WARNING: If the information in these instructions are not followed
exactly, a fire or explosion may result causing property damage,
personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Don’t touch any electrical switch; do not use any telephone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
Note: Not For Installation in Mobile Homes or Recreational Vehicle.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for the future reference.
563 Barton Street, Stoney Creek, Ontario, L8E 5S1
www.superiorradiant.com
02/14 LT094
CAUTION: FIRE OR EXPLOSION HAZARD
Maintain clearance to combustible constructions as further specified in this manual. Failure
to do so could result in a serious fire hazard. Heaters should not be located in hazardous
atmospheres containing flammable vapors or combustible dusts. Signs should be provided in
storage areas specifying maximum safe stacking height.
CAUTION: MECHANICAL HAZARD
This equipment expands and contracts with each operating cycle. The gas connection,
suspension hardware and the installation itself must safely allow this movement. Failure to
do so could result in serious fire or explosion hazard.
CAUTION: FIRE OR EXPLOSION HAZARD
This heater is equipped with an automatic ignition device. Do not attempt to light the burner
by hand. Failure to comply could result in a serious fire and personal injury hazard.
CAUTION: MECHANICAL HAZARD
Do not use high pressure (above 1/2 psi) to test the gas supply system with the burners
connected. Failure to do so could result in damage to the burner and its control components
requiring replacement.
CAUTION: SERVICE LIFE RISK
Do not install equipment in atmospheres containing halogenated hydrocarbons or other
corrosive chemicals. Failure to do so may lead to premature equipment failure and
invalidation of the warranty. Additionally, it is recommended that the equipment be installed
with a slope downward and away from the burner of ¼" inch in 10' feet to allow start-up
condensate drainage.
Superior Radiant Products is a company in the infrared heating industry founded on the principles of
product quality and customer commitment.
Quality commitments are evidenced by superior design, a regard for design detail and an upgrade of
materials wherever justifiable.
Customer commitment is apparent through our ready responses to market demands and a never ending
training and service support program for and through our distributor network.
Important
These instructions, the layout drawing, local codes and ordinances, and applicable standards such as
apply to gas piping and electrical wiring comprise the basic information needed to complete the
installation, and must be thoroughly understood along with general building codes before proceeding.
Only personnel who have been trained and understand all applicable codes should undertake the
installation. SRP Representatives are Factory Certified in the service and application of this
equipment and can be called on for helpful suggestions about installation.
Installation Codes
Installations must comply with local building codes, or in their absence, the latest edition of the national
regulations and procedures as listed below.
General Installation and Gas Codes
Heaters must be installed only for use with the type of gas appearing on the rating plate, and the
installation must conform to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 in the US and
CAN/CGA B149.1 and B149.2 Installation Codes in Canada.
This heater maybe approved for either indoor or outdoor installation. Not for use in residential dwellings,
refer to Rating plate.
Aircraft Hangar Installation
Installation in aircraft hangars must conform to the Standard for Aircraft Hangars, ANSI/NFPA 409 in the
US and CAN/CGA B149.1 and B149.2 Installation Codes in Canada.
Public Garage Installation
Installation in public garages must conform to the Standard for Parking Structures, NFPA-88A or
Standard for Repair Garages, NFPA 88B, in the US and CAN/CGA B149.1 and B149.2 Installation Codes in Canada.
Parking Structures
Technical requirements are outlined in ANSI/NFPA 88B (USA)
Series GR Page 4 February 10, 2014
Introduction
The appliance must be isolated from the gas piping system by closing equipment shutoff valve during
any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psi (305
Kpa)
Electrical
All heaters must be electrically grounded in accordance with the National Electric Code, ANSI/NFPA
70 in the USA and the Canadian Electric Code, CSA C22.1 in Canada, and must comply with all local
requirements.
Venting
Refer to the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) in the USA and CAN/CGA B149.1 and
B149.2 Installation Codes in Canada for proper location, sizing and installation of vents as well as
information on clearance requirements for conventional venting methods. See page 11 for horizontal
venting requirements.
This appliance shall not be connected to a chimney flue serving a separate solid-fuel burning
appliance.
High Altitude
When installing this appliance over 4500 ft. above sea level in Canada, the appliance must be properly
de-rated and installed according to local codes. In the absence of local codes the appliance must be derated in accordance with the most recent CAN/CGA-B149 code.
In the United States for installations over 2000ft above sea level the appliance must be installed in
accordance with the Current National Fuel Gas Code, ANSI Z223.1/NFPA 54.
Safety Features
This heater utilizes an airflow switch as blocked vent shut off system. This system is designed to
prevent the operation of the appliance if a fresh air supply is blocked or if the flue exhaust is blocked.
If this system fails to operate DO NOT ATTEMPT ADJUSTMENTS. Disconnect power to the
appliance and contact a qualified service person.
Series GR Page 5 February 10, 2014
General Specifications
Gas Supply
Inlet Pressure
Natural Gas: Min. 5.0" W.C. Propane Gas: Min. 11.5" W.C.
Max. 14.0" W.C. Max. 14.0" W.C.
Manifold Pressure
Natural Gas: 3.5" W.C. Propane Gas: 10.5" W.C.
Inlet Connection
Natural Gas or Propane Gas: 1/2" NPT. Female
Electric Supply
120 VAC, 60 Hz., 1 Amp: Heater includes a 36" power cord with grounded 3 prong plug.
Heater Specifications
Input: Model GR-30: 30,000 BTUh Model GR-45: 45,000 BTUh
Weight: Model GR-30: 100 lbs (45 Kg) Model GR-45: 100 lbs (45 Kg)
Venting: Horizontal venting, Max. air vent / flue for either rate is 10' feet
Roof Venting, Refer to ANSI Z223.1 and CAN/CSA B149.1 and B149.2 fan
assisted appliances for correct sizing.
Flue Dia.: 2" diameter (installed concentrically)
Note: The heater includes a horizontal vent installation kit. The kit contains all components
necessary to vent the heater horizontally and is required. See page 11.
A vertical vent kit is available as an alternate venting method. This Kit Part # RS022 is
available through SRP distributors and contains the appropriate adapters to allow the
connection of B-vent material. See roof-venting page 13.
113.01.0
1.8
15.1
7.5
3.8
5.4
6.4
Figure 1: Overall Dimensional Information
Series GR Page 6 February 10, 2014
Clearance to Combustibles
Clearance to Combustible Materials.
It is very important to observe the minimum clearance to combustibles at all times to avoid any
possibility of property damage or personal injury.
WARNING
Clearances as marked on the heater body must be maintained from vehicles parked beneath. Signs should
be posted identifying any possible violation of the clearance distances from the heater in all vehicle areas.
Maximum allowable stacking height in storage areas should be identified with signs or appropriate
markings adjacent to the thermostat or in a conspicuous location.
Table 1 lists the minimum clearance to combustible materials for various installation configurations.
Additional clearance may be required for glass, painted surfaces and other materials which may be
damaged by radiant or convective heat.
Combustible materials are considered to be wood, compressed paper, plant fibres, plastics, Plexiglas or
other materials capable of being ignited and burned. Such materials shall be considered combustible
even though flame-proofed, fire-retardant treated or plastered.
The stated clearance to combustibles represents a surface temperature of 90°F (50°C) above room
temperature. Building materials with low heat tolerance (such as plastics, vinyl siding, canvas, tri-ply,
etc…) maybe subject to degradation at lower temperatures. It is the installer’s responsibility to assure
that adjacent materials are protected from degradation.
It is important to observe minimum clearance to combustibles at all times to avoid any possibility of
property damage or personal injury. Clearances must be maintained from vehicles parked beneath heaters.
Signs should be posted identifying any possible violation of the clearance distances from the heater in
vehicle areas. Also maximum allowable stacking height in storage areas should be identified with signs or
appropriate markings. Figure 2 shows minimum clearance to combustible materials.
Series GR Page 7 February 10, 2014
Clearance to Combustibles
Configuration Dimension 30,000 BTUh 45,000 BTUh
A
B
Standard
45° Tilt
Vented
Table 1: Clearance to Combustible Table
A
C
D
A
B
C
D
End 5” 5”
2˝
18˝
36˝
18˝
2˝
2˝
33˝
33˝
2˝
18˝
50˝
18˝
3˝
3˝
48˝
48˝
A
D
B
D
B
45°
C
C
Figure 2: Clearance to Combustible Diagram
CAUTION
In all cases, the minimum hanging height from the floor shall be:
In Canada: 7' feet In USA: 8' feet
Series GR Page 8 February 10, 2014
Installation Detail
Installation Sequence
The heater is sent with all parts necessary for installation with the exception of chain.
It is recommended that the heater be hung as high as possible and along an uncluttered wall to give the
reflector a widest possible “view” of the space to be heated. Avoid installation directly over vehicle
parking, over cabinets, or where an open door will interfere. Adhere to minimum clearances on the rating
plate.
Leave adequate space around the burner box for future servicing.
Choose a location that permits easy installation of exterior venting. A horizontal vent length up to 10' feet
is allowed. For vertical venting adhere to local venting tables and methods.
Fasten Support Angle to Ceiling to
Accommodate Heater Hanging Points
96.00"
OR
Note:
Close all open ended "S" hooks, chain links,
and turnbuckles or any open connection.
Figure 3: General Overview of Components Utilized in the Installation
As required, fasten hanging angles to ceiling such that heater-hanging points can be accommodated.
Each hanging point must be able to hold at least 150 lbs.
Allow for movement of heater during expansion and contraction during operating cycle.
Heater must fire horizontally. To tilt reflector at 45°, lengthen two of the hanging points to an appropriate
length using chain. (Each chain length will be approximately 12" inches longer than the high side of the
heater). SRP recommends and make available “quick links” for connecting chain. If any open
ended “S” hooks and turnbuckles are used, the open ends must be closed to avoid unhooking chain
with inadvertent contact.
Series GR Page 9 February 10, 2014
Installation Detail
Outdoor Installation
For outdoor installations the heater must be installed not more than 8" from beneath awnings, and not
less than 24" from back and side as shown in Figure 4. If the heater cannot be protected from the
elements by an overhang, then a protective cover must be installed as shown in Figure 7, Figure 8 and
Figure 9.
Note:
Close all open ended "S" hooks, chain links,
and turnbuckles or any open connectio n.
SIDE
TOP
24"
8"
24"
BACK
When the heater is installed with back and side dimensions greater than the minimum of 24" then
the top dimension may be increased. The new maximum Top dimension is 1/3 of the smallest side or
back clearance.
Example:
Given:Side dimension = 36"
Back dimension = 48"
A ratio of 3:1 must be maintained
The side dimension gives us a maximum Top dimension of (36/3)" = 12"
The back dimension gives us a maximum Top dimension of (48/3)" = 16"
The new Top dimension is 12", the lesser of the two.
Series GR Page 10 February 10, 2014
Figure 4: Outdoors Heater Installation
Installation Detail
24.00" Min. or ("B")
8.39" or ("B/3") Max.
Figure 5: Mounting Distances for Outdoor Installations under Eaves.
28.00" Min. or ("B")
8.00" Max. or ("B/3")
Figure 6: Mounting Distances for Tilted (45°) Outdoor Installations under Eaves.
In the case where the heater is installed at a 45° angle, the minimum dimension inside the overhang is 28"
from both the back and side of the burner box and 8" maximum on the top. If the side or back dimensions
are increased then the top clearance may be increased using the same rules as for a horizontal installation.
NOTE: These dimensions are only for satisfying outdoor heater positioning. Clearance
to combustible must also be satisfied.
Series GR Page 11 February 10, 2014
28.00" Min. or ("B")
8.00" Max. or ("B/3")
Installation Detail
When a heater is installed outdoors without the presence of an adequate eave, then a protective cover must
be installed as illustrated below. This cover is available from your local dealer (Part # RS020).
Cover Installation Sequence
Install support brackets on to heater covers as shown in step 1 in Figure 7.
Pre-assemble the cover and its top covers and bottom cover as shown in step 2 in Figure 7.
Remove the two top screws holding the reflector in place.
Slide cover onto burner making sure the support brackets slide into slots on the bottom cover.
Secure cover to heater by screwing in the cover bracket in step 3B in Figure 8.
Install the extension covers (Front, Back, and Side) as shown in step 4 in Figure 8 if needed.
2
1
Install Both
Top Covers
As Shown,
Then Install
Assembly on
to Heater
Left Support
Bracket, Install
Screw on
Top Hole
Right Support
Bracket, Install
Screw on
Bottom Hole
Cover
Install Bottom
Cover As Shown
Figure 7: Cover Installation Sequence Steps 1 and 2
When a heater is to be installed outdoors at 45° without the presence of an adequate eave, an extension
cover must be used to protect the heater, refer to step 4 in Figure 8. This extension cover is available
through your local SRP Dealer (Part # RS021). Note that both the cover and extension cover must be used
in this case.
3
B
3
A
Attach Cover
Bracket
4
5
Note:
Close all open ended "S" hooks, chain links,
and turnbuckles or any open connection.
Figure 8: Cover Installation Sequence Steps 3 to 5
Series GR Page 12 February 10, 2014
Back
Install 45°
Extension
Covers
As Shown
Front
Side
Installation Detail
Note:
Close all open ended "S" hooks, chain links,
and turnbuckles or any open connection.
Figure 9: Extension Cover for 45° Outdoor Installations
Series GR Page 13 February 10, 2014
Extension Cover
Venting / Combustion Air Ducting
General Requirements
Refer to the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) in the USA and CAN/CGA B149.1
and B149.2 Installation Codes in Canada, as well as all local requirements for vertical venting and
general guidance for minimum distances to openings to the building.
This equipment is of balanced flue construction and mu st be horizontally vented (see Figure 10).
Vertical venting is permitted, but not as a balanced flue assembly. (See roof venting)
Heater may be sloped
Ø4" Combustion
Air Inlet Duct
Wall Thickness
(Max. 10")
(Min. 1")
1
" in 10 '
4
Vent Elbow Kit
P/N RT013
Ø4" Combustion
Air Inlet Duct
666
Ø2" Flue Pipe
Ø4" Combustion
Ø2" Flue
Pipe
Wall Terminal
P/N RS006
Wall Thickness
(Max. 10")
(Min. 1")
Air Inlet Duct
Wall Terminal
P/N RS006
Wall Thickness
(Max. 10")
(Min. 1")
Vent Elbow Kit
P/N RT013
NOTES:
1- This Heater may be rotated at 45° Tilt, but both ends of the heater must be kept at the same elevation.
2- Total Vent Length (Including One (1) Elbow) = 10'
Each Additional Elbow = 4'
Max. Number Of Elbows = 2
Figure 10: Various Venting Orientations
Ø2" Flue Pipe
Wall Terminal
P/N RS006
A flue/air vent length of 8 feet or less is recommended, although a maximum of 10' feet is
allowable (including one elbow).
An approved Wall Terminal that allows the air duct to pass through the wall is required. This is
included with your heater. The Wall Terminal is a zero clearance terminal for both combustible
and non-combustible walls.
For horizontal venting where an elbow is utilized an elbow kit (Part No. RT013) must be used,
refer to Figure 10 for more details.
The 2" inch flue pipe should extend a minimum of 6" inches beyond the end of the 4" inch wall terminal
(for horizontally vented heaters only see Figure 12). Where the vent is under an eave the 2" vent pipe
must have a minimum clearance of 7" from the centerline of the vent to the bottom of the eave, refer to
Figure 11. However, when the 2" pipe is less than 18" from the bottom of the eave, we
recommend the 2" inch flue extend just beyond the eave to prevent the possibility of frost. (Adhere
to any code requirements for clearances to opening in the building).
An optional “Horizontal Elbow Vent Terminal” kit for horizontal venting is also available, refer to
Figure 12 and Figure 13
Series GR Page 14 February 10, 2014
Venting / Combustion Air Ducting
7"
7"
Figure 11: Minimum Clearance under an Eave
The 2"-inch flue vent is inside (concentric with) the 4" inch combustion air inlet duct. Each of the
former must be seamless and all joints must be fastened with screws and sealed with GE RTV-106
high temperature sealant (or equivalent) refer to Figure 12. The exposed 4" combustion air intake pipe
is zero clearance throughout its length.
Seal Joints
Maximum 10 Feet of Venting
With One (1) Elbow
Fasten Screws (Min. one "1" Screw for 2" Flue Pipe)
4" Combustion Air Inlet Duct
2" Flue Pipe
(Flue Vent)
With RTV Silicone
Fasten Screws
(Min. 2 Screws
for 4" Duct)
2" Flue Pipe Should be
Concentric with the 4"
Combustion Air Inlet Duct
Wall Terminal
6.0"
Extension
Wall Terminal
OR
10.0"
Extension
Optional Horizontal
"Elbow Vent Terminal"
Figure 12: Venting / Combustion Air Ducting
Series GR Page 15 February 10, 2014
Seal Joints With RTV Silicone
Venting / Combustion Air Ducting
Optional Horizontal Elbow Vent Terminal
The GR Models are approved to be used with an Elbow as a Horizontal Vent Terminal see Figure 13 for
installation details..
When heater is to be vented through a roof (Vertical Venting), a B-Vent adapter kit (Part # RS022) must
be used. The B-vent must be installed in accordance to the National Fuel Gas Code, ANSI Z223.1 (NFPA
54) in the USA and CAN/CGA B149.1 and B149.2 Installation Codes in Canada. Refer to the former for
correct sizing. Refer to Figure 14 for general overview.
Combustion air may be supplied from the outdoors using the material provided in the vent adapter kit
(Part # RS022) available from your local dealer. Maximum length of fresh air is 10 feet including one
elbow. Fresh air ducting is not provided in the kit.
For Vertical Venting Refer To
ANSI Z223.1 and CAN/CSA B149.1
and B149.2 for Fan Assisted Appliances
for Correct Sizing, Clearance and
Penetration Requirements.
Vertical Vent Kit
P/N RS022
B-Vent
Adapter
4" Combustion
Air Inlet Duct
4" Fresh Air Terminal
(included in vertical vent kit)
B-Vent
Flue Pipe
(Flue Vent)
Figure 14: Roof Venting / Combustion Air Ducting
The B-vent adapter must be secured with screws and sealed with high temperature silicone sealant. Install
B-vent as per local code requirements.
Series GR Page 17 February 10, 2014
Gas Piping
General Requirements
The gas meter and service must be sufficiently large to supply gas to the connected building gas
load including the heating equipment and any other gas-fired equipment. Additionally, the gas
distribution piping must be designed according to local and national ordinances. Generally (low
pressure) systems designed with a maximum 1/2"-inch W.C. total pressure drop meet this
requirement.
Gas supply pipe sizing must be in accordance with the National Fuel Gas Code, ANSI Z223.1
(NFPA 54) in the USA and CAN/CGA B149.1 and B149.2 Installation Codes in Canada.
Before connecting burners to the gas supply system, verify that high pressure testing of the system
has been completed. Failure to do so may expose the burner components to damaging high
pressure, requiring replacement of key components.
Flexible gas connectors of approved type must be installed as shown in Figure 15, in one plane,
and without sharp bends, kinks or twists. A smooth loop of approximately 12" inches in diameter
is best. Failure to install the gas connection in the approved manner will result in a hazardous and
potentially deadly situation due to the movement of the heat exchanger and burner in the normal
course of operation.
CORRECT POSITIONS
Heater MovementVertical
12"
(30 cm)
3" (7.62 cm) Max.
Displacement
(As Shown Below)
INCORRECT POSITIONS
Heater Movement
WRONG
Heater Movement
WRONG
Alternate
Positions
Okay
Heater
Movement
Series GR Page 18 February 10, 2014
WRONGWRONG
Heater
Movement
Figure 15: Flexible Gas Connection
Electrical Wiring
General Requirements
Heaters are normally controlled with the thermostat that is included with your equipment. A 24V signal is
supplied by the heater control module for thermostat connection. Refer to wiring diagram, Figure 16. A
bulkhead fitting in the back panel of the control box is provided for the appropriate wire. In all cases,
heaters must be grounded in accordance with the National Electric Code, ANSI/NFPA 70 in the USA, and
the Canadian Electric Code, CSA C22.1 in Canada, and must comply with all local requirements.
If any of the original wire as supplied with the heater must be replaced, it must be replaced with wiring
having a rating of at least 105°C temperature service and 600 volts capability.
WIRING DIAGRAM
FENWALL DSI
MODEL RE
Yellow
GAS VALVE
Brown
24 Vac Thermostat
THERMOSTAT IS
MOUNTED EXTERNALLY
24V STAT
FENWALL DSI
TH
PSW
V1
IND
L1
24V
V2
GND
S1
HV
FENWALL DSI
TH
PSW
V1
IND
L1
24V
V2
GND
S1
HV
Black
Black
Black
Black
Red
BLOWER
Green
Pink
Yellow
Red
BLOWER
Green
Pink
AIR
SWITCH
Black
Blue
GAS VALVE
AIR
SWITCH
Black
Blue
Purple
Purple
Yellow
Purple
Purple
Yellow
24V
SENSOR
IGNITER
Brown
24V
SENSOR
IGNITER
Blue
Blue
Red
L1
TRANSFORMER
NEUTRAL
BURNER
120V
120 Vac Thermostat
Blue
Blue
Red
L1
TRANSFORMER
NEUTRAL
BURNER
120V
NOTE: The post purge feature is
not utilized with the thermostat
wired on the 120 Vac circuit. This
option only works if the heater is
wired with the thermostat on the
24 Vac circuit above.
THERMOSTAT IS
MOUNTED EXTERNALLY
120 Vac STAT
When connecting 120 VAC stat
the two blue wires used for the 24
Vac stat must be connected
internally.
Series GR Page 19 February 10, 2014
Figure 16: Internal Wiring
Operation / Maintenance
Starting Sequence of Operation
Turn the thermostat up. When the thermostat calls for heat, the blower motor will energize.
When the motor approaches nominal running RPM, the air-proving switch closes and activates the
ignition module.
The ignition module, after a pre-purge period of approximately 30 seconds, energizes the igniter.
Additionally, the gas valve is energized for this ignition trial period of 15 seconds.
If a flame is detected, the ignition sensing rod "reads" a rectification signal and the gas valve
remains open. The sparking stops when the flame signal is established.
If no flame is detected, the gas valve closes and a 30 sec inter-purge period begins. After the inter-
purge, the module repeats the trial for ignition period. If flame is still not established, a third and
final inter-purge followed by a final ignition trial cycle begins. After three trials, the module will
lockout for a period of approximately 1 hour or until reset. (Reset is accomplished by removing power from the module for at least 5 seconds.) After this 1-hour period, the module re-attempts the
full ignition sequence.
When using a 24V thermostat and the heat requirement has been met and the thermostat opens, the
burner shuts off but the fan continues to run for approximately 30 seconds. This is referred to as a
post purge. This allows the products of combustion to be removed from the heat exchanger to avoid
nuisance condensation and increase heat exchanger life.
When using a line voltage thermostat and the heat requirement has been met and the thermostat
opens, the burner and fan shut off with no post purge.
Maintenance
For best performance, the following minimal maintenance procedures should be performed before each
heating season:
Before performing any service or maintenance, shut off gas and electrical supply to heater.
Check condition of forced air blower scroll and motor. Dirt and dust may be blown or vacuumed
from the blower.
Check condition of burner. Remove any foreign objects or debris from inside the burner box or
burner cup.
Inspect the igniter. Replace igniter if there is excessive wear or erosion, breakage or other defects.
Check inside the heat exchanger tube visually with a flashlight. If carbon or scale are present,
scrape or otherwise remove deposits (a wire brush works well).
Be sure the burner observation window is clean and free of cracks or holes. Clean or replace as
necessary.
Check the flue pipe for soot or dirt and reattach to the heater after cleaning as necessary.
The heat exchanger reflector sections may be cleaned by wiping with a damp cloth.
A service agency qualified to adjust and repair infrared heaters should be engaged for service
other than routine maintenance.
Be sure vent terminal and fresh air inlet are free f rom obstructions. If either pipe is restricted, the
safety air switch will not operate properly, and the heater could fail to operate.
Series GR Page 20 February 10, 2014
Trouble Shooting
Blower Motor Fails to Run
Is the thermostat calling for heat? Is there 115V at the burner receptacle?
Check blower side door for seal. Repair as necessary.
Check blower for obstructions. Replace blower if necessary.
No Gas Supply
Check to see if manual supply valve to heater is ON.
Check to see if gas valve knob on heater gas control is ON.
Supply gas pressure can be checked at 1/8" NPT pressure tapping in gas supply system.
Is combination gas control opening? No manifold pressure indicates valve is closed. Gas pressure
downstream of gas control can be measured by connecting a manometer to pressure tap on control.
If the valve is closed, either the gas valve or the ignition module is faulty.
Burner Does Not Light
Is spark visible through site glass during ignition trial? If no, further electrical checks by a
qualified service person are probably necessary.
Check to see if gas lines were properly purged of air.
Check inlet and outlet gas pressure during ignition period.
Check for orifice and air plate obstruction.
Burner Does Not Stay Lit
Check ground wire continuity.
Check insulation on the igniter leads.
Measure flame signal current; it should be above 0.8 micro amps DC.
Replace module if necessary.
Series GR Page 21 February 10, 2014
Trouble Shooting
Troubleshooting Chart
Replace Module if
no power to Motor
Spin Freely?
Unplug Motor
Does Motor/Impeller
YES
Verify at Motor
Check 120V Power
Replace Motor If
Switch
Check Air Lines To
Rectify As Required
Required
For Obstruction
Check Burner System
NO
YES
Operating?
Is Pressure Switch
Set to 1/8"
Check Electrode Gap
Switch
Check For 24V At
Replace Ignition
Wiring As Required
Rectify Transformer Or
Control Module
Valve During
Does 24V Occur At
Replace Valve
YES
Position?
Is Valve In On
YES
As required
Wiring and Rectify
Ignition Trial? Check
Verify Wiring
Verify Ground
Verify Sense Electrode
Rectify As Required
TROUBLESHOOTING CHART
Check Thermostat
Replace If Required
NO
Blower
Turn Up
Thermostat
Series GR Page 22 February 10, 2014
Starts?
YES
Check Ignition Wire
Replace If Damaged
NO
Does
Spark?
Electrode
YES
YES
Valve? Is Gas
Is Gas Present At
Pressure Sufficient?
NO
Burner
Lights?
Rectify As Required
NO
YES
IF PROBLEM PERSISTS CONTACT YOUR LOCAL SRP REPRESENTATIVE
Is There A Flame
Signal To Module?
Min. 0.8 Micro Amps
NO
Lit?
YES
Stays
Burner
YES
Replacement Parts
Figure 17: Replacement Parts
ITEM #
1
2
3
4
PART #DESCRIPTION
CE010
CE158
CE160
CG001
CG009
CE015
45,000 BTU Pressure Switch
30,000 BTU Pressure Switch
Gas Valve - Natural - Honeywell
Gas Valve - Propane - Honeywell
Ignition Module
ITEM #
Not Shown
Not Shown
PART #DESCRIPTION
5
6
7
8
CE011Power Cord
CH011
CE003
RE019
CE008
CE006
Blower Motor
Sight Glass Assy
Flame Sensor
Ignitor
Transformer
Ignition Wire
Series GR Page 23 February 10, 2014
Warranty
SERIES GR INFRARED HEATERS
WARRANTY
The Manufacturer warrants to the original owner that the product will be free of defects in
material and workmanship. This warranty is limited to 36 months from the date of installation for
all components.
The Manufacturer’s obligation under this warranty is limited to repair or replacement, F.O.B. the
factory, of the defective part. In the case of replacement parts, the warranty period shall be the
longer of the original warranty or a period of 12 months from the date of purchase. In no event
shall the Manufacturer be liable for incidental expense or consequential damages of any kind.
This warranty does not cover any shipping, installation or other costs incurred in the repair or
replacement of the product. No materials will be accepted for return without authorization.
This warranty will not apply, if in the judgment of the Manufacturer, the equipment has been
improperly installed, unreasonably used, damaged or modified.
This warranty will not apply to damage to the product when used in corrosive atmospheres and in
particular atmospheres containing halogenated hydrocarbons. No person is authorized to assume
for the Manufacturer, any other warranty, obligation or liability.
THE REMEDIES PROVIDED FOR IN THE ABOVE EXPRESS WARRANTIES ARE THE SOLE
AND EXCLUSIVE REMEDIES. NO OTHER EXPRESS OR IMPLIED WARRANTIES ARE MADE
INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANT ABILITY
OR FITNESS FOR A PARTICULAR USE OR PURPOSE.
Address questions to your local distributor/ or Superior Radiant Products Ltd
Stoney Creek, Ontario 1-800-527-4328
Heater Series :_______________
Installed Rate :_______________Btu/Hr
Serial Number :_______________
Installed Date :_______________
Series GR Page 24 February 10, 2014
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.