SurgeX EV-23010 User Manual

Page 1
Software User Ma n ual
Software Ve rs ion 1.0
Page 2
Software User Manual
I. INSTALLATION ......................................................................................................... 2
1. COMPUTER REQUIREMENTS .................................................................................. 2
2. HARDWARE REQUIREMENTS .................................................................................. 2
3. Download and Install Software ............................................................................. 2
4. Install Data Interface Cable .................................................................................. 3
II. USING THE SOFTWARE ......................................................................................... 3
1. PYSICAL CONNECTIONS .......................................................................................... 3
2. START THE SOFTWARE ............................................................................................ 3
3. CONFIGURE THE DATA CABLE AND COM PORT ......................................................... 4
4. SOFTWARE MODES ................................................................................................ 5
a. MULTIMETER MODE ............................................................................................ 6
b. SCOPE MODE ..................................................................................................... 7
c. CHART MODE ..................................................................................................... 9
d. OUTLET CONTROL MODE ................................................................................... 10
e. HISTORICAL DATA MODE ................................................................................... 11
f. SETTINGS MODE ............................................................................................... 15
g. COM PORT SETUP MODE .................................................................................. 16
1
Page 3
I. Installation
1. Computer Requirements
2. Hardware Requirements
3. Download and Install Software
Software User Manual
a. Minimum 133MHz Pentium processor (or equivalen t ) , minimum 64MB of RAM,
minimum 10MB free hard drive space, VGA or higher resolut ion monitor , keyboard, mouse, CD or DVD drive, minimum screen resolut i on of 1024x768, Microsoft Windows XP/Vista/7/8.
a. For use with enVision enabled products and Data Interface Cable
a. Download the Software In s t aller from www.espei.com
. b. Unzip and run the installation ut i l it y. c. Follow the on-screen instructions to complete installat ion of the software.
(XG-PCS-1C-1)
2
Page 4

4. Install Data Interface Cable a. Automatic Installation (Requires Internet connection)

i. Plug the USB side of the Data Interface Cable int o an available USB port. ii. Windows will automatical ly detect and install appropriate device driver
b. Manual Installation
In the event that the automat ic dr iv er installation process was not s uccessful, or if no internet connection is available, the Data Interface Cable driver files may be installed manually.
Select “Install Drivers” dur ing t he Software Installation proce ss.
Or run “enVision PCS Interface Setup” from:
c. Once the Data Interface Cable has been successfully installed, it will appear
in Device Manager as “USB Serial Port (COMx)” unde r “P o rts (COM & LPT)”.
II. Using the Software
1. Physical Connection s
a. Plug the USB side of the Data Inter f ace Cable into an available US B por t . b. Plug the RJ-11 side of the Data I nt er fa ce Cable into the RJ-11 “OUT” jack
labeled “Data Port” on the enVision en abled unit, which is the jack closest t o the LCD.
c. Note: The enVision PCS must be powered by AC Mains for communications with
the software to operate.
2. Start the Software
a. Double-click the desktop shortcut lab el ed “enVison”, or use the
“ESP SurgeX enVision PCS” Start Menu shortcut located at: Start/All Programs/ESP SurgeX/enVision PCS
Software User Manual
files for the Data Interface Cable.
If a “Found New Hardware” pop-up box appears, follow the on-
screen instructions and a llow Windows to search online for dr iver files.
The installation could ta ke s everal minutes to search for and
download appropriate dr iv er fi les. O nc e t he files are found, follow the on-screen instructions to install.
Note: The driver installati on process will first install USB S er ia l
Converter driver files, and then will install USB Serial Port dr ivers separately.
Start/All Programs/ESP SurgeX/ESP enVision PCS
3
Page 5
Software User Manual
3. Configure the Data Inter f ace C abl e and COM Port
a. Click the COM Port Setup button labeled COM.
b. Click Configure.
i. The auto configuration process will auto matically set the correct device
parameters of the Data Inter fac e Cable to operate properly with the software and enVision.
Note: This process only n eeds t o be done once for each new
Data Interface Cable installed on the PC.
Note: This process edits Windows registry values, and so may be
blocked by MS Windows User Account Control (UAC) in Windows Vista/7/8. When using these operating systems, it m ay be necessary to exit the softw ar e and r estart it with administrativ e rights by right-clicking the soft w ar e shortcut and choosing “Run As Administrator”.
4
Page 6
Software User Manual
c. Click Detect.
i. The auto detect process will auto matically detect the COM Port number
assigned to the Data Inter fac e Ca ble
ii. If the auto detection proces s is successful, click Save. The so ftw ar e is
now properly configured a nd r eady for use.
iii. If the auto detect ion process is not successful, v er ify that the Data
Interface Cable device dr i vers are properly installed, and t hat the physical connections between the enVision and the PC hav e been made correctly.
.
4. Software Modes
The enVision Software is organized into several operational modes. The modes are activated by clicking the c or r esponding button at the bottom of the software interface.
Press the Help Button (“?”) in the upper right for additional information on the f eat ur es available in the current mode. Hovering the mouse c ur sor over items will also display additional information.
Scope Mode, Chart Mode, and Historical Data Mode include a Save function. Press the Save button to save data to a CSV file. T ime Sta mped data may also be saved as a repor t in P DF format.
5
Page 7
Software User Manual
a. Multimeter Mode
i. The Multimeter Mode provides information traditionally acquire d from one
or more handheld digital multim et er s, as well as an overview of the recorded power quality events and energy consumption o f connected equipment. ±2% Measurement Accur acy.
6
Page 8
Software User Manual
ii. Real-time display of 8 electrical parameters
Line Voltage: AC RMS Volts Line-Neutral (Line1-Line2)
Load Current Draw: AC RM S A m ps
Load Power Draw: Watts
Neutral-Ground Voltage: AC RMS Volts Neutral-Ground ( Line2-
Ground)
Line Frequency: Hertz
Load Power Factor
Line Voltage Crest Factor
Energy Usage (kWh) of connected equipment since date and
time of last manual usage reset
iii. Number of recorded power quality events
Surge Events: SG
Overvoltage Events wit h t ur n of f o f connected equipment: OVoff
Overvoltage Events wit h no t ur n of f of connected equipment:
OVrec
Undervoltage Events wit h no t ur n of f o f connected equipment:
UVrec
Undervoltage Events wit h t ur n of f of c onnected equipment: UVoff
Power Outage Events: P O
b. Scope Mode
i. The Scope Mode enables a real-time voltage, curren t , and power
oscilloscope which incor porates many functions available in standalone oscilloscopes. 4kHz Oscill oscope Bandwidth.
ii. Ch1-Ch3 buttons toggle waveform displays.
Ch1 button toggles line voltage trace.
Ch2 button toggles load current tr ace.
Ch3 button toggles load power trace.
7
Page 9
Software User Manual
iii. Up and Down Arrow buttons adjust the vert ical ax is scaling of each
channel.
iv. Left and Right Arrow buttons adj ust the horizontal (time) axis
scaling.
v. While in normal oper at io n, pr es si ng t he Wait but ton w ill freeze the
currently displayed waveform.
vi. One Shot Trigger Function
The scope may be set to acquire and ho ld a waveform display,
triggered by either Voltag e or Curr ent l evel.
Press the One Shot but t on above the desired channel. A trigger
level cursor will appear on t he display.
Next, Drag the trigger level cursor to the desired amplitu de and
press the Wait button
If the Voltage of Current exceeds the trigger level, the scope will
hold the display
8
Page 10
c. Chart Mode
i. The Chart Mode enables a chart style data logging functio n of 8 electrical
parameters. Data point measurement s are acquired once per second. The measured parameters may be enabled or disabled by pressing the corresponding button.
Software User Manual
ii. Chart display of 8 electrical parameters:
Line Voltage: AC RMS Volts Line-Neutral (Line1-Line2)
Load Current Draw: AC RMS Amps
Load Power Draw: Watts
Neutral-Ground Voltage: AC RMS Volts Neutral-Ground ( Line2-
Ground)
Line Frequency: Hertz
Load Power Factor
Line Voltage Crest Factor
Energy Usage (kWh) of connected equipment since date and
time of last manual usage reset
9
Page 11
Software User Manual
d. Outlet Control Mode
i. The Outlet Control Mode enables control of the AC outlets and provides
information about wiring fault s and abnormal line voltage.
ii. Use the green On/Off button to manually turn the AC outlets on and of f.
Pressing the blue Power Cycle button will result in the execution
of a power cycle. When commanded, the outlets will turn off, and then back on, after a 90 second del ay. The Power Cycle indicator will be illuminated while a power cycle is activ e.
10
Page 12
Software User Manual
e. Historical Data Mode
The Historical Data Mode allow s f or t he r et r ieval and display of the power qua li t y event and electrical parameter data stored in the enVision internal memory.
i. Time Stamped Power Quality Event Data
enVision is able to store a nd t i mestamp the 512 most recent
power quality events in its int er nal memory. Press the Import Time Stamped Data button to download the event data.
11
Page 13
Software User Manual
Twelve types of events are logged:
Overload: Load current draw has exceeded 25A  Surge: enVision has been exposed to a transient voltage
in one of the 3 possible modes (bet w een Live and Neutral, between Live and G r ound, bet ween Neutral and Ground) with a peak ampli tude of 500V* or higher and a frequency of 20 kHz or hig her. *500V surge voltage
amplitude appli es t o I EEE C62.41 Category B Im pulse; surge voltage amplitudes necessary for detection of ot her surge types may vary.
Over Voltage (Cutoff): Line voltage exceeded the over
voltage shutdown thresh ol d, and connected equipment was turned off.
Over Voltage (Record): Line voltage excee ded t he over
voltage record threshold, and connected equipment was not turned off.
Under Voltage (Record): Line voltage dropped below the
under voltage record threshold, and connected equi pm ent was not turned off.
Under Voltage (Cutoff): Line voltage droppe d below the
under voltage shutdown thr eshold, and connected equipment was turned off.
Power Outage: Loss of AC power .  Turn On: The enVision outlets were turned on.  Turn Off (Cycle): A power c ycle was initiated by a
received command.
Turn Off (Software): Outle ts were turned off by a received
command.
Turn Off (Button): Outlets were turned off by the
pushbuttons.
Turn Off (Loss of Ground): Outlets were turned off due to
the loss of the safety ground conductor at the wall receptacle.
12
Page 14
Software User Manual
ii. Historical Electrical Parameter Da ta
Every 30 minutes, enVision stores a snapshot of 6 electrical para meter s measured over the prior 30 m inute interval. The internal mem or y can store 138 days of data. Pr ess the Import Historical Data button to download the data.
Six electrical parameters are logged:
Average Power (Watts): The average real power draw of
connected equipment dur i ng the 30 minute recording interval.
Maximum Power Draw (Watts): The highest real power dr aw
measured during the 30 m inut e r ecording interval.
Average Recorded Voltage (V
): The average line voltage
RMS
during the 30 minute recording interval.
Maximum Recorded Voltage (V
): The highest line voltage
RMS
measured during the 30 m inut e r ecording interval.
Minimum Recorded Voltage (V
): The lowest line voltage
RMS
measured during the 30 m inut e r ecording interval.
Maximum Recorded Current (A
): The highest current draw
RMS
measured during the 30 m inut e r ecording interval.
After the historical electrical parameter data has been downloaded, it may be saved to a file or graphically displayed by pressing one of the 3 Graph buttons.
13
Page 15
Software User Manual
1. Average Power Graph Pressing the Average Power Graph button will display a bar graph
of the average real power draw of co nnected equipment during each 30 minute recording interv al.
2. Average Voltage Graph Pressing the Average Vol t age G raph button will display a bar graph
of the average line voltage during each 30 minute record ing inter val.
14
Page 16
3. Max/Min Graph Pressing the Max/Min Graph button will display line gr aphs of
maximum voltage, minim um voltage, maximum curr ent draw, and maximum power draw during each 30 minute recording interval.
Pressing the V Max, V Min, I Max, or P Max buttons will enab le or disable the display of the corresponding parameter.
Software User Manual
f. Settings Mode
i. The Settings mode enables the specificat ion o f t he user-configurable
parameters of enVision. When this mode is entere d, it disp lays the parameters currently in us e.
ii. Auto Set Clock: Automati cally sets the internal clock to the current date
and time.
iii. Set Clock: Sets t he internal clock to a date and time man ually specified in
the date/time field.
15
Page 17
Software User Manual
Limit
When Activated
Action
Factory Default
120V
208/240V
Over Voltage Shutdown
V > OV
Outlets turned Off and event recorded
150
280
Over Voltage Record
OV
> V > OV
Outlets stay On and event recorded
145
270
Over Voltage Restore
V < OV
After OV
Outlets turned On and event recorded
140
260
Under Voltage Restore
V > UV
After UV
Outlets turned On and event recorded
105
190
Under Voltage Record
UV
< V < UV
Outlets stay On and event recorded
100
180
Under Voltage Shutdown
V < UV
Outlets turned Off and event recorded
80
160
iv. Update ID: Sets the product identifier specified in the text box. 10
character limit.
v. Update Limits: Sets t he 6 voltage thresholds speci fied by the voltage
threshold selection fields.
Shutdown
Shutdown
Restore
Restore
Shutdown
Shutdown
g. COM Port Setup Mode
i. The COM Port Setup mode is used to configure new Data Interface
Cables for use.
Record
Shutdown
Shutdown
Record
ii. Detect: Automatically detect the COM Port when the enVision, Data
Interface Cable, and PC are properly connected and powered up.
iii. Configure: Automatically configure the advanced settings of the Data
Interface Cable. May require running the software with elevated permissions (right-click program shortcut and choose “Run As Administrator”) on Windows Vista/7/8 with UAC (User Account Control) enabled.
iv. Save: Saves the COM Port selection.
16