Symbol QRG 7875 User Manual

7875 Scanner/Scale
7875 Scanner / Scale
1999 SYMBOL TECHNOLOGIES, INC. All rights reserved. Symbol reserves the right to make changes to any product to improve reliability,
function, or design. Symbol does not assume any product liability arising out of, or in connection with, the
application or use of any product, circuit, or application described herein. No license is granted, either expressly or by implication, estoppel, or otherwise under
Symbol is a registered trademark of Symbol Technologies, Inc. Other product names mentioned in this manual may be trademarks or registered trademarks of their respective companies and are hereby acknowledged.
Symbol Technologies, Inc. One Symbol Plaza Holtsville, N.Y. 11742-1300
http://www.symbol.com
Quick Reference

Installation Steps

When installing the 7875 Scanner/Scale, follow the installation steps below. Skip step 4 if the unit does not have a scale.
1. Verify Checkstand Preparation, see page 1
- Checkstand Cutout
- Display Clearance
- Service Clearance
-Item Diverter
- Ventilation Requirements
- Electrical Wiring
- Cable Hole Requirements.
2. Connect the Cables, see page 7
- Power Supply
- Remote Display
- Interface Cables
- RS-232 Peripheral Cable.
3. Install 7875 in Checkstand, see page 10
- Set Communications Protocol Switch
- Put the 7875 in Checkstand Cutout
- Align the 7875 to the Checkstand.
4. Calibrate the Scale, see page 13
- Access Calibration Switch
-Exercise the Scale
- Perform Calibration
- Validate the Calibration
- Secure Calibration Switch.
5. Check the Scanner Operation, see page 20
- Modify Program Parameters
- Scan Valid Bar Code Tags.
1
7875 Scanner / Scale

Verify Checkstand Preparation

Checkstand Cutout 7875-1000/2000

C
D
I
H
DD CC
E B
ABCDE
7875-1000 Scanner
7875-2000 Scanner/Scale
29.51 cm 50.95 cm 3.49 cm 0.95 cm 43.97 cm 11 5/8 in. 20 1/16 in. 1 3/8 in. 3/8 in. 17 5/16 in.
30.63 cm 50.95 cm 3.49 cm 1.27 cm 43.97 cm 12 1/16 in. 20 1/16 in. 1 3/8 in. 1/2 in. 17 5/16 in.
FGHI
7875-1000 Scanner
7875-2000 Scanner/Scale
3.49 cm 13.0 cm 18.10 cm 18.42 cm 1 3/8 in. 5 1/8 in. 7 1/8 in. 7 1/4 in.
3.49 cm 13.0 cm 17.78 cm 18.42 cm 1 3/8 in. 5 1/8 in. 7 in. 7 1/4 in.
B E
C
A
*F
A
No electronics under 7875
F
* Recommended shelf to catch the 7875 if dropped during installation, although 7875 must not be supported by this shelf.
G
2
Quick Reference
Note: Dimension A for a 7875-2000 includes a spacer along
the side of the unit so that it fits an existing 7870-2000 cutout.

Checkstand Cutout – 7875-3000

D
H
G
D
C
E B
ABCD
29.51 cm 40.96 cm 3.49 cm 0.95 cm 11 5/8 in. 16 1/8 in. 1 3/8 in. 3/8 in.
EFGH
37.34 cm 12.54 cm 18.10 cm 18.42 cm 14 3/4 in. 4 15/16 in. 7 1/8 in. 7 1/4 in.
C
No electronics under NCR 7875
B
A
A
F
Note: The 7875-3000 must sit on a shelf below the checkstand
surface. The shelf should be open at the front and back.
3
7875 Scanner / Scale
t

Display Clearance

50
30
This area must b e clea r for viewing optional integrated display.
60

Service Clearance

Mounting surface for keyboard mus be removable for servicing and vertical window replacement.
B
A
All Installations
A
8.0 in. (20.3 cm) minimum if checkstand structure is not removable for servicing. 1.0 in. (2.5 cm) minimum if checkstand structure is re­movable for servicing.
B
14.0 in. (35.6 cm) minimum if checkstand structure is not removable for servicing. 7.0 in. (17.8 cm) minimum if checkstand structure is re­movable for servicing.
C
5.1in. (13.0 cm) minimum clearance to closest checkstand panel.
7875
must not be supported by this panel.
A
Installations Without Integrated Display
60
C
The
4
Quick Reference

Item Diverter

7.25 in. (18.4 cm)
Item Diverter (Must be removable to service Scanner/Scale in checkstand)

Ventilation Requirements

The 7875 Scanner/Scale is designed to operate without an exhaust fan in the checkstand; however, there must be adequate convection airflow. The ambient temperature inside the checkstand cannot be higher than 104° F (40° C). Also, the ambient temperature inside the checkstand cannot be higher than 12.6° F (7° C) above the ambient temperature outside the checkstand. For example, if the ambient temperature outside the checkstand is 76° F (24.4° C), the ambient temperature inside the checkstand cannot be greater than
88.6° F (31.4° C). If the checkstand contains other heat producing equipment, you may need to use forced air to keep the temperature within the specified range. However, air coming into or leaving the checkstand
MUST NOT
enter or exit past the 7875 Scanner/Scale.
5
7875 Scanner / Scale

Electrical Wiring to the Checkstand

Input Voltage
Neutral and Ground Bus
L3
Main Service Panel
N
G
Conduit
Circuit A: Checkstand
Note:
Feeder wiring and insulated ground from main service panel to distribution panel to be run in metal conduit.
Belt Control
Lighting
Misc. equip.
The electrical wiring must meet all electrical codes, laws and regulations.
Motor
Checkstand Frame
Belt
Isolated/Insulated Ground Bus
Neutral Bus
Distribution Panel
L2
L1
Circuit Breakers
Symbol circuits should be run in separate metal conduits.
Note:
Circuit B: Terminal
Circuit C: Scanner/Scale
Receptacle should be easily assessible and near the Scanner/Scale.
Isolated Ground Receptacles
Symbol circuits must be dedicated to Symbol equipment or other logically connected electronic equipment (modems, DAA, bridges, etc.)
Installation Type Input Voltage L1, L2 Circuit Breakers
U.S., Canada, Japan International 220 VAC to
100 VAC to 120 VAC
240 VAC
100 VAC to 120 VAC
220 VAC to 240 VAC
Standard single-pole; value determined by type of device branch and by electrical code.
European 220 VAC 220 VAC European double-pole.
6
Quick Reference
Note: The 7875 outlet in the checkstand must be connected to
a circuit breaker switch. This switch must be located close to the operator and is used as the On/Off switch for the 7875.

Hole Requirements for Cables

To run the various cables through the checkstand, you may need to drill holes in some of the panels. The holes must be large enough for the connector on one end of the cable to pass through. Ensure there are no sharp edges to cut the cable. The following table gives the minimum hole size for each of the 7875 cables.
Cable Cable Length Minimum Hole Size
Power Cord – Outlet to Power Supply
Power Cord – Power Supply to the 7875
Interface Cable 8.0 m (26.24 ft.)
Remote Display Cable 8.0 m (26.24 ft.)
3.05 m (10 ft.) 3.18 cm (3/4 in.)
1.22 m (4 ft.) 1.52 cm (1/2 in.)
1.90 cm(3/4 in.)
4.0 m (12.12 ft.)
4.0 m (12.12 ft.)
1.90 cm (3/4 in.)
1.90 cm (3/4 in.)
1.90 cm (3/4 in.)

Connect the Cables

There are several cables associated with the 7875, some required with every installation and some optional, depending on the system. Make sure you have all the necessary cables for your installation. Connect the cables according to one of the following two illustrations.
7
7875 Scanner / Scale

Single Cable Installation

AC Power Cord
Power Supply
DC Power Cable
Remote Display
Check switch settings
C
R
Y
E
D
E
T
A L
O
W
P
M
O
E
IS
P
R
D
R
X
E
A
N
M
N A
A
C
5
S
V 5
7875 Scanner/Scale
Interface Cable
Host Terminal
DUAL PERIPHERAL PORTS
PORT 1
PORT 2
RS-232 Peripheral
8
Quick Reference

Dual Cable Installation

AC Power Cord
Power Supply
DC Power Cable
Remote Display
Chec k switch sett ing s
C
Y
R
E
D
T
E
A L
O
W
P
M
O
IS
E
P
D
R
Scanner Interface Cable
X A M
A 5
V 5
/
R
T
E
R
N
O
N A
P
C
X
S
U A
7875 Scanner/Scale
Scale Interface Cable
Host Terminal
DUAL PERIPHERAL PORTS
R K H
C A T A D
PORT 1
PORT 2
RS-232 Peripheral
9
7875 Scanner / Scale

RS-232 Peripheral Cables

The cable on some RS-232 hand-held peripheral devices is not long enough to connect to the 7875 (under the checkstand) and still permit easy use of the device. In these cases, Symbol recommends installing an extension cable. You can obtain one from Symbol or you can make your own. If you make your own, it should be approximately 39 inches (1 meter) long with 8-pin phone type connectors on each end.
J1 P1
J1 Wire Number P1
111
222
333
444
555
666
777
888

Install 7875 in Checkstand

Set the Communications Protocol Switch

Before setting the 7875 into the cutout in the checkstand, verify that the Communications Protocol Switch is properly set. Single cable units have one switch, dual cable units have two. The switches are located on the Interface Board and you can access them through holes in the side of the unit. For RS-232 communications, both switches must be toward the front (operator side) of the unit. For all
10
Quick Reference
other communication protocols, both switches must be toward the back (customer side) of the unit.
AUX PORT/ DATACHKR
DATACHKR OCIA/IBM
RS-232 RS-232
Make sure power is off before changing switch setting
Switches
SCANNER

Installing 7875 into Checkstand Cutout

Grasp the 7875 Scanner/Scale and lower it into the checkstand cutout. Be careful not to damage any of the cables. After the unit is properly sitting on its supports, install the Top Plate.
Note: It is important that the 7875 does not rock on its sup-
ports. Make sure all adjustable supports are securely fastened and that the 7875 is sitting on all supports.
11
7875 Scanner / Scale

Align the 7875 to the Checkstand

The leading edge of the Top Plate must be flush or up to 1/16 in. (0.15 cm) below the top of the checkstand. The trailing edge of the Top Plate must be flush or up to 1/16 in. (0.15 cm) above the top of the checkstand.
Note: The four adjustable support posts on the Scale Hinge
Assembly are set at the factory. Do not attempt to adjust the Top Plate using these posts. Adjust the 7875 sup­ports to align the Top Plate with the checkstand.
If the Top Plate is properly aligned with the checkstand, an item should easily slide from the checkstand onto the Top Plate and then from the Top Plate onto the checkstand. The following illustration shows this alignment.
12
Loading...
+ 30 hidden pages