INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-2169-001R
B114LPBT Plug-in Detector Base
For use with the following smoke detectors: US - 1151, 2151, 2151T;
CANADA - 1151A, 2151A, 2151TA; EUROPE - 1151E, 2151E
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
SPECIFICATIONS
Base Diameter: 6.2 in (15.7 cm)
Base Height: 1.1 in (2.9cm)
Weight: 0.6 lb (260 g)
Mounting: 4˝ square box without plaster ring, minimum depth 1.5˝; 4˝ octagon box, minimum depth 1.5˝;
31⁄2˝ octagon box, minimum depth 1.5˝
Operating Temperature Range: 0°C to 49°C (32°F to 120°F)
Operating Humidity Range: 10% to 93% Relative Humidity
Electrical Ratings (includes base and detector)
System Voltage: 24 VAC/DC, 60 Hz
Relay Contact Ratings Resistive Load: Form A — 2.0A @ 30VAC/DC; Form C — 2.0A @ 30VAC/DC, 1.0A @ 125VAC
(If used, the RA400 Remote Annunciator and RTC operates within the specified detector system voltage)
Standby Current: 25 mA typical @ 24V AC/DC; 35 mA maximum @ 35V AC/DC
Alarm Current: 75 mA typical @ 24V AC/DC; 94 mA maximum @ 35V AC/DC
Start-up Time (after 60 second reset): 36.0 Seconds maximum
BEFORE INSTALLING
Please thoroughly read System Sensor’s manual I56-407, Guide for Proper Use
of System Smoke Detectors. This manual provides detailed information on de-
tector spacing, placement, zoning, wiring, and special applications, and is
available at no charge from System Sensor.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with this base must be tested and maintained
regularly following NFPA 72 requirements. The detector used with this base
should be cleaned at least once a year.
GENERAL DESCRIPTION
The B114LPBT detector base is designed for use with System Sensor model
2151 photoelectronic and 1151 ionization detector heads. The capability of
plugging these detectors into a variety of special bases makes them more ver-
two- or three-conductor wire be no smaller than 18 gauge (1.0 square mm).
For best performance, alarm loop conductors should be installed in separate
grounded conduit or shielded cable to protect the alarm loop from extraneous
electrical interference.
Smoke detectors and alarm systems control panels have specifications for allowable loop resistance. Consult the control panel manufacturer’s specifications for the total loop resistance allowed for the particular model control
panel being used before wiring the detector loops.
FIGURE 1. BASE TERMINALS:
24VDC/24VAC
TERMINALS
BASE
6
7
TERMINALS
satile than equivalent direct-wired models. Refer to the System Sensor catalog
for other available plug-in bases. The B114LPBT base is intended for use in
4-wire systems with terminals provided for remote annunciator and relay connections.
MOUNTING
The detector base mounts directly to 31/2- and 4-inch octagon boxes and 4-inch
square boxes. To mount the base, remove the decorative ring by rotating it in
either direction to unhook the snaps before separating the ring from the base.
STRIP GAUGE
8
9
10
11
2
3
1
4
5
12
13
14
SHORTING
SPRING
TAMPER
RESISTANT TAB
Use the screws supplied with the junction box to attach the base to the box
through the appropriate mounting slots in the base.
Position the decorative ring around the base and rotate it in either direction
until the ring snaps into place (see Figure 2).
BASE TERMINALS
NO. FUNCTION NO. FUNCTION
1 Remote Annunciator (+) 8 N.O. Alarm Relay
2 Test Coil (+) 9 N.O. Form A
3 Not Used 10 C. Initiation
4 Remote Annunciator (–) 11 C. Contacts
5 RTC (–) 12 N.O. Alarm Relay
6 C. Supervisory Relay 13 N.C. Form C
7 N.O. Form A Contacts 14 C. Auxiliary Contacts
FIGURE 2. MOUNTING BASE TO BOX:
SHORTING
SPRING
DECORATIVE
RING
SCREWS
(NOT SUPPLIED)
DETECT
BASE
C1025-00
INSTALLATION GUIDELINES
All wiring must be installed in compliance with the National Electrical Code,
all applicable local codes, and any special requirements of the authority having jurisdiction, using the proper wire size. The conductors used to connect
smoke detectors to control panels and accessory devices should be color-coded
to reduce the likelihood of wiring errors. Improper connections can prevent a
BOX
(NOT SUPPLIED)
system from responding properly in the event of a fire.
For signal wiring (the wiring between interconnected detectors), it is recommended that the wire be no smaller than 16 gauge (1.5 square mm), and that
C0503-00
D150-07-00 1 I56-2169-001R
FIGURE 3. TYPICAL WIRING DIAGRAM FOR 24VAC RMS/DC DETECTOR SYSTEMS:
PLASTIC LEVER
BREAK TAB AT DOTTED LINE BY
TWISTING TOWARD CENTER OF BASE
USE SMALL-BLADED SCREWDRIVER TO PUSH
PLASTIC LEVER IN DIRECTION OF ARROW
USE SMALL-BLADED SCREWDRIVER TO PUSH
PLASTIC LEVER IN DIRECTION OF ARROW
W
APA451
N
–
W
N
–
APA451
24VDC/24VAC
TERMINALS
CONTROL
PANEL
CONTROL
PANEL
RELEASING
14
13
12
DEVICE
24VDC/24VAC
TERMINALS
2
6
SUPERVISORY
3
2
6
7
ALARM INITIATION LOOP
NOTE: ABOVE DIAGRAM SHOWS NFPA REQUIRED WIRING OF SUPERVISED SYSTEMS.
SCHEMATIC SHOWN BELOW FOR REFERENCE.
4
5
1
11
10
9
8
SUPERVISORY
RELAY
67
ALARM
RELAY
10, 11
8, 9
ALARM
RELAY
3
1
7
8
RELAY
67
10, 11
8, 9
RELEASING
4
DEVICE
EOL
14
5
13
12
11
10
9
SPECIFIED BY PANEL
MANUFACTURER
EOL
C0668-00
WIRING INSTRUCTIONS
NOTE: Refer to the manufacturer’s instructions for releasing device wiring.
NOTE: To ensure that electrical connections are supervised, do NOT loop
wires under terminals 8, 9, 10, and 11. Cut the wire at each terminal.
To make electrical connections, strip approximately 3/8 inch (1 cm) insulation
from the end of each wire, slide the bare wire end under the clamping plate,
and tighten the clamping plate screw. Use the strip gauges molded into the
inside and underside of the base for ease of wiring to terminals 1 and 4, and
to terminals 6 through 14, respectively.
The zone wiring of the detector base should be checked before installing the
smoke detector heads. The base contains a built-in shorting spring to make
To make the base tamper resistant, simply break off the tab on the base (see
Figure 4A), before installing the detector.
To remove the detector from the base after it has been made tamper resistant,
insert a small screwdriver (see Figure 4B) into the small hole and press the
plastic lever away from the detector. Rotate the detector counterclockwise and
remove.
NOTE: Head removal after activating the tamper-resistance feature first requires removal of the decorative ring.
FIGURE 4A. ACTIVATING TAMPER-RESISTANCE FEATURE
this possible. After the detector base is wired and mounted to an electrical
box, position the shorting spring against terminal 3. This temporary connection energizes the supervisory relay and permits the wiring of the loop to be
checked for continuity.
After all detector bases have been mounted, wired, and the wiring checked,
install the detector heads. The shorting spring in the base automatically disengages when the detector head is removed from the base. DO NOT remove the
FIGURE 4B. REMOVING DETECTOR HEAD FROM BASE
C0130-00
shorting spring since it reengages as the detector head is turned into the base,
completing the circuit
TAMPER-RESISTANCE FEATURE
This detector base also includes an optional tamper-resistant feature that
when activated prevents removal of the detector without the use of a tool.
System Sensor warrants its enclosed smoke detector base to be free from defects in materials and workmanship under normal use and service for a period of three years from date
of manufacture. System Sensor makes no other express warranty for this smoke detector
base. No agent, representative, dealer, or employee of the Company has the authority to
increase or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of the smoke
detector base which is found to be defective in materials or workmanship under normal
use and service during the three year period commencing with the date of manufacture.
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: System Sensor, Repair
THREE-YEAR LIMITED WARRANTY
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a
note describing the malfunction and suspected cause of failure. The Company shall not
be obligated to repair or replace units which are found to be defective because of damage,
unreasonable use, modifications, or alterations occurring after the date of manufacture.
In no case shall the Company be liable for any consequential or incidental damages for
breach of this or any other Warranty, expressed or implied whatsoever, even if the loss
or damage is caused by the Company’s negligence or fault. Some states do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation
or exclusion may not apply to you. This Warranty gives you specific legal rights, and you
may also have other rights which vary from state to state.
C0130-00