Superior DT-400CEN, DR-400CEN, DR-400CMN, DT-400CEP, DT-400CMP User Manual

...
INSTALLATION INSTRUCTIONS
DIRECT VENT
DT-400 & DR-400
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
This appliance may be installed in an aftermar­ket permanently located, manufactured home (USA only) or mobile home, where not prohib­ited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
WARNING: IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO­SION MAY RESULT CAUSING PROPERTY DAM­AGE, PERSONAL INJURY OR LOSS OF LIFE.
VENTED GAS FIREPLACE HEATERS - DIRECT VENT MODELS P/N 700,020M REV. M 11/2004
MODELS
tlovilliM
sledoM
NMC004-TDNEC004-TD PMC004-TDPEC004-TD
NMC004-RDNEC004-RD PMC004-RDPEC004-RD
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUCTIONS DONNÉ DANS CETTE NOTICE POUR RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE BLESSURE OU LA MORT.
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser d'essence ni d'autre vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
cinortcelE
sledoM
• DO NOT light any appliance.
• DO NOT touch any electrical switches.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow your gas suppliers instructions.
• If your gas supplier cannot be reached, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
OTL Report No. 116-F-17-4
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une odeur de gaz:
Ne pas tenter d'allumer d'appareil.
Ne touchez à aucun interrupteur. Ne pas vous servir
des téléphones se trouvant dans le batiment où vous vous trouvez.
Evacuez la piéce, le bâtiment ou la zone.
Appelez immédiatement votre fournisseur de gaz
depuis un voisin. Suivez les instructions du fournisseur.
Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service dos incendies.
L'installation et service doit être exécuté par un qualifié installeur, agence de service ou le fournisseur de gaz.
1
TABLE OF CONTENTS
Packaging ........................................ page 2
Introduction ..................................... page 2
General Information......................... page 2
Location .......................................... page 4
Appliance and Vent Clearances ....... page 4
Vent Termination Clearances ........... page 5
Typical Installation Sequence .......... page 5
Detailed Installation Steps ............... page 5
Step 1. Framing ............................. page 5
Step 2. Routing Gas Line ............... page 5
Fireplace Specifications ................... page 8
Step 3. Install the Venting System. page 8
Vertical Termination Systems .......... page 9
Vent Section Length Chart ............... page 9
Vertical Vent Tables and Figures...... page 12
Horizontal Termination System ........ page 14
Horizontal Vent Tables and Figures . page 16
Venting Using Flexible Vent Pipe ..... page 19
Step 4. Field Wiring ....................... page 20
Step 5. Optional Blower Kit Wiring page 20
Step 6. Connecting Gas Line.......... page 21
Step 7. Installing Logs................... page 22
Step 8. Checking Unit Operation ..... page 22
Step 9. Installing Glass Door ......... page 22
Step 10. Burner Adjustments........... page 23
Step 11. Hood Installation ............... page 23
Finishing Requirements ................... page 23
Cold Climate Insulation.................... page 24
Installation Accessories ................... page 24
Gas Conversion Kits.................. page 26
This installation manual will help you obtain a safe, efficient, dependable installation for your appliance and vent system.
Please read and understand these instructions before beginning your
installation.
PACKAGING
The assembled vented gas fireplace heater is packaged with: 1 -one log set shrink-wrapped to the in-
side surface of the front glass enclo­sure panel.
2 - one plastic bag containing the literature
package which consists of the homeowner's care and operation instructions, installation instructions and warranty; plastic bag lo­cated in the control area.
3 - one vent restrictor for use in top vent appli-
cations; restrictor is taped to the inside of the cabinet bottom.
4 - one hood wrapped in plastic taped to the
front of the top unit standoffs.
5 -one bag of glowing embers located in the
control area.
INTRODUCTION
These vented gas fireplace heaters are sealed combustion, air circulating gas fireplaces de­signed for residential applications. These appli­ances must be installed with the Secure Vent™ and /or Secure Flex™ vent systems routed to the outside atmosphere.
Millivolt appliances are designed to operate on natural or propane gas. A millivolt gas control valve with piezo ignition system provides safe, efficient operation. External electrical power is required to operate the optional blower if in­stalled in these units.
Electronic appliances are designed to operate on natural or propane gas. An electronic inter­mittent pilot ignition system provides safe, efficient operation. External electrical power is required to operate these units.
These millivolt and electronic versions of these appliances are listed by Omni Test Laboratories for installation in bedrooms and mobile homes.
Installation must conform to local codes. In the absence of local codes, installation must com­ply with the current National Fuel Gas Code, ANSI Z223.1. (In Canada, the current CAN-1 B149 installation code.) Electrical wiring must comply with the National Electrical Code ANSI/ NFPA 70 - (latest edition). (In Canada, the current CSA C22-1 Canadian Electrical Code.)
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
GENERAL INFORMATION
Note: Installation and repair should be per-
formed by a qualified service person. The appli­ance should be inspected annually by a quali­fied professional service technician. More fre­quent inspections and cleanings may be re­quired due to excessive lint from carpeting, bedding material, etc. It is imperative that the control compartment, burners and circulating air passage ways of the appliance be kept clean.
S'assurer que le brùleur et le compartiment des commandes sont propres. Voir les instruc­tions d'installation et d'utilisation qui accompagnent l'appareil.
Provide adequate clearances around air open­ings and adequate accessibility clearance for service and proper operation. Never obstruct the front openings of the appliance.
These appliances are designed to operate on natural or propane gas only.
TYPICAL INSTALLATION
Figure 1
2
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Millivolt Models -
Millivolt models come standard with the manually-modulated gas valve; flame ap­pearance and heat output can be con­trolled at the gas valve. Input of millivolt models is shown in the following table:
htiwsledoMtlovilliM
evlaVsaGdetaludoM-yllaunaM
saGenaporPdnalarutaN
srebmuNledoM)H/UTB(etartupnI
004-TD 004-RD
Electronic Models -
Electronic models have a fixed rate gas valve. Input of electronic models is shown in the following table:
evlaVsaG
srebmuNledoM)H/UTB(etartupnI
004-TD 004-RD
All Models -
Maximum manifold pressure is 3.5 in. w.c. (0.87 kPa) for natural gas and 10 in. w.c. (2.49 kPa) for LP/Propane gas.
Installations at Altitudes of 0 to 4500 ft.­Units are tested and approved for elevations of 0 to 4500 feet (0 to 1372 meters).
Installations at Altitudes above 4500 ft.­For elevations above 4500 feet (1372 meters), install the unit according to the regulations of the local authorities having jurisdiction and, in the USA, the latest edition of the National Fuel Gas Code (ANSI Z223.1) or, in Canada, the latest edition of the CAN1-B149.1 and .2 codes.
Table 1
shows the units' gas orifice size for
the elevations indicated.
.oNledoM
larutaNenaporP
005,71ot005,31
etaR-dexiFhtiwsledoMcinortcelE
saGenaporPdnalarutaN
005,71
ezisecifirO
The millivolt appliances are manually controlled and feature a spark ignitor (piezo) that allows the appliance's pilot gas to be lit without the use of matches or batteries. This system provides continued service in the event of a power outage.
Do not use these appliances if any part has been under water. Immediately call a qualified, pro­fessional service technician to inspect the ap­pliance and to replace any parts of the control system and any gas control which have been under water.
Ne pas se servir de cet appareil s'il a été plongé dans l'eau, complètement ou en partie. Appeler un technicien qualifié pour inspecter l'appareil et remplacer toute partie du système de contrôle et toute commande qui ont été plongés dans l'eau.
This appliance may be installed in an af­termarket permanently located, manufac­tured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This ap­pliance is not convertible for use with other gases, unless a certified kit is used.
Cet appareil peut être installé dans un maison préfabriquée (É.-U. seulement) ou mobile déjà installée à demeure si les réglements locaux le permettent. Cet appareil doit être utilisé uniquement avec les types de gaz indiqués sur la plaque signalétique. Ne pas l'utiliser avec d'autres gaz sauf si un kit de con­version certifié est installé.
Test gage connections are provided on the front of the millivolt gas control valve (iden­tified IN for the inlet and OUT for the mani­fold side). A ¹⁄₈" NPT test gage connection is provided at the inlet and outlet side of the electronic gas control valve.
Minimum inlet gas pressure to these appli­ances is 5.0 inches water column (1.24 kPa) for natural gas and 11 inches water column (2.74 kPa) for propane for the purpose of input adjustment.
These appliances must be isolated from the gas supply piping system (by closing their individual manual shut-off valve) during any pressure test­ing of the gas supply piping system at test pressures equal to or less than ¹⁄₂ psig (3.5 kPa).
These appliances and their individual shut-off valves must be disconnected from the gas supply piping system during any pressure test­ing of that system at pressures in excess of ¹⁄₂ psig (3.5 kPa).
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning are similar to the flu with headaches, dizziness and/or nausea. If you have these signs, obtain fresh air immediately. Turn off the gas supply to the appliance and have it serviced by a qualified professional, as it may not be op­erating correctly.
WARNING: FAILURE TO COMPLY WITH THE INSTALLATION AND OPERATING IN­STRUCTIONS PROVIDED IN THIS DOCU­MENT WILL RESULT IN AN IMPROP­ERLY INSTALLED AND OPERATING AP­PLIANCE, VOIDING ITS WARRANTY. ANY CHANGE TO THIS APPLIANCE AND/OR ITS OPERATING CONTROLS IS DANGER­OUS. IMPROPER INSTALLATION OR USE OF THIS APPLIANCE CAN CAUSE SERI­OUS INJURY OR DEATH FROM FIRE, BURNS, EXPLOSION OR CARBON MON­OXIDE POISONING.
WARNING: CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES. USE CAUTION AROUND THE APPLIANCE TO AVOID BURNS OR CLOTHING IGNITION. YOUNG CHILDREN SHOULD BE CARE­FULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
Table 1
004-TD
54#
004-RD
840.0
hcni
Maximum inlet gas supply pressure to these appli­ances is 10.5 inches water column (2.61 kPa) for natural gas and 13.0 inches water column (3.23 kPa) for propane.
WARNING: DO NOT PLACE CLOTHING OR OTHER FLAMMABLE MATERIALS ON OR NEAR THIS APPLIANCE.
AVERTISSEMENT: SURVEILLER LES ENFANTS. GARDER LES VÊTEMENTS, LES MEUBLES, L'ESSENCE OU AUTRES LIQUIDES À VAPEUR INFLAMMABLES À COTE DE L'APPAREIL.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3
REAR VENT
APPLICATION
TOP VENT
APPLICATION
APPLICATION
TOP VENT
INSTALLATION
RECESSED
REAR VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
Figure 2
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important. Consideration should be given to traffic ways, furniture, draperies, etc., due to elevated surface temperatures ( The location should also be free of electrical, plumbing or other heating/air conditioning ducting.
These direct vent appliances are uniquely suited for installations requiring a utility shelf posi­tioned directly above the fireplace. Utility shelves like these are commonly used for locating television sets and decorative plants.
Figure 2
VERTICAL VENT (Rear Vent Application)
HORIZONTAL VENT (Rear Vent Application without a chase)
HORIZONTAL VENT (Rear Vent Application With a chase)
HORIZONTAL VENT (Top Vent Application)
VERTICAL VENT (Top Vent Application)
Typical Locations
.oNledoM
tneVeruceSxelFeruceStneVeruceSxelFeruceS 004-TD 8/144)1211(8/754)5611(A/NA/N 004-RD A/NA/N4/133)548(4/133)548(
woblEeergeD09enOhtiw-tneVpoTkcaBehttuOthgiartS-tneVraeR
).
Do not insulate the
Do not insulate the space between the
appliance and the
area above it.
Shelf Height
(
see table)
space between the
appliance and the
area above it.
Shelf Height
see table)
(
)mm(sehcnithgieHflehS
To provide for the lowest possible shelf surface use the alternate rear vent outlet with attached venting routed in a way to minimize obstruc­tions to the use of the space above the appli­ance. Do not insulate the space between the
appliance and the area above it. See
The minimum height from the base of the appliance to the underside of combustible ma­terials used to construct a utility shelf in this fashion is shown in the table in
Figure 3
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materi­als. However, if installed on combustible ma­terials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bot­tom surface must be used.
4
Figure 3
.
Shelf Above Fireplace With Rear Venting
Figure 3
.
APPLIANCE AND VENT CLEARANCES
The appliance is approved with zero clearance to combustible materials on all sides (as de­tailed in tion: When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit. In addition, when the unit is re­cessed, the side walls surrounding the unit must not extend beyond the front edge of the unit. See
Table 2
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
), with the following excep-
Figure 2
.
Shelf Above Fireplace With Top Venting
KCAB
SEDIS
SRECAPSPOT)mm0(.ni0
ROOLF)mm0(.ni0
mottoBmorF
ottinUfo
gnilieC
TNEV*)mm4.52(.ni1
TNORF)sretem9.0(.teeF3
)mm31(.ni2/1
srecaps)mm0(.ni0
)mm31(.ni2/1
srecaps)mm0(.ni0
)mm6261(.ni46
SECNARAELCECIVRES
VENT TERMINATION CLEARANCES
These instructions should be used as a guide­line and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and ­B149.2 in Canada.
Vertical Vent Termination Clearances
Terminate single vent caps relative to building components according to
TERMINATION HEIGHTS FOR VENTS ABOVE
Horizontal Overhang
2 FT MIN.
Termination
Storm Collar
Flashing
Concentric
Vent Pipe
FLAT OR SLOPED ROOFS
Vent
H*
*H = MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING OF VENT
Figure 4
2 FT MIN.
Lowest
Discharge
Opening
1 inch (25.4 mm) Minimum Clearance to Combustibles
12
Roof Pitch is X/12
hctiPfooR
Vertical
Wall
X
H
.
)teef(
21/6ottalF0.1
21/7ot21/6revO52.1 21/8ot21/7revO5.1 21/9ot21/8revO0.2
21/01ot21/9revO5.2
21/11ot21/01revO52.3
21/21ot21/11revO0.4
Figure 4
Terminate multiple vent terminations accord­ing to the installation codes listed at the top of this page.
Horizontal Vent Termination Clearances
The horizontal vent termination must have a minimum of 3" (76 mm) clearance to any overhead combustible projection of 2 ¹⁄₂" (64 mm) or less. See exceeding 2 ¹⁄₂" (64 mm), see
Figure 5.
For projections
Figure 5
. For
additional vent location restrictions refer to
Figure 7 on page 6
.
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation follows, however, each installation is unique resulting in variations to those described. See the page numbers references in the follow­ing steps for detailed procedures.
Step 1. (page 5) Construct the appliance
framing. Position the appliance within the framing and secure with nailing brackets.
Horizontal Vent Termination Clearances
Combustible Projection
2¹⁄₂ inches or less in length
Combustible Projection
greater than 2¹⁄₂ inches in length
Ventilated
Soffit
Unventilated
Soffit
3"
18"
(457 mm)
See
Figure 31
into exterior walls, of the round and square horizontal terminations.
Figure 5 -
12"
(305 mm)
or 32 for the recess allowances,
Side Elevation View
(76 mm)
Termination Kit
Step 2. (page 5) Route gas supply line to
appliance location.
Step 3. (page 8) Install the vent system and
exterior termination.
Step 4. (page 20) Field Wiring
Millivolt Appliances The operating control
switch is factory installed.
Step 5. (page 20) Install blower kit (optional
equipment).
Step 6. (page 21) Make connection to gas
supply.
Step 7. (page 22) Install the logs, vermicu-
lite and glowing embers.
Step 8. (page 22) Checkout appliance opera-
tion.
Step 9. (page 22) Install glass door frame
assembly.
Step 10. (page 23) Adjust burner to ensure
proper flame appearance.
Step 11. (page 23) Install the hoods.
DETAILED INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and pre-wired. Re­move the shipping carton, exposing the front glass door. Remove the top panel. Remove
the cardboard from underneath the pressure relief plates. Gently depress the outer top
corners of the access panel until the catches "pop" the panel free, allowing it to swing out and down to open. Open the two latches (located under the firebox floor) securing the glass door. Remove the door by tilting it outward at the bottom and lifting it up. Set the door aside protecting it from inadvertent damage.
Figure 50 on page 21.
Remove the two card­board pad strips from between the firebox subfloor and the firebox sides.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
See
Step 1. FRAMING
Frame these appliances as illustrated in
ures 8 on page 7,
installed in a corner. See
unless the appliance is to be
Figure 9 on page 7
for corner framing installations. All framing details must allow for a minimum clearance to combustible framing members as shown in
Table 2 on page 4
. If the appliance is to be elevated above floor level, a solid continuous platform must be constructed. Headers may be in direct contact with the appli­ance top spacers but must not be supported by them or notched to fit around them. All construc­tion above the appliance must be self supporting, DO NOT use the appliance for structural support. The fireplace should be secured to the side framing members using the unit's nailing flanges - one top and bottom on each side of the fireplace front. See
Figure 6.
Use 8d nails or their equivalent.
Side
Framing
Left Side Front Corner of Fireplace Shown
(Right Side Requirements the Same)
Unit Being Secured By Its Nailing Flanges
Note: The nailing flanges, combustible members and screw heads located in areas directly adjacent to the nailing flanges, are EXEMPT from the 1/2 clearance to combustible requirements for the firebox outer wrapper. Combustible framing may be
direct contact with the nailing flanges and may
in be located closer than 1/2 the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact dimensions specified in the framing details of this manual.
To The Framing
Unit Nailing Flange
(No clearance to
combustible
framing is required)
from screw heads and
Fig-
Figure 6
Step 2. ROUTING GAS LINE
Route a ¹⁄₂" (13 mm) gas line along the inside of the right side framing as shown in
Figure 7
Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations.
All appliances are factory-equipped with a flex­ible gas line connector and ¹⁄₂ inch shutoff valve. (See step 6 on page 20).
Right Side
Front Corner of
Fireplace Framing
3"
(76 mm)
6 ¹⁄₂"
(152 mm)
Figure 7
.
5
*
See Item D in the Text Below.
Exterior Wall
Horizontal Termination
B
V
L
X
= Air Supply Inlet
.denepo
ynoclab
EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS
*18
18
Inside Corner
.ynoclabro,kced
lanimretehtfoenil
ecnailpparehto
.sgnillewdhtob
Detail D
F
V
Center Line
of Termination
Ventilated Soffit
V
Fixed
Closed
Window
V
C
A
V
= Vent Terminal = Area where Terminal is not Permitted
C
C
C
,hcrop,adnarev,edargevobaecnaraelC=A
ebyamtahtroodrowodniwotecnaraelC=B
wodniwdesolcyltnenamrepotecnaraelC=C tneverpotdednemmocer)mm503("21
tiffosdetalitnevotecnaraelclacitreV=D
latnozirohanihtiwlanimretehtevobadetacol
retnecehtmorf)mm854(sehcni81foecnatsid
tiffosdetalitnevnuotecnaraelC=E)mm503("21)mm503("21
renrocedistuootecnaraelC=Fmuminim)mc7.21("5muminim)mc7.21("5
renrocedisniotecnaraelC=Gmuminim)mc2.51("6muminim)mc2.51("6
enilretnecfoedisnihcaeotecnaraelC=H
ylbmessarotaluger/retemevobadednetxe
teltuotnevrotalugerecivresotecnaraelC=I*)mc19(teef3**)mc19(teef3
telniylppusrialacinahcemnonotecnaraelC=J
ynaottelnirianoitsubmocehtrognidliubot
telniylppusrialacinahcemaotecnaraelC=K*)m38.1(teef6 )m3(teef01nihtiwfievoba)mc19(teef3
devaproklawedisdevapevobaecnaraelC=L
ytreporpcilbupnodetacolyawevid
rokced,hcrop,adnarevrednuecnaraelC=M
Corner Detail
A
B
V
B
B
Inside
G
V
= 9 in U.S.
A
= 12 in Canada
X
Operable
Window
B
A
J
*noitallatsnInaidanaC**noitallatsnISU
*)mc03(sehcni21**)mc03(sehcni21
secnailpparof)mc51(ni6
noitasnednocwodniw
)mm854("81)mm854("81
secnailpparof)mc51(ni6
)m31.2(teef7 )m31.2(teef7
*)mc03(sehcni21 )mc03(sehcni21
.sedoCsaGleuFlanoitaN45APFN/1.322ZSISNAtnerucehthtiwecnadroccanI**
H
3 ft.
A
3 ft.
I
)mc03(ni21,)Wk3(hutB000,01<
dna)Wk3(hutB000,01>secnailpparof
)mc19(sehcni63,)Wk03(hutB000,001<
*)Wk03(hutB000,001>secnailpparof
noitasnednocwodniw
teef51fothgiehanihtiw)mc19(teef3
*ylbmessarotaluger/retemehtevoba
)mc03(ni21,)Wk3(hutB000,01<
dna)Wk3(hutB000,01>secnailpparof
)mc19(sehcni63,)Wk03(hutB000,001<
*)Wk03(hutB000,001>secnailpparof
**yllatnoziroh
.edoCnoitallatsnIenaporPdnAsaGlanoitaN1.941B-ASCtnerrucehthtiwecnadroccanI*
:roolfehthtaenebsedis2muminimanonepoyllufsiynoclabrokced,hcrop,adnarevfidettimrepylnO‡*
E
D
V
M
V
secnailpparof)mc51(ni6
)mc32(ni9,)Wk3(hutB000,01<
dna)Wk3(hutB000,01>secnailpparof
)mc03(sehcni21,)Wk51(hutB000,05<
**)Wk51(hutB000,05>secnailpparof
tneverpotdednemmocer)mm922("9
teef51fothgiehanihtiw)mc19(teef3
**ylbmessarotaluger/retemehtevoba
secnailpparof)mc51(ni6
)mc32(ni9,)Wk3(hutB000,01<
dna)Wk3(hutB000,01>secnailpparof
)mc03(sehcni21,)Wk51(hutB000,05<
**)Wk51(hutB000,05>secnailpparof
sevresdnasgnillewdylimafelgnisowtneewtebdetacolsihcihwyawevirddevaproklawedisaevobayltceridetanimrettonllahstnevA
Figure 8
6
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
FIREPLACE FRAMING SPECIFICATIONS
Figure 9
**FRAMING WITH SQUARE HORIZONTAL TERMINATIONS (SV4.5HTSSL, SV4.5HTSS or SV4.5HTS)
VENT FRAMING ­TOP VENT WITH ONE 90° ELBOW
VENT FRAMING ­REAR VENT WITH NO ELBOWS
33¹⁄₄ (845)
Inches (mm)
16⁵⁄₈
(422)
33¹⁄₄
(845)
37¹⁄₈
(943)
AND ROUND HORIZONTAL TERMINATION (SV4.5HTR)
10¹⁄₂
(267)
7
(178)
19⁵⁄₈
(498)
*12⁷⁄₈
(327)
5¹⁄₈
(130)
5¹⁄₈
(130)
(178)
7
12¹⁄₈
(308)
12¹⁄₈
(308)
Framing should be constructed of 2x4 or larger lumber.
*12⁷⁄₈ inches (327 mm) is the required
framing depth dimension when the finish
material (drywall) thickness is 1/2 in.
(13mm).
** See the horizontal venting Figures 35 and 36 on page 16 for restrictions on the
use of the round termination (SV4.5HTR)
Note­Venting requirements for rear vent applications in corner installations -
- the round termination (SV4.5HTR) may not be used
- the horizontal vent length “a” to “b, must not exceed 28 inches (711 mm)
Framing should be constructed of
2x4 or larger lumber.
*These dimensions occur when one 45
degree elbow is connected directly to the
appliance collar and the unit moved ¹⁄₂ in.
(13 mm) into the room. This ¹⁄₂ in.
movement is required to achieve a min. of
5 in (127 mm) in the F dimension.
*34⁵⁄₁₆
(872)
SV4.5HTSS & SV4.5HTSSL
Termination
*F = 5 in. (127 mm)
a
33¹⁄₈
(841)
*48¹⁄₂
(1232)
Back wall of chase/enclosure (including any finishing materials)
CORNER FRAMING WITH SQUARE HORIZONTAL
TERMINATIONS (SV4.5HTSSL, SV4.5HTSS or SV4.5HTS)
SV4.5HTS Termination
b
7 (178)
b
8³⁄₁₆ (208)
*24¹⁄₄ (616)
*17³⁄₁₆
(437)
Inches
(millimeters)
Figure 10
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
7
FIREPLACE SPECIFICATIONS
FRAMING SPACERS (Top and Sides
and Rear)
Figure 11
33¹⁄₈
(841)
1
(25)
21¹⁄₂
(546)
10³⁄₄
(273)
Top View
(841)
27¹⁄₂ (699)
Front View
33¹⁄₈
17
(432)
6¹³⁄₁₆ (173)
3 (76)
30¹⁄₈
(765)
(Louvered Front Model Shown)
*CONCENTRIC FLUE
FLUE - 4¹⁄₂ (114)
COMBUSTION AIR - 7¹⁄₂ (190)
*DR models have only a rear vent *DT models have only a top vent
NOTE - Eyebrow hood shown as positioned in louvered front model.
ELECTRICAL INLET 2³⁄₄ x 2 (70 x 51) COVER PLATE with KNOCKOUT)
GAS INLET (Either Side and bottom)
3 (76)
Inches (millimeters)
13
(330)
8¹¹⁄₃₂
(212)
Right Side View
1⁵⁄₈ (42)
(13)
¹⁄₂
1 (25)
**19⁵⁄₈
**Rear vent models only
2³⁄₄
(70)
(498)
Step 3. INSTALL THE VENT SYSTEM
General Information
These instructions should be used as a guide­line and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and ­B149.2 in Canada.
These fireplaces are designed, tested and listed for operation and installation with, and only with, Secure Vent (SV 4.5) Direct Vent System Components, Secure Flex Flexible Vent Components manu­factured by Security Chimneys Interna­tional. These approved vent system com­ponents are labeled for identification.
DO NOT use any other manufacturer's vent components with these appli­ances. These fireplaces must be vented
directly to the outside.
The vent system may not service multiple appliances, and must never be connected to a flue serving a solid fuel burning appliance. The vent pipe is tested to be run inside an enclos­ing wall (such as a chase). There is no require­ment for inspection openings in the enclosing wall at any of the joints in the vent pipe.
Preparing the Appliance Top Vent Outlet in All Venting Applications Using the Appliance Top Vent Outlet
A vent restrictor may be needed with this appliance. Install the vent restrictor (provided) in the appliance top flue outlet as shown in
Figure 12
. It is held in place by friction, only.
VENT RESTRICTOR INSTALLATION
(TOP VENT)
In all venting applications using the top vent of
the appliance, a vent restrictor may be
needed. Install the vent restrictor in the top
vent of the appliance outlet.
If needed, install the restrictor orientated as
shown, either from inside or outside the unit,
in the inner fireplace collar.
RESTRICTOR
INNER
FIREPLACE
COLLAR
APPLIANCE TOP VENT OUTLET
Figure 12
8
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Select Venting System - Horizontal or Vertical
With the appliance secured in framing, deter­mine vent routing and identify the exterior termination location. The following sections describe vertical (roof) and horizontal (exterior wall) vent applications. Refer to the section relating to your installation. A list of approved
venting components is shown in the tables on pages 24 and 25.
VERTICAL TERMINATION SYSTEMS (ROOF)
Figures 13, and Figures 23 through 27 on pages 12 to 13
and their associated Vertical Vent Tables illustrate the various ver­tical venting configurations that are possible for use with these appliances. Secure Vent pipe applications are shown in these figures; Secure Flex pipe may also be used. A Vertical Vent Table summarizes each systems mini­mum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications. Both these vertical vent systems terminate through the roof. The minimum vent height above the roof and/or adjacent walls is specified in ANSI Z223.1-(latest edi­tion) (In Canada, the current CAN-1 B149 installation code) by major building codes. Always consult your local codes for specific requirements. A general guide to follow is the Gas Vent Rule (refer to
Figure 4
on page 5).
Vertical (Straight) Installation
Determine the number of straight vent sections required. 4 ¹⁄₂" (114 mm), 10 ¹⁄₂" (267 mm), 22 ¹⁄₂" (572 mm), 34 ¹⁄₂" (876 mm) and 46 ¹⁄₂" (1181 mm) net section lengths are available. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists. Refer to the Vent Section Length Chart.
SV4.5CGV-1 Termination
SV4.5FA OR SV4.5FB Flashing AND SV4.5SC STORM COLLAR
1" (25.4 mm) Minimum Clearance to Combustibles
*SV4.5BF Firestop/Spacer
lanimoN
htgneLnoitceS
621426384
)sehcni(
noitceSteN
2/1-42/1-012/1-222/1-432/1-64
)sehcni(htgneL
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
5.4573.0100001
957.0200002
5.01578.0010001
5152.1110002
5.91526.1210003
1257.1020002
5.22578.1001001
5.52521.2120003
5.13526.2030003
5.43578.2000101
5.73521.3111003
5.34526.3021003
5457.3002002
5.64578.3000011
5.94521.4102003
1552.4100012
5.55526.4012003
7557.4001102
6652.5022004
5.76526.5003003
9657.5000202 27 6103004
5.37521.6100203
5.97526.6010203
1857.6000112
095.7021014
5.19526.7002013
3957.7000022 69 8101204
5.79521.8100023
2015.8200024
5.301526.8000303
801 9100304
4115.9020024
71157.9105006
5.811578.9110305
6215.01001304
5.031578.01101305
53152.11006006
8315.11000404
5.931526.11000033
5.241578.11100405
T O T A L
Q T Y
TRAHCHTGNELNOITCESTNEV
TRAHCHTGNELNOITCESTNEV
noitceSlanimoN
621426384
)sehcni(htgneL
noitceSteN
2/1-42/1-012/1-222/1-432/1-64
)sehcni(htgneL
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
44121100034
0515.21010034
5.451578.21110035
5.061573.31020035
5.271573.41000505
77157.41100506
38152.51010506
6815.51000044
5.091578.51100045
5.691573.61010045
5.502521.71011507
70252.71000606
5.112526.71100607
5.712521.81010607
5.922521.91001607
5.232573.91000055
73257.91100056
5.142521.02000707
6425.02100708 25212010708 46222001708 67232000808
97252.32000066
5.082573.32100809
5.382526.32100067
5.982521.42010067
5.103521.52001067
5.013578.52000909
5135.621009001
5.523521.72000077
0335.72100078 63382010078
54357.8200001001
5.943521.9210001011
27313000088
5.673573.13100089
5.973526.1300011011
5.814578.43000099
32452.531000901
56457.8300000101
T O T A L
Q T Y
40' Max (12.2 M)
Figure 13
SV4.5L6/12/24/36/48 Vent Sections
*When using Secure Flex,
use Firestop/Spacer
SF4.5BF
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
9
Loading...
+ 19 hidden pages