Superior DT-400CEN, DR-400CEN, DR-400CMN, DT-400CEP, DT-400CMP User Manual

...
INSTALLATION INSTRUCTIONS
DIRECT VENT
DT-400 & DR-400
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
This appliance may be installed in an aftermar­ket permanently located, manufactured home (USA only) or mobile home, where not prohib­ited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
WARNING: IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO­SION MAY RESULT CAUSING PROPERTY DAM­AGE, PERSONAL INJURY OR LOSS OF LIFE.
VENTED GAS FIREPLACE HEATERS - DIRECT VENT MODELS P/N 700,020M REV. M 11/2004
MODELS
tlovilliM
sledoM
NMC004-TDNEC004-TD PMC004-TDPEC004-TD
NMC004-RDNEC004-RD PMC004-RDPEC004-RD
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUCTIONS DONNÉ DANS CETTE NOTICE POUR RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE BLESSURE OU LA MORT.
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser d'essence ni d'autre vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
cinortcelE
sledoM
• DO NOT light any appliance.
• DO NOT touch any electrical switches.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow your gas suppliers instructions.
• If your gas supplier cannot be reached, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
OTL Report No. 116-F-17-4
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une odeur de gaz:
Ne pas tenter d'allumer d'appareil.
Ne touchez à aucun interrupteur. Ne pas vous servir
des téléphones se trouvant dans le batiment où vous vous trouvez.
Evacuez la piéce, le bâtiment ou la zone.
Appelez immédiatement votre fournisseur de gaz
depuis un voisin. Suivez les instructions du fournisseur.
Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service dos incendies.
L'installation et service doit être exécuté par un qualifié installeur, agence de service ou le fournisseur de gaz.
1
TABLE OF CONTENTS
Packaging ........................................ page 2
Introduction ..................................... page 2
General Information......................... page 2
Location .......................................... page 4
Appliance and Vent Clearances ....... page 4
Vent Termination Clearances ........... page 5
Typical Installation Sequence .......... page 5
Detailed Installation Steps ............... page 5
Step 1. Framing ............................. page 5
Step 2. Routing Gas Line ............... page 5
Fireplace Specifications ................... page 8
Step 3. Install the Venting System. page 8
Vertical Termination Systems .......... page 9
Vent Section Length Chart ............... page 9
Vertical Vent Tables and Figures...... page 12
Horizontal Termination System ........ page 14
Horizontal Vent Tables and Figures . page 16
Venting Using Flexible Vent Pipe ..... page 19
Step 4. Field Wiring ....................... page 20
Step 5. Optional Blower Kit Wiring page 20
Step 6. Connecting Gas Line.......... page 21
Step 7. Installing Logs................... page 22
Step 8. Checking Unit Operation ..... page 22
Step 9. Installing Glass Door ......... page 22
Step 10. Burner Adjustments........... page 23
Step 11. Hood Installation ............... page 23
Finishing Requirements ................... page 23
Cold Climate Insulation.................... page 24
Installation Accessories ................... page 24
Gas Conversion Kits.................. page 26
This installation manual will help you obtain a safe, efficient, dependable installation for your appliance and vent system.
Please read and understand these instructions before beginning your
installation.
PACKAGING
The assembled vented gas fireplace heater is packaged with: 1 -one log set shrink-wrapped to the in-
side surface of the front glass enclo­sure panel.
2 - one plastic bag containing the literature
package which consists of the homeowner's care and operation instructions, installation instructions and warranty; plastic bag lo­cated in the control area.
3 - one vent restrictor for use in top vent appli-
cations; restrictor is taped to the inside of the cabinet bottom.
4 - one hood wrapped in plastic taped to the
front of the top unit standoffs.
5 -one bag of glowing embers located in the
control area.
INTRODUCTION
These vented gas fireplace heaters are sealed combustion, air circulating gas fireplaces de­signed for residential applications. These appli­ances must be installed with the Secure Vent™ and /or Secure Flex™ vent systems routed to the outside atmosphere.
Millivolt appliances are designed to operate on natural or propane gas. A millivolt gas control valve with piezo ignition system provides safe, efficient operation. External electrical power is required to operate the optional blower if in­stalled in these units.
Electronic appliances are designed to operate on natural or propane gas. An electronic inter­mittent pilot ignition system provides safe, efficient operation. External electrical power is required to operate these units.
These millivolt and electronic versions of these appliances are listed by Omni Test Laboratories for installation in bedrooms and mobile homes.
Installation must conform to local codes. In the absence of local codes, installation must com­ply with the current National Fuel Gas Code, ANSI Z223.1. (In Canada, the current CAN-1 B149 installation code.) Electrical wiring must comply with the National Electrical Code ANSI/ NFPA 70 - (latest edition). (In Canada, the current CSA C22-1 Canadian Electrical Code.)
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
GENERAL INFORMATION
Note: Installation and repair should be per-
formed by a qualified service person. The appli­ance should be inspected annually by a quali­fied professional service technician. More fre­quent inspections and cleanings may be re­quired due to excessive lint from carpeting, bedding material, etc. It is imperative that the control compartment, burners and circulating air passage ways of the appliance be kept clean.
S'assurer que le brùleur et le compartiment des commandes sont propres. Voir les instruc­tions d'installation et d'utilisation qui accompagnent l'appareil.
Provide adequate clearances around air open­ings and adequate accessibility clearance for service and proper operation. Never obstruct the front openings of the appliance.
These appliances are designed to operate on natural or propane gas only.
TYPICAL INSTALLATION
Figure 1
2
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Millivolt Models -
Millivolt models come standard with the manually-modulated gas valve; flame ap­pearance and heat output can be con­trolled at the gas valve. Input of millivolt models is shown in the following table:
htiwsledoMtlovilliM
evlaVsaGdetaludoM-yllaunaM
saGenaporPdnalarutaN
srebmuNledoM)H/UTB(etartupnI
004-TD 004-RD
Electronic Models -
Electronic models have a fixed rate gas valve. Input of electronic models is shown in the following table:
evlaVsaG
srebmuNledoM)H/UTB(etartupnI
004-TD 004-RD
All Models -
Maximum manifold pressure is 3.5 in. w.c. (0.87 kPa) for natural gas and 10 in. w.c. (2.49 kPa) for LP/Propane gas.
Installations at Altitudes of 0 to 4500 ft.­Units are tested and approved for elevations of 0 to 4500 feet (0 to 1372 meters).
Installations at Altitudes above 4500 ft.­For elevations above 4500 feet (1372 meters), install the unit according to the regulations of the local authorities having jurisdiction and, in the USA, the latest edition of the National Fuel Gas Code (ANSI Z223.1) or, in Canada, the latest edition of the CAN1-B149.1 and .2 codes.
Table 1
shows the units' gas orifice size for
the elevations indicated.
.oNledoM
larutaNenaporP
005,71ot005,31
etaR-dexiFhtiwsledoMcinortcelE
saGenaporPdnalarutaN
005,71
ezisecifirO
The millivolt appliances are manually controlled and feature a spark ignitor (piezo) that allows the appliance's pilot gas to be lit without the use of matches or batteries. This system provides continued service in the event of a power outage.
Do not use these appliances if any part has been under water. Immediately call a qualified, pro­fessional service technician to inspect the ap­pliance and to replace any parts of the control system and any gas control which have been under water.
Ne pas se servir de cet appareil s'il a été plongé dans l'eau, complètement ou en partie. Appeler un technicien qualifié pour inspecter l'appareil et remplacer toute partie du système de contrôle et toute commande qui ont été plongés dans l'eau.
This appliance may be installed in an af­termarket permanently located, manufac­tured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This ap­pliance is not convertible for use with other gases, unless a certified kit is used.
Cet appareil peut être installé dans un maison préfabriquée (É.-U. seulement) ou mobile déjà installée à demeure si les réglements locaux le permettent. Cet appareil doit être utilisé uniquement avec les types de gaz indiqués sur la plaque signalétique. Ne pas l'utiliser avec d'autres gaz sauf si un kit de con­version certifié est installé.
Test gage connections are provided on the front of the millivolt gas control valve (iden­tified IN for the inlet and OUT for the mani­fold side). A ¹⁄₈" NPT test gage connection is provided at the inlet and outlet side of the electronic gas control valve.
Minimum inlet gas pressure to these appli­ances is 5.0 inches water column (1.24 kPa) for natural gas and 11 inches water column (2.74 kPa) for propane for the purpose of input adjustment.
These appliances must be isolated from the gas supply piping system (by closing their individual manual shut-off valve) during any pressure test­ing of the gas supply piping system at test pressures equal to or less than ¹⁄₂ psig (3.5 kPa).
These appliances and their individual shut-off valves must be disconnected from the gas supply piping system during any pressure test­ing of that system at pressures in excess of ¹⁄₂ psig (3.5 kPa).
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning are similar to the flu with headaches, dizziness and/or nausea. If you have these signs, obtain fresh air immediately. Turn off the gas supply to the appliance and have it serviced by a qualified professional, as it may not be op­erating correctly.
WARNING: FAILURE TO COMPLY WITH THE INSTALLATION AND OPERATING IN­STRUCTIONS PROVIDED IN THIS DOCU­MENT WILL RESULT IN AN IMPROP­ERLY INSTALLED AND OPERATING AP­PLIANCE, VOIDING ITS WARRANTY. ANY CHANGE TO THIS APPLIANCE AND/OR ITS OPERATING CONTROLS IS DANGER­OUS. IMPROPER INSTALLATION OR USE OF THIS APPLIANCE CAN CAUSE SERI­OUS INJURY OR DEATH FROM FIRE, BURNS, EXPLOSION OR CARBON MON­OXIDE POISONING.
WARNING: CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES. USE CAUTION AROUND THE APPLIANCE TO AVOID BURNS OR CLOTHING IGNITION. YOUNG CHILDREN SHOULD BE CARE­FULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
Table 1
004-TD
54#
004-RD
840.0
hcni
Maximum inlet gas supply pressure to these appli­ances is 10.5 inches water column (2.61 kPa) for natural gas and 13.0 inches water column (3.23 kPa) for propane.
WARNING: DO NOT PLACE CLOTHING OR OTHER FLAMMABLE MATERIALS ON OR NEAR THIS APPLIANCE.
AVERTISSEMENT: SURVEILLER LES ENFANTS. GARDER LES VÊTEMENTS, LES MEUBLES, L'ESSENCE OU AUTRES LIQUIDES À VAPEUR INFLAMMABLES À COTE DE L'APPAREIL.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3
REAR VENT
APPLICATION
TOP VENT
APPLICATION
APPLICATION
TOP VENT
INSTALLATION
RECESSED
REAR VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
Figure 2
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important. Consideration should be given to traffic ways, furniture, draperies, etc., due to elevated surface temperatures ( The location should also be free of electrical, plumbing or other heating/air conditioning ducting.
These direct vent appliances are uniquely suited for installations requiring a utility shelf posi­tioned directly above the fireplace. Utility shelves like these are commonly used for locating television sets and decorative plants.
Figure 2
VERTICAL VENT (Rear Vent Application)
HORIZONTAL VENT (Rear Vent Application without a chase)
HORIZONTAL VENT (Rear Vent Application With a chase)
HORIZONTAL VENT (Top Vent Application)
VERTICAL VENT (Top Vent Application)
Typical Locations
.oNledoM
tneVeruceSxelFeruceStneVeruceSxelFeruceS 004-TD 8/144)1211(8/754)5611(A/NA/N 004-RD A/NA/N4/133)548(4/133)548(
woblEeergeD09enOhtiw-tneVpoTkcaBehttuOthgiartS-tneVraeR
).
Do not insulate the
Do not insulate the space between the
appliance and the
area above it.
Shelf Height
(
see table)
space between the
appliance and the
area above it.
Shelf Height
see table)
(
)mm(sehcnithgieHflehS
To provide for the lowest possible shelf surface use the alternate rear vent outlet with attached venting routed in a way to minimize obstruc­tions to the use of the space above the appli­ance. Do not insulate the space between the
appliance and the area above it. See
The minimum height from the base of the appliance to the underside of combustible ma­terials used to construct a utility shelf in this fashion is shown in the table in
Figure 3
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materi­als. However, if installed on combustible ma­terials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bot­tom surface must be used.
4
Figure 3
.
Shelf Above Fireplace With Rear Venting
Figure 3
.
APPLIANCE AND VENT CLEARANCES
The appliance is approved with zero clearance to combustible materials on all sides (as de­tailed in tion: When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit. In addition, when the unit is re­cessed, the side walls surrounding the unit must not extend beyond the front edge of the unit. See
Table 2
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
), with the following excep-
Figure 2
.
Shelf Above Fireplace With Top Venting
KCAB
SEDIS
SRECAPSPOT)mm0(.ni0
ROOLF)mm0(.ni0
mottoBmorF
ottinUfo
gnilieC
TNEV*)mm4.52(.ni1
TNORF)sretem9.0(.teeF3
)mm31(.ni2/1
srecaps)mm0(.ni0
)mm31(.ni2/1
srecaps)mm0(.ni0
)mm6261(.ni46
SECNARAELCECIVRES
VENT TERMINATION CLEARANCES
These instructions should be used as a guide­line and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and ­B149.2 in Canada.
Vertical Vent Termination Clearances
Terminate single vent caps relative to building components according to
TERMINATION HEIGHTS FOR VENTS ABOVE
Horizontal Overhang
2 FT MIN.
Termination
Storm Collar
Flashing
Concentric
Vent Pipe
FLAT OR SLOPED ROOFS
Vent
H*
*H = MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING OF VENT
Figure 4
2 FT MIN.
Lowest
Discharge
Opening
1 inch (25.4 mm) Minimum Clearance to Combustibles
12
Roof Pitch is X/12
hctiPfooR
Vertical
Wall
X
H
.
)teef(
21/6ottalF0.1
21/7ot21/6revO52.1 21/8ot21/7revO5.1 21/9ot21/8revO0.2
21/01ot21/9revO5.2
21/11ot21/01revO52.3
21/21ot21/11revO0.4
Figure 4
Terminate multiple vent terminations accord­ing to the installation codes listed at the top of this page.
Horizontal Vent Termination Clearances
The horizontal vent termination must have a minimum of 3" (76 mm) clearance to any overhead combustible projection of 2 ¹⁄₂" (64 mm) or less. See exceeding 2 ¹⁄₂" (64 mm), see
Figure 5.
For projections
Figure 5
. For
additional vent location restrictions refer to
Figure 7 on page 6
.
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation follows, however, each installation is unique resulting in variations to those described. See the page numbers references in the follow­ing steps for detailed procedures.
Step 1. (page 5) Construct the appliance
framing. Position the appliance within the framing and secure with nailing brackets.
Horizontal Vent Termination Clearances
Combustible Projection
2¹⁄₂ inches or less in length
Combustible Projection
greater than 2¹⁄₂ inches in length
Ventilated
Soffit
Unventilated
Soffit
3"
18"
(457 mm)
See
Figure 31
into exterior walls, of the round and square horizontal terminations.
Figure 5 -
12"
(305 mm)
or 32 for the recess allowances,
Side Elevation View
(76 mm)
Termination Kit
Step 2. (page 5) Route gas supply line to
appliance location.
Step 3. (page 8) Install the vent system and
exterior termination.
Step 4. (page 20) Field Wiring
Millivolt Appliances The operating control
switch is factory installed.
Step 5. (page 20) Install blower kit (optional
equipment).
Step 6. (page 21) Make connection to gas
supply.
Step 7. (page 22) Install the logs, vermicu-
lite and glowing embers.
Step 8. (page 22) Checkout appliance opera-
tion.
Step 9. (page 22) Install glass door frame
assembly.
Step 10. (page 23) Adjust burner to ensure
proper flame appearance.
Step 11. (page 23) Install the hoods.
DETAILED INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and pre-wired. Re­move the shipping carton, exposing the front glass door. Remove the top panel. Remove
the cardboard from underneath the pressure relief plates. Gently depress the outer top
corners of the access panel until the catches "pop" the panel free, allowing it to swing out and down to open. Open the two latches (located under the firebox floor) securing the glass door. Remove the door by tilting it outward at the bottom and lifting it up. Set the door aside protecting it from inadvertent damage.
Figure 50 on page 21.
Remove the two card­board pad strips from between the firebox subfloor and the firebox sides.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
See
Step 1. FRAMING
Frame these appliances as illustrated in
ures 8 on page 7,
installed in a corner. See
unless the appliance is to be
Figure 9 on page 7
for corner framing installations. All framing details must allow for a minimum clearance to combustible framing members as shown in
Table 2 on page 4
. If the appliance is to be elevated above floor level, a solid continuous platform must be constructed. Headers may be in direct contact with the appli­ance top spacers but must not be supported by them or notched to fit around them. All construc­tion above the appliance must be self supporting, DO NOT use the appliance for structural support. The fireplace should be secured to the side framing members using the unit's nailing flanges - one top and bottom on each side of the fireplace front. See
Figure 6.
Use 8d nails or their equivalent.
Side
Framing
Left Side Front Corner of Fireplace Shown
(Right Side Requirements the Same)
Unit Being Secured By Its Nailing Flanges
Note: The nailing flanges, combustible members and screw heads located in areas directly adjacent to the nailing flanges, are EXEMPT from the 1/2 clearance to combustible requirements for the firebox outer wrapper. Combustible framing may be
direct contact with the nailing flanges and may
in be located closer than 1/2 the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact dimensions specified in the framing details of this manual.
To The Framing
Unit Nailing Flange
(No clearance to
combustible
framing is required)
from screw heads and
Fig-
Figure 6
Step 2. ROUTING GAS LINE
Route a ¹⁄₂" (13 mm) gas line along the inside of the right side framing as shown in
Figure 7
Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations.
All appliances are factory-equipped with a flex­ible gas line connector and ¹⁄₂ inch shutoff valve. (See step 6 on page 20).
Right Side
Front Corner of
Fireplace Framing
3"
(76 mm)
6 ¹⁄₂"
(152 mm)
Figure 7
.
5
*
See Item D in the Text Below.
Exterior Wall
Horizontal Termination
B
V
L
X
= Air Supply Inlet
.denepo
ynoclab
EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS
*18
18
Inside Corner
.ynoclabro,kced
lanimretehtfoenil
ecnailpparehto
.sgnillewdhtob
Detail D
F
V
Center Line
of Termination
Ventilated Soffit
V
Fixed
Closed
Window
V
C
A
V
= Vent Terminal = Area where Terminal is not Permitted
C
C
C
,hcrop,adnarev,edargevobaecnaraelC=A
ebyamtahtroodrowodniwotecnaraelC=B
wodniwdesolcyltnenamrepotecnaraelC=C tneverpotdednemmocer)mm503("21
tiffosdetalitnevotecnaraelclacitreV=D
latnozirohanihtiwlanimretehtevobadetacol
retnecehtmorf)mm854(sehcni81foecnatsid
tiffosdetalitnevnuotecnaraelC=E)mm503("21)mm503("21
renrocedistuootecnaraelC=Fmuminim)mc7.21("5muminim)mc7.21("5
renrocedisniotecnaraelC=Gmuminim)mc2.51("6muminim)mc2.51("6
enilretnecfoedisnihcaeotecnaraelC=H
ylbmessarotaluger/retemevobadednetxe
teltuotnevrotalugerecivresotecnaraelC=I*)mc19(teef3**)mc19(teef3
telniylppusrialacinahcemnonotecnaraelC=J
ynaottelnirianoitsubmocehtrognidliubot
telniylppusrialacinahcemaotecnaraelC=K*)m38.1(teef6 )m3(teef01nihtiwfievoba)mc19(teef3
devaproklawedisdevapevobaecnaraelC=L
ytreporpcilbupnodetacolyawevid
rokced,hcrop,adnarevrednuecnaraelC=M
Corner Detail
A
B
V
B
B
Inside
G
V
= 9 in U.S.
A
= 12 in Canada
X
Operable
Window
B
A
J
*noitallatsnInaidanaC**noitallatsnISU
*)mc03(sehcni21**)mc03(sehcni21
secnailpparof)mc51(ni6
noitasnednocwodniw
)mm854("81)mm854("81
secnailpparof)mc51(ni6
)m31.2(teef7 )m31.2(teef7
*)mc03(sehcni21 )mc03(sehcni21
.sedoCsaGleuFlanoitaN45APFN/1.322ZSISNAtnerucehthtiwecnadroccanI**
H
3 ft.
A
3 ft.
I
)mc03(ni21,)Wk3(hutB000,01<
dna)Wk3(hutB000,01>secnailpparof
)mc19(sehcni63,)Wk03(hutB000,001<
*)Wk03(hutB000,001>secnailpparof
noitasnednocwodniw
teef51fothgiehanihtiw)mc19(teef3
*ylbmessarotaluger/retemehtevoba
)mc03(ni21,)Wk3(hutB000,01<
dna)Wk3(hutB000,01>secnailpparof
)mc19(sehcni63,)Wk03(hutB000,001<
*)Wk03(hutB000,001>secnailpparof
**yllatnoziroh
.edoCnoitallatsnIenaporPdnAsaGlanoitaN1.941B-ASCtnerrucehthtiwecnadroccanI*
:roolfehthtaenebsedis2muminimanonepoyllufsiynoclabrokced,hcrop,adnarevfidettimrepylnO‡*
E
D
V
M
V
secnailpparof)mc51(ni6
)mc32(ni9,)Wk3(hutB000,01<
dna)Wk3(hutB000,01>secnailpparof
)mc03(sehcni21,)Wk51(hutB000,05<
**)Wk51(hutB000,05>secnailpparof
tneverpotdednemmocer)mm922("9
teef51fothgiehanihtiw)mc19(teef3
**ylbmessarotaluger/retemehtevoba
secnailpparof)mc51(ni6
)mc32(ni9,)Wk3(hutB000,01<
dna)Wk3(hutB000,01>secnailpparof
)mc03(sehcni21,)Wk51(hutB000,05<
**)Wk51(hutB000,05>secnailpparof
sevresdnasgnillewdylimafelgnisowtneewtebdetacolsihcihwyawevirddevaproklawedisaevobayltceridetanimrettonllahstnevA
Figure 8
6
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
FIREPLACE FRAMING SPECIFICATIONS
Figure 9
**FRAMING WITH SQUARE HORIZONTAL TERMINATIONS (SV4.5HTSSL, SV4.5HTSS or SV4.5HTS)
VENT FRAMING ­TOP VENT WITH ONE 90° ELBOW
VENT FRAMING ­REAR VENT WITH NO ELBOWS
33¹⁄₄ (845)
Inches (mm)
16⁵⁄₈
(422)
33¹⁄₄
(845)
37¹⁄₈
(943)
AND ROUND HORIZONTAL TERMINATION (SV4.5HTR)
10¹⁄₂
(267)
7
(178)
19⁵⁄₈
(498)
*12⁷⁄₈
(327)
5¹⁄₈
(130)
5¹⁄₈
(130)
(178)
7
12¹⁄₈
(308)
12¹⁄₈
(308)
Framing should be constructed of 2x4 or larger lumber.
*12⁷⁄₈ inches (327 mm) is the required
framing depth dimension when the finish
material (drywall) thickness is 1/2 in.
(13mm).
** See the horizontal venting Figures 35 and 36 on page 16 for restrictions on the
use of the round termination (SV4.5HTR)
Note­Venting requirements for rear vent applications in corner installations -
- the round termination (SV4.5HTR) may not be used
- the horizontal vent length “a” to “b, must not exceed 28 inches (711 mm)
Framing should be constructed of
2x4 or larger lumber.
*These dimensions occur when one 45
degree elbow is connected directly to the
appliance collar and the unit moved ¹⁄₂ in.
(13 mm) into the room. This ¹⁄₂ in.
movement is required to achieve a min. of
5 in (127 mm) in the F dimension.
*34⁵⁄₁₆
(872)
SV4.5HTSS & SV4.5HTSSL
Termination
*F = 5 in. (127 mm)
a
33¹⁄₈
(841)
*48¹⁄₂
(1232)
Back wall of chase/enclosure (including any finishing materials)
CORNER FRAMING WITH SQUARE HORIZONTAL
TERMINATIONS (SV4.5HTSSL, SV4.5HTSS or SV4.5HTS)
SV4.5HTS Termination
b
7 (178)
b
8³⁄₁₆ (208)
*24¹⁄₄ (616)
*17³⁄₁₆
(437)
Inches
(millimeters)
Figure 10
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
7
FIREPLACE SPECIFICATIONS
FRAMING SPACERS (Top and Sides
and Rear)
Figure 11
33¹⁄₈
(841)
1
(25)
21¹⁄₂
(546)
10³⁄₄
(273)
Top View
(841)
27¹⁄₂ (699)
Front View
33¹⁄₈
17
(432)
6¹³⁄₁₆ (173)
3 (76)
30¹⁄₈
(765)
(Louvered Front Model Shown)
*CONCENTRIC FLUE
FLUE - 4¹⁄₂ (114)
COMBUSTION AIR - 7¹⁄₂ (190)
*DR models have only a rear vent *DT models have only a top vent
NOTE - Eyebrow hood shown as positioned in louvered front model.
ELECTRICAL INLET 2³⁄₄ x 2 (70 x 51) COVER PLATE with KNOCKOUT)
GAS INLET (Either Side and bottom)
3 (76)
Inches (millimeters)
13
(330)
8¹¹⁄₃₂
(212)
Right Side View
1⁵⁄₈ (42)
(13)
¹⁄₂
1 (25)
**19⁵⁄₈
**Rear vent models only
2³⁄₄
(70)
(498)
Step 3. INSTALL THE VENT SYSTEM
General Information
These instructions should be used as a guide­line and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and ­B149.2 in Canada.
These fireplaces are designed, tested and listed for operation and installation with, and only with, Secure Vent (SV 4.5) Direct Vent System Components, Secure Flex Flexible Vent Components manu­factured by Security Chimneys Interna­tional. These approved vent system com­ponents are labeled for identification.
DO NOT use any other manufacturer's vent components with these appli­ances. These fireplaces must be vented
directly to the outside.
The vent system may not service multiple appliances, and must never be connected to a flue serving a solid fuel burning appliance. The vent pipe is tested to be run inside an enclos­ing wall (such as a chase). There is no require­ment for inspection openings in the enclosing wall at any of the joints in the vent pipe.
Preparing the Appliance Top Vent Outlet in All Venting Applications Using the Appliance Top Vent Outlet
A vent restrictor may be needed with this appliance. Install the vent restrictor (provided) in the appliance top flue outlet as shown in
Figure 12
. It is held in place by friction, only.
VENT RESTRICTOR INSTALLATION
(TOP VENT)
In all venting applications using the top vent of
the appliance, a vent restrictor may be
needed. Install the vent restrictor in the top
vent of the appliance outlet.
If needed, install the restrictor orientated as
shown, either from inside or outside the unit,
in the inner fireplace collar.
RESTRICTOR
INNER
FIREPLACE
COLLAR
APPLIANCE TOP VENT OUTLET
Figure 12
8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Select Venting System - Horizontal or Vertical
With the appliance secured in framing, deter­mine vent routing and identify the exterior termination location. The following sections describe vertical (roof) and horizontal (exterior wall) vent applications. Refer to the section relating to your installation. A list of approved
venting components is shown in the tables on pages 24 and 25.
VERTICAL TERMINATION SYSTEMS (ROOF)
Figures 13, and Figures 23 through 27 on pages 12 to 13
and their associated Vertical Vent Tables illustrate the various ver­tical venting configurations that are possible for use with these appliances. Secure Vent pipe applications are shown in these figures; Secure Flex pipe may also be used. A Vertical Vent Table summarizes each systems mini­mum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications. Both these vertical vent systems terminate through the roof. The minimum vent height above the roof and/or adjacent walls is specified in ANSI Z223.1-(latest edi­tion) (In Canada, the current CAN-1 B149 installation code) by major building codes. Always consult your local codes for specific requirements. A general guide to follow is the Gas Vent Rule (refer to
Figure 4
on page 5).
Vertical (Straight) Installation
Determine the number of straight vent sections required. 4 ¹⁄₂" (114 mm), 10 ¹⁄₂" (267 mm), 22 ¹⁄₂" (572 mm), 34 ¹⁄₂" (876 mm) and 46 ¹⁄₂" (1181 mm) net section lengths are available. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists. Refer to the Vent Section Length Chart.
SV4.5CGV-1 Termination
SV4.5FA OR SV4.5FB Flashing AND SV4.5SC STORM COLLAR
1" (25.4 mm) Minimum Clearance to Combustibles
*SV4.5BF Firestop/Spacer
lanimoN
htgneLnoitceS
621426384
)sehcni(
noitceSteN
2/1-42/1-012/1-222/1-432/1-64
)sehcni(htgneL
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
5.4573.0100001
957.0200002
5.01578.0010001
5152.1110002
5.91526.1210003
1257.1020002
5.22578.1001001
5.52521.2120003
5.13526.2030003
5.43578.2000101
5.73521.3111003
5.34526.3021003
5457.3002002
5.64578.3000011
5.94521.4102003
1552.4100012
5.55526.4012003
7557.4001102
6652.5022004
5.76526.5003003
9657.5000202 27 6103004
5.37521.6100203
5.97526.6010203
1857.6000112
095.7021014
5.19526.7002013
3957.7000022 69 8101204
5.79521.8100023
2015.8200024
5.301526.8000303
801 9100304
4115.9020024
71157.9105006
5.811578.9110305
6215.01001304
5.031578.01101305
53152.11006006
8315.11000404
5.931526.11000033
5.241578.11100405
T O T A L
Q T Y
TRAHCHTGNELNOITCESTNEV
TRAHCHTGNELNOITCESTNEV
noitceSlanimoN
621426384
)sehcni(htgneL
noitceSteN
2/1-42/1-012/1-222/1-432/1-64
)sehcni(htgneL
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
44121100034
0515.21010034
5.451578.21110035
5.061573.31020035
5.271573.41000505
77157.41100506
38152.51010506
6815.51000044
5.091578.51100045
5.691573.61010045
5.502521.71011507
70252.71000606
5.112526.71100607
5.712521.81010607
5.922521.91001607
5.232573.91000055
73257.91100056
5.142521.02000707
6425.02100708 25212010708 46222001708 67232000808
97252.32000066
5.082573.32100809
5.382526.32100067
5.982521.42010067
5.103521.52001067
5.013578.52000909
5135.621009001
5.523521.72000077
0335.72100078 63382010078
54357.8200001001
5.943521.9210001011
27313000088
5.673573.13100089
5.973526.1300011011
5.814578.43000099
32452.531000901
56457.8300000101
T O T A L
Q T Y
40' Max (12.2 M)
Figure 13
SV4.5L6/12/24/36/48 Vent Sections
*When using Secure Flex,
use Firestop/Spacer
SF4.5BF
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
9
Vertical (Offset) Installation
1 inch (25.4 mm) minimum clearance to combustibles
Support Straps (Plumbers tape)
8 feet (2.4 m)
Maximum
Blocking
Analyze the vent routing and determine the quantities of vent sections and number of el­bows required. Refer to Vertical Vent Figures and Tables on page 12 and 13 to select the type of vertical installation desired. Vent sections are available in net lengths of 4 ¹⁄₂" (114 mm), 10 ¹⁄₂" (267 mm), 22 ¹⁄₂" (572 mm), 34 ¹⁄₂" (876 mm) and 46 ¹⁄₂" (1181 mm). Refer to the Vent Section Length Chart on page 9 for an aid in selecting length combinations. Elbows are avail­able in 90° and 45° configurations. Refer to
Figure 18
for the SV4.5E45 and SV4.5E90
elbow dimensional specifications.
Where required, a telescopic vent section (SV4.5LA) may be used to provide the installer with an option in installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location, or will not build up to the required length. The SV4.5LA Telescopic Vent Section has an effective length of from 1 ¹⁄₂" (38 mm) to 7 ¹⁄₂" (191 mm). The SV4.5LA is fitted with a locking inclined channel end (identical to a normal vent section component) and a plain end with 3 pilot holes. Slip the plain end over the locking channel end of a standard SV4.5 vent component the required distance and secure with three screws.
Maintain a minimum 1" (25 mm) clearance to combustible materials for all vertical elements. Clearances for all horizontal elements are 3" (76 mm) on top, 1" (25 mm) on sides and 1" (25 mm) on the bottom.
A. Frame ceiling opening - Use a plumb line
from the ceiling above the appliance to lo­cate center of the vertical run. Cut and/or frame an opening, 10¹⁄₂" x 10¹⁄₂" (267mm x 267mm) inside dimensions, about this cen­ter mark
(Figure 14)
.
10¹⁄₂ Min. (267 mm)
10¹⁄₂ Min. (267 mm)
All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent compo­nents fit over the appliance collar to create the positive twist lock connection.
First Vent Component
Align the dimple (four places) with the opening of the locking incline channel on appliance collar. Twist vent component
clockwise to engage and seal. Dimple Locking
Incline Channel
Appliance collar
Vent / Appliance Collar
Connection
Figure 15
Arrow
Arrow
Align the dimple (four places) of the upper vent section with the opening of the locking incline channel on the lower vent section. Twist vent component clockwise to engage and seal until arrow and dimple align.
Dimple
Locking Incline Channel
Connected
Vent Sections
Vent / Vent Section
Connection
Arrow
Figure 16
To attach a vent component to the appliance collar, align the dimpled end over the collar, adjusting the radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar (
Figure 15
). Push the vent component against the collar until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the channels. The unitized design of the Secure Vent components will engage and seal both the inner and outer pipe without the need for sealant or screws. If desired, a #6 x ¹⁄₂" screw may be used at the joint, but is not required as the pipe will se­curely lock when twisted.
refer to
To add another vent component to a length of vent run, align the dimpled end over the inclined channel end of the previously installed section, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section.
Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels.This seating position
is indicated by the alignment of the arrow and dimple as shown in
Figure 16.
D. Install firestop/spacer at ceiling - Use a
SV4.5BF firestop/spacer at ceiling joists. If there is living space above the ceiling level, the firestop/spacer must be installed on the bot­tom side of the ceiling. If attic space is above the ceiling, the firestop/spacer must be in­stalled on the top side of the joist. Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1" (25 mm) clear­ance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections.
E. Support the vertical vent run sections -
Note - Proper venting support is very impor-
tant. The weight of the vent must not be sup­ported by the firplace in any degree.
Support the vertical portion of the venting sys­tem every 8 feet (2.4m) above the fireplace vent outlet. One method of support is by utilizing field provided support straps (conventional plumber's tape). Secure the plumber's tape to the framing members with nails or screws.
Figure 14
B. Attach vent components to appliance ­Secure Vent SV4.5 direct vent system compo-
nents are unitized concentric pipe components featuring positive twist lock connections (
Figure 15
10
).
Note: An elbow may also be attached to the appliance collar. Attach in the same manner as you would a vent section.
C. Attach vent components to each other -
Other vent sections may be added to the pre­viously installed section in accordance with the requirements of the vertical vent figures and tables.
see
Figure 17
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Loop the tape around the vent, securing the ends of the tape to the framing. If desired, sheet metal screws #6 x ¹⁄₂" length may be used to secure the support straps to the vent pipe. Refer to
Figure 17.
Storm Collar
C
F. Change vent direction to horizontal/inclined run - At transition from or to a horizontal/
inclined run, install the SV4.5E45 and SV4.5E90 elbows in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the re­quired direction of the next vent run element.
Twist elbow sections in a clockwise direction only so as to avoid the possibility of unlocking any of the previously connected vent sec­tions. See
Swivel Joint
(360
Figure 18.
(122 mm)
°
swivel)
SV4.5E45
(45° Elbow)
4 ¹³⁄₁₆"
Swivel Joint
(360
°
swivel)
SV4.5E90
(90° Elbow)
8 ¹⁄₈"
(206 mm)
Figure 18
G. Continue installation of horizontal/inclined sections - Continue with the installation of the
straight vent sections in horizontal/inclined run as described in Step C. Install support straps every 5' (1.52 m) along horizontal/inclined vent runs using conventional plumbers tape.
very important that the horizontal/inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of ¹⁄₄" rise per foot (20 mm per meter) which is
ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level. Use a carpenters level to measure from a constant surface and adjust the support straps as necessary.
It is
D
Framing Dimensions for Roof
Pitch C D 0/12 10¹⁄₂ in. 10¹⁄₂ in.
(267 mm) (267 mm)
6/12 10¹⁄₂ in. 12 in.
(267 mm) (305 mm)
12/12 10¹⁄₂ in. 17 ³⁄₄ in.
(267 mm) (451 mm)
Figure 19
I. Install the roof flashing - Extend the vent
sections through the roof structure. Install the roof flashing over the vent section and posi­tion such that the vent column rises vertically (use carpenters level) (
Figure 20
perimeter to secure flashing or adjust roofing to overlap the flashing edges at top and sides only and trim where necessary. Seal the top and both sides of the flashing with waterproof caulking.
). Nail along
Figure 21
K. Install the vertical termination - The final
step involves installation of the SV4.5CGV-1 Vertical Termination. Extend the vent sections to the height as shown in the "Vertical vent termina­tion section" on page 5. The SV4.5CGV-1 Verti­cal Termination ( same fashion as any other Secure Vent section. Align the termination over the end of the previ­ously installed section, adjusting the radial align­ment until the four locking dimples of the termi­nation are aligned with the inlets of the four incline channels of the last vent section. Push the termination down until it fully engages, then twist the termination clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
Figure 22
) installs in the exact
It is important to maintain the required clear­ances to combustibles: 1" (25 mm) at all sides for all vertical runs; and 3" (76 mm) at the top, 1" (25 mm) at sides, and 1" (25 mm) at the bottom for all horizontal/inclined runs.
H. Frame roof opening - Identify location for
vent at the roof. Cut and/or frame opening per Roof Framing Chart and
Figure 19.
Figure 20
J. Install the storm collar - Install the storm
collar, supplied with the flashing, over the vent/ flashing joint. See collar screw. Slide collar down until it meets the top of the flashing. Tighten the adjusting screw. Apply non-combustible caulking or mastic around the circumference of the joint to pro­vide a water tight seal.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 21.
Loosen the storm
Figure 22
If the vent system extends more than 5' (1.5 m) above the roof flashing, stabilizers may be necessary. Additional screws may be used at section joints for added stability. Guide wires may be attached to the joint for additional support on multiple joint configurations.
11
VERTICAL VENT FIGURES/TABLES
V
H
*Ceiling Firestop/Spacer (SV4.5BF)
**Wall Firestop/Spacer (SV4.5HF)
*When using Secure Flex,
use Firestop/Spacer
SF4.5BF
**When using Secure
Flex, use Firestop/Spacer
SF4.5HF
BELBAT
VM
MUMINI
HmumixaM
teef)sretem(teef)sretem(
1)503.0(5)25.1(
2)016.0(01)1.3(
3)419.0(51)56.4(
4)22.1(02)2.6( V+V
1
)m4.21(teef04=H+
.xaM
H.xaM)m2.6(teef02=
Note: Secure Vent (rigid vent pipe) is shown in the figures; Secure Flex (flexible vent pipe) may also be used.
WARNING: UNDER NO CIRCUMSTANCES MAY SEPARATE SECTIONS OF CONCEN­TRIC FLEXIBLE VENT PIPE BE JOINED TOGETHER.
Note: It is very important that the horizontal/ inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of
meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level.
Note: SV4.5BF (Secure Vent), SF4.5BF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible floor or ceil­ing. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex)firestop/spacer must be used anytime vent pipe passes through a combustible wall.
¹⁄₄
" rise per foot (20 mm per
VM
MUMINI
teef)m(teef)m(
1)503.0(2)16.0(
2)16.0(4 )222.1(
3)419.0(6)68.1(
4)22.1(8)4.2(
Figure 24
-
Rear Vent - ONE 90 DEGREE ELBOW
AELBAT
mumixaMH
.xaM)m4.21(teef04=H+V
.xaM)m4.2(teef8=H
Note: Two 45 degree elbows may be used in place of one 90 degree elbow. The same rise to run ratios, as shown in the venting figures for 90 elbows, must be followed if 45 degree elbows are used.
*Ceiling
Firestop/Spacer
(SV4.5BF)
Figure 23
12
40 feet (12.2 meters)
Maximum
*When using
Secure Flex, use
Firestop/Spacer
SF4.5BF
- Top Vent - STRAIGHT
H
*Ceiling
Firestop/Spacer
(SV4.5BF)
*When using Secure Flex,
V1
Firestop/Spacer
**When using Secure
Flex, use Firestop/Spacer
SF4.5HF
Figure 25
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
-
Top Vent - TWO 90 DEGREE ELBOWS
use Firestop/Spacer
**Wall
(SV4.5HF)
*Ceiling
Firestop/Spacer
(SV4.5BF)
SF4.5BF
V
VERTICAL VENT FIGURES/TABLES
(continued)
DELBAT
muminiMVmumixaMHH+H
teef)m(teef)m(teef)m(
1)503.0(2)016.0(5)25.1(
2)016.0(4)22.1(01)1.3(
3)419.0(6)68.1(51)56.4(
4)22.1(8)84.2(02)2.6( H+H+
V+V
1
1
H+H
1
Figure 26
- Rear Vent - THREE ELBOWS
H1
1
.xaM)m84.2(teef8=H
mumixaM
*Ceiling
Firestop/Spacer
(SV4.5BF)
**Wall
Firestop/Spacer
.xaM)m4.21(teef04=
V1
(SV4.5HF)
.xaM)m2.6(teef02=
V
*When using Secure Flex,
use Firestop/Spacer
SF4.5BF
**When using Secure
Flex, use Firestop/Spacer
SF4.5HF
A Vent Restrictor, as
shown in Figure 18,
page 10, must be used
in this application
*Ceiling
Firestop/Spacer
(SV4.5BF)
H
VM
MUMINI
teef)m(teef)m(
1)503.0(5)25.1(
2)016.0(01)1.3(
3)419.0(51)56.4(
4)22.1(02)2.6( H+H
1
H+H+
V+V
1
1
Figure 27 -
Top Vent - THREE ELBOWS
HH+
EELBAT
1
mumixaM
.xaM)m2.6(teef02=
.xaM)m4.21(teef04=
V
1
*When using Secure Flex,
use Firestop/Spacer
**When using Secure
Flex, use Firestop/Spacer
H
1
SF4.5BF
SF4.5HF
*Ceiling Firestop/Spacer (SV4.5BF)
H
**Wall Firestop/Spacer (SV4.5HF)
V
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
13
HORIZONTAL (OUTSIDE WALL) TERMINATION SYSTEM
Figures 28, and Figures 34 to 41 on pages 16 to 18
and their associated Horizontal Vent Table illustrate the various horizontal venting configura­tions that are possible for use with these appli­ances. Secure Vent pipe applications are shown in these figures; Secure Flex pipe may also be used. A Horizontal Vent Table summarizes each system’s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications. Both of these horizontal vent systems terminate through an outside wall. Building Codes limit or prohibit terminating in specific areas. Refer to
Figure 8
on page 6 for location guidelines.
Secure Vent SV4.5 direct vent system compo-
nents are unitized concentric pipe components featuring positive twist lock connection, (
Figure 15
on page 10). All of the appliances
covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the appliance collar to create the positive twist lock connection.
A. Plan the vent run - Analyze the vent routing and determine the types and quantities of sections required 4 ¹⁄₂" (114 mm), 10 ¹⁄₂" (267 mm), 22 ¹⁄₂" (572 mm), 34 ¹⁄₂" (876 mm) and 46 ¹⁄₂" (1181 mm) net section lengths are available. Make allow­ances for elbows as indicated in
page 10
. Maintain a minimum 1" (25 mm) clearance to combustibles on the vertical sections. Clearances for the horizontal runs are; 3" (76 mm) on top, 1" (25 mm) on sides, and 1" (25 mm) at the bottom.
B. Frame exterior wall opening -
Locate the center of the vent outlet on the exterior wall according to the dimensions shown in page 7. Cut and/or frame an opening, 10¹⁄₂" x 12¹⁄₈" (267 mm x 308mm) inside dimensions, about this center.
C. Frame ceiling opening - If the vertical route is to penetrate a ceiling, use plumb line to locate the center above the appliance. Cut and/or frame an opening, 10¹⁄₂" x 10¹⁄₂" (267 mm x 267 mm) inside dimensions, about this center (refer to
Figure 14
on page 10 ).
D. Attach vent components to appliance - To
attach a vent component to the appliance collar, align the dimpled end over the collar, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels on the collar (
refer to Figure 15
page 10). Push the vent component against the collar until it fully engages, then twist the com­ponent clockwise, running the dimples down and along the incline channels until they seat at the end of the channels. The unitized design of the Secure Vent components will engage and seal both the inner and outer pipe elements with the same procedure.
14
refer to
Figure 18 on
Figure 9
on
on
Building
Support
Framing
SV4.5E90
Elbow
Vertical
Rise
Support
Brackets
Ceiling
TYPICAL HORIZONTAL VENT INSTALLATION
Horizontal / Inclined Run
*Ceiling
Firestop/Spacer
(SV4.5BF)
*When using Secure Flex
use Firestop/Spacer
See Figure 17 on page 10
Fireplace
for vertical vent section
support.
Figure 28
Sealant and securing screws are not required.
Note: An elbow may also be attached to the appliance collar. Attach in the same manner as you would a vent section.
E. Attach vent components to each other -
Other vent sections may be added to the previ­ously installed section in accordance with the requirements of the vent tables. To add another vent component to a length of vent run, align the dimpled end of the component over the inclined channel end of the previously installed section, adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section. Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels.This seating position is
indicated by the alignment of the arrow and dimple as shown in
F. Install firestop/spacer at ceiling -
When using Secure Vent, use SV4.5BF fir­estop/spacer at ceiling joists; when using Se­cure Flex, use SF4.5BF firestop/spacer. If there is living space above the ceiling level, the fir­estop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/ spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and se­cure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1" (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections.
G. Support the vertical run sections -
On the vertical run, support the venting system every 8 feet (2.4m) above the fireplace vent outlet with field provided support straps (Plumber's tape). pipe and secure to the framing members with nails or screws. See
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 16 on page 10.
Attach the straps to the vent
Figure 17 on page 10.
SV4.5HTSSL
Termination
Shown
SV4.5L6/12/24/36/48
Support Bracket Spacing Every 5 ft (1.52 m)
(SF4.5BF)
Firestop/Spacer
Vent Sections
Fireplace
Exterior Wall
SV4.5HTSSL
Termination
Shown
Exterior Wall
H. Change vent direction - At transition from
or to a horizontal/inclined run, install the SV4.5E45 and SV4.5E90 elbows in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element. Twist
elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking any of the previously connected vent sec­tions. See
Figure 18 on page 11
I. Continue installation of horizontal/inclined sections - Continue with the installation of the
straight vent sections in horizontal/inclined run as described in Step E. Install support straps every 5 ft. (1.52 m) along horizontal/ inclined vent runs using conventional plumber’s tape. See
Figure 28.
It is very important that the horizontal/inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of ¹⁄₄" rise per foot (20 mm
per meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level. Use a carpenter’s level to measure from a constant surface and adjust the support straps as necessary.
It is important to maintain the required clear­ances to combustibles: 1" (25 mm) at all sides for all vertical runs; and 3" (76 mm) at the top, 1" (25 mm) at sides, and 1" (25 mm) at the bottom for all horizontal/inclined runs.
J. Assemble vent run to exterior wall - If not
previously measured, locate the center of the vent at the exterior wall. Prepare an opening as described in Step B
When using square (SV4.5 HTS), short square (SV4.5 HTSS) or round (SV4.5HTR) horizon­tal termination -
Assemble the vent system to point where the terminus of the last section is within 6 in. (152 mm) to 10¹⁄₄ in. (260 mm) inboard of the exterior surface to which the termination is to be attached, see
Figure 31 on page 15
.
.
Siding
Stucco
1¹⁄₄" Maximum Recess of Square Termination into Exterior Finishing Material
Exterior Surface of Framing
Exterior Surface of Siding
Minimum wall thickness
*10³⁄₄ in. (273 mm)
Interior Surface of
Finished Wall
Maximum wall thickness
20 in. (508 mm)
Maximum Extent of Vent Run Sections Relative to Exterior Surface of Framing
Last Vent Section
SV4.5HTSSL Long Square Termination
*When using Secure Flex, use
Firestop/Spacer SF4.5HF.
Termination Securing
Screw
SV4.5HTSSL Long Square Termination
*Cut termination collar
for wall thicknesses
less than 10³⁄₄ in. (273 mm).
10³⁄₄ to 20 in.
(273 to 508 mm)
*Note - Firestop/Spacer
(SV4.5HF) required, but not
shown for clarity.
If the terminus of the last section is not within this distance, use the telescopic vent section SV4.5LA, as the last vent section. For wall thicknesses greater than that shown in
31
, refer to
table 3 on page 16
. This table lists
Figure
the additional venting components needed (in addition to the termination and adapter) for a particular range of wall thicknesses.
When using long square (SV4.5HTSSL) horizontal termination -
Assemble the vent system to point where the terminus of the last section is within 0 in. (0 mm) to 9³⁄₄ in. (248 mm) inboard of the exterior surface to which the termination is to be attached, see
Figure 32
.
K. When using square (SV4.5HTS) or short square (SV4.5 HTSS) horizontal termination
- attach termination adapter -
Attach the adapter (adapter - SV4.5RCH - pro­vided with the termination) to the vent section or telescoping vent section), elbow or appliance collar as shown in
Figure 29
in the same manner
as any SV4.5 vent component (refer to Step E).
L. Install Firestop/Spacer at exterior wall - When using either of the square terminations, install SV4.5HF (Secure Vent), or SF4.5HF (Secure Flex) firestop/spacer over the opening at the exterior side of the framing, long side up, with the 3 inch spacer clearance at the top as shown in
Figure 29 or 30
, and nail into place. (The Firestop/Spacer may be installed over the opening at the interior side of the framing.) When using the round termination, a separate firestop/spacer is not required since this termi­nation has integral spacers which provide the same function as a separate firestop/spacer.
*Firestop/Spacer (SV4.5HF) shown
on the exterior side of the wall. It
may also be installed on the
*Note - Firestop/Spacer integral
*Note - When using Secure Flex
Round Termination (SV4.5HTR).
interior side.
with round termination
(SV4.5HTR)
use Firestop/Spacer SF4.5HF
See Venting Figures for Use
Restrictions on the Horizontal
6 to 48 inch Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Installing Square HorizontalTermination (SV4.5HTS) Short Square Horizontal
Figure 29
*Firestop/Spacer (SV4.5HF) shown
on the exterior side of the wall. It
may also be installed on the
interior side.
Note: Centerline of Vent Piping is
NOT the Same as the Centerline of
the Framed Opening.
See Figure 9 on page 7
for Min. Distance to
Base of Appliance.
Base of Appliance
6 to 48 inch Vent Section, Elbow or Appliance Collar
*When using Secure Flex, use
Firestop/Spacer (SF4.5HF)
Termination (SV4.5HTSS) Round Horizontal Termination (SV4.5HTR)
Figure 30
SV4.5 HTSS Termination
Shown.
10¹⁄₂"
(267 mm)
(76 mm)
1"
(25.4 mm)
See Figure 9 on page
7 for Min. Distance to
Base of Appliance.
(76 mm)
1"
(25.4 mm)
Adapter
SV4.5RCH
Note: Centerline of Vent
Piping is NOT the Same as
the Centerline of the
Framed Opening.
10¹⁄₂"
(267 mm)
5¹⁄₈"
(130 mm)
5¹⁄₈"
(130 mm)
7"
(178)
12¹⁄₈"
(308 mm)
Base of Appliance
SV4.5 HTSSL
Termination
7"
(178)
12¹⁄₈"
(308 mm)
Installing Long Square HorizontalTermination (SV4.5HTSSL)
3"
3"
*Note - Firestop/Spacer
(SV4.5HF) required, but
not shown for clarity.
Interior Surface of Finished Wall Maximum Extent of
Vent Run Sections Relative to Exterior Surface of Framing
Last Vent Section. Use Telescopic Vent Section (SV4.5LA), If Necessary
Adapter
SV4.5RCH
Siding
Stucco
SV4.5HTSS Short Square
Termination Shown
Figure 31
Minimum wall thickness
*6 in. (152 mm)
Maximum wall thickness
10¹⁄₄ in. (260 mm)
Exterior Surface of Siding
Exterior Surface of Framing
6 in. to 10¹⁄₄ in.
(152 mm to 260 mm)
*Cut termination collar
for wall thicknesses
less than 6 in. (152 mm).
SV4.5HTSS Short
Square Termination
Shown
1¹⁄₄" Maximum Recess of Square Termination into Exterior Finishing Material. Round Termination may not be recessed at all.
*When using Secure Flex, use
Firestop/Spacer SF4.5HF
Connecting/Recessing
Square (SV4.5HTS)
Short Square (SV4.5HTSS)
or Round (SV4.5HTR)
Horizontal Termination
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 32
Connecting/Recessing
Long Square Horizontal
Termination (SV4.5HTSSL)
15
M. Install the desired termination - See the horizontal venting figures for application re­strictions on the round termination (SV4.5HTR).
1. Install the square (SV4.5HTS) or short square termination (SV4.5HTSS) - For the last step ,
from outside the exterior wall, slide the collars of the termination into the adapter (see
Figure 31
until the termination seats against the exterior wall surface to which it will be attached. Orient the housing of the termination with the arrow pointed upwards. Secure the termination to the exterior wall. The horizontal termination must not be recessed into the exterior wall or siding by more than the 1 ¹⁄₄" (32 mm) as shown in
Figure 31
.
2. Install the long square termination (SV4.5HTSSL) - For the last step , from outside
the exterior wall, slide the collars of the termi­nation onto the last vent section (see
Figure 32
until the termination seats against the exterior wall surface to which it will be attached.
Orient the housing of the termination with the arrow pointed upwards. Secure the termina­tion to the exterior wall. The horizontal termi-
nation must not be recessed into the exterior wall or siding by more than the 1 ¹⁄₄" (32 mm)
as shown in
)
3. Install the round termination (SV4.5HTR) – See
Figure 32
Figure 33
.
for an illustration of the round termination. For the last step, from outside the exterior wall, slide the collars of the termina­tion onto the adapter (same as shown in
ure 31
for the SV4.5HTSS short square termi­nation) until the termination seats against the exterior wall surface to which it will be at­tached. Orient the housing of the termination with the arrow pointed upwards. Secure the termination to the exterior wall.
)
Fig-
The SV4.5HTR Round Termination may not be used when the appliance is vented di­rectly out the wall from the rear as shown in
Figures 34 and 35
.
Do Not recess the SV4.5HTR round termina­tion at all.
See Horizontal Venting Figures and Tables for Use Restrictions
SV4.5HTR Horizontal
Figure 33
Round Termination
SFHRK Snorkel Cap –The snorkel cap is de-
signed to be fitted into a basement window box. The SFHRK cap is for use with flex vent The vertical distance between the inlet and outlet of the cap is 28 in. (711 mm). pipe.
HORIZONTAL VENT FIGURES/TABLES
roiretxEsuoiraVrofderiuqeRstnenopmoCgnitneV-3ELBAT
-stiKnoitanimreTesehTfoynAgnisUnehW,sessenkcihTllaW
noitanimreTerauqSllamS)STH5.4VS(noitanimreTerauqS
stnenopmoCgnitneV
deriuqeR
ylnOtiKnoitanimreT64/101ot)062ot251(
tnev.ni6dnatiKnoitanimreT
)6L5.4VS(noitces
tnev.ni21dnatiKnoitanimreT
)21L5.4VS(noitces
cipocseleTdnatiKnoitanimreT
.ni6dna)AL5.4VS(noitces
)6L5.4VS(noitcestnev
*Note: See Figure 35 for wall thickness range reductions when using SV4.5HTS and SV4.5HTSS terminations.
28 in. (711 mm)
Maximum
20 in. (508 mm)
Maximum
)RTH5.4VS(noitanimreTdnuoR)SSTH5.4VS(
sessenkcihTllaWroiretxE
mm(sehcni )
)573ot062(4/341ot4/101
)725*ot524(4/302*ot4/361
)255*ot892(4/312*ot4/311
Note: Secure Vent components (rigid vent pipe and terminal) are shown in the figures; Secure Flex components (flexible vent pipe and terminal) may also be used.
Note: SV4.5BF (Secure Vent), SF4.5BF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible floor or ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible wall.
Note: Two 45 degree elbows may be used in place of one 90 degree elbow. The same rise to run ratios, as shown in the venting figures for 90 elbows, must be followed if 45 degree elbows are used.
Note: It is very important that the horizontal/inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated
¹⁄₄
plane, in a direction away from the fireplace of
" rise per foot (20 mm per meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level.
WARNING: UNDER NO CIRCUMSTANCES MAY SEPARATE SECTIONS OF CONCENTRIC FLEXIBLE VENT PIPE BE JOINED TOGETHER.
28 in. (711 mm)
Maximum.
10³⁄₄ to 20 in.
(273 to 508 mm)
*When using Secure Flex,
use Firestop/Spacer
(SF4.5HF)
*Wall Firestop/Spacer
SV4.5HTSS Termination Shown
Note - In applications where the wall thickness is less than 6 inches
(152 mm), field shortening of the termination collar may be required.
See
Table 3
as an aid in venting component selection for a particular
(SV4.5HF)
range of exterior wall thicknesses.
The round horizontal termination (SV4.5HTR) may not be used.
Figure 34
Rear Vent - NO ELBOWS - with SV4.5HTS SQUARE OR
­SV4.5HTSS SHORT SQUARE TERMINATION
16
Note - It may be necessary to cut the termination collar
The round horizontal termination (SV4.5HTR) may not be used.
Figure 35
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
-
*Wall Firestop/Spacer
(SV4.5HF)
12 in. Vent Section
(SV4.5L12)
in some applications.
*When using Secure flex,
use Firestop/Spacer
SF4.5HF)
Rear Vent - NO ELBOWS - with SV4.5HTSSL LONG SQUARE TERMINATION
HORIZONTAL VENT FIGURES/TABLES (CONTINUED)
ELBATF
wobleeerged09en0=V
.xaM)m419.0(teef3=H
Refer to particular range of exterior wall thicknesses when using the square (SV4.5HTS), small square (SV4.5HTSS) or the round (SV4.5HTR) termination .
Short Square Termination (SV4.5HTSS) shown; Long Square Termination (SV4.5HTSSL) may also be used; Square Termination (SV4.5HTS) may also be used Round Termination (SV4.5HTR) may also be used.
Table 3 on page 16
for an aid in venting component selection for a
H
*Wall Firestop/Spacer
(SV4.5HF)
*When using Secure Flex, use Wall Firestop/Spacer SV4.5HF.
V
Figure 36
-
Top Vent - ONE 90 DEGREE ELBOW - ELBOW CONNECTION AT APPLIANCE
ELBATG
muminiMVmumixaMH
teef)m(teef)m(
1)503.0(5)25.1(
2)16.0(01)1.3(
3)419.0(51)56.4(
4)22.1(02)2.6( .xaM)m4.21(teef04=H+V
.xaM)m2.6(teef02=H
Table 3 on page 16
Refer to for a particular range of exterior wall thicknesses when using the square (SV4.5HTS), small square (SV4.5HTSS) or the round (SV4.5HTR) termination .
Short Square Termination (SV4.5HTSS) shown; Long Square Termination (SV4.5HTSSL) may also be used; Square Termination (SV4.5HTS) may also be used Round Termination (SV4.5HTR) may also be used.
*When using Secure Flex,
use Wall Firestop/Spacer
SF4.5HF.
for an aid in venting component selection
H
HELBAT
muminiMVmumixaMHH+H
1
teef)m(teef)m(teef)m(
1)503.0(2)016.0(5)25.1(
2)016.0(4)22.1(01)1.3(
3)419.0(6)68.1(51)56.4(
4)22.1(8)84.2(02)2.6( H+H+V
Refer to
Table 3 on page 16
1
H+H
1
for an aid in venting component selection for a
.xaM)m84.2(teef8=H
.xaM)m2.6(teef02=
particular range of exterior wall thicknesses when using the square (SV4.5HTS), small square (SV4.5HTSS) or the round (SV4.5HTR) termination .
Short Square Termination (SV4.5HTSS) shown; Long Square Termination (SV4.5HTSSL) may also be used; Square Termination (SV4.5HTS) may also be used Round Termination (SV4.5HTR) may also be used.
H
1
H
mumixaM
.xaM)m4.21(teef04=
*Wall Firestop/Spacer
(SV4.5HF)
**Ceiling Firestop/Spacer
(SV4.5BF)
**When using Secure Flex, use Ceiling
Firestop/Spacer SF4.5BF.
Figure 37
-
Top Vent - ONE 90 DEGREE ELBOW -
ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
*Wall
Firestop/Spacer
V
*When using Secure
Flex, use Wall
Firestop/Spacer
SF4.5HF.
**When using Secure
Flex, use Ceiling
Firestop/Spacer
SF4.5BF.
Figure 38
-
V
Rear Vent - TWO 90 DEGREE ELBOWS
(SV4.5HF)
**Ceiling
Firestop/Spacer
(SV4.5BF)
*Wall
Firestop/Spacer
(SV4.5HF)
17
HORIZONTAL VENT FIGURES/TABLE (CONTINUED)
VM
JELBAT
MUMINI
H+H
1
Refer to wall thicknesses when using the square (SV4.5HTS), small square (SV4.5HTSS) or the round (SV4.5HTR)
mumixaM
termination .
Table 3 on page 16
for an aid in venting component selection for a particular range of exterior
teef)m(teef)m(
1)503.0(5)25.1(
2)016.0(01)1.3(
3)419.0(51)56.4(
4)22.1(02)2.6( H+H+V
1
H+H
1
Short Square Termination (SV4.5HTSS) shown; Long Square Termination (SV4.5HTSSL) may also be used; Square Termination (SV4.5HTS) may also be used Round Termination (SV4.5HTR) may also be used.
Figure 39
-
Top Vent - TWO 90 DEGREE ELBOWS
.xaM)m4.21(teef04=
.xaM)m2.6(teef02=
*When using Secure Flex,
use Wall Firestop/Spacer
SF4.5HF.
**When using Secure
Flex, use Ceiling
Firestop/Spacer
SF4.5BF.
KELBAT
H+H
muminiMVmumixaMH
teef)m(teef)m(teef)m(
1)503.0(2)016.0(5)25.1(
2)016.0(4)22.1(01)1.3(
3)419.0(6)68.1(51)56.4(
4)22.1(8)84.2(02)2.6( H+H+V
1H+2
H+H
1H+2
Refer to
Table 3 on page 16
for an aid in venting component selection for a particular range of exterior wall thicknesses when using the square (SV4.5HTS), small square (SV4.5HTSS) or the round (SV4.5HTR) termination .
Short Square Termination (SV4.5HTSS) shown; Long Square Termination (SV4.5HTSSL) may also be used; Square Termination (SV4.5HTS) may also be used Round Termination (SV4.5HTR) may also be used.
Figure 40
- Rear Vent - THREE 90 DEGREE ELBOWS
1H+2
mumixaM
*When using Secure Flex, use Wall Firestop/Spacer
SF4.5HF.
.xaM)m4.21(teef04=
.xaM)m84.2(teef8=H
.xaM)m2.6(teef02=
**When using Secure Flex, use Ceiling Firestop/Spacer
SF4.5BF.
*Wall Firestop/Spacer
(SV4.5HF)
H
H
1
*Wall Firestop/Spacer
(SV4.5HF)
**Ceiling
Firestop/Spacer
(SV4.5BF)
*Wall Firestop/Spacer
(SV4.5HF)
H
1
H
2
**Ceiling Firestop/Spacer
(SV4.5BF)
V
H
V
LELBAT
VM
MUMINI
teef)m(teef)m(
1)503.0(5)25.1(
2)016.0(01)1.3(
3)419.0(51)56.4(
4)22.1(02)2.6( H+H
1
V+V
H+H+
1
1
Refer to
Table 3 on page 16
particular range of exterior wall thicknesses when using the square (SV4.5HTS), small square (SV4.5HTSS) or the round (SV4.5HTR) termination .
Short Square Termination (SV4.5HTSS) shown; Long Square Termination (SV4.5HTSSL) may also be used; Square Termination (SV4.5HTS) may also be used Round Termination (SV4.5HTR) may also be used.
Figure 41
-
Top Vent - THREE 90 DEGREE ELBOWS
18
HmumixaM
.xaM)m2.6(teef02=
.xaM)m4.21(teef04=
for an aid in venting component selection for a
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
H
*Wall Firestop/spacer
(SV4.5HF)
*When using Secure Flex,
use Wall Firestop/spacer
SF4.5HF.
1
V
1
*Wall Firestop/spacer
(SV4.5HF)
**When using Secure flex,
use Ceiling Firestop/spacer
SF4.5BF.
**Ceiling Firestop/spacer
(SV4.5BF)
H
V
5" (127 mm)
Radius Minimum
SF-12 or SF-18 Flexible Vent Section
VERTICAL OR HORIZONTAL VENTING USING
SECURE FLEX
Secure Flex venting kits and components may
be used in any venting application where rigid Secure Vent (SV4.5) direct vent components can be used. All restrictions, clearances and allowances that pertain to the rigid piping apply to the flexible venting.
not be modified; also, under no circumstances may separate sections of flex pipe be joined together. Secure Flex kits may be added to the
end of a vent run made up of rigid Secure Vent (SV4.5) vent sections provided that doing so does not violate any of the venting length, height, routing, horizontal to vertical ratio re­quirements or clearance considerations de­tailed in this manual.
Secure Flex kits come with an included adapter that can be fitted to the appliance collar or the inclined channel end of the last Secure Vent (SV4.5) vent section in a rigid system in the exact same fashion as any other Secure Vent section. Align the dimpled end of the adapter over the previously installed section or appli­ance collar, adjusting the radial alignment until the four locking dimples of the adapter are aligned with the inlets of the four incline chan­nels of the last vent section or collar. Push on the adapter until it fully engages, then twist the adapter clockwise running the dimples down and along the incline channels until they seat at the end of the channels.
Attach the flexible vent to the adapter as follows (see also
A. Install the Inner Flex Pipe -
1. Install the small gear clamp loosely around
the inner flexible vent pipe, push it back out of the way.
2. Apply a bead of Mill-Pac Black (700°F) high temperature sealant - Catalog No. 10K81) to the inner adapter collar, approxi-
mately ¹⁄₂ inch from the end.
3. Pull and extend the inner flexible vent pipe.
4. Slide the inner flex pipe over the adapter
collar. Ensure the flexible vent pipe completely engages the adapter collar to a distance of 1³⁄₄ inches from the end, and that it is free from damage or tears.
5. Slide the gear clamp down and tighten it fully to secure the flexible vent to the adapter inner collar approximately ³⁄₄ inch from the end of the flex.
6. Install three screws 120 degrees apart through the flexible vent pipe and into the adapter collar just below the gear clamp to provide additional security to the connection.
KITS AND COMPONENTS
Secure Flex
kits may
Figure 42):
NOTE: OUTER PIPE IS PULLED AWAY TO SHOW THE DETAIL OF THE INNER PIPE
Apply ONLY MIL-PAC BLACK HIGH TEMPERATURE SEALANT (Catalog No. 10K81) to the outside surface of both collars of the adapter (be especially careful to fill the grooves of the outer collar to be covered by the flexible pipe) and slide flexible pipe over inner and outer adapter collars.
1³⁄₄ in. (44 mm)
Flexible Pipe and
Adapter Outer Collar Overlap
Adapter
(SV4.5RF)
Attach Adapter to Appliance
Figure 42
Collar, or Secure Vent Sections
B. Install the Outer Flex Pipe -
1. Install the large gear clamp loosely around
the outer flexible vent pipe, push it back out of the way.
2. Apply a bead of Mill-Pac Black (700
°F) high
temperature sealant - Catalog No. 10K81) to the outer adapter collar; to the grooves of the collar which extend approximately 1 inch from the end and to the flat surface, approximately 1³⁄₈ inches from the end.
3. Pull and extend the outer flexible vent pipe.
4. Slide the outer flex pipe over the adapter
collar. Ensure the flexible vent pipe completely engages the adapter collar to a distance of 1³⁄₄ inches from the end, and that it is free from damage or tears.
5. Slide the gear clamp down and tighten it fully to secure the flexible vent to the adapter outer collar approximately ³⁄₄ inch from the end of the flex.
6. Install three screws 120 degrees apart through the flexible vent pipe and into the adapter collar just below the gear clamp to provide additional security to the connection.
C. Route Flex Vent -
Ensure that the flex vent is properly routed to provide the required clearance. Do Not allow the flexible vent to bend in a radius tighter than 5" (127 mm). Refer to
Figure 43
. Support horizontal sections of flex with metal straps at 2 foot (0.61 m) intervals.
FLEX VENT
SECURING SCREW
(3 PLACES EQUIDISTANT
JUST BELOW GEAR CLAMP)
GEAR CLAMPS
1³⁄₄ in. (44 mm)
Flexible Pipe and
Adapter Inner Collar Overlap
SECURING SCREW
(3 PLACES EQUIDISTANT
JUST BELOW GEAR CLAMP)
D. Install Firestop/Spacers at ceilings and walls -
When Secure Flex penetrates a wall or ceiling, a firestop/spacer is required: use the SF4.5 BF firestop/spacer for ceilings and the SF4.5 HF firestop/spacer for walls. See the appropriate sections and figures shown throughout the venting section for their installation requirments.
Figure 43
E. Attach Flex Vent to Termination ­Secure Flex components can be purchased
separately and attached to bulk lengths of Secure Flex flexible tubing cut to size at the job site. Secure the flexible vent to the Secure
Flex terminations in the same manner (see
Figure 42)
Note:
Secure Flex
substitute
Secure Vent
nents. The collars of tions and adapters have a different circum­ference than that used with the pipe. Additionally, have an extended length center tube for use in attaching the flexible vent.
as it was attached to the adapter.
Secure Flex
vent must be attached to
terminations only. DO NOT
Secure Vent
adapter for
terminations or the
Secure Flex
Secure Flex
Secure Flex
compo-
termina-
Secure Vent
components
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
19
1. If any of the original wire as supplied must be replaced,
1. it must be replaced with Type AWM 105°C – 18 GA. wire.
2. 120V, 60Hz – Less than 3 amps.
BK
Junction Box
Transf.
120 V.
24 V
Factory Wired Field Wired
BL
Electronic Wiring Diagram (Honeywell)
Showing the Blower Wiring for the Optional
FBK-100 and FBK-200 Kits
R
W
BL
OPT
BLOWER
G
W
*OPTIONAL
ACCESSORY
SWITCH
120
VAC.
BK
W
Gas Valve
B
R
IGNITER
PILOT
ASSEMBLY
Break Off
Tab
BK
G
*Blower speed control switch is provided in FBK200 blower kit.
Outlet Box
Green Ground
Screw
Hot side of Outlet
Schematic Representation Only
**ON/OFF Switch (Integral
with Gas Valve)
**Leave the ON/OFF switch, which is integral
with the gas valve, in the ON position.
OPTIONAL APPLIANCE-MOUNTED ON/OFF SWITCH
OR OPTIONAL WALL SWITCH
OR OPTIONAL THERMOSTAT
OR OPTIONAL REMOTE RECEIVER
Red pigtail
Black pigtail
White Wire to Opposite
Side
G
Step 4. FIELD WIRING
The gas valve is set in place and pre-wired at the factory on both models.
A. SIT and Honeywell Millivolt Wiring
(See Figure 44 )
1. Select any of the following optional con-
trols: appliance-mounted (rocker switch) or wall-mounted switch, thermostat, or one of the optional remote control kits. If appliance­mounted ON/OFF control is selected mount it in the gas valve mounting bracket.
2. If wall-mounted ON/OFF control or thermo­stat is selected mount it in a convenient location on a wall near the fireplace.
3. Wire the control switch within the millivolt control circuit using the 15 feet of 2 conductor wire supplied with the unit. Caution: do not
connect the optional wall switch to a 120V power supply.
4. Alternatively, the appliance may be operated
without the use of the controls indicated in step 1, solely by manipulating the gas valve control knob. In order to use this method, twist the free ends of the two conductor wire (located inside the bottom compartment of the unit) together as shown in
Figure 44
Note: The supplied 15 feet of 2 conductor wire
has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose inside the bottom com­partment of the unit.
If any of the original wire as supplied must be replaced, it must be replaced with Type AWM105°C – 18 GA. wire.
AB
*OPTIONAL ON/OFF SWITCH,
WALL SWITCH, THERMOSTAT
OR REMOTE CONTROL RECEIVER
*TWIST WIRES A AND B TOGETHER TO OPERATE UNIT
SOLELY BY MANIPULATING THE GAS VALVE CONTROL KNOB;
OR CONNECT WIRES TO OPTIONAL ON/OFF SWITCH OR WALL
SWITCH OR THERMOSTAT TO OPERATE UNIT.
Figure 44
.
Millivolt Wiring Diagram
Thermopile
TP
Note: The supplied 15 feet of 2 conductor wire
has one end of each conductor connected to
4. Connect the ground supply wire to the outlet's green ground screw.
the gas valve circuit and the other end of each conductor placed loose inside the bottom
5. Reinstall the outlet box.
compartment.
6. Insert the blower plug into the top outlet.
B. Electronic Wiring (See
Figure 45
) –
Note: The electronic appliance must be con-
nected to the main power supply.
1. Route a 3-wire 120Vac 60Hz 1ph power supply to the appliance junction box.
2. Remove the outlet box from the junction box by removing two screws .
(The bottom outlet is unused on millivolt units, while the burner control circuit plugs into the bottom outlet on electronic units.)
IMPORTANT: Ground lead must be con­nected to the green screw located on the outlet box. See
Figure 45
. Failure to do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes
3. Connect the black power supply wire to the lower outlet's red pigtail lead and the white
power supply wire to the common terminal of the outlet as shown in
Figure 46.
or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70­(latest edition). (In Canada, the current CSA C22-1 Canadian Electrical Code.)
4. Connect the ground supply wire to the outlet's green ground screw.
5. Locate and install a low voltage (24V) wall
switch or thermostat (not supplied) in the desired location.
6. Connect the low voltage wire to this switch or thermostat.
7.
Insert the control circuit plug into the lower
outlet box.
8. After wiring is complete, replace the outlet box.
Note: The gas valve-mounted ON/OFF switch
is shown in Figure 45. It is integral with the gas valve.
Step 5. WIRING - OPTIONAL FORCED AIR BLOWER KIT (See
An electrical outlet box is provided for the instal­lation of the FBK-100, FBK-200 forced air blower
TH
TP
TH
kits (optional). Electrical power must be pro­vided to this box to operate these blowers.
1. Route a 3-wire, 120Vac 60Hz 1ph power line with control switch to the lower right rear corner of the appliance.
2. Remove the outlet box by removing two screws.
3. Connect the supply wires to the blower control switch. Then connect the wires from the blower control switch to the outlet box' pigtail leads as shown in
Figure 45 )
Figure 45
Figure 45
.
20
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
FBK-250 Blower Kit (See
Figure 46
)
An electrical outlet box is provided for the instal­lation of the FBK-250 forced air blower kit. Electrical power must be provided to this box to operate these blowers. Install the blower kit according to the installation instructions pro­vided with the kit.
1. Route a 3-wire, 120Vac 60Hz 1ph power line to the lower right rear corner of the appliance.
2. Remove the outlet box by removing two screws.
3. Connect the black supply wire to both of the outlet box' pigtail leads and the white supply wire to the common terminal of the outlet box as shown in
Figure 46
.
4. Connect the ground supply wire to the outlet's green ground screw.
5. Reinstall the outlet box.
6. Insert the kit-provided module plug into the top outlet.
(The bottom outlet is unused on millivolt units, while the burner control circuit plugs into the bottom outlet on electronic units.)
7. Insert the blower plug into the module's receptacle.
Electronic Wiring Diagram (Honeywell)
Showing the Blower Wiring for the Optional
1. If any of the original wire as supplied must be replaced,
1. it must be replaced with Type AWM 105°C – 18 GA. wire.
2. 120V, 60Hz – Less than 3 amps.
*ON/OFF Switch (Integral
with Gas Valve)
BK
R
WH
OPTIONAL APPLIANCE-MOUNTED ON/OFF SWITCH
FBK-250 Kits
*Leave the ON/OFF switch, which is integral
with the gas valve, in the ON position.
Outlet Box Green
Gas Valve
IGNITER
Optional FBK-250
BL
OPT
BLOWER
Module
W
Hot side of Outlet
OR OPTIONAL WALL SWITCH
OR OPTIONAL THERMOSTAT
OR OPTIONAL REMOTE RECEIVER
Factory Wired Field Wired
Schematic Representation Only
PILOT
ASSEMBLY
B
Ground Screw
G
G
BL
R
G BK W
White Wire
To Opposite
Transf.
120 V.
24 V
Side
120
VAC.
BK
Figure 46
Step 6. CONNECTING GAS LINE
Make gas line connections. All codes re­quire a shut-off valve mounted in the supply line.
Figure 47
connecting the gas supply. The flex-line method is acceptable in the U.S., however, Canadian requirements vary depending on locality. Installation must be in compliance with local codes.
These appliances can be equipped with a gas flex line for use (where permitted) in connect­ing the unit to the gas line. The gas flex line (not provided) is to aid in attaching the direct vent appliance to the gas supply. The gas flex line can only be used where local codes per­mit. See The flex line is rated for both natural and propane gas. The optional gas flex line is equipped with a manual shut off valve.
Open the control compartment access panel
(Figure 48)
magnetic catches securing the panel, gently depressing the outer top corners of the panel until the catches "pop" the panel free, allowing it to swing out and down to open.
The millivolt control valve has a ³⁄₈" (10 mm) NPT thread inlet port.
Secure all joints tightly using appropriate tools and sealing compounds (ensure pro­pane resistant compounds are used in pro­pane applications).
Figure 47 -
illustrates two methods for
Figure 47
for flex line description.
by actuating the spring-loaded
Gas Valve
³₈" Nipple
³₈" Union
³₈" Close Nipple
GAS CONNECTION
Optional Gas Flex Line Connector
³₈" NPT x ³₈
Flare Fitting
³₈" Flex Tubing
Turn on gas supply and test for gas leaks using a soapy water solution. Never use an open
flame to check for leaks.
Open the lower panel or louver assembly by gently depressing the outer top corners of the panel until the catches pop the panel free,
allowing it to swing out and down to open.
Control Valve
Lower Control Compartment Door
Opening Control Compartment Door
Figure 48
A. Mix a 50% dish soap, 50% water solution.
B. Light the appliance (refer to the lighting
instructions provided in the Homeowner's Care and Operation Instructions).
C. Brush all joints and connections with the soapy water solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob to the “OFF” position. Either tighten or refasten the leaking connec­tion and retest as described above.
D. When the gas lines are tested and leak free, observe the individual tongues of flame on the burner. Make sure all ports are open and pro­ducing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.
¹₂" x ³₈" Flare
Shut-Off Valve
Gas
¹₂ x ³₈ " Reducer
³₈" Shut-Off Valve
Stub
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
21
Step 7. INSTALLING LOGS AND GLOWING EMBERS
The logs are packaged in a carton which is shrink-wrapped to the front glass enclosure panel. The glowing embers are packaged sepa­rately in a plastic bag located in the control area of the fireplace.
Refer to the homeowner's care and operation instructions for detailed placement instruc­tions for the logs and glowing embers.
Step 8. CHECKING APPLIANCE OPERATION
With gas line installed run initial system checkout before closing up the front of the unit. Follow the pilot lighting instructions provided in the Homeowner's Care and Operation Instructions. For piezo ignitor location see Honeywell millivolt appliances only).
Note: Instructions are also found on the litera­ture tag attached to the gas valve train.
When first lighting the appliance, it will take a few minutes for the line to purge itself of air. Once purging is complete, the pilot and burner will light and operate as indicated in the instruction manual. Subsequent lightings of the appliance will not require such purging. Inspect the pilot flame (remove logs, if necessary, handling carefully).
Figure 49
(SIT and
Replace logs if removed for pilot inspection.
To light the burner; turn ON the remote wall switch and rotate the gas valve control knob counterclockwise to the ON position.
SIT MILLIVOLT
Thermocouple
Pilot Nozzels
Hood Ignitor Rod
³⁄₈" Min (9 mm)
Thermopile
Figure 50
HONEYWELL MILLIVOLT
¹⁄₈" Min (3 mm)
Pilot
Nozzels
Thermopile
Thermocouple
Ignitor Rod
Hood
³⁄₈" Min (9 mm)
Step 9. INSTALLING THE GLASS DOOR
Retrieve the glass door. Visually inspect the gasket on the backside of the frame. Gasket surface must be clean, free of irregularities and seated firmly.
Position the door in front of the firebox opening with the bottom of the door held away from the fireplace the door frame over the top of the firebox frame.
Let the bottom of the door frame swing gently in towards the fireplace ensuring that the gas­ket seats evenly as the door frame draws shut. Fasten the two latches located underneath the firebox floor to the door's vee-flange. Close both the latches securely.
Latch
(Figure 53
). Hook the top flange of
Top Flange Door Frame
Glass Door
SIT Gas Valve
Honeywell Gas Valve
Piezo
Ignitor
Sit and Honeywell Millivolt Gas Valve
Showing Piezo Ignitor Location (Each Unit is
Equipped with Only One of these Gas Valves)
Figure 49
SIT and Honeywell Millivolt Appliance Checkout
The pilot flame should be steady, not lifting or floating. Flame should be blue in color with traces of orange at the outer edge. The top ³⁄₈" (10 mm) at the pilot generator (thermopile) and the top ¹⁄₈" min (tip) of the quick drop out thermocouple should be engulfed in the pilot flame. The flame should project 1" (25 mm) beyond the hood at all three ports (
- SIT, Figure 51 - Honeywell
Figure 50
)
Figure 51
Electronic Appliance Checkout
To light the burner, turn ‘ON’ the optional remote wall switch and turn the gas control switch to the “ON” position. Ensure the ignitor lights the pilot. The pilot flame should engulf the flame rod as shown in
ELECTRONIC
Proper Flame
Adjustment
Pilot Nozzle
Figure 52
.
3/8 To 1/2 Inch
(9 mm to 13 mm)
Ground Electrode
Flame Rod
Hot Surface
Igniter
Figure 52
Bottom Vee-flange
Door Frame
Figure 53
- INSTALLING THE GLASS DOOR
Latch
Firebox Floor
WARNING: HANDLE THIS GLASS WITH EXTREME CARE! THE GLASS PANEL IS SUSCEPTIBLE TO DAMAGE DO NOT SCRATCH WHILE HANDLING OR WHILE RE-INSTALLING THE GLASS DOOR FRAME.
WARNING: NEVER OPERATE THE APPLI­ANCE WITHOUT THE FRONT GLASS EN­CLOSURE PANEL IN PLACE AND SECURE.
22
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Step 10. BURNER ADJUSTMENTS
Flame Appearance and Sooting
Proper flame appearance is a matter of taste. Generally, most people prefer the warm glow of a yellow to orange flame. Appliances operated with air shutter openings that are too large will exhibit flames that are blue and transparent. These weak, blue and transparent flames are termed anemic. If the air shutter opening is too small sooting may develop.
Sooting is indicated by black puffs developing at the tips of very long orange flames. Sooting results in black deposits forming on the logs, appliance inside surfaces and on exterior sur­faces adjacent to the vent termination. Sooting is caused by incomplete combustion in the flames and lack of combustion air entering the air shutter opening. To achieve a warm yellow to orange flame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
No smoke or soot should be present. Reposition the logs if flames impinge on any of them. If the logs are properly positioned and sooting conditions exist, the air shutter opening on the main burner tube should be adjusted. Normally, the more offsets in the vent system, the greater the need for the air shutter to be opened further.
Burner Adjustment
Allow the burner to operate for at least 15 min­utes. Observe the flame continuously. If it ap­pears weak or sooty as previously described, adjust the air shutter by pushing or pulling on the adjustment rod until the flame appearance is as desired.
The adjustment rod and associated adjustable air shutter is patented technology. Flame adjust­ments can be made quickly and accurately to taste without the need of disassembling the appliance and waiting for 30 minutes after each adjustment.
Note: If the flame still appears anemic with the air shutter closed all the way against the stop (usually a result of lengthy vertical runs), turn the appliance off, turn the gas supply off, wait for the parts to cool, remove the glass door and logs to access the air shutter. The shutter is prevented from actually closing all the way by an adjustment set screw (see Figure 54). Re­move this screw using a
¹⁄₄
inch nut driver. Reinstall the logs and glass door, turn the gas back on and then restart the appliance. After 30 minutes, reobserve the flame. Adjust the air shutter as previously described.
When satisfied that the appliance operates properly, proceed to finish the installation. Leave the control knob in the ON position and the remote switch OFF. Close the lower control compartment door.
Step 11. HOOD INSTALLATION
All of these appliances must have hoods installed prior to operating.
On all clean face units, slide the hood into the slots on the lower edge of the radiant panel (
Figure 55
).
On louvered face units, slide the hood into the slots on the lower edge of the cabinet top (
Figure 56
).
FINISHING REQUIREMENTS Wall Details
Complete finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thick­ness of the finished wall (
Combustible Finished Wall Materials
Combustible
material may touch the appliance top.
Combustible
materials not
allowed below
this point on
the face of the
appliance.
Figures 55 and 56
This Area Must Remain Clear of Combustible Materials
1" Min
(25 mm)
Spacer
Top of Appliance
Radiant panel
Top of Door Frame
).
WARNING: AIR SHUTTER ADJUST­MENT SHOULD ONLY BE PERFORMED BY A QUALIFIED PROFESSIONAL SERVICE TECHNICIAN.
IMPORTANT: ENSURE THAT THE FRONT GLASS PANEL IS IN PLACE AND SEALED DURING ADJUSTMENT.
CAUTION: THE AIR SHUTTER DOOR AND NEARBY APPLIANCE SURFACES ARE HOT. EXERCISE CAUTION TO AVOID INJURY WHILE ADJUSTING FLAME APPEARANCE.
To adjust the flame, move the adjustment rod (located in the lower control area) up or down to increase or reduce the air shutter opening, respectively. Initially, always position the air
shutter to the factory setting (the minimum air opening position) as shown in can be done by pulling the adjustment rod all the way down.
Figure 54
. This
Burner Tube
Air Shutter
Adjustment Rod Down
(minimum air
opening position)
sledoM
004-TD
004-RD
Figure 54
Adjusting Set Screw
Adjustment Rod Up
(Fully Open Position)
RIAYROTCAF
GNITTESRETTUHS
saGlarutaN
sehcni
)mm(
23/1
)8.0(
Hood must be installed as shown.
Clean Face Models
Figure 55
Combustible Finished Wall Materials
Combustible
material
may touch the
appliance top.
saGenaporP
sehcni
)mm(
61/5
)0.8(
Combustible materials not
allowed below
this point on
the face of the
appliance.
Hood must be installed as shown.
Louver Face Models
This Area Must Remain Clear of Combustible Materials
1" Min
(25 mm)
Spacer
Top of Appliance
Louvers
Top of Door Frame
Figure 56
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
23
A hearth extension is not required with this appliance. If a hearth extension is used, do not block the lower control compartment door. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements.
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the appliance front face. See Figures 55 and 56 on page 23.
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face with these exceptions: they must not cover any portion of the glass or louvers; they may cover any portion of the top radiant panel or the air gaps surrounding the top radiant panel up to the installed hood.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel. (See
Figure 58
). Mantels constructed of non-
combustible materials may be installed at any height above the appliance opening; however, do not allow anything to hang below the hood.
Combustible materials may project beyond the sides of the fireplace opening as long as they are kept within the shaded areas illustrated in
Figure 57
Combustible Materials Allowed In Shaded Area Safe Zone
17"
.
Side Wall
12"
14"
Top View Of
Fireplace
45°
Side Wall
5"
8 ¹⁄₄"
Min. Distance To Unprotected Side Wall
Min. Distance To Protected Side Wall
Figure 57
Figure 58
14
(356)
12
(305)
(254)
MANTEL CLEARANCES
Inches (mm)
12 (305) MANTEL
10 (254) MANTEL
8 (203) MANTEL
6 (152) MANTEL
10
8
6
(203)
(152)
NOTE - Hood shown as positioned
in louvered front model. The hood position in the flush faced front model is lower than shown.
4 (102) MANTEL
4
(102)
2 (51) MANTEL
TOP OF APPLIANCE
COLD CLIMATE INSULATION
If you live in a cold climate, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level.
INSTALLATION ACCESSORIES
24
detsiL tneVeruceS stnenopmoC
.taC
.oN
59L68RTH5.4VSnoitanimreTdnuoRlatnoziroH
72L89LSSTH5.4VSerauqSllamSgnoLlatnoziroH
79L68STH5.4VSnoitanimreTerauqSlatnoziroH
01L49SSTH5.4VSerauqStrohSlatnoziroH
2512H1-VGC5.4VSnoitanimreTlacitreV
.oNledoMnoitpircseD
detsiL xelFeruceS stnenopmoC
.taC
.oN
)08K69(recapS/potseriFhtiw
49L68RTH-FSnoitanimreTdnuoRlatnoziroH
)16L47(retpadAdna
ledoM
.oN
noitpircseD
.retpadaxelfdnaspmalcraeg,recaps/potserifedulcnistiknoitanimretesehT
xelFtuohtiw
28L77R21TIKFS.ni21htiw.mreTdnuoRxelF
xelFdesserpmoc*fo)mm503(
htiwnoitanimreT
dna)08K69(recapS/potseriF
noitcestnev)mm503(.ni21
)17L77(
)08K69(recapS/potseriFhtiw
)16L47(retpadAdna
38L77R81TIKFS.ni81htiw.mreTdnuoRxelF
xelFdesserpmoc*fo)mm754(
48L77R42TIKFS.ni42htiw.mreTdnuoRxelF
xelFdesserpmoc*fo)mm016(
58L77R63TIKFS.ni63htiw.mreTdnuoRxelF
xelFdesserpmoc*)mm419(
68L77R84TIKFS.ni84htiw.mreTdnuoRxelF
xelFdesserpmoc*fo)mm9121(
10L78KRHFSxelFhtiwtiKresiRlekronS
htiwnoitanimreT
dna)08K69(recapS/potseriF
)16L47(retpadA
04M91FH5.4FS-recapS/potseriF
spmalCraeG
dna,xelFfonoitcesa,retpadA
)gnicaps1-1-3(latnoziroH
14M91FB5.4FS-recapS/potseriF
)gnicaps1-1-1(lacitreV
*All compressed flex vents can be expanded up to two times.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
INSTALLATION ACCESSORIES (Continued)
detsiL tneVeruceS stnenopmoC
.taC
.oN
07L77 17L77 27L77 37L77 47L77 57L77 67L7754E5.4VSwoblEeergeD54
77L7709E5.4VSwoblEeergeD09
10L19 20L19 30L19 18L776CS5.4VS)xob/sralloc6(sralloCmrotS
08K69FH5.4VS-recapS/potseriF
78K69FB5.4VS-recapS/potseriF
39K69US5.4VSpartStroppuS
49K69ASR5.4VSdleihSnoitalusnIcittA
29K69PS5.4VSetalPtroppuS
00K79RGH5.4VSdnuoRdrauGtaeH
20L78SGH5.4VSerauqSdrauGtaeH
.oNledoMnoitpircseD
6L5.4VS 21L5.4VS 42L5.4VS 63L5.4VS 84L5.4VS
AL5.4VS
B-F5.4VS B-AF5.4VS B-BF5.4VS
detsiL xelFeruceS stnenopmoC
.taC
.oN
noitceStneV)mm251(hcni6
90L49SSTH-FSerauqSllamStrohSlatnoziroH
noitceStneV)mm503(hcni21 noitceStneV)mm016(hcni42 noitceStneV)mm419(hcni63
noitceStneV)mm9121(hcni84
noitceScipocseleT
40L49-S21TIKFS
S
50L49-S81TIKFS
S
.oNledoMnoitpircseD
.retpadaxelfdnaspmalcraeg,recaps/potserifedulcnistiknoitanimretesehT
xelFtuohtiwnoitanimreT
.mreTerauqSllamStrohSxelF
fomm503(.ni21htiw
xelFdesserpmoc*
.mreTerauqSllamStrohSxelF
fo)mm754(.ni81htiw
xelFdesserpmoc*
60L49-S42TIKFS
S
.mreTerauqSllamStrohSxelF
fo)mm016(.ni42htiw
xelFdesserpmoc*
70L49-S63TIKFS
S
.rallocmrotsahtiwdegakcapemocsgnihsalfgniwollofehT
gnihsalFfooRtalF
gnihsalF.tsujdA21/7ot21/1
80L49-S84TIKFS
S
gnihsalF.tsujdA21/21ot21/7
xelFdesserpmoc*
xelFdesserpmoc*
.mreTerauqSllamStrohSxelF
fo)mm419(.ni63htiw
.mreTerauqSllamStrohSxelF
fo)mm9121(.ni84htiw
.retpadaxelfdnaspmalcraeg,recaps/potserifedulcnistiknoitanimretesehT
69L68STH-FSnoitanimreTerauqSlatnoziroH
xelFtuohtiw
78L77S21TIKFS.ni21htiw.mreTerauqSxelF
)gnicaps1-1-3(latnoziroH
)gnicaps1-1-1(lacitreV
88L77S81TIKFS.ni81htiw.mreTerauqSxelF
xelFdesserpmoc*fomm503(
desserpmoc*fo)mm754(
xelF
98L77S42TIKFS.ni42htiw.mreTerauqSxelF
desserpmoc*fo)mm016(
xelF
09L77S63TIKFS.ni63htiw.mreTerauqSxelF
desserpmoc*fo)mm419(
xelF
19L77S84TIKFS.ni84htiw.mreTerauqSxelF
desserpmoc*fo)mm9121(
xelF
47L6503TVFStalf(xelFrof.nimreTlacitreV
,retpadAxelFhtiw)21/6ot
foor,tnevdigirfonoitces
foor,ylbmessaralloctroppus
.rallocmrotsdnagnihsalf
25M715.4VS
1-SGH
35M715.4VS
21-SGH
89K69RDH5.4VSdnuoRrofrotcelfeDtaeH
noitanimreT
89L68FFR5.4VSecalperiFdepmirC-retpadA
tneVeruceSotralloC
30L99 20L99
63KRH5.4VS 41KRH5.4VS
"63tiKresiRlatnoziroH "41tiKresiRlatnoziroH
*All compressed flex vents can be expanded up to two times.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
57L6554TVFS21/6(xelFrof.nimreTlacitreV
)kcaP-1(erauqSdrauGtaeH
)kcaP-21(erauqSdrauGtaeH
retpadAxelFhtiw)21/21ot
foor,tnevdigirfonoitces
foor,ylbmessaralloctroppus
.rallocmrotsdnagnihsalf
01L0681-FSdesserpmoc*)m94.5(.tf81
xelF
30K8921-FSdesserpmoc*)m66.3(.tf21
xelF
t
n
a
l
a
e S
18K01PMFSerutarepmeT-iHkcalBcaPliM
tnalaeS
10J884CG-FS)mm411(.ni5.4pmalCraeG
xelFrof
00J387CG-FS5.091(.ni5.7pmalCraeG
xelFrof)mm
00L78FR5.4FSretpadAxelF
25
GAS CONVERSION KITS
tiKnoisrevnoCsaGlarutaNotenaporP
)smetsySllewyenoH(
.oNledoMepyTtinU.oNgolataC 004-TDtlovillim55M62 004-RDtlovillim55M62 004-TDcinortcele19L99 004-RDcinortcele19L99
WARNING: THIS CONVERSION KIT SHALL BE INSTALLED BY A QUALIFIED SERVICE AGENCY IN ACCORDANCE WITH THE MANUFACTURER'S IN­STRUCTIONS AND ALL APPLICABLE CODES AND REQUIREMENTS OF THE AUTHORIZED AGENCY HAVING JURISDICTION. IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EX­ACTLY, A FIRE, EXPLOSION OR PRODUCTION OF CARBON MONOXIDE MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. THE INSTALLATION IS NOT PROPER AND COMPLETE UNTIL THE OPERATION OF THE CON­VERTED APPLIANCE IS CHECKED AS SPECIFIED IN THE OWNER INSTRUCTIONS SUPPLIED WITH THE KIT. THE QUALIFIED SERVICE AGENCY PERFORM­ING THIS INSTALLATION ASSUMES RESPONSI­BILITY FOR THIS CONVERSION.
In Canada: THE CONVERSION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN1-B149.1 AND .2 INSTALLATION CODE.
LA CONVERSION DEVRA ÊTRE EFFECTUÉE CONFORMÉMENT AUX RECOMMANDATIONS DES AUTORITÉS PROVINCIALES AYANT JURIDICTION ET CONFORMÉMENT AUX EXIGENCES DU CODE D'INSTALLATION CAN1­B149.1 ET.2.
Gas conversion kits are available to adapt your appliance from the use of one type of gas to the use of another. These kits contain all the neces­sary components needed to complete the task including labeling that must be affixed to en­sure safe operation.
Kit part numbers are listed here and the follow­ing steps detail the conversion procedure.
Step 1. Turn off the gas supply to the appliance. Remove the front glass door/frame from the appliance. Access the control compartment.
Step 2. Carefully remove the logs.
care as not to break the logs.
Step 3. Locate the screws securing the burner
(tray) to the appliance. Remove the burner and retain the securing screws.
26
Exercise
Step 4. Millivolt Appliances - SIT Systems
a. See
with the kit. Using a Torx T20, remove and discard the three pressure regulator mounting screws. Remove the pressure regulator, spring, poppet, diaphragm and bushing. Discard all removed components. Ensure the rubber gas­ket installed on the back of the replacement pressure regulator is properly positioned and install the new pressure regulator using the new screws supplied with the kit. Tighten screws to 25 In. lb. torque.
AVERTISSEMENT: CET ÉQUIPEMENT DE CONVERSION SERA INSTALLÉ PAR UNE AGENCE QUALIFIÉE DE SERVICE CONFORMÉMENT AUX INSTRUCTIONS DU FABRICANT ET TOUTES EXIGENCES ET CODES APPLICABLES DE L'AUTORISÉS AVOIR LA JURIDICTION. SI L'INFORMATION DANS CETTE INSTRUCTION N'EST PAS SUIVIE EXACTEMENT, UN FEU, EXPLOSION OU PRODUCTION DE PROTOXYDE DE CARBONE PEUT RÉSULTER LE DOMMAGES CAUSER DE PROPRIÉTÉ, PERTE OU BLESSURE PERSONNELLE DE VIE. L'AGENCE QUALIFIÉE DE SERVICE EST ESPONSABLE DE L'INSTALLATION PROPRE DE CET ÉQUIPMENT. L'INSTALLATION N'EST PAS PROPRE ET COMPLÉTE JUSQU'À L'OPÉRATION DE L'APPAREIL CONVERTI EST CHÉQUE SUIVANT LES CRITÈRES ÉTABLIS DANS LES INSTRUCTIONS DE PROPRIÉTAIRE PROVISIONNÉES AVEC L'ÉQUIPEMENT.
)smetsySTIS(
.oNsledoMepyTtinU.oNgolataC
004-TDtlovillim4951H
004-RDtlovillim4951H
004-TDcinortcele09L99
004-RDcinortcele09L99
)smetsySTIS(
.oNledoMepyTtinU.oNgolataC 004-TDtlovillim5951H 004-RDtlovillim5951H 004-TDcinortcele19L99 004-RDcinortcele19L99
Figure 59
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
and the instructions provided
tiKnoisrevnoCsaGenaporPoTlarutaN
)smetsySllewyenoH(
.oNsledoMepyTtinU.oNgolataC 004-TDtlovillim15M62 004-RDtlovillim15M62 004-TDcinortcele09L99 004-RDcinortcele09L99
tiKnoisrevnoCsaGlarutaNotenaporP
SIT Millivolt Gas Valve
Pressure Regulator
Remove These Components
tiKnoisrevnoCsaGenaporPoTlarutaN
Figure 59
Pilot for SIT Millivolt Gas Valve
Pilot Orifice
Pilot for Honeywell Millivolt Gas Valve
(Loosening of Hex Fitting For Orifice Strip Tab Positioning)
Hood
7/16 in. Open End Wrench
Hood Alignment
Figure 60
b. Attach manometer to the manifold side
pressure test fitting and verify manifold pres­sure reads 3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.
c. Refer to hood assembly to access the hexed pilot ori­fice. Remove and replace the orifice with the one provided with the kit.
Step 5. Millivolt Appliances -
a.
Convert the gas valve as follows (
Remove the plastic protecting cap. Remove the gas type setting screw by turning it counter­clockwise. Obtain the replacement gas type setting screw from the kit and screw it into place (red for propane and blue for natural gas). Tighten the gas type setting screw by turning it clockwise. Replace the plastic protecting cap.
Figure 60
and remove the pilot
Honeywell Systems
see
Figure 61):
Honeywell Millivolt Gas Valve
Figure 62
Figure 63
Orifice Strip Tab
Take Care Not to Contact the Orifice Strip Tab
with the Hex Fitting Wrench - Distortion of the Tab
May Render the Pilot Inoperative.
Pilot for Honeywell Millivolt Gas Valve
Orifice Strip Tab Position Identification
For LP/Propane and Natural Gas
LP/Propane Gas Position -
1/16 in. Hole, LP and
Red Color shown on tab
L
P
Top View of Hex Fitting and Orifice Strip Tab
Natural Gas Position -
NAT shown on tab
NAT
Pilot for Honeywell Millivolt Gas Valve Orifice Strip Tab Positioning
Pilot Hood Position After Loosening Hex Fitting 1/4 Turn
Adjusting Knob
Regulator Cap
Figure 61
Conversion screw (blue natural gas; red LP/propane gas)
Figure 64
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Orifice Strip Tab
Push Tab to Set
Gas Type Usage
Note - Orifice Strip Tab May Be Randomly Located On Any Side Of The Hex Fitting
27
b. Attach manometer to the manifold side
pressure test fitting and verify manifold pres­sure reads 3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.
c.
Convert the pilot orifice as follows (refer to
Figures 62, 63 and 64 ): Note - Use extra care not to engage the orifice strip with the 7/16" open end wrench (contact­ing the orifice strip could cause strip distortion rendering the pilot inoperative). Also avoid wrench contact to any of the other pilot parts.
Use a 7/16" open end wrench and turn the pilot hex fitting counter-clockwise 1/4 turn. (
refer
to Figure 62 ).
Note - The orifice strip tab may be randomly located on any side of the hex fitting.
d. Push the orifice strip tab all the way against the hex fitting to align the appropriate gas type orifice
(refer to Figures 63 and 64)
. The type of gas for which the pilot is set, is, the gas type shown on the tab.
e. Retighten, clockwise, the pilot hex fitting until the pilot hood aligns with the thermo­couple and thermopile as indicated by the arrows shown in
Figure 62
.
Step 6. Electronic Appliances -
Honeywell Systems
See
Figure 65
and the instructions provided with the kit. Remove the slotted cap screw, o­ring, pressure-regulating adjusting screw and spring. Retain all parts for possible later use. Install new components from the kit. Black cap and red spring for propane gas units. Silver cap and stainless steel spring for natural gas units. Before installing the cap, attach manometer to the manifold side pressure test fitting and adjust screw until pressure reads 3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.
See
Figure 66
and replace the pilot orifice as follows: Remove the ignitor assembly retainer clip, and carefully remove the ignitor assembly.
Exercise extreme care to prevent damage to or breakage of the ignitor assembly.
CONTROL
I
G N I
T E
Manifold Pressure Test Port
Slotted Cap
OFFION
Inlet Pressure Test Port
I S P
Adjusting Screw
Spring
Figure 65
Remove the screw securing the pilot assembly to its mounting bracket. Back off the flare nut at the end of the pilot gas line to free the pilot assembly from the gas line.
Remove the pilot orifice and replace it with the one provided with the conversion kit. Reinstall the pilot assembly by reversing the steps de­tailed here.
When reinstalling the ignitor assembly, use extreme care to prevent damage and break­age. Do not apply any leverage to the ignitor assembly while restoring the retainer clip to its original position.
Pilot Orifice
Retaining
Flare Nut
Pilot Assembly
Ignitor Assembly
Clip
Note: If the ignitor is damaged, a replacement kit is available - order Catalog Number 87L54.
Figure 66
All Models
Step 7. Remove the orifice from the mani-
fold and replace it with the one provided with the kit. See the following table for orifice sizes for natural and propane models
. Figure 67
illustrates the orifice.
ezisecifirO
.oNledoM
larutaNenaporP
004-TD
54#
004-RD
840.0
hcni
Figure 67
Step 8. Reassemble all removed components
by reversing the procedures outlined in the preceding steps. Use pipe joint compound or Teflon tape on all pipe fittings before installing (ensure propane resistant compounds are used in propane applications, do not use pipe joint compounds on flare fittings).
Step 9. Attach the conversion label provided in the conversion kit to the rating plate on the appliance.
Step 10. Turn on gas supply and test for gas leaks.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2002 by Lennox Hearth Products
P/N 700,020M REV. M 11/2004
28
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
LHP 1110 West Taft Avenue Orange, CA 92865
Loading...