Superior DRT2033xxx *DRC2033, DRC2040, DRT2045, DRC2045, DRT2035 Installation And Operation Instructions Manual

...
P/N 900004-00 Rev. G 04/2015
PFS
USC
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 900004-02.
P900004-00
Report No. F13-094
Installation and Operation Instructions
Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
Models DRT2033xxx *
DRC2033xxx *
* “xxx” indicates unique model identifiers. This manual covers all Superior™ DRT2000 and DRC2000 models.
DRT2035xxx * DRC2035xxx *
DRT2040xxx * DRC2040xxx *
DRT2045xxx * DRC2045xxx *
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at-risk
Installateur : Laissez cette notice avec l’appareil. Consommateur : Conservez cette notice pour consultation ultérieure.
L’écran pare-étincelles fourni avec ce foyer réduit le risque de brûlure en cas de contact accidentel avec la vitre chaude et doit être installé pour la protection Des enfants et Des personnes à risques.
individuals. This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile
home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Cet appareil peut installé dans une maison préfabriquée (mobile) déjà installée à demeure, si les réglements locaux le permettent. Ce appareil doit être utilisé uniquement avec le type de gaz indiqué sure la plaque signalétique. Cet appareil ne peut être converti à d’autres gaz, sauf si une trousse de conversion est utilsée.
WARNING:
FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neigh­bor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a
qualified installer, service agency or the gas sup­plier.
AVERTISSEMENT: RISQUED’INDENDIE OU D’EXPLOSION
Le non-respect Des avertissements de sécurité pourrait d’entraîner des blessures graves, la mort ou des dommages matériels.
— Ne pas entreposer ni utilizer d’essence ni d’autres
vapeurs ou liquides inflammables dans le voisin­age de cet appareil ou de tout autre appareil.
— QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des téléphones se trouvant dans le bâti­ment où vous trouvez.
• Sortez immédiatement de bâtiment.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service des incindies.
— L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at-risk individuals.
See attached color flyer for proper color representation
General Information
900004-00, 04/2015
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
DANGER
VITRE CHAUDE
RISQUE DE BRÛLURES.
NE TOUCHEZ PAS UNE VITRE
NON REFROIDIE.
NE LAISSEZ JAMAIS UN ENFANT
DE TOUCHER LA VITRE.
L’écran pare-étincelles fourni avec ce foyer réduit le risque de brûlure en cas de contact accidentel avec la vitre chaude et doit être installé pour la protection Des enfants et Des personnes à risques.
Voir ci-joint tract pour une bonne représentation de la couleur
PELIGRO
EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
USTED DEBE NUNCA
TOCAR EL VIDRIO CALIENTE.
LOS NIÑOS DEBEN NUNCA
TOCAR EL VIDRIO.
Una barrera diseñada para reducir el riesgo de quemaduras desde la mir­illa (vidrio) caliente es proveida con este aparato y deberá instalarse para la protección de los niños y otros individuos en riesgo.
2
Vea el volante adjunto para la representación de color adecuado
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
General Information
900004-00, 04/2015
Safety and Your
Fireplace
All parts of your
IHP fireplace get
EXTREMELY HOT!
 To prevent severe
burns and injuries, install a screen or physical barrier to prevent direct contact with the glass.
 Follow the safety instructions
below and be sure everyone in your household understands this burn hazard:
• The surfaces on your fireplace get EXTREMELY HOT!
• The glass on the front of the fireplace reaches EXTREMELY HIGH temperatures and can cause severe burns if touched.
• Keep children away from an operating fireplace. Closely supervise children in any room where a fireplace is operating to prevent contact with glass.
• Keep clothing, furniture, gasoline, and other flammable liquids away from the fireplace.
• Even after the gas is turned off, fireplace surfaces remain extremely hot.
 Be sure to attach the enclosed
Safety-in-Operation Warnings where you turn on your fireplace, to help remind everyone of the dangers associated with high temperatures (Page 43).
 Read Important Safety Information
(Page 5)
3
EXTRÊMEMENT CHAUDES !
La sécurité et
votre foyer
Toutes les parties de votre
foyer IHP deviennent
 Afin d'éviter de vous
brûler gravement ou de vous blesser, installez une grille ou une barrière physique pour empêcher tout contact direct avec la vitre.
 Suivez les instructions de sécurité
ci-dessous et veillez à ce que tous les membres de votre famille soient conscients du danger de brûlure encouru :
Les surfaces de votre foyer deviennent EXTRÊMEMENT CHAUDES !
La vitre située à l'avant du foyer atteint des températures EXTRÊMEMENT ÉLEVÉES et peut causer de graves blessures en cas de contact.
Tenez les enfants à l'écart du foyer lorsqu'il fonctionne. Surveillez attentivement les enfants dans les pièces où un foyer est utilisé afin d'éviter qu'ils ne soient en contact avec la vitre.
Tenez tous les vêtements, les meubles, l'essence et tout autre liquide inflammable à l'écart du foyer.
Même après fermeture du gaz, les surfaces du foyer restent extrêmement chaudes.
Veillez à coller les Étiquettes de mise
en garde relatives à la sécurité d'utilisation à l'endroit où vous
utilisez le foyer, pour rappeler à tous les utilisateurs les dangers liés aux températures élevées (Page 43).
 Lisez L’information de sûreté
importante (Page 43).
[FRENCH][ENGLISH]
Seguridad y su
chimenea
¡Todas las partes de la
chimenea IHP se ponen
MUY CALIENTES!
 Instale una malla o barrera física para evitar
el contacto directo con el vidrio y prevenir las quemaduras y lesiones graves.
 Siga las instrucciones de seguridad
a continuación y asegúrese de que todos en su hogar sepan acerca de este peligro de quemadura:
• ¡Las superficies de la chimenea se ponen MUY CALIENTES!
• El vidrio delante de la chimenea alcanza temperaturas EXTREMADAMENTE ALTAS y puede causar quemaduras graves si se toca.
• Mantenga a los niños alejados de la chimenea en funcionamiento. Supervise en forma cercana a los niños en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio.
• Mantenga la ropa, mobiliario, gasolina y otros líquidos inflamables alejados de la chimenea.
• Aún después de haber apagado el gas, las superficies de la chimenea permanecen extremadamente calientes.
Asegúrese de colocar las Etiquetas
de advertencia de seguridad de operación en el lugar donde
enciende la chimenea, para que todos recuerden los peligros asociados con las altas temperaturas (Página 43).
 Lea Información importante de
seguridad (Página 5).
[SPANISH]
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
Traditional Fireplace Contemporary Fireplace
THANK YOU FOR YOUR PURCHASE. WE APPRECIATE YOUR BUSINESS!
Please carefully read and follow all instructions in this manual. Pay special attention to all warnings and safety information. Following these safety, care, and operation instructions will help ensure many years of dependable and enjoyable service from your fireplace.
General Information
900004-00, 04/2015
Please read and understand these instructions before installing, operating, or servicing this product.
General Information
Important Safety Information ............................................................5
Fireplace Installation, Operation, and Maintenance Notices ............... 6
Packaging .......................................................................................... 8
Introduction ....................................................................................... 8
Installation
Requirements for the Commonwealth of Massachusetts ................10
Cold Climate Insulation .................................................................... 10
Manufactured Home Requirements ................................................. 11
Location ...........................................................................................11
Vent Termination Clearances ...........................................................12
Minimum Clearances to Combustibles ............................................14
Wall Finishes / Surrounds / Mantels ................................................15
Installation Preparation ....................................................................15
Installation Sequence ......................................................................16
Construct the Fireplace Framing ...................................................... 16
Route the Gas Supply Line to the Fireplace .....................................18
Install the Vent System ....................................................................24
Complete the Field Wiring ................................................................36
Install the [Optional] Blower Kit after Installation in the Framing ..... 38
We recommend that our gas hearth products be installed and serviced by professionals who are certied in the U.S. by the National Fireplace Institute® (NFI) as NFI Gas Specialists.
Connect the Gas Line ....................................................................... 38
Verify Proper Fireplace Operation ....................................................39
Optional: Install the Firebox Liners ..................................................40
Contemporary Fireplaces: Install the Glass Media ........................... 40
Traditional Fireplaces: Install the Logs, Volcanic Stone,
and Glowing Embers .......................................................................40
Install the Glass Door ......................................................................40
Adjust the Air Shutter to Ensure Proper Flame Appearance ............. 40
Install the Hood ...............................................................................42
Install the Finishing Materials .......................................................... 42
Attach the Safety-in-Operation Warnings.........................................43
Installation Accessories ................................................................... 44
Gas Conversion Kits ........................................................................46
Operation
Maintenance .................................................................................... 59
Accessory Components ................................................................... 63
Lighting Instructions .......................................................................66
Troubleshooting ...............................................................................70
Replacement Parts ..........................................................................72
Warranty ..........................................................................................75
4
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
General Information
900004-00, 04/2015
GENERAL INFORMATION
IMPORTANT SAFETY INFORMATION L’information de sûreté importante Información importante de seguridad
WARNING AVERTISSEMENT ADVERTENCIA
Do not operate appliance with the glass front removed, cracked or broken.
Do not use this fireplace if any part has been under water. Immediately call a qualified service technician to inspect the fireplace and to replace any part of the control system and any gas control which has been under water.
Due to high temperatures, the fireplace should be located out of traffic and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Clothing or other flammable material should not be placed on or near the fireplace.
Young children should be carefully supervised when they are in the same room as the fireplace. Toddlers, young children, and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at-risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children, and other at­risk individuals out of the room and away from hot surfaces.
Any safety screen or guard removed for servicing a fireplace must be replaced prior to operating the fireplace.
Installation and repair should be done by a qualified service person. The fireplace should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, et cetera. It is imperative that control compartments, burners, and circulating air passageways of the fireplace be kept clean (Maintenance on Page 59).
[English] [French] [Spanish]
Ne pas utiliser l’appareil si le panneau frontal en verre n’est pas en place, est craqué ou brisé.
Ne pas utiliser cet appareil s’il a été plongé, même partiellement, dans l’eau. Appeler un technicien qualifié pour inspecter l’appareil et remplacer toute partie du système de commande et toute commande qui a été plongée dans l’eau.
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures.
Les enfants et les adultes devraient être informés des dangers que posent les températures de surface élevées et se tenir à distance afin d’éviter des brûlures ou que leurs vêtements ne s’enflamment.
On ne devrait pas placer de vêtements ni d’autres matières inflammables sur l’appareil ni à proximité.
Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la surface chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habitent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécurité ; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de poussière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres (Page 59).
No opere el artefacto con el frente de vidrio quitado, agrietado o roto.
No use este artefacto si alguna de sus partes ha estado bajo agua. Llame de inmediato a un técnico de servicio calificado para que inspeccione el artefacto y reemplace cualquier parte del sistema de control y cualquier control de gas que haya estado bajo agua.
Debido a las altas temperaturas, el artefacto debe situarse fuera de las áreas de tráfico y lejos del mobiliario y cortinas.
Se debe alertar a los niños y adultos sobre los peligros de las altas temperaturas en la superficie y que se mantengan alejados para evitar quemaduras o ignición de la ropa.
No debe colocarse ropa u otros materiales inflamables sobre y cerca del artefacto.
Se debe supervisar de cerca a los niños cuando estén en el mismo cuarto que el artefacto. Los niños pequeños, los jóvenes y otras personas pueden ser susceptibles a quemaduras por contacto accidental. Se recomienda instalar una barrera física si hay personas en riesgo en la casa. Para restringir el acceso a una chimenea o estufa, instale una puerta de seguridad ajustable para mantener a los niños pequeños, jóvenes y otras personas en riesgo fuera del cuarto y lejos de las superficies calientes.
Cualquier malla o resguardo de seguridad quitado para dar servicio a un artefacto, debe reinstalarse antes de operar el artefacto.
Una persona de servicio competente debe realizar la instalación y reparación. Una persona de servicio profesional debe inspeccionar el artefacto antes de usar al menos una vez por año. Se puede requerir limpieza más frecuente debido a la pelusa excesiva del alfombrado, del material de cobijas, etc. Es imprescindible mantener limpios los compartimientos de control, los quemadores y los pasajes de circulación del aire del artefacto (Página 59).
5
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
FIREPLACE INSTALLATION, OPERATION, AND MAINTENANCE NOTICES
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION, AND LISTINGS OF THIS UNIT.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
AVERTISSEMENT
Une installation, un réglage,une modification, une réparation ou un entretien mal effectué peut causer des dommages matériels ou des blessures. Voir la notice de l’utilisateur qui accompagne l’appareil. Pour de l’aide ou des renseignements supplémentaires, consultez un installateur, un technicien agréé ou le fournisseur de gaz.
WARNING
General Information
900004-00, 04/2015
Failure to comply with these installation instructions will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appliance and/or its operating controls is dangerous.
6
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
Clothing or other flammable material should not be placed on or near the appliance.
On ne devrait pas placer de vêtements ni d’autres matières inflammables sur l’appareil ni à proximité.
Improper installation or use of this appliance can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
Hot while in operation. Do not touch. Severe Burns may result. Keep children, clothing furniture, gasoline and other liquids having flammable vapors away.
General Information
900004-00, 04/2015
WARNING
AVERTISSEMENT
WARNING
CAUTION
ATTENTION
L’appareil est chaud lorsqu’il fonctionne. Ne pas toucher l’appareil. Risque de brûlures graves. Surveiller les enfants. Garder les vêtements, les meubles, l’essence ou autres liquides produisant des vapeur inflammables loin de l’appareil.
NOTE:
• If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this applian
• For use with barrier(s) Part No(s). F1902 (33” Models), F1839 (35” Models), F1840 (40” Models), and F1903 (45” Models). Follow installation instructions.
These fireplaces are designed as supplemental heaters, and are not to be used as the primary heat source when installed in a dwelling.
Provide adequate clearances around air openings and adequate accessibility clearance for service and proper operation. Never obstruct the front or back openings of the fireplace.
These fireplaces are designed to operate on natural or propane gas only. The use of other fuels or combination of fuels will degrade the performance of this system and may be dangerous.
These fireplaces must not be connected to a chimney or flue serving a separate solid fuel burning fireplace.
Only trim kit(s) supplied by the manufacturer shall be used in the installation of this fireplace.
Remarqué :
Seules les trousses de garniture fournies par le fabricant doivent être utilisées pour l’installation de cet appareil.
7
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
INSTALLATION
PACKAGING
All models include
The assembled vented gas fireplace heater is packaged with:
Literature Kit (envelope in bottom compartment containing Installation and Operation Instructions (this manual), and Safety-In-Operation Warning Labels)
U-Shaped Vent Restrictor (attached to Literature Kit envelope)
Hood (Inside firebox)
Traditional models also include
Log Set (packaged in a carton inside the firebox)
Volcanic Stone—1 bag (in bottom compartment)
Glowing Embers—1 bag (in bottom compartment)
Contemporary models also include
Glass Media
Contemporary Burner Panel
INTRODUCTION
General Information
900004-00, 04/2015
These vented gas fireplace heaters are sealed combustion, air-circulating gas fireplaces designed for residential and commercial applications.
Millivolt fireplaces have a millivolt gas control valve with piezo ignition system. If a blower will be installed, electrical power must be provided at the time of fireplace installation.
Electronic fireplaces are designed with an electronic intermittent pilot ignition system. External electrical power is required to operate these units. In the event of a power outage, four (4) AA batteries (in battery holder) provide backup power for fireplace operation (excluding the optional blower).
NOTE: Installation and repair should be done by a qualified service person. The fireplace should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the fireplace be kept clean.
Remarqué : L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres.
NOTE: Diagrams and illustrations are not necessarily shown to scale.
Approved Vent Components
These fireplaces are designed, tested and listed for operation and installation with the following vent components only:
Secure Vent
Secure Flex
Z-FLEX® Model GA Venting Systems listed to UL1777 and ULCS635 manufactured by Flexmaster Canada Limited.
®
Direct-Vent System Components,
®
Flexible Vent Components, and
Codes and Standards
8
Use only the correct size venting (4 1/2” inner and 7 1/2” outer). These approved vent system components are labeled for identification. DO NOT use any other manufacturer’s vent
components with these fireplaces.
These fireplaces comply with National Safety Standards and are tested and listed by PFS Corporation (Report No. F13-94) to ANSI Z21.88 (in Canada, CSA-2.33), and CAN/CGA-2.17-M91 in both USA and Canada, as vented gas fireplace heaters.
These fireplaces are listed for installation in bedrooms and manufactured homes. The installation must conform to local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54—latest edition (In Canada, the current CAN/CGA-B149.1 installation code). The fireplace, when installed, must be electrically grounded and wired in accordance with local codes or, in the
absence of local codes, with the National Electrical Code, ANSI/NFPA 70—latest edition, or the Canadian Electrical Code, CSA C22.1—latest edition.
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
BTU Input
Table 1: Input Rate, Gas Valves
Models
DRC2033 / DRT2033 12,000 10,000 DRC2035 / DRT2035 14,000 12,000 DRC2040 / DRT2040 16,000 15,000 DRC2045 / DRT2045 20,000 19,000
Table 2: Thermal Efficiency (%)
Model
DRC2033 / DRT2033 64 60.4 64 64.8 DRC2035 / DRT2035 65.5 61 65.5 65 DRC2040 / DRT2040 65.5 62 65.5 65 DRC2045 / DRT2045 65 63 65 66
* AFUE is a measurement of the US Department of Energy, ** P4 (EnerGuide) is a measurement of the Canadian Office of Energy Efficiency.
NOTE: Efficiiencies are based on the most commonly used F1797 termination.
General Information
900004-00, 04/2015
Input Rate (BTU/HR)
Natural Gas Propane Gas
Millivolt Electronic
AFUE * P4 ** AFUE * P4 **
Gas Pressure
Table 3: Inlet Gas Supply Pressure
Fuel Minimum Maximum
Natural Gas 5” WC / (1.25 kPa) 10.5” WC / (2.61 kPa)
Propane 11.0” WC / (2.74 kPa) 13.0” WC / (3.23 kPa)
Table 4: Manifold Gas Supply Pressure
Fuel Pressure
Natural Gas 3.5” WC / (0.87 kPa)
Propane 10.0” WC / (2.49 kPa)
Test gauge connections are provided on the front of the millivolt and electronic gas control valve (identified IN for the inlet and OUT for the manifold side). The control valves have a 3/8” (10 mm) NPT thread inlet and outlet side of the valve (Figure 1 and Figure 2).
Figure 1: Millivolt Gas Valve Figure 2: Electronic Gas Valve
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step down regulators to reduce the pressure to safe levels.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
9
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
Orifice Sizes—Sea Level to High Altitude
These fireplaces are tested and approved for installation at elevations of 0–4500 ft (0–1372 m) above sea level using the standard burner orifice sizes (Table 5). For elevations above 4500 ft, contact your gas supplier or qualified service technician.
Table 5: Burner Orifice Sizes, Elevation 0–4500 ft ( 0–1372 m)
Model
DRC2033 / DRT2033 #51 (0.067”)* #61 (0.039”)* DRC2035 / DRT2035 #49 (0.073”)* #58 (0.042”)* DRC2040 / DRT2040 #48 (0.076”)* #56 (0.046”)* DRC2045 / DRT2045 #44 (0.086”)* #55 (0.052”)*
* Standard size installed at factory
Deration
At elevations above 4500 ft, the amount of BTU fuel value delivered must be reduced by either:
Using gas that has been derated by the gas company.
Changing the burner orifice to a smaller size as regulated by the local authorities having jurisdiction and by the (USA) National Fuel Gas Code NFPA 54/ANSI Z223.1—latest edition or, in Canada, the CAN/CGA-B149.1 codes— latest edition.
NOTE: Flame breadth, height and width will diminish 4% for every 1,000 ft of altitude.
IN CANADA—CAN/CGA-2.17-M91 (HIGH ALTITUDE): THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER’S AUTHORIZED REPRESENTATIVE,
IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER, PROVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/ CGA-B149.1 OR CAN/CGA-B149.2 INSTALLATION CODES.
Natural Gas
drill size
Installation
900004-00, 04/2015
Propane drill size
REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in the U.S. state of Massachusetts if the following additional requirements are met:
Install this fireplace in accordance with Massachusetts Rules and Regulations 248 C.M.R..
Installation and repair must be done by a plumber or gas fitter licensed in the Commonwealth of Massachusetts.
The flexible gas line connector used shall not exceed 36” (914 mm) in length.
The individual manual shutoff must be a T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, horizontal terminations installed less than seven (7) ft above the finished grade must comply with the following additional requirements:
A hard wired carbon monoxide detector with an alarm and battery back-up must be installed on the floor level where the gas fireplace is installed. The carbon monoxide detector must comply with NFPA 720, be ANSI/UL 2034 listed and be ISA certified.
A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimum height of eight (8) ft above grade and be directly in line with the horizontal termination. The sign must read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your fireplace with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which fireplace rests, if floor is above ground level. Gas line holes and other openings should be caulked or stuffed with unfaced fiberglass insulation.
NOTE: Do not use loose, or blown-in insulation in the cavity surrounding the fireplace. If the fireplace is being installed on a cement slab in cold climates, a sheet of plywood or other raised platform can
be placed underneath to prevent conduction of cold transferring to the fireplace and into the room. It also helps to seal inside surfaces and tape for maximum air tightness and caulk firestops.
10
Innovative Hearth Products
(Rear Vent Application)
VERTICAL VENT
(Rear Vent Application without a chase)
HORIZONTAL VENT
Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
MANUFACTURED HOME REQUIREMENTS
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
Cet appareil peut être installé dans une maison préfabriquée (mobile) déjà installée à demeure si les règlements locaux le permettent.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil ne peut être converti à d’autres gaz, sauf si une trousse de conversion est utilisée.
Ensure that the cross members are not cut or weakened during installation. The structural integrity of the manufactured home floor, wall, and ceiling / roof must be maintained.
This appliance must be grounded to the chassis of the manufactured home in accordance with local codes or in the absence of local codes, with the National Electrical Code ANSI / NFPA 70—latest edition or the Canadian Electrical Code CSA C22.1—latest edition.
Installation
900004-00, 04/2015
CAUTION
CAUTION
LOCATION
In selecting the location, the aesthetic and functional use of the fireplace are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important.
Due to high temperatures, the fireplace should be located out of traffic and away from furniture and draperies.
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures.
The location should also be free of electrical, plumbing or other heating/air conditioning ducting. These direct-vent fireplaces are uniquely suited for installations requiring a utility shelf positioned directly above the
fireplace. Utility shelves like these are commonly used for locating television sets and decorative plants.
Be aware that this is a heat producing fireplace. Objects placed above the unit are exposed to elevated temperatures. Do not insulate the space between the fireplace and the area above it.
The minimum height from the base of the fireplace to the underside of combustible materials used to construct a utility shelf in this fashion is shown in Table 9 and Table 10.
Figure 3: Typical Locations and Venting
Top Vent
Top Vent
Rear Vent
Top Vent
Rear Vent
Horizontal Vent
(Rear Vent with chase)
Horizontal Vent
(Rear Vent without chase)
Recessed
Installation
Top Vent
Top Vent Top Vent
Vertical Vent
(Rear Vent)
Horizontal Vent
(Top Vent)
Vertical Vent
(Top Vent)
11
Innovative Hearth Products
12
X
Roof pitch is X/12
2 ft
minimum
2 ft minimum
Lowest
discharge
opening
H*
*H = minimum height from roof to
lowest discharge opening of vent
Horizontal overhang
Vertical
wall
Vent
termination
Storm collar
Concentric
vent pipe
Flashing
1” (25.4 mm) minimum clearance to combustibles
Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI Z223.1/NFPA 54) in the USA or the current standards of CAN/CGA-B149.1 in Canada.
Vertical Vent Termination Clearances
Terminate multiple vent terminations according to the installation codes listed above and Figure 4.
Figure 4: Multiple Terminations
(305 mm)
minimum
Terminate single vent caps relative to building components according to Table 6 and Figure 4.
Table 6: Termination Heights for Vents above Flat or Sloped Roofs (NFPA 54 / ANSI Z223.1)—Gas Vent Rule
12”
Installation
900004-00, 04/2015
6”
(153 mm)
Roof Pitch Termination Height *
Flat to 6/12 1.0 ft (0.3 m) 6/12 to 7/12 1.25 ft (0.38 m) 7/12 to 8/12 1.5 ft (0.46 m) 8/12 to 9/12 2.0 ft (0.61 m)
9/12 to 10/12 2.5 ft (0.76 m) 10/12 to 11/12 3.25 ft (0.99 m) 11/12 to 12/12 4.0 ft (1.22 m) 12/12 to 14/12 5.0 ft (1.52 m) 14/12 to 16/12 6.0 ft (1.83 m) 16/12 to 18/12 7.0 ft (2.13 m) 18/12 to 20/12 7.5 ft (2.29 m) 20/12 to 21/12 8.0 ft (2.44 m)
Horizontal Vent Termination Clearances
12
The horizontal vent termination must have a minimum of 6” (152 mm) clearance to any overhead combustible projection of 2 1/2” (64 mm) or less (Figure 5). For projections exceeding 2 1/2” (64 mm) (Figure 5). For additional vent location restrictions refer to Table 7.
All horizontal terminations may be located as close as 6” (152mm) to any (non-combustible and combustible) exterior sidewall. This distance may be decreased to 2” (51mm) for noncombustible exterior sidewalls with all approved terminations (Table 21).
Figure 5: Horizontal Vent Termination Clearances
*4” to center of termination for F1797, 8” for 94L10, and 10” for H1968
Combustible projection
2 1/2” or less in length
Combustible projection
greater than 2 1/2” in length
Ventilated soffit - 18” (457 mm)
Unventilated
soffit - 12”
(305 mm)
*
Termination kit*
6
(152)
Termination kit
NOTE: See Figure 27 on Page 31 for exterior
wall recess allowances
6”
for compact horizontal termination.
Use 6.5” for all horzontal terminations applicable
Innovative Hearth Products
(TERMINATION PROHIBITED)
Inside Corner
Balcony with No Side
Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
Table 7: Horizontal vent termination clearances for buildings with combustible and noncumbustible exteriors
Outside Corner Recessed Location
D
E
V
B
L
C
F
V
B
TERMINATION CAP
V
Fixed
Closed
Openable
V
Openable
V
B
A
AIR SUPPLY INLET
X
Fixed
Closed
J
B
V
B
X
G
GAS METER RESTRICTED AREA
A Clearance above grade, veranda, porch, desk, or balcony 12” (300 mm) ** 12” (300 mm) * B Clearance to window or door that may be opened 6” (150 mm)
C Clearance to permanently closed window 9” (229 mm)
D Vertical clearance to ventilated soffit located above the
termination within a horizontal distance of 18” (458 mm)
E Clearance to unventilated soffit 12” (305 mm) 12” (305 mm)
See Table 6
H
G
V
V
F
I
G
G
M
V
K
V
G
V
X
A
WallVBalcony with Perpendicular Side Wall
M
M
V
U.S. Installation ** Canadian Installation *
6” (150 mm)
for fireplaces < 10,000 Btu/h (3 kW), 9” (230 mm)
for fireplaces > 10,000 Btu/h (3 kW), and < 50,000 Btu/h
for fireplaces < 10,000 Btu/h (3 kW), 12” (300 mm)
for fireplaces > 10,000 Btu/h (3 kW)
(15 kW), 12” (300 mm)
for fireplaces > 50,000 Btu/h (15 kW) **
12” (305 mm)
recommended to prevent window condensation
recommended to prevent window condensation
18” (458 mm) 18” (458 mm)
Installation
900004-00, 04/2015
P
N
Q
O
V
F Clearance to outside corner 5” (127 mm)
minimum
5” (127 mm) minimum
G Clearance to inside corner 6” (152 mm) minimum 6” (152 mm) minimum H Clearance to each inside of center line extended above
meter / regulator assembly
36” (910 mm) within a height of 15 ft above the meter / regulator assembly **
36” (910 mm) within a height of 15 ft above the meter / regulator assembly *
I Clearance to service regulator vent outlet 36” (910 mm)** 36” (910 mm)*
J Clearance to nonmechanical air supply inlet to building or
the combustion air inlet to any other fireplace
6” (150 mm) for fireplaces < 10,000 Btu/h (3 kW),
9” (230 mm) for fireplaces > 10,000 Btu/h (3 kW) and < 50,000 Btu/h (15 kW),
6” (150 mm) for fireplaces < 10,000 Btu/h (3 kW),
12” (300 mm) for fireplaces > 10,000 Btu/h (3 kW)
12” (300 mm) for fireplaces > 50,000 Btu/h (15 kW)**
K Clearance to a mechanical air supply inlet 36” (910 mm) above if within 10 ft (3 m) horizontally ** 72” (1830 mm) * L Clearance above paved sidewalk or paved diveway located
84” (2130 mm) ‡ 84” (2130 mm) ‡
on public property
M Clearance under veranda, porch, deck or balcony 12” (300 mm) *‡ 12” (300 mm) *‡
N Depth of alcove (maximum) 72” (1830 mm) ** 72” (1830 mm) * O Clearance to termination (alcove) 6” (15.2 mm) ** 6” (15.2 mm)* P Width of alcove (minimum) 36” (910 mm) ** 36” (910 mm) * Q Clearance to combustible above (alcove) 18” (457 mm) ** 18” (457 mm) *
*
In accordance with the current CSA-B149.1 National Gas And Propane Installation Code
**
In accordance with the curent ANSI Z223.1/NFPA 54 National Fuel Gas Codes
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
*‡
Only permitted if veranda, porch, deck, or balcony is fully-open on a minimum two sides beneath the floor
13
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
MINIMUM CLEARANCES TO COMBUSTIBLES Fireplace And Vent Clearances
The fireplace is approved with zero clearance to combustible materials on all sides (Table 8), with the following exception: The unit may not be recessed (allowance made for mantel legs / side trim in Figure 6). When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit (Figure 6).
Table 8: Minimum Clearances *
From Bottom of Unit to Ceiling 64” (1626 mm)
Front Service Clearance—
clearance immediately in front of viewing area(s)
* 3” (76 mm) above any horizontal/inclined vent component. ** See Page 19 for clearance requirements to the nailing flange located at each side of the unit and any screw heads adjacent to it. *** Top vent clearance can be reduced to 2” on horizontal runs when first elbow is located at least 6 ft above the fireplace.
Back
Sides
Top Standoffs 0” (0 mm) to top standoffs
Floor 0” (0 mm)
Vent
1” (26mm) to wrapper for 45” model, all
others 1/2” (13mm) to wrapper
0” (0 mm) to Spacers
1/2” (13 mm) to wrapper 0” (0 mm) to Spacers **
3” (76 mm)—Top * ***
1” (25.4 mm)—Sides and Bottom
36” (914 mm)
Installation
900004-00, 04/2015
The fireplace must be mounted on a fully supported base extending the full width and depth of the unit. The fireplace may be located on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile or other combustible material other than wood flooring, the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
Hearth Extension
A hearth extension is not required with this fireplace. If a hearth extension is used, do not block the lower control compartment door. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements.
Shelf Height
To provide for the lowest possible shelf surface, use the rear vent model. For top vent models, the venting attached to the top vent should be routed in a way to minimize obstructions to the space above the fireplace. Do not insulate the space between the fireplace and the area above it (Table 9 and Table 10). The minimum height from the base of the fireplace to the underside of combustible materials used to construct a utility shelf in this fashion is shown in
Table 9 and Table 10.
Table 9: Combustible Shelf Height—Top Vent
Model
DRC2033 / DRT2033 44” (1118 mm) 46” (1168 mm) DRC2035 / DRT2035 47” (1194 mm) 49” (1245 mm) DRC2040 / DRT2040 52” (1321 mm) 54” (1372 mm) DRC2045 / DRT2045 50” (1270 mm) 52” (1321 mm)
Top Vent with one 90° Elbow
Secure Vent
®
Secure Flex® (flex elbow)
Shelf Height
(see table)
No combustibles or insulation in the shaded area between the appliance and the shelf above it.
14
Innovative Hearth Products
(152 mm)
mantel legs may
At 6 in. minimu side wall clearance, a combustible wal can project to an length
Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
Table 10: Combustible Shelf Height—Rear Vent
Model
DRC2033 / DRT2033 34” (864 mm) 34” (864 mm) DRC2035 / DRT2035 35 1/2” (902 mm) 35 1/2” (902 mm) DRC2040 / DRT2040 40 1/2” (1029 mm) 40 1/2” (1029 mm) DRC2045 / DRT2045 45 1/2” (1156 mm) 45 1/2” (1156 mm)
Figure 6: Combustible Side Clearances Figure 7: Mantel Height
At 6” minimum side wall clearance, a combustible wall can project to any length.
(152 mm)
.
6 in.
6”
m
l
y
o
o
45
45
3 1/2”
3 1/2 in.
(89 mm)
(89 mm)
Rear Vent with two 90° Elbows
Secure Vent
Top View of
Top View of
Fireplace
Fireplace
Combustible materials
Combustible Materials Allowed In Shaded Area
allowed in shaded area
Safe Zone
“Safe Zone”.
Combustible Walls
Combustible walls
shown in dark gray
shown in dark gray
Combustible
Combustible mantel
project beyond either side
legs may project
of the fireplace opening
beyond either side of
as long as they are kept within the shaded area
the fireplace opening
illustrated here.
as long as they are kept within the shaded area illustrated here.
Installation
900004-00, 04/2015
®
Secure Flex® (flex elbow)
3” clearance from shelf to
top of fireplace and/or vent
pipe, whichever is higher
No
Shelf Height
(see table)
combustibles or insulation in the shaded area between the appliance and the shelf above it.
Mantel depth
18 (457)
16 (406)
14 (356)
12 (305)
10 (254)
8 (203)
4
8
in. (mm)
12
(305)
10
(254)
(203)
6
(152)
(102)
Hood
2
(51)
Fireplace
Wall Finishes / Surrounds / Mantels
INSTALLATION PREPARATION
NOTE: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the fireplace front face (black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the fireplace face (Figure 41).
Non-combustible materials, such as surrounds and other fireplace trim, may be installed on the fireplace face, but they must not cover any portion of the removable glass panel or control compartment.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel (Figure 7). Mantels constructed of non-combustible materials may be installed at any height above the fireplace opening. However, do not allow anything to hang below the fireplace hood.
Minimum clearance requirements include any projections such as shelves, window sills, mantels, etc. above the fireplace.
NOTE: To avoid heat-related finish damage, use finish materials rated 175 °F, or higher, on the underside of the mantel.
The fireplace is shipped with all gas controls and components installed and pre-wired. Before installing the fireplace, follow these steps:
1. Remove the shipping carton, and retain the front of the carton (used to protect the fireplace during construction).
2. Remove the shipping pad, exposing the front glass door.
3. Remove the glass door (Page 57). NOTE: Place the glass door on the shipping carton to protect its surface.
15
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
INSTALLATION SEQUENCE
The typical sequence of installation is outlined below; however, each installation is unique and may result in variations to the steps described.
See the pages referenced in the following steps for detailed instructions.
Framing
1. Construct the Fireplace Framing (Page 16).
2. Prepare the Fireplace Top Spacers (Page 18).
3. Route the Gas Supply Line to the Fireplace (Page 18).
4. Rough in the Electrical Supply, if Needed (Page 19).
5. Install the [Optional] Blower Kit before Installation in the Framing (Page 19).
6. Place the Fireplace in the Framing and Secure (Page 19).
Venting
7. Select a Horizontal or Vertical Vent System (Page 19).
8. Install the Vent Restrictor (if necessary) (Page 21).
9. Install the Vent System (Page 24).
Electrical Connection
10. Complete the Field Wiring (Page 36).
11. Install the [Optional] Blower Kit after Installation in the Framing (Page 38).
Gas Connection
12. Connect the Gas Line (Page 38).
13. Verify Proper Fireplace Operation (Page 39).
Finishing
14. Optional: Install the Firebox Liners (Page 53).
15. Traditional Fireplaces: Install the Logs, Volcanic Stone, and Glowing Embers (Page 54).
16. Contemporary Fireplaces: Install the Glass Media (Page 53).
17. Install the Glass Door (Page 57).
18. Adjust the Air Shutter to Ensure Proper Flame Appearance (Page 40).
19. Install the Hood (Page 42).
20. Reinstall the Included Barrier (Page 42).
21. Install the Finishing Materials (Page 42).
22. Attach the Safety-in-Operation Warning Labels (Page 42).
Installation
900004-00, 04/2015
1. Construct the Fireplace Framing
1. Frame the fireplace as illustrated in Table 11. For corner framing installations, use Table 12. All framing details
must allow for a minimum clearance to combustible framing members as shown in Table 8.
2. If the fireplace is to be elevated above floor level, a solid continuous platform must be constructed below the fireplace. NOTE: Headers may be in direct contact with the fireplace top standoff spacers when they are bent up vertically,
maintaining the 4” clearance to the fireplace top, but must not be supported by them or notched to fit around them. All construction above the fireplace must be self-supporting. DO NOT use the fireplace for structural support.
16
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
Table 11: Fireplace Framing Specifications
Model A * B C D E
DRC2033 /
DRT2033
DRC2035 /
DRT2035
DRC2040 /
DRT2040
DRC2045 /
DRT2045
33 3/4
857
35 3/8
899
40 3/8
1026
45 3/8
1153
34 1/4
870
36 1/4
921
41 1/4
1048
41 1/4
1048
36 7/8
930
38 3/4
984
43 3/4
1111
43 3/4
1111
14 1/2
368
18
447
18
447
18
447
19 5/8
499
23 3/8
594
28 1/4
717
28 1/4
717
C = Minimum height of top vent installations E = Minimum height of rear vent installations
* Minimum opening size; additional 1/8” per side is recommended. NOTE: Framing specifications do NOT apply for flexible venting.
When using flexible venting, refer to the kit requirements for framing specifications.
NOTE: See Page 28 concerning use of compact terminations on rear-vent 45” Models.
NOTE: Dimension “D” is the required framing depth when the finish material (drywall) thickness is 1/2” (13mm).
Vent Framing—Top Vent
with One 90° Elbow
B
C
1/2 A
A
Inches (millimeters)
Installation
900004-00, 04/2015
Framing construction to be
10 1/2
2 x 4, or larger.
(267)
7 (178)
5 1/8
(130)
12 1/8
(308)
E
D
Table 12: Fireplace Framing Specifications—Corner Installation with Horizontal Termination
Model A B C D E
DRC/T2033
DRC/T2035
DRC/T2040
DRC/T2045
33 3/4
857
35 3/8
899
40 3/8
1026
45 3/8
1153
51 1/4
1302
59 1/2
1511
63 13/16
1621
70 3/8
1788
36 1/4
921
42 1/16
1068
45 11/32
1152
49 3/4
1264
25 5/8
651
3. 1/4 768
32 3/16
818
35 1/4
895
12 1/8
308
14 1/4
362
15 7/8
403
17 1/2
445
F G
5 1/2
140
6 5/8
168
8 1/2
216
10 1/4
260
14 1/2
368
18
457
18
457
18
457
C
Back wall of chase/enclosure (including finishing materials)
Table 13: Fireplace Specifications
NOTE: When finishing the area around the hood, 5/8” clearance above hood is required for hood installation.
K
L
O
E
N
J
G
H
F
Blower
access panel
E
F*
7 (178)
D
G
A
B
Inches (millimeters)
Hood
Junction
box access
Gas line
access
M
Top View Front View
Left Side View Right Side View
Model E F G H (door) J K L M N O
DRC2033 / DRT2033 30 1/8 (765) 26 1/4 (667) 18 5/16 (465) 30 1/2 (775) 33 5/8 (854) 21 7/8 (556) 10 15/16 (278) 31 (787) 8 1/2 (216) 14 (356) DRC2035 / DRT2035 32 1/8 (816) 28 3/4 (730) 22 1/4 (565) 32 3/8 (822) 35 1/4 (895) 25 (635) 12 1/2 (317) 32 7/8 (835) 10 1/16 (256) 17 (432) DRC2040 / DRT2040 37 1/8 (943) 33 1/4 (845) 27 1/4 (692) 37 3/8 (949) 40 1/4 (1022) 30 (762) 15 (381) 37 7/8 (962) 10 1/16 (256) 17 (432) DRC2045 / DRT2045 37 1/8 (943 33 1/4 (875) 27 1/4 (692) 42 3/8 (1076) 45 1/4 (1149) 35 (889) 17 1/2 (445) 42 7/8 (1089) 10 1/16 (256) 17 (432)
17
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
Prepare the Fireplace Top Spacers
2.
1. The two (2) 4” standoff spacers on top of the fireplace cabinet are shipped flat. Remove the screw adjacent to
the detached end (Figure 8).
2. Bend the standoffs as shown (Figure 9):
3. Align the hole in the standoff with the hole in the fireplace top, and secure with the screw that was removed in Step 1 (Figure 9).
Figure 8: Unassenbled standoff Figure 9: Assembled standoffs
Positioned flat as shipped from the factory
Screw
Top Standoff
Configuration for 1/2" finish materials
Top Standoff
Installation
900004-00, 04/2015
Configuration for 5/8" finish materials
Top Standoff
Fireplace Front
3. Route the Gas Supply Line to the Fireplace
1. Route a 1/2” (13 mm) gas line to the left side of the fireplace (Figure 10 & 10a).
NOTE: Gas lines must be routed, assembled, and made of materials that are in strict accordance with local codes
and regulations. All fireplaces are factory-equipped with a flexible gas line connector and a 1/2” shutoff valve (Page 39).
Figure 10: Routing the gas line - 35”, 40”,
45” Models
Left side front corner of fireplace framing
Pipe coupling (recommended)
7 5/8” (195 mm)
3”
(76 mm)
Proper Sizing of Gas Line
Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code, NFPA 54—latest edition (USA) or CAN/CGA-B149.1— latest edition (Canada).
The gas supply line should not be connected to the appliance until step 12. Connect the Gas Line (Page 38).
Fireplace
Front
Figure10a: Routing the Gas Line - 33” Model
Figure 60: Routing the gas line
Left side front corner of fireplace framing
Pipe coupling (recommended)
5 1/4” (140 mm)
3”
(76 mm)
Fireplace
Front
18
NOTE:
All fireplaces are factory-equipped with a flexible gas line connector and 1/2” shutoff valve (Figure 35).
See Massachusetts Horizontal Vent Requirements for additional requirements for installations in the state of Massachusetts in the USA.
A pipe joint compound rated for gas should be used on the threaded joints. Ensure propane-resistant compounds are used in propane applications. Be very careful that the pipe compound does not get inside the pipe.
A sediment trap in the supply line as close as possible to the fireplace is recommended.
Check with the local building official for local code requirements (e.g., Are below grade penetrations of the gas line allowed?, etc).
CAUTION
If propane is used, be aware that with a tank that is too small (i.e., under 100 lbs, if this is the only gas appliance in the dwelling—see NPFA 58), there may be a loss of pressure. This can result in insufficient fuel delivery that can cause sooting, delayed ignition, or other malfunctions. Any damage resulting from an improper installation is not covered by the limited warranty.
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
4.
Rough in the Electrical Supply, if Needed
1. As necessary, rough in the fireplace electrical supply per NEC and local codes.
5. Install the [Optional] Blower Kit before Installation in the Framing
1. Remove the left side blower cover panel screw, and blower cover panel (Table 13). Retain the panel and screw
for later reinstallation.
2. Slide the blower through the opening and position it with the bracket oriented to the front of the firebox and the blower discharge to the rear of the firebox. Bend the two tabs in the firebox floor to secure the blower to the floor.
3. Reinstall the blower cover panel and secure with the removed screw.
4. Access the blower supply wiring through the front of the firebox and plug it into the junction box in the right, rear
of the firebox (Figure 33).
5. Install the blower control switch according to its included instructions.
6. Place the Fireplace in the Framing and Secure
NOTE: Nailing flanges, combustible members, and screw heads in areas directly adjacent to the nailing flanges are
EXEMPT from the 1/2” clearance to combustible requirements for the firebox outer wrapper. NOTE: Combustible framing may be in direct contact with the nailing flanges and may be located within 1/2” of screw
heads and the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact dimensions specified in the framing details in this manual.
1. Bend out the appropriate nailing flanges for the drywall / finish material to be used (Figure 11). Nailing flanges are provided for:
flush framing,
1/2”, and
5/8” framing depths.
2. Secure the fireplace to the side framing members using the unit’s nailing flanges —one top and bottom on each side of the fireplace front (Figure 11). Use 8d nails or the equivalent.
Installation
900004-00, 04/2015
Figure 11: Nailing Flanges
Unit nailing flange
Side
framing
(no clearance to combustible framing is required)
VENT SYSTEM PREPARATION
7. Select a Horizontal or Vertical Vent System
1. With the fireplace secured in the framing, determine the vent route and identify the exterior termination location.
The following sections describe vertical (roof) and horizontal (exterior wall) vent applications. Use only approved vent components (Page 8 and Page 44).
NOTE: This fireplace must be vented directly to the outside.
The vent system may not service multiple appliances, and must never be connected to a flue serving a separate solid fuel burning appliance.
NOTE: The vent pipe is tested to be run inside an enclosed wall (such as a chase). There is no requirement for
inspection openings in the enclosing wall at any of the joints in the vent pipe.
WARNING
19
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
If you require a rear vent unit, check to see if rear venting has a vent cap and insulation in place. If so, remove cap and any insulation in vent pipes, make sure flue is open completely to firebox inside. Once flue pipe has clear passages on inner and outer pipes, proceed with vent connections.
Prepairing 45” Fireplaces for Top Venting Configuration
If you require a top vented unit, follow the next steps to convert before use.
Installation
900004-00, 04/2015
Step 1. Remove the 8 screws holding top vent cover plate and gasket. Retain screws.
Step 5. Remove and discard the large round gasket attached to the back of the unit. Install the cap from the top onto the rear pipe by bending tabs out securing with screws to rear outer wrapper.
Step 9. Remove the 4 screws around the rear vent and use to Re-install block off plate and gasket over the rear vent flue.
Step 2. Remove the round flue cover from top venting outlet and all insulation from inside flue inner and outer pipe.
Step 6. Reinstall screws to seal holes in wrapper.
Step 10. Using the 2 screws from the rear vertical baffle, Install the top baffle (shipped in bottom of unit) see photo.
Step 3. Remove all insulation from inside flue inner and outer pipe. Retain insulation.
Step 7. Remove the rear vertical Baffle from top, retain screws but discard baffle. Reinstall screws to seal holes after vertical baffle is removed. Discard the vertical baffle.
Step 11. Ensure flue passage is clear to inside of firebox, and that outer pipe is free of insulation.
Step 4. If rear vent does not have a cap already installed, pack inner and outer pipe with the insulation from top.
Step 8. Remove the 2 screws holding the block off plate and gasket to top vent flue. Retain screws as they will be re-used.
Unit is now ready to install as top-venting fireplace.
20
Innovative Hearth Products
None
1
3
20
40
6
20
40
25 ft Maximum
horizontal run
60 ft Maximum vertical run
60
1.9
25
Horizontal Distance (ft)
Vertical Height (ft)
Vertical Height (ft)
2
5
Elbow
5 10
15
Base + wingBase
6 ft Minimum vertical run
6 ft Minimum vertical run
Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
Install the Vent Restrictor (if necessary)
8.
900004-00, 04/2015
Installation
1. Use the vent run descriptions in Figure 12 to determine if a vent restrictor is necessary.
2. If necessary, assemble the vent restrictor and wing as detailed in Figure 12 and Figure 15.
3. If necessary, install the appropriate vent restrictor (Figure 13 and Figure 14).
NOTE: If installing the vent restrictor in a rear vent application, ensure the factory-installed intake air baffle is in place (Figure 14). NOTE: The vent restrictor is shipped in the firebox.
Figure 12: When to use a vent restrictor Figure 13: Vent restrictor installation, Top vent
*
U-Shaped Vent
Restrictor
Inner
Fireplace
Collar
Appliance Top Vent Outlet
Figure 14: Vent restrictor installation, Rear vent
Inner Fireplace Collar Appliance Rear
INNER FIREPLACE
COLLAR
Intake Air Baffle
*
Figure 15: Vent restrictor assembly
APPLIANCE REAR
Vent Outlet
VENT OUTLET
U-Shaped Vent
U-SHAPED VENT
Restrictor
RESTRICTOR
* For straight runs or runs with elbows as illustrated in Vertical Vent Figures/Tables starting on Page 27.
Vent Restrictor with Vertical Terminations
When vertically terminating the vent system through the roof and using the vent restrictor, install the vent restrictor in the top vent of the fireplace outlet.
If installing more than 6 ft of vertical venting, install the restrictor (Figure 13), from inside or outside the unit, in the inner fireplace collar. The vent restrictor is held in place by friction.
Base Vent Restrictor
Base Vent Restrictor + Wing
21
Innovative Hearth Products
SV4.5E90
(90
°
Elbow)
8 1/8 in.
(206 mm)
Swivel Joint
(360
°
swivel)
4 13/16 in.
(122 mm)
SV4.5E45
(45
°
Elbow)
Swivel Joint
(360
°
swivel)
Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
Vent Restrictor with Horizontal Terminations
When horizontally terminating a vent system with a vertical vent run up to 4 ft through an exterior wall, no vent restrictor is required.
If installing more than 4 ft of vertical venting, install the restrictor (Figure 14), from inside or outside the unit, in the inner fireplace collar. The vent restrictor is held in place by friction.
Table 14: Effective Vent Length
Model Effective Length
SV4.5L6 4 1/2” SV4.5L12 10 1/2” SV4.5L24 22 1/2” SV4.5L36 34 1/2” SV4.5L48 46 1/2”
Connecting the vent pipe
Secure Vent® SV4.5 direct-vent system components are unitized concentric pipe components featuring positive twist lock connections (Figure 16 and Figure 17). All of the fireplaces covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the fireplace/vent collar to create the positive twist lock connection.
1. Align the dimpled end over the collar, adjusting the radial alignment until the four (4) locking dimples are aligned
with the inlet of the four (4) inclined channels on the collar (Figure 16).
2. Push the vent component against the collar until it fully engages, then twist the component clockwise, running
the dimples down and along the incline channels until they seat at the end of the channels.
Installation
900004-00, 04/2015
Vent elbows
NOTE: The unitized design of the Secure Vent® components will engage and seal both the inner and outer vent pipe.
3. If desired, a #6 x 1/2” screw can be used at the joint, but is not required as the pipe will securely lock
when twisted (Figure 17).
Where required, a telescopic vent section (SV4.5LA) may be used to provide the installer with an option to install in tight and confined spaces, or where the vent run made up of fixed length pieces develops a joint in a undesirable location, or will not build up to the required length. The SV4.5LA Telescopic Vent Section has an effective length of from 1 1/2–7” (38–191 mm). The SV4.5LA is fitted with a locking inclined channel end (identical to a normal vent section component) and a plain end with three (3) pilot holes. Slip the plain end over the locking channel end of a standard SV4.5 vent component the required distance and secure with three (3) screws.
Figure 16: Connecting vent
components
Arrow
Dimple
Locking Incline Channel
Appliance Collar or Vent Section
Figure 17: Connected vent
components
Dimple
Locking
Incline
Channel
Arrow
Figure 18: Elbow Dimensions
4 13/16” (122 mm)
Swivel Joint
(360°)
SV4.5E45
(45° elbow)
Swivel Joint
(360°)
SV4.5E90
(90° elbow)
8 1/8” (206 mm)
Vent elbows are available in 90° and 45° configurations. Refer to Figure 18 for the SV4.5E45 and SV4.5E90 elbow dimensions. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element.
1. Rotate the elbow in a clockwise direction (to avoid the possiblity of unlocking any of the previously connected vent sections) for proper alignment (Figure 18). See Connecting the vent pipe for more information.
22
Innovative Hearth Products Superior™ DRT2000 and DRC2000 Direct-Vent Gas Fireplaces
900004-00, 04/2015
Vent section length table
Table 15 will assist calculating how many vent sections are needed for the planned vent configuration. When a vent section is engaged with another section, its effective length will be 1 1/2” shorter.
Table 15: Vent Section Length
Nominal Section
Length (in.)
Net Section Length
(in.)
Height of Vent
in. ft in. ft
4.5 0.375 1 0 0 0 0 1 252 21 0 1 0 7 0 8
9 0.75 2 0 0 0 0 2 276 23 0 0 0 8 0 8
10.5 0.875 0 1 0 0 0 1 279 23.25 0 0 0 0 6 6
15 1.25 1 1 0 0 0 2 280.5 23.375 1 0 0 8 0 9
22.5 1.875 0 0 1 0 0 1 289.5 24.125 0 1 0 0 6 7
31.5 2.625 0 3 0 0 0 3 301.5 25.125 0 0 1 0 6 7
34.5 2.875 0 0 0 1 0 1 310.5 25.875 0 0 0 9 0 9
37.5 3.125 1 1 1 0 0 3 325.5 27.125 0 0 0 0 7 7
43.5 3.625 0 2 1 0 0 3 330 27.5 1 0 0 0 7 8
45 3.75 0 0 2 0 0 2 345 28.75 0 0 0 10 0 10
46.5 3.875 0 0 0 0 1 1 349.5 29.125 1 0 0 10 0 11
51 4.25 1 0 0 0 1 2 372 31 0 0 0 0 8 8
55.5 4.625 0 1 2 0 0 3 379.5 31.625 0 0 0 11 0 11
57 4.75 0 0 1 1 0 2 418.5 34.875 0 0 0 0 9 9
67.5 5.625 0 0 3 0 0 3 465 38.75 0 0 0 0 10 10
69 5.75 0 0 0 2 0 2 475.5 39.625 0 1 0 0 10 11
73.5 6.125 1 0 0 2 0 3 480 40 1 1 0 0 10 12
79.5 6.625 0 1 0 2 0 3 492 41 1 0 1 0 10 12
81 6.75 0 0 0 1 1 2 499.5 41.625 0 0 0 1 10 11
91.5 7.625 0 0 2 0 1 3 504 42 1 0 0 1 10 12
93 7.75 0 0 0 0 2 2 511.5 42.625 0 0 0 0 11 11
97.5 8.125 1 0 0 0 2 3 520.5 43.375 0 2 0 1 11 14
103.5 8.625 0 0 0 3 0 3 531
108 9 1 0 0 3 0 4 538.5 44.875 1 0 0 2 11 14
117 9.75 1 0 5 0 0 6 549 45.75 1 0 2 1 11 15
118.5 9.875 1 1 0 3 0 5 558 46.5 0 0 0 0 12 12
126 10.5 0 0 1 3 0 4 562.5 46.875 1 0 0 0 12 13
130.5 10.875 1 0 1 3 0 5 568.5 47.375 0 1 0 0 12 13
135 11.25 0 0 6 0 0 6 573 47.75 1 1 0 0 12 14
139.5 11.625 0 0 0 0 3 3 580.5 48.375 0 0 1 0 12 13
142.5 11.875 1 0 0 4 0 5 589.5 49.125 0 1 2 2 10 15
144 12 1 0 0 0 3 4 595.5 49.625 1 1 1 0 12 15
154.5 12.875 1 1 0 0 3 5 604.5 50.375 0 0 0 0 13 13
160.5 13.375 0 2 0 0 3 5 615 51.25 0 1 0 0 13 14
172.5 14.375 0 0 0 5 0 5 625.5 52.125 0 2 0 0 13 15
177 14.75 1 0 0 5 0 6 631.5 52.625 1 0 1 0 13 15
186 15.5 0 0 0 0 4 4 637.5 53.125 0 1 1 0 13 15
196.5 16.375 0 1 0 0 4 5 651 54.25 0 0 0 0 14 14
207 17.25 0 0 0 6 0 6 655.5 54.625 1 0 0 0 14 15
211.5 17.625 1 0 0 6 0 7 672 56 0 2 0 0 14 16
217.5 18.125 0 1 0 6 0 7 678 56.5 1 0 1 0 14 16
229.5 19.125 0 0 1 6 0 7 688.5 57.375 1 1 1 0 14 17
232.5 19.375 0 0 0 0 5 5 697.5 58.125 0 0 0 0 15 15
241.5 20.125 0 0 0 7 0 7 702 58.5 1 0 0 0 15 16
246 20.5 1 0 0 7 0 8 712.5 59.375 1 1 0 0 15 17
6 12 24 36 48
4.5 10.5 22.5 34.5 46.5 Net Section Length (in.) 4.5 10.5 22.5 34.5 46.5
Number of Vent Sections
Nominal Section Length
Total Qty
(in.)
Height of Vent
44.25 0 2 2 0 11 15
720 60 0 0 1 0 15 16
6 12 24 36 48
Number of Vent Sections
Installation
Total Qty
23
Loading...
+ 53 hidden pages