System Sensor B116LP User Manual

D150-01-00 1 I56-599-03R
B116LP Plug-in Detector Base
For use with the following smoke detectors: In US: 1151, 2151 In Canada: 1151A, 2151A In Europe: 1151E, 2151E
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue,
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
Please thoroughly read the System Sensor manual I56-407, Guide for Proper Use of System Smoke Detectors, which pro­vides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor. (For installation in Canada, please refer to CAN4-S524, Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32.)
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with this base must be
Specifications
Base Diameter: 6.2 inches (157 mm) Base Height: 0.95 inches (24 mm) Weight: 0.3 lb. (130 g) Mounting: 4-inch square box with or without plaster ring. Min. Depth–1.5 inches
4-inch octagon box. Min. Depth–1.5 inches 3-1/2 inch-octagon box. Min. Depth–1.5 inches 50 mm box 60 mm box 70 mm box
Operating Temperature Range: 0° to +49°C (32° to 120°F) US and Canadian Installations
10°to 60°C (14° to 140°F) European Installations
Operating Humidity Range: 10% to 93% Relative Humidity
Electrical Ratings – includes base and detector
System Voltage: 24 VDC Maximum Ripple Voltage: 4 Volts peak to peak Start-up Capacitance: 0.02µF Maximum Standby Ratings: 15 VDC Minimum
35 VDC Maximum 120 µA Maximum
Alarm Ratings: 8 V Minimum at 16 mA
12 V Maximum at 100 mA
(Alarm current MUST be limited to 100 mA maximum by the control panel.) Relay Contact Ratings: Resistive or Inductive (60% power factor) Load Form C:* 2.0A @ 30 VAC/DC
0.6A @ 110 VDC
1.0A @ 125 VAC Reset Voltage: 1.4 VDC Minimum Reset Time: 0.3 Seconds Maximum Start-up Time: 34.0 Seconds Maximum *For Canadian installations relay contact ratings are 2.0A @ 30 VAC/DC.
tested and maintained regularly following NFPA 72 require­ments. The detector used with this base should be cleaned at least once a year.
General Description
The model B116LP plug-in detector base is used with System Sensor model 1151, 1151A, and 1151E ionization detector heads and model 2151, 2151A, and 2151E photo­electronic detector heads. The capability of plugging these detectors into a variety of special bases makes them more versatile than equivalent direct-wired models. Refer to the System Sensor catalog for other available plug-in detector bases.
D150-01-00 2 I56-599-03R
The B116LP base is intended for use in 2-wire systems, with screw terminals provided for power and relay contact connections. These bases MUST be current limited by the system control panel in the alarm state.
Mounting
This detector base mounts directly to 3-1/2-inch and 4­inch octagon boxes, and 4-inch square boxes (with or with­out plaster rings). To mount, remove decorative ring by turning it in either direction to unhook the snaps, then sep­arate the ring from the base. Install the base to the box using the screws supplied with the junction box and the appropriate mounting slots in the base. Place decorative ring onto base, then turn in either direction until the ring snaps in place (see Figure 1).
Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code and the local codes having jurISdiction. Proper wire gauges should be used. The con­ductors used to connect smoke detectors to control panels and accessory devices should be color-coded to prevent wiring mistakes. Improper connections can prevent a sys­tem from responding properly in the event of a fire.
For signal wiring (the wiring between inter-connected detectors), it is recommended that the wire be no smaller than 18 gauge. Wire sizes up to 12 gauge may be used with the base. For best system performance, the power (+) and (–) loop wires should be twisted pair and installed in sep­arate grounded conduit to protect the loop from extraneous electrical interference.
Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel manufacturer’s specifications for the total loop resistance allowed for the particular model control panel being used before wiring the detector loops.
Locate installations where normal ambient temperatures do not exceed 100°F.
Wiring Instructions
For system supervision — For terminals 2, 3, and 5 do not use looped wire under terminals. Break wire run to provide system supervision of connections.
Wire connections are made by simply stripping insulation from the end of the wire, sliding the bare end of the wire under the clamping plate, and tightening the clamping plate screw. Use the strip gauges molded into the inside
CAUTION
and underside of the base for ease of wiring to terminals 1 through 5, and to terminals 12 through 14, respectively.
System Sensor smoke detectors and mounting bases are marked with a compatibility identifier located as the last digit of a five digit code stamped on the back of the prod­uct. Connect detectors/mounting bases only to compatible control units as indicated in System Sensor’s compatibility chart which contains a current list of UL listed control units and detector head/base combinations. A copy of this list is available from System Sensor upon request.
The zone wiring of the detector base should be checked before the detector heads are installed in them. To make this possible, this base contains a special spring-type short­ing jumper. After a detector base is properly wired and mounted on an electrical box, make sure that the jumper spring is in contact with the base of Terminal 3. This tem­porary connection shorts the positive-in and positive-out leads and permits the wiring of the loop to be checked for continuity.
Figure 1. Mounting base to box:
A78-1175-01
SHORTING SPRING
SNAP ON DECORATIVE RING
SCREWS (NOT SUPPLIED)
DETECTOR BASE
BOX (NOT SUPPLIED)