SurgeX Defender Series Surge + PDU User Manual

Page 1
Defender Series Surge + PDU User Manual
Congratulations on your SurgeX purchase and thank you for your business. Our Defender Series multi-stage protection technology will increase server uptime by protecting your equipment from dangerous power events that can disrupt or even destroy your investment.
Your Defender Series Surge + PDU unit provides:
• Failsafe protection: Shields server equipment from damaging surges, spikes, over voltage, EMI/RFI noise, and wire faults that can cause downtime, disruption, and equipment shutdown
• Power distribution: A comprehensive Surge + PDU all-in-one solution
• Redundancy: Extended protection for UPS and ancillary equipment and creates a
stress free environment to keep your system up and running
• Uptime: Helps increase uptime, protect data, extend equipment life and increase reliability of connected equipment
Our goal is your complete satisfaction. Please visit surgex.com/defenderseries for additional product information, user manuals, warranty information, and product / warranty registration. Contact us at inquiries@surgex.com for direct assistance. Thank you for your purchase!
I. Product Description
• Power Distribution Unit with multi-stage Surge Protection
• Models:
o SX-DS-L630-FP
• 120/230 VAC Split Phase (North American)
o SX-DS-L530-FP
• 120 VAC Single Phase (North American)
o SX-DS-520-FP
• 120V Single Phases (North America)
24A Maximum Capacity 15A Maximum Capacity per Bank
(1) NEMA L6-30P input power cord
24A Maximum Capacity 15A Maximum Capacity per Bank
(1) NEMA L5-30P input
power cord
20A Maximum Capacity 10A Maximum Capacity per Bank
(6) IEC-320 C13 output
power receptacles
(6) IEC-320 C13 output
power receptacles
(2) 15A Branch-Rated
Circuit Breakers
(2) 15A Branch-Rated
Circuit Breakers
(1) NEMA 5-20P input
power cord
© SurgeX REV-C Page 1
(6) IEC-320 C13 output
power receptacles
(2) 15A Branch-Rated
Circuit Breakers
Page 2
Defender Series Surge + PDU User Manual
o SX-DS-IEC-FP
• 230 VAC Single Phase (International) 30A Maximum Capacity 10A Maximum Capacity per Bank
(1) IEC-60309 332P65 input
II. Hardware Included
• Tower Conguration Hardware – Option A
• Rack Mount Conguration Hardware – Option B
(1) Left
bracket
• Cable Organizing Hardware (optional)
(1) Cable Organizer (2) Thumbscrews
(6) IEC-320 C13 output
power cord
(1) Base stand (6) 6/32 x ½” Flathead Screws
(1) Right
bracket
(11) 6/32 x ¼”
Flathead Screws
power receptacles
(8) Plastic Ties
(3) 10A Branch Rated
Circuit Breakers
(4) Thumbscrews (4) Cage Nuts
III. Installation
• Warning: Before installing the SurgeX Defender Series unit,
Unpack the Unit and Accessories
• Connect Cable Organizing Hardware (Optional)
• Congure Unit
review the safety instructions that came with the unit
o Identify each item; refer to the Quick Start Guide for reference
o Use (2) thumbscrews to attach the cable organizer
to the rear panel (gure 1-a)
o Select Tower or Rack Mount Conguration
• Determine which conguration is best for your installation
o Option A: For tower installations, the Defender Series
Surge + PDU may be congured to mount upright as a Tower and can stand on any dry, at surface
o Option B: For rack installations, the Defender Series
Surge + PDU may be congured to mount within a
standard 19” equipment rack and will require 1 RU (Rack Unit) of space
o
1-a
2-a 2-b
© SurgeX REV-C Page 2
Page 3
o To Install Tower Conguration – Option A
• Use a Phillips screwdriver and (6) 6/32 x ½” athead screws to attach the base stand (gure 2-a)
• Place the Defender Series unit on a at, stable surface in an upright position resting on the base stand (gure 2-b)
o To Install Rack Mount Conguration – Option B
• Use a Phillips screwdriver and (5) 6/32 x ¼” athead screws to attach the left rack bracket (gure 3-a)
• Use a Phillips screwdriver and (6) 6/32 x ¼” athead screws to attach the right rack bracket (gure 3-a)
• Insert the Defender Series unit into an available 1RU rack space from the
front of the rack (gure 3-b) Product is designed for U-Space mounting only
• Use (4) thumbscrews to secure the left and right rack brackets to the rack
rails (gure 3-b)
• Use (4) cage nuts to secure the 4 thumbscrews to the rack (gure 3-b)
• Connect the Power Cables
o Connect the ancillary server equipment power plugs to the IEC output power
receptacles located on the rear panel of the Defender Series unit. Distribute
the equipment load evenly between the receptacle banks (gure 4-a)
o To properly protect your system, connect all ancillary server equipment
(including UPS/Battery Backup) to the SurgeX Defender Series output power receptacles; Refer to Common Congurations
section for reference
o Check that the equipment you have connected to the Defender Series meets
the following electrical rating requirements:
• SX-DS-L630-FP: IMPORTANT: ONLY CONNECT EQUIPMENT RATED FOR USE WITH
NORTH AMERICAN 120/230VAC SPLIT PHASE
• SX-DS-L530-FP: IMPORTANT: ONLY CONNECT EQUIPMENT RATED FOR USE WITH
NORTH AMERICAN 120VAC SINGLE PHASE
• SX-DS-520-FP: IMPORTANT: ONLY CONNECT EQUIPMENT RATED FOR USE WITH
NORTH AMERICAN 120VAC SINGLE PHASE
• SX-DS-IEC-FP: IMPORTANT: ONLY CONNECT EQUIPMENT RATED FOR USE WITH
230VAC SINGLE PHASE
Defender Series Surge + PDU User Manual
3-a
3-b
4-a
• Secure the Power Cables – (optional)
o Secure equipment power cords to the cable organizer (if desired) using
5-a
cable ties or zip ties, to prevent accidental removal (gure 5-a)
© SurgeX REV-C Page 3
Page 4
• Plug in the Power Cord
o Connect the input power cord of the
SurgeX Defender Series to AC Mains. Lock the SX-DS-L630-FP and SX-DS-
L530-FP plugs
(gure 6-a)
o Do not plug the unit into a UPS or
re-locatable power tap; UPS devices should only be connected to the SurgeX Defender Series unit
Defender Series Surge + PDU User Manual
6-a
by turning to the right
• Check Front Panel
o Check the front panel to make sure the green “Outlets On” LED is lit
• If the green “Outlets On” LED is lit, your Defender Series unit is ready to be used, and is protecting your server and ancillary equipment (gure 7-a)
o If the green “Outlets On” LED is not lit, but the red Wiring Fault Indicator
LED is lit, a wiring fault at the outlet has been detected. The SurgeX unit will not operate until the Wiring Fault is resolved by a qualied electrician. Refer to the “Front Panel LED Indicators” section for further instructions (gure 7-b)
CAUTION – Do not install this device if there is not at least 10 meters (30 feet) or more of wire between the electrical outlet and the electrical service panel.
IV. Common Congurations
• To properly protect your system, connect all ancillary server equipment (including UPS/Battery Backup)
to the SurgeX Defender Series output power receptacles (gure 8-a)
7-a
7-b
8-a
© SurgeX REV-C Page 4
Page 5
V. Front Panel LED Indicators
• Power Indicator (Green); the green Power Indicator LED located on the left/top of the front panel indicates that the electrical AC Mains is properly wired, and power is available at the output power receptacles (gure 9-a)
• Wiring Fault Indicator (Red); the red Wiring Fault Indicator LED located to the right/ below the green Power Indicator LED on the front panel indicates that the electrical AC Mains is not properly grounded, and power is not available at the output power
receptacles (gure 9-b)
o If the red Wiring Fault indicator LED is illuminated, contact a licensed
electrician to inspect the electrical AC source outlet and repair as necessary
o SX-DS-L530-FP model only: The red Wiring Fault Indicator LED may also
indicate that the electrical AC Mains is improperly wired with the Line and Neutral conductors reversed, and power is not available at the output power receptacles
• IMPORTANT: The presence of a safety Ground is essential to reduce the risk of electric shock. If the red
Wiring Fault indicator LED is illuminated, contact a licensed electrician to inspect the AC power source / outlet and repair as necessary.
Defender Series Surge + PDU User Manual
9-a
9-b
VI. Over Voltage Conditions
• In the event of a long duration over-voltage condition, the unit will stop passing power to connected equipment until the voltage returns to a safe operating level; this function is designed to protect your system
VII. Other Information You May Need
• Warning: See the safety and regulatory information that is shipped with your Defender Series unit.
Warranty information may be included within this document or as a separate document.
o The User Manual provides information about product features and describes how to install and troubleshoot the unit; this
document is available online at surgex.com/defenderseries
o The Quick Start guide that is shipped with your Defender Series unit describes how to install your system; this document is
available online at surgex.com/defenderseries
o The Safety Guide that is shipped with your Defender Series unit describes all safety and regulatory information; this document
is available online at surgex.com/defenderseries
o Note: Always check for updated materials at surgex.com/defenderseries and read through these updated materials rst,
because it may supersede information in other documents
• Service Kits for replacement mounting hardware can be obtained by ordering Part #SX-DS-SK-MH
VIII. Technical Assistance
• If you do not understand these instructions or if the unit does not perform as expected, visit surgex.com/ defenderseries or email inquires@surgex.com for further assistance
© SurgeX REV-C Page 5
Page 6
Defender Series Surge + PDU User Manual
IX. Specications
SX-DS-L630-FP SX-DS-L530-FP SX-DS-520-FP SX-DS-IEC-FP
Voltage Rating 120/230 Volts Split Phase 120 Volts Single Phase 120 Volts Single Phase 230 Volts Single Phase
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Load Rating 24 Amp Maximum Capacity 24 Amp Maximum Capacity 20 Amp Maximum Capacity 30 Amp Maximum Capacity
Input Connector NEMA L6-30P NEMA L5-30P NEMA 5-20P IEC-60309 332P65
Output Connector (6) IEC-320 C13 (6) IEC-320 C13 (6) IEC-320 C13 (6) IEC-320 C13
Overload Protection (2) Circuit Breaker (2) Circuit Breaker (2) Circuit Breaker (3) Circuit Breaker
Voltage Protection Rating (VPR)
Power Requirement (no load)
Attenuation
Over-Voltage Shutdown
Response Time 100 msec Over-Voltage 100 msec Over-Voltage 100 msec Over-Voltage
Dimensions
Weight 12.5 lb 12.5 lb 12.5 lb 12.5 lb
Input Cord Length 3 m 3 m 3 m 3 m
Rack Mounting Hardware
Standalone Hardware
Power Indicator LED (Green) LED (Green) LED (Green) LED (Green)
Wiring Fault Indicator
800V Line - Line 500V Line - Ground
8 Watts 8 Watts 8 Watts 8 Watts
Normal Mode: >30dB 50kHz - 50MHz Common Mode: >30dB 150kHz - 50MHz
280 Volts (±2%) Restores at 260 Volts (±2%)
17.44” W x 12.08” D x 1.71” H (1 RU)
Included Included Included Included
Included Included Included Included
LED (Red) Illuminated when no protective Earth Ground present
330V All Modes 330V All Modes
Normal Mode: >30dB 50kHz - 50MHz Common Mode: >30dB 50kHz - 50MHz
150 Volts (±2%) Restores at 135 Volts (±2%)
17.44” W x 12.08” D x 1.71” H (1 RU)
LED (Red) Illuminated when no protective Earth Ground present or when Line/Neutral reversed
Normal Mode: >30dB 50kHz – 50MHz Common Mode: >30dB 50kHz – 50MHz
150 Volts (±2%) Restores at 135 Volts (±2%)
17.44” W x 12.08” D x 1.71” H (1 RU)
LED (Red) Illuminated when no protective Earth Ground present or when Line/Neutral reversed
800V Line - Line 500V Line - Ground
Normal Mode: >30dB 50kHz - 50MHz Common Mode: >30dB 150kHz - 50MHz
280 Volts (±2%) Restores at 260 Volts (±2%)
100 msec Over-Voltage
17.44” W x 12.08” D x 1.71” H (1 RU)
LED (Red) Illuminated when no protective Earth Ground present
BTU/h
Temperature Range 5°C to 40°C 5°C to 40°C 5°C to 40°C 5°C to 40°C
Humidity Range
Agency Listings
 Specications subject to change without notice  All listed specications obtained at an ambient temperature of 25°
100 BTU/h Maximum at full rated load
5% to 95% R.H. Non­condensing
TUV Certied to UL 60950-1 Check surgex.com/ defenderseries for country
specic certications
100 BTU/h Maximum at full rated load
5% to 95% R.H. Non­condensing
TUV Certied to UL 60950-1 Check surgex.com/ defenderseries for country
specic certications
100 BTU/h Maximum at full rated load
5% to 95% R.H. Non­condensing
TUV Certied to UL 60950-1 Check surgex.com/ defenderseries for country
specic certications
140 BTU/h Maximum at full rated load
5% to 95% R.H. Non­condensing
CE/CB Check surgex.com/ defenderseries for country
specic certications
© SurgeX REV-C Page 6