SurgeX UPS-1000-OL, UPS-2000-OL, UPS-3000-OL Users Manual

Standalone Battery Backup
© 2016 AMETEK Electronic Systems Protection. All rights reserved. (PC v1.0)
Protect your investment with a comprehensive backup solution
Battery Backup
SurgeX offers a complete UPS product line to meet your battery backup needs. Available in multiple configurations, our standalone UPS solutions provide backup power to keep equipment running and properly shut down critical systems in the event of a power outage.
Reliable battery backup is possible. No matter what your industry, we have a premium standalone UPS solution for you.
Also available in a bundled solution with our SurgeX surge elimination technology rack mount product line to provide comprehensive protection for connected equipment.
Features:
Online, double-conversion Uninterruptible
Power Supply
True sinewave output
Controllable receptacles
Configurable as tower or 19” rack
Hot swappable-user replaceable
battery trays
Intuitive LCD screen
UPS monitoring software
Optional SNMP card available
3 Year Product Warranty
3 Year Battery Warranty
Model Number Description
UPS-1000-OL
UPS-2000-OL
UPS-3000-OL
Plug Configuration
Input
NEMA 5-15P
NEMA 5-20P
NEMA L5-30P
Output
(3x) NEMA 5-15R
Direct
(3x) NEMA 5-15R
Programmable
(2x) NEMA 5-20R
(1x) NEMA L5-20R
Direct
(2x) NEMA 5-15R
Programmable
(2x) NEMA 5-20R
(1x) NEMA 5-30R
(1 foot cord) Direct
(2x) NEMA 5-20R
Programmable
120V/15A, 1000 VA, Online, 2U
120V/20A, 2000 VA, Online, 2U
120V/30A, 3000 VA, Online, 2U
Standalone Battery Backup
© 2016 AMETEK Electronic Systems Protection. All rights reserved. (PC v1.0)
Battery Backup
Technical Specifications
Power Rating
Topology
Heat Dissipation (BTU/Hour)
Input Voltage (Nominal) Range
Input Frequency
Input Power Factor
Input Current THD
Efficiency
Output Voltage
Output Current
Voltage Regulation
Overload Online Mode
Overload Battery Mode
Overload Bypass Mode
Battery Voltage (Float / Nominal)
Charger Current
Backup Time (Full Load)
Communications Interface
Shipping Weight
Unit Weight
Length
Height
Depth
UPS-1000-OL UPS-2000-OL UPS-3000-OL
1000 VA / 900 W
On-Line Double Conversion
520 at 100% Load
100-120 VAC 90-150 VAC
50/60 Hz ±4 (Auto Sense on Start-Up)
>0.95
<9.0%
>84.0%
120 VAC (Default) 100/110/115 VAC (Selectable)
8.3 A (Default)
10.0/9.1/8.7 A (Selectable)
±1.0%
100-105%: Continuous; Warning Only 105-130%: 2 Minutes 130-200%: 10 Seconds >200%: 250 Milliseconds
100-105%: Continuous; Warning Only 105-130%: 10 Seconds >130%: 250 Milliseconds
100-110%: Continuous; Warning Only 110-120%: 30 Minutes 120-130%: 10 Minutes >130%: 1 Minute
27.4/24.0 VDC
1.0 A
>3.5 Minutes
USB / RS-232
47.0 lbs. / 21.4 kg.
38.0 lbs. / 17.3 kg.
17.25 in / 438 mm
3.39 in / 86 mm
16.26 in / 413 mm
2000 VA / 1800 W
On-Line Double Conversion
1171 at 100% Load
100-120 VAC 105-150 VAC
50/60 Hz ±4 (Auto Sense on Start-Up)
>0.95
<9.0%
>84.0%
120 VAC (Default) 100/110/115 VAC (Selectable)
16.7 A (Default)
20.0/18.2/17.4 A (Selectable)
±1.0%
100-105%: Continuous; Warning Only 105-130%: 2 Minutes 130-200%: 10 Seconds >200%: 250 Milliseconds
100-105%: Continuous; Warning Only 105-130%: 10 Seconds >130%: 250 Milliseconds
100-110%: Continuous; Warning Only 110-120%: 30 Minutes 120-130%: 10 Minutes >130%: 1 Minute
54.7/48.0 VDC
1.0 A
>3.6 Minutes
USB / RS-232
75.5 lbs. / 34.3 kg.
65.0 lbs. / 29.5 kg
17.25 in / 438 mm
3.39 in / 86 mm
20.20 in / 513 mm
3000 VA / 2700 W
On-Line Double Conversion
1756 at 100% Load
100-120 VAC 105-150 VAC
50/60 Hz ±4 (Auto Sense on Start-Up)
>0.95
<9.0%
>84.0%
120 VAC (Default) 100/110/115 VAC (Selectable)
25.0 A (Default)
30.0/27.3/26.1 A (Selectable)
±1.0%
100-105%: Continuous; Warning Only 105-130%: 2 Minutes 130-200%: 10 Seconds >200%: 250 Milliseconds
100-105%: Continuous; Warning Only 105-130%: 10 Seconds >130%: 250 Milliseconds
100-110%: Continuous; Warning Only 110-120%: 30 Minutes 120-130%: 10 Minutes >130%: 1 Minute
82.1/72.0 VDC
1.0 A
>3.6 Minutes
USB / RS-232
105.0 lbs. / 47.4 kg.
81.0 lbs. / 36.8 kg.
17.25 in / 438 mm
3.39 in / 86 mm
24.92 in / 633 mm
Loading...