INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-3736-001R
B224BI Plug-in Isolator
3825 Ohio Avenue, St. Charles, Illinois 60174
1.800.SENSOR2; Fax: 630.377.6495
Detector Base
www.systemsensor.com
SPECIFICATIONS
Base Diameter: 6.85 in (17.4 cm)
Base Height: 1.61 in (4.1 cm)
Operating Temperature Range: Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com
Operating Humidity Range: 10% to 93% Relative Humidity (Non-condensing)
Electrical Ratings
Operating Voltage: 15 to 32 VDC
Standby Current: 450µA Maximum
Isolation Current: 15mA Maximum
BEFORE INSTALLING
Please read the System Smoke Detector Applications Guide, which provides
FIGURE 2. MOUNTING BASE TO ELECTRICAL BOX:
detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this application guide are available from System
Sensor. NFPA 72 guidelines should be observed.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detectors used with these bases must be tested and maintained following NFPA 72 requirements. The detectors used with these bases
should be cleaned at least once a year.
SCREWS
(NOT SUPPLIED)
GENERAL INFORMATION
The isolator base is intended for use in an intelligent system. Isolator bases
prevent an entire communications loop from being disabled when a short circuit occurs. They accomplish this by isolating that part of the loop containing
the short from the remainder of the circuit. These bases also automatically
restore the entire loop when the cause of the short circuit is corrected. In
MOUNTING
PLATE
general, up to 25 addressable devices may be isolated between isolator bases.
B224BI TERMINALS
NO. FUNCTION
1. Positive (+) Comm. Line In
2. Negative (–) Comm. Line In and Out
3. Positive (+) Comm. Line Out
FIGURE 1: TERMINAL DESIGNATION:
2
3
INSTALLATION GUIDELINES
All wiring must be installed in compliance with all applicable local codes and
any special requirements of the local authority having jurisdiction, using the
proper wire sizes. The conductors used to connect smoke detectors to control
panels and accessory devices should be color-coded to reduce the likelihood
of wiring errors. Improper connections can prevent a system from responding
BOX
(NOT SUPPLIED)
C1008-01
properly in the event of a fire.
For signal wiring (the wiring between interconnected detectors), it is recommended that the wire be no smaller than 18 AWG (0.823 square mm). However, wire sizes up to 12 AWG (3.31 square mm) can be used with the base.
Alarm system control panels have specifications for allowable loop resistance.
Consult the control panel specifications for the total loop resistance allowed
before wiring the detector loops.
Check the zone wiring of all bases in the system before installing detectors.
This includes checking the wiring for continuity, correct polarity, ground fault
testing, and performing a dielectric test.
C0471-05
MOUNTING
Mount the mounting plate directly to an electrical box. The plate will mount
directly to 4-inch square (with and without plaster ring), 4-inch octagon,
3 1/2-inch octagon, single gang and double gang junction boxes.
1. Connect field wiring to terminals, as shown in Figure 3 and 4.
2. Attach the mounting plate to the junction box as shown in Figure 2.
FIGURE 3:
1 - COMM IN (+)
2 - COMM IN (–)
3 - COMM OUT (+)
2 - COMM OUT (–)
(+)
(+)
(–)
(–)
OTHER
INTELLIGENT
DEVICES
3. To mount the base, hook the tab on the base to the groove on the mounting plate.
4. Then, swing the base into position to engage the pins on the product with
the terminals on the mounting plate.
5. Secure the base by tightening the mounting screws.
6. Install a compatible smoke detector as described in the installation manual
for the detector.
LISTED COMPATIBLE CONTROL PANEL
CLASS A OPTIONAL WIRING
C1003-01
SS-450-002 1 I56-3736-001R
BREAK TAB AT DOTTED LINE BY
ALL WIRING SHOWN IS SUPERVISED.
FIGURE 4. WIRING DIAGRAM:
1 (+)
2 (–)
COMMUNICATION LINE
1 (+)
2 (–)
(–)
(+)
COMPATIBLE
CONTROL PANEL
2 (–)
1 (+)
2 (–)
3 (+)
2 (–)
3 (+)
SHORT CIRCUIT OCCURS ON THE SIGNALING
(–)
(+)
GROUPS OF ADDRESSABLE DEVICES ARE
SEPERATED BY FAULT ISOLATOR BASES. A NY
COMBINATION OF COMPATIBLE LISTED DEVICES
MAY BE MIXED WITHIN A GROUP
(–)
(+)
A PAIR OF FAULT ISOLATOR BASES WILL
DISCONNECT A GROUP OF DEVICES IF A
LINE CIRCUIT WITHIN THAT GROUP.
GROUP 3
WIRING INSTRUCTIONS
Make wiring connections by stripping about 3⁄8 of an inch (10 mm) of insulation from the wire end. Then, insert the wire into the appropriate terminal and
tighten the screw. Wire the communication line in (+) to terminal 1. Insert
both communication line in (–) and communication line out (–) to terminal 2.
Wire communication line out (+) to terminal 3 (see Figures 3 and 4).
A label is affixed to the base for recording the zone, address, and type of
detector being installed at the base location. This information is useful for setting the detector head address and for verification of the sensor type required
for that location.
Once all detector bases have been wired and mounted, and the loop wiring
has been checked, the detector heads may be installed in the bases.
TAMPER-RESIST FEATURE
NOTE: Do not use the tamper-resist feature if the removal tool is to be used.
This detector base includes a tamper-resist feature that prevents its removal
from the base without the use of a tool.
To activate this feature, break the tab from the detector base as shown in Figure 5A. Then, install the detector.
To remove the detector from the base once the tamper-resist feature has been
activated, insert a small-bladed screwdriver into the slot from the top and
press down on the lever (see Figure 5B). This allows the detector to be rotated
counterclockwise for removal.
The tamper-resist feature can be defeated by breaking and removing the plastic
lever from the base. However, this prevents the feature from being used again.
(–)
(–)
(+)
(+)
(–)
(+)
(–)
(+)
3 (+)
2 (–)
(–)
(–)
(+)
(–)
(+)
(+)
(–)
(+)
3 (+)
2 (–)
2 (–)
1 (+)
FIGURE 5A. ACTIVATING THE TAMPER-RESIST FEATURE:
TWISTING TOWARD CENTER OF BASE.
PLASTIC LEVER
FIGURE 5B. REMOVING THE DETECTOR HEAD FROM THE BASE:
SLOT
C1013-01
C1065-00
C1082-00
Please refer to insert for the Limitations of Fire Alarm Systems
System Sensor warrants its enclosed smoke detector base to be free from defects in materials and workmanship under normal use and service for a period of three years from
date of manufacture. System Sensor makes no other express warranty for this smoke
detector base. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s
obligation of this Warranty shall be limited to the replacement of any part of the smoke
detector base which is found to be defective in materials or workmanship under normal
use and service during the three year period commencing with the date of manufacture.
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: System Sensor, Returns
SS-450-002 2 I56-3736-001R
©2011 System Sensor
THREE-YEAR LIMITED WARRANTY
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include
a note describing the malfunction and suspected cause of failure. The Company shall
not be obligated to replace units which are found to be defective because of damage,
unreasonable use, modifications, or alterations occurring after the date of manufacture.
In no case shall the Company be liable for any consequential or incidental damages for
breach of this or any other Warranty, expressed or implied whatsoever, even if the loss
or damage is caused by the Company’s negligence or fault. Some states do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation
or exclusion may not apply to you. This Warranty gives you specific legal rights, and you
may also have other rights which vary from state to state.