Symmetricom 5087B Operation And Maintenance Manual

Symmetricom 5087B Wideband Distribution Amplifier
Operations and Maintenance Manual
Part Number 05087-13402
Revision E
Notices
© Symmetricom, Inc. 2004-2010
No part of this manual may be reproduced in any form or by any means (including electronic storage and retrieval or transla­tion into a foreign language) without prior agreement and written consent from Sym­metricom, Inc. as governed by United States and international copyright laws.
Manual Part Number
05087-13402
Edition
Rev. E, November 2010
www.symmetricom.com
support@symmetricom.com
Phone:
Worldwide (Main Number) 1-408-428-7907
USA toll-free 1-888-367-7966 (1-888-FOR-SYMM)
Warranty
The material contained in this doc­ument is provided “as is,” and is subject to being changed, without notice, in future editions. Further, to the maximum extent permitted by applicable law, Symmetricom disclaims all warranties, either express or implied, with regard to this manual and any information contained herein, including but not limited to the implied warranties of merchantability and fitness for a particular purpose. Symmetricom shall not be liable for errors or for incidental or consequential dam­ages in connection with the furnish­ing, use, or performance of this document or of any information contained herein. Should Symmet­ricom and the user have a separate written agreement with warranty terms covering the material in this document that conflict with these terms, the warranty terms in the separate agreement shall control.
Technology Licenses
The hardware and/or software described in this document are furnished under a license and may be used or copied only in accordance with the terms of such license.
Restricted Rights Legend
If software is for use in the performance of a U.S. Government prime contract or subcontract, Software is delivered and licensed as “Commercial computer soft­ware” as defined in DFAR 252.227-7014 (June 1995), or as a “commercial item” as defined in FAR 2.101(a) or as “Restricted computer software” as defined in FAR
52.227-19 (June 1987) or any equivalent agency regulation or contract clause. Use, duplication or disclosure of Software is subject to Symmetricom’s standard com­mercial license terms, and non-DOD Departments and Agencies of the U.S. Government will receive no greater than Restricted Rights as defined in FAR
52.227-19(c)(1-2) (June 1987). U.S. Gov­ernment users will receive no greater than Limited Rights as defined in FAR
52.227-14 (June 1987) or DFAR
252.227-7015 (b)(2) (November 1995), as applicable in any technical data.
Safety Notices
CAUTION
A CAUTION notice denotes a hazard. It calls attention to an operating procedure, practice, or the like that, if not correctly per­formed or adhered to, could result in damage to the product or loss of important data. Do not proceed beyond a CAUTION notice until the indicated conditions are fully understood and met.
WARNING
A WARNING notice denotes a hazard. It calls attention to an operating procedure, practice, or the like that, if not correctly performed or adhered to, could result in personal injury or death. Do not proceed beyond a WARNING notice until the indi­cated conditions are fully understood and met.
Contents
1Introduction
2 Installing and Setting Up the Symmetricom 5087B
Safety Requirements 6
Symbols 7
About This Manual 8
Conventions 9
Symmetricom 5087B Overview 10
Installing the Symmetricom 5087B 14
To set up the Symmetricom 5087B 14
Adjusting the Output Level 17
To adjust the output level 17
Assigning a Static IP Address 18
To assign the static IP address using the Lantronix DeviceInstaller
software 18
To assign the static IP address using Telnet 19
Cleaning 20
3 Monitoring the Symmetricom 5087B
Accessing the System 22
Checking System Status 23
Checking Alarms and Input Frequency 23 Understanding Alarm Output 24 Checking Model Number and Software Version 25
4 Troubleshooting the Symmetricom 5087B
Replacing Fuses 28
To replace a fuse 28
Verifying Operational Problems 29
Symmetricom 5087B Operations and Maintenance Manual Rev. E i
A Specifications
B Glossary
Directives 33
Electromagnetic Compatibility 89/336/EEC 33 Safety 73/23/EEC 33 Standards 33
Electrical Specifications 34
Environmental Specifications 36
Physical Specifications 37
ii Symmetricom 5087B Operations and Maintenance Manual Rev. E
Symmetricom 5087B Wideband Distribution Amplifier Operations and Maintenance Manual
1 Introduction
Symbols 7
About This Manual 8
Conventions 9
Symmetricom 5087B Overview 10
Front panel 10
Rear panel 11
5
1 Introduction
Safety Requirements
Do not attempt to install or operate this equipment if you have not
first acquired proper training.
Ensure that all cables are properly connected. The power cord must be easy to remove from the back.
Verify that input line voltage and current capacity are within specifications before turning on the unit.
Do not place power supply cords or other cables on top of unit or against heatsinks.
Operating and maintenance personnel must receive proper training before installing or maintaining electrical equipment.
6 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Symbols
Introduction 1
These symbols (icons) appear throughout the manual as well as on the unit itself.
Symbol Definition
On the unit, this symbol means: Caution - Refer to User Manual. This symbol identifies a hazard. The label next to the symbol indicates how serious the hazard is. Danger indicates an imminent hazard. If not avoided, the hazard will cause death or serious injury. War ning indicates a potential hazard. If not avoided, the hazard can cause death, serious injury, or substantial damage to equipment. Caution indicates a potential hazard. If not avoided, the hazard can cause moderate injury or moderate damage to equipment.
Hot surface.
CE marking. This symbol attests compliance to applicable European Directives.
Fuse.
Signal input.
Signal output.
Alarm signal out.
LAN port.
Chassis ground.
Earth terminal symbol: used to indicate an earth ground connection to chassis.
Symmetricom 5087B Operations and Maintenance Manual Rev. E 7
1 Introduction
About This Manual
This manual tells you how to install, set up, monitor, and troubleshoot the Symmetricom 5087B.
Chapter 1, “Introduction” explains symbols that appear in the manual
and on the unit as well as documentation conventions. The chapter also briefly describes the Symmetricom 5087B.
Chapter 2, “Installing and Setting Up the Symmetricom 5087B”
contains important safety information and describes how to install the Symmetricom 5087B, set the gain, and assign a fixed IP address.
Chapter 3, “Monitoring the Symmetricom 5087B” describes how to
monitor alarms.
Chapter 4, “Troubleshooting the Symmetricom 5087B” describes how
to replace fuses and verify operational problems.
Appendix A, “Specifications” contains the detailed specifications for
the Symmetricom 5087B.
8 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Conventions
Introduction 1
This manual uses several typographical conventions to help explain how to use the Symmetricom 5087B.
Table 1 Conventions
Convention Definition
Bold Words i n bold show:
Italics Words i n italics show:
Buttons and icons to click
Menu options to select
Commands to type
Non-variable information displayed in response to commands
Names of windows and dialog boxes
Variable information displayed in response to commands
Note This symbol means the following information is a note that gives you important
information that may affect how you use the Symmetricom 5087B.
Symmetricom 5087B Operations and Maintenance Manual Rev. E 9
1 Introduction
Symmetricom 5087B Overview
The Symmetricom 5087B Wideband Distribution Amplifier distributes multiple copies of a precise frequency throughout a research and development laboratory, manufacturing facility, calibration lab, or anywhere a precise frequency standard is required.
Its input accepts 1 to 10 MHz sine waves at amplitudes of 0.3 to 3.0 Vrms and uses automatic gain control to maintain the set output level when the input signal level varies. The Symmetricom 5087B produces low noise copies of the input signal on each of its 12 outputs. Output amplitude can be adjusted from 0.75 to 3 Vrms via a potentiometer screw accessible from the front panel to compensate for cable loss.
The Symmetricom 5087B uses a 2U high, 19-inch rack-mount chassis. An Ethernet port on the rear panel enables you to remotely monitor the status of the input and output signals. When the unit detects a failure, it immediately sends an alarm to the Ethernet port. The LEDs on the front panel show the status of the input signal, each of the 12 output signals, and the inputs.
Power–Green when power is on.
Alarm–Red when alarm condition
Figure 1 shows the instrument’s front panel, and Figure 2 shows the rear
panel.
A, B, and Input Select–Lit LED shows active input. Red when not receiving an input signal. B input is always off.
OUTPUT–LEDs green during normal operation of output signals. All red when unit has no input signal on the active channel.
Use the
potentiometer next
to each LED to set
Figure 1 Front panel
10 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Introduction 1
AC POWER– connector.
ETHERNET PORT–1 RJ-45 connector.
INPUT A–Connect 1 to 10 MHz source.
Figure 2 Rear panel
ALARM–Open collector output device.
OUTPUTS–12 BNC connectors.
Symmetricom 5087B Operations and Maintenance Manual Rev. E 11
1 Introduction
12 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Symmetricom 5087B Wideband Distribution Amplifier Operations and Maintenance Manual
2 Installing and Setting Up the Symmetricom 5087B
Installing the Symmetricom 5087B 14
Adjusting the Output Level 17
Assigning a Static IP Address 18
Cleaning 20
13
2 Installing and Setting Up the Symmetricom 5087B
Installing the Symmetricom 5087B
The Symmetricom 5087B ships ready for installation into a standard 19" (48.3 cm) rack.
Accessories included:
CD-ROM documentation P/N 05087-13402)
Power cord
Rear brackets with attaching hardware (Replacement kit P/N
05087-67002)
Required for installation:
North American or European IEC power cord. One or the other will be supplied with the unit.
#1 Phillips screwdriver.
Customer-supplied, RG223 cables with BNC connectors from source
and to next devices in system.
Customer-supplied, LAN cable for network connection (RJ-45).
Rack mounting screws.
Screwdriver for the rack mount screws, as needed.
Since the unit does not have a AC mains power switch, both the appliance inlet connector and the plug on the detachable power supply cord are considered to be suitable disconnect means for disconnecting the unit from the AC mains supply. If the rear of the unit is not accessible after installation in the instrument rack, you must provide a suitable external AC disconnect means for the unit.
To set up the Symmetricom 5087B
1 Unpack carefully and inspect the Symmetricom 5087B.
2 Check for physical damage.
If you observe physical damage, immediately contact Symmetricom, Inc. and the carrier.
We recommend saving the shipping container for submitting any necessary claims to the carrier.
14 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Installing and Setting Up the Symmetricom 5087B 2
3 (Optional.) Install the unit in a 19-inch rack.
Two rack mount brackets are included with the unit to provide rear chassis support when installed in a rack. Use the three 10-32 x 0.5 screws on each side of the unit to attach the brackets.
On short depth racks, shorten these rails as necessary to ensure that they do not cover the holes forward of the brackets’ rail mounting slots. You can break off the rails after the first set of slots by bending at the point where there is a perpendicular slot and notches in the side of the bracket.
4 Plug the female end of the power cord into the male IEC-320 plug on
the rear of each power supply.
5 Plug the male end of each power cord into a 100–240 VAC, 50/60 Hz
power source.
Ensure that this power supply cord is connected to a properly grounded mains receptacle.
6 Connect the input signal cables from a 1 to 10 MHz source to the
INPUT A BNC connector on the rear panel.
7 Connect up to 12 cables to the OUTPUT BNC connectors on the rear
panel to supply users with a copy of the input signal.
Symmetricom 5087B Operations and Maintenance Manual Rev. E 15
8 (Optional.) Connect a TTL input device to the ALARM BNC
connector on the rear panel of the Symmetricom 5087B.
9 (Optional.) Connect a LAN cable to the Ethernet port on the rear
panel of the Symmetricom 5087B.
2 Installing and Setting Up the Symmetricom 5087B
For information about configuring the network connection, see
“Assigning a Static IP Address" on page 18.
16 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Adjusting the Output Level
You can adjust the output level to a value between 0.75 Vrms and 3 Vrms.
Required equipment:
Oscilloscope
Small flat-head screwdriver
To adjust the output level
1 Connect an oscilloscope to the output you want to change.
2 Using a small flat-head screwdriver, turn the potentiometer next to
Installing and Setting Up the Symmetricom 5087B 2
the LED for the output until the oscilloscope shows the output level you want.
Symmetricom 5087B Operations and Maintenance Manual Rev. E 17
2 Installing and Setting Up the Symmetricom 5087B
Assigning a Static IP Address
The Symmetricom 5087B contains a Lantronix® Xport™ Ethernet to RS-232 converter, which provides the instrument’s Ethernet connection.
The Symmetricom 5087B ships from the factory with a default IP address of 0.0.0.0, which enables DHCP. If the network has a DHCP server, it will assign each unit an IP address, gateway address, and subnet mask when the unit starts up.
To monitor multiple Symmetricom 5087Bs remotely through their Ethernet connections, you must assign each unit a fixed IP address. You identify which unit is the source of an alarm by its IP address. Follow the instructions in this section to assign a unit’s IP address using either the Lantronix DeviceInstaller software or Telnet port 9999.
The DeviceInstaller software is available only by downloading from the Lantronix Web site. Go to: http://www.lantronix.com. For more detailed information about the DeviceInstaller software, see the Xport User Manual. Section 3.3 discusses several different ways that you can assign IP addresses. Chapter 4 explains how to permanently configure the IP address. You can download the Xport User Manual from the Lantronix® Web site as an Adobe® Acrobat® PDF file. Go to: http://www.lantronix.com
NOTE
If you move the Symmetricom 5087B to a different network hub after setting up the static IP address, the host computer may not be able to make a connection. You may need to release the IP address lease on your operating system.
To assign the static IP address using the Lantronix DeviceInstaller software
1 Obtain the following network information from your system
administrator for each Symmetricom 5087B you want to install:
IP Address: ______ ______ ______ ______
Subnet Mask: ______ ______ ______ ______
Gateway: ______ ______ ______ ______
2 Connect a Windows® PC to the same local subnet as the
Symmetricom 5087B.
3 Install and start the Lantronix® DeviceInstaller software.
4 Click the Search Network icon and search for XPORT devices
connected to the network, then click Save and Exit.
18 Symmetricom 5087B Operations and Maintenance Manual Rev. E
5 Click the IP icon or select Assign IP Address on the Too ls menu.
Installing and Setting Up the Symmetricom 5087B 2
The hardware device number and IP address appear in the Assign IP Address dialog box.
6 Type the new IP address and click OK.
The new IP address appears in the Lantronix® DeviceInstaller window.
7 Test the IP address by pinging the instrument’s Xport™ on the
Lantronix Xport Installer window.
Click the Ping icon or select Ping Device on the Tool s menu.
The Ping Device window should show the IP address of the instrument’s Xport™ device, and it should show successful replies if the IP address has been configured correctly.
8 Exit the browser.
To assign the static IP address using Telnet
1 Telnet to the assigned address, port 9999.
2 Press Enter within five seconds to enter the setup mode.
3 Select Option 0.
4 Set the IP address and follow the on-screen instructions to save the
setting.
5 Telnet to the new IP address, port 10001.
6 Type I
You do not need to type a carriage return or line feed.
The system returns I5087B-00\r\n, where the 00 is the hardware version, and turns on the front panel input LEDs for two seconds before returning to normal operation.
If you see these responses, you know you are communicating with the unit.
Symmetricom 5087B Operations and Maintenance Manual Rev. E 19
2 Installing and Setting Up the Symmetricom 5087B
Cleaning
Clean the main chassis with a soft cloth dampened with a mild soap and water solution.
CAUTION
Do not spray or use too much liquid when cleaning the unit. Liquid can enter the unit and damage sensitive electronic components.
20 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Symmetricom 5087B Wideband Distribution Amplifier Operations and Maintenance Manual
3 Monitoring the Symmetricom 5087B
Accessing the System 22
Checking System Status 23
Understanding Alarm Output 24
21
3 Monitoring the Symmetricom 5087B
Accessing the System
You access the Symmetricom 5087B system remotely by connecting to its Command-And-Response (CNR) Port through the Ethernet connection. The CNR port (Port 10001), which uses TCP/IP, lets users input commands, displays results of the commands, and publishes alarms as they occur.
When you Telnet to the CNR port, the system does not display a prompt.
22 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Checking System Status
Checking Alarms and Input Frequency
Monitoring the Symmetricom 5087B 3
You can check the system status and the model and software version remotely.
If you have connected a monitor to the open collector ALARM output connector, that device will also receive alarm information.
The system can report current alarms and latched alarms.
To check system status
Type: S
You do not need to type a carriage return or line feed.
The system returns Sabcde,fghij\r\n where
abcde is current status.
fghij is latched alarms and changed status since the last status
request.
Both abcde and fghij are hexadecimal numbers, with each bit position representing one output. LSB (farthest right) is output 1. MSB is the input. Bits 0–15 are latched alarms. Bits 16–19 are change in status bits.
Latched alarms remain active in the current status field and latched status field until the problem is corrected. Changed status bits are cleared upon next status request.
Example: S00001,00001
This example shows an output 1 failure that is active and occurred since the last status request.
Table 2 defines each status or alarm bit position.
Table 2 Status or alarm binary codes
Status or alarm character position
Bit position Bit value and description
Symmetricom 5087B Operations and Maintenance Manual Rev. E 23
a or f 19 and 18 Remote control bits:
1:1 = Not available
17 and 16 Front panel switch control bits:
1:1 = Not available
3 Monitoring the Symmetricom 5087B
Table 2 Status or alarm binary codes
Status or alarm character position
b or g 15 0 = Channel A active input
c or h 11 1 = output 12 failed
d or i 7 1 = output 8 failed
e or j 3 1 = output 4 failed
Bit position Bit value and description
1 = Channel B active input
14 1 = Cannot lock to input B
13 1 = Cannot lock to input A
12 1 = Autoswitch occurred
10 1 = output 11 failed
9 1 = output 10 failed
8 1 = output 9 failed
6 1 = output 7 failed
5 1 = output 6 failed
4 1 = output 5 failed
Understanding Alarm Output
The Symmetricom 5087B automatically publishes alarms to the CNR port as they occur.
The alarms appear in the format ALARMabcde where abcde is the summary status of the input and output signals. The format of the alarm status is identical to the “S” command response defined in Table 2 on page 23.
Example: ALARM00003
This example shows that outputs 1 and 2 have active faults.
2 1 = output 3 failed
1 1 = output 2 failed
0 1 = output 1 failed
24 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Monitoring the Symmetricom 5087B 3
Checking Model Number and Software Version
Both commands are case sensitive. You do not need to type a carriage return or line feed.
To check the model number
Type: I
The system returns I5087B-00\r\n.
To check the software version
Type: V
The system returns Vxx\r\n where xx is the software version.
Example: V00.
Symmetricom 5087B Operations and Maintenance Manual Rev. E 25
3 Monitoring the Symmetricom 5087B
26 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Symmetricom 5087B Wideband Distribution Amplifier Operations and Maintenance Manual
4 Troubleshooting the Symmetricom 5087B
Replacing Fuses 28
Verifying Operational Problems 29
Perform all of the following procedures before returning the unit for service. For the Customer Assistance Center contact:
Worldwide (Main Number): 1-408-428-7907
USA, Canada, Latin America including Caribbean, Pacific Rim
including Asia, Australia, and New Zealand: 1-408-428-7907
USA toll-free: 1-888-367-7966 (1-888-FOR-SYMM)
Europe, Middle East & Africa: 49 700 32886435
www.symmetricom.com
The Symmetricom 5087B does not have any user-serviceable parts.
27
4 Troubleshooting the Symmetricom 5087B
Replacing Fuses
If you know that a local event caused blown fuses throughout a rack, you can replace the fuses in each Symmetricom 5087B power entry module.
Required for this procedure:
Small flat-head screwdriver
Replacement fuse for a standard IEC 320 power entry module with
fuse (5 x 20 mm, 1-amp, 250-volt fuse) (P/N 2110-0973)
To replace a fuse
1 Disconnect the power cable from the back of the Symmetricom
5087B.
2 Using a small screwdriver, open the fuse cover on the back of the
Symmetricom 5087B.
3 Replace the old fuses as necessary.
4 Close the fuse cover.
5 Reconnect the power cable to the back of the Symmetricom 5087B.
28 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Verifying Operational Problems
If the unit does not operate properly after you have verified that:
the correct power is applied to the rear of the Symmetricom 5087B
and
the fuses are good,
return the unit to Symmetricom, Inc. for repair.
Troubleshooting the Symmetricom 5087B 4
Symmetricom 5087B Operations and Maintenance Manual Rev. E 29
4 Troubleshooting the Symmetricom 5087B
30 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Symmetricom 5087B Wideband Distribution Amplifier Operations and Maintenance Manual
A Specifications
Directives 33
Electrical Specifications 34
Environmental Specifications 36
Physical Specifications 37
31
A Specifications
EC Declaration of Conformity
In accordance with EN 45014:1998
We Timing Solutions Corporation
Of 4775 Walnut Drive Suite 1B
Boulder, CO 80301 USA
declare that:
Equipment Wideband Distribution Amplifier
Model Number Symmetricom 5087B
Product Options None
in accordance with the following Directives:
73/23/EEC The Low Voltage Directive
and its amending directives
89/336/EEC The Electromagnetic Compatibility
Directive and its amending directives
has been designed and manufactured to the following specifications:
Safety: EN61010-1: 2001
Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use - Part 1: General Requirements
EMC EN61326-1: 2001
Electrical Requirements for Electrical Equipment for Measurement, Control and Laboratory Use - Part 1: General Requirements EN 55011 Class A Radiated Emissions
I hereby declare that the equipment named above has been designed to comply with the relevant sections of the above referenced specifications. The unit complies with all essential requirements of the Directives.
For technical assistance, contact the factory.
Signed by:
32 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Name: S.R. Stein Position: President
Done at Boulder, Colorado U.S.A on 27 January 2005
Directives
Specifications A
The Symmetricom 5087B unit is designed to comply with the following directives and standards.
Electromagnetic Compatibility 89/336/EEC
Council Directive on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive with amendments).
Safety 73/23/EEC
Council Directive on the harmonization of the laws of the Member States relating to electronic devices for use within certain voltage limits (LVD – Low Voltage Directive with amendments).
Standards
EN 61010-1
EN 61326-1, Class A
For more information, refer to the letter of conformance (US) or the declaration of conformity (EU) accompanying the product.
Symmetricom 5087B Operations and Maintenance Manual Rev. E 33
A Specifications
Electrical Specifications
Table 3 lists the electrical specifications for the Symmetricom 5087B.
Table 3 Electrical specifications
Item Specification
Protection Class Class I (Grounded Type)
Power Input 100 to 240 V~ 50/60 Hz
Fluctuations not to exceed ± 10% of nominal supply voltage.
Power Consumption STD:
70 W, 70 VA, 0.98 PF, 10 VAR
Power Inlet Type IEC 60320 sheet C14
Power Supply Cord Set 18 AWG (0.75 mm
Power Mains Fuse (2) 250V 2A T 5x20 mm (part number 2110-0973).
2
minimum)
Signal Input
Connectors
SSB Phase Noise (5–10 MHz)
Signal Output
Number: One
Impedance: 50 Ω
Amplitude: 0.3 to 3 Vrms, +2.6 to 22.6 dBm
Frequency Range: 1.0–10.0 MHz
Signal Type: Sine wave
Voltage Standing Wave Ration (VSWR): <1.5
Damage Level: +24 dBm
Input Status Front Panel Indicator: Level detect minimum 0.3 Vrms
Input: 1 BNC
Output: 12 BNC
Alarm: 1 BNC
Network: RJ-45
1 Hz: –110 dBc/Hz
10 Hz: –123 dBc/Hz
100 Hz: –128 dBc/Hz
1 kHz: –144 dBc/Hz
10 kHz+: –150 dBc/Hz
Number: 12
Amplitude: Adjustable, 0.75 to 3 Vrms, +10.5 to 22.6 dBm into 50 Ω
Frequency Range: 1.0–10.0 MHz
Signal Type: Sine wave
SWR: <1.5
Alarm Port
Remote Interface
34 Symmetricom 5087B Operations and Maintenance Manual Rev. E
1 BNC connector
Open collector TTL output with 10 kohm pull-up to 5 VDC
Active low
Ethernet (10Base-T)
RJ-45 connector
Table 3 Electrical specifications (Continued)
Item Specification
Specifications A
Harmonic Distortion (input and output 1 Vrms)
Spurious (input and output 1 Vrms)
Isolation Output to output
Output to input
<–40 dBc
<–80 dBc (10 Hz to 50 kHz)
< -104 dBc (typical) Output isolation is measured by injecting 900 Hz signal (0.5Vpp and 20us wide) into an output port and measuring the associated phase noise spur at 900 Hz offset on adjacent output ports and input port.
< -100dBc
Symmetricom 5087B Operations and Maintenance Manual Rev. E 35
A Specifications
Environmental Specifications
CAUTION
Table 4 Environmental specifications
Item Temperature Relative Humidity Altitude
In Use 0°C to 50°C 10% to 85% (non-condensing) 4,000 meters (15,000 ft)
Storage –62°C to 75°C 5% to 95% non-condensing)
Transportation –62°C to 75°C 5% to 95% non-condensing)
This unit is for INDOOR USE ONLY. It is not sealed to prevent moisture from entering the enclosure.
Pollution Degree 2 per EN61010-1
Installation (Over-Voltage) Category II for transient over-voltages
per EN 61010-1
Equipment suitable for continuous operation
Table 4 lists the environmental specifications for the Symmetricom
5087B.
36 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Physical Specifications
Table 5 lists the physical specifications for the Symmetricom 5087B.
Table 5 Physical specifications
Item Specification
Width 450 mm (Standard 19-inch rack mount)
Height 90 mm (Standard 2U rack)
Depth 370 mm (excluding connectors)
Weight Weight 6.2 kg; 6.5 kg with optional 020 or 021
Specifications A
Symmetricom 5087B Operations and Maintenance Manual Rev. E 37
A Specifications
38 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Symmetricom 5087B Wideband Distribution Amplifier Operations and Maintenance Manual
B Glossary
\n Line feed
\r Carriage return
CNR Command and Response
DHCP Dynamic Host Configuration Protocol
ESD electrostatic discharge
LED light-emitting diode
LSB least significant bit
MSB most significant bit
PDF portable document format
PWA printed wiring assembly
RF radio frequency
TTL transistor-transistor logic
39
B Glossary
40 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Index
A
accessing
Symmetricom 5087B system, 22
alarms
checking, 23 understanding, 24
assigning
gateway address, 18 IP address, 18 subnet mask, 18
C
cables
connecting, 14 required, 14
CE marking
symbol, 7
checking
alarms, 23 input frequency, 23 model number, 25 software version, 25 system status, 23
cleaning
a Symmetricom 5087B, 20
Command-And-Response Port
explained, 22
commands
system, 23
connections
Ethernet, 10, 14 input power, 10, 14 input signal, 10 input signals, 14 output signal, 10 output signals, 14
conventions, typographic, 9
D
DeviceInstaller software, 18 directives
electromagnetic compatibility, 33 safety, 33
E
electromagnetic compatibility
directive, 33
Ethernet
connecting, 14, 22 port, 10, 18, 22
F
fuse
replacing, 28 symbol, 7
G
gateway address
assigning, 18
I
input
connector, 10 LEDs, 10
input frequency
checking, 23
input plug
symbol, 7
input signals
connecting, 14 installing the Symmetricom 5087B, 14 IP address
assigning, 18
L
LAN
connecting, 14 LAN port
symbol, 7 Lantronix DeviceInstaller software, 18 Lantronix® Xport™. See Xport™. LEDs
input, 10
output, 10
power, 10
M
model number
checking, 25 monitoring
a Symmetricom 5087B, 22
N
network
connecting, 14
O
operational problems
verifying, 29
output
connectors, 10 LEDs, 10
output signals
connecting, 14
P
panels
front, 10 rear, 10
ports
Command-And-Response, 22 Ethernet, 22
power
connecting, 14 connector, 10 LED, 10
procedures
troubleshooting, 27
publishing
alarms, 24
R
replacing
a fuse, 28
S
safety
directive, 33
software version
checking, 25
specifications
electrical, 34 environment, 36 physical, 37
standards
applicable to Symmetricom 5087B, 33
subnet mask
assigning, 18
symbols, 7
Symmetricom 5087B Operations and Maintenance Manual Rev. E 41
Index
CE marking, 7 fuse, 7 input plug, 7 LAN port, 7
Symmetricom 5087B
accessing, 22 alarms, 24 cleaning, 20 command interface, 23 directives, 33 front panel, 10 installing, 14 monitoring, 22 overview, 10 rear panel, 10 required cables, 14 specifications, 34 standards, 33 unpacking, 14
system
commands, 23
system status
checking, 23
T
troubleshooting
procedures, 27
typographic conventions, 9
U
unpacking the Symmetricom 5087B, 14
W
warning, 7
symbol, 7
X
Xport™
Ethernet to RS-232 converter, 18 user manual, 18
42 Symmetricom 5087B Operations and Maintenance Manual Rev. E
Loading...