INSTALLATION AND MAINTENANCE INSTRUCTIONS
BASE
TERMINALS
SHORTING
SPRING
STRIP GAUGE
1
2
3
5
4
TAMPER
RESISTANT TAB
6
7
8
9
10
11
12
13
14
24VDC/24VAC
TERMINALS
SNAP ON
DECORATIVE
RING
SCREWS
(NOT SUPPLIED)
DETECTOR
BASE
BOX
(NOT SUPPLIED)
SHORTING
SPRING
I56-0598-004R
B114LP Plug-in Detector Base
For use with the following smoke detectors: US - 1151, 2151, 2151T;
CANADA - 1151A, 2151A, 2151TA; EUROPE - 1151E, 2151E
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
SPECIFICATIONS
Base Diameter: 6.2 in (157 mm)
Base Height: 0.95 in (24 mm)
Weight: 0.6 lb (274 g)
Mounting: 4˝ square box with or without plaster ring, minimum depth 1.5˝; 4˝ octagon box, minimum depth 1.5˝;
3
1
⁄2˝ octagon box, minimum depth 1.5˝; 31⁄2˝ octagon box, minimum depth 1.5˝
Operating Temperature Range: 0°C to 49°C (32°F to 120°F)
Operating Humidity Range: 10% to 93% Relative Humidity Non-condensing
Electrical Ratings (includes base and detector)
System Voltage: 120 VAC, 60 Hz
Relay Contact Ratings Resistive Load: Form A — 2.0A @ 30VAC/DC; Form C — 2.0A @ 30VAC/DC, 1.0A @ 125VAC
(If used, the RA400 Remote Annunciator and RTC operates within the specified detector system voltage)
Start-up Time (after 60 second reset): 36.0 seconds maximum
BEFORE INSTALLING
Please thoroughly read the System Sensor manual I56-407, Guide for Proper
Use of System Smoke Detectors. This manual provides detailed information on
detector spacing, placement, zoning, wiring, and special applications, and is
available at no charge from System Sensor. (For installation in Canada, refer to
CAN/ULC-S524, Standard for the Installation of Fire Alarm Systems and CEC
Part 1, Sec. 32.)
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with this base must be tested and maintained
nect smoke detectors to control panels and accessory devices should be colorcoded to reduce the likelihood of wiring errors. Improper connections can
prevent a system from responding properly in the event of a fire.
For signal wiring (the wiring between interconnected detectors), it is recommended that the wire be no smaller than AWG 18. However, the screws and
clamping plate in the base can accommodate wire sizes up to AWG 12. The
use of twisted pair wiring for the power (+ and –) loop is recommended to
minimize the effects of electrical interference.
FIGURE 1. TERMINAL LAYOUT :
regularly following NFPA 72 requirements. The detector used with this base
should be cleaned at least once a year.
GENERAL DESCRIPTION
The model B114LP detector base is designed for use with System Sensor model
2151 photoelectronic and 1151 ionization detector heads. This four-wire base is
equipped with screw terminals for the connection of power, ground, relay connections, and an optional RA400Z remote annunciator. It also includes a resistor that
limits current when the associated smoke detector is in the alarm state.
MOUNTING
The detector base mounts directly to 31/2-inch and 4-inch octagon boxes and
4-inch square boxes, with or without plaster rings. To mount the base, remove
the decorative ring by rotating it in either direction to unhook the snaps before
separating the ring from the base. Use the screws supplied with the junction
box to attach the base to the box through the appropriate slots in the base.
Position the decorative ring around the base and rotate it in either direction
until the ring snaps into place (see Figure 2).
BASE TERMINALS
NO. FUNCTION NO. FUNCTION
1 Remote Annunciator (+) 8 N.O. Alarm Relay
2 Test Coil (+) 9 N.O. Form A
3 Not Used 10 C. Initiation
4 Remote Annunciator (–) 11 C. Contacts
5 RTC (–) 12 N.O. Alarm Relay
6 C. Supervisory Relay 13 N.C. Form C
7 N.O. Form A Contacts 14 C. Auxiliary Contacts
INSTALLATION GUIDELINES
Allowable loop resistance is an important specification for control panels as
well as for smoke detectors and their bases. The alarm system cannot be expected to operate correctly if system components have incompatible allowable
loop resistances. Therefore, before beginning installation, refer to the control
panel manufacturer’s loop resistance specification to ensure that it is listed as
compatible with the System Sensor base and smoke detector being installed.
All wiring must be installed in compliance with the National Electrical Code
and all applicable local codes and any special requirements of the authority
having jurisdiction, using the proper wire size. The conductors used to con-
D150-02-00 1 I56-0598-004R
FIGURE 2. MOUNTING BASE TO BOX:
C1025-00
C0503-00
FIGURE 3. WIRING DIAGRAM FOR A TYPICAL 120VAC DETECTOR SYSTEM:
APA451
RELEASING
DEVICE
1
6
7
8
9
10
11
12
13
14
2
3
4
5
APA451
RELEASING
DEVICE
1
6
7
8
9
10
11
12
13
14
2
3
4
5
W
N
–
W
N
–
CONTROL
PANEL
ALARM INITIATION LOOP
NOTE: ABOVE DIAGRAM SHOWS NFPA REQUIRED WIRING OF SUPERVISED SYSTEMS.
SCHEMATIC SHOWN BELOW FOR REFERENCE.
EOL
CONTROL
PANEL
SPECIFIED BY PANEL
MANUFACTURER
SUPERVISORY
RELAY
SUPERVISORY
RELAY
ALARM
RELAY
ALARM
RELAY
EOL
67
10, 11
8, 9
10, 11
8, 9
67
BLACK LEADS
TRANSFORMER
PRIMARY
120
VAC
BLACK LEADS
TRANSFORMER
PRIMARY
120
VAC
PLASTIC LEVER
BREAK TAB AT DOTTED LINE BY
TWISTING TOWARD CENTER OF BASE
USE SMALL-BLADED SCREWDRIVER TO PUSH
PLASTIC LEVER IN DIRECTION OF ARROW
USE SMALL-BLADED SCREWDRIVER TO PUSH
PLASTIC LEVER IN DIRECTION OF ARROW
C1040-00
WIRING INSTRUCTIONS
NOTE: Refer the manufacturer’s instructions for releasing device wiring.
NOTE: To ensure that electrical connections are supervised, do NOT loop
wires under terminals 8, 9, 10, and 11 - cut the wire at each terminal.
To make electrical connections, strip approximately 3/8 inch (1 cm) insulation
from the end of each wire. Slide a wire under the clamp plate on each side of
the terminal screw and tighten the screw.
If the base is being installed in a zoned system, check the zone wiring before
installing the smoke detector head. The built-in shorting spring makes it convenient to do this. After the detector base is wired and attached to the electrical box, position the shorting spring against terminal 3. Use the slot in the
retaining clip to hold the spring against the terminal, as shown in Figure 1.
This detector base can be made tamper resistant so the detector cannot be detached without the use of a tool. To make the base tamper resistant, break off
the smaller tab at the scribed line on the tamper-resistance tab, on the detector mounting bracket (see Figure 4A), before installing the detector.
To remove the detector from the base after it has been made tamper resistant,
remove the decorative ring by rotating it in either direction and pulling it away
from the base. Then, insert a small screwdriver (Figure 4B) into the notch
and press the plastic lever toward the mounting surface. Rotate the detector
counterclockwise and remove.
FIGURE 4A. ACTIVATING TAMPER-RESISTANCE FEATURE:
This shorts the negative-in and negative-out leads so that loop wiring can be
tested for continuity. Do NOT remove the shorting spring from the base when
continuity tests are completed.
After all detector bases have been mounted, wired, and the wiring checked,
install the detector heads. The shorting spring in the base automatically disengages when the detector head is removed from the base. DO NOT remove the
shorting spring since it reengages as the detector head is turned into the base,
completing the circuit.
TAMPER-RESISTANCE FEATURE
NOTE: Do NOT use the tamper-resistance feature if the System Sensor XR2
Removal Tool will be used to remove detectors from the base.
System Sensor warrants its enclosed smoke detector base to be free from defects in ma-
Please refer to insert for the Limitations of Fire Alarm Systems
terials and workmanship under normal use and service for a period of three years from
date of manufacture. System Sensor makes no other express warranty for this smoke
detector base. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s
obligation of this Warranty shall be limited to the repair or replacement of any part of the
smoke detector base which is found to be defective in materials or workmanship under
normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a
Return Authorization number, send defective units postage prepaid to: System Sensor,
D150-02-00 2 I56-0598-004R
©2007 System Sensor
FIGURE 4B. REMOVING THE DETECTOR HEAD FROM BASE:
THREE-YEAR LIMITED WARRANTY
Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure. The Company
shall not be obligated to repair or replace units which are found to be defective because
of damage, unreasonable use, modifications, or alterations occurring after the date of
manufacture. In no case shall the Company be liable for any consequential or incidental
damages for breach of this or any other Warranty, expressed or implied whatsoever, even
if the loss or damage is caused by the Company’s negligence or fault. Some states do not
allow the exclusion or limitation of incidental or consequential damages, so the above
limitation or exclusion may not apply to you. This Warranty gives you specific legal
rights, and you may also have other rights which vary from state to state.
C0130-00
C0130-00