System Sensor B224BI-WH, B224BI-IV Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
CAUTION
LISTED COMPATIBLE CONTROL PANEL
1
2
MOUNTING
I56-3736-005
B224BI-WH, B224BI-IV
3825 Ohio Avenue, St. Charles, Illinois 60174
1.800.SENSOR2; Fax: 630.377.6495
Plug-in Isolator Detector Base
www.systemsensor.com
SPECIFICATIONS
Base Diameter: 6.85 in (17.4 cm) Base Height: 1.61 in (4.1 cm) Operating Temperature Range: Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com Operating Humidity Range: 10% to 93% Relative Humidity (Non-condensing)
Electrical Ratings
Operating Voltage: 15 to 32 VDC Standby Current: 450 µA Maximum Isolation Current: 15 mA Maximum
BEFORE INSTALLING
Please read the System Smoke Detector Applications Guide, which provides detailed information on detector spacing, placement, zoning, wiring, and spe­cial applications. This manual is available online at www.systemsensor.com. NFPA 72 guidelines should be observed.
4. Then, swing the base into position to engage the pins on the product with the terminals on the mounting plate.
5. Secure the base by tightening the mounting screws.
6. Install a compatible smoke detector as described in the installation manual for the detector.
IMPORTANT: The detectors used with these bases must be tested and main-
tained following NFPA 72 requirements. The detectors used with these bases should be cleaned at least once a year.
GENERAL INFORMATION
The B224BI-WH and B224BI-IV isolator bases intended for use in an intelli­gent system. Isolator bases prevent an entire communications loop from being disabled when a short circuit occurs. They accomplish this by isolating that part of the loop containing the short from the remainder of the circuit. These bases also automatically restore the entire loop when the cause of the short circuit is corrected. In general, up to 25 addressable devices may be isolated between isolator bases.
MOUNTING
Mount the mounting plate directly to an electrical box. The plate will mount directly to 4" square (with and without plaster ring), 4" octagon, 31/2" octagon, single gang and double gang junction boxes.
1. Connect field wiring to terminals, as shown in Figure 3 and 4.
2. Attach the mounting plate to the junction box as shown in Figure 2.
3. To mount the base, hook the tab on the base to the groove on the mounting plate.
Do not over tighten mounting plate screws; this may cause mounting plate to flex.
INSTALLATION GUIDELINES
All wiring must be installed in compliance with all applicable local codes and any special requirements of the local authority having jurisdiction, using the proper wire sizes. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.
For signal wiring (the wiring between interconnected detectors), it is recom­mended that the wire be no smaller than 18 AWG (0.823 mm2). However, wire sizes up to 12 AWG (3.31 mm2) can be used with the base.
Alarm system control panels have specifications for allowable loop resistance. Consult the control panel specifications for the total loop resistance allowed before wiring the detector loops.
Check the zone wiring of all bases in the system before installing detectors. This includes checking the wiring for continuity, correct polarity, ground fault testing, and performing a dielectric test.
FIGURE 1. TERMINAL DESIGNATION
3
FIGURE 2. MOUNTING BASE TO ELECTRICAL BOX
SCREWS
(NOT SUPPLIED)
FIGURE 3.
1 - COMM IN (+)
2 - COMM IN (–)
3 - COMM OUT (+)
2 - COMM OUT (–)
(+)
(+)
(–)
(–)
OTHER
INTELLIGENT
DEVICES
C0471-05
B224BI-WH/B224BI-IV TERMINALS
No. Function
1. Positive (+) Comm. Line In
2. Negative (–) Comm. Line In and Out
3. Positive (+) Comm. Line Out
1 I56-3736-005 02/01/2018
PLATE
BOX
(NOT SUPPLIED)
C1008-01
CLASS A OPTIONAL WIRING
C1003-01
GROUP 1
FIGURE 4. WIRING DIAGRAM
SLOT
GROUP 2
1 (+)
2 (–)
(–)
(+)
COMPATIBLE
CONTROL PANEL
2 (–)
1 (+)
2 (–) 3 (+)
2 (–)
3 (+)
(–)
(+)
GROUPS OF ADDRESSABLE DEVICES ARE
SEPERATED BY FAULT ISOLATOR BASES. ANY
COMBINATION OF COMPATIBLE LISTED DEVICES
MAY BE MIXED WITHIN A GROUP
(–)
(+)
A PAIR OF FAULT ISOLATOR BASES WILL DISCONNECT A GROUP OF DEVICES IF A
SHORT CIRCUIT OCCURS ON THE SIGNALING
LINE CIRCUIT WITHIN THAT GROUP.
(–)
(+)
(–)
GROUP 3
WIRING INSTRUCTIONS
Make wiring connections by stripping about 3/8" (10 mm) of insulation from the wire end. Then, insert the wire into the appropriate terminal and tighten the screw. Wire the communication line in (+) to terminal 1. Insert both communication line in (–) and communication line out (–) to terminal 2. Wire communication line out (+) to terminal 3 (see Figures 3 and 4).
A label is affixed to the base for recording the zone, address, and type of detector being installed at the base location. This information is useful for set­ting the detector head address and for verification of the sensor type required for that location.
Once all detector bases have been wired and mounted, and the loop wiring has been checked, the detector heads may be installed in the bases.
TAMPER-RESIST FEATURE
NOTE: Do not use the tamper-resist feature if the removal tool is to be used.
This detector base includes a tamper-resist feature that prevents its removal
COMMUNICATION LINE
from the base without the use of a tool.
To activate this feature, break the tab from the detector base as shown in Figure 5A. Then, install the detector.
To remove the detector from the base once the tamper-resist feature has been activated, insert a small-bladed screwdriver into the slot from the top and press down on the lever (see Figure 5B). This allows the detector to be rotated counterclockwise for removal.
The tamper-resist feature can be defeated by breaking and removing the plas­tic lever from the base. However, this prevents the feature from being used again.
1 (+)
2 (–)
(–)
(+)
(–)
(+)
(+)
ALL WIRING SHOWN IS SUPERVISED.
3 (+)
2 (–)
(–)
(–)
(+)
(–)
(+)
(+)
(–)
(+)
3 (+)
2 (–)
2 (–)
1 (+)
C1013-01
FIGURE 5A. ACTIVATING THE TAMPER-RESIST FEATURE
BREAK TAB AT DOTTED LINE BY TWISTING TOWARD CENTER OF BASE.
PLASTIC LEVER
C1065-00
FIGURE 5B. REMOVING THE DETECTOR HEAD FROM THE BASE
SLOT
C1082-00
NOTE: B224BI-WH and B224BI-IV replace the previous model number B224BI; all are functionally the same.
Please refer to insert for the Limitations of Fire Alarm Systems
System Sensor warrants its enclosed smoke detector base to be free from defects in ma­terials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector base. No agent, representative, dealer, or employee of the Company has the au­thority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of the smoke detector base which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: Honeywell, 12220 Rojas
System Sensor® is a registered trademark of Honeywell International, Inc.
2 I56-3736-005 ©2018 System Sensor. 02/01/2018
THREE-YEAR LIMITED WARRANTY
Drive, Suite 700, El Paso TX 79936, USA. Please include a note describing the malfunc­tion and suspected cause of failure. The Company shall not be obligated to replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.