SurgeX UPS-1000-OL, UPS-2000-OL, UPS-3000-OL Users Manual

Online Battery Backup
User Manual
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com / UM-UPS-Standalone-Rev-B
UPS-1000-OL -
1000 VA UPS
UPS-2000-OL -
2000 VA UPS
UPS-3000-OL -
3000 VA UPS
Table of Contents
1. Introduction
1
1.1 Technical Support
1
1.2 FCC Compliance
1
1.3 Safety Compliance
1
1.4 About This Manual
1
1.5 Safety
2
1.5.1 Safety Intended Use
2
1.5.2 General Warnings
2
1.5.3 Safety Notices
2
1.5.4 Battery Safety
4
1.5.5 Repacking of Unit
4
2. Overview 5
2.1 UPS Devices and Batteries 5
2.2 Packing List 5
2.3 Storage 5
2.4 Recharging the UPS During Storage 6
2.5 Environmental Conditions 6
2.6 Floor Loading 6
2.7 Ventilation 6
2.8 Rear Panel View 7
2.8.1 Model: UPS-1000-OL 7
2.8.2 Model: UPS-2000-OL 7
2.8.3 Model: UPS-3000-OL 7
2.9 LCD Display ................................................................................................................................................. 8
2.9.1 Rack Display.............................................................................................................................................. 8
2.9.2 Tower Display 8
2.10 LCD: Display and Functional Description ................................................................................................. 9
3. Installation 10
3.1 Tower Installation 10
3.2 Rack Installation 11
3.2.1 Assembly Steps 11
3.3 Electrical Preparations 13
3.3.1 Battery Connections 13
4. Setting Up UPS Parameters 15
4.1 Factory Default Settings 15
4.2 Changing Default Settings 15
4.2.1 Output Voltage Setting (item 01) 16
4.2.2 Frequency Converter Enable/Disable (item 02) 16
4.2.3 Output Frequency Setting (item 03) 17
4.2.4 Bypass Mode Enable/Disable when the UPS is off (item 06) 17
4.2.5 Programmable Outlets Enable/Disable (item 07) 17
4.2.6 Programmable Outlets Setting (item 08) 18
4.2.7 LCD Display Direction Setting (item 09) 18
4.2.8 Acceptable Input Voltage Range Setting (item 10) 18
4.2.9 Number of External Battery Packs (item 11) 18
5. UPS Operation
19
5.1 UPS input connection
19
5.1.1 LCD Display in Bypass Mode
19
5.1.2 LCD Display in Standby Mode
19
5.2 Turn on the UPS (Put the UPS in OnLine Mode)
20
5.2.1 LCD Display in OnLine Mode
20
5.3 Connect Devices to the UPS
20
5.4 The UPS in Battery Mode
21
5.4.1 LCD Display in Battery Mode
21
5.5 Turn off the UPS
21
6. Interfaces 22
6.1 Serial Interface COM 3 22
6.2 Interface Slot COM 22
7. Emergency Power Off (EPO) 23
8. Maintenance 23
8.1 Cleaning 23
8.2 UPS Storage 23
8.3 Battery Testing 23
8.4 Replacing Batteries 24
9. Troubleshooting 27
9.1 Troubleshooting Table 27
9.2 Audible Alarm 29
9.3 LCD Display Abbreviation Index 29
9.4 Warning Indicators 30
9.5 UPS Fault 31
9.5.1 LCD Display in Fault Mode 31
9.5.2 Fault Reference Code 31
10. Appendix A: Specifications 32
10.1 SURGEX UPS (100 - 120 Volt UPS) Specifications 32
10.2 Extension battery packs for use with SurgeX UPS’s 38
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 1

1. Introduction

Thank you for selecting this uninterruptible power supply (UPS). SurgeX offers the most reliable protection from the harmful effects of electrical line disturbances for your computing and communications equipment.
1.1 Technical Support
Tel: (800) 645-9721 Email: Order.desk@ametek.com
Please check with technical support before attempting to repair or return any UPS product. If a UPS needs repair or replacement, technical support will issue a return material authorization (RMA) number along with instructions on how to return the UPS.
1.2 FCC Compliance
ATTENTION: Changes or modifications to this unit not expressly approved by the party responsible
or in FCC compliance could void the user’s authority to operate the equipment.
The 700-3kVA models have been tested and comply with the limits for a Class A digital device,
pursuant to Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the UPS is operating in a commercial environment. The UPS generates, uses, and can radiate radio frequency energy. If installation and use is not in accordance with the instruction manual, it may cause harmful interference to radio communications.
1.3 Safety Compliance
UL/cUL listing to UL1778, 4th Edition CE CAN/CSA C22.2 No 170.3-05, 2nd Edition
1.4 About This Manual
This manual contains information regarding the installation, operation, and maintenance of the uninterruptible power supply (UPS).
The following symbols are used in this manual:
ATTENTION: Indicates instructions, which if not observed, may endanger reliability of your UPS or
security of your data.
CAUTION: Indicates instructions, which if not observed, present risk of electric shock, may endanger
your life, your health, reliability of your UPS or the security of your data.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 2
1.5 Safety
1.5.1 Safety Intended Use
·
This device serves as an uninterruptible power supply for connected loads. The device is in compli-
ance with all relevant safety regulations concerning information technology equipment for use in an office environment.
·
Depending on the type and rating of UPS device, certain configurations of battery extensions may be connected. These battery extensions may only be connected to the compatible basic UPS unit.
1.5.2 General Warnings
CAUTION: The manufacturer considers the safety of personnel to be of paramount importance. For
this reason, it is essential that procedures relating to safety in this manual be carefully reviewed before commencing work, and properly adhered to later. The user or operator may intervene in the operation of the UPS provided that the instructions laid out in Section 3 “Installation” are strictly followed.
CAUTION: Even when all switches and/or circuit breakers are open, dangerous voltages are
present within this unit! There are no user-serviceable parts inside. Only factory authorized
technical personnel may carry out any operation that requires protection panels to be opened and/or removed. Any repairs or modifications by the user may result in out-of-warranty repair charges, unsafe electrical conditions, or violation of electrical codes.
1.5.3 Safety Notices
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
CAUTION: SAVE THESE INSTRUCTIONS - This Manual Contains Important Instructions that
should be followed during installation and maintenance of the UPS and batteries.
·
Temperature Rating - Units are acceptable for use in a maximum ambient of 40 °C (104°F).
·
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall be easily accessible.
CAUTION: To reduce the risk of fire, connect model UPS-3000-OL only to a circuit provided with 30 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70.
CAUTION: To reduce the risk of fire, connect models UPS-1000-OL and UPS-2000-OL only to a
circuit provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 3
·
The units are heavy. Lifting the units into the rack requires a minimum of two people.
·
When installing units in racks, do not allow racks to become “top heavy”. Install heaviest equip-
ment (typically the external battery pack) near bottom of rack, and install this equipment before installing equipment higher in the rack.
·
This equipment services power from more than one source. The output terminals and/or receptacles
may have voltage present even when the unit is unplugged. UPS’s present a different safety issue
than most electrical equipment because unplugging the UPS puts it into battery mode. Unplugging the UPS does not remove the electrical charge.
·
The UPS must be connected to an earthed mains outlet-socket.
·
When installing the equipment, ensure that the sum of the leakage current of the UPS and the con-
nected devices does not exceed 3.5mA.
·
Make sure that no objects (e.g. pins, necklaces, paper clips, etc.) get inside the device. In emergen­cies (e.g. damaged case, controls or power cables, penetration of liquids or foreign matter) switch off the device and contact technical support for assistance.
·
Transport the unit only in suitable packaging (protected against jolts and shocks).
·
If the equipment is moved from a cold environment to a warmer operation location, condensation
may occur. Before you switch on the equipment it must be absolutely dry. An acclimatization pe­riod of at least two hours is required.
·
Place all cords so that nobody can stand on or trip over them. When connecting the device to
the power supply, follow the instructions in Section 3 “Installation”.
·
Do not connect equipment that will overload the UPS or demand DC-current.
·
When cleaning the unit, follow the instructions in Section 8 “Maintenance”.
·
Emergency power off (EPO) is located on the rear of the unit (see Section 2.7 “Rear Panel View”).
When this connection is open, the logic circuit will immediately shut down the UPS output.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 4
1.5.4 Battery Safety
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
CAUTION: The batteries installed in the UPS and within the extended battery packs contain
electrolyte. Under normal conditions the containers are dry. A damaged battery may leak electrolyte that can be dangerous when in contact with the skin and cause irritation to the eyes. Should this happen, wash the affected part with copious amounts of water and seek immediate medical attention.
·
Voltage is always present on the battery terminals.
·
Even when discharged, a battery has the capacity to supply a high short circuit current, which in
addition to causing damage to the battery itself and to associated cables, may expose the operator to the risk of burns.
·
Batteries should not be kept in storage for periods exceeding 6 months at 25°C without being re-
charged (having been charged to 100% at the beginning of any such period). If these conditions are not respected, the performance of the battery can no longer be guaranteed. It is advisable to recharge the batteries at least once every 4 months.
·
Since new batteries often do not provide full capacity after an initial charge, it may be necessary to
carry out a number of discharge/recharge cycles before optimum performance is achieved.
·
In order to protect the environment, batteries must be disposed of in accordance with the regulations
governing disposal/recycling of toxic and harmful waste.
1.5.5 Repacking of Unit
Do not pack equipment until at least two (2) hours have elapsed since the last recharge.
Place the equipment in bags made of material sufficiently porous to allow it to breathe (e.g. 100μm polyethylene).
Do not remove air from the packaging.
When packing the unit for movement by common carrier, place in original or equivalent packaging container.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 5

2. Overview

NOTE: The equipment has been thoroughly checked before shipment. Upon receipt, check the packaging and en-
sure that the contents are undamaged and that no items are discarded. Any damage must be reported to the shipper and any missing parts must be reported to the supplier immediately. Please keep the original package in a safe place for future use.
2.1 UPS Devices and Batteries
The following table provides an overview of the various versions of the device:
SurgeX UPS Model
Battery Pack Model
UPS-1000-OL
UPS-BPX-1000
UPS-2000-OL
UPS-BPX-2000
UPS-3000-OL
UPS-BPX-3000
2.2 Packing List
Unpack the package and check the package contents. The shipping package contains:
2.3 Storage
If the UPS is to be stored prior to use, it should be stored in a clean, dry environment and away from temperature extremes. It is recommended that the equipment be stored in a temperature controlled, moderate humidity environ­ment. The table below provides the temperature and humidity storage limits:
Storage Data
Temperature Limits
32°F to 104°F (0°C to +40°C)
Relative Humidity (Non-Condensing)
0% to 90%
NOTE: When storing equipment, every 8°C above 25°C reduces the shelf life of the battery by 50%. More frequent battery charging is required to maintain the batteries in storage at these greater temperatures.
UPS Shipping Package
1.
One UPS
2.
One User Manual
3.
Mounting Ears
4.
Two Sets of Tower Stands (Feet)
5.
Rail Kit
6. USB Cable
Optional Extended Battery Pack
1.
One Battery Pack
2.
One Battery Cable
3.
Mounting Ears
4. Two Sets of Tower Stands (Feet and Extensions)
5.
Rail Kit
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 6
2.4 Recharging the UPS During Storage
Before storing, charge the UPS for five hours. During storage, recharge the battery in accordance with the follow­ing table:
Storage Temperature
Recharge Frequency
Charging Duration
-13°F to 104°F (-25°C to +40°C)
Every 3 Months
1-2 Hours
104°F to 113°F (40°C to +45°C)
Every 2 Months
1-2 Hours
2.5 Environmental Conditions
The UPS must be installed on a level and even surface. Install in an area protected from extremes of temperature, water, humidity and the presence of conductive powder or dust. Do not stack units and do not place any objects on top of a unit.
The functional temperature range of the UPS is 32°F to 104°F (0°C to +40°C).
The ideal ambient temperature range is 60°F to 77°F (15°C to 25°C).
Expected battery runtimes and battery life is based on operational temperatures between 68°F and 77°F (20°C and 25°C). Operation of the equipment above 77°F (25°C) reduces the service life of the batteries dramatically.
2.6 Floor Loading
Taking into consideration the weight of the UPS, extended battery packs, and any other equipment that may be mounted in an associated rack. Confirm that the floor chosen location is capable of supporting the weight of the combined units.
2.7 Ventilation
It is necessary to leave a minimum space of at least two inches (50 mm) in front and rear of the UPS to allow a flow of air.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 7
2.8 Rear Panel View
2.8.1 Models: UPS-1000-OL
2.8.3 Model: UPS-3000-OL
2.8.2 Model: UPS-2000-OL
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 8
2.9 LCD Display
2.9.1 Rack Display
2.9.2 Tower Display
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 9
2.10 LCD: Display and Functional Description
Display
Function
Backup time information
Indicates the backup time.
Indicates the backup time. H: hours, M: minutes
Warning & Fault information
Indicates that a warning and/or fault has occurred.
Indicates the warning and fault codes. The codes are listed in sections 9.4 and 9.5.
Setting Operation
Indicates the setting information.
Input/Output & Battery information
Indicates the input/output voltage, input/output frequency, and
battery voltage. V: voltage, Hz: frequency
Load information
Indicates load level by 0-25%, 26-50%, 51-75% and 76-100%.
Indicates overload.
Indicates that the load or the UPS output is short circuited.
UPS Status
Indicates that the programmable outlets are working.
Indicates that the UPS is in on-line mode.
Indicates that the UPS is in converter mode.
Indicates that the UPS is in bypass mode.
Indicates that the UPS alarm is disabled. Indicates that the battery charger is working.
Battery information
Indicates the battery level by 0-25%, 26-50%, 51-75%, and 76 ­100%.
Indicates low battery.
Indicates that there is something wrong with the battery.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 10

3. Installation

The UPS and external battery pack are designed to be rack-mounted in four post frames or to be floor standing in a tower configuration.
3.1 Tower Installation
ATTENTION: Use all supplied mounting hardware on each UPS and extended battery pack.
A. To install standalone, refer to the figure directly below:
Assemble two feet as one tower stand. Align the two stands. Put the UPS module in the stands.
B. To install a UPS module and one extended battery pack, refer to the figure directly below :
Assemble two feet each with an extension as one tower stand. Align the two stands. Put the UPS module and external battery pack in the stands.
NOTE: When installing the UPS or external battery pack with feet, please keep both feet a distance of 2.75in (70mm) from the edge of the unit. See figure below:
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 11
3.2 Rack Installation
The UPS and the external battery packs are designed to be rack-mounted in four post frames. The UPS and ex­ternal battery pack use identical mounting hardware and procedures.
NOTE: The rack-mount UPS draws air from the front. If the rack has a door on the front, make sure that there is some clearance between the UPS vents and the rack door.
Because of the weight of these units, two people are recommended to lift and hold into position while all fasteners are secured. Please use the supplied fasteners to attach the supplied mounting brackets to the UPS or external bat­tery pack.
If external batteries are included in your installation, please mount them first and as low as possible. Start with the lowest available position and work up. Your UPS should be installed last and end up on the top of all the battery packs for proper cable routing.
ATTENTION: Use all supplied mounting hardware on each UPS and external battery pack.
NEVER depend on lower devices to support other devices.
Included in each rack-mount carton is a rail kit. The rail kit consists of the following components:
3.2.1 Assembly Steps
Step 1: Use four M6 screws to mount the right and left rail sliders to the two front posts of the four-post rack.
Refer to the figure directly below:
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 12
Step 2. Use four M6 screws to mount the right and left rail sliders to the two back posts of the four-post rack.
Refer to the figure directly below:
Step 3. Insert one M6 nut into the right and left front posts of the four-post rack for a 2U installation.
Refer to figure directly below:
Step 4. Install UPS alone.
Add mounting ears to both sides of the unit and refer to figure directly below:
Step 5. Install UPS and external battery pack.
Refer to figure directly below:
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 13
3.3 Electrical Preparations
CAUTION: Before connecting any input wiring to the UPS, take precautions to ensure that all cir-
cuits being used are the proper voltage and current required for the UPS.
CAUTION: UPS output receptacles are energized when the UPS is connected to the mains and the
bypass is enabled.
CAUTION: Electrical shock hazard. Even when the UPS is disconnected from the mains, hazardous voltages may still exist at the output receptacles of the UPS. The UPS receives power from more than one source - AC input and DC input from batteries. All input sources (AC and DC) must be discon nected before carrying out maintenance work inside the UPS.
3.3.1 Battery Connections
CAUTION: Column one in the table below lists each of the UPS models and column two displays the
corresponding model of the extended battery pack which must be used with the UPS. DO NOT USE any other extended battery pack for the corresponding UPS.
UPS Model
Battery Pack Model
UPS-1000-OL
UPS-BPX-1000
UPS-2000-OL
UPS-BPX-2000
UPS-3000-OL
UPS-BPX-3000
CAUTION: Before connecting a battery pack to the UPS, the circuit breaker of the battery pack must
be switched to “OFF”. After electrical connection with the UPS is established, the breaker must be
switched to “ON”.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 14
NOTE: Each battery pack contains two battery connectors. The first battery pack is connected to the UPS using the cable supplied with the pack. Each additional extension battery pack is connected by attaching its cable to the previous pack. Refer to the figure below.
If additional battery packs (up to 4) are to be used, they should be connected prior to connecting the UPS to the input power. To connect external battery packs, follow the steps below:
1. Set the circuit breaker to the “OFF” position.
2. Remove the battery connector cover from the UPS.
3. Remove the battery connector cover from the extended battery pack.
4. If there are multiple extended battery packs, remove the additional battery connector covers. If not, proceed
to Step 5.
5. Connect the supplied battery cable to the extended battery pack.
6. Connect the other end of the battery cable to the UPS.
7. For multiple extended battery packs, connect the supplied battery cables as shown in the figure below.
8. Set the circuit breaker to the “ON” position.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 15

4. Setting Up UPS Parameters

4.1 Factory Default Settings
The UPS is shipped with the following default factory settings. Refer to the table below and also to the table “LCD
Display Abbreviation Index” in Section 9.3.
PARAMETER
FACTORY DEFAULT SETTING
100 - 120 Volt Models
Output Voltage
120
Frequency Converter
DIS
Output Frequency
60
Bypass Mode
ENA
Programmable Outlets
DIS
Programmable Outlets Backup Time Setting
2
LCD Display Direction Setting
RAC
Acceptable Input Voltage Range Setting
85-135
Number of External Battery Packs
0
If the factory default settings are acceptable, proceed directly to Section 5 “UPS OPERATION”. To change any of the default settings proceed directly to Section 4.2 “Changing Default Settings”.
4.2 Changing Default Settings
Plug the input of the UPS into a two-pole, three-wire, grounded receptacle. Avoid using extension cords. If the
mains voltage is within the acceptable range, the UPS will enter bypass mode. “BYPASS” will be displayed in the
UPS status window on the LCD display.
LCD Display in Bypass Mode
Rack Display
NOTE: The LCD will display the actual input voltage in the input/output and battery window.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 16
1. Press and hold the “SELECT” button for at least five seconds to enter the UPS setting mode.
2. Press the “UP” or the “DOWN” button to scroll thru all of the parameters itemized as (01, 02, 03, 06, 07, 08,
09, 10 and 11).
3. When you see the item of the parameter that you want changed press the “LEFT ARROW” button. In the
“Setting Operation” window on the LCD display the item will blink depending on the selected parameter.
4. Press the “UP” or the “DOWN” button to scroll thru all of the available settings for that parameter.
5. When you see the setting that you want for that parameter press the “LEFT ARROW” button to choose
that setting.
6. To exit the UPS setting mode press the “UP” or “DOWN” button and scroll to the ESCAPE function (item 00).
7. Press the “LEFT ARROW” button.
4.2.1 Output Voltage Setting (Item 01)
Interface
Setting
The following output voltage can be chosen for on-line mode operation: 100 - 120 Volt Models
100: Output Voltage is 100VAC 110: Output Voltage is 110VAC 115: Output Voltage is 115VAC 120: Output Voltage is 120VAC
4.2.2 Frequency Converter Enable/Disable (Item 02)
Interface
Setting
ENA: frequency converter mode is enabled. When the input frequency is at or between 40Hz to 70Hz the output frequency will be constant and equal to the value (50 Hz or 60Hz) chosen in section 4.2.3 and the output voltage will be constant and equal to the value chosen in section 4.2.1. The bypass will be disabled in this mode.
DIS: converter mode is disabled. The output frequency is equal to the input frequency and the output voltage will be equal to the value chosen in section
4.2.1.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 17
4.2.3 Output Frequency Setting (Item 03)
Interface
Setting
You may set the initial frequency on battery mode: 50: output frequency is 50Hz 60: output frequency is 60Hz
If converter mode is enabled, the following output frequency can be chosen: 50: output frequency is 50Hz 60: output frequency is 60Hz
4.2.4 Bypass Mode Enable /Disable when the UPS is off (Item 06)
Interface
Setting
ENA: Bypass mode is enabled when the UPS is turned off. When the UPS is first plugged in, it will enter bypass mode, or if the UPS is in on-line mode and then turned off, it will enter bypass mode.
DIS: Bypass mode is disabled when the UPS is turned off. When the UPS is first plugged in, it will enter standby mode with no output, or if the UPS is in on-line mode and then turned off , it will enter standby mode with no out­put.
4.2.5 Programmable Outlets Enable /Disable (Item 07)
Interface
Setting
ENA: Programmable outlets are enabled. When the UPS goes to Battery mode the programmable outlets will supply power to the connected load for a duration equal to the timer setting in section 4.2.6 or until the battery be­comes depleted, whichever occurs first.
DIS: Programmable outlets are disabled. When the UPS goes to battery mode the programmable outlets will supply power to the connected load until the battery becomes depleted.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 18
4.2.6 Programmable Outlets Setting (Item 08)
Interface
Setting
0-999: Backup time in minutes that programmable output receptacles will operate in battery mode.
4.2.7 LCD Display Direction Setting (Item 09)
Interface
Setting
RAC: the LCD display is horizontal. TOE: the LCD display is vertical.
4.2.8 Acceptable Input Voltage Range Setting (Item 10)
Interface
Setting
Display alternates between low and high voltage of the range. The following acceptable input voltage range may be chosen:
4.2.9 Number of External Battery Packs (Item 11)
Interface
Setting
The following number of external battery packs can be chosen: 0: No External Battery Pack. 1: One External Battery Pack. 2: Two External Battery Packs. 3: Three External Battery Packs. 4: Four External Battery Packs.
100 - 120 Volt Models
85/135: 85-135 V Input Range
80/130: 80-130 V Input Range
55/150: 55-150 V Input Range
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 19

5. UPS Operation

5.1 UPS Input Connection
Plug the input of the UPS into a two-pole, three-wire, grounded receptacle. Avoid using extension cords.
ATTENTION: This UPS is supplied with standard power cords and receptacles suitable for use in
your area of operation. It may be installed and operated by non-technical personnel.
If the mains voltage is within the acceptable range, and the bypass is enabled the UPS will enter bypass mode.
“BYPASS” will be displayed in the UPS status window on the LCD display. See Section 5.1.1 “LCD Display in
Bypass Mode”.
If instead the bypass is disabled, the UPS will enter standby mode. In this mode the UPS will not supply output power to the load. See Section 5.1.2 “LCD Display in Standby Mode”.
5.1.1 LCD Display in Bypass Mode
Rack Display Tower Display
5.1.2 LCD Display in Standby Mode
Rack Display Tower Display
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 20
5.2 Turn on the UPS (Put the UPS in On-Line Mode)
When the input voltage is within the acceptable range press and hold the “ON/Mute” button for at least two sec­onds. A few seconds later the UPS will turn on and enter on-line mode. “ONLINE” will be displayed in the UPS status window on the LCD display. The UPS will provide pure and stable AC power to the output. The UPS will also charge the batteries.
5.2.1 LCD Display in On-Line Mode
Rack Display Tower Display
5.3 Connect Devices to the UPS
After the UPS has been turned on, devices (load) can now be connected to the UPS. For socket-type outputs, there are two kinds of outputs: programmable outlets and general purpose outlets. Connect non-critical devices to the programmable outlets and critical devices to the general outlets. During power failure, you may extend the backup time to critical devices by enabling the programmable outlets (see Sections 4.2.5 and 4.2.6).
1) With the UPS on-line switch on the load devices one by one. The LCD display panel will display
the load level by 0-25%, 26-50%, 51-75% and 76-100%.
2) If the UPS is overloaded the audible alarm will beep twice every second and the LCD display panel
will display “OVERLOAD”.
3) When the UPS is overloaded remove some load immediately.
4) When the UPS is in on-line mode, and the overload time exceeds the duration listed in the specification,
the UPS will automatically transfer to bypass mode. At this time, if the bypass is enabled, the UPS will supply power to the load via bypass. If the bypass function is disabled, or the input voltage is not within the bypass acceptable range, the UPS will cutoff power to the load. After the overload is removed the UPS will return to on-line mode.
5) After repetitive overloads, the UPS will be locked in bypass mode. Remove excess loads from the UPS
output. Then restart the UPS.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 21
5.4 The UPS in Battery Mode
1) When the input voltage is not within the acceptable range or there is a mains failure the UPS will enter
battery mode. The batteries will continue to provide an uninterrupted supply of energy to the load.
2) When the UPS is in battery mode the LCD display panel will display the battery level by 0-25%, 26-50%,
51-75% and 76-100% and the battery voltage. The audible alarm will beep according to the battery capacity. Normally, the audible alarm will beep once every four seconds. When the battery voltage drops to low battery voltage level, the audible alarm will beep once per second and the UPS will automatically shut down. At this time, users could switch off any non-critical loads to disable the shutdown alarm and prolong the backup time. If no more load can be removed at this time, then all loads should be shut down as soon as possible to protect the devices or to save data. Otherwise, there is a risk of data loss or load failure.
3) When the UPS is in battery mode, overloaded, and the overload time exceeds the duration listed in the
specification, the UPS will enter a fault status. At this time, if the bypass is enabled, the UPS will supply power to the load via bypass. If the bypass function is disabled, or the input voltage is not within the bypass acceptable range, the UPS will cutoff power to the load.
5.4.1 LCD Display in Battery Mode
Rack Display Tower Display
5.5 Turn Off the UPS
Press and hold the “OFF/ENTER “button for at least two seconds.
At this time, if the bypass is enabled and if the mains voltage is within the acceptable range, the UPS will enter
bypass mode supplying power to the loads via bypass. The UPS will also charge the batteries. “BYPASS” will be
displayed in the UPS status window on the LCD display. See Section 5.1.1 “LCD Display in Bypass Mode”.
If instead the bypass is disabled, the UPS will enter standby mode. In this mode the UPS will not supply power to the load. The UPS will also charge the batteries. See Section 5.1.2 “LCD Display in Standby Mode”.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 22

6. INTERFACES

The UPS’s are equipped with a serial interface COM 3, USB and an interface slot COM. These interfaces can be used for:
1. Direct communication between UPS and a workstation/server.
2. Integration of the UPS as client into a network with centralized monitoring via a Manage UPSNET SNMP
adaptor in the slot COM.
3. Transfer of operational states to external alarm systems via voltage-free contacts: with interface card SIC in
the slot COM.
The necessary communication software packages and interface cables are available as options.
6.1 Serial Interface COM 3
The 9-pole SUB-D connector (pin contacts) contains RS232 compatible signals.
NOTE: The interface COM RS232 is electrically isolated from primary UPS circuits.
6.2 Interface Slot COM
The interface slot COM can be fitted with various optional interface cards. Interface cards include:
·
SNMP adapter (Manage UPSNET) for Connecting the Device to a Network
·
Isolated Contacts Card
Refer to the installation guide supplied with the optional interface card.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 23
Pin 1 and Pin 2 shown in closed status.

7. Emergency Power Off (EPO)

Disable and Enable the EPO Function
Keep Pin 1 and Pin 2 closed (shorted) for UPS normal operation. To activate the EPO function, remove the wire between Pin 1 and Pin 2.

8. Maintenance

8.1 Cleaning
1. Do not use scouring powder or plastic dissolving solutions to clean the UPS.
2. Do not allow liquid to get inside the UPS.
3. Make sure that the air vents on the UPS are not obstructed. Remove dust from the air vents with a vacuum
cleaner.
4. Clean the outside of the UPS housing by wiping with a dry or slightly damp cloth.
8.2 UPS Storage
1. For extended storage at ambient temperatures < 77°F (25°C), the batteries should be charged for five hours once
every four months. At higher storage temperatures it is advised that this period be reduced to two months.
2. To charge the batteries, connect the UPS to an appropriate power source and allow the batteries to charge for
about five hours. After charging, note the date recharging was performed on the UPS packaging.
8.3 Battery Testing
1. The UPS does not require maintenance by the user; however, the battery should be checked periodically.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 24
8.4 Replacing Batteries
The UPS does not require maintenance by the user, however, battery maintenance is recommended in accordance with IEEE Recommended Practice for Maintenance, Testing and Replacement of Valve­Regulated Lead-Acid (VRLA) Batteries for Stationary Applications (IEEE Std 1188-1996). When the batteries expire, trained battery service personnel must replace them. A certified disposal/recycling company should carry out disposal/recycling of the UPS and/or batteries. Exhausted rechargeable batteries are classified as “harmful toxic waste” and as such the law demands that they be disposed of/recycled by an
authorized recycling center. The manufacturer’s service center is fully equipped to deal with such batteries,
in accordance with the law and with the greatest respect for the environment. Contact Technical Support to arrange for maintenance and or battery replacement.
The typical battery life cycle is three to five years, at an ambient temperature of 77°F (25°C), but is also dependent on the frequency and duration of mains failure.
Once the battery has reached the end of its useful life, follow the procedure for battery replacement later in this section.
After the batteries have been replaced, a certified disposal/recycling company should carry out disposal/recycling of the used batteries.
Exhausted rechargeable batteries are classified as “harmful toxic waste” and as such the law demands that they be
disposed of/recycled by an authorized recycling center.
The manufacturer’s service center is fully equipped to deal with such batteries, in accordance with the law and with the greatest respect for the environment. Contact technical support to arrange for maintenance and/or battery replacement. See page 1 for contact information.
0
CAUTION:
· Servicing of batteries should be performed or supervised by personnel knowledgeable
about batteries and the required precautions.
· The batteries installed in the UPS and in the external battery packs contain electrolyte. Under
normal conditions the containers are dry. A damaged battery may leak electrolyte that can be dan­gerous in contact with skin and cause irritation to the eyes. Should this happen, wash the affected part with copious amounts of water and seek immediate medical attention.
· When replacing batteries, replace with the same type and number of batteries or battery packs.
· Do not dispose of batteries in a fire. The batteries may explode.
· Do not open or damage the battery cases. Released electrolyte is harmful to the skin and eyes and
may be toxic.
· A battery can present a risk of electrical shock and high short-circuit current. The following
precautions should be observed when working on batteries:
· Remove watches, rings or other metal objects.
· Use tools with insulated handles. Do not lay tools or metal parts on top of batteries.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 25
This UPS is equipped with internal batteries. The user can replace the batteries without shutting down the UPS or connected loads (hot-swappable battery design). Replacement is a safe procedure - isolated from electrical hazards.
ATTENTION: Consider all warnings, cautions, and notes before replacing batteries.
· The load attached to the UPS will not be protected against loss of input power
during this procedure.
· Battery pack is heavy. Use two hands when removing pack from unit.
· The battery packs for the UPS-3000-OL are not user replaceable. Contact technical support to arrange
for maintenance and battery replacement.
To replace internal batteries:
1. Place the UPS in bypass mode.
2. Place fingers on the left hand side of the front cover and pull forward until the left side of the front cover
“snaps” out of position. Remove the left side of the front cover and place it in a safe place. Refer to the figure
directly below:
3. Remove the four screws securing the battery retention plate to the UPS enclosure. Set the battery retention plate and retaining screws aside for later reuse. Cut the tie holding the two halves of the battery pack connector. Disconnect the battery connectors. Refer to the figures directly below:
4. Pull out the battery pack. Refer to the figure directly below:
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 26
5. Slide in replacement battery pack. Refer to the figure directly below:
6. Reconnect the battery connectors. Use the tie wrap supplied with the replacement battery kit to secure the two halves of the battery connector together. Re-install the battery retention plate using the screws removed in step 3. Refer to the figures directly below :
7. Align left plastic front cover and snap into place. Refer to the figure directly below:
9. Carefully pack used battery pack and send to authorized recycle center.
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal,
contact your local recycling/reuse or hazardous waste center.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 27

9. Troubleshooting

9.1 Troubleshooting Table
If the UPS does not function properly, resolve the problem by referring to the table below.
Symptom
Possible cause
Remedy
No warning or fault indication and no alarm even though the mains is normal. The AC input power cord may not be firmly con­nected to the input of the UPS or to the mains.
Confirm that the AC input power cord is firmly connected to the input of the UPS and also to the mains.
The AC input is con­nected to the UPS output.
Plug the AC input power cord firmly to the AC input.
The icon is flashing and the warning code
appears on the LCD display. The alarm
beeps once every second.
EPO function has been activated.
Set pin 1 and pin 2 on the EPO connector in a closed (shorted) position to disable the EPO function.
The icon is flashing and the warning code
appears on the LCD display. The alarm
beeps once every second.
The Line and neutral conductors of the UPS input are reversed.
Rotate the mains power socket by 180° and then reconnect to the UPS system.
The icon and are flashing and
the warning code appears on the LCD display. The alarm beeps once every second.
The external or the inter­nal battery is not con­nected properly.
Check if all batteries are properly connected.
Fault code is shown as 27 and the icon appears on the LCD display. The alarm beeps continuously.
The battery voltage is too high or the charger may be at fault.
Contact your dealer.
Fault code is shown as 28 and the icon appears on the LCD display. The alarm beeps continuously.
The battery voltage is too low or the charger may be at fault.
Contact your dealer.
The icon and are flashing
and the warning code appears on the LCD display. The alarm beeps twice every sec­ond.
UPS is overloaded.
Remove excess loads from UPS output.
UPS is overloaded. De­vices connected to the UPS are fed directly by the electrical network via the bypass.
Remove excess loads from UPS output.
After repetitive over­loads, the UPS is locked in the bypass mode. Con­nected devices are fed directly by the mains.
Remove excess loads from the UPS output. Then shut down the UPS and restart it.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 28
Symptom
Possible cause
Remedy
Fault code is shown as 43 and the icon
appears on the LCD
display. The alarm beeps continuously.
The UPS shut down automati­cally because of an overload on the output of the UPS.
Remove excess loads from UPS output and restart it.
Fault code is shown as 14 and the icon
The UPS shut down automati-
Check the output wiring and
appears on the LCD
display. The alarm beeps continuously.
cally because of a short circuit on the output of the UPS.
connected devices for a short circuit. Remove the short cir­cuit.
Fault code is shown as 01, 02, 03, 04,
A UPS internal fault has oc-
Contact your dealer.
11, 12, 13 and 41 on the LCD display
curred. There are two possible
and the alarm beeps continuously.
results:
1. The load is still supplied, but
directly from AC power via
bypass.
2. The load is no longer sup-
plied by power.
Battery backup time is shorter than the specified value.
Batteries are not fully charged.
Charge the batteries for at least five hours and then check ca­pacity. If the problem still per­sists, consult your dealer.
Batteries are defective.
Contact your dealer to replace the battery.
Fault code is shown as 05 on the LCD display. At the same time, the alarm is beeping continuously and the output of the UPS is cut off.
A UPS internal fault has oc­curred and the BUS is short circuited.
Consult your dealer. If power is supplied again to the UPS before the UPS is repaired then the DC/DC mosfet will be dam­aged.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 29
9.2 Audible Alarm
Battery Mode
Alarms Beeps Once Every Four Seconds
Low Battery
Alarm Beeps Once Every Second
Overload
Alarm Beeps Twice Every Second
Fault
Alarm Beeps Continuously
9.3 LCD Display Abbreviation Index
Abbreviation
Display Content
Meaning
ENA
Enable
DIS
Disable
ESC
Escape
RAC
Rack Display
TOE
Tower Display
B.L
Low Battery
O.L
Overload
N.C
Battery is Not Connected
O.C
Overcharge
SF
Site Fault
E.P
EPO
T.P
Over Temperature
C.H
Charger Failure
B.B
Battery Fault
F.U
Frequency is Unstable in Bypass Mode
B.V
Input Voltage is Out of Bypass Range
E.E
EEPROM Error
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 30
9.4 Warning Indicators
Warning
Icon (flashing)
Code
Alarm
Low Battery
Beeps Once Every Second
Overload
Beeps Twice Every Second
Battery is Not Connected
Beeps Once Every Second
Overcharge
Beeps Once Every Second
Site Wiring Fault
Beeps Once Every Second
EPO Enable
Beeps Once Every Second
Over Temperature
Beeps Once Every Second
Charger Failure
Beeps Once Every Second
Battery Fault
Beeps Once Every Second
Bypass Out Range
Beeps Once Every Second
Bypass Frequency Unstable
Beeps Once Every Second
EEPROM Error
Beeps Once Every Second
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 31
9.5 UPS Fault
When there is a fault with the UPS the fault icon flashes on the LCD display. A fault code will also be displayed directly below the flashing fault icon. When a fault occurs no output power is supplied from the UPS.
9.5.1 LCD Display in Fault Mode
Rack Display Tower Display
9.5.2 Fault Reference Code
Fault Event
Fault Code
Icon
Fault event
Fault Code
Icon
Bus Start Fail
01
x
Low Inverter Voltage
13
x
Bus Over
02
x
Inverter Output Short
14
Bus Under
03
x
Battery Voltage Too High
27
x
Bus Unbalance
04
x
Battery Voltage Too Low
28
Bus Short Circuited
05
x
Over Temperature
41
x
Inverter Soft Start Fail
11
x
Overload
43
High Inverter Voltage
12
x
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 32

10 APPENDIX A: SPECIFICATIONS

10.1 SURGEX UPS (100 - 120 Volt UPS’s) Specifications
SurgeX UPS 1000
VA Low Voltage
Model
UPS-1000-OL
Type
SurgeX
Power Rating
1000 VA / 900 W
Topology
On-Line Double Conversion
Heat Dissipation (BTU/Hour)
520 at 100% Load
Input Voltage (Nominal)
Range
100-120 VAC
90-150 VAC
Input Frequency
50/60 Hz ±4
(Auto Sense on Start-Up)
Input Power Factor
>0.95
Input Current THD
<9.0%
Efficiency
>84.0%
Output Voltage
120 VAC (Default)
100/110/115 VAC (Selectable)
Output Current
8.3 A (Default)
8.0/8.2/8.3 A (Selectable)
Voltage Regulation
±1.0%
Overload
Online Mode
100-105%: Continuous; Warning Only
105-130%: 2 Minutes
130-200%: 10 Seconds
>200%: 250 Milliseconds
Overload
Battery Mode
100-105%: Continuous; Warning Only
105-130%: 10 Seconds
>130%: 250 Milliseconds
Overload
Bypass Mode
100-110%: Continuous; Warning Only
110-120%: 30 Minutes 120-130%: 10 Minutes
>130%: 1 Minute
Battery Voltage (Float / Nominal)
27.4/24.0 VDC
Charger Current
1.0 A
Backup Time (Full Load)
>3.5 Minutes
Communications Interface
USB / RS-232
Shipping Weight
37.0 lbs. / 16.8 kg.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 33
SPECIFICATIONS CONT.
SURGEX UPS (100 - 120 Volt UPS’s) specifications cont.
Front Panel Controls
Internal Batteries
User Hot-Swappable (See Instruction Manual) Type - 12 V, 8.5 AH Quantity - 2 Batteries Recharge time - 12 Hours to 100%
Environmental
Temperature: 0 to 40
0
C (32 to 1040F) Operating
-20 to 500C (-40 to 1220F) Shipment, Storage
Humidity: <90% Non-Condensing (Operating,
Shipment, Storage)
Altitude: <1000m Operating, No De-Rating
>1000m De-Rate Output 1% per 100m
Safety Agency and EMC Compliance
All units are listed by UL, and marked with the UL/cUL
marking.
Product Listings
 UL1778  cUL to CSA22.2 No.107.1
Product Compliances
FCC Part 15J Class A IEC61000-4-2, Electrostatic Discharge IEC61000-4-3, Radiated Electromagnetic Field Immunity IEC61000-4-4, Electrical Fast Transient/Burst Immunity IEC61000-4-5, Surge Immunity  IEC61000-4-6, CS  IEC61000-4-8, Power Frequency Magnetic Field IEC61000-2-2, Low Frequency Signal RoHS
1. ON / MUTE - UP KEY (Previous Selection)
2. SELECT - DOWN KEY (Next Selection)
3. OFF / ENTER - CONFIRM KEY
Front Panel Display
Rear Panel Information and Controls
6 Foot Line Cord with NEMA 5-15P
(3) NEMA 5-15R Direct
(3) NEMA 5-15R Programmable
USB & RS-232 Communication
SNMP Adapter (Optional)
Internal Relay Contact Card (Optional)
Circuit Breaker
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 34
SPECIFICATIONS CONT.
SURGEX UPS (100 - 120 Volt UPS’s) specifications cont.
SurgeX UPS
2000 VA Low Voltage
Model
UPS-2000-OL
Type
SurgeX
Power Rating
2000 VA / 1800 W
Topology
On-Line Double Conversion
Heat Dissipation (BTU/Hour)
1171 at 100% Load
Input Voltage (Nominal)
Range
100-120 VAC 105-150 VAC
Input Frequency
50/60 Hz ±4
(Auto Sense on Start-Up)
Input Power Factor
>0.95
Input Current THD
<9.0%
Efficiency
>84.0%
Output Voltage
120 VAC (Default)
100/110/115 VAC (Selectable)
Output Current
16.7 A (Default)
16.0/16.4/16.5 A (Selectable)
Voltage Regulation
±1.0%
Overload
Online Mode
100-105%: Continuous; Warning Only
105-130%: 2 Minutes
130-200%: 10 Seconds
>200%: 250 Milliseconds
Overload
Battery Mode
100-105%: Continuous; Warning Only
105-130%: 10 Seconds
>130%: 250 Milliseconds
Overload
Bypass Mode
100-110%: Continuous; Warning Only
110-120%: 30 Minutes 120-130%: 10 Minutes
>130%: 1 Minute
Battery Voltage (Float / Nominal)
54.7/48.0 VDC
Charger Current
1.0 A
Backup Time (Full Load)
>3.6 Minutes
Communications Interface
USB / RS-232
Shipping Weight
58.0 lbs. / 26.4 kg.
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 35
SPECIFICATIONS CONT.
SURGEX UPS (100 - 120 Volt UPS’s) specifications cont.
Front Panel Controls
Internal Batteries
User Hot-Swappable (See Instruction Manual) Type - 12 V, 8.5 AH Quantity - 4 Batteries Recharge time - 12 Hours to 100%
Environmental
Temperature: 0 to 40
0
C (32 to 1040F) Operating
-20 to 500C (-40 to 1220F) Shipment, Storage
Humidity: <90% Non-Condensing (Operating,
Shipment, Storage)
Altitude: <1000m Operating, No De-Rating
>1000m De-Rate Output 1% per 100m
Safety Agency and EMC Compliance
All units are listed by UL, and marked with the UL/cUL
marking.
Product Listings
 UL1778  cUL to CSA22.2 No.107.1
Products Compliances
FCC Part 15J Class A IEC61000-4-2, Electrostatic Discharge IEC61000-4-3, Radiated Electromagnetic Field Immunity IEC61000-4-4, Electrical Fast Transient/Burst Immunity IEC61000-4-5, Surge Immunity  IEC61000-4-6, CS  IEC61000-4-8, Power Frequency Magnetic Field IEC61000-2-2, Low Frequency Signal RoHS
1. ON / MUTE - UP KEY (Previous Selection)
2. SELECT - DOWN KEY (Next Selection)
3. OFF / ENTER - CONFIRM KEY
Front Panel Display
Rear Panel Information and Controls
6 Foot Line Cord with NEMA 5-20P
(17201-01R Only, 1600 W Capability)
6 Foot Line Cord with NEMA L5-20P
(17201-02R Only, 1600 W Capability)
6 Foot Line Cord with NEMA L5-30P
(17201-03R Only, 1800 W Capability)
(2) NEMA 5-20R
(1) NEMA L5-20R Direct
(2) NEMA 5-15R Programmable
USB & RS-232 Communication
SNMP Adapter (Optional)
Internal Relay Contact Card (Optional)
Circuit Breaker
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 37
SPECIFICATIONS CONT.
SURGEX UPS (100 - 120 Volt UPS’s) specifications cont.
SurgeX UPS
3000 VA Low Voltage
Model
UPS-3000-OL
Type
SurgeX
Power Rating
3000 VA / 2700 W
Topology
On-Line Double Conversion
Heat Dissipation (BTU/Hour)
1756 at 100% Load
Input Voltage (Nominal)
Range
100-120 VAC
90-150 VAC
Input Frequency
50/60 Hz ±4
(Auto Sense on Start-Up)
Input Power Factor
>0.95
Input Current THD
<9.0%
Efficiency
>84.0%
Output Voltage
120 VAC (Default)
100/110/115 VAC (Selectable)
Output Current
25.0 A (Default)
24.0/24.5/24.8 A (Selectable)
Voltage Regulation
±1.0%
Overload
Online Mode
100-105%: Continuous; Warning Only
105-130%: 2 Minutes
130-200%: 10 Seconds
>200%: 250 Milliseconds
Overload
Battery Mode
100-105%: Continuous; Warning Only
105-130%: 10 Seconds
>130%: 250 Milliseconds
Overload
Bypass Mode
100-110%: Continuous; Warning Only
110-120%: 30 Minutes 120-130%: 10 Minutes
>130%: 1 Minute
Battery Voltage (Float / Nominal)
82.1/72.0 VDC
Charger Current
1.0 A
Backup Time (Full Load)
>3.6 Minutes
Communications Interface
USB / RS-232
Shipping Weight
81.0 lbs. / 36.8 kg.
36
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 37
SPECIFICATIONS CONT.
SURGEX UPS (100 - 120 Volt UPS’s) specifications cont.
Front Panel Controls
Internal Batteries
User Hot-Swappable (See Instruction Manual) Type - 12 V, 8.5 AH Quantity - 6 Batteries Recharge time - 12 Hours to 100%
Environmental
Temperature: 0 to 40
0
C (32 to 1040F) Operating
-20 to 500C (-40 to 1220F) Shipment,
Storage
Humidity: <90% Non-Condensing (Operating,
Shipment, Storage)
Altitude: <1000m Operating, No De-Rating
>1000m De-Rate Output 1% per 100m
Safety Agency and EMC Compliance
All units are listed by UL, and marked with the UL/cUL marking.
Product Listings
 UL1778  cUL to CSA22.2 No.107.1
Product Compliances
FCC Part 15J Class A IEC61000-4-2, Electrostatic Discharge IEC61000-4-3, Radiated Electromagnetic Field Immunity IEC61000-4-4, Electrical Fast Transient/Burst Immunity IEC61000-4-5, Surge Immunity  IEC61000-4-6, CS  IEC61000-4-8, Power Frequency Magnetic Field IEC61000-2-2, Low Frequency Signal RoHS
1. ON / MUTE - UP KEY (Previous Selection)
2. SELECT - DOWN KEY (Next Selection)
3. OFF / ENTER - CONFIRM KEY
Front Panel Display
Rear Panel Information and Controls
6 Foot Line Cord with NEMA L5-30P
(2) NEMA 5-20R
(2) NEMA 5-20R Programmable
(1) NEMA 5-30R (1 Foot Cord) Direct
USB & RS-232 Communication
SNMP Adapter (Optional)
Internal Relay Contact Card (Optional)
(2) Circuit Breakers
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 39
SPECIFICATIONS CONT.
10.2 Extension battery packs for use with SurgeX UPS
SurgeX Battery Pack
1000 VA Low Voltage
Model
UPS-BPX-1000
Type
SurgeX
Compatible UPS
UPS-1000-OL
Voltage (Nominal)
24.0 VDC
Battery Type
12V Flame Retardant
Sealed Lead-Acid
Battery Quantity
2 x 2 Strings
Recharge Time
24 Hours
(Single Battery Pack, 1A Charger)
Length
17.25 in / 438 mm
Height
3.39 in / 86 mm
Depth
16.26 in / 413 mm
Unit Weight
38.0 lbs. / 17.3 kg.
Shipping Weight
47.0 lbs. / 21.4 kg.
Safety Agencies
UL1778
cUL to CSA22.2 No. 107.1
38
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 39
SPECIFICATIONS CONT.
Extension battery packs for use with SurgeX specifications cont.
SurgeX UPS Battery Pack
2000 VA Low Voltage
Model
UPS-BPX-2000
Type
SurgeX
Compatible UPS
UPS-2000-OL
Voltage (Nominal)
48.0 VDC
Battery Type
12V Flame Retardant
Sealed Lead-Acid
Battery Quantity
4 x 2 Strings
Recharge Time
24 Hours
(Single Battery Pack, 1A Charger)
Length
17.25 in / 438 mm
Height
3.39 in / 86 mm
Depth
20.20 in / 513 mm
Unit Weight
65.0 lbs. / 29.5 kg.
Shipping Weight
75.5 lbs. / 34.3 kg.
Safety Agencies
UL1778
cUL to CSA22.2 No. 107.1
Percent Capacity
Watts
Number of Battery Packs
Internal
INT+1 EXT
INT+2 EXT
INT+3 EXT
INT+4 EXT
Runtimes are expressed in minutes Typical runtimes based on fully charged, new batteries, operating under typical load conditions Times estimated assuming a switch mode power supply Runtimes are affected by battery age, ambient temperature, site specific usage patterns and load conditions
0 0 517
> 16 hrs
> 16 hrs
> 16 hrs
> 16 hrs
10
160
60 267
532
836
> 16 hrs
20
320
27
121 242 380 533
30
480
16
74
147 232 325
40
640
11 52 103
162
227
50
800
8.9 39
77
122 171
60
960
7.0 31 61 96 135
70
1120
5.7 25
50
79
111
80
1280
4.8 21
42
66
93
90
1440
4.1 18
36
57
80
100
1600
3.6 16
31
49
69
© 2016 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 40
SPECIFICATIONS CONT.
Extension battery packs for use with SurgeX specifications cont.
SurgeX UPS Battery Pack
3000 VA Low Voltage
Model
UPS-BPX-3000
Type
SurgeX
Compatible UPS
UPS-3000-OL
Voltage (Nominal)
72.0 VDC
Battery Type
12V Flame Retardant
Sealed Lead-Acid
Battery Quantity
6 x 2 Strings
Recharge Time
24 Hours
(Single Battery Pack, 1A Charger)
Length
17.25 in / 438 mm
Height
3.39 in / 86 mm
Depth
24.92 in / 633 mm
Unit Weight
91.5 lbs. / 41.6 kg.
Shipping Weight
105.0 lbs. / 47.4 kg.
Safety Agencies
UL1778
cUL to CSA22.2 No. 107.1
Percent Capacity
Watts
Number of Battery Packs
Internal
INT+1 EXT
INT+2 EXT
INT+3 EXT
INT+4 EXT
Runtimes are expressed in minutes Typical runtimes based on fully charged, new batteries, operating under typical load conditions Times estimated assuming a switch mode power supply Runtimes are affected by battery age, ambient temperature, site specific usage patterns and load conditions
0 0 351
> 16 hrs
> 16 hrs
> 16 hrs
> 16 hrs
10
240 56
247 491 772
> 16 hrs
20
480 26
117 232 365 512
30
720 16
72
144 226 318
40
960
11 51 101
159
223
50
1200 8.8 38
77
120 169
60
1440 7.0 31
61
96
134
70
1680
5.7 25
50
78
110
80
1920 4.8 21
42
66
93
90
2160 4.1
18
36
57
80
100
2400
3.6 16
31
49
69
Loading...