System Sensor B401BR User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
CAUTION
I56-0352-007R
B401BR Plug-in Detector Base
For use with the following detectors: 1451, 2451, and 2451TH
SPECIFICATIONS
Base Diameter: 6.2 inches (157 mm) typical Base Height: 1.1 inches (29 mm) typical Weight: 0.3 lb. (130 g) typical Mounting: 4 inch square box with or without plaster ring. Min. Depth: 1.5 inches 4 inch octagon box. Min. Depth: 1.5 inches 3-1/2 inch octagon box. Min. Depth: 1.5 inches Operating Temperature Range: –10° to 60°C (14° to 140°F) NOTE: Do not install where normal ambient temperature extends beyond 0° to 49° (32° to 120°F) Operating Humidity Range: 10% to 93% Relative Humidity Electrical Ratings — includes base and detector System Voltage: 24 VDC Maximum Ripple Voltage: 4 Volts peak to peak Start-up Capacitance: 0.02 µF Maximum Standby Ratings: 17 VDC Minimum 32 VDC Maximum 120 µA Maximum Alarm Ratings: 10 mA Minimum at 10.5 VDC 62 mA Maximum at 32 VDC The optional RA400Z/RA100Z Remote Annunciator operates within the specified detector alarm currents. Reset Voltage: 2.50 VDC Minimum Reset Time: 0.3 Sec Maximum Start-up Time: 34.0 Sec Maximum
BEFORE INSTALLING
Please thoroughly read the System Sensor manual I56-407, Guide for Proper Use of System Smoke Detectors, which provides detailed information on de­tector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor. (For installations in Canada, refer to CAN4-S524, Standard for the Installation of Fire Alarm Systems, and CEC Part 1, Sec. 32.)
NOTICE: This manual should be left with the owner/user of this equipment. IMPORTANT: The detector used with this base must be tested and maintained regularly following NFPA 72 requirements. The detector used with this base should be cleaned at least once a year.
GENERAL DESCRIPTION
The plug-in detector base B401BR is used with System Sensor 400 Series photoelectronic, ionization, and heat detector heads. The ability to accept a variety of detector heads makes this base more versatile than equivalent direct-wired models. Refer to the System Sensor catalog for other available plug-in detector bases.
This B401BR base is intended for use in 2-wire systems, with screw terminals provided for power, ground, and remote annunciator connections. The B401BR base also contains a resistor to provide current limiting in the alarm state.
MOUNTING
This detector base mounts directly to 31⁄2 inch and 4 inch octagon boxes, and 4 inch square boxes (with or without plaster rings). To mount, remove decora­tive ring by turning it in either direction to unhook the snaps, then separate the ring from the base.
Install the base to the box using the screws supplied with the junction box and the appropriate mounting slots in the base. Place decorative ring onto base, then turn in either direction until the ring snaps in place (see Figure 1).
INSTALLATION GUIDELINES (FIGURE 2)
All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and acces­sory devices should be color-coded to prevent wiring mistakes. Improper con­nections can prevent a system from responding properly in the event of a fire.
For signal wiring (the wiring between interconnected detectors), it is recom­mended that the wire be no smaller than 18 gauge (1.0 square mm). Wire sizes up to 12 gauge wire (2.5 square mm) may be used with the base. For
D450-02-00 1 I56-0352-007R
best system performance, the power (+ and –) loop wires should be twisted pair and installed in separate grounded conduit to protect the loop from elec­trical interference.
Smoke detectors and alarm system control panels have specifications for al­lowable loop resistance. Consult the control panel manufacturer’s specifica­tions for the total loop resistance allowed for the particular model control panel being used before wiring the detector loops.
For system supervision — For terminals 2, 3, and 5 do not use looped wire un­der terminals. Break wire run to provide system supervision of connections.
Wire connections are made by simply stripping insulation from the end of the wire, sliding the bare end of the wire under the clamping plate, and tightening the clamping plate screw. Use the strip gauge molded into the base for ease of wiring to terminals.
System Sensor smoke detectors and mounting bases are marked with a com­patibility identifier located as the last digit of a five digit code stamped on the back of the product. Connect detectors/mounting bases only to compatible control units as indicated in System Sensor’s compatibility chart which con­tains a current list of UL listed control units and detector head/base combina­tions. A copy of this list is available from System Sensor upon request.
The zone wiring of the detector base should be checked before the detector heads are installed in them. To make this possible, this base contains a spe­cial spring-type shorting jumper. After a detector base is properly wired and mounted on an electrical box, make sure that the jumper spring is in contact with the base of Terminal 3. This temporary connection shorts the negative-in and negative-out leads and permits the wiring of the loop to be checked for continuity.
Once all the detector bases have been wired and mounted, and the loop wir­ing has been checked, the detector heads may be installed in the bases. The shorting spring in the base will disengage when the detector head is turned into place.
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
TAMPER-RESIST FEATURE
CAUTION
SNAP ON
Do not use the tamper resist feature if the XR5 removal tool is to be used.
This detector base also includes an optional tamper resist feature that, when activated, prevents removal of the detector without the use of a tool.
To activate this feature, break the tab from the detector base, as shown in Figure 3A, and install the detector. To remove the detector from the base once the tamper resist feature has been activated, insert a small-bladed screwdriver into the slot in the side of the base and press the plastic lever away from the detector head (see Figure 3B). This allows the detector to be rotated counter­clockwise and removed.
NOTE: Head removal after the tamper resist feature has been activated first requires removal of the decorative ring.
The tamper resist feature can be defeated by breaking and removing the plas­tic lever from the base. However, this permanently defeats the tamper resist feature.
FIGURE 1. MOUNTING DETECTOR TO BOX:
DECORATIVE
RING
SHORTING SPRING
SCREWS
(NOT SUPPLIED)
DETECTOR
(NOT SUPPLIED)
BASE
BOX
C0503-00
D450-02-00 2 I56-0352-007R