System Sensor 2551, 2551T User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
2551 and 2551T Plug-in Intelligent Photoelectronic Sensors with Communications
Specifications
Diameter: 6.1 inches (15.5 cm) installed in B501B
4.0 inches (10.2 cm) installed in B501
Height: 3.2 inches (8.1 cm)
Add 0.5 inches (1.3 cm) for thermal models Weight: 9.6 ounces (272 g) Installation Temperature Range
2551: 32° to 120°F (0° to 49°C)
2551T: 32° to 100°F (0° to 38°C)
Installation Humidity Range: 10% to 93% Relative Humidity Mounting: B501B flanged base
B501 flangeless base
B501 with RMK400 recessed mounting kit Maximum Air Velocity: 3000 Ft./Min. (15 m/S) Voltage Range: 15 to 32 Volts DC Peak Standby Current: 230 µA @ 24 VDC LED Current: 6.5 mA @ 24 VDC
Please thoroughly read the system wiring and installation manual, which provides detailed information on sensor spacing, placement, zoning, and special applications. Cop­ies of these manuals are available from System Sensor.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: These detectors must be tested and main­tained regularly following NFPA 72 requirements. These detectors should be cleaned at least once a year.
General Description
The model 2551/2551T photoelectronic sensors utilize a state-of-the-art, optical sensing chamber. These sensors are designed to provide open area protection, and to be used with compatible control panels only. Connect detectors only to compatible control units. (For installation in Canada, refer to CAN/ULC-S524-M86, Standard for the In­stallation of Fire Alarm Systems and CEC Part 1, Sec. 32.)
The 2551T adds a thermal heat collector that will alarm at a
fixed temperature of 135° F.
Wiring Guide
Refer to the installation instructions for the particular plug­in base being used: 1) for the B501B base (D550-01-01); 2) for the B501 base (D550-02-00); 3) for the RMK400 used with the B501 base (D450-07-00). Bases are provided with screw terminals for power, ground, and remote annunciator connections (see Figure 1).
NOTE: All wiring must conform to applicable local codes,
ordinances, and regulations.
NOTE: Verify that all sensor bases are installed and that
the wiring polarity is correct at each base.
Remove power from the loop before installing sensors.
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
WARNING
Two LEDs on each sensor light to provide a local 360° vis-
ibility of the sensor indication. The LEDs can be latched ON by code command from the panel for an alarm indica­tion. The LEDs can also be unlatched to the normal condi­tion by code command. Remote LED annunciator capability is available as an optional accessory (part no. RA400Z).
D500-04-00 1 I56-292-05
1. Install sensors: a. Verify that the sensor type matches the type written
on the label on the base.
b. Set the sensor to a desired address and then write the
address on the label on the base.
c. Place the sensor into the sensor base.
Figure 1. Wiring Diagram:
REMOTE ANNUNCIAT OR
+-
+
2
3
1
CONTROL PANEL
U.L. LISTED COMPATIBLE
-
­+
CLASS A OPTIONAL WIRING
d. Turn the sensor clockwise until it drops into place. e. Continue turning the sensor clockwise until it locks
into place.
WARNING
Sensor will not detect smoke if dust cover is installed.
2. Tamper-proof feature: The sensor bases include a tamper-proof feature that, when activated, prevents removal of the sensor without the use of a tool. See the installation instruction manual for the sensor base for details in using this feature.
3. After all sensors have been installed, apply power to the control unit.
4. Test all sensors per the TESTING section of this manual.
CAUTION: Do not loop wire under terminal 1 or 2. Break wire run to provide supervision of connections.
2
3
1
2
3
1
Testing
Before testing, notify the proper authorities that the smoke sensor system is undergoing maintenance, and therefore the system will temporarily be out of service. Disable the zone or system undergoing maintenance to prevent un­wanted alarms. Sensors must be tested after installation and periodic main­tenance. The sensor may be tested in the following ways:
A. Test Magnet (Model No. M02-04-00)
1. Place the magnet against the cover opposite the test module socket to activate the test feature (see Figure 2).
2. The LEDs should latch on within 10 seconds indicat­ing alarm and annunciating the panel.
B. Test Module (Model No. MOD400R)
The MOD400R is used with your DMM or voltmeter to check the sensor sensitivity as described in the MOD400R’s manual.
A78-1253-01
Figure 2. Views showing position of test magnet (model 2551T shown):
LED
TEST MODULE
SOCKET
LED
D500-04-00 2 I56-292-05
TEST
MAGNET
PAINTED
SURFACE
TEST
MAGNET
A78-1410-01
NOTE: If the sensor’s sensitivity limits or the MOD400R
limits do not appear on the back of the sensor, the MOD400R is not suitable for field sensitivity test­ing of that unit.
C. Smoke Entry Test per NFPA 72
The field test tool is the Gemini Model 501 aerosol gener­ator. Set the generator to represent 4%/ft to 5%/ft ob­scuration as described in the Gemini 501 manual. Using the bowl shaped applicator, apply aerosol until unit alarms. If the Gemini unit is not available, a punk, cot­ton wick, or cigarette are acceptable means of generating smoke to test all System Sensor ionization and photo­electronic sensors.
D. Direct Heat Method (Hair dryer of 1000-1500 watts)
Direct the heat toward the thermal collector. Hold the heat source about 12 inches from the detector in order to avoid damage to the plastic. The detector will reset only after the collector has had sufficient time to cool and the power source has been momentarily interrupted.
After testing, detectors must be reset from the control panel. Notify the proper authorities that the system is back on line.
Sensors that fail these tests should be cleaned as described under CLEANING and retested. If the sensors still fail these tests they should be returned for repair.
NOTE: This test only verifies proper operation of the sen-
sor and is not used to test sensitivity.
Figure 3:
REMOVABLE COVER
TEST SLOT
REMOVABLE SCREEN
P/N RS24 (W/O THERMAL)
RS24T (W/THERMAL
CAUTION
Dust cover is not a substitute for removing sensor during new construction or heavy remodeling. Cover only helps limit dust entry.
Cleaning the Sensor
NOTE: Before cleaning, notify the proper authorities that
the smoke sensor system is undergoing mainte­nance and will temporarily be out of service. Dis­able the loop or system undergoing maintenance to prevent unwanted alarms.
It is recommended that the sensor be removed from its mounting base to facilitate easier cleaning (see Figure 3). The sensor is cleaned as follows:
1. Remove the sensor cover by placing a small bladed screwdriver in the side slot of the sensor cover, twisting it slightly until the cover can be turned counterclockwise for removal.
2. Vacuum the screen carefully without removing it. If fur­ther cleaning is required continue with Step 3, otherwise skip to Step 6.
3. Remove the screen by pulling it straight out. Vacuum the inside.
4. Clean the vaned chamber piece by vacuuming or blow­ing out dust and particles.
5. To replace the screen, orient it so that the arrow on top aligns with the field test slot on the base of the detector. Carefully push the screen onto the base making sure it fits tightly to the chamber.
6. Replace the cover by gently rotating it clockwise until it locks in place.
A78-1941-01
D500-04-00 3 I56-292-05
The Limitations of Property Protection Smoke Detectors
This smoke detector is designed to activate and initiate emergency ac­tion, but will do so only when it is used in conjunction with an authorized fire alarm system. This detector must be installed in accordance with NFPA standard 72.
Smoke detectors will not work without power. AC or DC powered smoke detectors will not work if the power supply is cut off.
Smoke detectors will not sense fires which start where smoke does not reach the detectors. Smoldering fires typically do not generate a lot of
heat which is needed to drive the smoke up to the ceiling where the smoke detector is usually located. For this reason, there may be large de­lays in detecting a smoldering fire with either an ionization type detector or a photoelectric type detector. Either one of them may alarm only after flaming has initiated which will generate the heat needed to drive the smoke to the ceiling.
Smoke from fires in chimneys, in walls, on roofs or on the other side of a closed door(s) may not reach the smoke detector and alarm it. A detector cannot detect a fire developing on another level of a building quickly or at all. For these reasons, detectors shall be located on every level and in
every bedroom within a building.
Smoke detectors have sensing limitations, too. Ionization detectors and
photoelectric detectors are required to pass fire tests of the flaming and
WARNING
smoldering type. This is to ensure that both can detect a wide range of types of fires. Ionization detectors offer a broad range of fire sensing capa­bility but they are somewhat better at detecting fast flaming fires than slow smoldering fires. Photoelectric detectors sense smoldering fires better than flaming fires which have little, if any, visible smoke. Because fires de­velop in different ways and are often unpredictable in their growth, nei­ther type of detector is always best, and a given detector may not always provide early warning of a specific type of fire.
In general, detectors cannot be expected to provide warnings for fires re­sulting from inadequate fire protection practices, violent explosions, es­caping gases which ignite, improper storage of flammable liquids like cleaning solvents which ignite, other similar safety hazards, arson, smok­ing in bed, children playing with matches or lighters, etc. Smoke detectors used in high air velocity conditions may have a delay in alarm due to dilu­tion of smoke densities created by frequent and rapid air exchanges. Addi­tionally, high air velocity environments may create increased dust contamination, demanding more frequent maintenance.
Smoke detectors cannot last forever. Smoke detectors contain electronic parts. Even though smoke detectors are made to last over 10 years, any part can fail at any time. Therefore, smoke detectors shall be replaced after being in service for 10 years. The smoke detector system that this detector is used in must be tested regularly per NFPA 72. This smoke detector should be cleaned regularly per NFPA 72 or at least once a year.
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from de­fects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or work­manship under normal use and service during the three year period com­mencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Depart-
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifica­tions, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
D500-04-00 4 I56-292-05
© System Sensor 1996
Loading...