF ARROW.
WARNING
smoldering type. This is to ensure that both can detect a wide range of types of fires. Ionization detectors offer a broad range of fire sensing capa­bility but they are somewhat better at detecting fast flaming fires than slow smoldering fires. Photoelectric detectors sense smoldering fires better than flaming fires which have little, if any, visible smoke. Because fires de­velop in different ways and are often unpredictable in their growth, nei­ther type of detector is always best, and a given detector may not always provide early warning of a specific type of fire.
In general, detectors cannot be expected to provide warnings for fires re­sulting from inadequate fire protection practices, violent explosions, es­caping gases which ignite, improper storage of flammable liquids like cleaning solvents which ignite, other similar safety hazards, arson, smok­ing in bed, children playing with matches or lighters, etc. Smoke detectors used in high air velocity conditions may have a delay in alarm due to dilu­tion of smoke densities created by frequent and rapid air exchanges. Addi­tionally, high air velocity environments may create increased dust contamination, demanding more frequent maintenance.
Smoke detectors cannot last forever. Smoke detectors contain electronic parts. Even though smoke detectors are made to last over 10 years, any part can fail at any time. Therefore, smoke detectors shall be replaced after being in service for 10 years. The smoke detector system that this detector is used in must be tested regularly per NFPA 72. This smoke detector should be cleaned regularly per NFPA 72 or at least once a year.
A78-1175-03
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector base to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector base. No agent, representa­tive, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obli­gation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector base which is found to be defective in materials or workmanship under normal use and service during the three year pe­riod commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authori­zation number, send defective units postage prepaid to: System Sensor,
Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL
60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negli­gence or fault. Some states do not allow the exclusion or limitation of inci­dental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
D450-10-00 4 I56-530-03
© System Sensor 1997
Loading...