Superior DRT2033, DRC2033, DRC2035, DRT2040, DRC2040 Installation And Operation Instructions Manual

...
Page 1
Installation and Operation Instructions
Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
P/N 900004-00 Rev. C 04/2014
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 900004-02.
®
USC
Models DRT2033xxx *
DRC2033xxx *
DRT2035xxx * DRC2035xxx *
DRT2040xxx * DRC2040xxx *
DRT2045xxx * DRC2045xxx *
P900004-00
* “xxx” indicates unique model identifiers. This manual covers all Superior™ DRT2000 and DRC2000 models.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
Installateur : Laissez cette notice avec l’appareil. Consommateur : Conservez cette notice pour consultation ultérieure.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed.
Une barrière conçue pour réduire le risque de brûlure par le hublot chaude est fournie avec l’appareil et doit être installé.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
WARNING AVERTISSEMENT AVISO
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
UNE SURFACE VITRÉE CHAUDE PEUT
CAUSER DES BRÛLURES.
LAISSER REFROIDIR LA SURFACE VITRÉE
AVANT D’Y TOUCHER.
NE PERMETTEZ JAMAIS À UN ENFANT DE
TOUCHER LA SURFACE VITRÉE.
EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
USTED DEBE NUNCA TOCAR
EL VIDRIO CALIENTE.
LOS NIÑOS DEBEN NUNCA
TOCAR EL VIDRIO.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
AVERTISSEMENT : Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incindie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
— Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS:
s Do not try to light any appliance. s Do not touch any electrical switch; do not
use any phone in your building.
s Immediately call your gas supplier from
a neighbor’s phone. Follow the gas supplier’s instructions.
s If you cannot reach your gas supplier, call
the fire department.
— Installation and service must be performed
by a qualified installer, service agency or the gas supplier.
— Ne pas entreposer ni utilizer d’essence ni d’autres
vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
— QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
s Ne pas tenter d’allumer d’appareil. s Ne touchez à aucan interrupteur. Ne pas vous
servir des téléphones se trouvant dans le bâtiment où vous trouvez.
s Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions du fournisseur.
s Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
— L’installation et l’entretien doivent être assurés par un
installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
Page 2
General Information
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
2
An d'éviter de vous
brûler gravement ou de vous blesser, installez une grille ou une barrière physique pour empêcher tout contact direct avec la vitre.
Suivez les instructions de sécurité
ci-dessous et veillez à ce que tous les membres de votre famille soient conscients du danger de brûlure encouru :
s Les surfaces de votre foyer deviennent
EXTRÊMEMENT CHAUDES !
s La vitre située à l'avant du
foyer atteint des températures EXTRÊMEMENT ÉLEVÉES et peut causer de graves blessures en cas de contact.
s Tenez les enfants à l'écart
du foyer lorsqu'il fonctionne. Surveillez attentivement les enfants dans les pièces où un foyer est utilisé afin d'éviter qu'ils ne soient en contact avec la vitre.
s Tenez tous les vêtements, les
meubles, l'essence et tout autre liquide inflammable à l'écart du foyer.
s Même après fermeture du gaz,
les surfaces du foyer restent extrêmement chaudes.
Veillez à coller les Étiquettes de mise
en garde relatives à la sécurité d'utilisation à l'endroit où vous
utilisez le foyer, pour rappeler à tous les utilisateurs les dangers liés aux températures élevées (Page 41).
Lisez L’information de sûreté
importante (Page 41).
Instale una malla o barrera física para evitar
el contacto directo con el vidrio y prevenir las quemaduras y lesiones graves.
Siga las instrucciones de seguridad
a continuación y asegúrese de que todos en su hogar sepan acerca de este peligro de quemadura:
s ¡Las superficies de la chimenea
se ponen MUY CALIENTES!
s El vidrio delante de la
chimenea alcanza temperaturas EXTREMADAMENTE ALTAS y puede causar quemaduras graves si se toca.
s Mantenga a los niños alejados de
la chimenea en funcionamiento. Supervise en forma cercana a los niños en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio.
s Mantenga la ropa, mobiliario,
gasolina y otros líquidos inflamables alejados de la chimenea.
s Aún después de haber apagado
el gas, las superficies de la chimenea permanecen extremadamente calientes.
Asegúrese de colocar las Etiquetas
de advertencia de seguridad de operación en el lugar donde
enciende la chimenea, para que todos recuerden los peligros asociados con las altas temperaturas (Página 41).
Lea Información importante de
seguridad (Página 4).
Seguridad y su
chimenea
La sécurité et
votre foyer
[FRENCH][ENGLISH]
[SPANISH]
Safety and Your
Fireplace
To prevent severe
burns and injuries, install a screen or physical barrier to prevent direct contact with the glass.
Follow the safety instructions
below and be sure everyone in your household understands this burn hazard:
s The surfaces on your fireplace get
EXTREMELY HOT!
s The glass on the front of the
fireplace reaches EXTREMELY HIGH temperatures and can cause severe burns if touched.
s Keep children away from an
operating fireplace. Closely supervise children in any room where a fireplace is operating to prevent contact with glass.
s Keep clothing, furniture,
gasoline, and other flammable liquids away from the fireplace.
s Even after the gas is turned
off, fireplace surfaces remain extremely hot.
Be sure to attach the enclosed
Safety-in-Operation Warnings where you turn on your fireplace, to help remind everyone of the dangers associated with high temperatures (Page 41).
Read Important Safety Information
(Page 4)
All parts of your
IHP replace get
EXTREMELY HOT!
Toutes les parties de votre
foyer IHP deviennent
EXTRÊMEMENT CHAUDES !
¡Todas las partes de la
chimenea IHP se ponen
MUY CALIENTES!
Page 3
General Information
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
3
Traditional Fireplace Contemporary Fireplace
THANK YOU FOR YOUR PURCHASE. WE APPRECIATE YOUR BUSINESS!
Please carefully read and follow all instructions in this manual. Pay special attention to all warnings and safety information. Following these safety, care, and operation instructions will help ensure many years of dependable and enjoyable service from your fireplace.
Please read and understand these instructions before installing, operating, or servicing this product.
We recommend that our gas hearth products be installed and serviced by professionals who are certied in the U.S. by the National Fireplace Institute® (NFI) as NFI Gas Specialists.
General Information
Important Safety Information ............................................................4
Fireplace Installation, Operation, and Maintenance Notices ...............5
Packaging ..........................................................................................7
Introduction .......................................................................................7
Installation
Requirements for the Commonwealth of Massachusetts ..................9
Cold Climate Insulation ......................................................................9
Manufactured Home Requirements .................................................10
Location ...........................................................................................10
Vent Termination Clearances ...........................................................11
Minimum Clearances to Combustibles ............................................13
Wall Finishes / Surrounds / Mantels ................................................14
Installation Preparation ....................................................................14
Installation Sequence ......................................................................15
Construct the Fireplace Framing ......................................................15
Route the Gas Supply Line to the Fireplace .....................................17
Install the Vent System ....................................................................22
Complete the Field Wiring ................................................................34
Install the [Optional] Blower Kit after Installation in the Framing .....36
Connect the Gas Line .......................................................................36
Verify Proper Fireplace Operation ....................................................37
Optional: Install the Firebox Liners ..................................................38
Contemporary Fireplaces: Install the Glass Media ...........................38
Traditional Fireplaces: Install the Logs, Volcanic Stone,
and Glowing Embers .......................................................................38
Install the Glass Door ......................................................................38
Adjust the Air Shutter to Ensure Proper Flame Appearance .............38
Install the Hood ...............................................................................40
Install the Finishing Materials ..........................................................40
Attach the Safety-in-Operation Warnings.........................................41
Installation Accessories ...................................................................42
Gas Conversion Kits ........................................................................44
Operation
Maintenance ....................................................................................57
Accessory Components ...................................................................61
Lighting Instructions .......................................................................64
Troubleshooting ...............................................................................68
Replacement Parts ..........................................................................70
Warranty ..........................................................................................72
Page 4
General Information
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
4
GENERAL INFORMATION
IMPORTANT SAFETY INFORMATION L’information de sûreté importante Información importante de seguridad
WARNING AVERTISSEMENT ADVERTENCIA
Do not operate appliance with the glass front removed, cracked or broken.
Ne pas utiliser l’appareil si le panneau frontal en verre n’est pas en place, est craqué ou brisé.
No opere el artefacto con el frente de vidrio quitado, agrietado o roto.
Do not use this fireplace if any part has been under water. Immediately call a qualified service technician to inspect the fireplace and to replace any part of the control system and any gas control which has been under water.
Ne pas utiliser cet appareil s’il a été plongé, même partiellement, dans l’eau. Appeler un technicien qualifié pour inspecter l’appareil et remplacer toute partie du système de commande et toute commande qui a été plongée dans l’eau.
No use este artefacto si alguna de sus partes ha estado bajo agua. Llame de inmediato a un técnico de servicio calificado para que inspeccione el artefacto y reemplace cualquier parte del sistema de control y cualquier control de gas que haya estado bajo agua.
Due to high temperatures, the fireplace should be located out of traffic and away from furniture and draperies.
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures.
Debido a las altas temperaturas, el artefacto debe situarse fuera de las áreas de tráfico y lejos del mobiliario y cortinas.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Les enfants et les adultes devraient être informés des dangers que posent les températures de surface élevées et se tenir à distance afin d’éviter des brûlures ou que leurs vêtements ne s’enflamment.
Se debe alertar a los niños y adultos sobre los peligros de las altas temperaturas en la superficie y que se mantengan alejados para evitar quemaduras o ignición de la ropa.
Clothing or other flammable material should not be placed on or near the fireplace.
On ne devrait pas placer de vêtements ni d’autres matières inflammables sur l’appareil ni à proximité.
No debe colocarse ropa u otros materiales inflamables sobre y cerca del artefacto.
Young children should be carefully supervised when they are in the same room as the fireplace. Toddlers, young children, and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at-risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children, and other at­risk individuals out of the room and away from hot surfaces.
Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la surface chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habitent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécurité ; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
Se debe supervisar de cerca a los niños cuando estén en el mismo cuarto que el artefacto. Los niños pequeños, los jóvenes y otras personas pueden ser susceptibles a quemaduras por contacto accidental. Se recomienda instalar una barrera física si hay personas en riesgo en la casa. Para restringir el acceso a una chimenea o estufa, instale una puerta de seguridad ajustable para mantener a los niños pequeños, jóvenes y otras personas en riesgo fuera del cuarto y lejos de las superficies calientes.
Any safety screen or guard removed for servicing a fireplace must be replaced prior to operating the fireplace.
Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
Cualquier malla o resguardo de seguridad quitado para dar servicio a un artefacto, debe reinstalarse antes de operar el artefacto.
Installation and repair should be done by a qualified service person. The fireplace should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, et cetera. It is imperative that control compartments, burners, and circulating air passageways of the fireplace be kept clean (Maintenance on Page 57).
L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de poussière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres (Page 57).
Una persona de servicio competente debe realizar la instalación y reparación. Una persona de servicio profesional debe inspeccionar el artefacto antes de usar al menos una vez por año. Se puede requerir limpieza más frecuente debido a la pelusa excesiva del alfombrado, del material de cobijas, etc. Es imprescindible mantener limpios los compartimientos de control, los quemadores y los pasajes de circulación del aire del artefacto (Página 57).
[English] [French] [Spanish]
Page 5
General Information
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
5
FIREPLACE INSTALLATION, OPERATION, AND MAINTENANCE NOTICES
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION, AND LISTINGS OF THIS UNIT.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
AVERTISSEMENT
Une installation, un réglage,une modification, une réparation ou un entretien mal effectué peut causer des dommages matériels ou des blessures. Voir la notice de l’utilisateur qui accompagne l’appareil. Pour de l’aide ou des renseignements supplémentaires, consultez un installateur, un technicien agréé ou le fournisseur de gaz.
WARNING
Failure to comply with these installation instructions will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appliance and/or its operating controls is dangerous.
Page 6
General Information
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
6
WARNING
Clothing or other flammable material should not be placed on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de vêtements ni d’autres matières inflammables sur l’appareil ni à proximité.
WARNING
Improper installation or use of this appliance can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
CAUTION
Hot while in operation. Do not touch. Severe Burns may result. Keep children, clothing furniture, gasoline and other liquids having flammable vapors away.
ATTENTION
L’appareil est chaud lorsqu’il fonctionne. Ne pas toucher l’appareil. Risque de brûlures graves. Surveiller les enfants. Garder les vêtements, les meubles, l’essence ou autres liquides produisant des vapeur inflammables loin de l’appareil.
NOTE:
s If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this appliance. s These fireplaces are designed as supplemental heaters, and are not to be used as the primary heat source when
installed in a dwelling.
s Provide adequate clearances around air openings and adequate accessibility clearance for service and proper
operation. Never obstruct the front or back openings of the fireplace.
s These fireplaces are designed to operate on natural or propane gas only. The use of other fuels or combination of
fuels will degrade the performance of this system and may be dangerous.
s These fireplaces must not be connected to a chimney or flue serving a separate solid fuel burning fireplace. s Only trim kit(s) supplied by the manufacturer shall be used in the installation of this fireplace.
Remarqué :
s Seules les trousses de garniture fournies par le fabricant doivent être utilisées pour l’installation de cet appareil.
Page 7
General Information
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
7
INSTALLATION
PACKAGING
All models include
The assembled vented gas fireplace heater is packaged with: s Literature Kit (envelope in bottom compartment containing Installation and Operation Instructions (this manual),
and Safety-In-Operation Warning Labels)
s U-Shaped Vent Restrictor (attached to Literature Kit envelope) s Hood (Inside firebox)
Traditional models also include
s Log Set (packaged in a carton inside the firebox) s Volcanic Stone—1 bag (in bottom compartment) s Glowing Embers—1 bag (in bottom compartment)
Contemporary models also include
s Glass Media s Contemporary Burner Panel
INTRODUCTION
These vented gas fireplace heaters are sealed combustion, air-circulating gas fireplaces designed for residential and commercial applications.
Millivolt fireplaces have a millivolt gas control valve with piezo ignition system. If a blower will be installed, electrical power must be provided at the time of fireplace installation.
Electronic fireplaces are designed with an electronic intermittent pilot ignition system. External electrical power is required to operate these units. In the event of a power outage, four (4) AA batteries (in battery holder) provide backup power for fireplace operation (excluding the optional blower).
NOTE: Installation and repair should be done by a qualified service person. The fireplace should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the fireplace be kept clean.
Remarqué : L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres.
NOTE: Diagrams and illustrations are not necessarily shown to scale.
Approved Vent Components
These fireplaces are designed, tested and listed for operation and installation with the following vent components only:
s Secure Vent
®
Direct-Vent System Components,
s Secure Flex
®
Flexible Vent Components, and
s Z-FLEX® Model GA Venting Systems listed to UL1777 and ULCS635 manufactured by Flexmaster
Canada Limited.
Use only the correct size venting (4 1/2” inner and 7 1/2” outer). These approved vent system components are labeled for identification. DO NOT use any other manufacturer’s vent
components with these fireplaces.
Codes and Standards
These fireplaces comply with National Safety Standards and are tested and listed by PFS Corporation (Report No. F13-94) to ANSI Z21.88 (in Canada, CSA-2.33), and CAN/CGA-2.17-M91 in both USA and Canada, as vented gas fireplace heaters.
These fireplaces are listed for installation in bedrooms and manufactured homes. The installation must conform to local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54—latest edition (In Canada, the current CAN/CGA-B149.1 installation code). The fireplace, when installed, must be electrically grounded and wired in accordance with local codes or, in the
absence of local codes, with the National Electrical Code, ANSI/NFPA 70—latest edition, or the Canadian Electrical Code, CSA C22.1—latest edition.
Page 8
General Information
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
8
BTU Input
Tabl e 1: Input Rate, Gas Valves
Models
Input Rate (BTU/HR)
Natural Gas Propane Gas
DRC2033 / DRT2033 12,000 10,000 DRC2035 / DRT2035 14,000 12,000 DRC2040 / DRT2040 16,000 15,000 DRC2045 / DRT2045 20,000 19,000
Tabl e 2: Thermal Efficiency (%)
Model
Millivolt Electronic
AFUE * P4 ** AFUE * P4 **
DRC2033 / DRT2033 64 60.4 64 64.8 DRC2035 / DRT2035 65.5 61 65.5 65 DRC2040 / DRT2040 65.5 62 65.5 65 DRC2045 / DRT2045 65 63 65 66
* AFUE is a measurement of the US Department of Energy, ** P4 (EnerGuide) is a measurement of the Canadian Office of Energy Efficiency.
NOTE: Efficiiencies are based on the most commonly used F1797 termination.
Gas Pressure
Tabl e 3: Inlet Gas Supply Pressure
Fuel Minimum Maximum
Natural Gas 5” WC / (1.25 kPa) 10.5” WC / (2.61 kPa)
Propane 11.0” WC / (2.74 kPa) 13.0” WC / (3.23 kPa)
Tabl e 4: Manifold Gas Supply Pressure
Fuel Pressure
Natural Gas 3.5” WC / (0.87 kPa)
Propane 10.0” WC / (2.49 kPa)
Test gauge connections are provided on the front of the millivolt and electronic gas control valve (identified IN for the inlet and OUT for the manifold side). The control valves have a 3/8” (10 mm) NPT thread inlet and outlet side of the valve (Figure 1 and Figure 2).
Figure 1: Millivolt Gas Valve Figure 2: Electronic Gas Valve
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step down regulators to reduce the pressure to safe levels.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
Page 9
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
9
Orifice Sizes—Sea Level to High Altitude
These fireplaces are tested and approved for installation at elevations of 0–4500 ft (0–1372 m) above sea level using the standard burner orifice sizes (Table 5). For elevations above 4500 ft, contact your gas supplier or qualified service technician.
Tabl e 5: Burner Orifice Sizes, Elevation 0–4500 ft ( 0–1372 m)
Model
Natural Gas
drill size
Propane drill size
DRC2033 / DRT2033 #51 (0.067”)* #61 (0.039”)* DRC2035 / DRT2035 #49 (0.073”)* #58 (0.042”)* DRC2040 / DRT2040 #47 (0.078”)* #56 (0.046”)* DRC2045 / DRT2045 #44 (0.086”)* #55 (0.052”)*
* Standard size installed at factory
Deration
At elevations above 4500 ft, the amount of BTU fuel value delivered must be reduced by either:
s Using gas that has been derated by the gas company. s Changing the burner orifice to a smaller size as regulated by the local authorities having jurisdiction and by the
(USA) National Fuel Gas Code NFPA 54/ANSI Z223.1—latest edition or, in Canada, the CAN/CGA-B149.1 codes— latest edition.
NOTE: Flame breadth, height and width will diminish 4% for every 1,000 ft of altitude.
IN CANADA—CAN/CGA-2.17-M91 (HIGH ALTITUDE): THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER’S AUTHORIZED REPRESENTATIVE,
IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER, PROVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/ CGA-B149.1 OR CAN/CGA-B149.2 INSTALLATION CODES.
REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in the U.S. state of Massachusetts if the following additional requirements are met:
s Install this fireplace in accordance with Massachusetts Rules and Regulations 248 C.M.R.. s Installation and repair must be done by a plumber or gas fitter licensed in the Commonwealth of Massachusetts. s The flexible gas line connector used shall not exceed 36” (914 mm) in length. s The individual manual shutoff must be a T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, horizontal terminations installed less than seven (7) ft above the finished grade must comply with the following additional requirements:
s A hard wired carbon monoxide detector with an alarm and battery back-up must be installed on the floor level
where the gas fireplace is installed. The carbon monoxide detector must comply with NFPA 720, be ANSI/UL 2034 listed and be ISA certified.
s A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimum height
of eight (8) ft above grade and be directly in line with the horizontal termination. The sign must read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your fireplace with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which fireplace rests, if floor is above ground level. Gas line holes and other openings should be caulked or stuffed with unfaced fiberglass insulation.
NOTE: Do not use loose, or blown-in insulation in the cavity surrounding the fireplace. If the fireplace is being installed on a cement slab in cold climates, a sheet of plywood or other raised platform can
be placed underneath to prevent conduction of cold transferring to the fireplace and into the room. It also helps to seal inside surfaces and tape for maximum air tightness and caulk firestops.
Page 10
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
10
MANUFACTURED HOME REQUIREMENTS
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
Cet appareil peut être installé dans une maison préfabriquée (mobile) déjà installée à demeure si les règlements locaux le permettent.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil ne peut être converti à d’autres gaz, sauf si une trousse de conversion est utilisée.
CAUTION
Ensure that the cross members are not cut or weakened during installation. The structural integrity of the manufactured home floor, wall, and ceiling / roof must be maintained.
CAUTION
This appliance must be grounded to the chassis of the manufactured home in accordance with local codes or in the absence of local codes, with the National Electrical Code ANSI / NFPA 70—latest edition or the Canadian Electrical Code CSA C22.1—latest edition.
LOCATION
In selecting the location, the aesthetic and functional use of the fireplace are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important.
Due to high temperatures, the fireplace should be located out of traffic and away from furniture and draperies.
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures.
The location should also be free of electrical, plumbing or other heating/air conditioning ducting. These direct-vent fireplaces are uniquely suited for installations requiring a utility shelf positioned directly above the
fireplace. Utility shelves like these are commonly used for locating television sets and decorative plants.
Be aware that this is a heat producing fireplace. Objects placed above the unit are exposed to elevated temperatures. Do not insulate the space between the fireplace and the area above it.
The minimum height from the base of the fireplace to the underside of combustible materials used to construct a utility shelf in this fashion is shown in Table 9 and Table 10.
Figure 3: Typical Locations and Venting
Vertical Vent
(Rear Vent)
Horizontal Vent
(Top Vent)
Vertical Vent
(Top Vent)
(Rear Vent Application)
VERTICAL VENT
(Rear Vent Application without a chase)
HORIZONTAL VENT
Horizontal Vent
(Rear Vent with chase)
Horizontal Vent
(Rear Vent without chase)
Top Vent
Top Vent
Top Vent
Top Vent Top Vent
Top Vent
Rear Vent
Rear Vent
Recessed
Installation
Page 11
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
11
VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI Z223.1/NFPA 54) in the USA or the current standards of CAN/CGA-B149.1 in Canada.
Vertical Vent Termination Clearances
Terminate multiple vent terminations according to the installation codes listed above and Figure 4.
Figure 4: Multiple Terminations
12”
(305 mm)
minimum
Terminate single vent caps relative to building components according to Table 6 and Figure 4.
Tabl e 6: Termi na ti on H ei ghts fo r Ve nts a bo ve F la t or Sl op ed R oo fs ( NFPA 5 4 / ANS I Z2 23 .1 )—Gas Vent Rule
Roof Pitch Termination Height *
12
X
Roof pitch is X/12
2 ft
minimum
2 ft minimum
Lowest
discharge
opening
H*
*H = minimum height from roof to
lowest discharge opening of vent
Horizontal overhang
Vertical
wall
Vent
termination
Storm collar
Concentric
vent pipe
Flashing
1” (25.4 mm) minimum clearance to combustibles
Flat to 6/12 1.0 ft (0.3 m) 6/12 to 7/12 1.25 ft (0.38 m) 7/12 to 8/12 1.5 ft (0.46 m) 8/12 to 9/12 2.0 ft (0.61 m)
9/12 to 10/12 2.5 ft (0.76 m) 10/12 to 11/12 3.25 ft (0.99 m) 11/12 to 12/12 4.0 ft (1.22 m) 12/12 to 14/12 5.0 ft (1.52 m) 14/12 to 16/12 6.0 ft (1.83 m) 16/12 to 18/12 7.0 ft (2.13 m) 18/12 to 20/12 7.5 ft (2.29 m) 20/12 to 21/12 8.0 ft (2.44 m)
Horizontal Vent Termination Clearances
The horizontal vent termination must have a minimum of 6” (152 mm) clearance to any overhead combustible projection of 2 1/2” (64 mm) or less (Figure 5). For projections exceeding 2 1/2” (64 mm) (Figure 5). For additional vent location restrictions refer to Table 7.
All horizontal terminations may be located as close as 6” (152mm) to any (non-combustible and combustible) exterior sidewall. This distance may be decreased to 2” (51mm) for noncombustible exterior sidewalls with all approved terminations (Table 21).
Figure 5: Horizontal Vent Termination Clearances
NOTE: See Figure 27 on Page 29 for exterior
wall recess allowances for compact horizontal termination.
Combustible projection
2 1/2” or less in length
Combustible projection
greater than 2 1/2” in length
6
(152)
Termination kit*
Termination kit
6”
6”
(153 mm)
Ventilated soffit - 18” (457 mm)
Unventilated
soffit - 12”
(305 mm)
*4” to center of termination for F1797, 8” for 94L10, and 10” for H1968
*
Use 6.5” for all horzontal terminations applicable
Page 12
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
12
Tabl e 7: Horizontal vent termination clearances for buildings with combustible and noncumbustible exteriors
Fixed
Closed
Openable
Fixed
Closed
V
V
V
V
V
V
X
X
V
X
G
G
J
F
B
B
K
H
I
A
E
L
D
B
M
C
B
V
V
A
G
G
B
TERMINATION CAP
AIR SUPPLY INLET
GAS METER RESTRICTED AREA
(TERMINATION PROHIBITED)
Openable
See Table 6
V
V
Inside Corner
V
V
Outside Corner Recessed Location
Balcony with No Side WallVBalcony with Perpendicular Side Wall
G
F
M
M
N
P
O
Q
U.S. Installation ** Canadian Installation * A Clearance above grade, veranda, porch, desk, or balcony 12” (300 mm) ** 12” (300 mm) * B Clearance to window or door that may be opened 6” (150 mm)
for fireplaces < 10,000 Btu/h (3 kW),
9” (230 mm)
for fireplaces > 10,000 Btu/h (3 kW), and < 50,000 Btu/h
(15 kW),
12” (300 mm)
for fireplaces > 50,000 Btu/h (15 kW) **
6” (150 mm) for fireplaces < 10,000 Btu/h (3 kW),
12” (300 mm) for fireplaces > 10,000 Btu/h (3 kW)
C Clearance to permanently closed window 9” (229 mm)
recommended to prevent window condensation
12” (305 mm) recommended to prevent window condensation
D Vertical clearance to ventilated soffit located above the
termination within a horizontal distance of 18” (458 mm)
18” (458 mm) 18” (458 mm)
E Clearance to unventilated soffit 12” (305 mm) 12” (305 mm)
F Clearance to outside corner 5” (127 mm)
minimum
5” (127 mm) minimum
G Clearance to inside corner 6” (152 mm) minimum 6” (152 mm) minimum H Clearance to each inside of center line extended above
meter / regulator assembly
36” (910 mm)
within a height of 15 ft above the meter / regulator assembly **
36” (910 mm) within a height of 15 ft above the meter / regulator assembly *
I Clearance to service regulator vent outlet 36” (910 mm)** 36” (910 mm)*
J Clearance to nonmechanical air supply inlet to building or
the combustion air inlet to any other fireplace
6” (150 mm)
for fireplaces < 10,000 Btu/h (3 kW),
9” (230 mm)
for fireplaces > 10,000 Btu/h (3 kW) and < 50,000 Btu/h (15 kW),
12” (300 mm)
for fireplaces > 50,000 Btu/h (15 kW)**
6” (150 mm) for fireplaces < 10,000 Btu/h (3 kW),
12” (300 mm) for fireplaces > 10,000 Btu/h (3 kW)
K Clearance to a mechanical air supply inlet 36” (910 mm) above if within 10 ft (3 m) horizontally ** 72” (1830 mm) * L Clearance above paved sidewalk or paved diveway located
on public property
84” (2130 mm) ‡ 84” (2130 mm) ‡
M Clearance under veranda, porch, deck or balcony 12” (300 mm) *‡ 12” (300 mm) *‡
N Depth of alcove (maximum) 72” (1830 mm) ** 72” (1830 mm) * O Clearance to termination (alcove) 6” (15.2 mm) ** 6” (15.2 mm)* P Width of alcove (minimum) 36” (910 mm) ** 36” (910 mm) * Q Clearance to combustible above (alcove) 18” (457 mm) ** 18” (457 mm) *
*
**
*‡
In accordance with the current CSA-B149.1 National Gas And Propane Installation Code In accordance with the curent ANSI Z223.1/NFPA 54 National Fuel Gas Codes A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings Only permitted if veranda, porch, deck, or balcony is fully-open on a minimum two sides beneath the floor
Page 13
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
13
MINIMUM CLEARANCES TO COMBUSTIBLES Fireplace And Vent Clearances
The fireplace is approved with zero clearance to combustible materials on all sides (Table 8), with the following exception: The unit may not be recessed (allowance made for mantel legs / side trim in Figure 6). When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit (Figure 6).
Tabl e 8: Minimum Clearances *
Back
1” (26mm) to wrapper for 45” model, all
others 1/2” (13mm) to wrapper
0” (0 mm) to Spacers
Sides
1/2” (13 mm) to wrapper 0” (0 mm) to Spacers **
Top Standoffs 0” (0 mm) to top standoffs
Floor 0” (0 mm)
From Bottom of Unit to Ceiling 64” (1626 mm)
Vent
3” (76 mm)—Top * ***
1” (25.4 mm)—Sides and Bottom
Front Service Clearance—
clearance immediately in front of viewing area(s)
36” (914 mm)
* 3” (76 mm) above any horizontal/inclined vent component. ** See Page 18 for clearance requirements to the nailing flange located at each side of the unit and any screw heads adjacent to it. *** Top vent clearance can be reduced to 2” on horizontal runs when first elbow is located at least 6 ft above the fireplace.
The fireplace must be mounted on a fully supported base extending the full width and depth of the unit. The fireplace may be located on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile or other combustible material other than wood flooring, the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
Hearth Extension
A hearth extension is not required with this fireplace. If a hearth extension is used, do not block the lower control compartment door. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements.
Shelf Height
To provide for the lowest possible shelf surface, use the rear vent model. For top vent models, the venting attached to the top vent should be routed in a way to minimize obstructions to the space above the fireplace. Do not insulate the space between the fireplace and the area above it (Table 9 and Table 10). The minimum height from the base of the fireplace to the underside of combustible materials used to construct a utility shelf in this fashion is shown in
Table 9 and Table 10.
Ta bl e 9: Combustible Shelf Height—Top Vent
Model
Top Vent with one 90° Elbow
Shelf Height
(see table)
No combustibles or insulation in the shaded area between the appliance and the shelf above it.
Secure Vent
®
Secure Flex® (flex elbow)
DRC2033 / DRT2033 44” (1118 mm) 46” (1168 mm) DRC2035 / DRT2035 47” (1194 mm) 49” (1245 mm) DRC2040 / DRT2040 52” (1321 mm) 54” (1372 mm) DRC2045 / DRT2045 50” (1270 mm) 52” (1321 mm)
Page 14
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
14
Ta bl e 10: Combustible Shelf Height—Rear Vent
Model
Rear Vent with two 90° Elbows
Shelf Height
(see table)
No combustibles or insulation in the shaded area between the appliance and the shelf above it.
3” clearance from shelf to
top of fireplace and/or vent
pipe, whichever is higher
Secure Vent
®
Secure Flex® (flex elbow)
DRC2033 / DRT2033 34” (864 mm) 34” (864 mm) DRC2035 / DRT2035 35 1/2” (902 mm) 35 1/2” (902 mm) DRC2040 / DRT2040 40 1/2” (1029 mm) 40 1/2” (1029 mm) DRC2045 / DRT2045 45 1/2” (1156 mm) 45 1/2” (1156 mm)
Figure 6: Combustible Side Clearances Figure 7: Mantel Height
3 1/2 in.
(89 mm)
6 in.
(152 mm)
Top View of
Fireplace
45
o
Combustible
mantel legs may
project beyond either side of the fireplace opening as long as they are kept within the shaded area illustrated here.
Combustible Materials Allowed In Shaded Area Safe Zone
Combustible Walls shown in dark gray
At 6 in. minimum side wall clearance, a combustible wall can project to any length.
Top View of
Fireplace
45
o
6”
(152 mm)
Combustible materials allowed in shaded area “Safe Zone”.
Combustible walls shown in dark gray
Combustible mantel legs may project beyond either side of the fireplace opening as long as they are kept within the shaded area illustrated here.
At 6” minimum side wall clearance, a combustible wall can project to any length.
3 1/2”
(89 mm)
12
(305)
10
(254)
8
(203)
6
(152)
4
(102)
2
(51)
in. (mm)
8 (203)
10 (254)
12 (305)
14 (356)
16 (406)
18 (457)
Hood
Fireplace
Mantel depth
Wall Finishes / Surrounds / Mantels
NOTE: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the fireplace front face (black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the fireplace face (Figure 41).
Non-combustible materials, such as surrounds and other fireplace trim, may be installed on the fireplace face, but they must not cover any portion of the removable glass panel or control compartment.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel (Figure 7). Mantels constructed of non-combustible materials may be installed at any height above the fireplace opening. However, do not allow anything to hang below the fireplace hood.
Minimum clearance requirements include any projections such as shelves, window sills, mantels, etc. above the fireplace.
NOTE: To a vo id h ea t- relat ed fi ni sh d amage , us e fin is h mater ia ls r at ed 175 °F, or h ig he r, on the un de rs id e of the mantel.
INSTALLATION PREPARATION
The fireplace is shipped with all gas controls and components installed and pre-wired. Before installing the fireplace, follow these steps:
1. Remove the shipping carton, and retain the front of the carton (used to protect the fireplace during construction).
2. Remove the shipping pad, exposing the front glass door.
3. Remove the glass door (Page 55). NOTE: Place the glass door on the shipping carton to protect its surface.
Page 15
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
15
INSTALLATION SEQUENCE
The typical sequence of installation is outlined below; however, each installation is unique and may result in variations to the steps described.
See the pages referenced in the following steps for detailed instructions.
Framing
1. Construct the Fireplace Framing (Page 15).
2. Prepare the Fireplace Top Spacers (Page 17).
3. Route the Gas Supply Line to the Fireplace (Page 17).
4. Rough in the Electrical Supply, if Needed (Page 18).
5. Install the [Optional] Blower Kit before Installation in the Framing (Page 18).
6. Place the Fireplace in the Framing and Secure (Page 18).
Venting
7. Select a Horizontal or Vertical Vent System (Page 18).
8. Install the Vent Restrictor (if necessary) (Page 19).
9. Install the Vent System (Page 22).
Electrical Connection
10. Complete the Field Wiring (Page 34).
11. Install the [Optional] Blower Kit after Installation in the Framing (Page 36).
Gas Connection
12. Connect the Gas Line (Page 36).
13. Verify Proper Fireplace Operation (Page 37).
Finishing
14. Optional: Install the Firebox Liners (Page 51).
15. Traditional Fireplaces: Install the Logs, Volcanic Stone, and Glowing Embers (Page 52).
16. Contemporary Fireplaces: Install the Glass Media (Page 51).
17. Install the Glass Door (Page 55).
18. Adjust the Air Shutter to Ensure Proper Flame Appearance (Page 38).
19. Install the Hood (Page 40).
20. Reinstall the Included Barrier (Page 40).
21. Install the Finishing Materials (Page 40).
22. Attach the Safety-in-Operation Warning Labels (Page 40).
1. Construct the Fireplace Framing
1. Frame the fireplace as illustrated in Table 11. For corner framing installations, use Table 12. All framing details
must allow for a minimum clearance to combustible framing members as shown in Table 8.
2. If the fireplace is to be elevated above floor level, a solid continuous platform must be constructed below the fireplace. NOTE: Headers may be in direct contact with the fireplace top standoff spacers when they are bent up vertically,
maintaining the 3” clearance to the fireplace top, but must not be supported by them or notched to fit around them. All construction above the fireplace must be self-supporting. DO NOT use the fireplace for structural support.
Page 16
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
16
Tabl e 11: Fireplace Framing Specifications
Model A * B C D E
Vent Framing—Top Vent
with One 90° Elbow
NOTE: Dimension “D” is the required framing depth when the finish material (drywall) thickness is 1/2” (13mm).
Inches (millimeters)
Framing construction to be 2 x 4, or larger.
B
C
D
A
1/2 A
5 1/8
(130)
7 (178)
12 1/8
(308)
10 1/2
(267)
E
DRC2033 /
DRT2033
33 3/4
857
33 1/4
845
36 7/8
930
14 1/2
368
19 5/8
499
DRC2035 /
DRT2035
35 1/4
895
35 1/4
895
38 3/4
984
18
447
23 3/8
594
DRC2040 /
DRT2040
40 1/4
1022
40 1/4
1022
43 3/4
1111
18
447
28 1/4
717
DRC2045 /
DRT2045
45 1/4
1149
40 1/4
1022
43 3/4
1111
18
447
28 1/4
717
C = Minimum height of top vent installations E = Minimum height of rear vent installations
* Minimum opening size; additional 1/8” per side is recommended. NOTE: Framing specifications do NOT apply for flexible venting.
When using flexible venting, refer to the kit requirements for framing specifications.
NOTE: See Page 28 concerning use of compact terminations on rear-vent 45” Models.
Tabl e 12: Fireplace Framing Specifications—Corner Installation with Horizontal Termination
Model A B C D E
F G
B
A
C
Inches (millimeters)
D
E
Back wall of chase/enclosure (including finishing materials)
7 (178)
DRC/T2033
33 3/4
857
51 1/4
1302
36 1/4
921
25 5/8
651
12 1/8
308
5 1/2
140
14 1/2
368
DRC/T2035
35 1/4
895
59 1/2
1511
42 1/16
1068
3. 1/4 768
14 1/4
362
6 5/8
168
18
457
DRC/T2040
40 1/4
1022
63 13/16
1621
45 11/32
1152
32 3/16
818
15 7/8
403
8 1/2
216
18
457
DRC/T2045
45 1/4
1149
70 3/8
1788
49 3/4
1264
35 1/4
895
17 1/2
445
10 1/4
260
18
457
Tabl e 13: Fireplace Specifications
NOTE: When finishing the area around the hood, 5/8” clearance above hood is required for hood installation.
Top View Front View
Left Side View Right Side View
E
F
G
H
J
K
L
M
Blower
access panel
Hood
Junction
box access
Gas line
access
N
O
Model E F G H (door) J K L M N O
DRC2033 / DRT2033 30 1/8 (765) 26 1/4 (667) 18 5/16 (465) 30 1/2 (775) 33 5/8 (854) 21 7/8 (556) 10 15/16 (278) 31 (787) 8 1/8 (207) 14 (356) DRC2035 / DRT2035 32 1/4 (819) 28 3/4 (730) 22 1/4 (565) 32 3/8 (822) 35 1/4 (895) 25 (635) 12 1/2 (317) 32 7/8 (835) 10 1/16 (256) 17 (432) DRC2040 / DRT2040 37 1/8 (943) 33 1/4 (845) 27 1/4 (692) 37 3/8 (949) 40 1/4 (1022) 30 (762) 15 (381) 37 7/8 (962) 10 1/16 (256) 17 (432) DRC2045 / DRT2045 37 1/4 (946) 33 1/4 (875) 25 1/2 (648) 42 3/8 (1076) 45 1/4 (1149) 35 (889) 17 1/2 (445) 42 7/8 (1089) 10 1/16 (256) 17 (432)
F*
G
Page 17
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
17
2.
Prepare the Fireplace Top Spacers
1. The two (2) 3” standoff spacers on top of the fireplace cabinet are shipped flat. Remove the screw adjacent to
the detached end (Figure 8).
2. Bend the standoffs as shown (Figure 9):
3. Align the hole in the standoff with the hole in the fireplace top, and secure with the screw that was removed in Step 1 (Figure 9).
Figure 8: Unassenbled standoff Figure 9: Assembled standoffs
Positioned flat as shipped from the factory
Fireplace Front
Top Standoff
Screw
Configuration for 1/2" finish materials
Fireplace
Front
Top Standoff
Fireplace
Front
Top Standoff
Configuration for 5/8" finish materials
3. Route the Gas Supply Line to the Fireplace
1. Route a 1/2” (13 mm) gas line to the left side of the fireplace (Figure 10 & 10a).
NOTE: Gas lines must be routed, assembled, and made of materials that are in strict accordance with local codes
and regulations. All fireplaces are factory-equipped with a flexible gas line connector and a 1/2” shutoff valve (Page 37).
Figure 10: Routing the gas line - 35”, 40”,
45” Models
Left side front corner of fireplace framing
Pipe coupling (recommended)
7 5/8” (195 mm)
3”
(76 mm)
Proper Sizing of Gas Line
Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code, NFPA 54—latest edition (USA) or CAN/CGA-B149.1— latest edition (Canada).
The gas supply line should not be connected to the appliance until step 12. Connect the Gas Line (Page 36).
NOTE:
s All fireplaces are factory-equipped with a flexible gas line connector and 1/2” shutoff valve (Figure 35). s See Massachusetts Horizontal Vent Requirements for additional requirements for installations in the state of
Massachusetts in the USA.
s A pipe joint compound rated for gas should be used on the threaded joints. Ensure propane-resistant
compounds are used in propane applications. Be very careful that the pipe compound does not get inside the pipe.
s A sediment trap in the supply line as close as possible to the fireplace is recommended. s Check with the local building official for local code requirements (e.g., Are below grade penetrations of the gas
line allowed?, etc).
CAUTION
If propane is used, be aware that with a tank that is too small (i.e., under 100 lbs, if this is the only gas appliance in the dwelling—see NPFA 58), there may be a loss of pressure. This can result in insufficient fuel delivery that can cause sooting, delayed ignition, or other malfunctions. Any damage resulting from an improper installation is not covered by the limited warranty.
Figure 60: Routing the gas line
Left side front corner of fireplace framing
Pipe coupling (recommended)
5 1/4” (140 mm)
3”
(76 mm)
Figure10a: Routing the Gas Line - 33” Model
Page 18
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
18
4.
Rough in the Electrical Supply, if Needed
1. As necessary, rough in the fireplace electrical supply per NEC and local codes.
5. Install the [Optional] Blower Kit before Installation in the Framing
1. Remove the left side blower cover panel screw, and blower cover panel (Table 13). Retain the panel and screw
for later reinstallation.
2. Slide the blower through the opening and position it with the bracket oriented to the front of the firebox and the blower discharge to the rear of the firebox. Bend the two tabs in the firebox floor to secure the blower to the floor.
3. Reinstall the blower cover panel and secure with the removed screw.
4. Access the blower supply wiring through the front of the firebox and plug it into the junction box in the right, rear
of the firebox (Figure 33).
5. Install the blower control switch according to its included instructions.
6. Place the Fireplace in the Framing and Secure
NOTE: Nailing flanges, combustible members, and screw heads in areas directly adjacent to the nailing flanges are
EXEMPT from the 1/2” clearance to combustible requirements for the firebox outer wrapper. NOTE: Combustible framing may be in direct contact with the nailing flanges and may be located within 1/2” of screw
heads and the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact dimensions specified in the framing details in this manual.
1. Bend out the appropriate nailing flanges for the drywall / finish material to be used (Figure 11). Nailing flanges are provided for:
s flush framing, s 1/2”, and s 5/8” framing depths.
2. Secure the fireplace to the side framing members using the unit’s nailing flanges —one top and bottom on each side of the fireplace front (Figure 11). Use 8d nails or the equivalent.
Figure 11: Nailing Flanges
Side
framing
Unit nailing flange (no clearance to combustible framing is required)
VENT SYSTEM PREPARATION
7. Select a Horizontal or Vertical Vent System
1. With the fireplace secured in the framing, determine the vent route and identify the exterior termination location.
The following sections describe vertical (roof) and horizontal (exterior wall) vent applications. Use only approved vent components (Page 7 and Page 42).
NOTE: This fireplace must be vented directly to the outside.
WARNING
The vent system may not service multiple appliances, and must never be connected to a flue serving a separate solid fuel burning appliance.
NOTE: The vent pipe is tested to be run inside an enclosed wall (such as a chase). There is no requirement for
inspection openings in the enclosing wall at any of the joints in the vent pipe.
Page 19
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
19
8.
Install the Vent Restrictor (if necessary)
1. Use the vent run descriptions in Figure 12 to determine if a vent restrictor is necessary.
2. If necessary, assemble the vent restrictor and wing as detailed in Figure 12 and Figure 15.
3. If necessary, install the appropriate vent restrictor (Figure 13 and Figure 14).
NOTE: If installing the vent restrictor in a rear vent application, ensure the factory-installed intake air baffle is in place (Figure 14). NOTE: The vent restrictor is shipped in the firebox.
Figure 12: When to use a vent restrictor Figure 13: Vent restrictor installation, Top vent
None
1
3
20
40
6
20
40
25 ft Maximum
horizontal run
60 ft Maximum vertical run
60
1.9
25
Horizontal Distance (ft)
Vertical Height (ft)
Vertical Height (ft)
2
5
Elbow
5 10
15
Base + wingBase
6 ft Minimum vertical run
6 ft Minimum vertical run
*
*
U-Shaped Vent
Restrictor
Inner
Fireplace
Collar
Appliance Top Vent Outlet
Figure 14: Vent restrictor installation, Rear vent
U-SHAPED VENT RESTRICTOR
APPLIANCE REAR
VENT OUTLET
INNER FIREPLACE
COLLAR
Inner Fireplace Collar Appliance Rear
Vent Outlet
U-Shaped Vent Restrictor
Intake Air Baffle
Figure 15: Vent restrictor assembly
Base Vent Restrictor
Base Vent Restrictor + Wing
* For straight runs or runs with elbows as illustrated in Vertical Vent Figures/Tables starting on Page 25.
Vent Restrictor with Vertical Terminations
When vertically terminating the vent system through the roof and using the vent restrictor, install the vent restrictor in the top vent of the fireplace outlet.
If installing more than 6 ft of vertical venting, install the restrictor (Figure 13), from inside or outside the unit, in the inner fireplace collar. The vent restrictor is held in place by friction.
Page 20
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
20
Vent Restrictor with Horizontal Terminations
When horizontally terminating a vent system with a vertical vent run up to 4 ft through an exterior wall, no vent restrictor is required.
If installing more than 4 ft of vertical venting, install the restrictor (Figure 14), from inside or outside the unit, in the inner fireplace collar. The vent restrictor is held in place by friction.
Tabl e 14: Effective Vent Length
Model Effective Length
SV4.5L6 4 1/2” SV4.5L12 10 1/2” SV4.5L24 22 1/2” SV4.5L36 34 1/2” SV4.5L48 46 1/2”
Connecting the vent pipe
Secure Vent® SV4.5 direct-vent system components are unitized concentric pipe components featuring positive twist lock connections (Figure 16 and Figure 17). All of the fireplaces covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the fireplace/vent collar to create the positive twist lock connection.
1. Align the dimpled end over the collar, adjusting the radial alignment until the four (4) locking dimples are aligned
with the inlet of the four (4) inclined channels on the collar (Figure 16).
2. Push the vent component against the collar until it fully engages, then twist the component clockwise, running
the dimples down and along the incline channels until they seat at the end of the channels.
NOTE: The unitized design of the Secure Vent® components will engage and seal both the inner and outer vent pipe.
3. If desired, a #6 x 1/2” screw can be used at the joint, but is not required as the pipe will securely lock
when twisted (Figure 17).
Where required, a telescopic vent section (SV4.5LA) may be used to provide the installer with an option to install in tight and confined spaces, or where the vent run made up of fixed length pieces develops a joint in a undesirable location, or will not build up to the required length. The SV4.5LA Telescopic Vent Section has an effective length of from 1 1/2–7” (38–191 mm). The SV4.5LA is fitted with a locking inclined channel end (identical to a normal vent section component) and a plain end with three (3) pilot holes. Slip the plain end over the locking channel end of a standard SV4.5 vent component the required distance and secure with three (3) screws.
Figure 16: Connecting vent
components
Figure 17: Connected vent
components
Figure 18: Elbow Dimensions
Dimple
Locking Incline Channel
Arrow
Appliance Collar or Vent Section
Dimple
Locking
Incline
Channel
Arrow
SV4.5E90
(90
°
Elbow)
8 1/8 in.
(206 mm)
Swivel Joint
(360
°
swivel)
4 13/16 in.
(122 mm)
SV4.5E45
(45
°
Elbow)
Swivel Joint
(360
°
swivel)
4 13/16” (122 mm)
8 1/8” (206 mm)
Swivel Joint
(360°)
Swivel Joint
(360°)
SV4.5E45
(45° elbow)
SV4.5E90
(90° elbow)
Vent elbows
Vent elbows are available in 90° and 45° configurations. Refer to Figure 18 for the SV4.5E45 and SV4.5E90 elbow dimensions. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element.
1. Rotate the elbow in a clockwise direction (to avoid the possiblity of unlocking any of the previously connected vent sections) for proper alignment (Figure 18). See Connecting the vent pipe for more information.
Page 21
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
21
Vent section length table
Table 15 will assist calculating how many vent sections are needed for the planned vent configuration. When a vent section is engaged with another section, its effective length will be 1 1/2” shorter.
Tabl e 15: Vent Section Length
Nominal Section
Length (in.)
6 12 24 36 48
Total Qty
Nominal Section Length
(in.)
6 12 24 36 48
Total Qty
Net Section Length
(in.)
4.5 10.5 22.5 34.5 46.5 Net Section Length (in.) 4.5 10.5 22.5 34.5 46.5
Height of Vent
Number of Vent Sections
Height of Vent
Number of Vent Sections
in. ft in. ft
4.5 0.375 1 0 0 0 0 1 252 21 0 1 0 7 0 8
9 0.75 2 0 0 0 0 2 276 23 0 0 0 8 0 8
10.5 0.875 0 1 0 0 0 1 279 23.25 0 0 0 0 6 6
15 1.25 1 1 0 0 0 2 280.5 23.375 1 0 0 8 0 9
22.5 1.875 0 0 1 0 0 1 289.5 24.125 0 1 0 0 6 7
31.5 2.625 0 3 0 0 0 3 301.5 25.125 0 0 1 0 6 7
34.5 2.875 0 0 0 1 0 1 310.5 25.875 0 0 0 9 0 9
37.5 3.125 1 1 1 0 0 3 325.5 27.125 0 0 0 0 7 7
43.5 3.625 0 2 1 0 0 3 330 27.5 1 0 0 0 7 8
45 3.75 0 0 2 0 0 2 345 28.75 0 0 0 10 0 10
46.5 3.875 0 0 0 0 1 1 349.5 29.125 1 0 0 10 0 11
51 4.25 1 0 0 0 1 2 372 31 0 0 0 0 8 8
55.5 4.625 0 1 2 0 0 3 379.5 31.625 0 0 0 11 0 11
57 4.75 0 0 1 1 0 2 418.5 34.875 0 0 0 0 9 9
67.5 5.625 0 0 3 0 0 3 465 38.75 0 0 0 0 10 10
69 5.75 0 0 0 2 0 2 475.5 39.625 0 1 0 0 10 11
73.5 6.125 1 0 0 2 0 3 480 40 1 1 0 0 10 12
79.5 6.625 0 1 0 2 0 3 492 41 1 0 1 0 10 12
81 6.75 0 0 0 1 1 2 499.5 41.625 0 0 0 1 10 11
91.5 7.625 0 0 2 0 1 3 504 42 1 0 0 1 10 12
93 7.75 0 0 0 0 2 2 511.5 42.625 0 0 0 0 11 11
97.5 8.125 1 0 0 0 2 3 520.5 43.375 0 2 0 1 11 14
103.5 8.625 0 0 0 3 0 3 531
44.25 0 2 2 0 11 15
108 9 1 0 0 3 0 4 538.5 44.875 1 0 0 2 11 14
117 9.75 1 0 5 0 0 6 549 45.75 1 0 2 1 11 15
118.5 9.875 1 1 0 3 0 5 558 46.5 0 0 0 0 12 12
126 10.5 0 0 1 3 0 4 562.5 46.875 1 0 0 0 12 13
130.5 10.875 1 0 1 3 0 5 568.5 47.375 0 1 0 0 12 13
135 11.25 0 0 6 0 0 6 573 47.75 1 1 0 0 12 14
139.5 11.625 0 0 0 0 3 3 580.5 48.375 0 0 1 0 12 13
142.5 11.875 1 0 0 4 0 5 589.5 49.125 0 1 2 2 10 15
144 12 1 0 0 0 3 4 595.5 49.625 1 1 1 0 12 15
154.5 12.875 1 1 0 0 3 5 604.5 50.375 0 0 0 0 13 13
160.5 13.375 0 2 0 0 3 5 615 51.25 0 1 0 0 13 14
172.5 14.375 0 0 0 5 0 5 625.5 52.125 0 2 0 0 13 15
177 14.75 1 0 0 5 0 6 631.5 52.625 1 0 1 0 13 15
186 15.5 0 0 0 0 4 4 637.5 53.125 0 1 1 0 13 15
196.5 16.375 0 1 0 0 4 5 651 54.25 0 0 0 0 14 14
207 17.25 0 0 0 6 0 6 655.5 54.625 1 0 0 0 14 15
211.5 17.625 1 0 0 6 0 7 672 56 0 2 0 0 14 16
217.5 18.125 0 1 0 6 0 7 678 56.5 1 0 1 0 14 16
229.5 19.125 0 0 1 6 0 7 688.5 57.375 1 1 1 0 14 17
232.5 19.375 0 0 0 0 5 5 697.5 58.125 0 0 0 0 15 15
241.5 20.125 0 0 0 7 0 7 702 58.5 1 0 0 0 15 16
246 20.5 1 0 0 7 0 8 712.5 59.375 1 1 0 0 15 17
720 60 0 0 1 0 15 16
Page 22
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
22
Clearance to combustibles
Maintain the minimum clearance to combustibles (e.g., framing, attic, ceiling insulation, etc.). For all vertical runs:
s 1” (25 mm) from all sides NOTE: Attic insulation shield (96K94) must be installed when blown or loose-fill insulation is used, and is
recommended for all attic installations. For all horizontal/inclined runs:
s 3” (76 mm) from the top s 2” (51 mm) from the top when 6 ft or more above the fireplace s 1” (25 mm) from the sides s 1” (25 mm) from the bottom
9. Install the Vent System
Install the Vertical Termination Vent System
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 in Canada.
Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
Dégagement conforme aux codes d’installa tion locaux et aux exigences du foumisseunde gaz.
Vertical vent systems terminate through the roof. The minimum vent height above the roof and/or adjacent walls is specified in ANSI Z223.1 (In Canada, the current CAN/CGA-B149.1 installation code) by major building codes. Always consult your local codes for specific requirements. A general guide to follow is the gas vent rule (Table 6).
The following figures and their associated vertical vent tables illustrate the various configurations that are possible for use with these fireplaces. Secure Vent® pipe is shown in these figures; Secure Flex® pipe may also be used. A table summarizes each configuration’s minimum and maximum vertical and horizontal length parameters for a variety of applications.
1. Refer to Figure 25 and Table 17–Table 20 on Page 2526 to select the type of vertical installation desired. Elbows are available in 90° and 45° configurations. Refer to Figure 18 on Page 20 for the SV4.5E45 and SV4.5E90 elbow dimensional specifications.
Vertical (Straight) Installation
1. Determine the number of straight vent sections required. See Effective Vent Length on Page 20 for more information. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists.
Figure 19: Vertical (Straight) Installation
SV4.5FA or SV4.5FB Flashing AND SV4.5SC Storm Collar
SV4.5VF Firestop/Spacer*
1” (25.4 mm) Minimum Clearance to Combustibles
SV4.5CGV-1
Termination
SV4.5L6/12/24/36/48 Vent Sections
*When using Secure Flex, use Firestop/Spacer
SF4.5VF.
Max. 60 ft (18.3 m)
Page 23
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
23
Vertical (Offset) Installation
1. Analyze the vent route and determine the number of vent sections and elbows required—See Effective Vent Length on Page 20 for more information. Plan the venting so that a joint does not occur in the ceiling or roof joists. Allow for elbows (Figure 18). Maintain the minimum clearances for combustibles (Page 22).
2. Frame the ceiling opening—Use a plumb line from the ceiling above the fireplace to locate the center of the
vertical run. Cut and/or frame an opening, 10 1/2 x 10 1/2” (267 x 267 mm) inside dimensions, about this center mark (Figure 20).
Figure 20: Framing the ceiling opening Figure 21: Rear vent gasket
minimum 10 1/2 in. (267 mm)
minimum 10 1/2 in. (267 mm)
Roof Framing
Ceiling Framing
Plumb Bob
10 1/2” (267 mm) minimum
10 1/2” (267 mm)
minimum
Gasket
3. Install the rear vent gasket—The rear vent gasket is factory installed and required for all rear vent applications. If the gasket is missing, position a replacement gasket (contact your local dealer) around the vent collar before attaching other vent components to the fireplace (Figure 21). Loosely attach the gasket with two screws at the top and bottom.
4. Attach the vent components to the fireplace—See Connecting the vent pipe on Page 20.
5. Attach the vent components to each other—See Connecting the vent pipe on Page 20.
6. Install firestop/spacer at ceiling—When using Secure Vent®, use SV4.5VF firestop/spacer at ceiling joists; when
using Secure Flex®, use SF4.5VF firestop/spacer. If there is living space above the ceiling level, the firestop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1” (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections. The gap between the vent pipe and a vertical firestop can be sealed with non-combustible caulking.
NOTE: Attic insulation shield (96K94) must be installed when blown or loose-fill insulation is used, and is recommended for all attic installations.
7. Support the vertical vent run sections—Support the vertical portion of the venting system every 8 ft (2.4 m) above the fireplace vent outlet. One method of support is by utilizing field provided support straps (conventional plumber’s tape). Secure the plumber’s tape to the framing members with nails or screws. Loop the tape around the vent, securing the ends of the tape to the framing. If desired, sheet metal screws #6 x 1/2” length may be used to secure the support straps to the vent pipe (Figure 22).
NOTE: Proper venting support is very important.
Figure 22: Supporting the Vertical Vent Run
Blocking
Support straps (plumber’s tape)
8 ft (2.4 m)
maximum
1/2” (12.7 mm) minimum clearance to combustibles
Page 24
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
24
8. Change vent direction of horizontal/inclined run—Install the SV4.5E45 and SV4.5E90 elbows in the same manner as the straight vent sections. See Vent elbows on Page 20 for more information.
9. Continue installation of horizontal/inclined sections—Continue with the installation of the straight vent
sections in horizontal/inclined run. Install support straps every 5 ft (1.52 m) along horizontal/inclined vent runs using conventional plumber’s tape.
Rise per foot run ratios are acceptable all the way to level. For best results, maintain the horizontal/inclined run in a straight (no dips), slightly elevated plane of approximately 1/4” per 1 ft (20 mm per 1 m).
Maintain the required clearances to combustibles (Page 22).
10. Frame the roof opening—Identify the location for the vent at the roof. Cut and/or frame opening (Table 16).
Tabl e 16: Roof Framing Dimensions
C
D
Pitch C D
0/12 10 1/2” (267 mm) 10 1/2” (267 mm) 6/12 10 1/2” (267 mm) 12” (305 mm)
12/12 10 1/2” (267 mm) 17 3/4” (451 mm)
11. Install the roof flashing—Extend the vent sections through the roof structure. Install the roof flashing over the vent section and position such that the vent column rises vertically (use carpenters level). Nail along perimeter to secure flashing or adjust roofing to overlap the flashing edges at top and sides only and trim where necessary. Seal the top and both sides of the flashing with waterproof caulking.
12. Install the storm collar—Install the storm collar, supplied with the flashing, over the vent/flashing joint (Figure 23). Loosen the storm collar screw. Slide collar down until it meets the top of the flashing. Tighten the adjusting screw. Apply non-combustible caulking or mastic around the circumference of the joint to provide a water tight seal.
Figure 23: Installing the Storm Collar Figure 24: Installing the Vertical Termination
Storm Collar
13. Install the vertical termination—The final step involves installation of the SV4.5CGV-1 vertical termination. Extend the vent sections to the correct height (Figure 4). The SV4.5CGV-1 Vertical Termination (Figure 24) installs in the exact same fashion as any other Secure Vent® section. Align the termination over the end of the previously installed section, adjusting the radial alignment until the four (4) locking dimples of the termination are aligned with the inlets of the four (4) incline channels of the last vent section. Push the termination down until it fully engages, then twist the termination clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
If the vent system extends more than 5 ft (1.5 m) above the roof flashing, stabilizers may be necessary. Additional screws may be used at section joints for added stability. Guide wires or roof support assemblies may be attached to the joint for additional support on multiple joint configurations.
Page 25
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
25
Vertical Vent Figures/Tables
NOTE: Secure Vent® rigid vent pipe is shown in the figures; Secure Flex® flexible vent pipe may also be used. NOTE: Rise per foot run ratios are acceptable all the way to level. For best results, maintain the horizontal/inclined
run in a straight (no dips), slightly elevated plane of approximately 1/4” per 1 ft (20 mm per 1 m). NOTE: SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be used anytime vent pipe passes
through a combustible floor or ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex)firestop/spacer must be used anytime vent pipe passes through a combustible wall.
NOTE: Two (2) 45° elbows may be used in place of one (1) 90° elbow. The same rise to run ratios, as shown in the venting figures for 90° elbows, must be followed if 45° elbows are used.
NOTE: An elbow is acceptable as 1 ft of vertical rise, except where an elbow is the only vertical component in the system.
WARNING
Do NOT join separate sections of concentric flexible vent pipe.
Figure 25: Top Vent—Straight Ta ble 17: Rear Vent—One 90° Elbow
Ceiling
firestop/
spacer
SV4.5VF *
When using Secure Flex®, use ceiling firestop/spacer SF4.5VF.
*
60 ft (18.3 m)
maximum
Ceiling firestop/ spacer SV4.5VF *
When using Secure Flex®, use ceiling firestop/spacer SF4.5VF.
*
H
V
H Maximum V Minimum
feet meters feet meters
2 0.610 1 0.305
4 1.219 2 0.610
6 1.829 3 0.914
8 2.438 4 1.219
Install the U-shaped vent restrictor in any vent run with more than 6 ft of vertical rise. See Page 19 for more information.
Minimum 6 ft and maximum of 60 ft of vertical venting.
V + H = 60 ft (18.3 m) maximum H = 8 ft (2.4 m) maximum Install the U-shaped vent restrictor in any vent run with more than
6 ft of vertical rise. See Page 19 for more information.
If 8 ft of (H) horizontal vent run is needed, then 4 ft (straight section) minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 2 (H) ratio. For every 1 ft of (V) vertical, you are allowed 2 ft of (H) horizontal run, up to a maximum horizontal run of 8 ft.
Minimum 6 ft of vertical venting.
Page 26
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
26
Tabl e 18: Top V en t— Two 90° El bo ws Tab le 19: Rear Vent—Three Elbows Tabl e 20: Top V en t— Th ree E lb ow s
Ceiling firestop/ spacer SV4.5VF *
Wall firestop/ spacer SV4.5HF **
When using Secure Flex®, use ceiling firestop/spacer SF4.5VF. When using Secure Flex, use wall firestop/spacer SF4.5HF.
*
**
V1
H
V
V
V
Ceiling firestop/spacer SV4.5VF *
Wall firestop/ spacer SV4.5HF **
When using Secure Flex®, use ceiling firestop/ spacer SF4.5VF. When using Secure Flex, use wall firestop/ spacer SF4.5HF.
*
**
V1
H
Ceiling firestop/spacer SV4.5VF *
H1
Ceiling firestop/spacer SV4.5VF *
Wall firestop/ spacer SV4.5HF **
When using Secure Flex®, use ceiling firestop/spacer SF4.5VF. When using Secure Flex, use wall firestop/spacer SF4.5HF.
*
**
V1
H
V
H1
H Maximum V Minimum
H + H
1
Maximum
H Maximum V Minimum H + H1 Maximum V Minimum
feet meters feet meters ft m ft m ft m feet meters feet meters
5 1.524 Elbow Only 5 1.524 2 0.610 1 0.305 5 1.524 Elbow Only 5 1.524 1 0.305 10 3.048 4 1.219 2 0.610 5 1.524 1 0.305
10 3.048 2 0.610 15 4.572 6 1.829 3 0.914 10 3.048 2 0.610
15 4.572 3 0.914 20 6.096 8 2.438 4 1.219 15 4.572 3 0.914
25 7.62 5 1.524 H = 8 ft (2.4 m) maximum
H + H1 = 20 ft (6.1 m) maximum V + V1 + H + H1 = 60 ft (18.3 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 6 ft of vertical rise. See Page 19 for more information.
If 20 ft of (H) horizontal vent run is needed, then 4 ft (straight section) minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V) vertical, you are allowed 5 ft of (H) horizontal run, up to a maximum horizontal run of 20 ft.
NOTE: The vent system may have a maximum of three (3) 90° elbows.
Minimum 6 ft of vertical venting.
20 6.096 4 1.219
V + V
1
+ H = 60 ft (18.3 m) maximum H = 25 ft (7.62 m) maximum Install the U-shaped vent restrictor in any vent run
with more than 6 ft of vertical rise. See Page 19 for more information.
If 25 ft of (H) horizontal vent run is needed, then 5 ft (straight section) minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V) vertical, you are allowed 5 ft of (H) horizontal run, up to a maximum horizontal run of 25 ft.
Minimum 6 ft and maximum of 60 ft of vertical venting.
H + H1 = 20 ft (6.1 m) maximum V + V1 + H + H1 = 60 ft (18.3 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 6 ft of vertical rise. See Page 19 for more information.
If 20 ft of (H) horizontal vent run is needed, then 4 ft (straight section) minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V) vertical, you are allowed 5 ft of (H) horizontal run, up to a maximum horizontal run of 20 ft.
NOTE: The vent system may have a maximum of three (3) 90° elbows.
Minimum 6 ft and maximum of 60 ft of vertical venting.
Page 27
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
27
Install the Horizontal Termination Vent System
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 in Canada.
Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
Dégagement conforme aux codes d’installa tion locaux et aux exigences du foumisseunde gaz.
Horizontal vent systems terminate through an outside wall. Building Codes limit or prohibit terminating in specific areas (Table 7).
The following figures and their associated horizontal vent tables illustrate the various configurations that are possible for use with these fireplaces. Secure Vent
®
pipe is shown in these figures; Secure Flex® pipe may also be used.
A table summarizes each configuration’s minimum and maximum vertical and horizontal length parameters for a variety of applications. For more information on connecting the vent pipe, see Page 20.
Figure 26: Typical Horizontal Vent Installation
V
ertical
Rise
SV4.5E90
Elbow
Horizontal / Inclined Run
Termination
Firestop/Spacer
SV4.5L6/12/24/36/48
Vent Sections
Support bracket spacing every 5 ft (1.52 m)
Vertical Vent
Support
Brackets
Building
Support
Framing
Ceiling
Fireplace
Exterior Wall
Exterior Wall
Termination
1. Analyze the vent route and determine the number of vent sections and elbows required—See Effective Vent Length on Page 20 for more information. Plan the venting so that a joint does not occur in the ceiling or roof joists. Allow for elbows (Figure 18). Maintain the minimum clearances for combustibles (Page 22).
2. Frame the exterior wall opening—Locate the center of the vent outlet on the exterior wall (Table 11). Cut and/
or frame an opening, 10 1/2 x 12 1/8” (267 x 308 mm) inside dimensions, about this center.
3. Frame the ceiling opening—If the vertical route is to penetrate a ceiling, use plumb line to locate the center above the fireplace. Cut and/or frame an opening, 10 1/2 x 10 1/2” (267 x 267 mm) inside dimensions, about this center (Figure 20).
4. Install the rear vent gasket—The rear vent gasket is factory installed and required for all rear vent applications. If the gasket is missing, position a replacement gasket (contact your local dealer) around the vent collar before attaching other vent components to the fireplace (Figure 21). Loosely attach the gasket with two screws at the top and bottom.
5. Attach the vent components to the fireplace—See Connecting the vent pipe on Page 20.
6. Attach the vent components to each other—See Connecting the vent pipe on Page 20.
7. Install the firestop/spacer at the ceiling—When using Secure Vent®, use SV4.5VF firestop/spacer at ceiling
joists; when using Secure Flex®, use SF4.5VF firestop/spacer. If there is living space above the ceiling level, the firestop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Maintain 1” (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections.
8. Support the vertical run sections—On the vertical run, support the venting system every 8 ft (2.4 m) above the fireplace vent outlet with field provided support straps (Plumber’s tape). Attach the straps to the vent pipe and secure to the framing members with nails or screws (Figure 26).
Page 28
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
28
9. Change vent direction—At transition from or to a horizontal/inclined run, install SV4.5E45 or SV4.5E90 elbows
in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element. Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking any of the previously connected vent sections (Figure 18).
10. Continue installation of horizontal/inclined sections—Continue with the installation of the straight vent sections in horizontal/inclined run. Install support straps every 5 ft. (1.52 m) along horizontal/inclined vent runs using conventional plumber’s tape (Figure 26). Maintain the horizontal/inclined run in a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4” per 1 ft (20 mm per 1 m) horizontal, in a direction away from the fireplace. Smaller rise per foot run ratios are acceptable all the way to at or near level. Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary.
Maintain the required clearances to combustibles (Page 22).
11. Assemble the vent run to the exterior wall—If not previously measured, locate the center of the vent at the exterior wall. Prepare the opening. Assemble the vent system until the terminus of the last section is within 7” (178 mm) to 11 1/4” (286 mm) inboard of the exterior surface to which the SV4.5 HT termination is to be attached (Figure 27). If the terminus of the last section is not within this distance, use the telescopic vent section SV4.5LA, as the last vent section. Table 21 lists the additional venting components needed (in addition to the termination and adaptor) for a range of wall thicknesses.
12. Attach the termination adaptor—Attach the adaptor (SV4.5RCH, provided with the termination) to the vent section or telescoping vent section, elbow or fireplace collar (Figure 27).
13. Install the firestop/spacer at the exterior wall—When using the square termination, install SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) Firestop/Spacer over the opening at the exterior side of the framing, long side up, with the 3” spacer clearance at the top (Figure 27) and nail into place.
NOTE: The firestop/spacer may also be installed over the opening at the interior side of the framing.
14. Install the termination (SV4.5HT-2, SV4.5HTSS, or SV4.5HTKCT)—From outside the exterior wall, slide
the collars of the termination onto the adaptor (the outer over the outer and the inner inside the inner) until the termination seats against the exterior wall surface to which it will be attached. Orient the housing of the termination with the arrow pointed upwards. Secure the termination to the exterior wall. The horizontal termination must not be recessed into the exterior wall or siding by more than the 1 1/4” (32 mm) (Figure 28).
NOTE: Termination SV45HTKCT (and other compact terminations) should not be used with a straight, horizontally vented rear termination in the 45” units. A minimum 12” rise is required when venting the 45” units.
NOTE: If the venting exits the building below grade, or close to grade, see Installation Accessories on Page 42 for available snorkel terminations. The termination must be above grade and above the expected level of snow accumulation.
NOTE: The vent termination is hot while in operation and for a period of time following the use of the fireplace.
To prevent contact with hot surfaces, use a horizontal termination guard; available for purchase at your local dealer.
The horizontal terminations have been designed to perform in a wide range of weather conditions. Our terminations meet or exceed industry standards.
When selecting the locations of your horizontal terminations, do not place the termination where water from eaves and adjoining rooflines may create a heavy flow of cascading water onto the termination cap. If the cap must be placed where the possibility of cascading water exists, it is the responsibility of the builder to direct the water away from the termination cap by using gutters or other means.
Take care to carefully follow the installation instructions for the termination, including the use of silicone caulking where required.
Page 29
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
29
Figure 27: Installing the Horizontal Termination
Termination
10 1/2”
(267mm)
7”
(178)
5 1/8”
(130 mm)
12 1/8”
(308 mm)
Note: Centerline of Vent Piping is
NOT the Same as the Centerline of
the Framed Opening.
6 to 48” Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Min. Distance to Base
of Appliance.
Base of Appliance
3”
(76 mm)
1”
(25.4 mm)
Adapter
SV4.5RCH
To help minimize water
infiltration it is recommended that
the Firestop/Spacer (SV4.5HF)
be installed on the exterior
side of the wall.
See Table 11 for the minimum distance
to the base of the fireplace.
NOTE: To help minimize water infiltration install the firestop/spacer (SV4.5HF) on the exterior side of the wall.
Figure 28: Venting Connection and Exterior Wall Recessing of the Horizontal Compact Termination
(SV4.5HTKCT)
Siding
Stucco
1-1/4” Maximum Recess of the Square Termination into Exterior Finishing Material
Exterior Surface of
Framing
6 in. to 9 1/4”
(152 to 235 mm)**
Exterior Surface of Siding
Interior Surface of
Finished Wall
Maximum wall thickness
9 1/4” (235 mm)**
Maximum Extent of Vent Run Sections Relative to Exterior Surface of Framing
Last Vent Section. Use Telescopic Vent Section (SV4.5LA), If Necessary
Adapter
SV4.5RCH
*Use silicone caulking to seal the top and sides of the termination, up to the underlayment, stucco, or masonry wall surface.
*Caulk
*Caulk
** For thicknesses greater
than 10” (254 mm) see
Table 21.
Page 30
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
30
Tabl e 21: Venting Components Required for Various Exterior Wall Thicknesses, when using Typical Termination Kits
Vent Components Required Exterior Wall Thickness
Termination Kit Only 6–9 1/4” (152–235 mm)
Termination Kit and 6” Vent Section (SV4.5L6) 10 3/4–14” (273–356 mm)
Termination Kit and 12” Vent Section (SV4.5L12) 16 3/4–20” (426–508 mm)
Termination Kit and Telescopic Section (SV4.5L12) 11 3/4–20” (299–508 mm)
NOTE: See Figure 28 for wall thickness ranges when using SV4.5HTKCT termination kit.
Horizontal Vent Figures/Tables
NOTE: Secure Vent® rigid vent pipe and terminal are shown in the figures. Secure Flex® flexible vent pipe and terminal may also be used.
NOTE: Two (2) 45° elbows may be used in place of one (1) 90° elbow. The same rise to run ratios, as shown in the venting figures for 90° elbows, must be followed if 45° elbows are used.
NOTE: Maintain the horizontal/inclined run in a straight (no dips), slightly elevated plane. The recommended incline is approximately 1/4” per 1 ft (20 mm per 1 m) horizontal, in a direction away from the fireplace. Smaller rise per foot run ratios are acceptable all the way to at or near level. Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary.
NOTE: SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be used any time vent pipe passes through a combustible floor or ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must be used any time vent pipe passes through a combustible wall.
WARNING
Do not join separate sections of concentric flexible vent together.
Tabl e 22: Rear Vent—No Elbows
Compact termination (SV4.5HTKCT) shown. See Tab le 21 as an aid in venting component selection for a
particular range of exterior wall thicknesses.
Note: “H” is horizontal distance from rear of unit to outer wall surface
Note: On 45” models only, 1” vertical rise is required when using compact hoizontal termination with a rear vent.
When using Secure Flex®, use wall firestop/spacer SF4.5HF, and install venting with a minimum of 12” rise. (Page 33).
H = 21” (533 mm) maximum
27 1/2”
(699 mm)
Tabl e 23: Top V en t— On e 90° E lb ow, El bo w Co nn ectio n at F ir ep la ce
H Maximum V Minimum
Wall firestop/ spacer SV4.5HF *
When using Secure Flex®, use wall firestop/spacer SF4.5HF.
*
H
V
feet meters feet meters
3 0.91 Elbow only
Install the U-shaped vent restrictor in any vent run with more than 4 ft of vertical rise. See Page 19 for more information.
Compact termination (SV4.5HTKCT) shown. See Tab le 21 as an aid in venting component selection for a
particular range of exterior wall thicknesses.
NOTE: Only in top vent where elbow is connected at fireplace collar is it allowed to count elbow as 1 ft. vertical (V) rise.
H
Page 31
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
31
Tabl e 24: Top V en t— On e 90° E lb ow, El bo w Co nn ectio n NO T at F ir eplac e
H Maximum V Minimum
When using Secure Flex®, use ceiling firestop/spacer SF4.5VF. When using Secure Flex, use wall firestop/spacer SF4.5HF.
*
**
Wall firestop/
spacer SV4.5HF **
Ceiling
firestop/
spacer
SV4.5VF *
H
V
feet meters feet meters
5 1.524 1 0.305
10 3.048 2 0.610
15 4.572 3 0.914
25 7.62 5 1.524
Install the U-shaped vent restrictor in any vent run with more than 4 ft of vertical rise. See Page 19 for more information.
Compact termination (SV4.5HTKCT) shown. See Tab l e 21 as an aid in venting component selection for a particular range of exterior wall thicknesses. If 25 ft of (H) horizontal vent run is needed, then 5 ft minimum of (V) vertical vent will be required. This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V) vertical, you are allowed 5 ft of (H)
horizontal run, up to a maximum horizontal run of 25 ft (7.62 m).
Tabl e 25: Rear Vent—Two 90° Elbows
H + H1 Maximum H Maximum V Minimum
When using Secure Flex®, use ceiling firestop/spacer SF4.5VF. When using Secure Flex, use wall firestop/spacer SF4.5HF.
*
**
Wall firestop/
spacer
SV4.5HF **
Ceiling firestop/ spacer SV4.5VF *
H
V
H1
feet meters feet meters feet meters
5 1.524 2 0.610 1 0.305
10 3.048 4 1.219 2 0.610
15 4.572 6 1.829 3 0.914
25 7.62 10 3.048 5 1.524
V + H + H
1
= 60 ft (18.288 m) maximum H = 8 ft (2.438 m) maximum H + H1 = 25 ft (7.62 m) maximum Install the U-shaped vent restrictor in any vent run with more than 4 ft of vertical rise. See
Page 19 for more information.
Compact termination (SV4.5HTKCT) shown. See Tab l e 21 as an aid in venting component selection for a particular range of exterior wall thicknesses. If 25 ft of (H) horizontal vent run is needed, then 5 ft minimum of (V) vertical vent will be required. This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V) vertical, you are allowed 5 ft of (H)
horizontal run, up to a maximum horizontal run of 25 ft (7.62 m).
Tabl e 26: Top V en t— Two 90° El bo ws
H + H1 Maximum V Minimum
When using Secure Flex®, use ceiling firestop/spacer SF4.5VF. When using Secure Flex, use wall firestop/spacer SF4.5HF.
*
**
Wall firestop/
spacer
SV4.5HF **
Ceiling
firestop/spacer
SV4.5VF *
H
V
H1
Wall firestop/spacer SV4.5HF **
feet meters feet meters
3 0.91 Elbow only
5 1.524 1 0.305
10 3.048 2 0.610
15 4.572 3 0.914
25 7.62 5 1.524
V + H + H
1
= 60 ft (18.288 m) maximum H + H
1
= 25 ft (7.62 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 4 ft of vertical rise. See Page 19 for more information.
Compact termination (SV4.5HTKCT) shown. See Tab l e 21 as an aid in venting component selection for a particular range of exterior wall
thicknesses. If 25 ft of (H) horizontal vent run is needed, then 5 ft minimum of (V) vertical vent will
be required. This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V) vertical, you are allowed 5 ft of (H)
horizontal run, up to a maximum horizontal run of 25 ft (7.62 m).
Page 32
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
32
Tabl e 27: Rear Vent—Three 90° Elbows
H + H1 + H2 Maximum H Maximum V Minimum
V
When using Secure Flex®, use ceiling firestop/spacer SF4.5VF. When using Secure Flex, use wall firestop/ spacer SF4.5HF.
*
**
Wall firestop/spacer SV4.5HF **
Ceiling
firestop/spacer
SV4.5VF *
H
V
H1
H2
feet meters feet meters feet meters
5 1.524 2 0.610 1 0.305
10 3.048 4 1.219 2 0.610
15 4.572 6 1.829 3 0.914
20 6.096 8 2.438 4 1.219
V + H + H
1
+ H2 = 60 ft (18.288 m) maximum H = 8 ft (2.438 m) maximum H + H1 + H2 = 25 ft (7.62 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 4 ft of vertical rise. See Page 19 for more information.
Compact termination (SV4.5HTKCT) shown. See Tab le 21 as an aid in venting component selection for a particular range of
exterior wall thicknesses. If 20 ft of (H) horizontal vent run is needed, then 4 ft minimum of (V) vertical vent will
be required. This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V) vertical, you are allowed 5
ft of (H) horizontal run, up to a maximum horizontal run of 20 ft (6.096 m).
Tabl e 28: Top V en t— Th ree 9 0° E lb ow s
H Maximum V Minimum
Wall firestop/spacer
SV4.5HF **
When using Secure Flex®, use ceiling firestop/spacer SF4.5VF. When using Secure Flex, use wall firestop/spacer SF4.5HF.
*
**
Wall firestop/
spacer
SV4.5HF **
Ceiling firestop/spacer SV4.5VF *
H
V
H1
V1
feet meters feet meters
5 1.524 Elbow only
5 1.524 1 0.305
10 3.048 2 0.610
15 4.572 3 0.914
20 6.096 4 1.219
H + H
1
= 25 ft (7.62 m) maximum
V + V1 + H + H1 = 60 ft (18.288 m) maximum
Install the U-shaped vent restrictor in any vent run with more than 4 ft of vertical rise. See Page 19 for more information.
Compact termination (SV4.5HTKCT) shown. See Tab le 21 as an aid in venting component selection for a particular range of
exterior wall thicknesses. If 20 ft of (H) horizontal vent run is needed, then 4 ft minimum of (V) vertical vent
will be required. This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V) vertical, you are allowed
5 ft of (H) horizontal run, up to a maximum horizontal run of 20 ft (6.096 m). An elbow is acceptable as 1 ft of vertical rise, but may not be connected directly to
the fireplace collar.
Page 33
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
33
Vertical or Horizontal Venting Using Secure Flex Kits and Components
When Secure Flex® kits are used in a rear flue, horizontal termination installation, at least 1 ft of vertical rise is required.
Secure Flex venting kits and components may be used in any other vent installation where rigid Secure Vent® (SV4.5) direct-vent components can be used. All restrictions, clearances and allowances pertaining to rigid vent also apply to flexible vent. Do NOT modify Secure Flex kits . Also, do NOT join separate sections of flex vent together. Secure Flex kits can be installed on the end of a Secure Vent (SV4.5) rigid vent run, provided that doing so does not violate any of the venting length, height, routing, horizontal to vertical ratio requirements, or clearance considerations detailed in this manual.
Secure Flex kits come with an included adaptor that can be installed on the fireplace collar or the inclined channel end of the last Secure Vent (SV4.5) vent section in a rigid system in the exact same fashion as any other Secure Vent section. Align the dimpled end of the adaptor over the previously installed section or fireplace collar, adjusting the radial alignment until the four locking dimples of the adaptor are aligned with the inlets of the four incline channels of the last vent section or collar. Push on the adaptor until it is fully engaged, then twist the adaptor clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
Figure 29: Flexible Vent Adaptor Figure 30: Flexible Vent
Apply ONLY MIL-PAC BLACK
HIGH TEMPERATURE
SEALANT (P/N 10K81) to
the outside surface of both collars of the adaptor (fill the grooves of the outer collar to
be covered by the flexible pipe)
and slide the flexible vent over
the inner and outer adaptor
collars
NOTE: Outer vent pipe is pulled away to show inner vent pipe details.
1 3/4” (44 mm) flexible
vent and adaptor outer
collar overlap
Adaptor (SV4.5RF)
Attach adaptor to vent collar or Secure Vent sections
1 3/4” (44 mm) flexible vent and adaptor inner collar overlap
Securing screws in three (3) places just below the gear clamp
Gear clamps
Securing screws in three (3) places just below the gear clamp
Flexible vent Flexible vent section
5” (127 mm) radius minimum
1. Install the Inner Flex Pipe. a. Install the small gear clamp loosely around the inner flexible vent, then push it back out of the way.
b. Apply a bead of Mill-Pac Black (700 °F) high temperature sealant (P/N 10K81) to the inner adaptor collar,
approximately 1/2” from the end.
c. Pull and extend the inner flexible vent. d. Slide the inner flex vent over the adaptor collar at least 1 3/4”. NOTE: Ensure the flex vent is free from damage or tears. e. Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor inner collar
approximately 3/4” from the end of the flex.
f. Install three (3) screws 120° apart through the flexible vent and into the adaptor collar just below the gear
clamp to provide additional security to the connection.
2. Install the outer Flex Pipe. a. Install the large gear clamp loosely around the outer flexible vent pipe, then push it back out of the way.
b. Apply a bead of Mill-Pac Black (700 °F) high temperature sealant (P/N 10K81) to the outer adaptor collar.
Cover to the grooves of the collar that extend approximately 1” from the end and to the flat surface, approximately 1 3/8” from the end.
c. Pull and extend the outer flexible vent.
Page 34
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
34
d. Slide the outer flexible vent over the adaptor collar. Ensure the flexible vent completely engages the adaptor collar
1 3/4” from the end, and that it is free from damage or tears.
e. Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor outer collar
approximately 3/4” from the end of the flexible vent.
f. Install three (3) screws 120° apart through the flexible vent and into the adaptor collar just below the gear
clamp to provide additional security to the connection.
3. Route the flexible vent. NOTE: Ensure that the flexible vent is properly routed to provide the required clearance. Do NOT allow the flexible vent
to bend in a radius tighter than 5” (127 mm) (Figure 30). Place the internal flexible vent spacers evenly and avoid kinking the inner vent. Support horizontal sections of flexible vent with metal straps at 2 ft (0.61 m) intervals.
4. Install firestop/spacers at ceiling and wall penetrations.
s SF4.5 VF firestop/spacer for ceilings s SF4.5 HF firestop/spacer for walls
NOTE: See the appropriate sections and figures shown throughout the venting section for installation requirements.
5. Attach the flexible vent to the termination. NOTE: Secure Flex
®
components can be purchased separately and attached to bulk lengths of Secure Flex flexible vent cut to size at the job site. Attach the flexible vent to the Secure Flex terminations as it was attached to the adaptor (Figure 29).
NOTE: Attach Secure Flex vent to Secure Flex terminations only. Do NOT substitute Secure Vent
®
terminations or Secure Vent adaptor for Secure Flex components. Secure Flex termination and adaptor collars are a different circumference than Secure Vent collars. Secure Flex vent has an longer center tube to improve ease-of-installation.
10.
Complete the Field Wiring
CAUTION
The ground supply lead must be connected to the wire attached to the green ground screw located on the outlet box (see wiring diagrams). Failure to do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70—latest edition (in Canada, the current CSA C22-1 Canadian Electrical Code).
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
ATTENTION
Au moment de l’entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de cáblage peuvent entraîner un fonctionnement inadéquat et dangereux.
Verify proper operation after servicing.
S’assurer que l’appareil fonctionne adéquatement une fois l’entretien terminé.
The gas valve is set in place and pre-wired at the factory for both millivolt and electronic models.
Millivolt Wiring
Millivolt units are not provided with factory-installed controls; therefore, one of the optional control switches is required to operate the unit (Page 63):
s ON/OFF Wall Switch, s Unit-Mountable ON/OFF Switch, s Thermostat, or s Remote Control.
See the Operation section on Page 48 for more details.
Page 35
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
35
Figure 31: Wiring Diagram—Millivolt Gas Valves Figure 32: Wiring Diagram—Electronic Gas Valves
TP-TH
TP
TH
APPLIANCE- MOUNTED ON/OFF SWITCH (OPTIONAL)
BK/W(1)
BK/W(1)
WALL-MOUNTED ON/OFF SWITCH (OPTIONAL) THERMOSTAT (OPTIONAL)
JUNCTION BOX
BLACK
W
GR
120 V
AC
WALL MOUNTED CONFIGURATION FOR FAN SWITCH (OPTIONAL)
BK
R
THERMOPILE
GAS VALVE
FAN
(OPTIONAL)
P/N 580491-01
JUNCTION BOX
120V AC
REMOTE RECEIVER
ON/OFF SWITCH
WALL SWITCH
LIMIT SWITCH
B-VENT MODELS
ONLY
AC/DC POWER ADAPTOR
HOT
NEUTRAL
OPTIONAL
GROUND
BATTERY HOLDER
DFC WIRE HARNESS
SPARK WIRE CABLE
PILOT GROUND WIRE
PILOT SENSOR CABLE
HOOD
IGNITER ROD
FLAME SENSOR
PILOT TUBE
OPTIONAL CPI SWITCH OFF (O) = INTERMITTENT PILOT MODE ON (-) = STANDING PILOT MODE
PROFLAME DFC BOARD
PROFLAME VALVE
ELECTRONIC PILOT ASSEMBLY
B = BLACK BR = BROWN GY = GRAY PU = PURPLE R = RED
BL = BLUE G = GREEN O = ORANGE W = WHITE Y = YELLOW
WIRING COLOR CODE
B
B
B
R
R
W
W
B
B
B
B
BL
BL
G
G
O
Y
Y
R
R
Y
W
G
G
O
SCHEMATIC REPRESENTATION ONLY
1. If installing an ON/OFF wall switch or thermostat, mount it in a convenient location on a wall near the fireplace.
2. Wire the control switch within the millivolt control circuit using the 15 ft of 2-conductor wire supplied with
the unit (Figure 31).
NOTE: The supplied 15 ft of 2-conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose inside the bottom compartment.
CAUTION
In millivolt systems, do NOT connect a wall switch to a 120 V power supply.
Electronic Wiring
One of the following optional controls must be used:
s ON/OFF Wall Switch, s Thermostat, or s Remote Control.
See the Operation section on Page 48 for more details. NOTE: Electronic models must be connected to the main power supply.
1. Route a 3-wire, 120 Vac, 60 Hz, 1 ph power supply to the fireplace junction box.
2. Remove the electrical inlet cover plate from the side of the unit by removing the plate’s securing screws
(Table 8).
3. If unit is not supplied with a strain relief, remove the cover plate knockout. Then, feed the power supply wire
through the knockout opening and into the unit junction box.
4. Connect the black power supply wire to the lower outlet’s red pigtail lead (Figure 32 and Figure 33). Connect the
white power supply wire to the outlet’s common terminal.
5. Connect the ground supply wire to the pigtail lead attached to the outlet’s green ground screw. Restrain the inlet
power lead per NEC or local codes.
6. If a wall-mounted ON/OFF control or thermostat is to be used, mount it in a convenient location on a wall near the fireplace.
7. If an optional control is to be used, wire it in the low voltage circuit (Figure 32). NOTE: The supplied 15 ft of 2-conductor wire has one end of each conductor connected to the gas valve circuit
and the other end of each conductor placed loose inside the bottom compartment.
Page 36
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
36
8. After the wiring is complete, replace the cover plate.
WARNING
Electronic models of these appliances are equipped with a three-prong (grounding) plug utilized in connecting the electronic components to the junction box in the lower compartment. This grounding plug provides protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. DO NOT cut or remove the grounding prong from the plug.
11. Install the [Optional] Blower Kit after Installation in the Framing
NOTE: For steps 11 and 12, it may be helpful to remove the control compartment door (Page 50).
FBK-100, FBK-200, and FBK-250 Kits
An electrical outlet box is provided for the installation of the FBK-100, FBK-200, and FBK-250 forced air blower kits. Electrical power must be provided to the box to operate the blower. Install the blower kit according to the installation instructions provided with the kit.
NOTE: The tab connecting the receptacles of the outlet box must be broken in FBK-100 and FBK-200 blower kit applications (Figure 33).
Figure 33: Junction Box Wiring, 120 V, 6 0 hz, 1 phase
Ground: green
Neutral: white
120 VAC: black
Wall-mounted ON/ OFF blower switch or variable speed control switch
*
Junction
box
Tab broken
Hot side of receptacle
Neutral side of receptacle
Green ground screw
Tab intact
Field wired
Factory wired
Blower
Ground
Plug blower into
this receptacle
Red
Black
Green
White
12. Connect the Gas Line
All codes require a shutoff valve mounted in the supply line. Figure 35 illustrates two methods for connecting the gas supply. The flex-line method is acceptable in the U.S., however, Canadian requirements vary depending on locality. Installation must be in compliance with local codes.
NOTE: Ensure the CPI/IPI switch is set to intermittent mode with the pilot in the OFF position. See control compartment door label for more information.
NOTE: A sediment trap is recommended in the gas piping within the home to prevent moisture and debris in the line from damaging the valve.
NOTE: Secure all joints tightly using appropriate tools and sealing compounds (ensure propane resistant compounds are used in propane applications). Optional: Seal around the gas line to prevent cold air leakage. Gas line holes and other openings can be caulked or stuffed with unfaced fiberglass insulation.
Page 37
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
37
Figure 34: Control Compartment Figure 35: Gas Line Connection
Main gas
shutoff valve
Gas valve
Optional burner ON/OFF switch (millivolt units)
CPI/IPI switch (electronic units)
Piezo (millivolt units)
Door latch
(Optional) flexible gas
line connector
Gas
valve
3/8” Nipple
3/8” Union
3/8” Close nipple
3/8” Shutoff valve
3/8 NPT x 3/8” Flare fitting
1/2 x 3/8” Flare shutoff valve
3/8” Flex tubing
Gas stub
1/2 x 3/8”
Reducer
These fireplaces are equipped with a gas flex line for use (where permitted) in connecting the unit to the gas line. A gas flex line is provided to aid in attaching the direct-vent fireplace to the gas supply. The gas flex line can only be used where local codes permit. The flex line is rated for both natural and propane gas. A manual shut off valve is also provided with the flex line.
The gas control valve is located in the lower control compartment (Figure 34).
Access the Control Compartment
See Page 50 for instructions on Accessing the Control Compartment. Millivolt and electronic control valves have a 3/8” (10 mm) NPT thread inlet port. Secure all joints tightly using appropriate tools and sealing compounds (ensure propane resistant compounds are
used in propane applications). Optionally, seal around the gas line to prevent cold air leakage. Gas line holes and other openings can be caulked or stuffed with unfaced fiberglass insulation.
All codes require a shutoff valve mounted in the supply line. The orientation of the shutoff valve should face the front. Figure 35 illustrates two methods for connecting the gas supply. A sediment trap is recommended to prevent moisture and debris in the gas line from damaging the valve.
Test Factory and Field Connections for Gas Leaks
WARNING
Never use an open flame to check for leaks.
Turn on gas supply and test for gas leaks, using a gas leak test solution—also known as bubble leak solution. NOTE: Using a soapy water solution is an effective leak test solution but it is not recommended, because the soap
residue that is left on the pipes/fittings can result in corrosion over time.
1. Light the fireplace (refer to the lighting instructions label in the control compartment or Page 64).
2. Brush all joints and connections with the gas leak test solution to check for leaks. If bubbles are formed, or
gas odor is detected, turn the gas control knob (OFF/PILOT/ON) to the OFF position (millivolt units), or turn the receiver or remote control to the OFF position (electronic units). Either tighten or refasten the leaking connection, and then retest as described above.
3. When the gas lines are tested and leak free, rinse off the leak testing solution
13. Verify Proper Fireplace Operation
1. With the gas line installed, inspect the system before closing the front of the unit.
2. Follow the pilot lighting instructions:
s Millvolt Systems (Page 64) s Electronic Systems (Page 66)
NOTE: When lighting the fireplace for the first time, it will take a few minutes for the gas line to purge itself of air. When purged, the pilot and burner will light and operate as indicated. Subsequent lighting of the fireplace will not require purging. Inspect the pilot flame (carefully remove logs, if necessary).
Millivolt Fireplace Inspection
The pilot flame should be steady, not lifting or floating. Flame should be blue in color with traces of orange at the outer edge. The top 3/8” (10 mm) at the pilot generator (thermopile) and the top 1/8” (3.175 mm) minimum (tip) of the quick drop out thermocouple should be engulfed in the pilot flame. The flame should project 1” (25 mm) beyond the hood at all three ports (Figure 36). Replace the logs if removed for pilot inspection.
To light the burner, turn ON the remote wall switch and rotate the gas valve control knob counterclockwise to the ON position (the top of the valve).
Page 38
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
38
Electronic Fireplace Inspection
To light the burner, turn ON the wall or remote control switch. Ensure the igniter lights the pilot. The pilot flame should engulf the flame rod (Figure 37).
Figure 36: Millivolt Pilot Figure 37: Electronic Pilot
Thermocouple
Hood
Igniter rod
3/8”
(9 mm)
min
Thermopile
Pilot
nozzels
Igniter
Flame Rod
Pilot Hood
14. Optional: Install the Firebox Liners
1. See Page 51 for instructions on Traditional Only: Installing the Firebox Liners.
15. Contemporary Fireplaces: Install the Glass Media
1. See Page 51 for instructions on Contemporary Only: Installing the Glass Media.
16. Traditional Fireplaces: Install the Logs, Volcanic Stone, and Glowing Embers
1. See Page 52 for instructions on Installing the logs, volcanic stone, and glowing embers.
17. Install the Glass Door
1. See Page 55 for instructions on Installing and removing the glass door.
18. Adjust the Air Shutter to Ensure Proper Flame Appearance
WARNING
sAir shutter adjustment should only be performed by a qualified professional service technician. sEnsure glass door is in place and sealed during adjustment.
CAUTION
sSoot will be produced if the air shutter is closed too much. Any damage due to sooting,
resulting from improperly setting the air shutter, is not covered under the warranty.
sThe air shutter rod and nearby appliance surfaces are hot. Exercise caution to avoid injury
while adjusting flame appearance.
Flame Appearance and Sooting
The flame should be blue at the base, and yellow-orange in the body of the flame. When the fireplace is first lit, the entire flame may be blue and will gradually turn yellow-orange during the first 15
minutes of operation. If the flame remains blue, or if the flame is orange with evidence of sooting (black tip), the air shutter opening may need to be adjusted.
If the air shutter opening is closed too far, sooting may develop. Sooting is indicated by black puffs developing at the tips of very long orange flames. Sooting results in black deposits forming on the logs, fireplace inside surfaces, and on exterior surfaces adjacent to the vent termination.
Sooting is caused by incomplete combustion in the flames and lack of combustion air entering the air shutter opening. To achieve a warm yellow-orange flame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
Page 39
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
39
Air Shutter Adjustment Guidelines
s If smoke or soot is present, first check the log set positioning to ensure that the flames are not impinging on any
of the logs. If the log set is properly positioned and a sooting condition persists, then the air shutter should be opened more.
s The more offsets in the vent system, the wider the air shutter will need to be opened. s An fireplace operated with the air shutter opened too far may have flames that appear blue and transparent.
These weak, blue, and transparent flames are termed anemic.
s Propane models may exhibit flames that candle or appear stringy. If this condition is present and persists, adjust
the air shutter to a more closed position, then operate the fireplace for a few more minutes to ensure that the flame normalizes and the flames do not appear sooty.The following chart is provided to help achieve the correct air shutter adjustment for your installation.
Ta bl e 29: Air Shutter Adjustment Guidelines Figure 38: Air Shutter Adjustment Rod
Amount of Primary
Air
Flame Color Air Shutter Adjustment
Air Shutter
Adjustment
Rod Down
(Fully-Open
Position)
Burner
Tube
Adjustment Rod Up (Fully-Closed Position)
Adjustment Set-Screw
If air shutter is
closed too far
Flame will be orange
Air shutter gap should be increased
If air shutter is
open too far
Flame will
be blue
Air shutter gap should be decreased
1. Move the adjustment rod down to decrease air flow and up to increase it. The rod is located in the lower control compartment. Position the air shutter to the factory setting (Table 30).
2. Light the fireplace. Follow the lighting procedure on the lighting label in the control compartment or Page 64.
3. Allow the burner to operate for at least fifteen (15) minutes while observing the flame continuously to ensure
that the proper flame appearance is achieved (Figure 39 and Figure 40). If the following conditions are present, adjust accordingly.
s If flame appears weak or sooty, adjust the air shutter, incrementally, to a more open position until the proper
flame appearance is achieved.
s If flame remains blue, adjust the air shutter, incrementally, to a more closed position until the proper flame
appearance is achieved.
4. When satisfied that the burner flame appearance is normal, reinstall the lower control compartment door, then proceed to finish the installation.
Figure 39: Traditional Fireplaces Flame Appearance Figure 40: Contemporary Fireplaces
Flame Appearance
Ta bl e 30: Main Burner Shutter Opening—Factory Setting
Models Natural Gas Propane
All
1/16”
(1.6 mm)
1/8”
(3.2 mm)
Page 40
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
40
19.
Install the Hood
NOTE: All models must have a hood installed prior to operation.
1. Install the hood by sliding it into the slots on the lower edge of the cabinet top.
NOTE: To install the non-combustible finish material flush with the top of the hood, the hood must be installed
before installing the finish material. If finish material is installed flush with the top edge of the hood, the hood cannot be removed.
NOTE: To install the hood after installing the non-combustible finish material over the black surface above the fireplace opening, the bottom edge of the finish material must be 5/8” above the top edge of the hood to allow clearance for installation and removal of the hood.
20. Reinstall the Included Barrier
WARNING
Reinstall any barrier removed before operating the fireplace. The barrier is designed to reduce the risk of burns from hot glass. Do not operate the fireplace without the barrier installed.
NOTE: All models must have a barrier installed prior to operation.
1. Open the control compartment door (Page 50).
2. Hold the barrier in front of the glass door and slide it up into the slots above the glass door and under the hood.
3. Slide the barrier bottom down into the slots below the glass door, securing it in place.
21.
Install the Finishing Materials
1. Complete finished interior wall.
NOTE: To install the fireplace facing flush with the finished wall, position framework to accommodate the thickness
of the finished wall.
Figure 41: Combustible Wall Framing
Top Of Appliance
3”
(76 mm)
This Area Must Remain Clear of Combustible Materials
1” Min. (25 mm)
3” Clearance Minimum
Hood
Combustible
Material May
Touch The
Appliance
Top
Stand Off
Must Be Bent
To Vertical
Position
Combustible
Finished Wall
Materials
NOTE: See Cold Climate Insulation on Page 9 and Vent Termination Clearances on Page 11.
22. Attach the Safety-in-Operation Warning Labels
1. Attach the furnished safety instruction labels at all fireplace operation and control points (Page 41).
NOTE: The installer MUST ensure these warnings are properly attached during installation. The warning labels are a
critical means of informing consumers of safe operation practices.
Page 41
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
41
ATTACH THE SAFETY-IN-OPERATION WARNINGS
NOTE: It is the installer’s responsibility to ensure these warnings are properly affixed during installation. These warning labels are a
critical step in informing consumers of safe operation of this fireplace.
Attaching Safety-in-Operation Warnings
It is required that the safety instruction labels furnished with the fireplace be affixed to the operation and control point of the fireplace. A safety instruction label must be affixed to the wall switch plate where the fireplace is turned on and off (Figure A) or wall thermostat (Figure B) and if used on the remote control handheld transmitter (Figure C). The warnings should already have been put in place when the fireplace initial set-up was completed. If they are not affixed at these spots, locate the multi-lingual adhesive labels provided with these instructions and proceed as follows:
Apposition des mises en garde relatives à la sécurité d’utilisation
Il est impératif que les étiquettes de sécurité fournies avec le foyer soient collées à côté des dispositifs de contrôle du foyer. Une étiquette de sécurité doit être collée sur la plaque de l’interrupteur contrôlant l’allumage du foyer (Figure A) ou sur le thermostat mural (Figure B) et, le cas échéant, sur le boîtier de la télécommande (Figure C). Les mises en garde auraient dû être collées au moment de l’installation initiale du foyer. Si ce n’est pas le cas, prenez les étiquettes adhésives multilingues fournies avec ces instructions et procédez comme suit:
Colocación de advertencias de seguridad en operación
Se requiere que las etiquetas de instrucciones de seguridad incluidas con la chimenea se coloquen en el punto de operación y control de la misma. Se debe colocar una etiqueta de instrucciones de seguridad en la placa del interruptor de pared desde el cual se enciende y se apaga la chimenea (Figura A) o en el termostato de pared (Figura B) y en el transmisor de control remoto (Figura C) si se usa. Las advertencias ya deben haberse colocado cuando se completó la instalación inicial de la chimenea. Si no están colocadas en estos lugares, encuentre las etiquetas adhesivas multilingües proporcionadas con estas instrucciones y prosiga de la siguiente manera:
1. Locate the wall switch or wall thermostat
that controls the fireplace (verify the switch operates the fireplace by turning it on and off). Clean the wall switch plate or wall thermostat thoroughly to remove any dust and oils. Affix the label to the surface of the plate of the wall switch that controls the fireplace (Figure A) or the wall thermostat (Figure B). Choose the language primarily spoken in the home. If unknown, affix the English language label.
2. If a remote control is used to control the
fireplace, locate the transmitter and clean it thoroughly to remove any dust and oils. Affix the label to the surface of handheld transmitter (Figure C). Choose the language primarily spoken in the home. If unknown, affix the English language label.
3. If you are unable to locate the labels, please
contact IHP or your nearest IHP dealer to receive additional safety instruction labels free of charge.
1. Repérez l’interrupteur ou le thermostat mural
qui contrôle le foyer (vérifiez que l’interrupteur contrôle le fonctionnement du foyer en le faisant basculer de Marche à Arrêt, et vice­versa). Nettoyez soigneusement la plaque murale de l’interrupteur ou le thermostat mural pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur la surface de la plaque de l’interrupteur mural qui contrôle le foyer (Figure A) ou du thermostat mural (Figure B) . Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
2. Si une télécommande est utilisée pour
contrôler le foyer, nettoyez la soigneusement pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur le boîtier de la télécommande (Figure C). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
3. Si vous ne parvenez pas à localiser les
étiquettes, s’il vous plaît contactez IHP ou votre revendeur le plus proche pour recevoir IHP étiquettes d’instructions de sécurité supplémentaires gratuitement.
1. Identifique el interruptor o el termostato de
pared que controla la chimenea (verifique que el interruptor opera la chimenea encendiéndola y apagándola). Limpie bien la placa del interruptor o el termostato de pared para quitar el polvo y aceite. Pegue la etiqueta en la superficie de la placa del interruptor que controla la chimenea (Figura A) o en el termostato de pared (Figura B). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
2. Si se usa un control remoto para controlar
la chimenea, encuentre el transmisor y límpielo bien para quitar el polvo y aceite. Pegue la etiqueta en la superficie del transmisor (Figura C). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
3. Si usted es incapaz de localizar las etiquetas,
por favor póngase en contacto con IHP, o con su distribuidor más cercano IHP recibir instrucción etiquetas de seguridad adicionales sin costo.
Cat. No. H8024 Replacement Label Kit Étiquettes de remplacement, n° cat. H8024 Juego de etiquetas de repuesto - Nº de cat. H8024 NOTE: English is red text on clear label. French
and Spanish are white text on black label.
Remarqué : Le texte anglais est rouge sur un support transparent. Le texte français et espagnol est blanc sur un support noir.
Nota: La etiqueta en inglés es transparente con texto rojo. Las etiquetas en francés y español son negras con texto blanco.
SAFETY LABEL DIAGRAMS DIAGRAMMES DES ÉTIQUETTES DE SÉCURITÉ DIAGRAMAS DE ETIQUETAS DE SEGURIDAD
Innovative Hearth Products
Illustrations are for example only. Your accessories may be different.
Les illustrations sont par exemple uniquement. Vos accessoires peuvent être différents.
Las ilustraciones son sólo ejemplos. Tu accesorios pueden ser diferentes.
Remote
Off
On
PRG
Figure A
Figure B
Figure C
Figura A
Figura B
Figura C
Page 42
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
42
INSTALLATION ACCESSORIES
Tabl e 31: Listed Secure Vent® Components
Catalog Number
Model Description
Catalog
Number
Model Description
F1797 * SV4.5HTKCT
Rigid, Horizontal,
Compact Termination
with Firestop/Spacer
(H2246), Adaptor (74L61)
(see 750204M)
The following flashing comes packaged with a storm collar
F1798 * SV4.5HTKCT20
Rigid, Horizontal Compact
Termination, 20” with Shield
and Firestop (see 750247M
and 750204M)
* See Page 28 concerning use with the 45” model
H1968 SV4.5HT-2
Horizontal Square Termination
with Firestop/Spacer (H2246),
and Adaptor (74L61)
77L78 SV4.5F Flat Roof Flashing
77L79 SV4.5FA
1/12 to 7/12 Adjustable
Flashing
77L80 SV4.5FB
7/12 to 12/12 Adjustable
Flashing
94L10 SV4.5HTSS
Rigid, Horizontal, Small
Square Termination
with Firestop/Spacer
(H2246), Adaptor (74L61)
(see 750204M)
77L81 SV4.5SC6 Storm Collar (6 pack)
H5817 SV4.5-20SSWSK
Rigid, Small, Square
Termination, 20” with Shield
and Firestop (see 750247M
and 750204M)
H6183 SV4.5HF5 Firestop Spacer, 5”, rigid
H2152 SV4.5CGV-1
Vertical Termination Cap, High
Wind
H6184 SF4.5HF5 Firestop Spacer, 5”, flex
H8914 SV4.5TK90HT2
Horizontal Termination Kit HT-2
with 90° elbow
H2246 SV4.5HF-10
Firestop/Spacer-Horizontal,
rigid (3-1-1 spacing), 10 Pack
H8915 SV4.5TK90SS
Horizontal Termination Kit
Small Square with 90° elbow
H2247 SV4.5VF-10
Firestop/Spacer-Vertical, rigid
(1-1-1 spacing), 10 Pack
96K92 SV4.5SP Support Plate
Vent Sections (Rigid)
77L70 SV4.5L6 6” (152 mm)
17M52 SV4.5HGS-1
Termination Guard, Square (1
pack) (see 750109M)
77L71 SV4.5L12 12” (305 mm)
77L72 SV4.5L24 24” (610 mm) 17M53 SV4.5HGS-12
Termination Guard,
Horizontal Square (12 pack)
(see 750109M)
77L73 SV4.5L36 36” (914 mm)
87L02 SV4.5HGS
Termination Guard
for Horizontal Square
Termination (Deluxe)(1 pack)
(see 750055M)
77L74 SV4.5L48 48” (1219 mm)
77L75 SV4.5LA
Telescopic Length Slip Section
(2–7 1/2” rigid)
Page 43
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
43
Tabl e 31: Listed Secure Vent® Components
77L76 SV4.5E45 45° Elbow
H5820 SV4.5HTSK
Termination Shroud (Guard)
for Horizontal Square Termination (1 pack)
(see 750246M)
77L77 SV4.5E90 90° Elbow
Catalog Number
Model Description
Catalog
Number
Model Description
H5816
750,247M
SV4.5-TWSK10
Through Wall Shield Kit
(to shield direct-vent pipe
from blown insulation)
(see 750247M)
H3907 SV4.5ARSA
Attic Insulation Shield with
adjustable height, 12–22”
96K93 SV4.5SU Support Strap
S
e
a
l
a
n
t
10K81 SFMP
Mill-Pac, Black, High-
Temperature Sealant
99L02 SV4.5HRK14
Horizontal Riser Kit, 14”(see
750146M)
89L40 SFMP-12
Mill-Pac, Black, High-
Temperature Sealant
(bulk 12-pack)
99L03 SV4.5HRK36
Horizontal Riser Kit, 36”
(see 750146M)
Tabl e 32: Listed Secure Flex® Components
Catalog Number
Model Description
Catalog Number
Model Description
These termination kits include firestop/spacer, gear clamps, and flex adaptor.
94L04 SFKIT12SS
Small Square Termination for flex,
with 12” (305 mm) of *compressed
flex vent (see 750204M)
60L10 SF-18
18 ft (5.49 m)* compressed flex
(see 750053M)
98K03 SF-12
12 ft (3.66 m)*compressed flex
(see 750052M)
94L05 SFKIT18SS
Small Square Termination for flex,
with 18” (457 mm) of *compressed
flex vent (see 750204M)
H2248 SF4.5HF-10
Firestop/Spacer, Horizontal, flex
(3-1-1 spacing), 10 Pack
94L06 SFKIT24SS
Small Square Termination for flex,
with 24” (610 mm) of *compressed
flex vent (see 750204M)
H2249 SF4.5VF-10
Firestop/Spacer, Vertical, flex (1-1-1
spacing),10 Pack
94L07 SFKIT36SS
Small Square Termination for flex,
with 36” (914 mm) of *compressed
flex vent (see 750204M)
F1803 SF4.5HTKCT
Horizontal Compact Termination
for flex (without flex)
94L08 SFKIT48SS
Small Square Termination for flex, with
48” (1219 mm) of *compressed flex
vent (see 750204M)
F1799 SFKIT18CT
Compact Termination for flex with
18” (457 mm) compressed flex
94L09 SF-HTSS
Horizontal Small Square Termination
for flex, without flex vent
(see 750204M)
F1800 SFKIT24CT
Compact Termination for flex with
24” (610 mm) compressed flex
F1801 SFKIT36CT
Compact Termination for flex with
36” (914 mm) compressed flex
F1802 SFKIT48CT
Compact Termination for flex with
48” (1219 mm) compressed flex
Page 44
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
44
Tabl e 32: Listed Secure Flex® Components
H1969 SF4.5HT-2
Horizontal Square Termination for
flex (without flex)
56L74 SFVT30
Vertical Termination for flex (flat to 6/12) with flex adaptor, section of rigid vent, roof support collar assembly, roof flashing and
storm collar. (see 750052M)
77L87 SFKIT12S
Square Term. for flex with
12” (305 mm)* compressed flex
77L88 SFKIT18S
Square Term. for flex with
18” (457 mm)* compressed flex
77L89 SFKIT24S
Square Term. for flex with
24” (610 mm)* compressed flex
56L75 SFVT45
Vertical Termination for flex (6/12 to 12/12) with flex adaptor, section of rigid vent, roof support collar assembly, roof flashing and
storm collar. (see 750052M)
77L90 SFKIT36S
Square Term. for flex with
36” (914 mm)* compressed flex
H7748 H7748
36” Flex Connector Kit.
36” of flex with two adaptors for
mating two rigid sections of vent
together.
77L91 SFKIT48S
Square Term. for flex with
48” (1219 mm)* compressed flex
91L66 SFGC4-6
Gear Clamp 4.5” (114 mm) for flex
(6-pack)
91L67 SFGC7-6
Gear Clamp 7.5” (190.5 mm) for
flex (6 pack)
*All compressed flex vents can be expanded up to two times.
GAS CONVERSION KITS
WARNING
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire, explosion, or the production of carbon monoxide may result; causing property damage, personal injury, or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.The qualified service agency performing this installation assumes responsibility for this conversion.
AVERTISSEMENT
Cette trousse de conversion doit être installée par un technicien agréé, selon les instructions du fabricant et selon toutes les exigences et tous les codes pertinents de l’autorité compétente. Assurez-vous de bien suivre les instructions dans cette notice pour réduire au minimum le risque d’incendie, d’explosion ou la production de monoxyde de carbone pouvant causer des dommages matériels, des blessures ou la mort. Le tecnicien agréé est responsable de l’installation de cette trousse. L’installation n’est pas adéquate ni complète tant que le bon fonctionnement de l’appareil converti n’a pas été vérifié selon les instructions du fabricant fournies avec la trousse. Le fournisseur de service qualifié ayant réalisé l’installation assume les responsabilités liées à la conversion.
In Canada: The conversion shall be carried out in accordance with the requirements of the provincial authorities having
jurisdiction and in accordance with the requirements of the CAN/CGA-B149.1 Installation code.
La conversion devra être effectuée conformément aux recommandations des autorités provinciales ayant juridiction et conformément aux exigences du code d’installation CAN/CGA-B149.1.
Gas conversion kits are available to adapt your fireplace from the use of one type of gas to the use of another. These kits contain all the necessary components needed to complete the task including labeling that must be affixed to ensure safe operation.
Refer to the instructions provided with the conversion kit when performing any gas conversion.
Ta bl e 33: Millivolt Systems,Natural Gas To Propane Gas Conversion Kits Tab le 34: Millivolt Systems, Propane Gas to Natural Gas Conversion Kits
Models Catalog Number Models Catalog Number
DRC2033 / DRT2033 F1893 DRC2033 / DRT2033 F1891 DRC2035 / DRT2035 F1771 DRC2035 / DRT2035 F1769 DRC2040 / DRT2040 F1772 DRC2040 / DRT2040 F1770 DRC2045 / DRT2045 F1897 DRC2045 / DRT2045 F1895
Page 45
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
45
Ta bl e 35: Electronic Systems, Natural Gas To Propane Gas Conversion Kits Tab l e 36: Electronic Systems, Propane Gas To Natural Gas Conversion Kits
Models Catalog Number Models Catalog Number
DRC2033 / DRT2033 F1892 DRC2033 / DRT2033 F1890 DRC2035 / DRT2035 F1773 DRC2035 / DRT2035 F1767 DRC2040 / DRT2040 F1774 DRC2040 / DRT2040 F1768 DRC2045 / DRT2045 F1896 DRC2045 / DRT2045 F1894
Page 46
Installation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
46
Installing Gas Conversion Kits
WARNING
The gas supply shall be shut OFF prior to disconnecting the electrical power, before proceeding with the conversion.
AVERTISSEMENT
Avant d’effecteur la conversion, coupez d’abord l’alimentation en gaz, ensuite, coupez l’alimentation electrique.
1. TURN OFF THE GAS SUPPLY TO THE FIREPLACE and disconnect power supply at the circuit breaker. Ensure
fireplace is cold.
2. Open the lower control compartment door (Page 50).
3. Remove the front glass door/frame from the fireplace (Page 55).
4. Remove the logs / glass media. If necessary, remove the log grate. NOTE: Exercise care so as not to break the logs (Page 58).
5. Remove the sub floor.
6. Remove the two (2) screws securing the burner assembly. Remove the burner assembly with the attached
venturi tube.
Millivolt and Electronic Ignition System Fireplaces
7. Refer to the instructions provided with the SIT Regulator Conversion Kit, and Figure 42. Using a Torx T20 driver (with 1/4” shank) or slotted screwdriver, remove and discard the pressure regulator mounting screws (two screws for electronic models, three screws for millivolt models), pressure regulator tower, the diaphragm assembly (if applicable) and the spring. Discard all removed components.
Figure 42: Valve Regulator Conversion
(millivolt shown)
Pressure Regulator
Remove These Components
Pressure
Regulator
Remove these components
8. Install the new pressure regulator assembly using the supplied screws. Tighten the screws to 25 in. lbs.
9. Install the enclosed identification label to the valve body where it can be easily seen.
10. Remove the pilot hood assembly to access the hex pilot orifice (Figure 43). Remove and replace the pilot
orifice with the one provided with the kit. Exercise extreme care to prevent damage to or breakage of the igniter assembly.
11. Remove the burner orifice from the manifold and replace it with the one provided in the kit (Figure 44). NOTE: See Table 5 for burner orifice sizes.
Page 47
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
47
Figure 43: Millivolt Pilot Figure 44: Orifice
Pilot
Orifice
Pilot
Orifice
12. Use pipe joint compound or Teflon® tape on all pipe fittings before installing. NOTE: Ensure propane resistant compounds are used in propane applications, do not use pipe joint compounds
on flare fittings.
13. Retrieve the burner and hold the venturi tube above the orifice. Place the shutter adjusting rod in the slot of the shutter arm (Figure 38). Set the burner assembly into its position and secure the trapezoidal plate with the two screws previously removed.
14. Reinstall the baffle with the two baffle securing screws.
15. Reassemble the remaining components.
16. Turn on gas supply and test for gas leaks (Page 37).
17. Relight the main burner. The lighting instructions can be found on the lighting label in the control compartment or Page 64. Verify proper burner ignition and operation (Page 38).
18. Inspect the pilot system for proper flame. The pilot flame should engulf the flame sensor (Figure 36 and
Figure 37).
19. Using a manometer, test the inlet and manifold gas pressures (Table 3 and Table 4).
NOTE: Always test pressures with the valve regulator control at the highest setting.
Page 48
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
48
OPERATION
WARNING
Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la surface chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habitent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécurité; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
WARNING
Reinstall any barrier removed before operating the fireplace. The barrier is designed to reduce the risk of burns from hot glass. Do not operate the fireplace without the barrier installed.
WARNING
Do not operate the fireplace if:
sThe glass front is removed, cracked, or broken sThe surround trim assembly and screen are not installed
CARBON MONOXIDE POISONING: Early signs of carbon monoxide poisoning are similar to the flu with headaches, dizziness and/or nausea. If you have these signs, obtain fresh air immediately. Turn off the gas supply to the appliance and have it serviced by a qualified professional, as it may not be operating correctly. Some people are more affected by carbon monoxide than others, including pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
NOTE: Do not place furniture or other combustible materials within 36” of the front of viewing area(s). NOTE: Children and adults should be alerted to the hazards of high surface temperature and should stay away to
avoid burns or clothing ignition.
Remarqué : Les enfants et les adultes devraient être infor-més des dangers que posent les températures de surface élevées et se tenir à distance afin d’éviter des brûlures ou que leurs vêtements ne s’enflamment.
NOTE: Installation and repair should be done by a qualified service person. The fireplace should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the fireplace be kept clean.
Remarqué : L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres.
NOTE: Do not use these fireplaces if any part has been under water. Immediately call a qualified, professional service technician to inspect the fireplace and to replace any parts of the control system and any gas control which have been under water.
Remarqué : Ne pas utiliser cet appareil s’il a été plongé, même partiellement, dans l’eau. Appeler un technicien qualifié pour inspecter l’appareil et remplacer toute partie du système de commande et toute commande qui a été plongée dans l’eau.
Page 49
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
49
ATTACH THE SAFETY-IN-OPERATION WARNINGS
NOTE: It is the installer’s responsibility to ensure these warnings are properly affixed during installation. These warning labels are a
critical step in informing consumers of safe operation of this fireplace.
Attaching Safety-in-Operation Warnings
Your fireplace has been furnished with safety instruction labels that are to be affixed to the operation and control point of the fireplace. A safety instruction label should be affixed to the wall switch plate where the fireplace is turned on and off (Figure A) or wall thermostat (Figure B) and if used on the remote control handheld transmitter (Figure C). The warnings should already have been put in place when the fireplace initial set-up was completed. If they are not affixed at these spots, locate the multi-lingual adhesive labels provided with these instructions and proceed as follows:
Apposition des mises en garde relatives à la sécurité d’utilisation
Votre foyer a été livré avec des étiquettes de sécurité qui doivent être collées à côté des dispositifs de contrôle du foyer. Une étiquette de sécurité doit être collée sur la plaque de l’interrupteur contrôlant l’allumage du foyer (Figure A) ou sur le thermostat mural (Figure B) et, le cas échéant, sur le boîtier de la télécommande (Figure C). Les mises en garde auraient dû être collées au moment de l’installation initiale du foyer. Si ce n’est pas le cas, prenez les étiquettes adhésives multilingues fournies avec ces instructions et procédez comme suit :
Colocación de advertencias de seguridad en operación
Su chimenea incluye etiquetas de instrucciones de seguridad que deben colocarse en el punto de operación y control de la chimenea. Se debe colocar una etiqueta de instrucciones de seguridad en la placa del interruptor de pared desde el cual se enciende y se apaga la chimenea (Figura A) o en el termostato de pared (Figura B) y en el transmisor de control remoto (Figura C) si se usa. Las advertencias ya deben haberse colocado cuando se completó la instalación inicial de la chimenea. Si no están colocadas en estos lugares, encuentre las etiquetas adhesivas multilingües proporcionadas con estas instrucciones y prosiga de la siguiente manera:
1. Locate the wall switch or wall thermostat
that controls the fireplace (verify the switch operates the fireplace by turning it on and off). Clean the wall switch plate or wall thermostat thoroughly to remove any dust and oils. Affix the label to the surface of the plate of the wall switch that controls the fireplace (Figure A) or the wall thermostat (Figure B). Choose the language primarily spoken in the home. If unknown, affix the English language label.
2. If a remote control is used to control the
fireplace, locate the transmitter and clean it thoroughly to remove any dust and oils. Affix the label to the surface of handheld transmitter (Figure C). Choose the language primarily spoken in the home. If unknown, affix the English language label.
3. If you are unable to locate the labels, please
contact IHP or your nearest IHP dealer to receive additional safety instruction labels free of charge.
1. Repérez l’interrupteur ou le thermostat mural
qui contrôle le foyer (vérifiez que l’interrupteur contrôle le fonctionnement du foyer en le faisant basculer de Marche à Arrêt, et vice­versa). Nettoyez soigneusement la plaque murale de l’interrupteur ou le thermostat mural pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur la surface de la plaque de l’interrupteur mural qui contrôle le foyer (Figure A) ou du thermostat mural (Figure B) . Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
2. Si une télécommande est utilisée pour
contrôler le foyer, nettoyez la soigneusement pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur le boîtier de la télécommande (Figure C). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
3. Si vous ne parvenez pas à localiser les
étiquettes, s’il vous plaît contactez IHP ou votre revendeur le plus proche pour recevoir IHP étiquettes d’instructions de sécurité supplémentaires gratuitement.
1. Identifique el interruptor o el termostato de
pared que controla la chimenea (verifique que el interruptor opera la chimenea encendiéndola y apagándola). Limpie bien la placa del interruptor o el termostato de pared para quitar el polvo y aceite. Pegue la etiqueta en la superficie de la placa del interruptor que controla la chimenea (Figura A) o en el termostato de pared (Figura B). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
2. Si se usa un control remoto para controlar
la chimenea, encuentre el transmisor y límpielo bien para quitar el polvo y aceite. Pegue la etiqueta en la superficie del transmisor (Figura C). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
3. Si usted es incapaz de localizar las etiquetas,
por favor póngase en contacto con IHP, o con su distribuidor más cercano IHP recibir instrucción etiquetas de seguridad adicionales sin costo.
Cat. No. H8024 Replacement Label Kit Étiquettes de remplacement, n° cat. H8024 Juego de etiquetas de repuesto - Nº de cat. H8024 NOTE: English is red text on clear label. French
and Spanish are white text on black label.
Remarqué : Le texte anglais est rouge sur un support transparent. Le texte français et espagnol est blanc sur un support noir.
Nota: La etiqueta en inglés es transparente con texto rojo. Las etiquetas en francés y español son negras con texto blanco.
SAFETY LABEL DIAGRAMS DIAGRAMMES DES ÉTIQUETTES DE SÉCURITÉ DIAGRAMAS DE ETIQUETAS DE SEGURIDAD
Innovative Hearth Products
Illustrations are for example only. Your accessories may be different.
Les illustrations sont par exemple uniquement. Vos accessoires peuvent être différents.
Las ilustraciones son sólo ejemplos. Tu accesorios pueden ser diferentes.
Remote
Off
On
PRG
Figure A
Figure B
Figure C
Figura A
Figura B
Figura C
Page 50
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
50
Burn-in Period
The first few times this fireplace is operated, there will be an odor from the curing of paint and the burning off of the lubricants used in the manufacturing process. Depending on usage, the burn-in period may take a few hours or a few days.
NOTE: Ventilate the site during the burn-in period. The resulting odor and haze may set off a smoke detector. Do not operate the blower during the burn-in period.
A white film may develop on the glass front during the first few fires as part of the burn-in period. The glass should be kept clean during the burn-in period to prevent the film from baking on—making it very difficult to remove (Cleaning the glass door on Page 57).
Accessing the Control Compartment
NOTE: If the door is difficult to open/close, remove it as instructed and straighten the door tabs (Figure 46).
1. Access the control compartment (Figure 34) by holding the control compartment door by the top and gently
lifting it up, then rotating it away from the fireplace.
Closing the Control Compartment
1. Swing the door gently up and then lift and set the door so it catches in the upright, closed position.
Removing the Control Compartment Door
1. Remove the bottom, left screw (Figure 45) inside the control compartment securing the control compartment door. Retain the screw for later reinstallation.
2. Position the left side door tab (Figure 46) out of the tab groove and align it with the vertical slot (Figure 45).
Figure 45: Control compartment door slots Figure 46: Control compartment door tabs
Vertical
slot
Screw hole
Tab pivot
hole
Tab
groove
Door tabs
3. Lift the left side of the control compartment door with the tabs in the vertical slot until the tabs clear the slot, disengaging the left side of the door from the fireplace.
4. Pull the door to the left to disengage the right side door tabs, and remove the door. Store the control compartment door in a secure location until reinstallation.
Gas Controls
The standard controls for fireplace operation are located in the control compartment, below the glass door (Figure 34). Optional control switches are also available.
Millivolt and electronic gas control systems operate differently. Before lighting and operating the fireplace determine if it is a millivolt or electronic system:
s Millivolt Fireplaces (Figure 1) s Electronic Fireplaces (Figure 2)
Familiarize yourself with the gas control valve and the lighting procedure (Page 64).
Millivolt Fireplaces
Detailed lighting instructions are found on Page 64. Also, millivolt fireplace lighting instructions are found on the pull-out lighting instructions attached to the gas control valve.
When the pilot is lit, the main burner can be turned ON/OFF using a wall switch, remote control, optional on-unit rocker switch (FRS), or wall thermostat.
Page 51
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
51
If the millivolt fireplace is equipped with an optional remote switch (wall switch, remote control, rocker switch, or wall thermostat) and the pilot is lit, the fireplace main burner can be turned ON/OFF using the optional switch.
NOTE: Do NOT wire more than one valve to the burner control switch. This will help prevent excessive resistance in the burner circuit, that can cause burner operation problems.
Electronic Fireplaces
Detailed lighting instructions are found on Page 66. Also, electronic fireplace lighting instructions are found on the pull-out lighting instructions attached to the gas control valve.
If the electronic fireplace is equipped with an optional remote wall switch or remote control, the fireplace main burner can be turned ON/OFF with the wall switch or remote control.
If the electronic fireplace is not equipped with a wall switch or remote control, the main burner must be turned ON/ OFF with a gas control switch installed separately. Contact the installer for more information. Check the batteries, if installed, at least every three (3) months to ensure they are properly charged.
To light the fireplace in a power outage:
1. Confirm that batteries are installed in the battery pack.
2. Set the unit-mounted switch, or wall switch to the ON Position.
3. The unit should spark at the pilot and light. NOTE: If there is no spark, replace the batteries.
4. Operate the fireplace normally.
Installing the Backup Batteries
With a battery backup, electronic fireplaces can automatically switch to battery power. In the event of a power outage, this allows ON/OFF operation (without blower functionality). Install new batteries before every burn season.
1. Open the control compartment (Page 50), and locate the battery holder.
2. Install four (4) AA batteries in the battery holder.
3. Close the control compartment door.
Continuous Pilot Ignition Switch
Fireplaces with an electronic gas valve have a continuous pilot ignition (CPI) switch installed in the control compartment.
This switch allows the pilot to be switched from intermittent mode to continuous mode:
s Intermittent Mode—The pilot is extinguished when the fireplace is OFF. s Continuous Mode—The pilot stays ON when the fireplace is OFF.
In periods of extreme cold, condensation may form on the glass door when the fireplace is OFF and the pilot is in intermittent mode. Also, with the pilot in intermittent mode, the fireplace may cycle startup (i.e., the pilot and burner ignite, but the burner extinguishes and reignites several times until the flue reaches the temperature for proper drafting).
s To save energy—switch to intermittent mode. s For a standing pilot that will help prevent glass door condensation and cycle startup—switch to continuous mode.
NOTE: Continuous mode is indicated by a pilot that comes ON and remains lit when the fireplace is OFF.
Traditional Only: Installing the Firebox Liners
1. Remove the three (3) firebox liner panels from the packing materials.
2. Carefully position the rear panel, upper edge first, in the firebox against the rear wall.
3. While holding the rear panel, carefully position the left side panel in the firebox.
4. Carefully position the right side panel in the firebox. NOTE: Do not force the panels. Excessive force may cause breakage. If the panels are correctly positioned, they
will fit snugly in place.
Contemporary Only: Installing the Glass Media
1. Install the glass media in the recessed area between the front and rear floors. NOTE: 35” fireplaces require less than a full bag of glass media. 40” fireplaces require an entire bag of media.
2. Spread the glass media in a thin layer, evenly over the burner and pilot. NOTE: Do NOT mound the media.
Page 52
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
52
Installing the logs, volcanic stone, and glowing embers
WARNING
sTurn OFF all gas and electricity to the appliance before installing the volcanic stone, embers, and logs. sDo NOT install the logs until the appliance has been competely installed, the gas line connected and
tested for leaks, and the initial burner operation has been confirmed.
sUse of an unapproved log set in the fireplace will void the warranty and will result in incomplete
combustion, sooting, and poor flame quality.
sLogs get very hot and remain hot for up to one hour after the gas supply is turned OFF. Handle the logs
only when cool.
sThis appliance is not designed to burn wood. Any attempt to do so could cause irreparable damage to
appliance and prove hazardous.
sIf the logs are not installed according to these instructions, improper combustion could occur. This could
result in the excessive production of soot and/or the colorless, odorless, toxic gas carbon monoxide (CO).
NOTE: If applicable, install the firebox liner before placing the stone. Logs can be installed after the volcanic stone.
Installing the volcanic stone, and glowing embers
1. If necessary, remove the glass door (Page 55).
2. Spread the decorative volcanic stone in a pleasing pattern on the firebox floor along the slope and to the back
right and left sides of the burner (Figure 47).
NOTE: Do not place stone on the burner.
3. Separate and fluff the glowing embers into pieces approximately the size of a quarter (Figure 48).
Figure 47: Installing the volcanic stone Figure 48: Separating the glowing embers
4. Position the separated glowing embers over the small holes on the burner surface (Figure 49). Do NOT cover the large burner slots.
Figure 49: Installing the glowing embers
NOTE: Enough glowing ember material is provided for several applications. For best glowing effect, replace the ember material annually.
Page 53
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
53
Installing the DRT2033 and DRT2035
The logs have notches/tabs to assist proper positioning. Upper logs rest on lower logs via notches/tabs. Proper log placement is critical to prevent sooting. Place the logs in the gaps between flame peaks, so they do not impinge the flames. Follow the log placement instructions precisely.
NOTE: Do not cover the burner ports. NOTE: Ensure the left front log (1) and right front log (2) are correctly installed on the burner positioning pins.
Tabl e 37: DRT2033 and 35 Log Sets
4
5
3
2
1
Log Number Description
1 Rear Log 2 Left Front Log 3 Right Front Log 4 Left Cross Log 5 Right Cross Log
Catalog number for the entire set: H7666 - 35” Aries and F1885 33” Aries
1. If necessary, remove the glass door (Page 54) Locate and bend up Burner Locating Tabs (Figure 50).
2. Locate the log placement brackets (Figure 50). Place embers and other media (see Page 52)
Figure 50: Locating the log placement brackets Figure 51: Placing logs 1 and 2
Left Log Bracket (front & rear)
Right Log Bracket (front & rear)
Left and Right Burner Locating Tabs
1
3. Align the notches in the bottom of the rear log (1) with the left rear brackets (Figure 51).
4. Position the left rear log (1) on the left rear bracket and the left front log (2) on the left front log bracket and the
left burner locating tab (Figure 51).
Figure 52: Placing log 3 Figure 53: Placing logs 4 and 5
3
4
5
5. Position the right front log (3) on the right front log bracket and right burner locating tab (Figure 52).
6. Position the left cross log (4) on the left rear log (1) and right cross log (5) on the right rear log bracket
(Figure 53).
2
Page 54
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
54
Installing the DRT2040 and DRT2045 logs
The logs have notches/tabs to assist proper positioning. Upper logs rest on lower logs via notches/tabs. Proper log placement is critical to prevent sooting. Place the logs in the gaps between flame peaks, so they do not impinge the flames. Follow the log placement instructions precisely.
NOTE: Do not cover the burner ports.
Tabl e 38: DRT2040 Log Set
4
5
3
2
1
Log Number Description
1 Rear Log 2 Left Front Log 3 Right Front Log 4 Left Cross Log
5 Right Cross Log
Catalog number for the entire set: DRT2040: F1830 DRT2045: F1884
1. If necessary, remove the glass door (Page 55).
2. Locate the log placement brackets (Figure 54).
Figure 54: Placing log 1 Figure 55: Placing logs 2 and 3
Glowing Embers
(Do not place glowing embers over burner slots)
Right Rear Log Bracket
1
Volcanic Stone
Log Rack
3
2
3. Position rear log (1) on the left rear log bracket (Figure 54)
4. Position the left front log (2) and the right front log (3) against the log rack (Figure 55).
5. Position the left cross log (4) over the rear log (1) and left front log (2) with the front resting on the log rack
(Figure 56).
Figure 56: Placing log 4 Figure 57: Placing log 5
4
2
1
3
5
6. Position the right cross log (5) on the right rear log bracket and over right front log (3) (Figure 57).
Page 55
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
55
Installing and removing the glass door
WARNING
sDo not attempt to substitute the materials used on these doors, or replace cracked or broken glass. sHandle this glass with extreme care! Glass is susceptible to damage—Do not scratch or handle roughly
while reinstalling the glass door frame.
sThe glass door of this appliance must only be replaced as a complete unit as provided by the
manufacturer. Do not attempt to replace broken, cracked or chipped glass separately.
sDo not attempt to touch the front enclosure glass with your hands while the fireplace is in use.
WARNING
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed.
WARNING
Une barrière conçue pour réduire le risque de brûlure par le hublot chaude est fournie avec l’appareil et doit être installé.
WARNING
Do not operate appliance with the glass front removed, cracked, or broken.
AVERTISSEMENT
Ne pas utiliser l’appareil si le panneau frontal en verre n’est pas en place, est craqué, ou brisé.
WARNING
Any safety screen or guard removed for servicing the appliance must be replaced prior to operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
Only doors certified with the fireplace shall be used.
Seules des portes certifiées pour cet appareil doivent être utilisées.
CAUTION
Do NOT abuse the glass door by striking it or slamming it shut.
Page 56
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
56
Installing the glass door
1. Visually inspect the gasket on the backside of the glass door. NOTE: The gasket surface must be clean, free of irregularities, and seated firmly. Ensure it is properly located.
Make sure the bead is not rolled into the channel at the top of the door, but remains flat against the top of the glass.
2. Position the door in front of the firebox opening with the bottom of the door held away from the fireplace at a 45° angle (Figure 58). Hook the top flange of the door frame over the top of the firebox frame.
NOTE: Ensure the glass door is centered—with even spacing on each side.
3. Let the bottom of the glass door swing gently in towards the fireplace ensuring that the gasket seats evenly as
the door draws shut. Securely fasten the two (2) latches beneath the firebox floor to the door V-flange.
4. Install the barrier.
5. Close the control compartment door.
Removing the glass door
1. Open the control compartment door (Page 50). NOTE: If necessary, remove the door and place it in a safe location for later reinstallation.
2. Remove the barrier. Place the barrier in a safe location for later reinstallation.
3. Detach the two (2) door latches beneath the firebox floor.
4. Swing the bottom of the glass door away from the fireplace to a 45° angle (Figure 58)
5. Carefully grip the door at the top and bottom, and remove it from the fireplace. Place the door in a safe location
for later reinstallation.
Figure 58: Glass Door
Latch
Control
Compartment
Door
Glass
Door
Hood
Page 57
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
57
MAINTENANCE
Refer to the Maintenance Schedule on Page 60 for maintenance tasks, procedures, frequency, and a listing of by whom the tasks should be performed. Always verify proper fireplace operation after servicing.
WARNING
Turn OFF gas and electrical power to the fireplace and allow it to cool before cleaning or servicing the appliance.
CAUTION
Wear gloves and safety glasses for protection while doing required maintenance.
Verify proper operation after servicing.
S’assurer que l’appareil fonctionne adéquatement une fois l’entretien terminé.
Always turn OFF gas before cleaning. Before relighting, refer to the lighting instructions in this manual. Instructions are also found on a pull-out panel located in the control compartment.
Always keep the appliance area clear and free from combustible materials, gasoline and other flammable liquids. NOTE: Prior to the first use of the fireplace and each burn season and periodically during the burn season, inspect the
horizontal termination for debris such as bird nests, leaves, paper or branches. Remove any items from the surfaces of the termination prior to use. Also be aware of shrubs and plantings that may encroach on the termination.
Inspecting the venting system
The fireplace and venting system should be thoroughly inspected before initial use and at least annually by a qualified service technician. Inspection should include ensuring that exhaust or intake passages are unobstructed and vent components are properly assembled and not damaged.
The homeowner must contact a qualified service technician at once if any abnormal condition is observed.
If the venting system is disassembled for any reason, a qualified service technician should follow vent installation instructions for proper reassembly and proper sealing of the venting system components. However, more frequent periodic inspections and cleanings should be performed by the homeowner.
NOTE: Prior to the first use of the fireplace and each burn season and periodically during the burn season, inspect the horizontal termination for debris such as bird nests, leaves, paper or branches. Remove any items from the surfaces of the termination prior to use. Also be aware of shrubs and plantings that may encroach on the termination.
Inspecting the burner flame appearance
Periodically inspect the burner and pilot flame. Ensure that the burner flame appearance resembles the flame shown in Figure 39 and Figure 40 on Page 39 and as described in Flame Appearance and Sooting on Page 38. Any necessary burner flame adjustments must be performed by qualified personnel only (Page 38). Refer to Page 37 for more information about the pilot flame appearance. Contact a qualified service technician at once if any abnormal condition is observed.
Cleaning the glass door
CAUTION
Do not use abrasive cleaners on glass. Never clean the glass when it is hot.
Clean the glass during the Burn-in Period, and then only when necessary and when the fireplace is cool. Wipe the surface with a clean, dampened, soft cloth. Follow with a dry, soft towel as desired. Take care not to scratch the glass surface. Periodically, remove any build-up caused by the following:
s During start-up, it is normal for condensation to form on the inside of the glass (this condensation and fog will
usually disappear in a few minutes). The moisture can cause lint, dust and other airborne particles to cling to the glass surface.
s Initial curing of the high temperature paint and burning off of lubricants used in the manufacturing process may
result in a film on the glass.
s A white coating may form on the glass as a result of impurities and minerals in the fuel. Clean the glass two or three times each heating season, depending on the circumstances present. The following
cleaning solutions are approved for use:
s Non-ammonia based glass cleaner s 50/50 mixture of white vinegar / water s Gas fireplace/stove glass cleaner
Page 58
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
58
Inspecting the glass gasket
Visually inspect the gasket on the backside of the glass door. The gasket surface must be clean, free of irregularities, and seated firmly.
Cleaning the control compartment
Keep the control compartment clean by vacuuming or brushing it out at least twice a year. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
Touching up paint in small areas
Only use a factory-supplied paint kit for any touch-ups. Paint is available at your local IHP dealer. Never attempt to paint a hot fireplace. Do not attempt to repaint the fireplace until the finish is completely cured (Burn-in Period on
Page 50). If the surface becomes stained or marred, it may be lightly sanded and touched up.
Logs
Removing and cleaning the logs
CAUTION
The fiber logs become very fragile after curing.
Carefully remove the logs. Clean carbon from the logs using a vacuum cleaner, or a soft bristle brush (e.g., paint brush).
Reinstalling the embers and logs
Carefully follow the placement instructions (Page 52). All logs should fit onto the corresponding pins and/or log stoppers. This will ensure proper flame and safe combustion.
NOTE: Improper positioning of logs can create carbon build-up and will alter the performance of the fireplace.
Replacing the logs
If the logs become damaged and need replacement, use only the proper replacement logs from manufacturer (Page 70).
Page 59
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
59
Glass Media
Removing and cleaning the glass media
CAUTION
Risk of personal injury. Allow the media to completely cool before handling.
Use a clean, dry, empty shop vac to remove glass media. Wash the media in warm, soapy water. Rinse and dry before reinstalling.
Reinstalling the glass media
Carefully follow the placement instructions (Page 51). This will ensure a proper flame and safe combustion. NOTE: Improper positioning of media can create carbon build-up and will alter the performance of the fireplace.
Replacing the media
If the media needs replacement, use only the proper replacement media from manufacturer (Page 70).
Cleaning the burner
Carefully remove the logs/media. Vacuum out any foreign matter on the burner (e.g., lint, carbon, etc.). Ensure the burner ports are free of debris.
NOTE: Improper positioning of logs/media can create carbon build-up and will alter the performance of the fireplace.
Inspecting the wiring
Refer to the wiring diagram (Figure 31 and Figure 32).
CAUTION
When servicing controls, label all wires prior to disconnection. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
ATTENTION
Au moment de l’entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de cáblage peuvent entraîner un fonctionnement inadéquat et dangereux.
Inspect and clean all wire connections. Ensure that there is no wire melting or damage. The inspection should include:
s Terminals at the valve s ON/OFF switch s Optional wall thermostat, remote control, or wall switch
Page 60
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
60
MAINTENANCE SCHEDULE
See the tables below for detailed information about required maintenance, both regular and annual.
Tabl e 39: Maintenance Performed Annually—Before the Burning Season
Maintenance Task Performed By Procedure
Inspecting/Cleaning Burner, Logs and Controls
Qualified Service Technician Inspect valve and ensure it is properly
operating. Check piping for leaks. Vacuum the control compartment, fireplace logs and burner area.
Checking Flame Patterns and Flame Height
Qualified Service Technician Verify the flame pattern and height displayed
by the fireplace (Figure 39 and Figure 40). Flames must not impinge on the logs.
Inspecting/Cleaning Pilot and Burner Qualified Service Technician Remove any surface build-up on pilot and
burner assembly. Wipe the pilot nozzles, igniter/flame rod and hood. Ensure the pilot flame engulfs the flame sensor as shown.
Checking Vent System Qualified Service Technician Inspect the vent system at the top and at
the base (within the firebox) for signs of blockage or obstruction. Look for any signs of dislocation of the vent components.
Fireplace Inspection Qualified Service Technician Perform the appropriate fireplace inspection
procedure detailed in this manual.
Replacing Glowing Embers Homeowner/Qualified Services Technician Remove the old glowing embers and
vacuum the area. Place new glowing embers (Figure 49).
Replacing Batteries Homeowner/Qualified Services Technician For electronic gas valve models:
Replace the batteries in the battery holder.
Tabl e 40: Maintenance Performed Periodically—After the Burning Season
Maintenance Task Performed By Procedure
Cleaning Firebox Interior Homeowner Carefully remove logs, volcanic stone and
glowing embers / glass media. Vacuum out interior of the firebox. Clean firebox walls and log grate, if installed. Replace removed items as detailed in this manual.
Check Flame Patterns and Flame Height Homeowner Verify the flame pattern and height displayed
by the fireplace (Figure 39 and Figure 40). Flames must not impinge on the logs.
Checking Vent System Homeowner Inspect the vent system at the top and at
the base (within the firebox) for signs of blockage or obstruction. Look for any signs of dislocation of the vent components.
Cleaning Glass Door Homeowner Clean as necessary following the directions
provided in this manual (Page 57). Do not touch or attempt to clean the glass while hot.
Page 61
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
61
ACCESSORY COMPONENTS Touch-Up Paint Kits
Repair minor scratches and discoloration of the fireplace black painted surfaces with the touch-up paint kits.
Tabl e 41: Touch -U p Pa in t Kit
Catalog No. Description
F1881 Firebox interior touch-up paint F1882 Chassis touch-up paint
Forced Air Kits
The FBK-100 blower provides constant velocity forced air circulation. The FBK-200 assembly with variable speed, wall-mountable switch provides variable speed forced air circulation. The FBK-250 offers variable speed control and a heat-activated switch; perfect for fireplaces controlled thermostatically.
Tabl e 42: Forced Air Kits
Catalog Model Description
80L84 FBK-100 Blower, Standard (single speed) 80L85 FBK-200 Blower, Variable Speed (with wall-mounted switch) 80L86 FBK-250 Blower, Variable Speed (with thermal snap switch)
Glowing Embers and Volcanic Stone
Order kits as part of the periodic maintenance of the fireplace.
Tabl e 43: Glowing Embers and Volcanic Stone
Catalog Model Description
88L53 FGE Bag of Glowing Embers 80L42 FDVS Bag of Volcanic Stone
Glass Media
Tabl e 44: Glass Media
Catalog Model Description
H8412 CRSHGL-RBLK Bag of Glass Media, Reflective Black
Brickaded Firebox Liner Kits
Tabl e 45: Brickaded Firebox Liner Kits
Catalog Model Description Used on
F1887 MBLK33B Buff DRC2033 / DRT2033 F1827 MBLK35B Buff DRC2035 / DRT2035 F1828 MBLK40B Buff DRC2040 / DRT2040 F1889 MBLK45B Buff DRC2045 / DRT2045
Termination Guard Kits
The vent termination guards may be used to cover the vent termination on the exterior of the home to minimize exposure to the hot surface of the termination.
Tabl e 46: Termi na ti on G ua rd Ki ts
Square
Termination
Guard
(fits 94L10
and H1968)
Deluxe
Termination
Guard
(fits 94L10
and H1968)
Termination
Shroud
(fits H1968)
Catalog Model Description
H5820 4.5HTSK Termination Shroud
87L02 SV4.5HGS Termination Guard, Deluxe
17M52 SV4.5HGS-1 Termination Guard, Square
Thermostatic Control Kits
Page 62
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
62
Feature a thermostatic ON/OFF mode as well as manual ON/OFF operation.
Tabl e 47: Thermostatic Control Kits
RC-S-STAT, Thermostatic or manual operation Catalog Number
s LCD display s Receiver wall-mounted or placed in the
valve compartment
s Up to 9-hr countdown timer
s Child lock s Low battery indicator s Batteries included
H8861
RC-S-Touch, State-of-the-art control with touch screen operation Catalog Number
s Backlit LCD display s Transmitter wall-mounted docking station s Receiver wall-mounted or placed in the
control compartment
s Thermostatic or manual ON/OFF operation
s Programmable weekday/
weekend modes
s Flame icon s Low battery indicator s Batteries included
H8865
WS-S-STAT, Wall control Catalog Number
s Large LCD display s Shows room and set temperatures in
°F and °C
s Wall-mounted
s Thermostatic or manual
ON/OFF operation
s Connects to wall
switch wire
H8864
ON/OFF and Timer Control Kits
Feature a timed ON/OFF mode as well as manual ON/OFF operation.
Tabl e 48: ON/OFF and Timer Control Kits
G-Fire, Cost Effective Solution Catalog Number
s Manual ON/OFF operation s Works with millivolt and low voltage
electronic ignition controls
s Kit includes remote and receiver
H8840
RC-S-1, Manual or up to 3-hour timer modes Catalog Number
s LCD display s Shows room temperature in °F and °C s Wall clip included s Receiver wall-mounted or placed in the
control compartment
s White face plate included s Flame icon s Low battery indicator s Batteries included
H8860
WS-S-TMR, Wall Control Catalog Number
s 4-button timer with 30/60/120/OFF minutes s Wall-mounted s Perfect for rental and resort applications s Connects to wall switch wire
H8863
Page 63
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
63
Unit-Mountable Rocker Switch Kit
This rocker switch kit can be installed directly in the control compartment to provide ON/OFF operation in lieu of a wall switch.
Tabl e 49: Unit-Mountable Rocker Switch
Catalog Model
80L41 FRS
OFF/ON Wall Switch Kit
The OFF/ON wall switch kit can be used to control the operation of the fireplace burner or blower. Install the OFF/ON wall switch in a convenient location near the fireplace.
Tabl e 50: OFF/ON Wall Switch Kit
Catalog Model
85L87 FWSK
Variable Speed Wall Switch Kit
The variable speed wall switch kit provides variable speed control if the optional FBK-100 blower kit is installed.
Tabl e 51: Variable Speed Wall Switch Kit
Catalog Model
045571H VSWS
Page 64
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
64
LIGHTING INSTRUCTIONS Millivolt Gas Valve
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result, causing property damage, personal injury, or loss of life.
A.
This appliance has a pilot which must be lighted by a piezo igniter. When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for gas. Be
sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
s Do not try to light any appliance. s Do not touch any electric switch; do not use any phone in your building. s Immediately call your gas supplier from a neighbor’s phone. Follow
the gas supplier’s instructions.
s If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never
use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above on this page.
2. (If applicable) Set the thermostat to lowest setting. Turn wall on/off
switch, unit mounted on/off switch or remote control switch OFF.
3. Turn OFF all electric power to the appliance.
4. Access the control compartment.
5. Push in gas control knob slightly and turn clockwise to OFF.
6. Knob cannot be turned from PILOT to OFF unless knob is pushed in
slightly. Do Not force.
7. Wait five (5) minutes to clear out any gas. Then smell for gas,
including near the floor. If you smell gas, STOP! Follow B in the safety information above on this page. If you don’t smell gas, go to the next step.
8. Find pilot — located in firebox on the same plane as the top of the
burner.
9. Turn knob on gas control counterclockwise to PILOT
10. Push in control knob all the way and hold in. Immediately light the
pilot by triggering the piezo igniter (pushing the button) until pilot lights. Continue to hold the control knob in for about 1 1/2 minutes after the pilot is lit. Release knob and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 10.
s If knob does not pop up when released, stop and immediately
call your service technician or gas supplier.
s If the pilot will not stay lit after several tries, turn the gas
control knob to OFF, and call your service technician or gas supplier.
11. Turn gas control knob counterclockwise to ON.
12. Close control compartment.
13. (If applicable) Turn on all electrical power to the appliance.
14. (If applicable) Set thermostat to desired setting. Turn wall on/off
switch, unit mounted on/off switch or remote control switch ON.
H
I
L
O
W
TPTH TP TH
P
I
L
O
T
P
I
L
O
T
O
N
it
O
F
F
OUT
IN
Gas Control Valve Pilot Assembly
Gas control knob
TO TURN OFF GAS TO APPLIANCE
1. (If applicable) Set the thermostat to lowest setting. Turn wall on/off
switch, unit mounted on/off switch or remote control switch OFF.
2. Turn OFF all electric power to the appliance if service is to
be performed.
3. Access the control compartment.
4. Push in gas control knob slightly and turn clockwise to OFF.
Do not force.
5. Close the main line gas shut-off valve.
6. Close control compartment.
WARNING
Hot glass will cause burns. Do not touch glass until cooled. Never allow children to touch glass.
Page 65
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
65
POUR PLUS DE SÉCURITÉ, LIRE AVANT D’ALLUMER
AVERTISSEMENT : Quiconque ne respecte pas à la lettre les instructions dans la présente notice risque de déclencher un incendie ou une explosion entraînant des dommages, des blessures ou la mort.
A.
Cet appareil est muni d’une veilleuse qui doit être allumée avec un allumeur piézo-électrique. Respectez les instructions ci-dessous à la lettre.
B. AVANT L’ALLUMAGE: Avant d’allumer la veilleuse, reniflez tout
autour de l’appareil pour déceler une odeur de gaz. Reniflez près du plancher, car certains gaz sont plus lourds que l’air et peuvent s’accumuler au niveau du sol.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
s Ne pas tenter d’allumer d’appareil. s Ne touchez à aucun interrupteur ; ne pas vous servir des téléphones
se trouvant dans le bâtiment.
s Appelez immédiatement votre fournisseur de gaz depuis un voisin.
Suivez les instructions du fournisseur.
s Si vous ne pouvez rejoindre le fournisseur, appelez le service des incendies.
C. Ne pousser ou tourner la manette d’admission du gaz qu’à la
main. Ne jamais employer d’outil à cette fin. Si la manette reste coincée, ne tentez pas de la réparer; appelez un technicien qualifié. Quiconque tente de forcer la manette ou de la réparer peut provoquer une explosion ou un incendie.
D. N’utilisez pas cet appareil s’il a été plongé dans l’eau, même
partiellement. Faites inspecter l’appareil par un technicien qualifié et remplacez toute partie du système de contrôle et toute commande qui ont été plongés dans l’eau.
INSTRUCTIONS D’ALLUMAGE
1. ARRÊTEZ ! Lisez les instructions de sécurité sur la portion
supérieure de cette étiquette.
2. (Si applicable) Réglez le thermostat à la température la plus basse.
Tournez l’interrupteur murale, l’interrupteur sur l’unité ou le contrôle à distance à OFF.
3. Coupez l’alimentation électrique de l’appareil.
4. Accédez au compartiment de contrôle.
5. Enfoncez légèrement le bouton de réglage du gaz et tournez-le dans
le sens des aiguilles d’une montre jusqu’à la position d’arrêt
OFF. Remarque: Il est impossible de tourner le bouton de PILOT à OFF à moins qu’il ne soit légèrement enfoncé. Ne le forcez pas.
6. Attendre cinq (5) minutes pour laisser échapper tout le gaz. Reniflez
tout autour de l’appareil, y compris près du plancher, pour déceler une odeur de gaz. Si vous sentez une odeur de gaz, ARRÊTEZ ! Passez à l’étape B des instructions de sécurité sur la portion supérieure de cette étiquette. S’il n’y a pas d’odeur de gaz, passez à l’étape suivante.
7. Trouver le pilote — Situé dans l’âtre sur la même surface que le
dessus du brûleur.
8. Tournez le bouton de contrôle sur la valve à gaz dans le sens
antihoraire vers PILOT.
9. Enfoncez le bouton de réglage jusqu’au fond et gardez-le enfoncé.
Allumez immédiatement la veilleuse en déclenchant l’allume-gaz à étincelle (en poussant le bouton) jusqu’à ce que la veilleuse s’enflamme. Continuez de tenir le bouton de réglage enfoncé pendant environ 90 secondes après l’allumage de la veilleuse. Relâchez le bouton et il sortira subitement. La veilleuse devrait rester allumée. Si elle s’éteint, répétez les étapes 5 à 9 inclusivement.
s Si la manette ne se soulève pas d’elle-même lorsqu’on la
relâche, arrêter et appeler immédiatement un technicien qualifié ou le fournisseur de gaz.
s Si la veilleuse ne reste pas allumée après plusieurs tentatives,
réglez la manette d’admission du gaz à la position OFF, et appelez un technicien qualifié ou le fournisseur de gaz.
10. Tournez le bouton de réglage du gaz en sens inverse des aiguilles
d’une montre jusqu’à sa position de marche ON.
11. Fermer le compartiment de contrôle.
12. (Si applicable) Mettez l’appareil sous tension.
13. (Si applicable) Réglez le thermostat à la température désirée.
Tournez l’interrupteur murale, l’interrupteur sur l’unité ou le contrôle à distance à ON.
H
I
L
O
W
TPTH TP TH
P
I
L
O
T
P
I
L
O
T
O
N
it
O
F
F
OUT
IN
Vanne Gaz Millivolt Millivolt Pilot
Bouton de réglage
du gaz
COMMENT COUPER L’ADMISSION DE GAZ DE L’APPAREIL
1. (Si applicable) Réglez le thermostat à la température la plus basse.
Tournez l’interrupteur murale, l’interrupteur sur l’unité ou le contrôle à distance à OFF.
2. Coupez l’alimentation électrique de l’appareil s’il faut procéder à
l’entretien.
3. Accédez au compartiment de contrôle.
4. Enfoncez légèrement le bouton de réglage du gaz et tournez-le
dans le sens des aiguilles d’une montre jusqu’à la position d’arrêt OFF. Ne forcez pas le bouton.
5. Fermer la valve de gaz principale.
6. Fermer le compartiment de contrôle.
AVERTISSEMENT
UNE SURFACE VITRÉE CHAUDE PEUT CAUSER DES BRÛLURES. LAISSER REFROIDIR LA SURFACE VITRÉE AVANT D’Y TOUCHER. NE PERMETTEZ JAMAIS À UN ENFANT DE TOUCHER LA SURFACE VITRÉE.
Page 66
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
66
Electronic Gas Valve
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result, causing property damage, personal injury, or loss of life.
A. This appliance is equipped with an ignition device which
automatically lights the pilot. Do not try to light the pilot by hand.
B. BEFORE OPERATING smell all around the appliance area for gas. Be
sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
s Do not try to light any appliance. s Do not touch any electric switch; do not use any phone in your building. s Immediately call your gas supplier from a neighbor’s phone. Follow the
gas supplier’s instructions.
s If you cannot reach your gas supplier, call the fire department.
C. If any portion of this appliance does not operate as the instructions
indicate, do not try to repair it, call a qualified service technician. Do not use tools. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above on this label.
2. Read the Care and Operation manual including the section on
“Remote Control System,” (if applicable).
3. Slide the switch on the receiver, wall switch or ON/OFF switch to OFF.
4. Turn OFF all electric power to the appliance.
NOTE: The control may have a battery backup (remove batteries, if installed).
5. This appliance is equipped with an ignition device which
automatically lights the pilot. Do not try to light the pilot by hand.
6. Wait five (5) minutes to clear out any gas. If you then smell gas,
STOP! Follow B in the safety information above on this page. If you do not smell gas, go to the next step.
7. Turn on all electric power to the appliance.
NOTE: The control may have a battery backup (install batteries, if applicable).
8. Slide the switch on the receiver to REMOTE or ON/OFF switch / wall
switch to ON.
9. (if applicable) Press ON/OFF button on remote control transmitter to ON.
10. (if applicable) Set thermostat on remote control to desired setting.
11. If the appliance will not operate, follow the instructions “To Turn Off
Gas To Appliance” and call your service technician or gas supplier.
Electronic Pilot Assembly
Electronic Gas Control
Valve—SIT
Electronic gas control valve
Electronic pilot assembly
TO TURN OFF GAS TO APPLIANCE
1. Slide the switch on the receiver, wall switch or ON/OFF switch to OFF.
2. (if applicable) Press ON/OFF button on remote control transmitter
to OFF.
3. Turn off all electric power to the appliance if service is to be
performed.
NOTE: The control may have a battery backup (remove batteries, if installed).
4. Close the main line gas shut-off valve.
WARNING
Hot glass will cause burns. Do not touch glass until cooled. Never allow children to touch glass.
Page 67
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
67
POUR PLUS DE SÉCURITÉ, LIRE AVANT DE METTRE EN MARCHE
AVERTISSEMENT : Quiconque ne respecte pas à la lettre les instructions dans la présente notice risque de déclencher un incendie ou une explosion entraînant des dommages, des blessures ou la mort.
A.
Cet appareil est muni d’un dispositif d’allumage qui allume automatiquement la veilleuse. Ne tentez pas d’allumer la veilleuse manuellement.
B. AVANT DE FAIRE FONCTIONNER, reniflez tout autour de l’appareil
pour déceler une odeur de gaz. Reniflez près du plancher, car certains gaz sont plus lourds que l’air et peuvent s’accumuler au niveau du sol.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
s Ne pas tenter d’allumer d’appareil. s Ne touchez à aucun interrupteur; ne pas vous servir des téléphones
se trouvant dans le bâtiment.
s Appelez immédiatement votre fournisseur de gaz depuis un voisin.
Suivez les instructions du fournisseur.
s Si vous ne pouvez rejoindre le fournisseur, appelez le service
des incendies.
C. Si un élément de cette unité ne fonctionne pas tel que décrit dans
les instructions, n’essayez pas de le réparer, appelez un technicien qualifié. N’utilisez-pas d’outils. Le fait de forcer la manette ou de la réparer peut déclencher une explosion ou un incendie.
D. N’utilisez pas cet appareil s’il a été plongé dans l’eau, même
partiellement. Faites inspecter l’appareil par un technicien qualifié et remplacez toute partie du système de contrôle et toute commande qui ont été plongés dans l’eau.
INSTRUCTIONS DE MISE EN MARCHE
1. ARRÊTEZ ! Lisez les avertissements de sécurité à l’endos de
cette étiquette.
2. Lisez le manuel d’utilisation et d’entretien incluant la section
« Système de télécommande » (si applicable).
3. Placez l’interrupteur mural ou “on/off” en position OFF.
4. Coupez l’alimentation électrique de l’appareil.
Remarqué : Le contrôleur peut avoir une batterie de secours (retirer les
batteries au besoin).
5. Cet appareil est muni d’un dispositif d’allumage qui allume
automatiquement la veilleuse. Ne tentez pas d’allumer la veilleuse manuellement.
6. Attendre cinq (5) minutes** pour laisser échapper tout le gaz.
Reniflez tout autour de l’appareil, y compris près du plancher, pour déceler une odeur de gaz. Si vous sentez une odeur de gaz, ARRÊTEZ ! Passez à l’étape B des instructions de sécurité sur la portion supérieure (à gauche) de cette étiquette. S’il n’y a pas d’odeur de gaz, passez à l’étape suivante.
7. Mettez l’appareil sous tension.
Remarqué : Le contrôleur peut avoir une batterie de secours (installer les
batteries au besoin).
8. Placez l’interrupteur du récepteur en position REMOTE (ou
l’interrupteur mural en position ON).
9. Si applicable) Appuyez sur le bouton “ON/OFF” pour
sélectionner ON.
10. (Si applicable) Ajustez le thermostat sur la télécommande à
l’ajustement désiré.
11. Si l’appareil ne se met pas en marche, suivez les instructions
intitulées «Comment couper l’admission de gaz de l’appareil » et appelez un technicien qualifié ou le fournisseur de gaz.
Electronic Pilot Assembly
Electronic Gas Control
Valve—SIT
Valve électronique
Module de veilleuse
électronique
COMMENT COUPER L’ADMISSION DE GAZ DE L’APPAREIL
1. Placez l’interrupteur mural ou “on/off” en position OFF.
2. (Si applicable) Sélectionnez OFF sur le récepteur.
3. Coupez l’alimentation électrique de l’appareil s’il faut procéder à
l’entretien.
Remarqué : Le contrôleur peut avoir une batterie de secours (retirer les batteries au besoin).
4. Fermer la valve de gaz principale.
AVERTISSEMENT
UNE SURFACE VITRÉE CHAUDE PEUT CAUSER DES BRÛLURES. LAISSER REFROIDIR LA SURFACE VITRÉE AVANT D’Y TOUCHER. NE PERMETTEZ JAMAIS À UN ENFANT DE TOUCHER LA SURFACE VITRÉE.
Page 68
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
68
TROUBLESHOOTING
Before troubleshooting, ensure that the fireplace main line gas shutoff valve and the wall switch are in the ON position. The following troubleshoots the fireplace only to an elementary level. For detailed remote and ignition system troubleshooting, refer to the instructions provided with the remote.
Detailed valve system troubleshooting should only be performed by a qualified service technician.
Tabl e 52: Troub le sh oo ti ng Mill iv ol t Sy st em s
1. Spark igniter will
not light pilot after repeated triggering of igniter button.
WARNING: if the pilot will not light after 1 minute of attempting, wait for at least 5 minutes for gas to clear before attempting again.
a. Defective igniter (no spark at electrode). Check for spark at electrode and pilot; if no spark and
electrode wire is properly connected, replace igniter.
b. Defective or misaligned electrode at pilot
(spark at electrode).
Using a match, light pilot. If pilot lights, turn off pilot and trigger the igniter button again. If pilot lights, an improper gas mixture caused the bad lighting and a longer purge period is recommended. If pilot will not light – check gap at electrode and pilot – should be 1/8” to have a strong spark. If gap measures 1/8”, replace pilot.
c. Gas supply pressure errant. Check inlet gas pressure. It should be within the limits
as marked on the rating plate.
d. Pilot orifice plugged. Clean or replace pilot orifice.
2. Pilot will not stay
lit after carefully following the lighting instructions.
a. Defective pilot generator (thermocouple). Check pilot flame, it must impinge on thermocouple.
Clean and/or adjust pilot for maximum flame impingement on thermocouple. Ensure that the connection between the valve and thermocouple are tight and secure.
3. Pilot burning, no
gas to burner, Valve knob “ON,” and the (standard) burner OFF/ON switch is ON.
NOTE: If an optional* remote switch is used for burner operation, if the standard burner OFF/ON switch is still installed on fireplace it must be in the OFF position.
a. Wall switch or wires defective. Check wall switch and wires for proper connections.
Jumper wire across terminals at wall switch, if burner comes on, replace defective wall switch. If okay, jumper wires across wall switch wires at valve, if burner comes on, wires are faulty or connections are bad.
b. Thermopile may not be generating
sufficient millivolts.
Check thermopile with millivolt meter. Take reading at thermopile terminals of gas valve. Should read 325 millivolts minimum with optional wall switch OFF. Replace faulty thermopile if reading is below specified minimum.
c. Plugged burner orifice. Check burner orifice for blockage and remove. d. OFF/ON Switch and *Remote Switch are
in the “ON” position resulting in excessive resistance.
When turning on the burner using a *remote switch, ensure that the standard OFF/ON switch is in the OFF position. If both switches are in the ON position, it may result in excessive resistance (and millivolt drainage) and the burner may not come on.
4. Frequent pilot/burner
outage problem.
a. Pilot flame may be too low or blowing
(high) causing the pilot/valve safety to drop out.
Clean and/or adjust pilot flame for maximum flame impingement on thermocouple
* Optional remote switch kits—wall switch, wall thermostat or remote control.
Page 69
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
69
Tabl e 53: Troub le sh oo ti ng Elec tr on ic S ys te ms
1. Nothing happens
when the fireplace is turned ON/OFF.
a. Remote is not functioning properly. Check that the wall switch plate is set to REMOTE.
Operate the fireplace from the wall plate switch. Replace remote and/or wall switch batteries.
b. Gas is not reaching the fireplace. Check the gas supply and gas shutoff valves. * c. Unit is not receiving power. Check/replace backup batteries behind the wall plate.
Replace unit battery backup. Check building circuit breakers to ensure power is ON
to the fireplace.
2. The main burner
does not light and the igniter is sparking.
a. Gas is not reaching the fireplace. Check the gas supply and gas shutoff valves. b. Loose wires to the valve. Check control compartment for any obviously loose
wiring (call a service technician, if necessary).
c. Loose wires to ignition module. Check control compartment for any obviously loose
wiring (call a service technician, if necessary).
d. Air in the gas line. Purge gas line of air (call a service technician if
required).
e. Unit is not receiving power. Replace unit battery backup.
3. The main Burner
comes on but then goes out.
a. Gas is not reaching the fireplace. Check the gas supply and gas shutoff valves. b. Loose wires to the valve or ignition
module.
Check control compartment for any obviously loose wiring (call a service technician, if necessary).
c. Pilot flame is not engulfing the sensor. Call a service technician. d. Obstructed vent system. Call a service technician.
4. Soot is present on the
logs and glass.
a. Excessive flame impingement on the logs. Properly position the logs as detailed on Page 52. b. Initial fireplace operation. A white film may develop on the glass during the first
few fires as part of the burn-in process. The first few times you use the fireplace, clean
the glass after each use (AFTER THE GLASS HAS COMPLETELY COOLED); otherwise, the white film will bake onto the glass and become difficult to remove.
See glass cleaning instructions in the MAINTENANCE section of this manual.
c. Improper vent restrictor setting. Open the air shutter by adjusting the air shutter
adjustment lever according to the instructions in this manual.
d. Improper air shutter opening. Open the air shutter by pushing in the rod.
5. Poor flame and/or
blue flame.
a. Door seal is not properly aligned, causing
gaps and air leaks.
Remove and realign the door so the gasket seal is fully engaged around the door frame.
*The unit may have multiple gas supply shutoffs (the main gas supply valve in the house, the gas supply valve in the fireplace control compartment, and/or an additional shutoff valve near the fireplace).
Page 70
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
70
REPLACEMENT PARTS
Tabl e 54: Installer Replacement Parts
Description
DRC2033 / DRT2033 DRC2035 / DRT2035 DRC2040 / DRT2040 DRC2045 / DRT2045
Catalog
Number
Qty
Catalog Number
Qty
Catalog
Number
Qty
Catalog Number
Qty
1 Tou ch -U p Pa in t 90L73 1 90L73 1 90L73 1 90L73 1 2 Blower Assembly 80L84 1 80L84 1 80L84 1 80L84 1 3 Volcanic Stone 80L42 1 80L42 1 80L42 1 80L42 1 4 Electronic Pilot Assembly, Natural Gas H7268 1 H7268 1 H7268 1 H7268 1 5 Electronic Pilot Assembly, Liquid Propane H7269 1 H7269 1 H7269 1 H7269 1 6 Electronic DFC Wire Harness Assembly H8601 1 H8601 1 H8601 1 H8601 1 7 Electronic DFC Ignition Board H7272 1 H7272 1 H7272 1 H7272 1 8 Electronic Power Transformer H8006 1 H8006 1 H8006 1 H8006 1 9 Electronic Battery Holder (for backup batteries) H8803 1 H8803 1 H8803 1 H8803 1 10 Electronic Ground Wire H7278 1 H7278 1 H7278 1 H7278 1 11 Electronic ON/OFF Switch 27K30 1 27K30 1 27K30 1 27K30 1 12 Electronic Control Module H7272 1 H7272 1 H7272 1 H7272 1 13 Millivolt Pilot Assembly, Natural Gas 69L17 1 69L17 1 69L17 1 69L17 1 14 Millivolt Pilot Assembly, Liquid Propane 69L18 1 69L18 1 69L18 1 69L18 1 15 Millivolt Piezo Igniter 10K86 1 10K86 1 10K86 1 10K86 1 16 Millivolt Piezo Igniter Wire 56L21 1 56L21 1 56L21 1 56L21 1 17 Millivolt Pilot Generator 60J79 1 60J79 1 60J79 1 60J79 1 18 Millivolt Thermocouple 74L57 1 74L57 1 74L57 1 74L57 1 19 Millivolt Pilot Tube 74L56 1 74L56 1 74L56 1 74L56 1 20 MIllivolt Electrode and Cable H6212 1 H6212 1 H6212 1 H6212 1 21 Orifice Holder H7257 1 H7257 1 H7257 1 H7257 1 22 Gas Flex Line Connector 93L32 1 93L32 1 93L32 1 93L32 1 23 Gas Valve, Electronic, Natural Gas F1831 1 F1831 1 F1831 1 F1831 1 24 Gas Valve, Electronic, Liquid Propane F1832 1 F1832 1 F1832 1 F1832 1 25 Gas Valve, Millivolt, Natural Gas F1833 1 F1833 1 F1833 1 F1833 1 26 Gas Valve, Millivolt, Liquid Propane F1834 1 F1834 1 F1834 1 F1834 1 27 Contemporary Burner Assembly F1843 1 F1843 1 F1843 1 F1904 1 28 Tra di ti on al B ur ne r As se mb ly F1843 1 F1843 1 F1844 1 F1843 1 29 Vent Restrictor Base H8987 1 H8987 1 H8987 1 H8987 1 30 Vent Restrictor Wing H8988 1 H8988 1 H8988 1 H8988 1 31 Gas Train Assembly Gasket H1264 2 H1264 2 H1264 2 H1264 2 32 Door Latch Assembly H1264 2 H1264 2 H1264 2 H1264 2 33 Brass Orifice, Female—Natural Gas LB-69547 1 21L8201 1 99K7401 1 19L5201 1 34 Brass Orifice, Female—Liquid Propane 35M9101 1 100934-08 1 62L3701 1 60J8001 1 35 Assembly Harness, Control H8601 1 H8601 1
H8601 1 H8601 1 36 Glass Media, 5 lb bag—Reflective Black H8412 1 H8412 1 H8412 1 H8412 1 37 Logset F1883 1 F1829 1 F1830 1 F1884 1
Page 71
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
71
Figure 59: Replacement Parts
Back view not
representative of all
fireplace models
38
27
28
23
24
25
26
41
37
40
39
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
WARNING
Never use substitute materials. Use of non-approved parts can result in poor performance and safety hazards.
Tabl e 55: Homeowner Replacement Parts
Description
DRC2033 / DRT2033 DRC2035 / DRT2035 DRC2040 / DRT2040 DRC2045 / DRT2045
Catalog
Number
Qty
Catalog
Number
Qty
Catalog
Number
Qty
Catalog
Number
Qty
38 Hood F1900 1 F1837 1 F1838 1 F1901 1 39 Barrier F1902 1 F1839 1 F1840 1 F1903 1 40 Glass Door F1905 1 F1841 1 F1842 1 F1906 1 41 Control Compartment Door F1898 1 F1835 1 F1836 1 F1899 1 42 Tou ch -U p Pa in t FTPK-B 1 FTPK-B 1 FTPK-B 1 FTPK-B 1 43 Glowing Embers 88L53 1 88L53 1 88L53 1 88L53 1 44 Volcanic Stone 80L42 1 80L42 1 80L42 1 80L42 1
Page 72
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
72
WARRANTY
Innovative Hearth Products
Superior™ Brand Gas Fireplaces, Stoves and Inserts
20 Year Limited Warranty
THE WARRANTY
Innovative Hearth Products (“IHP”) 20 Year Limited Warranty warrants your Superior™ Brand gas fireplace, Stove or Insert (“Product”) to be free from defects in materials and workmanship at the time of manufacture. The Product body and firebox carry the 20 Year Limited Warranty. Ceramic glass carries the 20 Year Limited Warranty against thermal breakage only. After installation, if covered components manufactured by IHP are found to be defective in materials or workmanship during the 20 Year Limited Warranty period and while the Product remains at the site of the original installation, IHP will, at its option, repair or replace the covered components. If repair or replacement is not commercially practical, IHP will, at its option, refund the purchase price or wholesale price of the IHP product, whichever is applicable. IHP will also pay IHP prevailing labor rates, as determined in its sole discretion, incurred in repairing or replacing such components for up to five years. THERE ARE EXCLUSIONS AND LIMITATIONS to this 20 Year Limited Warranty as described herein.
COVERAGE COMMENCEMENT DATE
Warranty coverage begins on the date of installation. In the case of new home construction, warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the Product by an independent IHP dealer/distributor, whichever occurs earlier. The warranty shall commence no later than 24 months following the date of product shipment from IHP, regardless of the installation or occupancy date.
EXCLUSIONS AND LIMITATIONS
This 20 Year Limited Warranty applies only if the Product is installed in the United States or Canada and only if operated and maintained in accordance with the printed instructions accompanying the Product and in compliance with all applicable installation and building codes and good trade practices.
This warranty is non-transferable and extends to the original owner only. The Product must be purchased through a listed supplier of IHP and proof of purchase must be provided. The Product body and firebox carry the 20 Year Limited Warranty from the date of installation. Vent components, trim components and paint are excluded from this 20 Year Limited Warranty. The following do not carry the 20 Year Limited Warranty but are warranted as follows:
Burner – Repair or replacement for one year from the date of installation Gas components – Repair or replacement for one year from the date of installation Gaskets – Repair or replacement for one year from the date of installation Logs – Replacement for one year from the date of installation against thermal breakage only Optional blowers & remote controls – Repair or replacement for one year from the date of installation Optional glass doors – Repair or replacement for 90 days from the date of installation Tempered Glass -Replacement for one year from the date of installation Labor coverage – Prevailing IHP labor rates apply for the warranty period of the component
Parts not otherwise listed carry a 90 day warranty from the date of installation. Whenever practicable, IHP will provide replacement parts, if available, for a period of 10 years from the last date of manufacture of the Product.
IHP will not be responsible for: (a) damages caused by normal wear and tear, accident, riot, fire, flood or acts of God; (b) damages caused by abuse, negligence, misuse, or unauthorized alteration or repair of the Product affecting its stability or performance (The Product must be subjected to normal use. The Product is designed to burn either natural or propane gas only. Burning conventional fuels such as wood, coal or any other solid fuel will cause damage to the Product, will produce excessive temperatures and could result in a fire hazard.); (c) damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product; (d) damages, repairs or inefficiency resulting from faulty installation or application of the Product.
IHP is not responsible for inadequate fireplace system draft caused by air conditioning and heating systems, mechanical ventilation systems, or general construction conditions which may generate negative pressure in the room in which the appliance is installed. Additionally IHP assumes no responsibility for drafting conditions caused by venting configurations, adjoining trees or buildings, adverse wind conditions or unusual environmental factors and conditions that affect the operation of the unit.
This 20 Year Limited Warranty covers only parts and labor as provided herein. In no case shall IHP be responsible for materials, components or construction, which are not manufactured or supplied by IHP or for the labor necessary to install, repair or remove such materials, components or construction. Additional utility bills incurred due to any malfunction or defect in equipment are not covered by this warranty. All replacement or repair components will be shipped F.O.B. from the nearest stocking IHP factory.
LIMITATION ON LIABILITY
It is expressly agreed and understood that IHP’s sole obligation and the purchaser’s exclusive remedy under this warranty, under any other warranty, expressed or implied, or in contract, tort or otherwise, shall be limited to replacement, repair, or refund, as specified herein.
In no event shall IHP be liable for any incidental or consequential damages caused by defects in the Product, whether such damage occurs or is discovered before or after repair or replacement, and whether such damage is caused by IHP’s negligence. IHP has not made and does not make any representation or warranty of fitness for a particular use or purpose, and there is no implied condition of fitness for a particular use or purpose.
IHP makes no expressed warranties except as stated in this 20 Year Limited Warranty. The duration of any implied warranty is limited to the duration of this expressed warranty.
No one is authorized to change this 20 Year Limited Warranty or to create for IHP any other obligation or liability in connection with the Product. Some states and provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. The provisions of this 20 Year Limited Warranty are in addition to and not a modification of or subtraction from any statutory warranties and other rights and remedies provided by law.
INVESTIGATION OF CLAIMS AGAINST WARRANTY
IHP reserves the right to investigate any and all claims against this 20 Year Limited Warranty and to decide, in its sole discretion, upon the method of settlement. To receive the benefits and advantages described in this 20 Year Limited Warranty, the appliance must be installed and repaired by a licensed contractor approved by IHP. Contact IHP at the address provided herein to obtain a listing of approved dealers/distributors. IHP shall in no event be responsible for any warranty work done by a
contractor that is not approved without first obtaining IHP’s prior written consent.
HOW TO REGISTER A CLAIM AGAINST WARRANTY
In order for any claim under this warranty to be valid, you must contact the IHP dealer/distributor from which you purchased the product. If you cannot locate the dealer/ distributor, then you must notify IHP in writing. IHP must be notified of the claimed defect in writing within 90 days of the date of failure. Notices should be directed to theIHP Warranty Department at 1508 Elm Hill Pike, Suite 108; Nashville, TN 37210 or visit our website at WWW.SUPERIORFIREPLACES.US.COM.
Printed in U.S.A. © 2013 Innovative Hearth Products LLC
P/N 900223-00, Rev. NC 12/2013
Innovative Hearth Products
%LM(ILL0IKE3UITEs.ASHVILLE4.
Page 73
Operation
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
73
Contact an IHP dealer to obtain parts. Please contact IHP for the phone number of your nearest IHP dealer.
www.superiorfireplaces.US.com
Record the following important information about your fireplace:
Fireplace model number
Fireplace serial number
Date fireplace was Installed
Typ e o f g as fire place use s
Dealer name
Page 74
Installation and Operation Instructions
900004-00, 04/2014
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
P900004-00
www.IHP.us.com
Innovative Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2013–2014 Innovative Hearth Products LLC P/N 900004-00 Rev. C 04/2014 %LM(ILL0IKE3UITEs.ASHVILLE4.