Sungrow SG5.0RT, SG17RT, SG4.0RT, SG12RT, SG10RT User guide

...
Page 1
4.Qibtf!QW!Hsje.Dpoofdufe!Jowfsufs
Vtfs!Nbovbm
SG3.0RT / SG4.0RT / SG5.0RT / SG6.0RT / SG7.0RT / SG8.0RT / SG10RT / SG12RT / SG15RT / SG17RT / SG20RT
WWW.SUNGROWPOWER.COM
SG3.0-20RT-UEN-Ver13-202104
Page 2
Page 3
AAllllRRiigghhttssRReesseerrvveedd
Nopartofthisdocumentcanbereproducedinanyformorbyanymeanswithoutthe
priorwrittenpermissionofSungrowPowerSupplyCo.,Ltd(hereinafter"SUNGROW").
TTrraaddeemmaarrkkss
andotherSungrowtrademarksusedinthismanualareownedby
SUNGROW.
Allothertrademarksorregisteredtrademarksmentionedinthismanualareownedby
theirrespectiveowners.
SSooffttwwaarreeLLiicceennsseess
It is prohibitedto use datacontained in firmwareor software developedby
SUNGROW,inpartorinfull,forcommercialpurposesbyanymeans.
Itisprohibitedtoperformreverseengineering,cracking,oranyotheroperationsthat
compromisetheoriginalprogramdesignofthesoftwaredevelopedbySUNGROW.
I
Page 4

AboutThisManual

Themanualmainlycontainstheproductinformation,aswellasguidelinesforinstallation,
operationandmaintenance.Themanualdoesnotincludecompleteinformationabout
thephotovoltaic(PV)system.Thereadercangetadditionalinformationaboutother
devicesatwwwwww..ssuunnggrroowwppoowweerr..ccoommoronthewebpageoftherespectivecomponent
manufacturer.
VVaalliiddiittyy
Thismanualisvalidforthefollowinginvertermodels:
SG3.0RT
SG4.0RT
SG5.0RT
SG6.0RT
SG7.0RT
SG8.0RT
SG10RT
SG12RT
SG15RT
SG17RT
SG20RT
Theywillbereferredtoas"inverter"hereinafterunlessotherwisespecified.
TTaarrggeettGGrroouupp
Thismanualisintendedforinverterownerswhowillhavetheabilitytointeractwiththe
inverterandqualifiedpersonnelwhoareresponsiblefortheinstallationand
commissioningoftheinverter.Qualifiedpersonnelshouldhavethefollowingskills:
Trainingforinstallationandcommissioningofelectricalsystem,aswellasdealing
withhazards
Knowledgeofthemanualandotherrelateddocuments
Knowledgeofthelocalregulationsanddirectives
HHoowwttooUUsseeTThhiissMMaannuuaall
Readthemanualandotherrelated documentsbeforeperforminganyworkonthe
inverter.Documentsmustbestoredcarefullyandbeavailableatalltimes.
Contentsmaybeperiodicallyupdatedorrevisedduetotheproductdevelopment.The
manualcontentofsubsequentversionsoftheinvertermaybesubjecttochange.The
latestmanualcanbefoundat
ssuuppppoorrtt..ssuunnggrroowwppoowweerr..ccoomm.
II
Page 5
SSyymmbboollss
Importantinstructionscontainedinthismanualshouldbefollowedduringinstallation,
operationandmaintenanceoftheinverter.Theywillbehighlightedbythefollowing
symbols.
Indicatesahazardwithahighlevelofriskthat,ifnotavoided,willresultindeath
orseriousinjury.
Indicatesahazardwithamediumlevelofriskthat,ifnotavoided,couldresultin
deathorseriousinjury.
Indicatesahazardwithalowlevelofriskthat,ifnotavoided,couldresultin
minorormoderateinjury.
Indicatesasituationthat,ifnotavoided,couldresultinequipmentorproperty
damage.
Indicatesadditionalinformation,emphasizedcontentsortipsthatmaybe
helpful,e.g.tohelpyousolveproblemsorsavetime.
III
Page 6
Page 7
CCoonntteennttss
AllRightsReserved.....................................................................................................I
AboutThisManual.....................................................................................................II
1Safety..............................................................................................................1
1.1PVPanels.....................................................................................................1
1.2UtilityGrid....................................................................................................1
1.3Inverter........................................................................................................2
2ProductDescription....................................................................................4
2.1SystemIntroduction.....................................................................................4
2.2ProductIntroduction.....................................................................................5
2.3SymbolsontheProduct...............................................................................7
2.4LEDIndicator...............................................................................................8
2.5CircuitDiagram............................................................................................8
2.6FunctionDescription....................................................................................9
3UnpackingandStorage...........................................................................12
3.1UnpackingandInspection..........................................................................12
3.2InverterStorage.........................................................................................12
4MechanicalMounting..............................................................................13
4.1SafetyduringMounting..............................................................................13
4.2LocationRequirements..............................................................................13
4.2.1EnvironmentRequirements...............................................................13
4.2.2CarrierRequirements........................................................................14
4.2.3AngleRequirements.........................................................................14
4.2.4ClearanceRequirements..................................................................15
4.3InstallationTools.........................................................................................16
4.4MovingtheInverter....................................................................................17
4.5InstallingtheInverter..................................................................................17
5ElectricalConnection...............................................................................20
5.1SafetyInstructions......................................................................................20
5.2TerminalDescription...................................................................................20
5.3ElectricalConnectionOverview..................................................................22
5.4AdditionalGroundingConnection...............................................................23
V
Page 8
5.4.1AdditionalGroundingRequirements..................................................24
5.4.2ConnectionProcedure......................................................................24
5.5ACCableConnection.................................................................................25
5.5.1ACSideRequirements......................................................................25
5.5.2AssemblingtheACConnector(<15kW)..........................................26
5.5.3InstallingtheACConnector(<15kW)...............................................28
5.5.4AssemblingtheACConnector(≥15kW).........................................29
5.5.5InstallingtheACConnector(≥15kW)..............................................31
5.6DCCableConnection.................................................................................33
5.6.1PVInputConfiguration......................................................................34
5.6.2AssemblingthePVConnectors.........................................................35
5.6.3InstallingthePVConnectors.............................................................36
5.7WiNet-SConnection..................................................................................38
5.7.1EthernetCommunication..................................................................38
5.7.2WLANCommunication.....................................................................40
5.8WiFiConnection(forBrazil)........................................................................40
5.9MeterConnection......................................................................................41
5.9.1AssemblingtheCOMConnector.......................................................41
5.9.2InstallingtheCOMConnector...........................................................43
5.10RS485Connection...................................................................................44
5.10.1RS485CommunicationSystem......................................................44
5.10.2AssemblingtheCOMConnector.....................................................45
5.10.3InstallingtheCOMConnector.........................................................48
5.11DOConnection.........................................................................................49
5.12DRMConnection......................................................................................50
5.13DIConnection..........................................................................................50
6Commissioning...........................................................................................54
6.1InspectionbeforeCommissioning...............................................................54
6.2PoweringontheSystem.............................................................................54
6.3AppPreparation.........................................................................................55
6.4CreatingaPlant..........................................................................................55
6.5InitializingtheDevice..................................................................................58
6.6ConfiguringthePlant..................................................................................61
7iSolarCloudApp..........................................................................................65
7.1BriefIntroduction........................................................................................65
7.2InstallingtheApp........................................................................................65
VI
Page 9
7.3AccountRegistration..................................................................................66
7.4Login..........................................................................................................67
7.4.1Requirements...................................................................................67
7.4.2LoginProcedure...............................................................................67
7.5InitialSettings.............................................................................................69
7.6FunctionOverview.....................................................................................69
7.7Home.........................................................................................................70
7.8RunInformation.........................................................................................71
7.9Records.....................................................................................................72
7.10More........................................................................................................75
7.10.1SystemParameters........................................................................75
7.10.2OperationParameters....................................................................76
7.10.3PowerRegulationParameters.........................................................77
7.10.4CommunicationParameters...........................................................82
7.10.5FirmwareUpdate............................................................................82
8SystemDecommissioning......................................................................84
8.1DisconnectingtheInverter..........................................................................84
8.2DismantlingtheInverter..............................................................................85
8.3DisposaloftheInverter...............................................................................85
9TroubleshootingandMaintenance......................................................86
9.1Troubleshooting.........................................................................................86
9.2Maintenance..............................................................................................90
9.2.1MaintenanceNotices........................................................................90
9.2.2RoutineMaintenance........................................................................91
9.2.3FanMaintenance.............................................................................91
10Appendix....................................................................................................94
10.1TechnicalData.........................................................................................94
10.2QualityAssurance..................................................................................104
10.3ContactInformation...............................................................................105
VII
Page 10
Page 11
1

Safety

Thedevicehas beendesigned andtested strictlyaccording tointernational safety
regulations.Readallsafetyinstructionscarefullypriortoanyworkandobservethemat
alltimeswhenworkingonorwiththedevice.
Incorrectoperationorworkmaycause:
Injuryordeathtotheoperatororathirdparty;
Damagetothedeviceandotherproperties.
Alldetailedwork-relatedsafetywarningsandnotesarespecifiedatcriticalpointsinthis
manual.
Thesafetyinstructionsinthismanualcannotcoveralltheprecautionsthat
shouldbefollowed.Performoperationsconsideringactualonsiteconditions.
SUNGROWshallnotbeheldliableforanydamagecausedbyviolationofthe
safetyinstructionsinthismanual.

1.1PVPanels

PVstringswillproduceelectricalpowerwhenexposedtosunlightandcan
causealethalvoltageandanelectricshock.
Alwayskeep inmindthat theinverteris dualpowersupplied.Electrical
operatorsmustwearproperpersonalprotectiveequipment:helmet,
insulatedfootwear,gloves,etc.
BeforetouchingtheDCcables,operatormustuseameasuringdeviceto
ensurethatthecableisvoltage-free.
TheopeatormustfollowallwarningsonthePVstringsandinitsmanual.

1.2UtilityGrid

Followtheregulationsrelatedtotheutilitygrid.
1
Page 12
1SafetyUserManual
Allelectricalconnectionsmustbeinaccordancewithlocalandnational
standards.
Onlywiththepermissionofthelocalutilitygridcompany,theinvertercanbe
connectedtotheutilitygrid.

1.3Inverter

Dangertolifefromelectricshocksduetolivevoltage
Donotopentheenclosureatanytime.Unauthorizedopeningwillvoidwarranty
andwarrantyclaimsandinmostcasesterminatetheoperatinglicense.
Riskofinverterdamageorpersonalinjury
DonotconnectordisconnectthePVandACconnectorswhentheinverteris
running.
Waitatleast10minutesfortheinternalcapacitorstodischargeafterall
electricdevicesareremovedandtheinverterispoweredoff.
Ensurethatthereisnovoltageorcurrentbeforeconnectingordisconnecting
thePVandACconnectors.
Allsafetyinstructions,warninglabels,andnameplateontheinverter:
Mustbeclearlylegible.
Shouldnotberemovedorcovered.
Riskofburnsduetohotcomponents!
Donottouchanyhotparts(suchastheheatsink)duringoperation.OnlytheDC
switchcansafelybetouchedatanytime.
2
Page 13
UserManual1Safety
Onlyqualifiedpersonnelcanperformthecountrysetting.Unauthorized
alterationmaycauseabreachofthetype-certificatemarking.
Riskofinverterdamageduetoelectrostaticdischarge(ESD)!
Bytouchingtheelectroniccomponents,youmaydamagetheinverter.For
inverterhandling,besureto:
avoidanyunnecessarytouching;
wearagroundingwristbandbeforetouchinganyconnectors.
3
Page 14
2

ProductDescription

2.1SystemIntroduction

Theinverterisatransformerless3-phasePVgrid-connectedinverter.Asanintegral
componentinthe PVpowersystem, theinverter isdesignedto convertthe direct
currentpowergeneratedfromthePVmodulesintogrid-compatibleACcurrentand
feedstheACcurrenttotheutilitygrid.
TheinvertermustonlybeoperatedwithPVstringswithclassIIprotectionin
accordancewithIEC61730,applicationclassA.Itisnotallowedforthe
positivepoleorthenegativepoleofthePVstringstobegrounded.Thiscan
causedamagetotheinverter.
DamagestotheproductduetoafaultyordamagedPVinstallationarenot
coveredbywarranty.
Anyuseotherthantheonedescribedinthisdocumentisnotpermitted.
Theintendedusageoftheinverterisillustratedinthefollowingfigure.
FFiigguurree22--11InverterApplicationinPVPowerSystem
IItteemm
A
BInverter
C
D
Thefollowingfigureshowsthecommongridconfigurations.
4
DDeessccrriippttiioonn
PVstrings
MeteringdeviceMetercupboardwithpowerdistributionsystem
Utilitygrid
NNoottee
Compatiblewithmonocrystallinesilicon,polycrystalline
silicon,andthin-filmmoduleswithoutgrounding
SG3.0RT,SG4.0RT,SG5.0RT,SG6.0RT,SG7.0RT,
SG8.0RT,SG10RT,SG12RT,SG15RT,SG17RT,SG20RT
TT,TN-C,TN-S,TN-C-S
Page 15
UserManual2ProductDescription

2.2ProductIntroduction

MMooddeellDDeessccrriippttiioonn
Themodeldescriptionisasfollows(takeSG10RTasanexample):
AAppppeeaarraannccee
Thefollowingfigureshowsthedimensionsoftheinverter.Theimageshownhereisfor
referenceonly.Theactualproductreceivedmaydiffer.
5
Page 16
2ProductDescriptionUserManual
FFiigguurree22--22InverterAppearance
NNoo..NNaammee
DDeessccrriippttiioonn
Toclearlyidentifytheproduct,includingdevicemodel,S/
1
Nameplate
N,importantspecifications,marksofcertification
institutions,etc.
2LEDindicator
Hanger
3
4Label
5DCswitch
Electrical
6
connectionarea
7Fans
Toindicatethecurrentworkingstateoftheinverter.
Complementtotheincludedwall-mountingbracketfor
hangingtheinverter.
InformationaboutCCOOMM22pindefinition,supportedDRM
modes,etc.
TosafelydisconnecttheDCcircuitwhenevernecessary.
DCterminals(SG20RTforexample),ACterminal,
additionalgroundingterminalandcommunication
terminals.
Optimizationoftheinverter’sheatdissipation.Onlythe
SG15RT,SG17RTandSG20RTareequippedwithfans.
DDiimmeennssiioonnss
Thefollowingfigureshowsthedimensionsoftheinverter.
6
Page 17
UserManual2ProductDescription
FFiigguurree22--33DimensionsoftheInverter(inmm)

2.3SymbolsontheProduct

SSyymmbboollEExxppllaannaattiioonn
Regulatorycompliancemark.
TÜVmarkofconformity.
CEmarkofconformity.
Donotdisposeoftheinvertertogetherwithhouseholdwaste.
Theinverterdoesnothaveatransformer.
Disconnecttheinverterfromalltheexternalpowersources
beforemaintenance!
Readtheusermanualbeforemaintenance!
Burndangerduetothehotsurfacethatmayexceed60℃.
7
Page 18
2ProductDescriptionUserManual
SSyymmbboollEExxppllaannaattiioonn
Dangertolifeduetohighvoltages!
Donottouchlivepartsfor10minutesafterdisconnection
fromthepowersources.
Onlyqualifiedpersonnelcanopenandmaintaintheinverter.
Additionalgroundingpoint.
*Thetableshownhereisforreferenceonly.Theactualproductreceivedmaydiffer.

2.4LEDIndicator

TheLEDindicatoronthefrontoftheinverterindicatestheworkingstateoftheinverter.
Table2-1StatedescriptionoftheLEDindicator
LLEEDDccoolloorrSSttaatteeDDeeffiinniittiioonn
On
Theinverterisoperatingnormally.
Blue
Red
Gray

2.5CircuitDiagram

Thefollowingfigureshowsthemaincircuitoftheinverter.
Flashing
On
Off
Theinverterisatstandbyorstartupstate(not
feedingpowerintothegrid).
Asystemfaulthasoccured.
BoththeACandDCsidesarepowereddown.
8
Page 19
UserManual2ProductDescription
FFiigguurree22--44CircuitDiagram(SG5.0RTforexample)
TheDCswitchisusedtosafelydisconnecttheDCcircuit.
TheMPPTisutilizedforDCinputtoensurethemaximumpowerfromthePVarrayat
differentPVinputconditions.
TheinvertercircuitconvertstheDCpowerintoACpowerandgeneratesACpowerto
loadsorutilitygridthroughtheACterminal.
Theprotectioncircuitensuresthesafeoperationofthedeviceandpersonalsafety.

2.6FunctionDescription

BBaassiiccFFuunnccttiioonn
Conversionfunction
TheinverterconvertstheDCpowerfromthePVarraytotheACpower,inconformity
withthegridrequirements.
Datastorage
Theinverterlogsrunninginformation,errorrecords,etc.
Parameterconfiguration
Theinverterprovidesvariousparameterconfigurationsfor optimaloperation.
ParameterscanbesetviatheiSolarCloud Apporthecloudserver. Forfurther
configurations,whichexceedstheusualparametersconfiguration,pleasecontact
Sungrow.
Communicationinterface
Theinverter isequippedwithtwo communicationinterfaces.Thecommunication
devicecanbeconnectedtotheinverterviabothinterfaces.
Aftercommunicationconnectionisestablished,userscanviewinverterinformation,
operationaldataandcansetinverterparametersthroughtheiSolarCloud.
ItisrecommendedtousethecommunicationmodulefromSUNGROW.
Usingadevicefromothercompaniesmayleadtocommunicationfailure
orotherunexpecteddamage.
9
Page 20
2ProductDescriptionUserManual
ProtectionFunction
Severalprotectivefunctions areintegrated intheinverter, includingshort circuit
protection,grounding insulationresistancemonitoring, residualcurrentprotection,
gridmonitoring,DCovervoltage/overcurrentprotection,etc.
EEaarrtthhFFaauullttAAllaarrmm
TheinverterisequippedwithaDOrelayforthelocalearthfaultalarm.Theadditional
equipmentrequiredisalightindicatorand/orabuzzerthatneedsadditionalpower
supply.
After theconnection, if the earthfault occurs, theDO dry-contact willswitch on
automaticallytosignaltheexternalalarm.
DDRRMM((""AAUU""//""NNZZ""))
TheDRMfunctionisonlyapplicabletoasingleinverter.
TheinverterprovidesterminalsforconnectingtoaDemandResponseEnablingDevice
(DRED).Aftertheconnection,theDREDassertsdemandresponsemodes(DRMs).The
inverterdetectsandinitiatesaresponsetoallsupporteddemandresponsemodeslisted
inthefollowingtable.
Table2-2DemandResponseModeExplanation
MMooddeeEExxppllaannaattiioonn
DRM0Theinverterisinthestateofstandby.
RRiipppplleeCCoonnttrrooll
Theinverterprovidesterminals(DRM)forconnectingtoaRippleControlReceiver(RCR).
Aftertheconnection,thegriddispatchingcenterissuesregulationinstructionsviadry
contact (DI).The inverter cancontrol power outputaccording to thelocal preset
instructions.
PPIIDDRReeccoovveerryy
Forpositivevoltagescheme,afterthePIDfunctionisenabled,thevoltagetoground
ofallPVstringsisgreaterthan0,andthereforethePVstring-to-groundvoltageisa
positivevalue.
10
Fornegativevoltagescheme,afterthePIDfunctionisenabled,thevoltagetoground
ofallPVstringsislowerthan0,andthereforethePVstring-to-groundvoltageisa
negativevalue.
Page 21
UserManual2ProductDescription
BeforeenablingthePIDrecoveryfunction,makesurethevoltagepolarityof
thePVmodulestogroundmeetsrequirement.Ifthereareanyquestions,
contactthePVmodulemanufacturerorreaditscorrespondingusermanual.
Ifthe voltageschemefor thePID recoveryfunction doesnotmeet the
requirementofcorrespondingPVmodules,thePIDfunctionwillnotworkas
expectedorevendamagethePVmodules.
Whenthe inverteris notrunning, thePID modulewillapply inversevoltage toPV
modules,torestorethedegradedmodules.
IfthePIDrecoveryfunctionisenabled,itonlyworksatnight.
AfterthePIDrecoveryfunctionisenabled,thevoltageofthePVstringsto
groundis500VDCbydefault,andthedefaultvaluecanbemodified
throughtheApp.
11
Page 22
3

UnpackingandStorage

3.1UnpackingandInspection

Thedevice isthoroughly testedand strictlyinspected beforedelivery. Nonetheless,
damagemaystilloccurduringshipping.Forthisreason,pleaseconductathorough
inspectionafterreceivingthedevice.
Checkthepackingcaseforanyvisibledamage.
Checkthescopeofdeliveryforcompletenessaccordingtothepackinglist.
Checktheinnercontentsfordamageafterunpacking.
ContactSUNGROWorthetransportcompanyincaseofanydamageor
incompleteness,andprovidephotostofacilitateservices.
Donotdisposeoftheoriginalpackingcase.Itisrecommendedtostorethedeviceinthe
originalpackingcasewhenthedeviceisdecommissioned.

3.2InverterStorage

Properstorageisrequirediftheinverterisnotinstalledimmediately.
Storetheinverterintheoriginalpackingcasewiththedesiccantinside.
The storage temperaturemust be alwaysbetween -30℃ and +70℃,and the
storagerelativehumiditymustbealwaysbetween0and95%,non-condensing.
Incaseofstackingstorage,thenumberofstackinglayersshouldneverexceedthe
limitmarkedontheoutersideofthepackingcase.
Thepackingcaseshouldbeupright.
Iftheinverterhasbeenstoredmorethanhalfayear,thequalifiedpersonnelshould
thoroughlycheckandtestitbeforeinstallation.
12
Page 23
4

MechanicalMounting

4.1SafetyduringMounting

Makesurethereisnoelectricalconnectionbeforeinstallation.
Inordertoavoidelectricshockorotherinjury,makesurethatholeswillnotbe
drilledoveranyelectricityorplumbinginstallations.
Riskofinjuryduetoimproperhandling
Alwaysfollowtheinstructionswhenmovingandpositioningtheinverter.
Improperoperationmaycauseinjuriesorseriouswounds.
Inthecaseofpoorventilation,thesystemperformancemaycompromise.
Keeptheheatsinksuncoveredtoensureheatdissipationperformance.

4.2LocationRequirements

Selectanoptimalmountinglocationforsafeoperation,longservicelifeandexpected
performance.
TheinverterwithprotectionratingIP65canbeinstalledbothindoorsandoutdoors.
Installtheinverterataplaceconvenientforelectricalconnection,operation,and
maintenance.

4.2.1 EnvironmentRequirements

Theinstallationenvironmentmustbefreeofinflammableorexplosivematerials.
Thelocationshouldbenotaccessibletochildren.
13
Page 24
4MechanicalMountingUserManual
Theambienttemperatureandrelativehumiditymustmeetthefollowing
requirements.
Avoiddirectexposuretosun,rainandsnow.
Theinvertershouldbewellventilated.Ensureaircirculation.
Neverinstall theinverterin livingareas. Theinverter willgenerate noiseduring
operation,affectingdailylife.

4.2.2 CarrierRequirements

Theconcretewallshouldbecapableofwithstandingaforceoffourtimestheweightof
theinverterandbesuitableforthedimensionsoftheinverter.
Theinstallationcarriershouldmeetthefollowingrequirements:

4.2.3 AngleRequirements

Install the inverter vertically. Never install the inverterhorizontally, or at forward/
backwardtilted,sidetilted,orupsidedown.
14
Page 25
UserManual4MechanicalMounting

4.2.4 ClearanceRequirements

Reserveenough clearancearound theinverter toensure sufficientspace forheat
dissipation.
Incaseofmultipleinverters,reservespecificclearancebetweentheinverters.
15
Page 26
4MechanicalMountingUserManual
Installthe inverterat anappropriateheight forease ofviewing LEDindicatorand
operatingswitch(es).

4.3InstallationTools

Installationtoolsincludebutarenotlimitedtothe followingrecommendedones.If
necessary,useotherauxiliarytoolsonsite.
Table4-1Toolspecification
Goggles
EarplugsDustmaskProtectivegloves
InsulatedshoesUtilityknifeMarkerWriststrap
WirecutterWirestripperHydraulicplierRubbermallet
Hammerdrill
(φ10)
Phillipsscrewdriver
(M3,M4,M6)
Electricscrewdriver
(M3,M4,M6)
Wrench(30mm,
35mm,46mm)
16
RJ45crimpingtoolVacuumcleanerMeasuringtapeHeatshrinktubing
Page 27
UserManual4MechanicalMounting
Heatgun
crimpingtool(4
mm2–6mm2)
Slotted
screwdriver(M2)

4.4MovingtheInverter

Beforeinstallation, removethe inverterfrom thepacking caseandmove itto the
installationsite.Followtheinstructionsbelowasyoumovetheinverter:
Alwaysbeawareoftheweightoftheinverter.
Lifttheinverterusingthehandlespositionedonbothsidesoftheinverter.
Movetheinverterbyoneortwopeopleorbyusingapropertransporttool.
Donotreleasetheequipmentunlessithasbeenfirmlysecured.
MC4terminal
MC4terminal
wrench
Tubeterminal
crimpingtool(0.5
mm2–1.0mm2)
Multimeter(≥
1100Vdc)

4.5InstallingtheInverter

Inverterisinstalledonthewallbymeansofwall-mountingbracketandtheexpansion
plugsets.
Theexpansionplugsetshownbelowisrecommendedfortheinstallation.
(1)Self-tapping
screwM6
(2)Expansiontube(3)Fenderwasher(4)Springwasher
17
Page 28
4MechanicalMountingUserManual
Step1Placethewall-mountingbrackettoaproperpositiononthewall.Observethelevelon
thebracketandadjustuntilthebubbleisinthemiddleposition.Markthepositionsand
drilltheholes.
Thedepthoftheholesshouldbeabout70mm.
Step2Placetheexpansiontubesintotheholes.Thensecurethewall-mountingbrackettothe
wallfirmlywiththeexpansionboltsets.
Step3Lifttheinverterandslideitdownalongthewall-mountingbrackettomakesurethey
matchperfectly.Usethefastenersettolockthedevice.
18
Page 29
UserManual4MechanicalMounting
----EEnndd
19
Page 30
5

ElectricalConnection

5.1SafetyInstructions

Priorto anyelectricalconnections, keepinmind thattheinverter hasdualpower
supplies. It is mandatory for thequalified personnel to wear personal protective
equipments(PPE)duringtheelectricalwork.
Dangertolifeduetoahighvoltageinsidetheinverter!
ThePVstringwillgeneratelethalhighvoltagewhenexposedtosunlight.
Beforestarting electricalconnections,disconnect theDCand ACcircuit
breakersandpreventthemfrominadvertentreconnection.
Ensurethatallcablesarevoltagefreebeforeperformingcableconnection.
Anyimproperoperationsduringcableconnectioncancausedevicedamage
orpersonalinjury.
Onlyqualifiedpersonnelcanperformcableconnection.
All cablesmust be undamaged, firmlyattached, properly insulatedand
adequatelydimensioned.
ComplywiththesafetyinstructionsrelatedtothePVstringsandtheregulations
relatedtotheutilitygrid.
Allelectricalconnections mustbe inaccordance withlocal andnational
standards.
Onlywiththepermissionofthelocalutilitygridcompany,theinvertercanbe
connectedtotheutilitygrid.

5.2TerminalDescription

Allelectricalterminalsarelocatedatthebottomoftheinverter.
20
Page 31
UserManual5ElectricalConnection
FFiigguurree55--11Terminals(SG20RTforexample)
*Theimageshownhereisforreferenceonly.Theactualproductreceivedmaydiffer.
Table5-1TerminalDescription
DDeecciissiivvee
NNoo..NNaammee
DDeessccrriippttiioonn
VVoollttaaggee
CCllaassssiiffiiccaattiioonn
PV1+,PV1–,PV2+,
PV2–,PV3+,PV3–,
1
PV4+,PV4–
MC4terminalsforPVinput.
Theterminalnumberdependson
invertermodel.
DVC-C
Communicationaccessoryportto
2COM1
beconnectedtoWiNet-Sfor
countriesexceptBrazilortoWiFi
DVC-A
forBrazil.
3AC
ACterminaltoconnecttothegrid.
DVC-C
4
Additionalgroundingterminal.Notapplicable
CommunicationconnectionforDI/
5COM2
DRM,DO,Loggerandsmart
energymeter.
ThepindefinitionofCOM2terminalisshowninthefollowinglabel.
DVC-A
21
Page 32
5ElectricalConnectionUserManual
FFiigguurree55--22LabelofCOM2Terminal
Table5-2LabelDescriptionofCOM2Terminal
LLaabbeell
RSD
NS
DRM
RSD-1,
RSD-2
NS-1,NS-2
D1/5,D2/6,
D3/7,D4/8,
R,C
DDeessccrriippttiioonn
Reserved
Reserved
ForexternalDemandResponseEnablingDevice("AU"/
"NZ")
ForRippleControl
Forinverterdaisychain
RS485-1
A1,B1
(CannotbeusedsimultaneouslywithCOM1portfor
WiNet-S)
Externalalarminterface,e.g.lightindicatorand/orbuzzer
DO
NO,COM
TheexternalDCvoltageshouldnotbehigherthan30V
andthecurrentnothigherthan1A.
RS485-3
Meter
A3,B3
A2,B2
Reserved
Smartenergymeterinterface

5.3ElectricalConnectionOverview

Theelectricalconnectionshouldberealizedasfollows:
22
(A)PVstring(B)Inverter(C)Grid
(D)Externaldevice(E)ACcircuitbreaker(F)Smartenergymeter
Page 33
UserManual5ElectricalConnection
Table5-3CableRequirements
NNoo..CCaabbllee
1DCcable
2Ethernet
cable
3Meter
RS485
(1)
cable
ACcable
4
Additional
5
Grounding
cable
TTyyppee
Outdoormulti-core
copperwirecable
complyingwith
1100Vand30A
standard
CAT5Eoutdoor
shieldednetwork
cable
Shieldedtwisted
pair
Outdoor5-core
(2)
copperwirecable
Outdoorsingle-
corecopperwire
cable
CCaabblleeDDiiaammeetteerr
6mm–9mm4mm
5.3mm–7mm8*0.2mm
5.3mm–7mm
SG3.0RTto
SG12RT:10
mm–21mm
SG15RTto
SG20RT:14
mm–25mm
WWiirreeCCoonndduuccttoorr
CCrroossss--sseeccttiioonn
2
–6mm
2
2
2*(0.5–1.0)mm
SG3.0RTto
SG12RT:4mm2–6
2
mm
SG15RTto
SG20RT:6mm
2
10mm
2
ThesameasthatofthePEwireintheAC
cable
2
(1)ThecablerequirementsforCCOOMM22terminalconnectionarethesame.
(2)AlltheACwiresshouldbeequippedwithcorrectlycoloredcablesfordistinguishing.
Pleaserefertorelatedstandardsaboutthewiringcolor.

5.4AdditionalGroundingConnection

Since the inverteris transformerless, neither thenegative pole nor the
positivepoleofthePVstringmustbegrounded.Otherwise,theinverterwill
notoperatenormally.
Connecttheadditionalgroundingterminaltotheprotectivegroundingpoint
beforeACcableconnection,PVcableconnection,andcommunicationcable
connection.
Thegroundconnectionofthisadditionalgroundingterminalcannotreplace
theconnectionofthePEterminaloftheACcable.Makesurethoseterminals
are bothgrounded reliably. SUNGROW shallnot be held liablefor any
damagecausedbytheviolation.
23
Page 34
5ElectricalConnectionUserManual

5.4.1 AdditionalGroundingRequirements

Allnon-currentcarryingmetalpartsanddeviceenclosuresinthePVpowersystem
shouldbegrounded,forexample,mountsofPVmodulesandtheinverterenclosure.
WhenthereisonlyoneinverterinthePVsystem,connecttheadditionalgrounding
cabletoanearbygroundingpoint.
WhentherearemultipleinvertersinthePVsystem,connectgroundingpointsofall
invertersandthePVarrayframestotheequipotentialcable(accordingtotheonsite
conditions)toimplementanequipotentialconnection.

5.4.2 ConnectionProcedure

AdditionalgroundingcableandOT/DTterminalarepreparedbycustomers.
Step1PreparethecableandOT/DTterminal.
(1)Heatshrinktubing
(2)OT/DTterminal
Step2Removethescrewonthegroundingterminalandfastenthecablewithascrewdriver.
24
Page 35
UserManual5ElectricalConnection
Step3Applypainttothegroundingterminaltoensurecorrosionresistance.
----EEnndd

5.5ACCableConnection

5.5.1 ACSideRequirements

Connecttheinvertertothegridonlyaftergettinganapprovalfromthelocal
electricpowercompany.
Before connectingthe inverterto thegrid, ensurethe gridvoltage andfrequency
complywithrequirements,forwhich,referto""TTeecchhnniiccaallDDaattee"".Otherwise,contactthe
electricpowercompanyforhelp.
AACCCCiirrccuuiittBBrreeaakkeerr
Anindependentthreeorfour-polecircuitbreakermustbeinstalledontheoutputsideof
theinvertertoensuresafedisconnectionfromthegrid.Therecommended
specificationsareasfollows.
IInnvveerrtteerrMMooddeell
SG3.0RT/SG4.0RT/SG5.0RT/
SG6.0RT
SG7.0RT/SG8.0RT20A
SG10RT25A
SG12RT32A
SG15RT/SG17RT40A
SG20RT50A
RReeccoommmmeennddeeddSSppeecciiffiiccaattiioonn
16A
25
Page 36
5ElectricalConnectionUserManual
DeterminewhetheranACcircuitbreakerwithgreaterovercurrentcapacityis
requiredbasedonactualconditions.
Multipleinverterscannotshareonecircuitbreaker.
Neverconnectaloadbetweentheinverterandthecircuitbreaker.
RReessiidduuaallCCuurrrreennttMMoonniittoorriinnggDDeevviiccee
Withanintegrateduniversalcurrent-sensitiveresidualcurrentmonitoringunitincluded,
theinverterwilldisconnectimmediatelyfromthemainspoweronceafaultcurrentwith
avalueexceedingthelimitisdetected.
Howeverifanexternalresidualcurrentdevice(RCD)ismandatory,theswitchmustbe
triggeredataresidualcurrentof300mA(recommended),oritcanbesettoother
valuesaccordingtolocalregulations.ForexampleinAustralia,theinvertercanusean
additional30mA(typeA)RCDininstallations.
MMuullttiipplleeIInnvveerrtteerrssiinnppaarraalllleellCCoonnnneeccttiioonn
Ifmultipleinvertersareconnectedinparalleltothegrid,ensurethatthetotalnumberof
parallelinvertersdoesnotexceed5.Otherwise,pleasecontactSUNGROWfortechnical
scheme.

5.5.2 AssemblingtheACConnector(<15kW)

TheACterminalblockisonthebottomsideoftheinverter.ACconnectionisthethree-
phase-four-wiregrid+PEconnection(L1,L2,L3,N,andPE).
Step1UnscrewtheswivelnutoftheACconnector.
Step2Takeoutthespring-loadedterminalfromthehousing.
26
Page 37
UserManual5ElectricalConnection
Step3ThreadtheACcableofappropriatelengththroughtheswivelnut,thesealingringand
thehousing.
Step4Remove45mmofthecablejacketand12mm–16mmofthewireinsulation.
Step5Opentheclamponthespring-loadedterminalandinsertthewiresintothe
correspondingholes.Closetheclampandpushtheterminalintothehousinguntilthere
isanaudibleclick.
27
Page 38
5ElectricalConnectionUserManual
Observetheterminalassignment.Donotconnectanyphaselinetothe"PE"
terminalorPEwireto"N"terminal.Otherwise,unrecoverabledamagetothe
invertermayfollow.
Step6Ensurethatthewiresaresecurelyinplacebyslightlypullingthem.Tightentheswivel
nuttothehousing.
----EEnndd

5.5.3 InstallingtheACConnector(<15kW)

Highvoltagemaybepresentininverter!
Ensureallcablesarevoltage-freebeforeelectricalconnection.
DonotconnecttheACcircuitbreakeruntilallinverterelectricalconnectionsare
completed.
Step1DisconnecttheACcircuitbreakerandsecureitagainstreconnection.
Step2RemovethewaterprooflidfromtheAACCterminal.
28
Page 39
UserManual5ElectricalConnection
Step3LiftthelockingpartupwardsandinserttheACconnectorintotheAACCterminalonthe
bottomsideoftheinverter.Thenpressthelockingpartandsecureitwiththescrew.
Step4ConnectthePEwiretogroundandthephaselinesandthe“N”linetoACcircuit
breaker.ThenConnecttheACcircuitbreakertoelectricboard.
Step5Makesureallwiresarefirmlyinstalledviatherighttorquetoolordraggingthecables
slightly.
----EEnndd

5.5.4 AssemblingtheACConnector(≥15kW)

TheACterminalblockisonthebottomsideoftheinverter.ACconnectionisthethree-
phase-four-wiregrid+PEconnection(L1,L2,L3,N,andPE).
Step1UnscrewtheswivelnutoftheACconnector.
Step2(Optional)Removetheinnersealingringifthe cablediameteris19mm–25mm.
Otherwiseskipthisstep.
29
Page 40
5ElectricalConnectionUserManual
Step3Takeoutthescrew-typeterminalplugfromthehousing.
Step4ThreadtheACcableofappropriatelengththroughtheswivelnutandthehousing.
Step5Remove80mm–90mmofthecablejacketand12mmofthewireinsulation.
Step6((OOppttiioonnaall))Whenusingamulti-coremulti-strandcopperwirecable,connecttheAC
wireheadtothecordendterminal(hand-tight).Incaseofsingle-strandcopperwire,
skipthisstep.
Step7Fixallthewirestothescrew-typeterminalaccordingtotheassignmentandtightentoa
torqueof1.2Nm–1.5Nm withascrewdriver. Thenpushtheterminal intothe
housinguntilthereisanaudibleclick.
30
Page 41
UserManual5ElectricalConnection
Observetheterminalassignment.Donotconnectanyphaselinetothe"PE"
terminalorPEwireto"N"terminal.Otherwise,unrecoverabledamagetothe
invertermayfollow.
Step8Ensurethatthewiresaresecurelyinplacebyslightlypullingthem.Tightentheswivel
nuttothehousing.
----EEnndd

5.5.5 InstallingtheACConnector(≥15kW)

Highvoltagemaybepresentininverter!
Ensureallcablesarevoltage-freebeforeelectricalconnection.
DonotconnecttheACcircuitbreakeruntilallinverterelectricalconnectionsare
completed.
Step1DisconnecttheACcircuitbreakerandsecureitagainstreconnection.
Step2RemovethewaterprooflidfromtheAACCterminal.
31
Page 42
5ElectricalConnectionUserManual
Step3InserttheACconnectorintotheAACCterminalonthebottomoftheinverteruntilthereis
anaudiblesound.
Step4((OOppttiioonnaall))SecuretheACconnector,asshowninthefigurebelow.
32
Page 43
UserManual5ElectricalConnection
Step5ConnectthePEwiretogroundandthephaselinesandthe"N"linetoACcircuitbreaker.
ThenconnecttheACcircuitbreakertoelectricboard.
Step6Makesureallwiresarefirmlyinstalledviatherighttorquetoolordraggingthecables
slightly.
----EEnndd

5.6DCCableConnection

Dangerofelectricshock!
ThePVarraywillgeneratelethalhighvoltageonceexposedtosunlight.
MakesurethePVarrayiswellinsulatedtogroundbeforeconnectingittothe
inverter.
Riskofinverterdamage!Observethefollowingrequirements.Failuretodoso
willvoidguaranteeandwarrantyclaims.
MakesurethemaximumDCvoltageandthemaximumshortcircuitcurrent
ofanystringneverexceedinverterpermittedvaluesspecifiedin"Technical
Data".
MixeduseofdifferentbrandormodelofPVmodulesinaPVstringora
compromisedPVstringdesigncomposedwithPVmodulesfromrooftoops
ofdifferentorientationmaynotdamageinverterbutwillcausesystembad
performance!
Theinverterentersstandbystatewhentheinputvoltagerangesbetween
1,000Vand1,100V.Theinverterreturnstorunningstateoncethevoltage
returnstotheMPPToperatingvoltagerange,namely,160Vto1,000V.
33
Page 44
5ElectricalConnectionUserManual

5.6.1 PVInputConfiguration

TheinvertersSG3.0RT/SG4.0RT/SG5.0RT/SG6.0RThavetwoPVinputs,SG7.0RT/
SG8.0RT/SG10RT/SG12RT havethree PVinputs andSG15RT/SG17RT/SG20RT
havefourPVinputs.
TheinvertershavetwoMPPtrackers.EachDCinputareacanoperateindependently.
ThePVstringstothesameDCinputareashouldhavethesametype,thesame
numberofPVpanels,identicaltiltandidenticalorientationformaximumpower.
ThePVstrings totwoDCinputareasmaydifferfromeachother,includingPV
moduletype,numberofPVmodulesineachstring,angleoftilt,andinstallation
orientation.
FFiigguurree55--33PVInputConfiguration(SG20RTforexample)
PriortoconnectingtheinvertertoPVinputs,thespecificationsinthefollowingtable
shouldbemet:
IInnvveerrtteerrMMooddeell
OOppeenn--cciirrccuuiittVVoollttaaggeeLLiimmiittMMaaxx..ccuurrrreennttffoorriinnppuuttccoonnnneeccttoorr
Allmodels1100V30A
Thefollowingfigureshowstheopen-circuitvoltagelimitsatdifferentaltitudes.Before
configuringthePVpanels,needtotakethisderatingcurveinconsiderationunderhigh
altitudesituation.
34
Page 45
UserManual5ElectricalConnection
FFiigguurree55--44Open-circuitVoltageDeratingCurve

5.6.2 AssemblingthePVConnectors

Highvoltagemaybepresentintheinverter!
Ensureallcablesarevoltage-freebeforeperformingelectricaloperations.
DonotconnecttheACcircuitbreakerbeforefinishingelectricalconnection.
UseMC4DCterminalsifthemaximuminputvoltageisnomorethan1,000V.
UseMC4-Evo2DCterminalsifthemaximuminputvoltageisgreaterthan
1,000V.TopurchasetheMC4-Evo2DCterminals,contactSUNGROW.
SelectappropriateDCterminalsasrequiredabove.Otherwise,SUNGROW
shallbeheldnoliabilityforthedamagecaused.
SUNGROWprovidescorrespondingPVconnectorsinthescopeofdeliveryfor
quickconnectionofPVinputs.ToensureIP65protection,useonlythe
suppliedconnectorortheconnectorwiththesameingressofprotection.
Step1Strip7mm–8mmoftheinsulationfromeachPVcable.
Step2Assemblethecableendswiththecrimpingpliers.
35
Page 46
5ElectricalConnectionUserManual
1:Positivecrimpcontact2:Negativecrimpcontact
Step3For somecountries suchas Australia wherethe DCprotection coverdelivered
separatelyneedtobeinstalledonsite,pleasefirstlyleadthePVcablesthroughthe
waterproofterminalontheDCprotectioncoverbeforeassemblingtheconnector.See
theguidancewiththeDCprotectioncoverfordetails.
PVcableswithconnectorscannotgothroughthewaterproofterminalonthe
DCprotectioncover.Reworkmaycausedamagetotheconnectors,whichwill
notbecoveredbythewarranty.
Step4Leadthecablethroughcablegland,andinsertthecrimpcontactintotheinsulatoruntilit
snapsintoplace.Gentlypullthecablebackwardtoensurefirmconnection.Tightenthe
cableglandandtheinsulator(torque2.5N.mto3N.m).
Step5Checkforpolaritycorrectness.
IfthePVpolarityisreversed,theinverterwillbeinafaultoralarmstateandwill
notoperatenormally.
----EEnndd

5.6.3 InstallingthePVConnectors

Step1RotatetheDCswitchto"OFF"position.
36
Page 47
UserManual5ElectricalConnection
Step2CheckthecableconnectionofthePVstringforpolaritycorrectnessandensurethatthe
opencircuitvoltageinanycasedoesnotexceedtheinverterinputlimitof1,100V.
Step3ConnectthePVconnectorstocorrespondingterminalsuntilthereisanaudibleclick.
CheckthepositiveandnegativepolarityofthePVstrings,andconnectthe
PV connectorstocorrespondingterminalsonlyafter ensuringpolarity
correctness.
ElectricarcorcontactorovertemperaturemayoccurifthePVconnectors
arenot firmlyin place,and SUNGROWshall notbe heldliable forany
damagecausedduetothisoperation.
Step4SealtheunusedPVterminalswiththeterminalcaps.
----EEnndd
37
Page 48
5ElectricalConnectionUserManual

5.7WiNet-SConnection

TheWiNet-SmodulesupportsEthernetcommunicationandWLANcommunication.Itis
notrecommendedtousebothcommunicationmethodsatthesametime.
TheWiNet-ScommunicationforEthernetcannotbeusedsimultaneouslywithA1and
B1terminalsforRS485daisychain.
Fordetails,seethequickguidefortheWiNet-Smodule.ScanthefollowingQRcodefor
thequickguide.

5.7.1 EthernetCommunication

TheWiNet-ScommunicationforEthernetcannotbeusedsimultaneouslywithA1and
B1terminalsforRS485daisychain.
Step1((OOppttiioonnaall))StriptheinsulationlayerofthecommunicationcablewithanEthernetwire
stripper,andleadthecorrespondingsignalcablesout.Insertthestripped
communicationcableintotheRJ45pluginthecorrectorder,andcrimpitwithacrimper.
1:RJ45plug2:Protectivecap
SkipthisstepifastandardnetworkcablewithRJ45plugisprepared.
Step2Unscrewtheswivelnutfromthecommunicationmoduleandtakeouttheinnersealing
ring.
38
Page 49
UserManual5ElectricalConnection
Step3Unscrewthehousingfromthecommunicationmodule.
Step4Threadthenetworkcablethroughtheswivelnutandgasket.Afterwards,routethecable
intotheopeningofthesealing.Finally,insertthecablethroughthehousing.
Step5InserttheRJ45plugintothefrontplugconnectoruntilthereisanaudibleclickand
tightenthehousing.Installthegasketandfastentheswivelnut.
39
Page 50
5ElectricalConnectionUserManual
Step6RemovethewaterprooflidfromtheCCOOMM11terminalandinstallWiNet-S.
Step7Slightlyshakeitbyhandtodeterminewhetheritisinstalledfirmly.
----EEnndd

5.7.2 WLANCommunication

Step1RemovethewaterprooflidfromtheCCOOMM11terminal.
Step2Installthemodule.Slightlyshakeitbyhandtodeterminewhetheritisinstalledfirmly,as
shownbelow.
Step3Refertotheguidedeliveredwiththemodulefortheset-up.
----EEnndd

5.8WiFiConnection(forBrazil)

Step1RemovethewaterprooflidfromtheCCOOMM11terminal.
40
Page 51
UserManual5ElectricalConnection
Step2Installthemodule.Slightlyshakeitbyhandtodeterminewhetheritisinstalledfirmly,as
shownbelow.
Step3Refertotheguidedeliveredwiththemodulefortheset-up.
----EEnndd

5.9MeterConnection

Inasingleinverterscenario,theMeter(A2,B2)terminalsaredesignedtoconnecttothe
SmartEnergyMeterforthefeed-inpowerfunction.

5.9.1 AssemblingtheCOMConnector

Step1Unscrewtheswivelnutfromtheconnector.
Step2Takeouttheterminalblock.
41
Page 52
5ElectricalConnectionUserManual
Step3Removethesealandleadthecablethroughthecablegland.
Step4Removethecablejacketandstripthewireinsulation.
Step5(Optional)Whenusingamulti-coremulti-strandwirecable,connectthewireheadto
thecordendterminal.Incaseofsingle-strandcopperwire,skipthisstep.
Step6Plugthewiresorterminalsintothecorrespondingterminalsasshowninthefollowing
figure.
42
Page 53
UserManual5ElectricalConnection
FFiigguurree55--55A2,B2connection
Step7Ensurethat thewires aresecurely inplace byslightly pullingthem andinsert the
terminalplugintothehousinguntilthereisanaudibleclick.
Step8Fastentheswivelnut.
----EEnndd

5.9.2 InstallingtheCOMConnector

Step1RemovethewaterprooflidfromtheCCOOMM22connector.
43
Page 54
5ElectricalConnectionUserManual
Step2InserttheCOMconnectorintoCCOOMM22terminalonthebottomoftheinverteruntilthereis
anaudibleclick.
----EEnndd

5.10RS485Connection

5.10.1RS485CommunicationSystem

TheRS485(A1,B1)connectioncanestablishthecommunicationbetweentheinverter
andanexternaldevice,aswellasthecommunicationbetweentwoinvertersinparallel.
Incaseofmultipleinverters,alltheinverterscanbeconnectedviaRS485cablesin
daisychainmanner.
44
Page 55
UserManual5ElectricalConnection
FFiigguurree55--66Multi-inverterConnection
Themaximumnumberofinvertersallowedtobeconnectedinthedaisy
chainis5.
TheRS485communicationcableshouldbeshieldedtwistedpaircablesor
shieldedtwistedpairEthernetcables.
TheRS485cablebetweentwodevicesshouldbenotlongerthan10m.
TheRS485communicationcannotbeusedsimultaneouslywithCOM1
portforWiNet-S.
RefertothemanualofLoggerforthecommunicationconnectiontothe
meter.

5.10.2AssemblingtheCOMConnector

Step1Unscrewtheswivelnutfromtheconnector.
Step2Takeouttheterminalblock.
45
Page 56
5ElectricalConnectionUserManual
Step3Removethesealandleadthecablethroughthecablegland.
Step4Removethecablejacketandstripthewireinsulation.
Step5(Optional)Whenusingamulti-coremulti-strandwirecable,connectthewireheadto
thecordendterminal.Incaseofsingle-strandcopperwire,skipthisstep.
Step6Plugthewiresorterminalsintothecorrespondingterminalsasshowninthefollowing
figure.
46
Page 57
UserManual5ElectricalConnection
FFiigguurree55--77A1,B1connection
Step7Ensurethat thewires aresecurely inplace byslightly pullingthem andinsert the
terminalplugintothehousinguntilthereisanaudibleclick.
Step8FFoorrRRSS448855ddaaiissyycchhaaiinn::CrimptwowiresAtoatwo-wirecoreendterminalandtwo
wiresBtoanotherterminal.PlugtheterminalstoA1andB1respectively.
FFiigguurree55--88RS485daisychainconnection
Step9Fastentheswivelnut.
47
Page 58
5ElectricalConnectionUserManual
----EEnndd

5.10.3InstallingtheCOMConnector

Step1RemovethewaterprooflidfromtheCCOOMM22connector.
Step2InserttheCOMconnectorintoCCOOMM22terminalonthebottomoftheinverteruntilthereis
anaudibleclick.
----EEnndd
48
Page 59
UserManual5ElectricalConnection

5.11DOConnection

The inverteris equipped witha DOrelay for anearth faultalarm. The additional
equipmentrequiredisalightindicatorand/orabuzzerthatneedsadditionalpower
supply.
Oncefaultoccurs,therelaytripsandthecircuitisconnected.Theexternalindicatorgets
on.Therelayremainstriggereduntilthefaultisremoved.
FFiigguurree55--99DONormalOpenConnect
TheadditionalDCpowersupplyshouldcomplywithrelatedrequirements:
Max.voltage:30V
Max.current:1A
Refer to section
"5.9.1 Assembling the COM Connector" for detailed assembling
procedure.PlugthewirestoNNOOandCCOOMMterminalsaccordingthelabelsonthebottom
oftheinverter.
Refertosection"5.10.3InstallingtheCOMConnector"toinstalltheconnector.
49
Page 60
5ElectricalConnectionUserManual

5.12DRMConnection

InAustraliaandNewZealand,theinvertersupportsthedemandresponsemodesas
specifiedinthestandardAS/NZS4777.
ThefollowingfigureshowsthewiringbetweentheinverterandtheexternalDRED.
Table5-4MethodofAssertingDRM
MMooddee
DRM0
Refer to section
procedure.PlugthewirestoRRandCCterminalsaccordingthelabelsonthebottomof
theinverter.
Refertosection"5.10.3InstallingtheCOMConnector"toinstalltheconnector.
AAsssseerrtteeddbbyySShhoorrttiinnggTTeerrmmiinnaallss
oonnIInnvveerrtteerr
R&CCloseS1andS5
"5.9.1 Assembling the COM Connector" for detailed assembling
SSwwiittcchhOOppeerraattiioonnoonnEExxtteerrnnaall
DDRREEDD

5.13DIConnection

ThegridcompanyusesaRippleControlReceivertoconvertthegriddispatchingsignal
andsenditasadrycontactsignal.
The followingfigure showsthe wiringbetween theinverter andthe ripplecontrol
receiver.
50
Page 61
UserManual5ElectricalConnection
Table5-5MethodofAssertingDIMode
SS22SS33SS44SSwwiittcchhOOppeerraattiioonnoonn
SS11
EExxtteerrnnaallRRCCRR
0000None100%(configurableaccordingto
1000
0100
0010
1100
CloseS1
CloseS2
CloseS3
CloseS1andS20%(disconnectfromgrid)
Step1Unscrewtheswivelnutfromtheconnector.
Step2Takeouttheterminalblock.
OOuuttppuuttppoowweerr((iinn%%oofftthheeRRaatteedd
AACCoouuttppuuttppoowweerr))
need)
100%
60%
30%
Step3Removethesealandleadthecablethroughthecablegland.
51
Page 62
5ElectricalConnectionUserManual
Step4Removethecablejacketby7mm–10mm.
Step5Plugthewiresintothecorrespondingterminalsasshowninthefollowingfigure.
FFiigguurree55--1100DIconnection
Step6Ensurethat thewires aresecurely inplace byslightly pullingthem andinsert the
terminalplugintothehousinguntilthereisanaudibleclick.
52
Page 63
UserManual5ElectricalConnection
Step7Fastentheswivelnut.
Step8Refertosection"5.10.3InstallingtheCOMConnector"toinstalltheconnector.
----EEnndd
53
Page 64
6

Commissioning

6.1InspectionbeforeCommissioning

Checkthefollowingitemsbeforestartingtheinverter:
Alltheinstallationsitesareconvenientforoperation,maintenanceandservice.
Alldevicesarefirmlyinstalled.
Spaceforventilationissufficientforoneinverterormultipleinverters.
Nothingisleftonthetopoftheinverter.
Theinverterandaccessoriesarecorrectlyconnected.
Cablesareroutedsafelyandprotectedagainstmechanicaldamage.
TheselectionoftheACcircuitbreakerisinaccordancewiththismanualandall
applicablelocalstandards.
Allunusedterminalsatthebottomoftheinverterareproperlysealed.
Warningsigns&labelsareintactandlegible.

6.2PoweringontheSystem

Ifalloftheitemsmentionedabovemeettherequirements,proceedasfollowstostart
uptheinverterforthefirsttime.
Step1TurnontheACcircuitbreakerbetweentheinverterandthegrid.
Step2RotatetheDCswitchoftheinverterto"ON"position.
Step3TurnontheexternalDCswitch(ifapplicable)betweentheinverterandthePVstring.
Step4If the irradiation and grid conditions meet requirements, the inverter will operate
normally.ObservetheLEDindicatortoensurethattheinverteroperatesnormally.Refer
to
"2.4IndicatorDefinition"fordetails.
Step5Refertothequickguideforcommunicationmoduleforitsindicatordefinition.
Step6SetinitialprotectionparametersviatheiSolarCloudApp.
ForWiFimodule,pleasereferto
and"7.5InitialSettings".
ForWiNet-Smodule,pleaserefertosections6.3to6.6.
----EEnndd
54
"7.2InstallingtheApp","7.4.2LoginProcedure"
Page 65
UserManual6Commissioning

6.3AppPreparation

Step1InstalltheiSolarCloudAppwithlatestversion.Referto"7.2InstallingtheApp".
Step2Registeranaccount.Referto
andpasswordfromthedistributor/installerorSUNGROW,skipthisstep.
Step3Downloadthefirmwarepackagetothemobiledevice inadvance.Referto
FirmwareUpdate"
----EEnndd
.Thisistoavoiddownloadfailureduetopooron-sitenetworksignal.
"7.3AccountRegistration".Ifyouhavegottheaccount

6.4CreatingaPlant

Screenshotsofcreatingaplantareforreferenceonly.Fordetails,refertotheactual
screen.
Step1OpentheApp,tap
sameserveraswhenregistering.
attheupperrightcornerandtapSSeelleeccttSSeerrvveerr.Choosethe
"7.10.5
FFiigguurree66--11SelectingtheServer
Step2EntertheaccountandpasswordontheloginscreenandtapLLooggiinntoentertheApp
homescreen.
Step3Taptheicon
attheupperrightcornertoenterthecreatingscreen.
55
Page 66
6CommissioningUserManual
FFiigguurree66--22CreatingPowerPlant
Step4SelectplanttypetoRREESSIIDDEENNTTIIAALLandinvertertypetoPPVV.
FFiigguurree66--33SelectingPlant/InverterType
Step5ScantheQRcodeonthecommunicationdeviceormanuallyentertheserialnumberof
thecommunicationdevice.TapNNeexxttaftertheQRcodeisidentifiedortheserialnumber
enterediscorrectandthentapCCOONNFFIIRRMM.Yourmobiledeviceisthusconnectedtothe
WiNet-Ssuccessfully.
FFiigguurree66--44ConnectingMobileDevicetoWiNet-S
Step6SelecttheInternetaccessmodetoWWLLAANN((CCOONNNNEECCTTEEDD))orEETTHHEERRNNEETTaccordingto
actualconnection.ThefollowingdescriptionisforWLANaccessmode.
56
Page 67
UserManual6Commissioning
FFiigguurree66--55SelectingInternetAccessMode
Step7The EEAASSYYCCOONNNNEECCTT IINNSSTTRRUUCCTTIIOONN screen will prompt. Press themulti-function
buttonontheWiNet-SmoduleoncetoturnonEasyConnectmode.TheWLANindicator
onWiNet-Sblinksquicklywhenthismodeisturnedon.ReturntotheAppandthe
screendisplayssuccessfulconnectiontotheinverterWLAN.TapNNEEXXTT.
FFiigguurree66--66TurnonEasyConnectMode
TheEasyConnectmodecanbeusedonlywhentherouteris2.4GHz.
IftheEasyConnectmodefails,refertotheWiNet-Squickguideforthe
instructionsofothermodes.
Step8Connecttheinvertertorouternetwork.Enternetworknameandpassword.TapNNEEXXTT
and thescreen displayprompt informationof successfulconnection tothe router
network.
FFiigguurree66--77ConnectingInvertertoRouterNetwork
----EEnndd
57
Page 68
6CommissioningUserManual

6.5InitializingtheDevice

Theinverterissuccessfullyconnectedtotherouter.
Ifthereisnolatestequipmentupgradepackage,skipsteps1and2.
Theactualinitializingproceduremaydifferduetodifferentcountries.Pleasefollowthe
actualAppguidance.
Step1Ifalatestequipmentupgradepackageisavailable,thefollowingpromptwindowpops
up.TapUUPPDDAATTEENNOOWWtodownloadthelatestupdatepackage.
FFiigguurree66--88UpgradeReminder
Step2Afterdownload,itwouldtakearound15minutestoupdate.Aftersuccessfulupgrade,
thescreenwillshowtheversionnumbersbeforeandaftertheupgradeaswellasthe
upgradetime.TapNNEEXXTT.
FFiigguurree66--99UpgradingInverter
Ifthecommunicationequipmentisupgraded,aftersuccessfulupgrade,check
andconfirmthatthephoneisconnectedtotheinverterWLAN.
Step3TapCCoouunnttrryy//RReeggiioonnand selectthe countrywhere theinverteris installedat. The
supportedcountriesandcorrespondingsettingsareasfollows.
CCoouunnttrryy//RReeggiioonnSSeettttiinngg
Australia("AU")Australia
NewZealand("NZ")NewZealand
Poland("PL")Poland
58
Page 69
UserManual6Commissioning
CCoouunnttrryy//RReeggiioonnSSeettttiinngg
Germany("DE")Germany
Brazil("BR")Brazil
Portugal/Norway/Hungary/RomaniaEN50549-1
Countriesnotlistedabove"Other50Hz"or"Other60Hz"
TheparameterCCoouunnttrryy//RReeggiioonnmustbesettothecountry(region)wherethe
inverterisinstalledat.Otherwise,theinvertermayreporterrors.
Step4WhenthecountryissettoAustralia,additionallysettheapplicablenetworkservice
providerandthenthegridtype.
Theimage shownhere isfor referenceonly. Referto theactual interfacefor the
supportednetworkserviceproviders.
Table6-1DescriptionofNetworkServiceProviderandGridType
NNeettwwoorrkkSSeerrvviicceePPrroovviiddeerrGGrriiddTTyyppee
AS/NZS4777.2:2015/
STNW1170:single-phase<10kVA
ENERGEX&ErgonEnergy
&three-phase<30kVA
STNW1174: 30kVA <Pn≤ 1500
kVA
59
Page 70
6CommissioningUserManual
NNeettwwoorrkkSSeerrvviicceePPrroovviiddeerrGGrriiddTTyyppee
≤10kVAperphase(or30kVAper
Jemena
threephase)
ELEGU0014:30kVA–200kVA
EndeavourEnergy
Ausgrid
MDI0043
NS194
≤5kVAforsingle-phase&30kVA
CitiPower&Powercor
forthree-phase
>30kVAthree-phase
UE-ST-2008.1:≤10kVAforsingle-
UnitedEnergy
phase&30kVAforthree-phase
UE-ST-2008.2:>30kVAthree-
phase
PowerWaterAS/NZS4777.2:2015
TS129-2019:<10kWforsingle-
phase&30kWforthree-phase
SAPowerNetworks
TS130-2017:>30kW&≤200kW
TS131-2018:>200kW
Step5Initializeparametersaccordingtolocalgridrequirements,includinggridtype,reactive
power regulation mode,etc. The screen displays thatthe inverter is successfully
configured.
FFiigguurree66--1100InitializingParameters
60
----EEnndd
Page 71
UserManual6Commissioning

6.6ConfiguringthePlant

Theinverterissuccessfullyaddedtotheplantandinitialized.Refertotheguidancein
previoussections.
Thedistributor/installerwhocreatesaplantfortheenduserneedstogettheenduser's
e-mailaddress.Inconfiguringaplant,thee-mailaddressisrequired,andeache-mail
addresscanberegisteredonlyonce.
Step1TheAppscreenwilldisplaytheaddedinverter.TapNNEEXXTTtoconfiguretheplant.
FFiigguurree66--1111DisplaytheAddedInverter
Step2Fillintheplantinformation.Thefieldsmarkedwith*mustbefilledin.
FFiigguurree66--1122EnteringPlantInformation
Step3((OOppttiioonnaall))Fillinthetariffinformation.Theelectricitypricecanbesettoaspecificvalue
orTime-of-Usetariff.
61
Page 72
6CommissioningUserManual
FFiigguurree66--1133EnteringTariffInformation
Step4Fillintheenduser's e-mailaddress.Thefirsttimeyoufillintheend user'se-mail
address,thesystemwillcreateanaccountfortheenduserandsendanemailtothe
enduser.Theendusercanactivatetheaccountviatheemail.
TheDistributor/installercreatesplantsfortheenduserandcanmanagethe
plantsbydefault.
FFiigguurree66--1144EnteringOwener'se-mail
Step5TapNNEEXXTTtowaitfortheinvertertoconnecttotheiSolarCloud.
62
Page 73
UserManual6Commissioning
FFiigguurree66--1155ConfigurationCompleted
Step6((OOppttiioonnaall))TabVViieewwlliivveeddaattaaffoorrtthheeddeevviiccee,tickIInnvveerrtteerrorTToottaallPPllaannttDDeevviicceessand
tabAALLLLPPLLAANNTTSSOOPPEENN.Theclocksymbleindicatesthatthelivedataviewfunctionis
successfullyenabled.Tabtheinvertertoviewthelivedataaboutvoltage,current,power
orcurve.
FFiigguurree66--1166LiveDataViewFunctionSetting
ConsultSungrowserviceforthedevicesthatsupportlivedatafunction.
Step7Tab BBAACCKK to the CCOOMMPPLLEETTEEDD screen. Tab PPDDFF RREEPPOORRTT to export the plant
configurationreport.
63
Page 74
6CommissioningUserManual
Step8TabBBAACCKKtotheCCOOMMPPLLEETTEEDDscreen.TabDDAASSHHBBOOAARRDDtoreturn andmanually
refreshthepageuntilthenewlycreatedplantisdisplayedwithstatuscommissioned.
----EEnndd
64
Page 75
7

iSolarCloudApp

7.1BriefIntroduction

TheiSolarCloudAppcanestablishcommunicationconnectiontotheinverterviathe
WLAN,providingremotemonitoring,dataloggingandnear-endmaintenanceonthe
inverter.UserscanalsoviewinverterinformationandsetparametersthroughtheApp.
*ToachievedirectloginviaWLAN,thewirelesscommunicationmoduledevelopedand
manufactured by SUNGROWis required. The iSolarCloud Appcan also establish
communicationconnectiontotheinverterviaEthernetconnection.
Thismanualdescribes onlyhow toachieve near-endmaintenance via
WLANdirectconnection.
Screenshots inthis manualare basedon theV2.1.6 Appfor Android
system,andtheactualinterfacesmaydiffer.

7.2InstallingtheApp

MMeetthhoodd11
DownloadandinstalltheAppthroughthefollowingapplicationstores:
MyApp(Android,mainlandChinausers)
GooglePlay(Android,usersotherthanmainlandChinaones)
AppStore(iOS)
MMeetthhoodd22
ScanthefollowingQRcodetodownloadandinstalltheAppaccordingtotheprompt
information.
TheAppiconappearsonthehomescreenafterinstallation.
65
Page 76
7iSolarCloudAppUserManual

7.3AccountRegistration

Theaccountdistinguishestwousergroups,enduseranddistributor/installer.
Theendusercanviewplantinformation,createplants,setparameters,shareplants,
etc.
Thedistributor/installercanhelptheendusertocreateplants,manage,install,or
maintainplants,andmanageusersandorganizations.
Step1TapRREEGGIISSTTEERRtoentertheregistrationscreen.
Step2SelectEEnndduusseerrorDDiissttrriibbuuttoorr//IInnssttaalllleerrtoenterthecorrespondingscreen.
FFiigguurree77--11SelectingUserGroup
Step3Fillintheregistrationinformation,includingserverselection,email,verificationcode,
passwordandaffirmance,country(region)andtimezone.Thedistributor/installerhas
thepermissiontofillinthecompanynameandthecodeofupperleveldistributor/
installer.
66
Page 77
UserManual7iSolarCloudApp
Thecodeofupperleveldistributor/installercanbeobtainedfromtheupper
leveldistributor/installer.Onlywhenyourorganizationbelongstotheupper
leveldistributor/installerorganization,canyoufillinthecorrespondingcode.
Step4TickAAcccceeppttpprriivvaaccyypprroottooccoollandtapRReeggiisstteerrtofinishtheregistrationoperation.
----EEnndd

7.4Login

7.4.1 Requirements

Thefollowingrequirementsshouldbemet:
TheACandDCsidesortheACsideoftheinverterispowered-on.
TheWLANfunctionofthemobilephoneisenabled.
Themobilephoneiswithinthecoverageofthewirelessnetworkproducedbythe
communicationmodule.

7.4.2 LoginProcedure

Step1FortheWiNet-Smodule,pressthemulti-functionbutton3timestoenabletheWLAN
hotspot.Nopasswordisrequiredandthevalidtimeis30minutes.
FFiigguurree77--22EnablingtheWLANHotspot
Step2Connect the mobile phone tothe WLAN network named as "SG-xxxxxxxxxxx" (-
xxxxxxxxxxxistheserialnumberindicatedonthesideofthecommunicationmodule).
Step3OpentheApptoentertheloginscreen.TapLLooccaallAAcccceesssstoenterthenextscreen.
Step4SelectWWLLAANNandselectthedevice(SN),thenenterthepasswordandtapLLOOGGIINN.
Thedefaultaccountis"user"andtheinitialpasswordis"pw1111"which
shouldbechangedfortheconsiderationofaccountsecurity.Tap"More"at
thelowerrightcorneronhomepageandchoose"ChangePassword".
67
Page 78
7iSolarCloudAppUserManual
FFiigguurree77--33WLANLocalAccess
Step5Iftheinverteris notinitialized, navigatetothe quicksettingscreen toinitializethe
protectionparameters.Fordetails,pleasereferto""IInniittiiaallSSeettttiinnggss"".
The"Country/Region"mustbesettothecountrywheretheinverterisinstalled
at.Otherwise,theinvertermayreporterrors.
FFiigguurree77--44WLANLocalAccess
Step6Afterfinishingthesettings,tapTTUUNNRROONNDDEEVVIICCEEattheupperrightcornerandthe
devicewillbeinitialized.TheAppwillsendstartinstructionsandthedevicewillstartand
operate.
Step7Afterinitializationsettings,theAppwillreturnautomaticallytothehomepage.
68
Page 79
UserManual7iSolarCloudApp
----EEnndd

7.5InitialSettings

TapCCoouunnttrryy//RReeggiioonnandselectthecountrywheretheinverterisinstalled.Forcountries
exceptAustraliaandGermany,theinitializationiscompleted.
Theactualinitializingproceduremaydifferduetodifferentcountries.Please
followtheactualAppguidance.
Forsomecountries,youshouldinitializeparametersaccordingtolocalgrid
requirements.Fordetails,see6.5InitializingtheDevice.

7.6FunctionOverview

TheAppprovidesparameterviewingandsettingfunctions,asshowninthefollowing
figure.
69
Page 80
7iSolarCloudAppUserManual
FFiigguurree77--55AppKeyFunctionMenu

7.7Home

HomepageoftheAppisshowninthefollowingfigure.
70
Page 81
UserManual7iSolarCloudApp
FFiigguurree77--66Home
Table7-1HomePageDescription
NNoo..NNaammee
1Inverterstate
2
Energyflow
chart
Real-time
3
power
Nominal
4
5
6
7
power
TodayyieldShowstodaypowergenerationoftheinverter
TotalyieldShowsaccumulativepowergenerationoftheinverter
Navigationbar
Iftheinverterrunsabnormally,thefaulticon
thescreen.Userscantaptheicontoviewdetailedfaultinformationandcorrective
measures.

7.8RunInformation

DDeessccrriippttiioonn
Presentoperationstateoftheinverter
ShowsthePVpowergenerationpower,feed-inpower,etc.
Thelinewithanarrowindicatesenergyflowbetween
connecteddevices,andthearrowpointingindicates
energyflowdirection.
Showsthepresentoutputpoweroftheinverter.
Showstheinstalledpoweroftheinverter.
Includesmenusof"HHoommee","RRuunnIInnffoommaattiioonn","RReeccoorrddss"
and"MMoorree".
willappearontheupperleftcornerof
Tap RRuunnIInnffoorrmmaattiioonnon the navigationbar toenter thescreen showingrunning
information,slidethescreenupwardstoviewalldetailedinformation.
71
Page 82
7iSolarCloudAppUserManual
Table7-2DescriptionofRunInformation
IItteemm
PVinformation
Inverter
information
Input
Output
Meterinformation

7.9Records

TapRReeccoorrddssonthenavigationbarto enterthescreen showingeventrecords,as
showninthefollowingfigure.
DDeessccrriippttiioonn
ShowsvoltageandcurrentofeveryPVstring.
Showsbasicinformationsuchasrunningstate,on-gridrunning
time,negativevoltagetogrid,busvoltage,internalair
temperature,inverterefficiency,etc.
ShowstotalDCpower,voltageandcurrentofMPPT1and
MPPT2.
Showsdaily/monthly/annual/totalyield,totalactive/reactive/
apparentpower,totalpowerfactor,gridfrequency,phase
voltageandcurrent.
Showsactivepowerandphaseactivepowerofthemeter.
72
FFiigguurree77--77Records
CChhaarrtt
Tap CChhaarrttto enter thescreen showing dailypower generation, asshown inthe
followingfigure.
Page 83
UserManual7iSolarCloudApp
FFiigguurree77--88Chart
TheAppdisplayspowergenerationrecordsinavarietyofforms,includingdailypower
generation graph, monthly power generation histogram, annual power generation
histogramandtotalpowergenerationhistogram.
Table7-3DescriptionofPowerCurve
IItteemm
DDeessccrriippttiioonn
DailyDailycurvethatindicatesthereal-timepower.
Month
Monthlycurvethatindicatesdailyyieldandequivalenthoursinamonth.
Annualcurvethatindicatesmonthlyyieldandequivalenthoursina
Year
Total
year.
Acurvethatindicatesannualyieldandequivalenthourssince
installation.
FFaauullttAAllaarrmmRReeccoorrdd
TapFFaauullttAAllaarrmmRReeccoorrddtoenterthescreen,asshowninthefollowingfigure.
73
Page 84
7iSolarCloudAppUserManual
FFiigguurree77--99FaultAlarmRecord
Clicktoselectatimesegmentandviewcorrespondingrecords.
Selectoneoftherecordsinthelistandclicktherecord,toviewthedetailedfaultinfoas
showninfollowingfigure.
FFiigguurree77--1100DetailedFaultAlarmInformation
EEvveennttRReeccoorrdd
TapEEvveennttRReeccoorrddtoenterthescreen,asshowninthefollowingfigure.
74
Page 85
UserManual7iSolarCloudApp
FFiigguurree77--1111EventRecord
Clicktoselectatimesegmentandviewcorrespondingrecords.

7.10More

TapMMoorreeonthenavigationbartoenterthecorrespondingscreen,asshowninthe
followingfigure.
InadditiontoviewingtheWLANconfigurationandAppsoftwareversion,theMMoorree
screensupportsthefollowingoperations:
Setparametersincludinginvertersystemparameters,operationparameters,power
regulationparametersandcommunicationparameters.
Upgradeinverterfirmware.

7.10.1SystemParameters

TapSSeettttiinnggss→→SSyysstteemmPPaarraammeetteerrsstoenterthecorrespondingscreen,asshowninthe
followingfigure.
FFiigguurree77--1122More
75
Page 86
7iSolarCloudAppUserManual
FFiigguurree77--1133SystemParameters
BBoooott//SShhuuttddoowwnn
TapBBoooott//SShhuuttddoowwnntosendtheboot/shutdowninstructiontotheinverter.
ForAustraliaandNewZealand,whentheDRMstateisDRM0,the"Boot"optionwillbe
prohibited.
DDaattee//TTiimmee
Thecorrectsystemtimeisveryimportant.Wrongsystemtimewilldirectlyaffectthe
dataloggingandpowergenerationvalue.Theclockisin24-hourformat.

7.10.2OperationParameters

RRuunnnniinnggTTiimmee
TapSSeettttiinnggss→→OOppeerraattiioonnPPaarraammeetteerrss→→RRuunnnniinnggTTiimmeeto enterthe corresponding
screen,onwhichyoucansetthe"ConnectingTime"and"ReconnectingTime".
76
FFiigguurree77--1144RunningTime
PPIIDDPPaarraammeetteerrss
TapSSeettttiinnggss→→OOppeerraattiioonnPPaarraammeetteerrss→→PPIIDDPPaarraammeetteerrsstoenterthecorresponding
screen,onwhichyoucanset"ConnectingTime"and"ReconnectingTime".
Page 87
UserManual7iSolarCloudApp
FFiigguurree77--1155PIDSetting
Table7-4PIDParameterDescription
PPaarraammeetteerr
DDeessccrriippttiioonn
Setenabling/disablingofthePIDnightrecoveryfunction.PID
PPIIDDRReeccoovveerryy
nightrecoveryfunctionsbetween22:00pmand5:00amby
default.
IfISOimpedanceabnormalityorPIDfunctionexceptionis
CClleeaarrPPIIDDaallaarrmm
detectedduringrunningofthePIDfunction,theinverterreports
aPIDfalsealarmandremindstheusertotakecorresponding
measures.Afterprocessing,clearthealarmviathisparameter.
PPIIDDSScchheemmeeApplynegativeorpositivevoltage.
Fortheselectionofnegativeorpositivevoltage,pleaseconsultthesupplier
ofPVpanels.
AfterthePIDnightrecoveryfunctionisenabled,thefaultindicatoronthe
inverterfrontpanelturnsgreen.

7.10.3PowerRegulationParameters

AAccttiivveePPoowweerrRReegguullaattiioonn
TapSSeettttiinnggss→→PPoowweerrRReegguullaattiioonnPPaarraammeetteerrss→→AAccttiivveePPoowweerrRReegguullaattiioonntoenter
thescreen,asshowninthefollowingfigure.
77
Page 88
7iSolarCloudAppUserManual
FFiigguurree77--1166ActivePowerRegulation
Table7-5DescriptionofActivePowerRegulationParameters
PPaarraammeetteerr
AAccttiivveePPoowweerrSSoofftt
SSttaarrttaafftteerrFFaauulltt
AAccttiivveePPoowweerrSSoofftt
SSttaarrttTTiimmeeaafftteerrFFaauulltt
AAccttiivveePPoowweerrGGrraaddiieenntt
CCoonnttrrooll
AAccttiivveePPoowweerrDDeecclliinnee
GGrraaddiieenntt
AAccttiivveePPoowweerrRRiissiinngg
GGrraaddiieenntt
AAccttiivveePPoowweerrSSeettttiinngg
PPeerrssiisstteennccee
AAccttiivveePPoowweerrLLiimmiitt
AAccttiivveePPoowweerrLLiimmiitt
RRaattiioo
DDRRMM
DDeessccrriippttiioonnRRaannggee
Switchforactivating/deactivatingthe
functionofactivepowersoftstartaftera
On/Off
faultoccurs
Thesoftstarttimerequiredforraisingactive
powerfrom0toratedvalueafterafault
occurs
Setwhethertoenableactivepowergradient
control
Declinegradientofinverteractivepowerper
minute
Risinggradientofinverteractivepowerper
minute
1s–1200
s
On/Off
3%/min–
6000
%/min
Switchforactivating/deactivatingthe
functionofactivepowersettingpersistence
Switchforlimitingactivepower
Theratioofactivepowerlimittoratedpower
inpercentage
Switchforactivating/deactivatingtheDRM
function
On/Off
On/Off
0.0%–
110.0%
On/Off
78
RReeaaccttiivveePPoowweerrRReegguullaattiioonn
TapSSeettttiinnggss→→PPoowweerrRReegguullaattiioonnPPaarraammeetteerrss→→RReeaaccttiivveePPoowweerrRReegguullaattiioonntoenter
thescreen,asshowninthefollowingfigure.
Page 89
UserManual7iSolarCloudApp
FFiigguurree77--1177ReactivePowerRegulation
Table7-6DescriptionofReactivePowerRegulationParameters
PPaarraammeetteerr
RReeaaccttiivveePPoowweerr
SSeettttiinnggPPeerrssiisstteennccee
DDeessccrriippttiioonnRRaannggee
Switchforactivating/deactivatingthe
functionofreactivepowersetting
On/Off
persistence
RReeaaccttiivveePPoowweerr
RReegguullaattiioonnMMooddee
RReeaaccttiivveeRReessppoonnssee
RReeaaccttiivveeRReessppoonnssee
TTiimmee
Off/PF/Qt/Q(P)/Q(U)
Switchforactivating/deactivatingthe
functionofreactiveresponse
Timeforreactiveresponse
Off/PF/Qt/Q
(P)/Q(U)
On/Off
0.2s
""OOffff""MMooddee
Thereactivepowerregulationfunctionisdisabled.ThePFisfixedat+1.000.
""PPFF""MMooddee
Thepowerfactor(PF)isfixedandthereactivepowerisregulatedbytheparameterPF.
ThePFrangesfrom0.8leadingto0.8lagging.
Leading:theinverterissourcingreactivepowertothegrid.
Lagging:theinverterisinjectingreactivepowerintothegrid.
""QQtt""MMooddee
IntheQtmode,thereactivepowercanberegulatedbytheparameterQ-Varlimits(in
%). The system rated reactive poweris fixed, the system injects reactive power
accordingto thedelivered reactivepowerratio. The"Reactive PowerRatio"is set
throughtheApp.
Thesettingrangeofthereactivepowerratioisfrom-100%to100%,correspondingto
therangesofinductiveandcapacitivereactivepowerregulationrespectively.
""QQ((PP))""MMooddee
ThePFoftheinverteroutputvariesinresponsetotheoutputpoweroftheinverter.
79
Page 90
7iSolarCloudAppUserManual
Table7-7"Q(P)"ModeParametersExplanation
PPaarraammeetteerrEExxppllaannaattiioonnRRaannggee
Q(P)CurveSelectcorrespondingcurveaccordingtolocal
A,B,C
*
regulations
QP_P1OutputpoweratpointP1ontheQ(P)modecurve
(in%)
QP_P2OutputpoweratpointP2ontheQ(P)modecurve
(in%)
QP_P3OutputpoweratpointP3ontheQ(P)modecurve
(in%)
20.0%–100.0
%
20.0%–100.0
%
20.0%–100.0
%
QP_K1PowerfactoratpointP1ontheQ(P)modecurveCurveA/C:
QP_K2PowerfactoratpointP2ontheQ(P)modecurve
0.800to1.000
CurveB:-0.600
QP_K3PowerfactoratpointP3ontheQ(P)modecurve
QP_
VoltageforQ(P)functionactivation(in%)
EnterVoltage
QP_
VoltageforQ(P)functiondeactivation(in%)
ExitVoltage
QP_
PowerforQ(P)functiondeactivation(in%)
to0.600
100.0%–110.0
%
90.0%–100.0
%
1.0%–20.0%
ExitPower
80
QP_
EnableMode
Unconditionalactivation/deactivationofQ(P)
function
*CurveCisreservedandconsistentwithCurveAcurrently.
FFiigguurree77--1188ReactivePowerRegulationCurveinQ(P)Mode
""QQ((UU))""MMooddee
Yes,No
Page 91
UserManual7iSolarCloudApp
Thereactivepoweroutputoftheinvertervariesinresponsetothegridvoltage.
Table7-8"Q(U)"ModeParameterExplanation
PPaarraammeetteerr
Q(U)curve
Hysteresis
Ratio
QU_V1
QU_V2
QU_V3
QU_V4
QU_Q1
QU_Q2
EExxppllaannaattiioonnRRaannggee
Selectcorrespondingcurveaccordingtolocal
regulations
VoltagehysteresisratioontheQ(U)modecurve
GridvoltagelimitatpointP1ontheQ(U)mode
curve(in%)
GridvoltagelimitatpointP2ontheQ(U)mode
curve(in%)
GridvoltagelimitatpointP3ontheQ(U)mode
curve(in%)
GridvoltagelimitatpointP4ontheQ(U)mode
curve(in%)
ValueofQ/SnatpointP1ontheQ(U)modecurve
(in%)
ValueofQ/SnatpointP2ontheQ(U)modecurve
(in%)
A,B,C
0.0%–5.0%
80.0%–100.0
%
80.0%–110.0
%
100.0%–
120.0%
100.0%–
120.0%
-60.0%to0.0
%
-60.0%to60.0
%
*
QU_Q3
QU_Q4
QU_
ValueofQ/SnatpointP3ontheQ(U)modecurve
(in%)
ValueofQ/SnatpointP4ontheQ(U)modecurve
(in%)
ActivepowerforQ(U)functionactivation(in%)
EnterPower
QU_
ActivepowerforQ(U)functiondeactivation(in%)
ExitPower
QU_
EnableMode
QU_Limited
Unconditionalactivation/deactivationofQ(U)
function
PresetPFvalue0–0.95
PFValue
*CurveCisreservedandconsistentwithCurveAcurrently.
-60.0%to60%
0.0%to60.0%
20.0%–100.0
%
1.0%–20.0%
Yes,No,Yes(-
LimitedbyPF)
81
Page 92
7iSolarCloudAppUserManual
FFiigguurree77--1199ReactivePowerRegulationCurveinQ(U)Curve

7.10.4CommunicationParameters

TapSSeettttiinnggss→→CCoommmmuunniiccaattiioonnPPaarraammeetteerrssto enterthecorrespondingscreen,as
showninthefollowingfigure.Thedeviceaddressrangesfrom1to246.
FFiigguurree77--2200CommunicationParameters

7.10.5FirmwareUpdate

Toavoiddownloadfailureduetopooron-sitenetworksignal,itisrecommendedto
downloadthefirmwarepackagetothemobiledeviceinadvance.
Step1Enablethe"Mobiledata"ofthemobiledevice.
Step2OpentheApp,tap
attheupperrightcornerandselectFFiirrmmwwaarreeDDoowwnnllooaadd.
82
Page 93
UserManual7iSolarCloudApp
FFiigguurree77--2211FirmwareDownload
Step3Select thefirmware fromthe filelist anddownload. TapDDoowwnnllooaaddeedd toview
successfullydownloadedfirmwarepackage.
FFiigguurree77--2222DownloadingFirmwarePackage
Step4LogintheAppvialocalaccessmode.Referto"7.4Login".
Step5TabMMoorreeon theApphome screenand thentab FFiirrmmwwaarreeUUppggrraaddee.Select the
desiredupgradepackagetoupgradethefirmware.
FFiigguurree77--2233UpdatingFirmware
----EEnndd
83
Page 94
8

SystemDecommissioning

8.1DisconnectingtheInverter

Formaintenanceorotherservicework,theinvertermustbeswitchedoff.
Proceedas followstodisconnecttheinverterfromtheACandDCpowersources.
Lethalvoltagesordamagetotheinverterwillfollowifotherwise.
Step1DisconnecttheexternalACcircuitbreakerandsecureitagainstreconnection.
Step2RotatetheDCswitchtothe"OFF"positionfordisconnectingallofthePVstringinputs.
Step3Waitabout10minutesuntilthecapacitorsinsidetheinvertercompletelydischarge.
Step4EnsurethattheDCcableiscurrent-freeviaacurrentclamp.
Step5InsertaMC4wrenchintothenotchandpressthewrenchwithanappropriateforceto
removetheDCconnector.
Step6OOppttiioonnaall::RemovetheblockwiththePhillipsscrewdriver.
Step7LaythetoolinthelocationofsnapandpressthetooldowntoremovetheACconnector.
EnsurethattheACwiringterminalsarevoltage-freeviaamultimeter,andremovethe
ACwiresandcommunicationwires.
Step8InstalltheMC4waterproofplugs.
84
Page 95
UserManual8SystemDecommissioning
Forfurtherdisconnectionandreconnectioninstructions,pleasevisitthe
webpageofrespectivecomponentmanufacturer.
----EEnndd

8.2DismantlingtheInverter

Riskofburninjuriesandelectricshock!
Donottouchanyinnerlivepartsuntilforatleast10minutesafterdisconnecting
theinverterfromtheutilitygridandthePVinput.
Step1Referto
steps.
Step2Dismantletheinverterreferringto
Step3Ifnecessary,removethewall-mountingbracketfromthewall.
Step4Iftheinverterwillbereinstalledinthefuture,pleasereferto
properconservation.
----EEnndd
"5ElectricalConnection"fortheinverterdisconnectionofallcablesinreverse
"4MechanicalMounting"inreversesteps.

8.3DisposaloftheInverter

Userstaketheresponsibilityforthedisposaloftheinverter.
Somepartsanddevicesoftheinverter,suchasthecapacitors,maycause
environmentalpollution.
Donotdisposeoftheproducttogetherwithhouseholdwastebutinaccordance
withthedisposalregulationsforelectronicwasteapplicableattheinstallation
site.
"3.2InverterStorage"fora
85
Page 96
9

TroubleshootingandMaintenance

9.1Troubleshooting

Whenanalarmoccurs,thealarminformationcanbeviewedthroughtheApp.
AlarmIDandcorrectivemeasuresareasfollows:
AAllaarrmmIIDDAAllaarrmmNNaammeeCCoorrrreeccttiivveeMMeeaassuurreess
001
002
Gridovervoltage
Grid
undervoltage
Generally,theinverterwillbereconnectedtothe
gridafterthegridrecovers.Ifthealarmoccurs
frequently:
1.Measurethegridvoltage,andcontactthelocal
utilitygridcompanyforsolutionsifthegridvoltage
exceedsthespecifiedvalue.
2.Check,throughtheApp,whethertheprotection
parametersareappropriatelyset.
3.Checkwhetherthecross-sectionalareaofthe
ACcablemeetstherequirement.
4.Ifthealarmpersists,contactSUNGROW.
Generally,theinverterwillbereconnectedtothe
gridafterthegridrecovers.Ifthealarmoccurs
frequently:
1.Measurethegridvoltage,andcontactthelocal
utilitygridcompanyforsolutionsifthegridvoltage
isbelowthespecifiedvalue.
2.Check,throughtheApp,whethertheprotection
parametersareappropriatelyset.
3.CheckwhethertheACcableisfirmlyinplace.
4.Ifthealarmpersists,contactSUNGROW.
86
Page 97
UserManual9TroubleshootingandMaintenance
AAllaarrmmIIDDAAllaarrmmNNaammeeCCoorrrreeccttiivveeMMeeaassuurreess
003
Grid
overfrequency
Generally,theinverterwillbereconnectedtothe
gridafterthegridrecovers.Ifthealarmoccurs
frequently:
1.Measurethegridfrequency,andcontactthe
localutilitygridcompanyforsolutionsifthegrid
004
Grid
underfrequency
frequencyisbeyondthespecifiedrange.
2.Check,throughtheApp,whethertheprotection
parametersareappropriatelyset.
3.Ifthealarmpersists,contactSUNGROW.
Generally,theinverterwillbereconnectedtothe
gridafterthegridrecovers.Ifthealarmoccurs
frequently:
1.Checkwhetherthegridsuppliespowerreliably.
2.CheckwhethertheACcableisfirmlyinplace.
005NoGrid
3.CheckwhethertheACcableiscorrectly
connected(whetherthelivewireandtheNwire
areincorrectplace).
4.CheckwhethertheACswitchorcircuitbreaker
isdisconnected.
5.Ifthealarmpersists,contactSUNGROW.
1.Thealarmcanbecausedbypoorsunlightor
dampenvironment,andtheinverterwillbe
reconnectedtothegridaftertheenvironmentis
006
Overhigh
leakagecurrent
improved.
2.Iftheenvironmentisnormal,checkwhetherthe
ACandDCcablesarewellinsulated.
3.Ifthealarmpersists,contactSUNGROW.
Generally,theinverterwillbereconnectedtothe
gridafterthegridrecovers.Ifthealarmoccurs
frequently:
007Gridabnormal
1.Measurethegridfrequency,andcontactthe
localutilitygridcompanyforsolutionsifthegrid
frequencyexceedsthespecifiedvalue.
2.Ifthealarmpersists,contactSUNGROW.
87
Page 98
9TroubleshootingandMaintenanceUserManual
AAllaarrmmIIDDAAllaarrmmNNaammeeCCoorrrreeccttiivveeMMeeaassuurreess
Generally,theinverterwillbereconnectedtothe
gridafterthegridrecovers.Ifthealarmoccurs
frequently:
1.Measurethegridvoltage.Ifthegridphase
voltagediffersgreatly,contacttheutilitygrid
008
Gridvoltage
unbalance
companyforsolutions.
2.Ifthevoltagedifferencebetweenthethree
phasesiswithinthepermissiblerangeofthelocal
utilitygridcompany,modifytheparametersetting
throughtheApp.
3.Ifthealarmpersists,contactSUNGROW.
1.Checkwhetherthecorrespondingstringisof
reversepolarity.Ifso,disconnecttheDCswitch
andadjustthepolaritywhenthesolarradiationis
lowandthestringcurrentdropsbelow0.5A.
2.CheckwhetherPVstringsconnectedtothe
009
PVreverse
connectionfault
sameMPPThavethesamenumberofPVmodules.
Ifnot,takecorrectivemeasures.
3.Ifthealarmpersists,contactSUNGROW.
1.Checkwhethertheinverterisdirectlyexposedto
sunlight.Ifso,takesomeshadingmeasures.
012
Highambient
temperature
2.Checkandcleantheairducts.
3.Checkwhetherthesub-alarmID070(fanalarm)
occursthroughtheApp.Ifso,replacethefaultyfan.
4.Ifthealarmpersists,contactSUNGROW.
1.Stopanddisconnecttheinverter.
Lowambient
013
temperature
2.Restarttheinverterwhentheambient
temperatureiswithinthepermissiblerange.
88
Page 99
UserManual9TroubleshootingandMaintenance
AAllaarrmmIIDDAAllaarrmmNNaammeeCCoorrrreeccttiivveeMMeeaassuurreess
Waitfortheinvertertorecover.Ifthefaultoccurs
frequently:
1.Checkwhethertheinsulationresistance
protectionvalueisextremelylargethroughtheApp,
andensurethatitcomplieswiththelocal
regulations.
2.ChecktheresistancetogroundfromthePV
module/cable.Takecorrectivemeasuresincaseof
014
LowISO
resistance
leadingtoshortcircuitordamagedinsulationlayer.
3.Ifthecableisnormalandthealarmoccurson
rainydays,checkitagainwhentheweatherturns
fine.
4.Ifthefaultoccursonacloudydaywithoutrain
butthereisstagnantwaterorvegetationonsite,
clearthewaterandvegetation.Ifthefaultpersists,
checkitagainwhentheweatherturnsfine.
5.Ifthealarmpersists,contactSUNGROW.
1.CheckwhethertheACcableiscorrectly
connected.
015
Groundingcable
fault
2.Checkwhetherthegroundingcableandwire
coresarewronglyinsulated.
3.Ifthealarmpersists,contactSUNGROW.
1.DisconnecttheDCinputsandcheckwhether
theDCcablesaredamaged,whetherthewiring
terminalsorfuses,ifnecessary,arelooseorin
poorcontact,andwhetherthereisaPVmodule
burnt.Ifso,takecorrespondingcorrective
016Arcfault
measures.
2.Aftertakingcorrespondingmeasuresinstep1,
reconnecttheDCinputs.Removethearcfault
throughtheApp,andthereforetheinverterwill
recover.
3.Ifthealarmpersists,contactSUNGROW.
89
Page 100
9TroubleshootingandMaintenanceUserManual
AAllaarrmmIIDDAAllaarrmmNNaammeeCCoorrrreeccttiivveeMMeeaassuurreess
1.CheckwhethertheSmartEnergyMeter
communicationcableandterminalareabnormal.If
so,removethecorrespondingabnormity.
2.ReconnecttheSmartEnergyMeter
communicationcable.
3.Ifthealarmpersists,contactSUNGROW.
Theinvertercanoperatenormally.
1.Checkwhethertherelatedcableconnectionand
terminalsareabnormal,andcheckwhetherthe
ambientenvironmentisabnormal.Ifso,take
correctivemeasures.
2.Ifthealarmpersists,contactSUNGROW.
1.Waitfortheinvertertorecover.
2.DisconnecttheACandDCswitchesorcircuit
breakers,andconnectthemagainafter15minutes.
3.Ifthealarmpersists,contactSUNGROW.
019
063
064
SmartEnergy
Meter
communication
error
Systemalarm
Systemfault

9.2Maintenance

9.2.1 MaintenanceNotices

TheDCswitchcanbesecuredwithalockintheOFFpositionoracertainanglebeyond
theOFFposition.
Riskofinverterdamageorpersonalinjuryduetoincorrectservice!
Alwayskeepinmindthattheinverterispoweredbydualsources:PVstrings
andutilitygrid.
Beforeanyservicework,observethefollowingprocedure.
DisconnecttheACcircuitbreakerandthensettheDCload-breakswitchof
theinvertertoOFF;
Waitatleast10minutesforinnercapacitorstodischargecompletely;
Verifythatthereisnovoltageorcurrentbeforepullinganyconnector.
Keepnon-relatedpersonsaway!
Atemporarywarningsignorbarriermustbepostedtokeepnon-related
personsawaywhileperformingelectricalconnectionandservicework.
90