INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-3387-006R
B200S
Intelligent Sounder Base
This model is compatible with Sytem Sensor Models MDL, MDL3R, MDLW, MDL3W and SYNC-1
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Specifications
Base Diameter: 6.875” (17.46 cm)
Base Height (less sensor): 2.0” (5.08 cm)
Weight: 0.50 lb. (227 gm)
Operating Temperature Range: Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com
Operating Humidity Range: 10% to 93% relative humidity (non-condensing)
External Supply Electrical Ratings
External Supply Voltage: 16 to 33 VDC (VFWR)
Standby Current: 500 μA maximum
Alarm Current: 35 mA maximum (at high volume setting); 15 mA maximum (at low volume setting)
SLC Electrical Ratings
SLC Operating Voltage: 15 to 32 VDC
SLC Standby Current: 300 μA maximum
Sound Output
High Volume: Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone)
Low Volume: Greater than 75 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone)
BEFORE INSTALLING
Please read the System Sensor Smoke Detector Application Guide, which provides detailed information on sensor spacing, placement, zoning, wiring, and
special applications. Copies of this manual are available from System Sensor.
NFPA 72 and NEMA guidelines should be observed.
NOTE: 200 Series sounder bases are not compatible with remote test capable
200 series detectors.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with this base must be tested and maintained
regularly following NFPA 72 requirements. The detector should be cleaned at
least once a year.
GENERAL DESCRIPTION
The B200S sounder base is used with System Sensor 200-Series sensor heads or
equivalent. For a list of compatible sensors, refer to the System Sensor website
at www.systemsensor.com. Refer to the appropriate manual for more information on sensors.
The B200S sounder base was designed specifically to meet the needs of dwelling unit applications. It offers maximum flexibility in configuration and operation to meet or exceed the requirements of UL268 and UL464.
The sounder base is capable of producing a variety of tone patterns, including
the distinctive three-pulse temporal pattern (ANSI Temporal 3) fire alarm signal now required by NFPA 72 for commercial and residential applications.
The B200S can be commanded by the Fire Alarm Control Panel to adopt the
address of the attached sensor head, but as a unique device type on the loop.
By using the address, the fire alarm control panel can command an individual
sounder base to activate, or a group of sounders in a suite or other multi-room
configuration. The command set from the panel can be tailored to the specific
event, allowing selection of volume, tone, and group. The device offers two
volume levels: 75 dBA and 85 dBA. The available tones are Continuous, ANSI
Temporal 3, ANSI Temporal 4, and March Time. In addition, some fire alarm
panels will offer the ability to command a custom tone pattern. Refer to the
appropriate fire alarm control panel manual for more information.
In addition, the B200S is equipped with the circuitry to recognize the System
Sensor synchronization protocol, enabling the sounder base to be used as a
component of the general evacuation signal – producing an NFPA 72 compliant
Temporal 3 pattern in synchronization with other System Sensor notification
devices. This requires connection to a power supply capable of generating
the System Sensor synchronization pulses, a FACP NAC output configured
to System Sensor synchronization protocol, or a separate synchronization
module.
The sounder base is intended for use with intelligent systems. In addition to
being connected to the SLC, the sounder base requires a connection to either
24 VDC constant power or a NAC circuit, depending on the FACP and intended
use. The connections for 24V constant/NAC power and the communication
loop are isolated to prevent electrical interaction between them.
When connected to a NAC, power is supervised via the NAC circuit supervision while in standby mode (EOL resistor required for Class B operation).
when activated, the B200S provides supervision of NAC power (see Figure 5).
When using a FACP equipped with a “sounder base standby power monitoring” mode (see table) and constant 24 V power, power supervision EOL
devices (supervision relays and resistors) should not be used (see Figure 4).
In this case, the B200S will provide supervision in both standby and alarm/
active mode. If your FACP is not listed in the table or you choose not to use
“sounder base standby power monitoring” mode, power supervision relays
and EOL resistors are required to provide supervision in standby mode.
NOTE: If the FACP’s “sounder base standby power monitoring” mode is
enabled, connecting B200S sounder bases to the NAC will result in power
supervision failure when in standby. Only connect B200S sounder bases to
constant 24 V power in this case. Refer to the panel manual for maximum allowable number of units per loop.
NOTE: For NFPA72 Installations, the Temporal 3 tone at high volume should
be used for public mode evacuation. The use of other tone styles and low
volume level will be at the discretion of the local Authority Having Jurisdiction (AHJ).
NOTE: When not used as a supplementary evacuation system, the external 24
VDC supply shall be treated as a component of the main power supply system
and shall fall under the requirements of the main power supply system per
NFPA 72.
FACPS EQUIPPED WITH “SOUNDERBASE STANDBY POWER MONITORING” MODE
Manufacturer FACP Model Firmware Revision
Notifier NFS-320 Rev. 20 or Higher
Notifer NFS2-640 Rev. 20 or Higher
Notifier NFS2-3030 Rev. 20 or Higher
Gamewell-FCI E3 Series Rev. 2.4 or Higher
Gamewell-FCI S3 Series All Revisions
Honeywell XLS120 Rev. 21 or Higher
Honeywell XLS140-2 Rev. 21 or Higher
Honeywell XLS3000 Rev. 21 or Higher
Silent Knight 5820XL, 5820XL-EVS Rev. 13 or Higher
Silent Knight 5808 Rev. 13 or Higher
Silent Knight 5700 Rev. 13 or Higher
SS-450-000 1 I56-3387-006R
Silent Knight IFP-2000, IFP-2000ECS Rev. 4 or Higher
Silent Knight IFP-1000, IFP-1000ECS Rev. 13 or Higher
Silent Knight IFP-100, IFP-100ECS Rev. 13 or Higher
Silent Knight IFP-50 Rev. 13 or Higher
Johnson Controls IFS-320 Rev. 21 or Higher
Johnson Controls IFC2-640 Rev. 21 or Higher
Johnson Controls IFC2-3030 Rev. 21 or Higher
WIRING GUIDELINES
All wiring must be installed in compliance with the National Electrical Code
and the local codes having jurisdiction and must not be of such length or wire
size which would cause the base to operate outside of its published specifications. The conductors used to connect smoke sensors to control panels and
accessory devices should be color coded to reduce the likelihood of wiring
errors. Improper connections can prevent a system from responding properly
in the event of a fire.
Wire sizes up to 12 AWG (2.5 mm2) may be used with the base. The sounder
base will be shipped with the screw terminals set for 14 AWG wiring. If 12
AWG wire is to be used, back out the screws to allow the wire to fit beneath
the clamping plates.For best system performance, the power (+ and -) wires
and the communication circuit wires should be twisted pair or shielded cable
installed in a separate grounded conduit to protect the communication loop
from electrical interference.
Make wire connections by stripping about 3/8” of insulation from the end of
the wire. Then, slide the bare end of the wire under the appropriate clamping
plate (See Figure 1), and tighten the clamping plate screw. Do NOT loop the
wire under the clamping plate (See Figure 2) The wiring diagram for a typical
2-wire intelligent system is shown in Figure 4.
FIGURE 1:
2
5
6
mount directly to 4˝ square (with and without plaster ring), 4˝ octagon, 3 1/2˝
octagon, single gang or double gang junction boxes.
1. Connect field wiring to terminals, as shown in Figure 1 and 2.
2. Attach the mounting plate to the junction box as shown in Figure 3.
3. To mount the sounder base, hook the tab on the sounder base to the groove
on the mounting plate.
4. Then, swing the sounder base into position to engage the pins on the
product with the terminals on the mounting plate.
5. Secure the sounder base by tightening the mounting screws.
6. Install a compatible smoke sensor as described in the installation manual
for the sensor.
TAMPER RESISTANT FEATURE
NOTE: Do not use the tamper-resist feature if the removal tool is to be used.
This detector base includes a tamper-resist feature that prevents its removal
from the base without the use of a tool. To activate this feature, break the tab
from the detector base as shown in Figure 7A. Then, install the detector. To
remove the detector from the base once the tamper-resist feature has been
activated, insert a small-bladed screwdriver into the slot from the top and
press down on the lever (see Figure 7B). This allows the detector to be rotated
counterclockwise for removal. The tamper-resist feature can be defeated by
breaking and removing the plastic lever from the base. However, this prevents
the feature from being used again.
TESTING AND MAINTENANCE
Sensors and bases must be tested after installation and as an integral part of a
periodic maintenance program. Test the B200S as follows:
NOTE: Before testing, notify the proper authorities that the smoke sensor
system is undergoing maintenance and, therefore, will be temporarily out of
service. Disable the system undergoing maintenance to prevent unwanted
alarms.
1. Via the fire alarm control panel, command the individual B200S to activate
using the associated sensor address. That sounder base should sound in
approximately five seconds.
2. Via the fire alarm control panel, command all B200S sounder bases to activate using group communication to all associated addresses. All devices on
the loop should sound, and if a temporal tone is commanded, the tones can
be synchronized to each other.
NOTE: Synchronization requires a power supply capable of producing the System Sensor synchronization pulses or a synchronization module.
When performing maintenance on connected smoke sensors, carefully note
the location and address of each removed sensor. When re-installed, the
B200S will confirm that address of the sensor matches the address stored in
C0471-07
the sounder base memory. If there is a mismatch, this will be communicated
to the fire alarm control panel and the sounder base can be commanded to
chirp at regular intervals until the correct head is installed.
FIGURE 2:
If a replacement head is installed or address changes are required, the mismatch may be resolved at the panel by commanding the B200S sounder base to
re-enter its address learning mode and adopting the address of the new sensor.
C0473-00
FIGURE 3: MOUNTING
CAUTION
For system monitoring - for terminals 2, 3, 4, and 5, do not use looped wire
under terminals. Break wire run as shown in Figure 2 to provide monitoring
of connections.
B200S TERMINALS
No. Function
1. Not Used
2. Positive (+) Comm. Line In and Out
3. Negative (-) Comm. Line In and Out
4. External Supply Positive (+)
5. External Supply Negative (-)
6. Remote Annunciator
MOUNTING
Mount the B200S mounting plate directly to an electrical box. The plate will
SS-450-000 2 I56-3387-006R
C0891-07