TECHNICAL DESCRIPTION
The SA-82-AR shall be a compact mountable unit in a magnetic shielding steel enclosure. It shall operate from 120 volts AC and include a separate 3-foot, grounded, 3-wire #18 line cord. There shall be 2 grounded AC receptacles. Overall dimensions shall be 1.75" H x 5.31" W x 9.06" D. Weight shall be 3.4 pounds. The SA-82-AR shall have a load rating of 8 amps at 120 volts, a self-test circuit with visual indicator, and provide EMI/RFI filtering and catastrophic over-voltage shutdown. It shall have remote control, scheduling, and AutoPing functions via wired Ethernet HTTP, Telnet, and DxP protocols. It shall withstand at least 1000 occurrences of surge pulse voltages up to 6000 volts.
SPECIFICATIONS
Load Rating
Voltage Rating
Power Requirement (no load)
Surge Let-through Voltage (6000 Volt Surge)
Maximum Applied Surge Voltage
Maximum Applied Surge Current
Maximum Applied Surge Energy
Endurance (C62.41-1991 category B3 pulses)
1RUPDOPRGHORDG
EMI/RFI Filter
&RPPRQ0RGHORDG
Under-Voltage Auto Shutdown
Over-Voltage Auto Shutdown
Over-Current Auto Shutdown
Over-Temperature Auto Shutdown
8A
120V
12 W
0 Volts
6000 Volts *
Unlimited (due to current limiting) *
Unlimited (due to current limiting) *
1 KV > 500,000; 3 KV > 10,000; 6 KV > 1000
>20dB 27kHz - 50MHz > 30dB 90kHz - 26MHz 30 dB @ 100 kHz; 56 dB @ 300 kHz; 64 dB @ 3 MHz; 24 dB @ 30 MHz
> 10dB 360kHz - 50MHz > 20dB 2 MHz - 40MHz 9 dB @ 300 kHz; 16 dB @ 1 MHz; 28 dB @ 5 MHz; 35 dB @ 20 MHz
No
145V
Circuit Breaker
None
Voltage NA
Measurement Accuracy
Current NA
Power NA
Energy NA
Temperature NA
Network Port
Serial Port
Temperature Sensor Input
Auxiliary Relay Outputs
Contact Closure Input
Dimensions
Weight
Temperature Range:
Humidity Range
Agency Listings
Single 10/100 Unshielded Twisted Pair Ethernet Jack
None
None
No
No
11.375" W x 7.625" D x 1.8125" H
4.75 lbs
5C to 35C
5% to 95% R.H. Non-condensing
Conforms to UL Stds 1283 & 1449 Certified to CSA Std C22.2 No. 8
* 1.2 x 50 microsecond industry standard combination wave surge as per IEEE C62.41
** Specifications subject to change without notice
SPECS v.030118
11.212
SA-82-AR
SX-1115-RT
AXESS
RST
ON
Ready
FLATPAK
Surge Protector / Power Conditioner
SYSTEM ON
SELF - TEST
120 VOLTS, 8 AMPS MAX LOAD TOTAL
SA-82-AR
1.806
7.278
v1.0
surgex.com
Loading...