Supermicro FatTwin F628G3-FT+, FatTwin F628G3-FTPT+ User Manual

Page 1
FatTwin
®
F628G3-FT+
F628G3-FTPT+
USER’S MANUAL
Revision 1.0
Page 2
manual, please see our web site at
www.supermicro.com.
Super Micro Computer, Inc. ("Supermicro") reserves the right to make changes to the product described in this manual at any time and without notice. This product, including software and documentation, is the property of Supermicro and/or its licensors, and is supplied only under a license. Any use or reproduction of this product is not allowed, except as expressly permitted by the terms of said license.
IN NO EVENT WILL SUPERMICRO BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, SPECULATIVE OR CONSEQUENTIAL DAMAGES ARISING FROM THE USE OR INABILITY TO USE THIS PRODUCT OR DOCUMENTATION, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. IN PARTICULAR, SUPERMICRO SHALL NOT HAVE LIABILITY FOR ANY HARDWARE, SOFTW ARE, OR DA TA STORED OR USED WITH THE PRODUCT, INCLUDING THE COSTS OF REPAIRING, REPLACING, INTEGRATING, INSTALLING OR RECOVERING SUCH HARDWARE, SOFTWARE, OR DATA.
Any disputes arising between manufacturer and customer shall be governed by the laws of Santa Clara County in the State of California, USA. The State of California, County of Santa Clara shall be the exclusive venue for the resolution of any such disputes. Super Micro's total liability for all claims will not exceed the price paid for the hardware product.
FCC Statement: This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the manufacturer’s instruction manual, may cause harmful interference with radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case you will be required to correct the interference at your own expense.
California Best Management Practices Regulations for Perchlorate Materials: This Perchlorate warning applies only to products containing CR (Manganese Dioxide) Lithium coin cells. “Perchlorate Material-special handling may apply. See
www.dtsc.ca.gov/hazardouswaste/perchlorate
WARNING: Handling of lead solder materials used in this product may expose you to lead, a chemical known to the State of California to cause birth defects and other reproductive harm.
Revision 1.0 Release Date: June 25, 2015
Unless you request and receive written permission from Super Micro Computer, Inc., you may not copy any part of this document.
Information in this document is subject to change without notice. Other products and companies referred to herein are trademarks or registered trademarks of their respective companies or mark holders.
Copyright © 2015 by Super Micro Computer, Inc. All rights reserved.
Printed in the United States of America
Page 3
iii
Preface
Preface
About This Manual
This manual is written for professional system integrators and PC technicians. It provides information for the installation and use of the FatTwin™ F628G3-FT+/FTPT+. Installation and maintainance should be performed by experienced technicians only .
The FatTwin F628G3-FT+/FTPT+ is a high-end server based on the F424AG-R2K04BP 4U rackmount chassis and a dual processor X10DRFF-iG/iTG serverboard. All models have four serverboard nodes, each node with an IPMI LAN port and two (2) hot-swap hot-swap 3.5" SATA Hard Disk Drives (HDD). The only difference between the two server models is that the F628G3-FTPT+ has 10-Gigabit LAN ports, wheras the F628G3-FT+ only has Gigabit LAN ports.
Manual Organization
Chapter 1: Introduction
The fi rst chapter provides a checklist of the main components included with the server system and describes the main features of the X10DRFF-iG/iTG serverboards and the F424AG-R2K04BP chassis.
Chapter 2: Server Installation
This chapter describes the steps necessary to install the FatTwin F628G3-FT+/FTPT+ into a rack and check out the server confi guration prior to powering up the system. If your server was ordered without processor and memory components, this chapter will refer you to the appropriate sections of the manual for their installation.
Chapter 3: System Interface
Refer here for details on the system interface, which includes the functions and information provided by the control panel on the chassis as well as other LEDs located throughout the system.
Chapter 4: Standardized Warning Statements for AC Systems
You should thoroughly familiarize yourself with this chapter for a general overview of safety precautions that should be followed when installing and servicing the FatTwin F628G3-FT+/FTPT+.
Page 4
FatTwin F628G3-FT+/FTPT+ User's Manual
iv
Chapter 5: Advanced Serverboard Setup
Chapter 5 provides detailed information on the X10DRFF-iG/iTG serverboards, including the locations and functions of connections, headers and jumpers. Refer to this chapter when adding or removing processors or main memory and when reconfi guring the serverboard.
Chapter 6: Advanced Chassis Setup
Refer to Chapter 6 for detailed information on the F424AG-R2K04BP server chassis. You should follow the procedures given in this chapter when installing, removing or reconfi guring SATA or peripheral drives and when replacing system power supply units and cooling fans.
Chapter 7: BIOS
The BIOS chapter includes an introduction to BIOS and provides detailed information on running the CMOS Setup Utility.
Appendix A: System Specifi cations
Page 5
v
FatTwin F628G3-FT+/FTPT+ User's Manual
Notes
Page 6
vi
Table of Contents
Chapter 1 Introduction
1-1 Overview .........................................................................................................1-1
1-2 Serverboard Features .....................................................................................1-2
Processors ......................................................................................................1-2
Memory ...........................................................................................................1-2
Serial ATA ....................................................................................................... 1-3
PCI Expansion Slots .......................................................................................1-3
Onboard Controllers/Ports .............................................................................. 1-3
Graphics Controller .........................................................................................1-3
Aspeed AST2400 Controller .......................................................................... 1-3
Other Features Supported by the Aspeed AST2400 Controller ................1-4
Power Supply .................................................................................................. 1-4
Super I/O ......................................................................................................... 1-5
1-3 Server Chassis Features ................................................................................ 1-5
System Power ................................................................................................. 1-5
SATA Subsystem ............................................................................................. 1-5
I/O Ports ..........................................................................................................1-5
Cooling System ............................................................................................... 1-5
Air Shrouds ..................................................................................................... 1-6
Mounting Rails ................................................................................................ 1-6
1-4 Advanced Power Management ....................................................................... 1-6
Intel® Intelligent Power Node Manager (NM) .................................................1-6
Manageability Engine (ME) ............................................................................. 1-6
1-5 Contacting Supermicro ....................................................................................1-8
1-6 Fat Twin: System Notes .................................................................................. 1-9
Nodes ..............................................................................................................1-9
System Power ................................................................................................. 1-9
SATA Backplane/Drives ................................................................................... 1-9
Chapter 2 Server Installation
2-1 Overview .........................................................................................................2-1
2-2 Unpacking the System .................................................................................... 2-1
2-3 Preparing for Setup ......................................................................................... 2-1
2-4 Warnings and Precautions .............................................................................. 2-2
Choosing a Setup Location .............................................................................2-2
Rack Precautions ............................................................................................ 2-2
Server Precautions ..........................................................................................2-2
FatTwin F628G3-FT+/FTPT+ User's Manual
Page 7
vii
Rack Mounting Considerations ....................................................................... 2-3
Ambient Operating Temperature ................................................................ 2-3
Reduced Airfl ow ......................................................................................... 2-3
Mechanical Loading ................................................................................... 2-3
Circuit Overloading ..................................................................................... 2-3
Reliable Ground ......................................................................................... 2-4
2-5 Rack Mounting Instructions .............................................................................2-4
Identifying the Sections of the Rack Rails ...................................................... 2-4
Adjusting the Rails ..........................................................................................2-5
Locking Tabs ................................................................................................... 2-5
Installing the Rails on a Rack ......................................................................... 2-6
Chassis Installation .........................................................................................2-7
2-6 Checking the Serverboard Setup ....................................................................2-8
2-7 Checking the Drive Bay Setup ........................................................................2-9
Chapter 3 System Interface
3-1 Overview .........................................................................................................3-1
3-2 F424AG Front I/O Control Panel .................................................................... 3-1
Control Panel Buttons ..................................................................................... 3-2
3-3 Drive Carrier LEDs .......................................................................................... 3-3
Chapter 4 Standardized Warning Statements for AC Systems
4-1 About Standardized Warning Statements ....................................................... 4-1
Warning Defi nition ...........................................................................................4-1
Installation Instructions ....................................................................................4-4
Circuit Breaker ................................................................................................ 4-5
Power Disconnection Warning ........................................................................ 4-6
Equipment Installation ..................................................................................... 4-8
Restricted Area ................................................................................................ 4-9
Battery Handling ............................................................................................4-10
Redundant Power Supplies .......................................................................... 4-12
Backplane Voltage ........................................................................................4-13
Comply with Local and National Electrical Codes ........................................ 4-14
Product Disposal ........................................................................................... 4-15
Hot Swap Fan Warning .................................................................................4-16
Power Cable and AC Adapter ...................................................................... 4-18
Table of Contents
Page 8
viii
Chapter 5 Advanced Serverboard Setup
5-1 Handling the Serverboard ............................................................................... 5-1
Precautions .....................................................................................................5-1
Unpacking .......................................................................................................5-1
5-2 Connecting Cables .......................................................................................... 5-2
Connecting Data Cables ................................................................................. 5-2
5-3 Control Panel Connectors and I/O Ports ........................................................ 5-2
5-4 Processor and Heatsink Installation................................................................5-3
Installing a Passive CPU Heatsink ................................................................. 5-7
Removing the Passive Heatsink ..................................................................... 5-8
5-5 Installing Memory ............................................................................................5-9
Removing Memory Modules ........................................................................... 5-9
Memory Support ............................................................................................5-10
5-6 Serverboard Details ...................................................................................... 5-12
5-7 Connector Defi nitions ....................................................................................5-15
5-8 Jumper Settings ............................................................................................ 5-19
Explanation of Jumpers ................................................................................ 5-19
5-9 Onboard Indicators ........................................................................................5-22
5-10 Serial ATA and SAS Connections .................................................................5-24
5-11 Installing Drivers ............................................................................................5-25
SuperDoctor 5 ............................................................................................... 5-26
5-12 Serverboard Battery ......................................................................................5-28
Chapter 6 Advanced Chassis Setup
6-1 Static-Sensitive Devices ..................................................................................6-1
Precautions .....................................................................................................6-1
Unpacking .......................................................................................................6-1
6-2 Control Panel ..................................................................................................6-2
6-3 Removing the Power Cord ..............................................................................6-3
6-4 Removing Nodes from the Chassis ................................................................ 6-3
6-5 Installing and Removing Hard Drives ............................................................. 6-4
Removing Hard Drives from the Front of the Node ........................................6-5
Installing 3.5" Hard Drives into the Drive Carriers ..........................................6-6
6-6 Node Confi gurations ....................................................................................... 6-8
6-7 Removing the Node Cover..............................................................................6-9
6-8 Removing and Installing the Backplane ........................................................6-10
Removing the Backplane .............................................................................. 6-10
Installing the Backplane .................................................................................6-11
6-9 Power Distributor Board Replacement ..........................................................6-12
FatTwin F628G3-FT+/FTPT+ User's Manual
Page 9
6-10 Installing the Serverboard ............................................................................ 6-14
Compatible Motherboards ............................................................................. 6-14
Permanent and Optional Standoffs ...............................................................6-14
6-11 Installing Front and Rear Expansion Cards .................................................. 6-16
PCI-E Slot Setup ........................................................................................... 6-16
F424AG PCI-E Slot Confi gurations ............................................................... 6-16
Installing a Low-Profi le Expansion Card ....................................................... 6-17
6-12 Installing Internal GPUs ................................................................................6-18
Installing a Front Nvidia GPUs/Intel Xeon Phi into the GPU Bracket ......... 6-18
Installing a Front Nvidia GPUs/Intel Xeon Phi into the Node ......................6-18
Installing Rear Nvidia GPUs/Intel Xeon Phi into the Bracket ...................... 6-19
Installing Rear Nvidia GPUs/Intel Xeon Phi into a Node ............................ 6-20
6-13 Installing the Air Shroud ................................................................................6-21
Air Shrouds ................................................................................................... 6-21
6-14 Checking the Airfl ow ....................................................................................6-22
Installation Complete .....................................................................................6-22
6-15 Replacing System Fans ................................................................................ 6-23
6-16 Replacing the Power Supply .........................................................................6-24
Power Supply Replacement ..........................................................................6-24
Chapter 7 BIOS
7-1 Introduction ......................................................................................................7-1
Starting BIOS Setup Utility ..............................................................................7-1
How To Change the Confi guration Data ......................................................... 7-1
Starting the Setup Utility .................................................................................7-2
7-2 Main Setup ...................................................................................................... 7-2
7-3 Advanced Setup Confi gurations...................................................................... 7-3
7-4 Event Logs .................................................................................................... 7-41
7-5 IPMI ............................................................................................................... 7-43
7-6 Security Settings ........................................................................................... 7-45
7-7 Boot Settings ................................................................................................. 7-46
7-8 Save & Exit ................................................................................................... 7-48
Appendix A System Specifi cations
ix
Table of Contents
Page 10
x
Notes
FatTwin F628G3-FT+/FTPT+ User's Manual
Page 11
Chapter 1
Introduction
1-1 Overview
The FatTwin F628G3-FT+/FTPT+ is a high-end server comprised of four main subsystems: the F424AG-R2K04BP 4U server chassis and the X10DRFF-iG/iTG dual processor serverboard in four hot-swap nodes. Please refer to our web site for information on operating systems that have been certifi ed for use with the system (www.supermicro.com).
In addition to the serverboard and chassis, various hardware components have been included with the SuperServer F628G3-FT+/FTPT+ server, as listed below:
Heatsinks:
Four (4) 1U passive high-performance CPU heat sinks with narrow ILM (SNK-P0057PS) Four (4) 1U passive CPU heat sinks with narrow ILM (SNK-P0047PSC)
Four (4) air shrouds for F424AG/BG chassis (MCP-310-42405-0B)
Four (4) Air blocks for F424AG/BG systems (MCP-310-42406-0B)
Power Adapter Boards:
Four (4) FatTwin power adapter boards (BPN-ADP-F418L-O-P) Four (4) FatTwin 2U GPU power adapter boards (BPN-ADP-2UGPU-O-P)
SATA Backplane:
Four (4) 10-cm and 7-cm 18AWG 8-pin male to two 4-pin male power cables (CBL-0460L-02) Four (4) 35-cm 16AWG 8-pin female to 8-pin female 12V CPU power cables (CBL-PWEX-0705) Eight (8) 21-cm 30AWG SATA S-S cables (CBL-0473L) Eight (8) black hot swap 3.5" HDD trays (MCP-220-00094-0B)
Riser Cards:
Four (4) riser cards (RSC-F2F-6-O-P) Four (4) riser cards (RSC-R2UFF-2E16B-O-P)
One (1) F418/F424 rail set (MCP-290-41803-0N)
Chapter 1: Introduction
1-1
Page 12
1-2
FatTwin F628G3-FT+/FTPT+ User's Manual
Note: For your system to work properly, please follow the links below to download all necessary drivers/utilities and the user’s manual for your server.
Supermicro product manuals: http://www.supermicro.com/support/manuals/
Product drivers and utilities: ftp://ftp.supermicro.com
Product safety information:
http://www.supermicro.com/about/policies/safety_information.cfm
If you have any questions, please contact our support team at:
support@supermicro.com
1-2 Serverboard Features
At the heart of the FatTwin F628G3-FT+/FTPT+ lies the X10DRFF-iG/iTG, a dual processor serverboard based on the Intel® C612 chipset and designed to provide maximum performance. Two of these serverboards can be mounted in the F424AG-R2K04BP chassis.
The sections below cover the main features of the X10DRFF-iG/iTG serverboard (see Figure 1-1 for a block diagram of the chipset).
Processors
The X10DRFF-iG/iTG supports single or dual Intel® Xeon® E5-2600 v3 family processors (Socket R3 LGA 2011). Each processor supports four full-width Intel QuickPath Interconnect (QPI) links, with support of up to 25.6 GT/s per QPI link and with Data Transfer Rate of up to 9.6 GT/s per direction. Please refer to the serverboard description pages on our web site for a complete listing of supported processors (www.supermicro.com).
Memory
Each X10DRFF-iG/iTG serverboard node has sixteen (16) DIMM slots supporting up to 1 TB of LRDIMM registered ECC or up to 512 GB of RDIMM ECC at DDR4-2133/1866/1600 MHz speeds and up to 4 GB, 8 GB, 16 GB or 32 GB sizes at 1.2V voltages. See Chapter 5 for details.
Note: For the latest CPU/memory updates, please refer to our website at
http://www.supermicro.com/products/serverboard.
Page 13
1-3
Chapter 1: Introduction
Serial ATA
A Serial ATA controller is integrated into the C612 to provide up to ten (10) SATA
3.0 connections, including six (6) SATA 3.0 ports supported by Intel PCH (I-SATA 0-5) and four (4) SATA 3.0 with 4 connections supported by the PCH (S-SATA 0-3) .
These drives support RAID 0, 1, 5 and 10 capabiltiy. The SATA drives are hot­swappable units.
Note: The operati ng system yo u use must h ave R AID su ppor t to e nable t he hot­swap capability and RAI D function of the SATA drives.
PCI Expansion Slots
Each node in the the FatTwin F628G3-FT+/FTPT+ server has the following available PCI-E slots for the node:
1x PCI-E 3.0 x16 slot
2x PCI-E 3.0 x8 low-pro le, half-length slots
1x PCI-E 3.0 x32 right riser slot
Onboard Controllers/Ports
One Fast UART 16550 serial port is located on the serverboard. The I/O ports include one VGA (monitor) port, two USB 3.0 ports, an IPMI dedicated LAN port and either two Gigabit or two 10GBased-T Ethernet ports.
Note: For IPMI Confi guration Instructions, please refer to the Embedded IPMI Configuration User's Guide available at http://www.supermicro.com/support/
manuals/.
Graphics Controller
The X10DRFF-iG/iTG features an integrated Aspeed AST2400 BMC Controller for onboard graphics capability.
Aspeed AST2400 Controller
Note: The term "IPMI controller" and the term "BMC controller" can be used
interchangeably in this section. The Aspeed AST2400 Controller, a Baseboard Management Controller (BMC),
supports 2D/VGA-compatible Graphic Cores with PCI interface, creating multi-media virtualization via Keyboard/Video/Mouse Redirection (KVMR). The WPCM450R Controller is ideal for remote system management.
Page 14
1-4
FatTwin F628G3-FT+/FTPT+ User's Manual
The Aspeed AST2400 Controller interfaces with the host system via PCI connections to communicate with the graphics cores. It supports USB 3.0 and 2.0 for remote keyboard/mouse/virtual media emulation. It also provides LPC interface support to control Super IO functions. The Aspeed AST2400 is connected to the network via an external Ethernet PHY module or shared NCSI connections.
The Aspeed AST2400 communicates with onboard components via six SMBus interfaces, PECI (Platform Environment Control Interface) buses, and General Purpose I/O ports.
Other Features Supported by the Aspeed AST2400 Controller
The Aspeed AST2400 supports the following features:
IPMI 2.0
Serial over LAN
KVM over LAN
LAN Alerting-SNMP Trap
Event Log
X-Bus parallel interface for I/O expansion
Multiple ADC inputs, Analog and Digital Video outputs
SPI Flash Host BIOS and rmware bootstrap program supported
Reduced Media Independent Interface (RMII)
OS (Operating System) Independency
Provides remote Hardware Health Monitoring via IPMI. Key features
Provides Network Management Security via remote access/console redirection.
Supports the following Management tools: IPMIView, CLI (Command Line
Interface)
RMCP+ protocol supported
Note: For more information on IPMI confi guration, please refer to the IPMI User's Guide posted on our website at http://www.supermicro.com/support/manuals/.
Power Supply
Please connect the power cable from the SMC-Proprietary Adaptor (BPN-ADP­F418L) to the serverboard in order to provide power to the system.
Page 15
1-5
Chapter 1: Introduction
Super I/O
The Super I/O provides functions that comply with ACPI (Advanced Confi guration and Power Interface), which includes support of legacy and ACPI power management through an SMI or SCI function pin. It also features auto power management to reduce power consumption.
1-3 Server Chassis Features
The following is a general outline of the main features of the F424AG server chassis.
System Power
The F424AG chassis model includes four high-effi ciency 96%+ Titanium certifi ed redundant 2000 Watt power supplies. In the unlikely event your power supply fails, replacement is simple and can be accomplished without tools.
SATA Subsystem
Each node in F424AG chassis supports two (2) hot-swap 3.5" SATA drives in trays for for a total of eight (8) drives in the system. These drives are hot-swappable units and are connected to backplanes (that provides power and control).
Note: The operating system you use must have RAID support to enable the hot-swap capability of the drives. For more information, visit our Web site at:
http://www.supermicro.com.
I/O Ports
The F424AG is an proprietary form factor chassis designed to be used in a 4U rackmount confi guration. The F424AG chassis provides two low-profi le add-on card slots, a VGA port, two USB 3.0 ports, one IPMI Ethernet port and either two Gigabit (F628G3-FT+) or 10-Gigabit (F628G3-FTPT+) Ethernet ports per node.
Cooling System
The F424AG chassis accepts eight (8) 8-cm system fans powered from either the backpane or the serverboards. When one of the serverboard nodes is removed, another serverboard will continue to operate the fans.
Page 16
1-6
FatTwin F628G3-FT+/FTPT+ User's Manual
Air Shrouds
The F424AG chassis requires mylar air shrouds for each node to direct the airfl ow where cooling is needed. The air shroud will differ for different motherboards. If using a serverboard which is not the default in the chassis, refer to the optional parts in the Appendix of this manual, or the Supermicro Web site at
www.supermicro.com
to puchase the proper air shroud.
Mounting Rails
The F424AG includes a set of rails, and can be placed in a rack for secure storage and use. To setup your rack, follow the step-by-step instructions included in this manual.
1-4 Advanced Power Management
Intel® Intelligent Power Node Manager (NM)
The Intel® Intelligent Power Node Manager (IPNM) provides your system with real-time thermal control and power management for maximum energy effi ciency. Although IPNM Specifi cation Version 1.5 is supported by the BMC (Baseboard Management Controller), your system must also have IPNM-compatible Manageability Engine (ME) fi rmware installed to use this feature.
Manageability Engine (ME)
The Manageability Engine, which is an ARC controller embedded in the IOH (I/O Hub), provides Server Platform Services (SPS) to your system. The services provided by SPS are different from those proveded by the ME on client platforms.
Page 17
1-7
Chapter 1: Introduction
Figure 1-1. Intel C612 Chipset:
System Block Diagram
Note: This is a general block diagram and may not exactly repre-
sent the features on your serverboard. See the previous pages for
the actual specifi cations of your serverboard. This block diagram is
intended for your reference only.
SPI
LAN3
RGRMII
Debug Card
FRONT PANEL
SYSTEM POWER
CTRL
FAN SPEED
PCI-E X1 G2
USB 2.0
X10DRFF-iG Rev. 1.00
PCH
6.0 Gb/S
LPC
SATA
RTL8211E
-VB-CG
RJ45
BIOS
SPI
SPI
Temp Sensor
EMC1402-1 *2 at di SMBUS
TPM HEADER
USB 3.0
USB
BIOS
HEADER
SPI
AST2400
BMC
RMII/NCSI
COM1
VGA CONN
BMC Boot Flash
DDR3
5 PHASE 145W
P1
P1
P0
VR12.5
P0
QPI
9.6G
DMI2
PCI-E X16 G3
DMI2
DMI2
SNB CORE
DDR4
SNB CORE
DDR4
QPI
9.6G
5 PHASE 145W
VR12.5
#3
I350/ X540
LAN
PCI-E X8
SBX2 PCI-E X16 X16 Proprietary Slot
SLOT2 PCI-E x8
PCI-E X8 G3
PCI-E X16 G3
PCI-E X16 G3
#1
#2-8
SXB1; PCI-E X16 Proprietary Slot
PCI-E X8 G3
Slot1 PCI-E X8
SLOT3 PCI-E X4 in X8
PCI-E X4 G2
LSI3008
SAS3
PCI-E X8 G3
Port 4-7
AHCI
SCU
6.0 Gb/S
#2 #3A #1 #2 #3
CPU1
CPU2
#2-7
#2-6
#2-5
#2-4
#2-3
#2-2
1600/2133
DDR4
#2-1
1600/2133
DDR4
#1-4
#1-3
#1-2
#1-1
#1-5
#1-6
#1-7
#1-8
Header
Mini SAS
Port 0-3
0-5
SATA
0-3
RJ45
RJ45
HD
Mini SAS
HD
Page 18
1-8
FatTwin F628G3-FT+/FTPT+ User's Manual
1-5 Contacting Supermicro
Headquarters
Address: Super Micro Computer, Inc.
980 Rock Ave.
San Jose, CA 95131 U.S.A. Tel: +1 (408) 503-8000 Fax: +1 (408) 503-8008 Email: marketing@supermicro.com (General Information)
support@supermicro.com (Technical Support) Website:
www.supermicro.com
Europe
Address: Super Micro Computer B.V.
Het Sterrenbeeld 28, 5215 ML
's-Hertogenbosch, The Netherlands Tel: +31 (0) 73-6400390 Fax: +31 (0) 73-6416525 Email: sales@supermicro.nl (General Information)
support@supermicro.nl (Technical Support)
rma@supermicro.nl (Customer Support) Website:
www.supermicro.nl
Asia-Pacifi c
Address: Super Micro Computer, Inc.
3F, No. 150, Jian 1st Rd.
Zhonghe Dist., New Taipei City 235
Taiwan (R.O.C) Tel: +886-(2) 8226-3990 Fax: +886-(2) 8226-3992 Email: support@supermicro.com.tw Website:
www.supermicro.com.tw
Page 19
1-9
Chapter 1: Introduction
1-6 Fat Twin: System Notes
As a FatTwin confi guration, the FatTwin F628G3-FT+/FTPT+ is a unique server system. With four system boards incorporated into a single chassis acting as four separate nodes, there are several points you should keep in mind.
Nodes
Each of the four serverboards act as a separate node in the system. As independant nodes, each may be powered off and on without affecting the others. In addition, each node is a hot-swappable unit that may be removed from the rear of the chassis. The nodes are connected to the server backplane by means of an adapter card.
Note: A guide pin is located between the upper and lower nodes on the inner chassis wall. This guide pin also acts as a “stop” when a node is fully installed. If too much force is used when inserting a node this pin may break off. Take care to slowly slide a node in until you hear the “click” of the locking tab seating itself.
System Power
Four 2000 Watt power supplies are used to provide the power for all serverboards. Each serverboard however, can be shut down independently of the other with the power button on its own control panel.
SATA Backplane/Drives
As a system, the FatTwin F628G3-FT+/FTPT+ supports the use of eight (8) 3.5" Hot-swap SATA drives. Each of the four backplanes in the system works to apply system-based control for power and fan speed functions, yet at the same time logically connects a set of two (2) hot-swap SATA drives to each backplane/ serverboard. Consequently, RAID setup is limited to a two drive scheme (RAID cannot be spread across all drives). See Chapter 6 for the logical hard drive and node confi guration.
Page 20
1-10
FatTwin F628G3-FT+/FTPT+ User's Manual
Notes
Page 21
Chapter 2: Server Installation
2-1
Chapter 2
Server Installation
2-1 Overview
This chapter provides a quick setup checklist to get your FatTwin F628G3-FT+/­FTPT+ up and running. Following these steps in the order given should enable you to have the system operational within a minimum amount of time. This quick setup assumes that your system has come to you with the processors and memory preinstalled. If your system is not already fully integrated with a serverboard, processors, system memory etc., please turn to the chapter or section noted in each step for details on installing specifi c components.
2-2 Unpacking the System
You should inspect the box the FatTwin F628G3-FT+/-FTPT+ was shipped in and note if it was damaged in any way. If the server itself shows damage you should le a damage claim with the carrier who delivered it.
Decide on a suitable location for the rack unit that will hold the FatTwin F628G3­FT+/-FTPT+. It should be situated in a clean, dust-free area that is well ventilated. Avoid areas where heat, electrical noise and electromagnetic fi elds are generated. You will also need it placed near a grounded power outlet. Read the Rack and Server Precautions in the next section.
2-3 Preparing for Setup
The box the FatTwin F628G3-FT+/-FTPT+ was shipped in should include two sets of rail assemblies, two rail mounting brackets and the mounting screws you will need to install the system into the rack. Follow the steps in the order given to complete the installation process in a minimum amount of time. Please read this section in its entirety before you begin the installation procedure outlined in the sections that follow.
Page 22
2-2
FatTwin F628G3-FT+/-FTPT+ User's Manual
2-4 Warnings and Precautions
Choosing a Setup Location
Leave enough clearance in front of the rack to enable you to open the front door
completely (~25 inches) and approximately 30 inches of clearance in the back of the rack to allow for suffi cient airfl ow and ease in servicing.
This product is for installation only in a Restricted Access Location (dedicated
equipment rooms, service closets and the like).
This product is not suitable for use with visual display work place devices
acccording to §2 of the the German Ordinance for Work with Visual Display Units.
Rack Precautions
Ensure that the leveling jacks on the bottom of the rack are fully extended to
the fl oor with the full weight of the rack resting on them.
In single rack installation, stabilizers should be attached to the rack. In multiple
rack installations, the racks should be coupled together.
Always make sure the rack is stable before extending a component from the
rack.
You should extend only one component at a time - extending two or more
simultaneously may cause the rack to become unstable.
Server Precautions
Review the electrical and general safety precautions in Chapter 4.
Determine the placement of each component in the rack before you install the
rails.
Install the heaviest server components on the bottom of the rack fi rst, and then
work up.
Use a regulating uninterruptible power supply (UPS) to protect the server from
power surges, voltage spikes and to keep your system operating in case of a power failure.
Allow any hot plug drives and power supply modules to cool before touching
them.
Always keep the rack's front door and all panels and components on the servers
closed when not servicing to maintain proper cooling.
Page 23
Chapter 2: Server Installation
2-3
Rack Mounting Considerations
Warning! To prevent bodily injury when mounting or servicing this unit in a
rack, you must take special precautions to ensure that the system remains stable. The following guidelines are provided to ensure your safety:
This unit should be mounted at the bottom of the rack if it is the only unit in
the rack.
When mounting this unit in a partially fi lled rack, load the rack from the bottom
to the top with the heaviest component at the bottom of the rack.
If the rack is provided with stabilizing devices, install the stabilizers before
mounting or servicing the unit in the rack.
Ambient Operating Temperature
If installed in a closed or multi-unit rack assembly, the ambient operating temperature of the rack environment may be greater than the ambient temperature of the room. Therefore, consideration should be given to installing the equipment in an environment compatible with the manufacturer’s maximum rated ambient temperature (Tmra).
Reduced Airfl ow
Equipment should be mounted into a rack so that the amount of airfl ow required for safe operation is not compromised.
Mechanical Loading
Equipment should be mounted into a rack so that a hazardous condition does not arise due to uneven mechanical loading.
Circuit Overloading
Consideration should be given to the connection of the equipment to the power supply circuitry and the effect that any possible overloading of circuits might have on overcurrent protection and power supply wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing this concern.
Page 24
2-4
FatTwin F628G3-FT+/-FTPT+ User's Manual
Reliable Ground
A reliable ground must be maintained at all times. To ensure this, the rack itself should be grounded. Particular attention should be given to power supply connections other than the direct connections to the branch circuit (i.e. the use of power strips, etc.).
2-5 Rack Mounting Instructions
This section provides information on installing the chassis into a rack unit with the rails provided. There are a variety of rack units on the market, which may mean that the assembly procedure will differ slightly from the instructions provided. You should also refer to the installation instructions that came with the rack unit you are using.
Note: This rail will fi t a rack between 26.5" and 36.4" deep. The SCF418 is not designed for installation into a Telco post-style rack unit.
Warning: Do not pick up the server with the front handles. They are designed
to pull the system from a rack only.
Stability Hazard: The rack stabilizing mechanism must be in place, or the rack must be bolted to the fl oor before you slide the unit out for servicing. Failure to stabilize the rack can cause the rack to tip over.
Warning: Slide rail mounted equipment is not to be used as a shelf or a work space.
Warning: When initially installing the server to a rack, test that the rail locking tabs engage to prevent the server from being overextended. Have a rack lift in place as a precaution in case the test fails.
Warning: In any instance of pulling the system from the rack, always use a rack lift and follow all associated safety precautions.
Identifying the Sections of the Rack Rails
The chassis package includes two rail assemblies in the rack mounting kit. Each assembly consists of two sections: A front section which secures to the front post of the rack and a rear section which adjusts in length and secures to the rear post of the rack. These assemblies are specifi cally designed for the left and right side of the chassis (see Figure 2-1).
Page 25
Chapter 2: Server Installation
2-5
Figure 2-1: Identifying the Outer Rail and Inner Rails
(Left Rail Assembly Shown)
Inner Rail
This Side Faces
Outward
Adjusting Screw
Outer Rail
Locking Tab
Adjusting the Rails
Each rail assembly has an adjusting screw. loosening this screw allows you to adjust the length of the rail to fi t a variety of rack sizes.
Locking Tabs
Each inner rail has a locking tab. This tab locks the chassis into place when installed and pushed fully into the rack. These tabs also lock the chassis in place when fully extended from the rack. This prevents the server from coming completely out of the rack when when the chassis is pulled out for servicing.
Page 26
2-6
FatTwin F628G3-FT+/-FTPT+ User's Manual
Installing the Rails on a Rack
Installing the Rails
1. Adjust the length of both rails as described on the previous page.
2. Align the front section of the outer rail with the slots on the front post of the rack. Secure the front of the outer rail to the rack with two screws.
3. Pull out the rear section of the outer rail, adjusting the length until it fi ts within the posts of the rack.
4. Align the rear section of the rail with the slots on the rear post of the rack. Secure the rear of the outer rail to the rear of the rack with two screws.
5. Repeat steps 1-4 for the remaining rail.
Figure 2-2: Attaching the Rails to a Rack
Page 27
Chapter 2: Server Installation
2-7
Note: The fi gure above is for illustration purposes only. Always install servers to the bottom of the rack fi rst.
Figure 2-3: Installing into a Rack
Chassis Installation
Installing the Chassis into a Rack
1. Confi rm that the rails are correctly installed on the rack.
2. Align the bottom of the chassis with the bottom of the rails.
3. Insert the chassis into the rails, keeping the pressure even on both sides, pushing the chassis into the rack until it clicks into the locked position.
4. Secure the chassis handles to the front of the rack.
Page 28
2-8
FatTwin F628G3-FT+/-FTPT+ User's Manual
2-6 Checking the Serverboard Setup
After you install the FatTwin F628G3-FT+/-FTPT+ in the rack, you will need to open the unit to make sure the serverboard is properly installed and all the connections have been made.
Accessing the inside of the System
Before operating the server for the rst time, it is important to remove the protective lm covering the top of the chassis, in order to allow for proper ventilation and
cooling.
Warning: Except for short periods of time, do NOT operate the server without the cover in place. The chassis cover must be in place to allow proper airfl ow and prevent overheating.
Checking the Components and Setup
1. You may have one or two processors already installed into the serverboard. Each processor needs its own heat sink. See Chapter 5 for instructions on processor and heat sink installation.
2. Your FatTwin F628G3-FT+/-FTPT+ server system may have come with system memory already installed. Make sure all DIMMs are fully seated in their slots. For details on adding system memory, refer to Chapter 5.
3. If desired, you can install add-on cards to the system. See Chapter 5 for details on installing PCI add-on cards.
4. Make sure all power and data cables are properly connected and not blocking the chassis airfl ow. Also make sure that no cables are positioned in front of the fans. See Chapter 5 for details on cable connections.
Page 29
Chapter 2: Server Installation
2-9
2-7 Checking the Drive Bay Setup
Next, you should check to make sure the peripheral drives and the SATA drives have been properly installed and all connections have been made.
Checking the Drives
1. All drives are accessable from the front of the server. A hard drive can be installed and removed from the front of the chassis without removing the top chassis cover.
2. Depending upon your system's confi guration, your system may have one or more drives already installed. If you need to install hard drives, please refer to Chapter 6.
Checking the Airfl ow
1. Make sure there are no objects to obstruct airfl ow in and out of the server. In addition, if you are using a front bezel, make sure the bezel's fi lter is replaced periodically.
2. Do not operate the server without drives or drive trays in the drive bays. Use only recommended server parts.
3. Make sure that no wires or foreign objects obstruct air fl ow through the chassis. Pull all excess cabling out of the airfl ow path or use shorter cables. The control panel LEDs inform you of the system status. See “Chapter 3 System Interface” for details on the LEDs and the control panel buttons.
Providing Power
1. Plug the power cord(s) from the power supply unit(s) into a high-quality power strip that offers protection from electrical noise and power surges. It is recommended that you use an uninterruptible power supply (UPS).
2. Depress the power on button on the front of the chassis.
Page 30
2-10
FatTwin F628G3-FT+/-FTPT+ User's Manual
Notes
Page 31
Chapter 3: System Interface
3-1
Chapter 3
System Interface
3-1 Overview
There are several buttons and LEDs are located on each of the serverboard nodes and on the drive carriers to keep you constantly informed of the overall status of the system.
This chapter explains the meanings of all LED indicators and the appropriate re­sponse you may need to take.
3-2 F424AG Front I/O Control Panel
Figure 3-1: F424AG Front I/O Control Panel
Page 32
FatTwin F628G3-FT+/FTPT+ User's Manual
3-2
Control Panel Buttons
Power: The main power button on each of the four control panels is used to
apply or remove power from the power supply to each of the four systems in the chassis. Turning off system power with this button removes the main power, but keeps standby power supplied to the system. Therefore, you must unplug system before servicing. The power button has a built-in LED which will turn green when the power is on
UID: When used with a UID compatible serverboard, the UID button is used
to turn on or off the blue light function of the LED. This is built into the front side of the UID button and at the rear end of each serverboard node, for those motherboards which support it. Once the blue light is activated, the unit can be easily located in very large racks and server banks.
Page 33
Chapter 3: System Interface
3-3
3-3 Drive Carrier LEDs
The chassis includes externally accessible SAS/SATA drives. Each drive carrier displays two status LEDs on the front of the carrier.
LED Color State Status
Activity LED
Green Solid On SAS drive installed Green Blinking I/O activity
Status LED
Red Solid On Failed drive for SAS/SATA with RSTe
support
Red Blinking at 1 Hz Rebuild drive for SAS/SATA with RSTe
support
Red Blinking with two blinks
and one stop at 1 Hz
Hot spare for SAS/SATA with RSTe support
Red On for fi ve seconds,
then off
Power on for SAS/SATA with RSTe support
Red Blinking at 4 Hz Identify drive for SAS/SATA with RSTe
support
Page 34
FatTwin F628G3-FT+/FTPT+ User's Manual
3-4
Notes
Page 35
4-1
Chapter 4: Warning Statements for AC Systems
Chapter 4
Standardized Warning Statements for AC Systems
4-1 About Standardized Warning Statements
The following statements are industry standard warnings, provided to warn the user of situations which have the potential for bodily injury. Should you have questions or experience difficulty, contact Supermicro's Technical Support department for assistance. Only certifi ed technicians should attempt to install or confi gure components.
Read this appendix in its entirety before installing or confi guring components in the Supermicro chassis.
These warnings may also be found on our web site at http://www.supermicro.com/ about/policies/safety_information.cfm.
Warning Defi nition
Warning!
This warning symbol means danger. You are in a situation that could cause bodily injury. Before you work on any equipment, be aware of the hazards involved with electrical circuitry and be familiar with standard practices for preventing accidents.
警告の定義
この警告サインは危険を意味します。
人身事故につながる可能性がありますので、いずれの機器でも動作させる前に、
電気回路に含まれる危険性に注意して、標準的な事故防止策に精通して下さい。
此警告符号代表危险。
您正处于可能受到严重伤害的工作环境中。在您使用设备开始工作之前,必须充分 意识到触电的危险,并熟练掌握防止事故发生的标准工作程序。请根据每项警告结 尾的声明号码找到此设备的安全性警告说明的翻译文本。
此警告符號代表危險。
您正處於可能身體可能會受損傷的工作環境中。在您使用任何設備之前,請注意觸 電的危險,並且要熟悉預防事故發生的標準工作程序。請依照每一注意事項後的號 碼找到相關的翻譯說明內容。
Page 36
4-2
FatTwin F628G3-FT+/FTPT+ User's Manual
Warnung WICHTIGE SICHERHEITSHINWEISE Dieses Warnsymbol bedeutet Gefahr. Sie befi nden sich in einer Situation, die zu
Verletzungen führen kann. Machen Sie sich vor der Arbeit mit Geräten mit den Gefahren elektrischer Schaltungen und den üblichen Verfahren zur Vorbeugung vor Unfällen vertraut. Suchen Sie mit der am Ende jeder Warnung angegebenen Anweisungsnummer nach der jeweiligen Übersetzung in den übersetzten Sicherheitshinweisen, die zusammen mit diesem Gerät ausgeliefert wurden.
BEWAHREN SIE DIESE HINWEISE GUT AUF.
INSTRUCCIONES IMPORTANTES DE SEGURIDAD Este símbolo de aviso indica peligro. Existe riesgo para su integridad física. Antes
de manipular cualquier equipo, considere los riesgos de la corriente eléctrica y familiarícese con los procedimientos estándar de prevención de accidentes. Al nal de cada advertencia encontrará el número que le ayudará a encontrar el texto traducido en el apartado de traducciones que acompaña a este dispositivo.
GUARDE ESTAS INSTRUCCIONES.
IMPORTANTES INFORMATIONS DE SÉCURITÉ Ce symbole d'avertissement indique un danger. Vous vous trouvez dans une
situation pouvant entraîner des blessures ou des dommages corporels. Avant de travailler sur un équipement, soyez conscient des dangers liés aux circuits électriques et familiarisez-vous avec les procédures couramment utilisées pour éviter les accidents. Pour prendre connaissance des traductions des avertissements gurant dans les consignes de sécurité traduites qui accompagnent cet appareil, référez-vous au numéro de l'instruction situé à la fi n de chaque avertissement.
CONSERVEZ CES INFORMATIONS.
ןונקת תורהצהאהרהז
ןה תואבה תורהצהא ינפמ שמתשמה תא ריהזהל תנמ לע ,היישעתה ינקת יפ לע תורהז הלבח
ה וא תולאש שיו הדימב .תירשפא תיזיפי ,יהשלכ היעבב תולקתרוציל שי הכימת תקלחמ םע רשק
רידגהל וא ןיקתהל םיאשר דבלב םיכמסומ םיאנכט .ורקימרפוס לש תינכט תאה .םיביכר
אורקל שי .ורקימרפוס יזראמב םיביכרה
תרדגה וא תנקתה ינפל ואולמב חפסנה תא
Page 37
4-3
Warning Statements for AC Systems
안전을 위한 주의사항
경고!
이 경고 기호는 위험이 있음을 알려 줍니다. 작업자의 신체에 부상을 야기 할 수 있는 상태에 있게 됩니다. 모든 장비에 대한 작업을 수행하기 전에 전기회로와 관련된 위험요소들을 확인하시고 사전에 사고를 방지할 수 있도록 표준 작업절차를 준수해 주시기 바랍니다.
해당 번역문을 찾기 위해 각 경고의 마지막 부분에 제공된 경고문 번호를 참조하십시오
BELANGRIJKE VEILIGHEIDSINSTRUCTIES Dit waarschuwings symbool betekent gevaar. U verkeert in een situatie die
lichamelijk letsel kan veroorzaken. Voordat u aan enige apparatuur gaat werken, dient u zich bewust te zijn van de bij een elektrische installatie betrokken risico's en dient u op de hoogte te zijn van de standaard procedures om ongelukken te voorkomen. Gebruik de nummers aan het eind van elke waarschuwing om deze te herleiden naar de desbetreffende locatie.
BEWAAR DEZE INSTRUCTIES
. ﻲﻓ ﻚﻧﺍ ﻥﺃ ﻦﻜﻤﻳ ﺔﻟﺎﺣ ﻲﻓ ﺐﺒﺴﺘﺗ ﺔﺑﺎﺻﺍ ﺔﻳﺪﺴﺟ ﺰﻣﺮﻟﺍ ﺍﺬﻫ ﻲﻨﻌﻳ ﺮﻄﺧ !ﺮﻳﺬﺤﺗ
ﻥﺃ ﻞﺒﻗ ﻱﺃ ﻰﻠﻋ ﻞﻤﻌﺗ ﺕﺍﺪﻌﻣ،ﻛﻢﻠﻋ ﻰﻠﻋ ﻦﻋ ﺔﻤﺟﺎﻨﻟﺍ ﺮﻁﺎﺨﻤﻟﺎﺑ ﺮﺋﺍﻭﺪﻟﺍ
ﺔﻴﺋﺎﺑﺮﻬﻜﻟﺍ
ﻛﻭﺔﻳﺍﺭﺩ ﻰﻠﻋ ﻦ ﺭﺎﻤﻤﻟﺎﺑﺕﺎﺳ ﺔﻴﺋﺎﻗﻮﻟﺍ ﻊﻨﻤﻉﻮﻗﻭ ﻱﺃﺙﺩﺍﻮﺣ
ﻢﻗﺭ ﻡﺪﺨﺘﺳﺍ ﻥﺎﻴﺒﻟﺍ ﺹﻮﺼﻨﻤﻟﺍ ﺔﻳﺎﻬﻧ ﻲﻓ ﺮﻳﺬﺤﺗ ﻞﻛ ﺭﻮﺜﻌﻠﻟ ﺎﻬﺘﻤﺟﺮﺗ
Page 38
4-4
FatTwin F628G3-FT+/FTPT+ User's Manual
Installation Instructions
Warning!
Read the installation instructions before connecting the system to the power source.
設置手順書 システムを電源に接続する前に、設置手順書をお読み下さい。
警告
将此系统连接电源前,请先阅读安装说明。
警告
將系統與電源連接前,請先閱讀安裝說明。
Warnung Vor dem Anschließen des Systems an die Stromquelle die Installationsanweisungen
lesen.
¡Advertencia! Lea las instrucciones de instalación antes de conectar el sistema a la red de
alimentación.
Attention Avant de brancher le système sur la source d'alimentation, consulter les directives
d'installation.
ﻟﺍ ﺕﺍﺩﺎﺷﺭﺇ ﺮﻗﺍﺐﻴﻛﺮﺘ ﻞﻴﺻﻮﺗ ﻞﺒﻗ ﻰﻟﺇ ﻡﺎﻈﻨﻟﺍ ﺔﻗﺎﻄﻠﻟ ﺭﺪﺼﻣ
אורקל שי רוקמל תכרעמה רוביח ינפל הנקתה תוארוה תאחתמ.
시스템을 전원에 연결하기 전에 설치 안내를 읽어주십시오.
Waarschuwing Raadpleeg de installatie-instructies voordat u het systeem op de voedingsbron
aansluit.
Page 39
4-5
Chapter 4: Warning Statements for AC Systems
Circuit Breaker
Warning!
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure that the protective device is rated not greater than: 250 V, 20 A.
サーキット・ブレーカー
この製 品 は、短絡(過電流)保護装置がある建物での設置を前提としています。
保護装置の定格が250V、20Aを超えないことを確認下さい。
警告
此产品的短路(过载电流)保护由建筑物的供电系统提供,确保短路保护设备的额定电 流不大于250V,20A。
警告
此產品的短路(過載電流)保護由建築物的供電系統提供,確保短路保護設備的額定電 流不大於250V,20A。
Warnung Dieses Produkt ist darauf angewiesen, dass im Gebäude ein Kurzschluss-
bzw. Überstromschutz installiert ist. Stellen Sie sicher, dass der Nennwert der Schutzvorrichtung nicht mehr als: 250 V, 20 A beträgt.
¡Advertencia! Este equipo utiliza el sistema de protección contra cortocircuitos (o sobrecorrientes)
del edifi cio. Asegúrese de que el dispositivo de protección no sea superior a: 250 V, 20 A.
Attention Pour ce qui est de la protection contre les courts-circuits (surtension), ce produit
dépend de l'installation électrique du local. Vérifi ez que le courant nominal du dispositif de protection n'est pas supérieur à :250 V, 20 A.
לע ךמתסמ הז רצומנגהה תעינמל םינבמב תנקתומה יכ אדוול שי .ילמשח רצק
רצקה ינפמ ןגמה רישכמה ילמשחהמ רתוי אל אוה-
250 V, 20 A
Page 40
4-6
FatTwin F628G3-FT+/FTPT+ User's Manual
Power Disconnection Warning
Warning!
The system must be disconnected from all sources of power and the power cord removed from the power supply module(s) before accessing the chassis interior to install or remove system components.
電源切断の警告 システムコンポーネントの 取り付けまたは取り外しのために、シャーシー内部にアクセス
するには、 システムの電源はすべてのソースから切断され、電源コードは電源モジュールから取り
外す必要があります。
警告
在你打开机箱并安装或移除内部器件前,必须将系统完全断电,并移除电源线。
警告
在您打開機殼安裝或移除內部元件前,必須將系統完全斷電,並移除電源線。
경고!
이 제품은 전원의 단락(과전류)방지에 대해서 전적으로 건물의 관련 설비에 의존합니다. 보호장치의 정격이 반드시 250V(볼트), 20A(암페어)를 초과하지 않도록 해야 합니다.
Waarschuwing Dit product is afhankelijk van de kortsluitbeveiliging (overspanning) van uw electrische
installatie. Controleer of het beveiligde aparaat niet groter gedimensioneerd is dan 220V, 20A.
ﺞﺘﻨﻤﻟﺍ ﺍﺬﻫ ﻰﻠﻋ ﺪﻤﺘﻌﻳ ﺕﺍﺪﻌﻣ ﺔﻳﺎﻤﺤﻟﺍ ﺓﺮﻴﺼﻘﻟﺍﺮﺋﺍﻭﺪﻟﺍ ﻦﻣ ﺎﻬﺘﻴﺒﺜﺗ ﻢﺗ ﻲﺘﻟﺍ ﻲﻓ
ﻰﻨﺒﻤﻟﺍ
20A, 250V : ﻦﻣ ﺪﻛﺄﺗ ﻥﺃ ﻢﻴﻴﻘﺗ ﺯﺎﻬﺠﻟﺍ ﻟﺍﻲﺋﺎﻗﻮ ﺲﻴﻟ ﻦﻣ ﺮﺜﻛﺃ
Page 41
4-7
Chapter 4: Warning Statements for AC Systems
Warnung Das System muss von allen Quellen der Energie und vom Netzanschlusskabel
getrennt sein, das von den Spg.Versorgungsteilmodulen entfernt wird, bevor es auf den Chassisinnenraum zurückgreift, um Systemsbestandteile anzubringen oder zu entfernen.
¡Advertencia! El sistema debe ser disconnected de todas las fuentes de energía y del cable
eléctrico quitado de los módulos de fuente de alimentación antes de tener acceso el interior del chasis para instalar o para quitar componentes de sistema.
Attention Le système doit être débranché de toutes les sources de puissance ainsi que de
son cordon d'alimentation secteur avant d'accéder à l'intérieur du chassis pour installer ou enlever des composants de systéme.
ילמשח קותינ ינפמ הרהזא
!הרהזא
למשחה תורוקמ לכמ תכרעמה תא קתנל שי ריסהל שיו קפסהמ ילמשחה לבכ תא
נקתה ךרוצל זראמה לש ימינפה קלחל השיג ינפלת רסה ואת .םיביכר
ﻞﺼﻓ ﺐﺠﻳ ﻡﺎﻈﻨﻟﺍ ﻊﻴﻤﺟ ﻦﻣﺭﺩﺎﺼﻣ ﺔﻗﺎﻄﻟﺍ ﺔﻟﺍﺯﺇﻭ ءﺎﺑﺮﻬﻜﻟﺍ ﻚﻠﺳ ﻦﻣ ﺓﺪﺣﻭ ﺩﺍﺪﻣﺍ
ﺔﻗﺎﻄﻟﺍ ﻞﺒﻗ
ﻰﻟﺇ ﻝﻮﺻﻮﻟﺍ ﺔﻴﻠﺧﺍﺪﻟﺍ ﻖﻁﺎﻨﻤﻟﺍﻞﻜﻴﻬﻠ ﺔﻟﺍﺯﺇ ﻭﺃ ﺖﻴﺒﺜﺘﻟ ﺕﺎﻧﻮﻜﻣ ﺯﺎﻬﺠﻟﺍ
경고!
시스템에 부품들을 장착하거나 제거하기 위해서는 섀시 내부에 접근하기 전에 반드시 전원 공급장치로부터 연결되어있는 모든 전원과 전기코드를 분리해주어야 합니다.
Waarschuwing Voordat u toegang neemt tot het binnenwerk van de behuizing voor het installeren
of verwijderen van systeem onderdelen, dient u alle spanningsbronnen en alle stroomkabels aangesloten op de voeding(en) van de behuizing te verwijderen
Page 42
4-8
FatTwin F628G3-FT+/FTPT+ User's Manual
Equipment Installation
Warning!
Only trained and qualifi ed personnel should be allowed to install, replace, or service this equipment.
機器の設置
トレーニングを受け認定された人だけがこの装置の設置、交換、またはサービスを許可
されています。
警告
只有经过培训且具有资格的人员才能进行此设备的安装、更换和维修。
警告
只有經過受訓且具資格人員才可安裝、更換與維修此設備。
Warnung Das Installieren, Ersetzen oder Bedienen dieser Ausrüstung sollte nur geschultem,
qualifi ziertem Personal gestattet werden.
¡Advertencia! Solamente el personal califi cado debe instalar, reemplazar o utilizar este equipo.
Attention Il est vivement recommandé de confier l'installation, le remplacement et la
maintenance de ces équipements à des personnels qualifi és et expérimentés.
!הרהזא
שר דבלב ךמסומ תווצתא ףילחהל ,ןיקתהל יא .דויצה רובע תוריש תתל וא דויצה
ﻦﻴﺑﺭﺪﻤﻟﺍﻭ ﻭ ﺐﻴﻛﺮﺘﻟﻝﺍﺪﺒﺘﺳﺍ ﻭﺃ ﺔﻣﺪﺧ ﺯﺎﻬﺠﻟﺍ ﺍﺬﻫ ﺢﻤﺴﻳ ﻥﺃ ﺐﺠﻳ ﻂﻘﻓ ﻦﻴﻠﻫﺆﻤﻟﺍ ﻦﻴﻔﻅﻮﻤﻠﻟ
경고!
훈련을 받고 공인된 기술자만이 이 장비의 설치, 교체 또는 서비스를 수행할 수 있습니다.
Page 43
4-9
Chapter 4: Warning Statements for AC Systems
Restricted Area
Warning!
This unit is intended for installation in restricted access areas. A restricted access area can be accessed only through the use of a special tool, lock and key, or other means of security. (This warning does not apply to workstations).
アクセス制限区域
このユニットは 、アクセス制限区域に設置されることを想定しています。
アクセス制限区域は、特別なツール、鍵と錠 前 、その他のセキュリティの手段を用いての み出入りが可能です。
警告
此部件应安装在限制进出的场所,限制进出的场所指只能通过使用特殊工具、锁和 钥匙或其它安全手段进出的场所。
警告
此裝置僅限安裝於進出管制區域,進出管制區域係指僅能以特殊工具、鎖頭及鑰匙 或其他安全方式才能進入的區域。
Warnung Diese Einheit ist zur Installation in Bereichen mit beschränktem Zutritt vorgesehen.
Der Zutritt zu derartigen Bereichen ist nur mit einem Spezialwerkzeug, Schloss und Schlüssel oder einer sonstigen Sicherheitsvorkehrung möglich.
¡Advertencia! Esta unidad ha sido diseñada para instalación en áreas de acceso restringido.
Sólo puede obtenerse acceso a una de estas áreas mediante la utilización de una herramienta especial, cerradura con llave u otro medio de seguridad.
Attention Cet appareil doit être installée dans des zones d'accès réservés. L'accès à une
zone d'accès réservé n'est possible qu'en utilisant un outil spécial, un mécanisme de verrouillage et une clé, ou tout autre moyen de sécurité.
Waarschuwing Deze apparatuur mag alleen worden geïnstalleerd, vervangen of hersteld door
geschoold en gekwalifi ceerd personeel.
Page 44
4-10
FatTwin F628G3-FT+/FTPT+ User's Manual
Battery Handling
Warning!
There is the danger of explosion if the battery is replaced incorrectly. Replace the battery only with the same or equivalent type recommended by the manufacturer. Dispose of used batteries according to the manufacturer's instructions
電池の取り扱い
電池交換が正しく行われなかった場合、破裂の危険性があります。交換する電池はメー カーが推奨する型、または同等のものを使用下さい。 使用済電池は製造元の指示に従 って処 分して下さい。
警告
电池更换不当会有爆炸危险。请只使用同类电池或制造商推荐的功能相当的电池更
换原有电池。请按制造商的说明处理废旧电池。
警告
電池更換不當會有爆炸危險。請使用製造商建議之相同或功能相當的電池更換原有
電池。請按照製造商的說明指示處理廢棄舊電池。
תלבגומ השיג םע רוזא
!הרהזא
תרזעב תנתינ השיגה .השיג תלבגה םהב שיש םירוזאב הדיחיה תא ןיקתהל שי
.('דכו לוענמ ,חתפמ) דבלב החטבא ילכ
. ﺺﻴﺼﺨﺗ ﺓﺪﺣﻮﻟﺍ ﻩﺬﻫ ﻲﻓ ﺎﻬﺒﻴﻛﺮﺘﻟ ﻖﻁﺎﻨﻣ ﺓﺭﻮﻈﺤﻣ ﻢﺗ
ﺻﻮﻟﺍ ﻦﻜﻤﻳﻰﻟﺇ ﻝﻮ ﺔﻘﻄﻨﻣ ﺓﺭﻮﻈﺤﻣ ﻂﻘﻓ ﻡﺍﺪﺨﺘﺳﺍ ﻝﻼﺧ ﻦﻣ ،ﺔﺻﺎﺧ ﺓﺍﺩﺃ
ﻭﺃ ﻱﺃ ﻼﻟ ﻯﺮﺧﺃ ﺔﻠﻴﺳﻭﻥﺎﻣﻷ ﺡﺎﺘﻔﻣﻭ ﻞﻔﻗ
경고!
이 장치는 접근이 제한된 구역에 설치하도록 되어있습니다. 특수도구, 잠금 장치 및 키, 또는 기타 보안 수단을 통해서만 접근 제한 구역에 들어갈 수 있습니다.
Waarschuwing Dit apparaat is bedoeld voor installatie in gebieden met een beperkte toegang.
Toegang tot dergelijke gebieden kunnen alleen verkregen worden door gebruik te maken van speciaal gereedschap, slot en sleutel of andere veiligheidsmaatregelen.
Page 45
4-11
Chapter 4: Warning Statements for AC Systems
Warnung Bei Einsetzen einer falschen Batterie besteht Explosionsgefahr. Ersetzen Sie die
Batterie nur durch den gleichen oder vom Hersteller empfohlenen Batterietyp. Entsorgen Sie die benutzten Batterien nach den Anweisungen des Herstellers.
Attention Danger d'explosion si la pile n'est pas remplacée correctement. Ne la remplacer
que par une pile de type semblable ou équivalent, recommandée par le fabricant. Jeter les piles usagées conformément aux instructions du fabricant.
¡Advertencia! Existe peligro de explosión si la batería se reemplaza de manera incorrecta.
Reemplazar la batería exclusivamente con el mismo tipo o el equivalente recomendado por el fabricante. Desechar las baterías gastadas según las instrucciones del fabricante.
!הרהזא
תנכס תמייקץוציפ .הניקת אל ךרדב הפלחוהו הדימב הללוסה לש ףילחהל שי
גוסב הללוסה תא מ םאותה תרבחלמומ ןרציתצ.
תוללוסה קוליס תושמושמה עצבל שי .ןרציה תוארוה יפל
ﺮﻄﺧ ﻙﺎﻨﻫ ﻦﻣ ﻝﺍﺪﺒﺘﺳﺍ ﺔﻟﺎﺣ ﻲﻓ ﺭﺎﺠﻔﻧﺍ ﺔﻳﺭﺎﻄﺒﻟﺍ ﺔﺤﻴﺤﺻ ﺮﻴﻏ ﺔﻘﻳﺮﻄﺑ ﻚﻴﻠﻌﻓ
ﺔﻳﺭﺎﻄﺒﻟﺍ ﻝﺍﺪﺒﺘﺳﺍ
ﻂﻘﻓ ﻉﻮﻨﻟﺍ ﺲﻔﻨﺑ ﺎﻬﻟﺩﺎﻌﻳ ﺎﻣ ﻭﺃ ﺎﻤﻛﺖﺻﻭﺃ ﺔﻌﻨﺼﻤﻟﺍ ﺔﻛﺮﺸﻟﺍ ﻪﺑ
ﺕﺎﻳﺭﺎﻄﺒﻟﺍ ﻦﻣ ﺺﻠﺨﺗ ﻟ ﺎﻘﻓﻭ ﺔﻠﻤﻌﺘﺴﻤﻟﺍﺔﻌﻧﺎﺼﻟﺍ ﺔﻛﺮﺸﻟﺍ ﺕﺎﻤﻴﻠﻌﺘ
경고!
배터리가 올바르게 교체되지 않으면 폭발의 위험이 있습니다. 기존 배터리와 동일하거나 제조사에서 권장하는 동등한 종류의 배터리로만 교체해야 합니다. 제조사의 안내에 따라 사용된 배터리를 처리하여 주십시오.
Waarschuwing Er is ontploffi ngsgevaar indien de batterij verkeerd vervangen wordt. Vervang de
batterij slechts met hetzelfde of een equivalent type die door de fabrikant aanbevolen wordt. Gebruikte batterijen dienen overeenkomstig fabrieksvoorschriften afgevoerd te worden.
Page 46
4-12
FatTwin F628G3-FT+/FTPT+ User's Manual
Redundant Power Supplies
Warning!
This unit might have more than one power supply connection. All connections must be removed to de-energize the unit.
冗長電源装置
このユニットは複数の電源装置が接続されている場合があります。
ユニットの電源を切るためには、すべての接続を取り外さなければなりません。
警告
此部件连接的电源可能不止一个,必须将所有电源断开才能停止给该部件供电。
警告
此裝置連接的電源可能不只一個,必須切斷所有電源才能停止對該裝置的供電。
Warnung Dieses Gerät kann mehr als eine Stromzufuhr haben. Um sicherzustellen, dass
der Einheit kein trom zugeführt wird, müssen alle Verbindungen entfernt werden.
¡Advertencia! Puede que esta unidad tenga más de una conexión para fuentes de alimentación.
Para cortar por completo el suministro de energía, deben desconectarse todas las conexiones.
Attention Cette unité peut avoir plus d'une connexion d'alimentation. Pour supprimer toute
tension et tout courant électrique de l'unité, toutes les connexions d'alimentation doivent être débranchées.
דחא קפסמ רתוי םייק םא
!הרהזא
.קפס לש דחא רוביחמ רתוי שי הדחיל תא ריסהל שי ןקורל תנמ לע םירוביחה לכ
חיה תאי.הד
Page 47
4-13
Chapter 4: Warning Statements for AC Systems
Backplane Voltage
Warning!
Hazardous voltage or energy is present on the backplane when the system is operating. Use caution when servicing.
バックプレーンの電圧 システムの稼働中は危険な電圧または電力が、バックプレーン上にかかっています。 修理する際には注意ください。
警告
当系统正在进行时,背板上有很危险的电压或能量,进行维修时务必小心。
警告
當系統正在進行時,背板上有危險的電壓或能量,進行維修時務必小心。
Warnung Wenn das System in Betrieb ist, treten auf der Rückwandplatine gefährliche
Spannungen oder Energien auf. Vorsicht bei der Wartung.
¡Advertencia! Cuando el sistema está en funcionamiento, el voltaje del plano trasero es peligroso.
Tenga cuidado cuando lo revise.
. ﺪﻗ ﺍﺬﻬﻟ ﻥﻮﻜﻳ ﻟﺍﺯﺎﻬﺠ ﺕﻻﺎﺼﺗﺍ ﺓﺪﻋ ﺕﺍﺪﺣﻮﺑ ﺔﻗﺎﻄﻟﺍ ﺩﺍﺪﻣﺍ
ﺔﻟﺍﺯﺇ ﺐﺠﻳ ﺕﻻﺎﺼﺗﻻﺍ ﺔﻓﺎﻛ ﻝﺰﻌﻟ ﻟﺍﺓﺪﺣﻮ ﻦﻋ ءﺎﺑﺮﻬﻜﻟﺍ
경고!
이 장치에는 한 개 이상의 전원 공급 단자가 연결되어 있을 수 있습니다. 이 장치에 전원을 차단하기 위해서는 모든 연결 단자를 제거해야만 합니다.
Waarschuwing Deze eenheid kan meer dan één stroomtoevoeraansluiting bevatten. Alle
aansluitingen dienen verwijderd te worden om het apparaat stroomloos te maken.
Page 48
4-14
FatTwin F628G3-FT+/FTPT+ User's Manual
Comply with Local and National Electrical Codes
Warning!
Installation of the equipment must comply with local and national electrical codes.
地方および国の電気規格に準拠
機器の取り付けはその地方および国の電気規格に準拠する必要があります。
警告
设备安装必须符合本地与本国电气法规。
警告
設備安裝必須符合本地與本國電氣法規。
Warnung
Die Installation der Geräte muss den Sicherheitsstandards entsprechen.
ﻙﺎﻨﻫ ﺮﻄﺧ ﻦﻣ ﻲﺋﺎﺑﺮﻬﻜﻟﺍ ﺭﺎﻴﺘﻟﺍ ﻰﻠﻋ ﺓﺩﻮﺟﻮﻤﻟﺍ ﺔﻗﺎﻄﻟﺍﻭﺃ ﺔﺣﻮﻠﻟﺍ
ﻥﻮﻜﻳ ﺎﻣﺪﻨﻋﻡﺎﻈﻨﻟﺍ ﻞﻤﻌﻳ ﺪﻨﻋ ﺍﺭﺬﺣ ﻦﻛ ﺔﻣﺪﺧ ﺯﺎﻬﺠﻟﺍ ﺍﺬﻫ
경고!
시스템이 동작 중일 때 후면판 (Backplane)에는 위험한 전압이나 에너지가 발생 합니다. 서비스 작업 시 주의하십시오.
Waarschuwing Een gevaarlijke spanning of energie is aanwezig op de backplane wanneer het
systeem in gebruik is. Voorzichtigheid is geboden tijdens het onderhoud.
ירוחאה לנפב חתמ
זא!הרה
ךלהמב רהזיהל שי .תכרעמה לועפת ןמזב ירוחאה לנפב חתמ תנכס תמייק
.הדובעה
Attention Lorsque le système est en fonctionnement, des tensions électriques circulent sur
le fond de panier. Prendre des précautions lors de la maintenance.
Page 49
4-15
Chapter 4: Warning Statements for AC Systems
Product Disposal
Warning!
Ultimate disposal of this product should be handled according to all national laws and regulations.
製品の廃棄
この製品を廃棄処分する場合、国の関係する全ての法律・条例に従い処理する必要が
あります。
警告
本产品的废弃处理应根据所有国家的法律和规章进行。
警告
本產品的廢棄處理應根據所有國家的法律和規章進行。
יצראה למשחה יקוח םואית
!הרהזא
תנקתה םייצראהו םיימוקמה למשחה יקוחל תמאות תויהל תבייח דויצה.
ﺕﺍﺪﻌﻤﻟﺍ ﺐﻴﻛﺮﺗ ﺔﻴﺋﺎﺑﺮﻬﻜﻟﺍ ﻠﻟ ﻞﺜﺘﻤﻳ ﻥﺃ ﺐﺠﻳ ﻦﻴﻧﺍﻮﻘﺔﻴﻨﻁﻮﻟﺍﻭ ﺔﻴﻠﺤﻤﻟﺍ ﺔﻘﻠﻌﺘﻤﻟﺍ
ءﺎﺑﺮﻬﻜﻟﺎﺑ
¡Advertencia! La instalacion del equipo debe cumplir con las normas de electricidad locales y nacionales.Attention L'équipement doit être installé conformément aux normes électriques nationales
et locales.
경고!
현 지역 및 국가의 전기 규정에 따라 장비를 설치해야 합니다.
Waarschuwing Bij installatie van de apparatuur moet worden voldaan aan de lokale en nationale
elektriciteitsvoorschriften.
Page 50
4-16
FatTwin F628G3-FT+/FTPT+ User's Manual
Warnung
Die Entsorgung dieses Produkts sollte gemäß allen Bestimmungen und Gesetzen
des Landes erfolgen.
¡Advertencia!
Al deshacerse por completo de este producto debe seguir todas las leyes y
reglamentos nacionales.
Attention
La mise au rebut ou le recyclage de ce produit sont généralement soumis à des
lois et/ou directives de respect de l'environnement. Renseignez-vous auprès de
l'organisme compétent.
Hot Swap Fan Warning
Warning!
The fans might still be turning when you remove the fan assembly from the chassis. Keep fi ngers, screwdrivers, and other objects away from the openings in the fan assembly's housing.
ファン・ホットスワップの警告
シャーシから冷却ファン装置を取り外した際、ファンがまだ回転している可能性があり
ます。ファンの開口部に、指、ドライバー、およびその他のものを近づけないで下さい。
警告
רצומה קוליס
!הרהזא
ו תויחנהל םאתהב תויהל בייח הז רצומ לש יפוס קוליס.הנידמה יקוח
ﻲﺋﺎﻬﻨﻟﺍ ﺺﻠﺨﺘﻟﺍ ﻦﻣ ﺞﺘﻨﻤﻟﺍ ﺍﺬﻫ ﻪﻌﻣ ﻞﻣﺎﻌﺘﻟﺍ ﻲﻐﺒﻨﻳ ﻟ ﺎﻘﻓﻭ ﻊﻴﻤﺠﺔﻴﻨﻁﻮﻟﺍ ﺢﺋﺍﻮﻠﻟﺍﻭ ﻦﻴﻧﺍﻮﻘﻟﺍ ﺪﻨﻋ
경고!
이 제품은 해당 국가의 관련 법규 및 규정에 따라 폐기되어야 합니다.
Waarschuwing
De uiteindelijke verwijdering van dit product dient te geschieden in overeenstemming
met alle nationale wetten en reglementen.
Page 51
4-17
Chapter 4: Warning Statements for AC Systems
!הרהזא
יקלח תא םיריסמ רשאכ שי .םידבוע ןיידע םיררוואמהו ןכתי ,זראמהמ ררוואמה
קיחרהללררוואמה ךותב םיחתפהמ םינוש הדובע ילכו תועבצאה תא חוטב קחרמ
ﻦﻜﻤﻤﻟﺍ ﻦﻣ ﺡﻭﺍﺮﻤﻟﺍ ﻥﺃ ﻝﺍﺰﺗ ﻻ ﺔﻟﺍﺯﺇ ﺪﻨﻋﺭﻭﺪﺗ ﺔﻠﺘﻛ ﺔﺣﻭﺮﻤﻟﺍ ﻞﻜﻴﻬﻟﺍ ﻦﻣ ﺐﺠﻳ ءﺎﻘﺑﺇ
ﻊﺑﺎﺻﻷﺍﻲﻏﺍﺮﺒﻟﺍ ﺕﺎﻜﻔﻣ
. ءﺎﻴﺷﻷﺍ ﻦﻣ ﺎﻫﺮﻴﻏﻭ ﺍﺪﻴﻌﺑ ﻦﻋ ﺕﺎﺤﺘﻔﻟﺍ ﻲﻓ ﺔﻠﺘﻛ ﺔﺣﻭﺮﻤﻟﺍ
경고!
섀시로부터 팬 조립품을 제거할 때 팬은 여전히 회전하고 있을 수 있습니다. 팬 조림품 외관의 열려있는 부분들로부터 손가락 및 스크류드라이버, 다른 물체들이 가까이 하지 않도록 배치해 주십시오.
当您从机架移除风扇装置,风扇可能仍在转动。小心不要将手指、螺丝起子和其他 物品太靠近风扇
警告
當您從機架移除風扇裝置,風扇可能仍在轉動。小心不要將手指、螺絲起子和其他 物品太靠近風扇。
Warnung Die Lüfter drehen sich u. U. noch, wenn die Lüfterbaugruppe aus dem Chassis
genommen wird. Halten Sie Finger, Schraubendreher und andere Gegenstände von den Öffnungen des Lüftergehäuses entfernt.
¡Advertencia! Los ventiladores podran dar vuelta cuando usted quite ell montaje del ventilador
del chasis. Mandtenga los dedos, los destornilladores y todos los objetos lejos de las aberturas del ventilador
Attention Il est possible que les ventilateurs soient toujours en rotation lorsque vous retirerez
le bloc ventilateur du châssis. Prenez garde à ce que doigts, tournevis et autres objets soient éloignés du logement du bloc ventilateur.
Page 52
4-18
FatTwin F628G3-FT+/FTPT+ User's Manual
Power Cable and AC Adapter
Warning!
When installing the product, use the provided or designated connection cables, power cables and AC adaptors. Using any other cables and adaptors could cause a malfunction or a fi re. Electrical Appliance and Material Safety Law prohibits the use of UL or CSA -certifi ed cables (that have UL/CSA shown on the code) for any other electrical devices than products designated by Supermicro only.
電源コードとACアダプター 製品を設置する場合、提供または指定された接続ケーブル、電源コードとACアダプター
を使用下さい。 他のケーブルやアダプタを使用すると故障や火災の原因になることがあ ります。 電気用品安全法は、ULまたはCSA認定のケーブル(UL/CSEマークがコードに表
記)をSupermicroが指定する製品以外に使用することを禁止しています。
警告
安装此产品时,请使用本身提供的或指定的连接线,电源线和电源适配器.使用其它线 材或适配器可能会引起故障或火灾。除了Supermicro所指定的产品,电气用品和材 料安全法律规定禁止使用未经UL或CSA认证的线材。(线材上会显示UL/CSA符号)。
警告
安裝此產品時,請使用本身提供的或指定的連接線,電源線和電源適配器.使用其它線 材或適配器可能會引起故障或火災。除了Supermicro所指定的產品,電氣用品和材 料安全法律規定禁止使用未經UL或CSA認證的線材。(線材上會顯示UL/CSA符號)。
Warnung Bei der Installation des Produkts, die zur Verfügung gestellten oder benannt
Anschlusskabel, Stromkabel und Netzteile. Verwendung anderer Kabel und Adapter kann zu einer Fehlfunktion oder ein Brand entstehen. Elektrische Geräte und Material Safety Law verbietet die Verwendung von UL-oder CSA-zertifi zierte Kabel, UL oder CSA auf der Code für alle anderen elektrischen Geräte als Produkte von Supermicro nur bezeichnet gezeigt haben.
Waarschuwing Het is mogelijk dat de ventilator nog draait tijdens het verwijderen van het
ventilatorsamenstel uit het chassis. Houd uw vingers, schroevendraaiers en eventuele andere voorwerpen uit de buurt van de openingen in de ventilatorbehuizing.
Page 53
4-19
Chapter 4: Warning Statements for AC Systems
¡Advertencia! Al instalar el producto, utilice los cables de conexión previstos o designados, los
cables y adaptadores de CA. La utilización de otros cables y adaptadores podría ocasionar un mal funcionamiento o un incendio. Aparatos Eléctricos y la Ley de Seguridad del Material prohíbe el uso de UL o CSA cables certifi cados que tienen UL o CSA se muestra en el código de otros dispositivos eléctricos que los productos designados por Supermicro solamente.
Attention Lors de l'installation du produit, utilisez les bables de connection fournis ou désigné.
L'utilisation d'autres cables et adaptateurs peut provoquer un dysfonctionnement ou un incendie. Appareils électroménagers et de loi sur la sécurité Matériel interdit l'utilisation de UL ou CSA câbles certifi és qui ont UL ou CSA indiqué sur le code pour tous les autres appareils électriques que les produits désignés par Supermicro seulement.
אתמו םיילמשחמ י
AC
!הרהזא
םימאתמו םיקפס ,םילבכב שמתשהל שי ,רצומה תא םיניקתמ רשאכ
AC רשא
וא הלקתל םורגל לוכי רחא םאתמ וא לבכ לכב שומיש .ךכ םשל וקפוסו ודעונ
טב יקוחו למשח ירישכמב שומיש יקוח יפ לע .ילמשח רצק רוסיא םייק ,תוחי
ב םיכמסומה םילבכב שמתשהל-
UL ב וא- CSA לש דוק םהילע עיפומ ראשכ)
UL/CSA( רחא ילמשח רצומ לכ רובע.דבלב ורקימקרפוס ידי לע ןיוצ אלש
ﺐﻴﻛﺮﺗ ﺪﻨﻋ ﻡﺍﺪﺨﺘﺳﺍ ﺐﺠﻳ ﺯﺎﻬﺠﻟﺍ ﻭ،ﻞﻴﺻﻮﺘﻟﺍ ﺕﻼﺑﺎﻛ ﺔﻴﺋﺎﺑﺮﻬﻜﻟﺍ ﺕﻼﺑﺎﻜﻟﺍ
ﺕﻻﻮﺤﻣﻭ ﺩﺩﺮﺘﻤﻟﺍ ﺭﺎﻴﺘﻟﺍ
. ﻥﺃ ﻱﺃ ﻡﺍﺪﺨﺘﺳﺍ ﺕﻼﺑﺎﻛ ﺕﻻﻮﺤﻣﻭ ﻯﺮﺧﺃ ﺐﺒﺴﺘﻳ ﻲﻓ ﻞﻄﻋ ﺙﻭﺪﺣ ﻖﻳﺮﺣ ﻭﺃ . ﻲﺘﻟﺍ
ﻚﻟ ﺎﻫﺮﻴﻓﻮﺗ ﻢﺗ ﺞﺘﻨﻤﻟﺍ ﻊﻣ
UL ﻭﺃ CSA ﺔﻴﺋﺎﺑﺮﻬﻜﻟﺍ ﺓﺰﻬﺟﻷﺍ ﺩﺍﻮﻣﻭ ﻥﻮﻧﺎﻗ ﺔﻣﻼﺴﻟﺍ ﻡﺍﺪﺨﺘﺳﺍ ﺮﻈﺤﻳ ﺕﻼﺑﺎﻜﻟﺍ
ﻞﺒﻗ ﻦﻣ ﺓﺪﻤﺘﻌﻣ
Supermicro ﺓﺰﻬﺟﺃ ﻯﺮﺧﺃ ﺔﻴﺋﺎﺑﺮﻬﻛ ﺮﻴﻏ ﺕﺎﺠﺘﻨﻤﻟﺍ ﺔﻨﻴﻌﻤﻟﺍ ﻞﺒﻗ ﻦﻣ ﻱﻷ
(UL/CSA ﻞﻤﺤﺗ ﻲﺘﻟﺍﺔﻣﻼﻋ )
경고!
제품을 설치할 때에는 제공되거나 지정된 연결케이블과 전원케이블, AC어댑터를 사용해야 합니다. 그 밖의 다른 케이블들이나 어댑터들은 고장 또는 화재의 원인이 될 수 있습니다. 전기용품안전법 (Electrical Appliance and Material Safety Law)은 슈퍼마이크로에서 지정한 제품들 외에는 그 밖의 다른 전기 장치들을 위한 UL또는 CSA에서 인증한 케이블(전선 위에 UL/CSA가 표시)들의 사용을 금지합니다.
Page 54
4-20
FatTwin F628G3-FT+/FTPT+ User's Manual
Waarschuwing Bij het installeren van het product, gebruik de meegeleverde of aangewezen kabels,
stroomkabels en adapters. Het gebruik van andere kabels en adapters kan leiden tot een storing of een brand. Elektrisch apparaat en veiligheidsinformatiebladen wet verbiedt het gebruik van UL of CSA gecertifi ceerde kabels die UL of CSA die op de code voor andere elektrische apparaten dan de producten die door Supermicro alleen.
Page 55
Chapter 5: Advanced Serverboard Setup
5-1
Chapter 5
Advanced Serverboard Setup
This chapter covers the steps required to install the X10DRFF-iG/iTG serverboard into the chassis, connect the data and power cables and install add-on cards. All serverboard jumpers and connections are also described. A layout and quick reference chart are included in this chapter for your reference. Remember to completely close the chassis when you have fi nished working with the serverboard to better cool and protect the system.
5-1 Handling the Serverboard
Electrostatic Discharge (ESD) can damage electronic com ponents. To prevent damage to any printed circuit boards (PCBs), it is important to handle them very carefully (see previous chapter). To prevent the serverboard from bending, keep one hand under the center of the board to support it when handling. The following measures are generally suffi cient to protect your equipment from electric static discharge.
Precautions
Use a grounded wrist strap designed to prevent Electrostatic Discharge (ESD).
T ouch a grounded metal object before removing any board from its antistatic bag.
Handle a board by its edges only; do not touch its components, peripheral chips,
memory modules or gold contacts.
When handling chips or modules, avoid touching their pins.
Put the serverboard, add-on cards and peripherals back into their antistatic
bags when not in use.
For grounding purposes, make sure your computer chassis provides excellent
conductivity between the power supply, the case, the mounting fasteners and the serverboard.
Unpacking
The serverboard is shipped in antistatic packaging to avoid electrical static discharge. When unpacking the board, make sure the person handling it is static protected.
Page 56
5-2
FatTwin F628G3-FT+/FTPT+ User's Manual
5-2 Connecting Cables
Now that the processors are installed, the next step is to connect the cables to the serverboard.
Connecting Data Cables
The cables used to transfer data from the peripheral devices have been carefully routed in preconfi gured systems to prevent them from blocking the fl ow of cooling air that moves through the system from front to back. If you need to disconnect any of these cables, you should take care to reroute them as they were originally after reconnecting them (make sure the red wires connect to the pin 1 locations). If you are confi guring the system, keep the airfl ow in mind when routing the cables.
5-3 Control Panel Connectors and I/O Ports
The I/O ports are in conformance with the PC 99 specifi cation. See Figure 5-1 below for the colors and locations of the various I/O ports.
I/O Port Locations and Defi nitions
1 Front USB 3.0 Port 1 2 Front USB 3.0 Port 2 3 Dedicated IPMI LAN Port 4 Gigabit LAN Port 1 (for X10DRFF-iG), 10GBase-T LAN Port 1 (for X10DRFF-iTG) 5 Gigabit LAN Port 2 (for X10DRFF-iG), 10GBase-T LAN Port 2 (for X10DRFF-iTG) 6 VGA Port 7 Power Switch 8 UID (Unit Identifi er) Button
Figure 5-1. I/O Ports
21 53 4 6 7 8
Page 57
Chapter 5: Advanced Serverboard Setup
5-3
Installing the LGA2011 Processor
1. There are two load levers on the LGA2011 socket. To open the socket cover, rst press and release the load lever labeled 'Open 1st'.
OPEN 1st
OPEN 1st
WARNING!
WARNING!
Press down on
Load Lever
labeled 'Open 1st'.
OPEN 1st
OPEN 1st
WARNING!
WARNING!
5-4 Processor and Heatsink Installation
Warning! When handling the processor package, avoid placing direct pressure on
the label area. Warning! If you buy a CPU separately, make sure that you use an Intel-certifi ed multi-
directional heatsink only.
Notes:
1. Always connect the power cord last, and always remove it before adding, removing or changing any hardware components. Make sure that you install the processor into the CPU socket before you install the CPU heatsink.
2. Make sure to install the system board into the chassis before you install the CPU heatsink.
3. When receiving a server board without a processor pre-installed, make sure that the plastic CPU socket cap is in place and none of the socket pins are bent; otherwise, contact your retailer immediately.
4. Refer to the Supermicro website for updates on CPU support.
5. When only one CPU is installed, be sure to install it on CPU Socket 1 fi rst.
Note: Graphics and drawings shown in this manual are for illustration only. Your components may or may not look the same as the graphics shown in the manual.
Page 58
5-4
FatTwin F628G3-FT+/FTPT+ User's Manual
2. Press the second load lever labeled 'Close 1st' to release the load plate that covers the CPU socket from its locking position.
OPEN 1st
OP
EN
1s
t
WARNING!
WARNING!
OPEN 1st
OPEN 1st
WARNING!
WARNING!
Press down on
Load the Lever
labeled 'Close 1st'
Pull lever away
from the socket
3. With the lever labeled 'Close 1st' fully retracted, gently push down on the 'Open 1st' lever to open the load plate. Lift the load plate to open it completely.
Gently push down to pop the
load plate open.
OPEN 1st
OPEN 1st
WARNING!
WARNING!
WARNING!
WARNING!
4. Using your thumb and the index fi nger, remove the 'WARNING' plastic cap from the socket.
WARNING!
Page 59
Chapter 5: Advanced Serverboard Setup
5-5
5. Use your thumb and index fi nger to hold the CPU on its edges. Align the CPU keys, which are semi-circle cutouts, against the socket keys.
Socket Keys
CPU Keys
6. Once they are aligned, carefully lower the CPU straight down into the socket. (Do not drop the CPU on the socket. Do not move the CPU horizontally or vertically. Do not rub the CPU against the surface or against any pins of the socket to avoid damaging the CPU or the socket.)
Caution: You can only install the CPU inside the socket in one direction. Make sure that it is properly inserted into the CPU socket before closing the load plate. If it doesn't close properly, do not force it as it may damage your CPU. Instead, open the load plate again and double-check that the CPU is aligned properly.
Page 60
5-6
FatTwin F628G3-FT+/FTPT+ User's Manual
7. With the CPU inside the socket, inspect the four corners of the CPU to make sure that the CPU is properly installed.
OPEN 1st
OPEN
1st
Push down and lock the
level labeled 'Close 1st'.
Gently close the
load plate.
OPEN 1st
OPEN
1st
OPEN 1st
OPEN 1st
Lever Lock
Lever Lock
Push down and lock
the lever labeled
'Open 1st'
8. Close the load plate with the CPU inside the socket. Lock the lever labeled 'Close 1st' fi rst, then lock the lever labeled 'Open 1st' second. Use your thumb to gently push the load levers down to the lever locks.
Page 61
Chapter 5: Advanced Serverboard Setup
5-7
Installing a Passive CPU Heatsink
1. Apply the proper amount of thermal grease to the heatsink.
2. Place the heatsink on top of the CPU so that the two mounting holes on the heatsink are aligned with those on the retention mechanism.
3. Inser t t wo push -p ins on th e sides o f the heat sink th rough t he mount ing hol es on the se rve rboa rd, and tu rn the p ush- pins c loc kw ise to lo ck the m.
Note: For optimized airfl ow, please follow your chassis airfl ow direction to properly install the correct heatsink. Graphics included in this manual are for reference only . They might look different from the components installed in your system.
OPEN 1st
O
PEN 1st
Screw#1
Screw#2
Direction of Airfl ow
Page 62
5-8
FatTwin F628G3-FT+/FTPT+ User's Manual
Removing the Passive Heatsink
Warning: We do not recommend that the CPU or the heatsink be removed. However,
if you do need to remove the heatsink, please follow the instructions below to uninstall the heatsink to avoid damaging the CPU or other components.
1. Unplug the power cord from the power supply.
2. Press down the push-pin on the heatsink, and turn counter-clock-wise to loosen it. Repeat the same step to loosen the second push-pin.
3. Hold the heatsink as shown in the picture below, and gently wriggle the heatsink to loosen it. (Do not use excessive force when wriggling the heatsink.)
4. Once the heatsink is loosened, remove it from the CPU.
Note: For optimized airfl ow, please follow your chassis airfl ow direction to properly install the heatsink. Graphics included in this manual are for reference only. They might look different from the components installed in your system.
Loosen screws in the sequence as shown.
Screw#2
Serverboard
Screw#1
Screw#3
Screw#4
Direction of Airfl ow
Page 63
Chapter 5: Advanced Serverboard Setup
5-9
5-5 Installing Memory
Caution: exercise extreme care when installing or removing DIMM modules to prevent
any possible damage.
Installing Memory
1. Insert the desired number of DIMMs into the memory slots, starting with P1-DIMM #A1. (For best performance, please use the memory modules of the same type and speed in the same bank.)
2. Push the release tabs outwards on both ends of the DIMM slot to unlock it.
3. Align the key of the DIMM module with the receptive point on the memory slot.
4. Align the notches on both ends of the module against the receptive points on the ends of the slot.
5. Use two thumbs together to press on both ends of the module straight down into the slot until the module snaps into place.
6. Press the release tabs to the locking positions to secure the DIMM module into the slot.
Reverse the steps above to remove the DIMM modules from the serverboard. Note: 4 GB, 8 GB, 16 GB or 32 GB size memory modules are supported. It is
highly recommended that you remove the power cord from the system before installing or changing memory modules. Please refer to our web site for memory that has been tested on the X10DRFF-iG/iTG serverboard.
Figure 5-2. Installing DIMM into Slot
Release Tabs
Notches
Press both notches straight down into the memory slot at the same time.
Removing Memory Modules
Press the release tabs on both ends of the memory module to unlock it. Once it is loosened, remove the DIMM module from the memory slot.
Page 64
5-10
FatTwin F628G3-FT+/FTPT+ User's Manual
Memory Support
The X10DRFF-iG/iTG serverboard supports up to 1 TB of Load Reduced (LRDIMM) or up to 512 GB of Registered (RDIMM) DDR4 (288-pin) ECC DDR4-2133/1866/1600 MHz speed memory modules in sixteen (16) slots (with 1 DIMM per channel). Memory speed support depends upon the processors used in the system.
Note: For the latest CPU/memory updates, please refer to our website at
http://www.supermicro.com/products/serverboard.
Processors and their Corresponding Memory Modules
CPU# Corresponding DIMM Modules
CPU 1
P1-
DIMMA1
P1-
DIMMB1
P1-
DIMMC1
P1-
DIMMD1
P1-
DIMMA2
P1-
DIMMB2
P1-
DIMMC2
P1-
DIMMD2
CPU2
P2-
DIMME1
P2-
DIMMF1
P2-
DIMMG1
P2-
DIMMH1
P2-
DIMME2
P2-
DIMMF2
P2-
DIMMG2
P2-
DIMMH2
Processor and Memory Module Population for Optimal Performance
Number of
CPUs+DIMMs
CPU and Memory Population Confi guration Table (For memory to work properly, please follow the instructions below.)
1 CPU &
2 DIMMs
CPU1 P1-DIMMA1/P1-DIMMB1
1 CPU &
4 DIMMs
CPU1 P1-DIMMA1/P1-DIMMB1, P1-DIMMC1/P1-DIMMD1
1 CPU &
5~8 DIMMs
CPU1 P1-DIMMA1/P1-DIMMB1, P1-DIMMC1/P1-DIMMD1 + any pair of P1-DIMMA2/P1­DIMMB2/P1-DIMMC2/P1-DIMMD2 slots
2 CPUs &
4 DIMMs
CPU1 + CPU2 P1-DIMMA1/P1-DIMMB1, P2-DIMME1/P2-DIMMF1
2 CPUs &
6 DIMMs
CPU1 + CPU2 P1-DIMMA1/P1-DIMMB1/P1-DIMMC1/P1-DIMMD1, P2-DIMME1/P2-DIMMF1
2 CPUs &
8 DIMMs
CPU1 + CPU2 P1-DIMMA1/P1-DIMMB1/P1-DIMMC1/P1-DIMMD1, P2-DIMME1/P2-DIMMF1/P2­DIMMG1/P2-DIMMH1
2 CPUs &
9~16 DIMMs
CPU1/CPU2 P1-DIMMA1/P1-DIMMB1/P1-DIMMC1/P1-DIMMD1, P2-DIMME1/P2-DIMMF1/P2­DIMMG1/P2-DIMMH1 + any pair of P1, P2 DIMM slots
2 CPUs & 16 DIMMs
CPU1/CPU2 P1-DIMMA1/P1-DIMMB1/P1-DIMMC1/P1-DIMMD1, P2-DIMME1/P2-DIMMF1/P2­DIMMG1/P2-DIMMH1,P1-DIMMA2/P1-DIMMB2/P1-DIMMC2/P1-DIMMD2, P2-DIMME2/ P2-DIMMF2/P2-DIMMG2/P2-DIMMH2
Page 65
Chapter 5: Advanced Serverboard Setup
5-11
Populating Memory Modules
Intel E5-2600v3 Series Processor Memory Support
Type Ranks Per
DIMM &
Data Width
(See the
Note
Below)
Memory Capacity
Per DIMM
Speed (MT/s) and Voltage (V)
1 Slot Per
Channel
2 Slots Per Channel
1DPC 1DPC 2DPC
4 GB 8 GB 1.2V 1.2V 1.2V
RDIMM SRx4 8 GB 16 GB 2133 2133 1866 RDIMM SRx8 4 GB 8 GB 2133 2133 1866 RDIMM DRx8 8 GB 16 GB 2133 2133 1866 RDIMM DRx4 16 GB 32 GB 2133 2133 1866
LRDIMM QRx4 32 GB 64 GB 2133 2133 2133
Note: For detailed information on memory support and updates, please refer to the SMC Recommended Memory List posted on our website at
http://www.supermicro.com/support/resources/mem.cfm.
Other Important Notes and Restrictions
For the memory modules to work properly, please install DIMM modules in pairs
(w/even number of DIMMs installed).
Mixing memory modules of different types, different speeds or different sizes
is not allowed.
Page 66
5-12
FatTwin F628G3-FT+/FTPT+ User's Manual
5-6 Serverboard Details
Figure 5-3. X10DRFF-iG/iTG Serverboard Layout
(not drawn to scale)
SAN MAC
J23
SAS CODE
MAC CODE IPMI CODE
JVRM1
JVRM2
JWD1
JPB1 JPL1
JPG1
JPME2
J21
UID_LED1
JTPM1
JSD2
JUIDB1
FAN7
FAN6
FAN1
FAN4
FAN5
FAN3
FAN2
FAN8
JBT1
1
BIOS LICENSE
BAR CODE
I-SATA5
I-SATA3
I-SATA2
I-SATA1
I-SATA0
S-SATA2
S-SATA3
S-SATA0
S-SATA1
I-SATA4
SXB1
HDD_LED1
LEDBMC
FAILURE_LED2
USB1
PWR_SW1
JPW1
HDD_PWR2
HDD_PWR1
IPMI_LAN1
JPW3
LEDS2
J22
BT1
S-SGPIO1
T-SGPIO2
JL1
JIPMB1
JP
REAR_FAN1
REAR_FAN2
SAS4-7
SAS0-3
PCH SLOT4 PCIE-E 2.0 X4
CPU2 SLOT3 PCI-E 3.0 X8
CPU1 SLOT2 PCI-E 3.0 X8
SXB1: CPU1 SLOT1 PCI-E X16 PROPRIETARY SLOT
USB12/13(3.0)
COM1
VGA
LAN1
P1-DIMMA2
P1-DIMMB1
P1-DIMMB2
P1-DIMMA1
P2-DIMME1
P2-DIMME2
P2-DIMMF1
P2-DIMMF2
P2-DIMMG1
SXB2:CPU2 PCI-E X32 PROPRIETARY SLOT
P2-DIMMG2
P2-DIMMH1
P2-DIMMH2
JPW2
P1-DIMMC2
P1-DIMMC1
P1-DIMMD2
P1-DIMMD1
LAN2
JNVI2C1
T-SGPIO1
CLOSE 1st
OPEN 1st
CPU2
CLOSE 1st
OPEN 1st
CPU1
X10DRFF-iG
Rev. 1.00
JNVI2C2
BIOS
SAS CTRL
LAN CTRL
PCH
BMC
Battery
USB0
JSD1
Page 67
Chapter 5: Advanced Serverboard Setup
5-13
Notes:
1. For the latest CPU/Memory updates, please refer to our website at http://
www.supermicro.com/products/serverboard/ for details.
2. Use only the correct type of onboard CMOS battery as specifi ed by the manufacturer. Do not install the onboard battery upside down, in order to avoid possible explosion.
3. Components/Jumpers/LED Indicators that are not documented in this manual are reserved for internal testing only.
X10DRFF-iG/iTG Serverboard Jumpers
Jumper Description Default Setting
JBT1 Clear CMOS/Reset BIOS Confi guration See Section 5-8 for
details JPB1 BMC Enabled Pins 1-2 (Enabled) JPG1 VGA Enabled Pins 1-2 (Enabled) JPL1 GLAN1/GLAN2 Enable (X10DRFF-iG) or 10G TLAN1/TLAN2
Enable (X10DRFF-iTG)
Pins 1-2 (Enabled)
JPME2 Manufacture Mode (ME) Select Pins 1-2 (Normal) JWD1 Watch Dog Pins 1-2 (Reset)
X10DRFF-iG/iTG Serverboard LED Indicators
LED Description State
HDD_LED1 HDD Activity LED Green: Blinking (HDD Active)
Failure_LED2 Serverboard Failure LED
Solid: On (Overheating) Blinking at 1Hz (Fan Failure) Blinking at 0.25Hz (Power Supply Failure)
LEDBMC BMC Heartbeat LED Green: Blinking (BMC Normal)
UID_LED1 Rear UID LED Blue: On (Unit Identifi ed)
Page 68
5-14
FatTwin F628G3-FT+/FTPT+ User's Manual
X10DRFF-iG/iTG Serverboard Connectors
Connectors Description
BT1 (Battery) Onboard CMOS battery (See Chpt. 3 for Used Battery Disposal) COM1 Serial port header FAN1-8, Rear FAN1/2 CPU/system fan headers (Fan 1-Fan 8, Rear Fan1/Rear Fan1) HDD PWR1/2 8-pin power connectors (1/2) for HDD devices IPMI_LAN IPMI_dedicated LAN support by the ASpeed controller LAN1/LAN2 Gigabit Ethernet (GLAN) ports 1/2 (X10DRFF-iG)
10G-bit Ethernet (TLAN) ports 1/2 (X10DRFF-iTG)
JIPMB1 4-pin external BMC I
2
C header (for an IPMI card) JL1 Chassis intrusion header JNVI
2
C1/2 System management bus (SMBbus) (I2C) for Non-Volitale (NV) memory
JPI
2
C1 Power supply SMBbus I2C header JPW3 4-pin (PS_ON_N) power connector JPW1/JPW2 12V 8-pin power connectors 1/2 JTPM1 TPM (Trusted Platform Module)/Port 80 header JUIDB1 UID (Unit Identifi cation) switch JVRM1/2 VRM headers 1/2 PWR_SW1 Power switch I-SATA 0-5 SATA 3.0 connectors supported by Intel PCH (I-SATA 0-5), (I-SATA4/I-SATA5:
can be used as Supermicro SuperDOM (Disk-on-Module) with built-in power connectors)
S-SATA 0-3 SATA 3.0 connectors (0-3) supported by Intel PCH S-SGPIO1 Seria_Link General Purpose I/O header for S-SATA ports (S-SATA0-3)
T-SGPIO1/2 Seria_Link General Purpose I/O headers 1/2 for SATA ports (I-SGPIO1 for
I-SATA0-3, I-SGPIO2 for I-SATA4/5)
(CPU1) Slot2 PCI-Express 3.0 x8 slot from CPU1 (CPU2) Slot3 PCI-Express 3.0 x8 slot from CPU2 (PCH) Slot4 PCI-Express 2.0 x4 slot from PCH SXB1 Slot1 CPU1 SLOT1 PCI-E x16 Proprietary Slot SXB2 Slot2 CPU1 SLOT2 PCI-E x32 Proprietary Slot (BP) USB 12/13 (3.0) USB 3.0 ports 12/13 (USB0/1) VGA VGA port
Page 69
Chapter 5: Advanced Serverboard Setup
5-15
5-7 Connector Defi nitions
Power Connectors
Two 8-pin power connectors (JPW1/ JPW2) provide main power to the serverboard, while other two 8-pin power connectors (HDD_PWR1/HDD_PWR2) are used to supply power to HDD devices. The 4-pin power connector (JPW3) is used as auxiliary power. These power connectors to provide adequate power to the system. See the tables on the right for pin defi nitions.
12V 8-pin
Power Connector
(JPW1/JPW2)
Pin Defi nitions
Pins Defi nition 1 through 4 Ground 5 through 8 +12V
12V 8-pin
HDD PWR Connector
(HDD_PWR1/2HDD)
Pin Defi nitions
Pins Defi nition 1 +12V 2-3 Ground 4 +5V
Universal Serial Bus (USB)
Two USB ports (USB 12/13) are located on the I/O panel to provide USB 3.0 connections to the system. (Cables are not included.) See the tables on the right and below for pin defi nitions.
Panel USB 12/13 (3.0)
Pin Defi nitions
Pin# Description 1 VBUS 2 SSRX­3 SSRX+ 4 Ground 5 SSTX­6 SSTX+ 7 GND_DRAIN 8D­9D+
Power Switch
A power switch is located next to the VGA port on the IO panel. Press this switch to turn on or turn off the system power. See the layout below for the location of the power switch.
Warning: To ensure adequate power supply to your serverboard, be sure to connect all the power connectors mentioned above to your power supply For proper system operation.
Page 70
5-16
FatTwin F628G3-FT+/FTPT+ User's Manual
Video Connector
A Video (VGA) connector is located next to LAN2 on the IO panel. This connector provides video and CRT display. Refer to the board layout below for the location.
Ethernet Ports
Two Ethernet ports (LAN1/2) are located on the I/O panel on the serverboard. These two LAN ports support 1GigE LAN (F628G3-FT+) or 10GBase-T (F628G3-FTPT+) LAN connections. In addition, an IPMI-dedicated LAN, located next to LAN 1 on the I/O panel, provides IPMI KVM support. All these ports accept RJ45 type cables. (Note: Please refer to the LED Indicator Section for LAN LED information.)
Serial Port Header
A COM port header is located next to the DIMM memory P1-DIMMC1 slot on the serverboard. COM1 provides serial connection support.
Unit Identifi er Button/UID LED Indicators
A rear Unit Identifi er (JUIDB1) button and a UID LED (UID_LED1) are located next to the VGA port on the IO panel. When you press the rear UID button, rear UID LED will be turned on. Press the UID button again to turn off the LED indicator. The UID indicator provides easy identifi cation of a system unit that may be in need of service.
Note: UID can also be triggered via IPMI on the serverboard. For more information on IPMI, please refer to the IPMI user's guide posted on our website at
http://
www.supermicro.com.
UID Switch
(JUIDB1)
Pin# Defi nition 1 Ground 2 Ground 3 Button In 4 Ground
UID LED Status
(UID_LED1)
Color/State Status Blue: On Unit Identifi ed
Chassis Intrusion
A Chassis Intrusion header is located at JL1 on the serverboard. Attach an appropriate cable from the chassis to inform you of a chassis intrusion when the chassis is opened.
Chassis Intrusion
(JL1)
Pin Defi nitions
Pin# Defi nition 1 Intrusion Input 2 Ground
Page 71
Chapter 5: Advanced Serverboard Setup
5-17
Fan Header
Pin Defi nitions
Pin# Defi nition 1 Ground 2 +12V 3 Tachometer 4 PWR Modulation
Fan Headers
This serverboard has ten system/CPU fan headers (Fans 1-8, Rear Fan 1, and Rear Fan 2) on the serverboard. All these 4-pin fans headers are backward­compatible with the traditional 3-pin fans. However, fan speed control is available for 4-pin fans only by Thermal Management via the IPMI 2.0 interface. See the table on the right for pin defi nitions.
DOM Power Connectors
Two power connectors for SATA DOM (Disk_On_Module) devices are located at JSD1/JSD2. Connect appropriate cables here to provide power support for your Serial Link DOM devices.
DOM PWR
(JSD1/2)
Pin Defi nitions
Pin# Defi nition 1 +5V 2 Ground 3 Ground
TPM Header/Port 80
A Trusted Platform Module (TPM)/Port 80 header is located at JTPM1 to provide TPM support and Port 80 connections. Use this header to enhance system performance and data security. See the table on the right for pin defi nitions.
TPM/Port 80 Header (JTPM1)
Pin Defi nitions
Pin# Defi nition Pin# Defi nition 1 LCLK 2 GND 3 LFRAME# 4 <(KEY)> 5 LRESET# 6 No Connection 7 LAD 3 8 LAD 2 9 +3.3V 10 LAD1 11 LAD0 12 GND 13 No Connection 14 No Connection 15 +3V_DUAL 16 SERIRQ 17 GND 18 CLKRUN# (X) 19 LPCPD# 20 No Connection
Page 72
5-18
FatTwin F628G3-FT+/FTPT+ User's Manual
T-SGPIO 1/2 & S-SGPIO 1 Headers
Three SGPIO (Serial Link General Purpose Input/Output) headers are located on the serverboard. T-SGPIO1/2 support onboard I-SATA 0-5, while S-SGPIO1 supports S-SATA 0-3 connections. See the tables on the right for SGPIO support and for pin defi nitions of the connectors.
T-SGPIO1/2, S-SGPIO
Pin Defi nitions
Pin# Defi nition Pin# Defi nition 1NC 2NC 3 Ground 4 Data 5 Load 6 Ground 7 Clock 8 NC
NC indicates no connection.
I-SGPIO 0/1
T-SGPIO1 I-SATA 3.0 ports 0-3 Supported T-SGPIO2 I-SATA 3.0 ports 4/5 Supported S-SGPIO1 S-SATA 3.0 ports 0-3 Supported
Power SMB (I2C) Connector
The Power System Management Bus (I2C) connector (JPI2C1) monitors power supply, fan, and system temperatures. See the table on the right for pin defi nitions.
PWR SMB
Connector (JPI2C1)
Pin Defi nitions
Pin# Defi nition 1 Clock 2 Data 3 PMBUS_Alert 4 Ground 5 +3.3V
IPMB I2C SMB
A System Management Bus header for IPMI 2.0 is located at JIPMB1. Connect the appropriate cable here to use the IPMB I2C connection on your system.
SMB Header
(JIPMB1)
Pin Defi nitions
Pin# Defi nition 1 Data 2 Ground 3 Clock 4 No Connection
Page 73
Chapter 5: Advanced Serverboard Setup
5-19
5-8 Jumper Settings
Explanation of Jumpers
To modify the operation of the serverboard, jumpers can be used to choose between optional settings. Jumpers create shorts between two pins to change the function of the connector. Pin 1 is identifi ed with a square solder pad on the printed circuit board. See the diagram at right for an example of jumping pins 1 and 2. Refer to the serverboard layout page for jumper locations.
Note: On two-pin jumpers, "Closed" means the jumper is on and "Open" means the jumper is off the pins.
Connector
Pins
Jumper
Setting
3 2 1
3 2 1
JBT1 contact pads
CMOS Clear
JBT1 is used to clear CMOS, which will also clear any passwords. Instead of pins, this jumper consists of contact pads to prevent accidentally clearing the contents of CMOS.
To Clear CMOS
1. First power down the system and unplug the power cord(s). It is also recommended that you remove the onboard battery from the serverboard.
2. With the power disconnected, short the CMOS pads with a metal object such as a small screwdriver.
3. Remove the screwdriver (or shorting device).
4. Reconnect the power cord(s) and power on the system.
Note 1. For an ATX power supply, you must completely shut down the system, remove the AC power cord, and then short JBT1 to clear CMOS.
Note 2. Be sure to remove the onboard CMOS Battery before you short JBT1 to clear CMOS.
Note 3. Clearing CMOS will also clear all passwords. Note 4: Do not use the PW_ON connector to clear CMOS.
Page 74
5-20
FatTwin F628G3-FT+/FTPT+ User's Manual
LAN Enable/Disable
JPL1 enables or disables GbE LAN ports 1/2 on the X10DRFF-iG and 10GbE LAN ports 1/2 on the X10DRFF-i TG. S e e t h e table on the right for jumper settings. The defau lt sett ing is Ena bled.
LAN Enable (JPL1)
Jumper Settings
Jumper Setting Defi nition Pins 1-2 Enabled (Default) Pins 2-3 Disabled
Watch Dog Enable/Disable
The Watch Dog (JWD1) is a system monitor that will reboot the system when a software application hangs. Close pins 1-2 to re set the syste m if an appli ­cation hangs. Close pins 2-3 to generate a non- maskable inter rupt signal fo r the applic at i o n th at h an gs . Se e t he table on the ri ght fo r jump er s et tin gs. T he Watch Dog must also be enabled in the BIOS.
Watch Dog (JWD1)
Jumper Settings
Jumper Setting Defi nition Pins 1-2 Reset (Default) Pins 2-3 NMI Open Disabled
VGA Enable (JPG1)
Jumper Settings
Jumper Setting Defi nition Pins 1-2 Enabled (Default) Pins 2-3 Disabled
BMC Enable (JPB1)
Jumper Settings
Jumper Setting Defi nition Pins 1-2 BMC Enable
(Default)
Pins 2-3 Disabled
VGA Enable
Jumper JPG1 allows the user to enable the onboard VGA connector. The default setting is on pins 1-2 to enable the connection. See the table on the right for jumper settings.
BMC Enable
Jumper JPB1 allows you to enable the embedded ASpeed AST2400 Baseboard Management Controller (BMC) to provide IPMI 2.0/KVM support on the serverboard. See the table on the right for jumper settings.
Page 75
Chapter 5: Advanced Serverboard Setup
5-21
ME Mode Select (JPME2)
Jumper Settings
Jumper Setting Defi nition Pins 1-2 Normal (Default) Pins 2-3 Manufacture Mode
Manufacturer Mode Select
Close pin 2 and pin 3 of Jumper JPME2 to bypass SPI fl ash security and force the system to operate in the manufacturer mode, which will allow the user to fl ash the system fi rmware from a host server for system setting modifi cations. See the table on the right for jumper settings.
Page 76
5-22
FatTwin F628G3-FT+/FTPT+ User's Manual
5-9 Onboard Indicators
IPMI Dedicated LAN LEDs
In addition to the LAN Port 1, an IPMI Dedicated LAN is also located on the I/O panel. The amber L ED on the right indic ates conn ectio n and activ ity; wh ile the gree n LED on the lef t indic ates the speed of the connection. See the tables at right fo r more info rmati on.
IPMI LAN Link/Speed LED (Left) & Activity LED (Right)
LED Color/Status Defi nition
Link (Left)
Green: Solid 100 Mbps Amber: Solid 1 Gbps
Activity (Right) Orange: Blinking Active
IPMI LAN
Activity LEDLink LED
LAN LEDs
The Ethernet LAN port is located on the IO Backplane on the serverboard. Each LAN port has two LEDs. The Yellow LED indicates activity. The Link LED on the left side of the LAN port may be green, amber or off to indicate the speed of the connection. See the tables on the right for more information.
Activity LED
Link Speed
LED
GLAN LED
LAN Port Activity LED (Left)
LED State
Color Status Defi nition Orange Flashing Active
1Gbps LAN Link
LED Settings
(For X##xxx-MB)
Color Defi nition Off No Connection,
10 Mbps
Green 100 Mbps Amber 1 Gbps
10Gbps LAN Link
LED Settings
(For X##xxx-MB)
Color Defi nition Off No Connection,
10 or 100 Mbps
Green 10 Gbps Amber 1 Gbps
Page 77
Chapter 5: Advanced Serverboard Setup
5-23
BMC Heartbeat LED
A BMC Heartbeat LED is located at LEDBMC on the serverboard. When LEDBMC is blinking, the BMC is norm al. See the tabl e at right for mo re information.
BMC Heartbeat LED
States
Color/State Defi nition Green: Blinking BMC: Normal
HDD Activity LED
Status
Color/State Defi nition Green: Blinking HDD: Active
HDD Activity LED
The HDD Activity LED is located at HDD_LED1 on the serverboard. When HDD_LED1 is blinking, HDD is active. See the table on the right for more information.
Serverboard Fault LED
The serverboard Fault LED is located at Failure_LED2 on the serverboard. When Failure_LED2 is on or blinking, an error has occurred to the serverboard. See the table on the right for more information.
Serverboard Fault LED
Status
State Defi nition Solid: On MB overheating Blinking@1Hz Fan Failure Blinking@0.25Hz Power Supply
Failure
Page 78
5-24
FatTwin F628G3-FT+/FTPT+ User's Manual
5-10 Serial ATA and SAS Connections
SATA 3.0 Connections
Ten SATA 3.0 connections (I-SATA0-5, S-SATA0-3) are located on the serverboard. All these SA T A 3.0 ports are supported by the Intel PCH C612. I-SAT A4/5, the yellow connectors with power pins built-in, are used with Supermicro SuperDOM (Disk­on-Module) connectors, and do not require external power cables. SuperDOMs are backward-compatible with regular SATA HDDs and SATA DOMs that require external power cables. All SATA ports provide serial-link signal connections, which are faster than the connections of Parallel ATA.
Note: For more information on the SATA HostRAID confi guration, please refer to the Intel SATA HostRAID user's guide posted on our website at
http://www.
supermicro.com..
Page 79
Chapter 5: Advanced Serverboard Setup
5-25
Figure 5-4. Driver/Tool Installation Display Screen
5-11 Installing Drivers
The Supermicro ftp site contains drivers and utilities for your system at ftp://ftp.
supermicro.com. Some of these must be installed, such as the chipset driver.
After accessing the ftp site, go into the CDR_Images directory and locate the ISO le for your serverboard. Download this fi le to create a CD/DVD of the drivers and utilities it contains. (You may also use a utility to extract the ISO fi le if preferred.)
Another option is to go to the Supermicro Website at
http://www.supermicro. com/products/. Find the product page for your serverboard here, where you may
download individual drivers and utilities. After creating a CD/DVD with the ISO fi les, insert the disk into the CD/DVD drive
on your system and the display shown in Figure 5-4 should appear.
Page 80
5-26
FatTwin F628G3-FT+/FTPT+ User's Manual
Note: Click the icons showing a hand writing on paper to view the readme fi les for each item. Click the computer icons to the right of these items to install each item (from top to the bottom) one at a time. After installing each item, you must re-boot the system before moving on to the next item on the list. The bottom icon with a CD on it allows you to view the entire contents.
SuperDoctor 5
The Supermicro SuperDoctor® 5 is a hardware and operating system services monitoring program that functions in a command-line or web-based interface in Windows and Linux operating systems. The program monitors system health information such as CPU temperature, system voltages, system power consumption, fan speed, and provides alerts via email or Simple Network Management Protocol (SNMP).
SuperDoctor 5 comes in local and remote management versions and can be used with Nagios to maximize your system monitoring needs. With SuperDoctor 5 Management Server (SSM Server), you can remotely control power on/off and reset chassis intrusion for multiple systems with SuperDoctor 5 or IPMI. SD5 Management Server monitors HTTP, FTP, and SMTP services to optimize the effi ciency of your operation.
Note: The default User Name and Password for SuperDoctor 5 is admin / admin.
Figure 5-5. SuperDoctor 5 Interface Display Screen (Health Information)
Page 81
Chapter 5: Advanced Serverboard Setup
5-27
Figure 5-6. SuperDoctor 5 Interface Display Screen (Remote Control)
Note: The SuperDoctor 5 program and User’s Manual can be downloaded from the
Supermicro web site at http://www.supermicro.com/products/nfo/sms_sd5.cfm. For Linux, we recommend that you use the SuperDoctor II application instead.
Page 82
5-28
FatTwin F628G3-FT+/FTPT+ User's Manual
5-12 Serverboard Battery
Caution: There is a danger of explosion if the onboard battery is installed upside
down, which will reverse its polarites (see Figure 5-7). This battery must be replaced only with the same or an equivalent type recommended by the manufacturer (CR2032). Dispose of used batteries according to the manufacturer's instructions.
Figure 5-7. Installing the Onboard Battery
LITHIUM BATTERY
BATTERY HOLDER
Please handle used batteries carefully. Do not damage the battery in any way; a damaged battery may release hazardous materials into the environment. Do not discard a used battery in the garbage or a public landfi ll. Please comply with the regulations set up by your local hazardous waste management agency to dispose of your used battery properly.
Page 83
Chapter 6: Advanced Chassis Setup
6-1
Chapter 6
Advanced Chassis Setup
This chapter covers the steps required to install components and perform maintenance on the F424AG-R2K04BP chassis. For component installation, follow the steps in the order given to eliminate the most common problems encountered. If some steps are unnecessary, skip ahead to the step that follows.
Tools Required: The only tool you will need to install components and perform maintenance is a Philips screwdriver.
6-1 Static-Sensitive Devices
Electrostatic discharge (ESD) can damage electronic com ponents. To prevent damage to any printed circuit boards (PCBs), it is important to handle them very carefully. The following measures are generally suffi cient to protect your equipment from ESD damage.
Precautions
Use a grounded wrist strap designed to prevent static discharge.
T ouch a grounded metal object before removing any board from its antistatic bag.
Handle a board by its edges only; do not touch its components, peripheral chips,
memory modules or gold contacts.
When handling chips or modules, avoid touching their pins.
Put the serverboard, add-on cards and peripherals back into their antistatic
bags when not in use.
For grounding purposes, make sure your computer chassis provides excellent
conductivity between the power supply, the case, the mounting fasteners and the serverboard.
Unpacking
The serverboard is shipped in antistatic packaging to avoid static damage. When unpacking the board, make sure the person handling it is static protected.
Page 84
6-2
FatTwin F628G3-FT+/FTPT+ User's Manual
Figure 6-1. Front and Rear Chassis Views
6-2 Control Panel
The control panel for each node is located on the front of the chassis. The LEDs inform you of system status.
See Chapter 3 for details on the LEDs and the control panel buttons.
Ethernet Ports USB Ports VGA Port IPMI LAN Port
SATA Drives (8)
Power Supply
PCI-E Expansion Slots
Chassis Fan
Page 85
Chapter 6: Advanced Chassis Setup
6-3
6-3 Removing the Power Cord
Before performing any setup or maintenance on the chassis, use the following procedure to ensure that power has been removed from the system.
Removing the Power Cord
1. Use the operating system to power down the node, following the on-screen
prompts.
2. After the system has completely shut-down, carefully grasp the head of the
power cord and gently pull it out of the back of the power supply.
3. If your system has dual redundant power supplies, remove the cords from
both power supplies.
4. Disconnect the cord from the power strip or wall outlet.
6-4 Removing Nodes from the Chassis
Each of the four individual serverboard nodes may be removed from the chassis. Note that any time a node is removed from the chassis, the hard drives located in the node will shut-down.
Removing a Serverboard Node
1. Power down the system and remove the power cords from the rear of the
node as described in Section 6-3 above.
2. Grasp the node by the handles on either side of the front of the node.
3. Carefully pull the node forward and out of the chassis.
Page 86
6-4
FatTwin F628G3-FT+/FTPT+ User's Manual
6-5 Installing and Removing Hard Drives
The F424AG chassis contains individual motherboards in separate 2U nodes. Each serverboard node controls the hard drives contained within that node. Note that if a serverboard node is pulled out of the chassis, the hard drives associated with that node will power down as well. Refer to the charts below and on the following pages for your specifi c chassis confi guration. These instructions apply to hot-swappable hard drives in both 2.5" and 3.5" sizes.
Only enterprise level hard drives are recommended for use in Supermicro chassis.
F424AG-R2K04BP
Node 2
Controls two 3.5" HDDs, B1-B2
Node 4
Controls two 3.5" HDDs, D1-D2
Node 1
Controls two 3.5" HDDs, A1-A2
Node 3
Controls two 3.5" HDDs, C1-C2
Figure 6-2: Node Locations
Node 2
Node 4
Node 1
Node 3
Page 87
Chapter 6: Advanced Chassis Setup
6-5
Removing Hard Drives from the Front of the Node
F424AG models are equipped with two (2) hot-swap 3.5" hard drives per node. These hard drives are hot-swappable and can be removed without powering down the server. The procedure to remove hard drives from the node is the same for both models.
Removing Hard Drive Carriers from the Chassis
1. Press the release button on the drive carrier. This extends the drive bay
handle.
2. Use the handle to pull the drive carrier out of the chassis.
Figure 6-3: Removing a Hard Drive Carrier from the Front of the Node
1
1
1
2
Page 88
6-6
FatTwin F628G3-FT+/FTPT+ User's Manual
Figure 6-4: Removing a Dummy Drive from the Drive Carrier
Drive Carrier
Dummy Drive
1
2
1
2
Installing 3.5" Hard Drives into the Drive Carriers
The hard drives are mounted in drive carriers to simplify their installation and removal from the chassis. These carriers also help promote proper airfl ow through the drive bays.
Removing the Dummy Drive from the Drive Carrier
1. Remove the hard drive carrier from the chassis as described in the previous section and lay the drive carrier on a fl at surface.
2. Remove the screws securing the dummy drive to the drive carrier.
3. Lift the dummy drive from the drive carrier.
Warning: Except for short periods of time while swapping hard drives, do not operate the server with the hard drive bays empty.
Page 89
Chapter 6: Advanced Chassis Setup
6-7
Caution: Enterprise level hard disk drives are recommended for use in Supermicro chassis and servers. For information on recommended HDDs, visit the Supermicro Web site at http://www.supermicro.com/products/nfo/fi les/
storage/SAS-CompList.pdf
Installing a Hard Drive into the Drive Carrier
1. Place the hard drive carrier on a fl at surface.
2. Insert the hard drive into the carrier with the printed circuit board side facing downward and so that the mounting holes in the drive align with those in the drive carrier.
3. Secure the hard drive to the carrier with the screws included with the hard drive.
4. Use the open handle of the drive carrier to insert the drive carrier into the open drive bay.
5. Secure the drive carrier into the drive bay by closing the drive carrier handle.
Drive Carrier
SATA
Hard Drive
Figure 6-5: Installing a Hard Drive into the Drive Carrier
1
3
1
3
Page 90
6-8
FatTwin F628G3-FT+/FTPT+ User's Manual
6-6 Node Confi gurations
Node confi guration specifi cations are shown in the table below.
F424AG-R2K04BP
Front of Node Rear of Node
Two low-profi le PCI-E slots
Two 3.5" HDDs
Two optional fi xed fans
Figure 6-6: F424AG Node
Front of the Node
Rear of the Node
Page 91
Chapter 6: Advanced Chassis Setup
6-9
6-7 Removing the Node Cover
Each node has a removable cover which will permit access to the nodes components.
Removing the Node Cover
1. Power down the system and remove the power cord from the rear of the power supply as described in Section 6-3. Remove the node from the chassis as described in Section 6-4 and place the node on a fl at, stable surface.
2. Remove the screws securing the cover to the node, as illustrated above.
3. Lift the cover up and off the node.
Figure 6-7: Removing the Node Cover
Page 92
6-10
FatTwin F628G3-FT+/FTPT+ User's Manual
6-8 Removing and Installing the Backplane
The F424AG chassis backplane is located behind the hard drives in each serverboard node. Although backplane failure rarely occurs, in the event of a backplane failure, follow the instructions below.
Removing the Backplane
Removing the Backplane from the Node
1. Remove the power cord from the rear of the node as described in Section 6-3. Remove the node from the chassis as described in Section 6-4. Place the node on a fl at, stable surface and remove the node cover as described in Section 6-7.
2. Lift the mylar air shroud off the top of the serverboard and remove it from the node.
3. Remove the two screws securing the backplane to the node.
Figure 6-8: Removing the Screws from the Backplane
4. Lift the backplane up and out of the node.
Figure 6-9: Removing the Backplane from the Node
1
3
1
4
Page 93
Chapter 6: Advanced Chassis Setup
6-11
Installing the Backplane
Installing the Backplane into the Node
1. Ensure that all of the hard drive carriers have been removed from the bays in the front of the node (see 6-5 Installing and Removing Hard Drives).
2. Ease the backplane forward, against the front of the node.
3. Align the mounting holes in the backplane with the holes in the chassis. Replace the screws securing the backplane to the Node.
Figure 6-10: Installing the Backplane
4. Reconnect all cables and return the hard drive trays to their bays in the front of the serverboard node.
5. Return the air shroud to its position on the serverboard, reinstall the cover onto the node, plug the power cord into the back of the power supply and power up the system.
1
2
1
3
Page 94
6-12
FatTwin F628G3-FT+/FTPT+ User's Manual
Figure 6-12: Removing the Lower Power Distributor Board
Figure 6-11: Removing the Upper Power Distributor Board
6-9 Power Distributor Board Replacement
Each of the serverboard nodes includes an upper and lower power distributor board. In the unlikely event of a failure of the power distributor board, replacement is simple and requires only a Phillips head screwdriver.
Changing the Power Distributor Board
1. Remove the power cord from the rear of the node as described in Section 6-3. Remove the node from the chassis as described in Section 6-4. Place the node on a fl at, stable surface and remove the node cover as described in Section 6-7.
2. Remove the four screws securing the upper power distributor board to the support bracket.
3. Carefully lift the power distributor board up and out of the node. Set the screws aside for later use.
4. Remove the screw securing the bracket to the fl oor of the node and lift it out of the node.
5. Remove the screws securing the lower power distributor board to the fl oor of the node and set the screws aside for later use.
6. Lift the lower power distributor board up and out of the chassis.
1
3
1
6
Page 95
Chapter 6: Advanced Chassis Setup
6-13
Figure 6-13: Installing the Lower Power Distributor Board
Figure 6-14: Installing the Upper Power Distributor Board
7. Install the replacement lower power distributor board into the same position on the fl oor of the serverboard node, aligning the mounting holes of the board with those in the node.
8. Secure the lower power distributor board with the two screws previously set aside. Do not exceed eight pounds of torque when tightening the screws.
9. Put the support bracket back into place in the node and secure it with the screw previously set aside.
10. Secure the upper power distributor board to the support bracket using the four screws previously set aside. Do not exceed eight pounds of torque when tightening the screws.
11. Replace the air shroud and return the node to its bay in the chassis.
12. Reattach the power cord to the back of the power supply and power up the node.
1
7
1
10
Page 96
6-14
FatTwin F628G3-FT+/FTPT+ User's Manual
6-10 Installing the Serverboard
Compatible Motherboards
For the most up-to-date information on compatible motherboards and other parts, visit the Supermicro Web site at www.supermicro.com.
Permanent and Optional Standoffs
Standoffs prevent short circuits by creating space between the serverboard and the oor of the node. The F424AG chassis includes permanent standoffs in locations used by most motherboards. These standoffs use the rounded Phillips head screws included in the F424AG accessories packaging.
Some motherboards require additional screws for heatsinks, general components and/or non-standard security. Optional standoffs are used for these motherboards.
To use an optional standoff, compare the mounting holes in the serverboard with those in the fl oor of the serverboard node. Then place a screw through the bottom the node and secure the screw with a hexagonal nut (rounded side up).
Depending upon the confi guration of the serverboard being used, it is also possible that some of the optional standoffs which are pre-installed in the chassis, may need to be removed. Add or remove standoffs as needed.
Installing the Serverboard
1. Review the documentation that came with your serverboard. Become familiar with component placement, requirements, cautions, and cable connections.
2. Power down the system and remove the power cord from the rear of the power supply as described in Section 6-3. Remove the node from the chassis as described in Section 6-4 and place the node on a fl at, stable surface. Remove the cover from the node as described in Section 6-7.
3. Compare the holes in the serverboard with those in the fl oor of the node, then add or remove standoffs as needed.
4. Secure the serverboard to the fl oor of the node tray using the rounded, Phillips head screws included for this purpose. Do not exceed eight pounds of torque when tightening down the serverboard.
5. Install the expansion card associated with the serverboard if the chassis is a hot-swappable version. Refer to the next section for instructions on installing the expansion card
6. Secure the CPU(s), heatsinks, and other components to the serverboard as described in the serverboard documentation.
Page 97
Chapter 6: Advanced Chassis Setup
6-15
7. Connect the cables between the serverboard, backplane, chassis, front panel, and power supply, as needed. The fans may be temporarily removed to allow access to the backplane ports.
8. Replace the expansion card bracket and secure the bracket with a screw.
9. Repeat steps 3 - 5 for the remaining nodes.
Figure 6-15: Installing the Serverboard in the Serverboard Node Tray
Page 98
6-16
FatTwin F628G3-FT+/FTPT+ User's Manual
6-11 Installing Front and Rear Expansion Cards
PCI-E Slot Setup
The nodes of some F424AG chassis models support expansion cards. To install low-profi le expansion cards, follow the instructions on the following pages.
Figure 6-16: PCI-E Slot Shield Confi guration
PCI-E Slot Cover
F424AG PCI-E Slot Confi gurations
The F424AG chassis supports up to two expansion cards in the PCI-E slots of each node, Refer to the tables below to determine the PCI-E slot confi guration for your particular chassis.
Page 99
Chapter 6: Advanced Chassis Setup
6-17
F424AG-R2K04BP
Front of Node Rear of Node
Two low-profi le expansion cards
Two 3.5" HDDs
Two optional fi xed fans
Installing a Low-Profi le Expansion Card
Each serverboard node supports two low-profi le expansion cards.
Installing an Expansion Card into a Node
1. Remove the power cord from the rear of the node as described in Section 6-3. Remove the node from the chassis as described in Section 6-4. Place the node on a fl at, stable surface and remove the node cover as described in Section 6-7.
2. Remove the mounting screw which secures the PCI-E slot cover in the PCI-E slot and set this aside for later use.
3. Remove the PCI-E slot cover by sliding it upward and out of the PCI-E slot.
4. Simultaneously slide the expansion card into the open PCI-E slot, while inserting the expansion card into the serverboard.
5. Secure the expansion card to the node using the screws that were previously set aside.
6. Replace the air shroud as described in the following section.
7. Place the cover on the node and secure it with the screws previously set aside.
8. Return the node to its bay in the chassis.
Figure 6-17: Installing the Expansion Card
PCI-E Slot
Expansion
Card
Mounting Screw
Page 100
6-18
FatTwin F628G3-FT+/FTPT+ User's Manual
6-12 Installing Internal GPUs
Each node supports up to three (3) internal GPUs with optional internal rear fans. There are a variety of internal GPUs supported by the F424AG chassis. For the most up-to-date list of compatible GPUs, visit the Supermicro web site at www.
supermicro.com
.
Installing a Front Nvidia GPUs/Intel Xeon Phi into the GPU Bracket
Installing a Front Nvidia GPUs/Intel Xeon Phi into a Bracket
1. Remove the power cord from the rear of the node as described in Section 6-3. Remove the node from the chassis as described in Section 6-4. Place the node on a fl at, stable surface and remove the node cover as described in Section 6-7.
2. Secure both mounting brackets with three screws.
3. Insert the Nvidia GPUs/Intel Xeon Phi into the GPU bracket and secure with ve screws.
4. Confi rm that the Nvidia GPUs/Intel Xeon Phi is securely mounted in the GPU bracket
Figure 6-18: Installing the Nvidia GPUs/Intel Xeon Phi into the Bracket
1
2
1
3
1
4
Installing a Front Nvidia GPUs/Intel Xeon Phi into the Node
Installing a Front Nvidia GPUs/Intel Xeon Phi into a Node
1. Confi rm that the Nvidia GPUs/Intel Xeon Phi has been correctly installed in the GPU bracket as described in the previous section.
2. Position the GPU bracket in the node as illustrated below.
3. Secure the GPU bracket to the node as shown using the four screws provided.
4. Proceed to the next section to install the rear GPUs.
Loading...