System Sensor B110LP Installation Instructions

INSTALLATION AND MAINTENANCE INSTRUCTIONS
SNAP ON
B110LP Plug-in Detector Base
For use with the following smoke detectors: IN US: 1151, 2151 IN CANADA: 1151A, 2151A IN EUROPE: 1151E, 2151E
SPECIFICATIONS
Base Diameter: 6.2 inches (157 mm) Base Height: 0.95 inches (24 mm) Weight: 0.3 lb. (137 g) Mounting: 4-inch square box with or without plaster ring. Min. depth–1.5 inches 3-1/2-inch octagon box. Min. depth–1.5 inches Operating Temperature Range: 0° to 49°C (32° to 120°F) Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing
Electrical Ratings - includes base and detector
System Voltage: 12/24 VDC Maximum Ripple Voltage: 4 Volts peak-to-peak Start-up Capacitance: 0.02 µF Maximum Standby Ratings: 8.5 VDC Minimum 35 VDC Maximum 120 µA Maximum Alarm Ratings: 4.2 VDC Minimum at 10 mA
6.6 VDC Maximum at 100 mA
Reset Voltage: 2.5 VDC Minimum Reset Time: 0.3 Seconds Minimum Start-up Time: 34.0 Seconds Maximum
(Alarm current must be limited to 100 mA (130 mA for models 1151 and 2151) by the control panel. If it is used, the RA400Z Remote Annunciator operates within the specified
detector alarm currents.)
I56-0594-005R
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
BEFORE INSTALLING
Please thoroughly read the System Smoke Detectors Application Guide, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor. (For installation in Canada, please refer to CAN/ULC-S524, Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32.)
NOTICE: This manual should be left with the owner/user of this equipment. IMPORTANT: The detector used with this base must be tested and maintained regu­larly following NFPA 72 requirements. The detector used with this base should be cleaned at least once a year.
GENERAL DESCRIPTION
The Model B110LP detector base is designed for use with System Sensor models 2151 photoelectronic and 1151 ionization detector heads. This two-wire base is equipped with screw terminals for the connection of power, ground, and an optional remote annunciator.
MOUNTING
The detector base mounts directly to 3-½ inch and 4-inch octagon boxes and 4-inch square boxes, with or without plaster rings. To mount the base, remove the decorative ring by rotating it in either direction to unhook the snaps before separating the ring from the base. Use the screws supplied with the junction box to attach the base to the box through the appropriate slots in the base (see Figure 1). Position the decorative ring around the base and rotate it in either direction until the ring snaps into place.
INSTALLATION GUIDELINES
Allowable loop resistance is an important specification for control panels as well as for smoke detectors and their bases. The alarm system cannot be expected to oper­ate correctly if system components have incompatible allowable loop resistances. Therefore, before beginning installation, refer to the control panel manufacturer’s loop resistance specification to ensure that it is listed as compatible with the System Sensor base and smoke detector being installed.
System Sensor smoke detectors and mounting bases are marked with a compatibility identifier as the last digit of a five-digit code stamped on the back of the product. Connect detectors only to compatible control units as indicated in System Sensor’s compatibility chart. This chart consists of a current list of UL-listed control unit/ detector combinations and is available from System Sensor upon request.
All wiring must be installed in compliance with the National Electrical Code and all applicable local codes and any special requirements of the authority having jurisdic-
FIGURE 1. MOUNTING BASE TO BOX:
SHORTING SPRING
DECORATIVE
RING
SCREWS
(NOT SUPPLIED)
DETECTOR
BASE
BOX
(NOT SUPPLIED)
C0503-00
1 I56-0594-005R 04-21
2
3
4
1
REMOTE
ANNUNCIATOR
2
3
4
1
REMOTE
ANNUNCIATOR
2-WIRE CONTROL PANEL
E O L
CLASS A OPTIONAL WIRING
PLASTIC LEVER
BREAK TAB AT DOTTED LINE BY TWISTING TOWARD CENTER OF BASE
USE SMALL-BLADED SCREWDRIVER TO PUSH PLASTIC LEVER IN DIRECTION OF ARROW
USE SMALL-BLADED SCREWDRIVER TO PUSH PLASTIC LEVER IN DIRECTION OF ARROW
tion, using the proper wire size. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding prop­erly in the event of a fire.
For signal wiring (the wiring between interconnected detectors), it is recommended that the wire be no smaller than AWG 18. However, the screws and clamping plate in the base can accommodate wire sizes up to AWG 12. The use of twisted pair wiring for the power (+ and -) loop is recommended to minimize the effects of electrical interference.
NOTE: To ensure that electrical connections are supervised, do NOT loop wires un­der terminals 2, 3, and 5 - break the wire at each terminal.
To make electrical connections, strip approximately 3/8˝(1 cm) insulation from the end of each wire. Slide the wires under the clamp plate and tighten the terminal screw.
Check the zone wiring before installing the smoke detector head. The built-in short­ing spring makes it convenient to do this. After the detector base is wired and at­tached to the electrical box, position the shorting spring against terminal 3. Use the slot in the retaining clip to hold the spring against the terminal, as shown in Figure 1. This shorts the negative-in and negative-out leads so that loop wiring can be tested for continuity.
The shorting spring in the base will disengage automatically when the detector head is removed from the base. DO NOT remove the shorting spring since it reengages as the detector head is turned into the base, completing the circuit.
TAMPER-RESISTANCE FEATURE
NOTE: DO NOT use the tamper-resistance feature if the System Sensor XR2 Re­moval Tool will be used to remove detectors from the base.
This detector base can be made tamper resistant so that the detector cannot be de­tached without the use of a tool. To make the base tamper-resistant, break off the smaller tab at the scribed line on the tamper-resistance tab, on the detector mounting bracket (see Figure 3A), before installing the detector.
To remove the detector from the base after it has been made tamper resistant, remove the decorative ring by rotating it in either direction and pulling it away from the base.
Then, insert a small screwdriver into the notch (see Figure 3B), and press the plastic lever toward the mounting surface before rotating the detector counterclockwise for removal.
FIGURE 2. WIRING DIAGRAM FOR A TYPICAL 2-WIRE DETECTOR SYS­TEM:
C0529-00
Note: If a remote annunciator is not used, polarity of these terminals may be reversed.
FIGURE 3A. ACTIVATING THE TAMPER-RESISTANCE FEATURE:
C0130-00
FIGURE 3B. REMOVING DETECTOR HEAD FROM BASE:
THREE-YEAR LIMITED WARRANTY
System Sensor warrants its enclosed smoke detector base to be free from defects in ma­terials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector base. No agent, representative, dealer, or employee of the Company has the au thority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector base which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: Honeywell,
2 I56-0594-005R ©2016 System Sensor. 04-21
12220 Rojas Drive, Suite 700, El Paso TX 79936 USA. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the
­Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
C0130-00