System Sensor 2951 Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
2951 Intelligent Photoelectronic
3825 Ohio Avenue, St. Charles, Illinois 60174
Smoke Sensor
Specifications
Operating Voltage Range: 15 to 30 VDC Current: 270µA Max. Communication active but not to device in blink mode LED Current: 6.5 mA Continous ON Operating Humidity Range: 10% to 93% Relative Humidity, noncondensing Operating Temperature Range: 0° to 49°C (32° to 120°F) Height: 1.95 inches (50 mm) installed in Base Diameter: 4.0 inches (102 mm) installed in Base Weight: 2.96 oz. (92 g)
Before Installing
General Description
Model 2951 is a plug-in type smoke sensor that combines a photoelectronic sensing chamber with addressable-analog communications. The sensor transmits an analog represen­tation of smoke density over a communication line to a control panel. The sensor’s address is set b y the Hand Held Programmer (HHP ). An LED on the sensor is controlled b y the panel to indicate sensor status.
The Model 2951 requires compatible addressable com­munications to function properly. Connect this sensor to listed-compatible control panels only.
Spacing
System Sensor recommends spacing sensors in compliance with NFPA 72. In low air flow applications with smooth ceilings, space sensors 30 feet apart. For specific informa­tion regarding sensor spacing, placement, and special ap­plications, refer to NFPA 72 or the S y stem Sensor Guide For Proper Use of System Smoke Detectors, available at no charge from System Sensor (P/N I56-407-XX).
Wiring Instructions
All wiring must be installed in compliance with the Na­tional Electrical Code, applicable local codes, and any spe­cial requirements of the Authority Having Jurisdiction. Proper wire gauges should be used. The installation wires should be color-coded to limit wiring mistakes and ease system troubleshooting. Improper connections will prevent a system from responding properly in the event of a fire.
NOTE: The mounting base (B901) uses SEMS Plate termi-
nals and can accommodate 2 wires each. The 2 wires can differ by a maximum of 2 wire gauges.
Remove power from the communication line before in­stalling sensors.
All wiring must conform to applicable local codes, ordi­nances, and regulations.
1. Wire the sensor base (supplied separately) per the wir­ing diagram, see Figure 1.
2. Prior to installation, address the sensor using the Hand Held Programmer (HHP ). See Hand Held Programmer instruction manual for proper operation.
3. Install the sensor into the sensor base. Push the sensor into the base while turning it clockwise to secure it in place.
1-800-SENSOR2, FAX: 630-377-6495
A Division of Pittway
D200-86-00 1 I56-1321-00
Figure 1:
Remote Annunciator
+
-
+
OUT
+IN/OUT
-
IN
-
+R/A
-
-
-
U.L. listed compatible control panel
4. After all sensors have been installed, apply power to the control unit and activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
Dust covers provide limited protection against airborne dust particles during shipping. Dust covers must be re­moved before the sensors can sense smoke. Remove sen­sors prior to heavy remodeling or construction.
+
CAUTION
CLASS A OPTIONAL WIRING
+R/A
+IN/OUT
-
OUT
IN
The sensor can be tested in the following ways:
A. Smoke Entry: Aerosol Generator
Aerosol generators for smoke entry testing are available from a number of third party manufacturers (e.g., Gemini Scientific). Follo wing the manufacturer’ s instruc­tions, apply aerosol until the panel alarms.
Coded signals, transmitted from the panel, can cause the LEDs to blink, latch on, or latch off. Refer to the control panel technical documentation for sensor LED status operation and expected delay to alarm.
+R/A
-
OUT
+IN/OUT
-
IN
A78-2665-01
B. Sensitivity:
Testing
Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out of service. Disable the system to prevent unwanted alarms.
All sensors must be tested after installation and periodi­cally thereafter. Testing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer maximum perfor­mance when tested and maintained in compliance with NFPA 72 and all applicable codes, ordinances and regula­tions.
D200-86-00 2 I56-1321-00
The sensitivity of the detector can be monitored and tested by the Hand Held Programmer. R efer to HHP docu­mentation for sensitivity testing information. Certain control panels may also monitor and test the detector’s sensitivity. Refer to control panel documentation for sen­sitivity testing information. The sensitivity indication is independent of communication. An acceptable sensitiv­ity range is stamped on the back of the sensor.
A sensor that fails any of these tests should be cleaned as described under CLEANING, and retested. If the sensor fails after cleaning, it must be replaced and returned for repair.
When testing is complete, restore the system to normal op­eration and notify the proper authorities that the system is back in operation.
Loading...
+ 2 hidden pages