SA-1810
Advanced
SERIES MODE PRO
™
Surge Supressor and Power Conditioner
Top View
Front View
e SA-1810 provides guaranteed surge protection for audio, video, computer and all sensitive
electronic equipment. e unit is rated for 15 amps, features ten industrial grade grounded
AC receptacles, Impedance Tolerant® EMI/RFI [Common Mode and Normal Mode] ltering and can
be tted with optional mounting brackets. SurgeX patented advanced Series Mode Pro™ technology
is superior to conventional MOV circuitry. It provides proven, reliable protection; blocking and
containing multiple surges of up to 6,000 volts, unlimited current, without noise producing ground
contamination. e SA-1810 meets the most stringent government speci cations for AC powerline
surge suppressors. e A-1-1 rating assures you of dependable protection from destructive spikes,
INDUSTRY EXCLUSIVE 10 YEAR WARRANTY
w w w . s u r g e x . c o m
SURGE PROBLEMS ARE HISTORY!
6131-B Kellers Church Road
Pipersville, PA 18947
PH: 215-766-1240
Professional AC Power Products
Fax: 215-766-9202

SA-1810
Advanced
SERIES MODE PRO
™
Surge Supressor and Power Conditioner
FEATURES
• Made in U.S.A., Listed to UL 1449-2
• Magnetic shielding steel enclosure
• 6’ grounded 3-wire #14 line cord
• Ten grounded receptacles
• Thermal circuit breaker overload protection
• Self-test circuit with visual indicator
• Dimensions: 4.0” H x 10.2” W x 4.2” D (10.2 x 25.9 x 10.7 cm)
• Weight: 8.5 lbs. (3.8 kg)
SPECIFICATIONS
• Load Rating: 15 amps @ 120 volts.
• UL 1449-2 Adjunct Classication Test Results: 1000 surges, 6000 volts, 3000 amps, C1 pulse, measured suppressed
voltage 290 volts, no failures.
• 1996 Federal Guidelines, Grade A, Class 1, Mode 1: SA-1810 meets guidelines. Limiters (3 circuits): Series surge
reactor current limiter. Cascaded autotracking dual polarity voltage limiter. Dual pulse inverters.
• Clamping Voltage Onset: 172 volts nominal (2 volts above peak line voltage, auto-tracking).
• Filter (bi-directional, wave tracking): With 50 ohm load: 3 dB @ 3 kHz; 38 dB @ 100 kHz; 50 dB @ 300 kHz; 50
dB @ 5 MHz; 50 dB @ 30 MHz
• Let-Through Slew Rate: 5000 volt/µs disturbance reduced to 28 volt/µs within power wave envelope; less than
10 volt/µs outside power wave envelope.
• Snubber: Instant-reacting snubber for fast-rising surges generated within the building.
• Maximum Applied Surge Pulse Joule Rating: Unlimited, due to current limiting (8 x 20 µs).
• Maximum Applied Surge Pulse Voltage: 6000 volts (1.2 x 50 µs pulse), industry standard rating.
• Maximum Applied Surge Pulse Current: 100,000 amperes (8 x 20 µs). Endurance: IEEE C62.41-1991 Category B3
(C1) Pulses: 1 kv>500,000; 3 kv>10,000; 6 kv>1000 (NRTL-UL certied).
ARCHITECTURAL AND ENGINEERING SPECIFICATIONS
The surge suppressor shall be a compact standalone unit in a magnetic shielding steel enclosure. It shall operate from
120 volts AC and have a 6-foot, grounded, 3-wire #14 line cord. There shall be ten, unswitched, AC grounded
receptacles and self-test circuit with visual indicator. Overall dimensions shall be 4.0” H x 10.2” W x 4.2” D
(10.2 x 25.9 x 10.7 cm). Weight shall be 8.5 pounds. The surge suppressor shall have a load rating of 15 amps @ 120
volts. It shall be listed to UL 1449-2 and meet 1996 Federal Grade A, Class 1, Mode 1 Guidelines for powerline surge
suppressors. There shall be three limiter circuits: a series surge reactor current limiter, a cascaded auto-tracking dualpolarity voltage limiter, and dual pulse inverters. The onset clamping voltage shall be 172 volts nominal, and the unit
shall have an instant-reacting snubber to protect against fast-rising surges generated within the installation location.
The surge suppressor shall have an unlimited Applied Surge Current rating (8 x 20 µs) and shall withstand at least 1000
occurrences of Surge Pulse Voltages up to 6000 volts.
INDUSTRY EXCLUSIVE 10 YEAR WARRANTY
w w w . s u r g e x . c o m
SURGE PROBLEMS ARE HISTORY!
6131-B Kellers Church Road
Pipersville, PA 18947
PH: 215-766-1240
Professional AC Power Products
Fax: 215-766-9202