System Sensor B200S User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-3387-006R
B200S Intelligent Sounder Base
This model is compatible with Sytem Sensor Models MDL, MDL3R, MDLW, MDL3W and SYNC-1
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Specifications
Base Diameter: 6.875” (17.46 cm) Base Height (less sensor): 2.0” (5.08 cm) Weight: 0.50 lb. (227 gm) Operating Temperature Range: Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com Operating Humidity Range: 10% to 93% relative humidity (non-condensing)
External Supply Electrical Ratings
External Supply Voltage: 16 to 33 VDC (VFWR) Standby Current: 500 μA maximum Alarm Current: 35 mA maximum (at high volume setting); 15 mA maximum (at low volume setting)
SLC Electrical Ratings
SLC Operating Voltage: 15 to 32 VDC SLC Standby Current: 300 μA maximum Sound Output High Volume: Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone) Low Volume: Greater than 75 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone)
BEFORE INSTALLING
NOTE: 200 Series sounder bases are not compatible with remote test capable 200 series detectors.
NOTICE: This manual should be left with the owner/user of this equipment. IMPORTANT: The detector used with this base must be tested and maintained
regularly following NFPA 72 requirements. The detector should be cleaned at least once a year.
GENERAL DESCRIPTION
The B200S sounder base is used with System Sensor 200-Series sensor heads or equivalent. For a list of compatible sensors, refer to the System Sensor website at www.systemsensor.com. Refer to the appropriate manual for more informa­tion on sensors.
The sounder base is capable of producing a variety of tone patterns, including the distinctive three-pulse temporal pattern (ANSI Temporal 3) fire alarm sig­nal now required by NFPA 72 for commercial and residential applications.
The B200S can be commanded by the Fire Alarm Control Panel to adopt the address of the attached sensor head, but as a unique device type on the loop. By using the address, the fire alarm control panel can command an individual sounder base to activate, or a group of sounders in a suite or other multi-room configuration. The command set from the panel can be tailored to the specific event, allowing selection of volume, tone, and group. The device offers two volume levels: 75 dBA and 85 dBA. The available tones are Continuous, ANSI Temporal 3, ANSI Temporal 4, and March Time. In addition, some fire alarm panels will offer the ability to command a custom tone pattern. Refer to the appropriate fire alarm control panel manual for more information.
In addition, the B200S is equipped with the circuitry to recognize the System Sensor synchronization protocol, enabling the sounder base to be used as a component of the general evacuation signal – producing an NFPA 72 compliant Temporal 3 pattern in synchronization with other System Sensor notification devices. This requires connection to a power supply capable of generating the System Sensor synchronization pulses, a FACP NAC output configured to System Sensor synchronization protocol, or a separate synchronization module.
The sounder base is intended for use with intelligent systems. In addition to being connected to the SLC, the sounder base requires a connection to either 24 VDC constant power or a NAC circuit, depending on the FACP and intended
use. The connections for 24V constant/NAC power and the communication loop are isolated to prevent electrical interaction between them.
NOTE: If the FACP’s “sounder base standby power monitoring” mode is enabled, connecting B200S sounder bases to the NAC will result in power supervision failure when in standby. Only connect B200S sounder bases to constant 24 V power in this case. Refer to the panel manual for maximum al­lowable number of units per loop.
NOTE: For NFPA72 Installations, the Temporal 3 tone at high volume should be used for public mode evacuation. The use of other tone styles and low volume level will be at the discretion of the local Authority Having Jurisdic­tion (AHJ). NOTE: When not used as a supplementary evacuation system, the external 24 VDC supply shall be treated as a component of the main power supply system and shall fall under the requirements of the main power supply system per NFPA 72.
FACPS EQUIPPED WITH “SOUNDERBASE STANDBY POWER MONI­TORING” MODE
Manufacturer FACP Model Firmware Revision
Notifier NFS-320 Rev. 20 or Higher
Notifer NFS2-640 Rev. 20 or Higher
Notifier NFS2-3030 Rev. 20 or Higher
Gamewell-FCI E3 Series Rev. 2.4 or Higher
Gamewell-FCI S3 Series All Revisions
Honeywell XLS120 Rev. 21 or Higher
Honeywell XLS140-2 Rev. 21 or Higher
Honeywell XLS3000 Rev. 21 or Higher
Silent Knight 5820XL, 5820XL-EVS Rev. 13 or Higher
Silent Knight 5808 Rev. 13 or Higher
Silent Knight 5700 Rev. 13 or Higher
SS-450-000 1 I56-3387-006R
Silent Knight IFP-2000, IFP-2000ECS Rev. 4 or Higher
1
3
4
Silent Knight IFP-1000, IFP-1000ECS Rev. 13 or Higher
Silent Knight IFP-100, IFP-100ECS Rev. 13 or Higher
Silent Knight IFP-50 Rev. 13 or Higher
Johnson Controls IFS-320 Rev. 21 or Higher
Johnson Controls IFC2-640 Rev. 21 or Higher
Johnson Controls IFC2-3030 Rev. 21 or Higher
WIRING GUIDELINES
All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction and must not be of such length or wire size which would cause the base to operate outside of its published specifica­tions. The conductors used to connect smoke sensors to control panels and accessory devices should be color coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.
Wire sizes up to 12 AWG (2.5 mm2) may be used with the base. The sounder base will be shipped with the screw terminals set for 14 AWG wiring. If 12 AWG wire is to be used, back out the screws to allow the wire to fit beneath the clamping plates.For best system performance, the power (+ and -) wires and the communication circuit wires should be twisted pair or shielded cable installed in a separate grounded conduit to protect the communication loop from electrical interference.
Make wire connections by stripping about 3/8” of insulation from the end of the wire. Then, slide the bare end of the wire under the appropriate clamping plate (See Figure 1), and tighten the clamping plate screw. Do NOT loop the wire under the clamping plate (See Figure 2) The wiring diagram for a typical 2-wire intelligent system is shown in Figure 4.
FIGURE 1:
2
5
6
mount directly to 4˝ square (with and without plaster ring), 4˝ octagon, 3 1/2˝ octagon, single gang or double gang junction boxes.
1. Connect field wiring to terminals, as shown in Figure 1 and 2.
2. Attach the mounting plate to the junction box as shown in Figure 3.
3. To mount the sounder base, hook the tab on the sounder base to the groove on the mounting plate.
4. Then, swing the sounder base into position to engage the pins on the product with the terminals on the mounting plate.
5. Secure the sounder base by tightening the mounting screws.
6. Install a compatible smoke sensor as described in the installation manual for the sensor.
TAMPER RESISTANT FEATURE
NOTE: Do not use the tamper-resist feature if the removal tool is to be used. This detector base includes a tamper-resist feature that prevents its removal from the base without the use of a tool. To activate this feature, break the tab from the detector base as shown in Figure 7A. Then, install the detector. To remove the detector from the base once the tamper-resist feature has been activated, insert a small-bladed screwdriver into the slot from the top and press down on the lever (see Figure 7B). This allows the detector to be rotated counterclockwise for removal. The tamper-resist feature can be defeated by breaking and removing the plastic lever from the base. However, this prevents the feature from being used again.
TESTING AND MAINTENANCE
Sensors and bases must be tested after installation and as an integral part of a periodic maintenance program. Test the B200S as follows:
NOTE: Before testing, notify the proper authorities that the smoke sensor system is undergoing maintenance and, therefore, will be temporarily out of service. Disable the system undergoing maintenance to prevent unwanted alarms.
1. Via the fire alarm control panel, command the individual B200S to activate using the associated sensor address. That sounder base should sound in approximately five seconds.
When performing maintenance on connected smoke sensors, carefully note the location and address of each removed sensor. When re-installed, the B200S will confirm that address of the sensor matches the address stored in
C0471-07
the sounder base memory. If there is a mismatch, this will be communicated to the fire alarm control panel and the sounder base can be commanded to chirp at regular intervals until the correct head is installed.
FIGURE 2:
C0473-00
FIGURE 3: MOUNTING
CAUTION
For system monitoring - for terminals 2, 3, 4, and 5, do not use looped wire under terminals. Break wire run as shown in Figure 2 to provide monitoring of connections.
B200S TERMINALS
No. Function
1. Not Used
2. Positive (+) Comm. Line In and Out
3. Negative (-) Comm. Line In and Out
4. External Supply Positive (+)
5. External Supply Negative (-)
6. Remote Annunciator
MOUNTING
Mount the B200S mounting plate directly to an electrical box. The plate will
SS-450-000 2 I56-3387-006R
C0891-07
FIGURE 4: WIRING DIAGRAM
THE SYNCHRONIZATION PULSES (SEE FIGURE 6)
USED TO PROVIDE THE SYNCHRONIZATION PULSES
(CONNECTED TO 24V POWER USING COMPATIBLE FACP WITH “SOUNDER BASE STANDBY POWER MONITORING” ENABLED)
NOTE: Only use this wiring diagram when connecting to 24VDC power using a FACP listed in the table on page 1. Please consult your FACP manufacturer for panel-specific wiring configurations and special cases.
Additional Audible Visible devices may be connected to the same power supply or the the NAC output of the Fire Alarm Control Panel (FACP) to provide a syn­chronized communication of the alarm signal.
CLASS A OPTIONAL WIRING
OPTIONAL REMOTE
ANNUNCIATOR MODEL
(–) SLC
(+) SLC
RA400Z/100Z
EXT +
RA
SLC –
EXT –
C0474-12
(+) CONSTANT POWER
CONTROL PANEL
(–) CONSTANT POWER
U.L. LISTED COMPATIBLE
(+) NAC
(–) NAC
USED
NOT
FIRST SOUNDER BASE
SLC +
EXT +
SLC –
(+) (+)
(–)
HORN HORNHORN/STROBE
EXT +
RA
EXT –
SLC +
USED
NOT
SECOND SOUNDER BASE
SLC –
RA
EXT –
SLC +
USED
NOT
NTH SOUNDER BASE
/ /
(+)
E O L
(–)
(–)
A SEPERATE SYNCHRONIZATION MODULE MAY BE USED TO PROVIDE
FIGURE 5: WIRING DIAGRAM (CONNECTED TO NAC OR 24V POWER; OPTIONAL EOL DEVICES FOR CONSTANT SUPERVISION)
NOTE: Only use this wiring diagram when connecting to a NAC or a 24V power supply that does not support “sounder base standby power monitoring” (see page 1).
CLASS A OPTIONAL WIRING
OPTIONAL REMOTE
ANNUNCIATOR MODEL
(–) SLC
(+) SLC
CONTROL PANEL
U.L. LISTED COMPATIBLE
RA400Z/100Z
SLC +
USED
NOT
FIRST SOUNDER BASE
(+) NAC OR CONSTANT POWER*
(–) NAC OR CONSTANT POWER*
EXT +
SLC –
RA
EXT –
SLC +
USED
NOT
SECOND SOUNDER BASE
EXT +
SLC –
RA
EXT –
SLC +
USED
NOT
NTH SOUNDER BASE
/ /
EXT +
RA
SLC –
EXT –
E O L
/
(+) NAC
UL LISTED 24V
POWER SUPPLY
(–) NAC
(+) (+)
(–)
(–)
HORN HORNHORN/STROBE
A SEPERATE SYNCHRONIZATION MODULE MAY BE
(+)
E
*WHEN USING 24V CONSTANT POWER
O L
(–)
(AUX POWER), ADDITIONAL POWER SUPERVISION RELAYS AND MODULES WILL BE REQUIRED FOR PROVIDING SUPERVISION WHEN THE SOUNDER BASES ARE INACTIVE.
(SEE FIGURE 6)
SS-450-000 3 I56-3387-006R
/
C0474-11
BREAK TAB AT
USE SMALL-BLADED
SLOT
FIGURE 6: SYNCHRONIZATION DIAGRAM (FOR MDL SERIES SYNC MODULES ONLY)
FACP #1
TEMP JUMP OFF
+
B+
NAC 1
}
B–
B+
NAC 2
}
B–
B+
NAC 3
}
B–
NOTE: Wiring shown for System Sensor MDL Series Sync Module. For additional wiring configurations, see your sync module manual.
FIGURE 7A:
PLASTIC LEVER
EOL (1)
+
+
+
}
+
}
+
}
+
}
HORN CONTROL
ZONE 1 IN
MASTER
ZONE 2 IN
SLAVE IN
ZONE 1
OUT
ZONE 2
OUT
NAC
SLAVE IN
SLAVE
OUT
DOTTED LINE BY TWISTING TOWARD CENTER OF BASE.
} } } }
+
+
+
+
SOUNDER
BASE
SOUNDER
BASE
TO NEXT DEVICE OR EOL (1)
OPTIONAL
2 STYLE Y ZONES
(CLASS B)
TO NEXT DEVICE OR EOL (1)
SCREWDRIVER TO PUSH PLASTIC LEVER IN DIRECTION OF ARROW.
C1090-00
C0144-00
FIGURE 7B:
C1082-00
Please refer to insert for the Limitations of Fire Alarm Systems
THREE-YEAR LIMITED WARRANTY
System Sensor warrants its enclosed smoke detector base to be free from defects in mate­rials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector base. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector base which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns
SS-450-000 4 I56-3387-006R ©2013 System Sensor
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Loading...