AUTOPING & POWER REBOOT
Each power outlet can be configured to run Autoping and reboot. Please use the web interface to complete the settings.
POWER OUTLET MANUAL SWITCH (IF EQUIPPED)
Press the “Power Outlet Manual Switch” button located on the front panel. Keep press and release the button until desired outlet LED is blinking. THEN HOLD THE SWITCH DOWN FOR 3 SECONDS. The selected outlet will change the On/Off state.
Note: a user reserved power outlet can’t be manually controlled.
SNMP AND TRAP (S SERIES)
By default, SNMP agent and TRAP are disabled.
Default community string is “public”. To obtain a copy of SNMP MIB files, open the device web page.
Down load the MIB file by clicking “get mib file” at Network Setting” web page.
SAVE/LOAD SETTINGS
Saving and reloading system configuration data file is done by running a small utility program on a PC. This operation requires network connection.
Download “synCfg.exe” by visiting www.synaccess-net.com/support.php
Run the program at DOS prompt: “syncfg.exe –h”
FIRMWARE UPGRADING
The system is firmware upgradable via network. Please contact us or visit our web site for upgrading instructions and firmware version information.
PROGRAMMING INTERFACING
The unit can be easily managed by using direct TCP or serial port interfacing.
Using Telent Port: default port # is 23.
Format: CmdCode Arg1 Arg2
Using HTTP/HTTPS. Note: HTTPS for T version. http://my_IP_addr/cmd.cgi?cmdCode Arg1 Arg2
Command List
Command |
Code |
Arg 1 |
|
Arg 2 |
Login |
$A1 |
ID |
|
PWD |
Logout |
$A2 |
|
|
|
Set Outlet to |
$A3 |
Port# |
|
V (1-ON; |
ON/OFF |
|
|
|
0-OFF) |
Reboot |
$A4 |
Port# |
|
|
Get Outlet |
$A5 |
|
|
|
Status |
|
|
|
|
Status Return |
$A5 |
xxxx,cccc,cccc,tt |
||
|
|
Or xxxx,cccc,tt |
|
|
|
|
Each “x” denotes an outlet |
||
|
|
state (“1” denotes ON; “0” |
||
|
|
for OFF). The most right |
||
|
|
“x” for relay1. “c” denotes |
||
|
|
AC current draw (amp) and |
||
|
|
“t” for temperature (c). |
||
Set All Outlet |
$A7 |
V (1-ON; 0- |
|
|
ON/OFF |
|
OFF) |
|
|
Return Code |
$A0 |
|
|
|
(OK) |
|
|
|
|
|
|
|
|
|
Return Code |
$AF |
|
|
|
(Failed) |
|
|
|
|
|
|
|
|
|
Unknown |
$AF |
|
|
|
Code |
|
|
|
|
At serial or Telnet terminal, type command
“help” or “?” to get a list of commands.
Synaccess Networks, Inc
QUICK STARTUP
REFERENCE
For netBooter™ series S, T or B Part # 1090 V9
Default IP: 192.168.1.100
DHCP is not enabled. To enable it, see Section DEFAULT SETTINGS below.
Default serial port: 9600-8-N-1.
Using WEB browser to see more detailed system configuration descriptionHow to. start:
For serial or Telnet interfacing, type command
“help” to see a list of commands.
1)Use a straight-thru Ethernet cable connect the unit to your network:
By default, DHCP is disabled. The static IP address is 192.168.1.100. Use a WEB or Telnet program to configure the unit. The default ID/Password is admin/admin. If you need to enable the DHCP, please read “DEFAULT SETTINGS” section.
2)Use a crossover Ethernet cable to connect to a PC directly:
The static IP address for the unit is 192.168.1.100. Make sure your PC IP address is on the same subnet. 192.168.1.x. Use WEB or Telnet program to configure the unit.
3)Use a serial cable to connect the unit and a PC:
Run a Terminal Program on the PC to configure the unit. The serial port settings are 9600-8-N-1.
Type command “help” or “?” to view a list of command.
Synaccess Networks, Inc.
75 W Baseline Rd, Suite 10
Gilbert, AZ85233
(928)257-1838 Fax-(760) 930-0550 www.synaccess-net.com
Page 5 |
Page 6 |
Page 1 |
|