Features and specifications are subject to change at any
time without notice.
Important Note
To ensure this product is installed and operated as safely
and efficiently as possible, take note of the following types
of highlighted information throughout this guide:
IMPORTANT NOTE highlights information that is especially
important.
CAUTION indicates a situation where minor injury or product
damage may occur if instructions are not followed.
WARNING states a hazard that may cause serious injury or
death if precautions are not followed.
IMPORTANT NOTE: Save these instructions for the local
electrical inspector.
Product Information
Important product information including the model and
serial number are listed on the product rating plate. The
rating plate is located on the underside of the control panel,
on the left. Refer to the illustrations below.
If service is necessary, contact Sub-Zero factory certified
service with the model and serial number.
RATING PLATE
RATING PLATE
Models ICBUW-24 and
ICBUW-24FS.
Model ICBBW-30.
Tools and Materials
• Screwdrivers—standard, Phillips and Torx.
• Power drill.
• Drill bits (masonry bits required for concrete installation).
• Standard socket and wrench set.
• .6 m and 1.2 m levels.
• Material to protect home, flooring and cabinetry during
installation.
2 | English
MODEL ICBUW-24 / ICBUW-24FS SITE PREPARATION
Opening Dimensions
MODEL ICBUW-24
610 mm
OPENING
DEPTH
TOP VIEW
876 mm
OPENING
HEIGHT
SIDE VIEWFRONT VIEW
OPENING WIDTHW
ICBUW-24610 mm
Two 610 mm Models*1222 mm
*A dual installation kit will be required for this installation.
W
OPENING WIDTH
DUAL INSTALLATION
If two units are installed side by side, a dual installation kit
may be required. Installations without a custom filler strip
require a dual installation kit. If a dual installation kit is not
specified, a 51 mm filler strip is recommended between
units. Dual installations without a filler strip can only be
accomplished using two units with opposite hinges. Refer to
the illustrations below.
Dual installation kits are available through an authorized
Sub-Zero dealer.
WITHOUT FILLER STRIP
Opposite hinges.
FILLER STRIP
Same side hinges.
Electrical
Installation must comply with all applicable electrical codes
and be properly grounded (earthed).
The electrical supply should be located within the shaded
area shown in the illustration below. A separate circuit, servicing only this appliance is required. A ground fault circuit
interrupter (GFCI) is not recommended and may cause interruption of operation.
ELECTRICAL REQUIREMENTS
Power Supply 220-240 V AC, 50/60 Hz
Circuit Breaker10 amp
Receptaclegrounding-type (earthed)
CAUTION
The outlet must be checked by a qualied electrician to
be sure that it is wired with the correct polarity. Verify
that the outlet is properly grounded (earthed).
LEFT SIDE
OF OPENING
51
394 mm
mm
E
FLOOR
76 mm
Preparation
To operate properly, the door must open a minimum of 90°.
Use a minimum 76 mm filler in corner installations to assure
a 90° door opening.
Uncrate the unit and inspect for damage. Remove and
recycle packing materials. Do not discard the kickplate, antitip bracket, hardware and the leveling legs which hold the
wood base to the bottom of the unit.
Electrical supply location.
Electrical
Shock
Hazard
Plug power cord directly into a properly
grounded (earthed) outlet.
Do not defeat the grounding (earthing)
nature of the plug.
Do not use adapter or extension cord.
Failure to follow these instructions could
cause serious injury or death.
See installation instructions
subzero.com | 3
MODEL ICBUW-24 / ICBUW-24FS SITE PREPARATIONMODEL ICBUW-24 / ICBUW-24FS INSTALLATION
Anti-Tip Bracket
WARNING
To prevent the unit from tipping forward, the anti-tip
bracket must be installed.
MODEL ICBUW-24
The anti-tip bracket should be attached to the wall behind
the unit with the bracket flange located 6 mm above the top
of the unit. Refer to the illustration below. Failure to properly
position the anti-tip bracket will prevent proper engagement.
For installations that cannot accommodate the anti-tip
bracket, a countertop bracket is provided to secure the unit
to the countertop. Refer to the illustration below.
6 mm
Anti-tip bracket (ICBUW-24). Countertop bracket.
COUNTERTOP
BRACKET
MODEL ICBUW-24FS
The back of the anti-tip bracket must be installed 625 mm
from the front and centered behind the unit. Refer to the
illustration below. Refer to page 10 for wood and concrete
floor applications.
ANTI-TIP BRACKET
Anti-tip bracket (ICBUW-24FS).
Custom Panel
MODEL ICBUW-24
For overlay applications, a custom door panel must be
installed. Panel size is critical for a proper fit. To verify panel
requirements and dimensions, refer to the Sub-Zero design
guide.
Finish all sides of the custom panel. They may be visible
when the door is open or through the glass door.
The custom overlay door panel is attached using screws
provided, through the door frame. Screw locations are
marked on the back of the custom panel using tenon centers inserted into holes of the door frame.
With the unit secured and door closed, hold the custom
panel in desired position on the door. Lightly tap the front
of the panel to locate mounting positions. Remove tenon
centers. Refer to the illustration below.
The door frame has mounting holes to accommodate
Sub-Zero accessory handles. If handle mounting holes are
not utilized, the handle should be attached to the custom
panel prior to mounting. Screw heads may need to be countersunk into the panel for proper alignment.
DOOR
FRAMEPANEL
TENON CENTER
GASKET
11 mm
DIAMETER
6 mm
DIAMETER
GLASS
To mount the custom panel, open the door and use predrilled holes to position the panel. Drive screws into the
panel through black tape on the door frame. Screw holes
are hidden behind the door gasket. Use as many screws as
necessary to secure the custom panel. Refer to the illustration below.
Adjustments can be made to the custom panel with a few
mounting screws in place, but not fully tightened. Once the
proper position is achieved, install and secure all screws.
Cover holes on the inside of the door frame with the cover
patches or plugs provided.
CAUTION
A solid panel cannot be installed over the glass door. A
solid door is available through an authorized Sub-Zero
dealer.
4 | English
Tenon center.
Door frame cross section.
MODEL ICBUW-24 / ICBUW-24FS INSTALLATION
Placement
CAUTION
Before moving the unit into position, secure the door
closed and protect any nished ooring.
Use an appliance dolly to move the unit near the opening.
If the unit has been on its back or side, it must stand upright
for a minimum of 24 hours before connecting power.
If the unit will be connected to a home security system, run
lead wires through the compressor compartment prior to
positioning the unit. Once the unit is in position, wiring connection can be completed from the front.
Alignment
LEVELING
Level the unit before sliding it into position. Turn each of the
four leveling legs clockwise to raise the unit and counterclockwise to lower. Refer to the illustration below.
LEVELING LEGS
Leveling.
Completion
Plug the power cord into the grounded (earthed) outlet,
then slide the unit into position. Verify the anti-tip bracket is
properly engaged.
It may be necessary to install the unit 6 mm beyond the
front surface of adjacent cabinetry, to prevent interference
when the door is opened to 145°. Refer to the full-scale
template on page 6.
HOME SECURITY CONNECTION
If the unit will be connected to a home security system,
make connections to the leads shown in the illustration
below. Refer to the following color codes:
• Normally open contacts—white with red stripe wire.
• Normally closed contacts—white with blue stripe wire.
• Common—gray with white stripe wire.
Use the spade terminals or wire nuts provided to make
proper wiring connections.
CAUTION
The alarm circuit in the unit is intended as a lowvoltage, low-current device only. It should not be used
to switch line power. Any unused terminals should be
completely insulated and all wires should be secured
away from conductive or moving components.
ANCHORING
To anchor, use the countertop bracket provided to secure
the unit to the underside of the countertop. Refer to the
illustration below. If the countertop bracket can not be
utilized, install shims along the top and sides of the unit.
KICKPLATE INSTALLATION
Install the kickplate using the two screws provided. Refer
to the illustration below. The kickplate must be removable
for service. The floor cannot interfere with removal. Do not
cover the louvered section of the kickplate.
COUNTERTOP
BRACKET
KICKPLATE
Anchoring.
Kickplate installation.
HOME SECURITY
LEADS
Home security connection.
subzero.com | 5
MODEL ICBUW-24 / ICBUW-24FS INSTALLATION
Door Clearance
FULL-SCALE TEMPLATE
To allow for a 145° door opening, the
unit should extend a minimum of 6 mm
beyond the front surface of adjacent
cabinetry. The unit can be installed
flush, however, there is potential for
interference with the panel if the door is
opened past 90°.
ADJACENT
CABINETRY
13 mm
6
mm
3 mm
HINGE AT 145°
OPENING
(DOOR OPENS
PAST 145°)
6 | English
SCALE
145° door opening (top view).
UNDERCOUNTER
UNIT
DOOR CLOSED
19 mm
DOOR PANEL
25 mm0 mm
MODEL ICBBW-30 SITE PREPARATION
SIDE
Opening Dimensions
STANDARD INSTALLATION
2127 mm
OPENING
HEIGHT
NOTE: Shaded line represents profile of unit.
610 mm
OPENING
DEPTH
TOP VIEW
W
OPENING WIDTH
FRONT VIEWSIDE VIEW
Opening Dimensions
FLUSH INSET INSTALLATION
665 mm
FLUSH
INSET
DEPTH
56 mm
6 mm
2134 mm
FLUSH
INSET
HEIGHT
VIEW
*76 mm typical depth. Shaded areas will be visible and should be finished to match cabinetry.
NOTE: Shaded line represents profile of unit with 19 mm
32 mm
FLUSH INSET WIDTH
panel.
TOP VIEW
W
FRONT VIEW
FINISHED
CLEATS*
102 mm
32
mm
76
mm*
TYPICAL
mm
56
OPENING WIDTHW
ICBBW-30749 mm
If two units are installed side by side, refer to page 8.
FLUSH INSET WIDTH W
ICBBW-30813 mm
Dimensions assume a 19 mm panel thickness. If two units
are installed side by side, refer to page 8.
subzero.com | 7
MODEL ICBBW-30 SITE PREPARATION
SIDE
Opening Dimensions
DUAL STANDARD INSTALLATION
610 mm
OPENING
DEPTH
2127 mm
OPENING
HEIGHT
NOTE: Shaded line represents profile of unit.
TOP VIEW
W
OPENING WIDTH
FRONT VIEWSIDE VIEW
Opening Dimensions
DUAL FLUSH INSET INSTALLATION
665 mm
FLUSH
INSET
DEPTH
56 mm
TOP VIEW
6 mm
2134 mm
FLUSH
INSET
HEIGHT
VIEW
*76 mm typical depth. Shaded areas will be visible and should be finished to match cabinetry.
NOTE: Shaded line represents profile of unit with 19 mm
32 mm
FLUSH INSET WIDTH
FRONT VIEW
panel.
FINISHED
CLEATS*
W
32
mm
102 mm
56
76
mm*
TYPICAL
mm
OPENING WIDTHW
ICBBW-30 and 762 mm Built-In Model 1518 mm
ICBBW-30 and 914 mm Built-In Model 1670 mm
8 | English
A dual installation kit will be required for this installation.
FLUSH INSET WIDTH W
ICBBW-30 and 762 mm Built-In Model 1581 mm
ICBBW-30 and 914 mm Built-In Model 1734 mm
Dimensions assume a 19 mm panel thickness. A dual installation kit will be required for this installation.
MODEL ICBBW-30 SITE PREPARATION
Dual Installation
If two units are installed side by side, a dual installation kit
may be required. Installations without a custom filler strip
require a dual installation kit. If a dual installation kit is not
specified, a 51 mm filler strip is recommended between
units. Dual installations without a filler strip can only be
accomplished using two units with opposite hinges. Refer to
the illustrations below.
Dual installation kits are available through an authorized
Sub-Zero dealer.
WITHOUT FILLER STRIP
Opposite hinges.
FILLER STRIP
Same side hinges.
Electrical
Installation must comply with all applicable electrical codes
and be properly grounded (earthed).
The electrical supply should be located within the shaded
area shown in the illustration below. A separate circuit, servicing only this appliance is required. A ground fault circuit
interrupter (GFCI) is not recommended and may cause interruption of operation.
ELECTRICAL REQUIREMENTS
Power Supply 220-240 V AC, 50/60 Hz
Circuit Breaker10 amp
Receptaclegrounding-type (earthed)
CAUTION
The outlet must be checked by a qualied electrician to
be sure that it is wired with the correct polarity. Verify
that the outlet is properly grounded (earthed).
178
E
mm
152
mm
1918 mm
FROM FLOOR
RIGHT SIDE
OF OPENING
Electrical supply location.
Electrical
Shock
Hazard
Plug power cord directly into a properly
grounded (earthed) outlet.
Do not defeat the grounding (earthing)
nature of the plug.
Do not use adapter or extension cord.
Failure to follow these instructions could
cause serious injury or death.
See installation instructions
Preparation
Uncrate the unit and inspect for damage. Remove the wood
base and discard shipping bolts and brackets. Remove and
recycle packing materials. Do not discard the kickplate, antitip brackets and hardware.
Completely retract the front leveling legs to allow the unit to
be moved into position. The front and rear leveling legs can
be adjusted from the front once the unit is in position.
Remove the drain pan to avoid damage, and allow for
proper appliance dolly placement.
The grille assembly should be removed prior to moving the
unit. To remove, pull out on the bottom edge of the grille and
rotate upward. Loosen the two back grille mounting screws
and remove the two front grille mounting screws. With the
grille held firmly, pull forward to remove. Refer to the illustrations below.
GRILLE
ADJUSTMENT
FRONT
GRILLE SCREW
SCREWS
Grille removal.
BACK GRILLE
SCREW
Grille mounting screws.
subzero.com | 9
MODEL ICBBW-30 INSTALLATION
Anti-Tip Bracket
WARNING
To prevent the unit from tipping forward, the anti-tip
brackets must be installed.
The two anti-tip brackets must be installed exactly 610 mm
from the front of the opening to the back of the brackets
and a minimum of 102 mm from the sides of the opening.
This depth will increase to 665 mm for a flush inset installation, based on 19 mm thick panels. Failure to properly position the anti-tip brackets will prevent proper engagement.
Use all anti-tip bracket hardware as instructed for wood or
concrete floors.
IMPORTANT NOTE: For wood or concrete floor applications,
if the #12 screws do not hit a wall stud or wall plate, use the
#8 screws and #12 washers with the wall anchors.
IMPORTANT NOTE: In some installations the subflooring or
finished floor may necessitate angling the screws used to
fasten the anti-tip brackets to the back wall.
ANTI-TIP HARDWARE
2Anti-tip brackets
12#12 x 64 mm pan head screws
3
/8"–16 x 95 mm wedge anchors
4
12#12 flat washers
4#8–18 x 32 mm truss head screws
4Nylon Zip-it
®
wall anchors
WOOD FLOOR
After properly locating the anti-tip brackets in the opening,
drill pilot holes 5 mm diameter maximum in the wall studs or
wall plate. Use the #12 screws and washers to secure the
brackets. Verify the screws penetrate through the flooring
material and into wall studs or wall plate a minimum of 19
mm. Refer to the illustration below.
CONCRETE FLOOR
After properly locating the anti-tip brackets in the opening,
drill pilot holes 5 mm diameter maximum in the wall studs
or wall plate. Drill 10 mm diameter holes into the concrete a
minimum of 38 mm deep. Use the #12 screws and washers
to secure the brackets to the wall, and use the
3
/8" wedge
anchors to secure the brackets to the floor. Verify the screws
penetrate wall studs or wall plate a minimum of 19 mm.
Refer to the illustration below.
102 mm
FINISHED
FLOORING
610
mm
MIN
102 mm
FINISHED
FINISHED
FLOORING
FLOORING
610
mm
MIN
CONCRETE WEDGE ANCHOR INSTALLATION
1 Drill a 10 mm diameter hole any depth exceeding the
minimum embedment. Clean the hole or drill additional
depth to accommodate drill fines.
2 Assemble the washer and nut flush with the end of
anchor to protect threads. Drive the anchor through the
material to be fastened until the washer is flush with the
surface material.
3 Expand the anchor by tightening the nut 3–5 turns past
hand-tight position or to 34 newton-meters of torque.
WARNING
Verify there are no electrical wires or plumbing in the
area which the screws could penetrate.
CAUTION
Always wear safety glasses and use other necessary
protective devices or apparel when installing or working
with anchors.
Anchors are not recommended for use in lightweight
masonry material such as block or brick, or for use in
new concrete which has not had sufcient time to cure.
The use of core drills is not recommended to drill holes
for the anchors.
Custom Panels
For overlay and flush inset applications, custom door and
grille panels must be installed. Panel size is critical for a
proper fit. To verify panel requirements and dimensions,
refer to the Sub-Zero design guide.
IMPORTANT NOTE: Flush inset applications require a
minimum 13 mm reveal on all sides.
Finish all sides of the custom panel. They may be visible
when the door is open or through the glass door.
CAUTION
A solid panel cannot be installed over the glass door.
10 | English
WALL PLATE
SUBFLOORING
Wood oor.
WOOD FLOOR
WALL PLATE
WALL PLATE
SUBFLOORING
SUBFLOORING
CONCRETE
CONCRETE
FLOOR
FLOOR
Concrete oor.
11/2"
38 mm
min
MIN
(38)
MODEL ICBBW-30 INSTALLATION
2134
mm
610 mm
OPTIONAL
TOE KICK
CUT-OUT
102 mm
48 mm
25 mm
ROUT TO
3 mm
FRONT
OF SIDE
PANEL
67 mm
MAIN
FRAME
SIDE PANEL
ROUTING
25 mm
48 mm
3 mm
13 mm
Panel Installation
DOOR PANEL
To install the custom door panel, remove the handle side
trim molding. Insert a screwdriver tip into the top corner slot
on the handle side and pop out the trim. Remove the screws
and frame. Refer to the illustration below.
The door has a 6 mm frame for the custom panel to slide
into. If the panel is thicker than a 6 mm, rout an edge around
the panel or mount the panel on a sheet of 6 mm thick
material, then insert into the frame.
Door side trim.
A 3 mm space is required between the backer panel and the
custom panel to allow the panel to slide into the door frame.
Refer to the illustrations below for critical dimensions.
Install handle hardware before inserting the panel. Large
D-style handles are recommend rather than knobs. Screw
heads must be countersunk into the panel.
Slide the panel into the frame.
To reinstall the door trim molding, insert the top of the trim
into grooves at the top of the door and work downward,
snapping the trim into clips on the door frame.
SPACER PANEL
CUSTOM PANEL
BACKER PANEL
TRIM
8 mm min
3 mm (OVERLAY)
Panel assembly cross section
(overlay).
CUSTOM
PANEL
19
mm
typical
Panel assembly rear view.
3 mm
SPACER
PANEL
BACKER
PANEL
6 mm
GRILLE PANEL
Remove the bottom grille frame by extracting the lower
two corner screws from each side of the grille assembly.
Refer to the illustration below.
With the bottom section removed, slide the custom grille
panel into the frame. If the panel is thinner than 6 mm, a
filler material will need to be installed to achieve a proper
fit. Once the panel is installed, reattach the bottom grille
frame by sliding the corner brackets back into position, then
reinstall the four corner screws.
BOTTOM
GRILLE
FRAME
Grille frame assembly.
SIDE PANEL
When installing a custom side panel, an accessory kit is
required and is available through an authorized Sub-Zero
dealer. Stainless steel and white enamel side panels are also
available from an authorized Sub-Zero dealer.
IMPORTANT NOTE: The use of side panels may change the
width of the opening.
A custom side panel must be a minimum of 610 mm deep
and 13 mm thick. Routing will be necessary for the side
panel to fit flush against the side of the unit. Refer to the
illustrations below.
IMPORTANT NOTE: The height of the side panel will vary
with the height of the grille. Verify the finished height before
modifying panels.
Side panel dimensions.
Routing detail.
subzero.com | 11
MODEL ICBBW-30 INSTALLATION
Placement
CAUTION
Before moving the unit into position, secure the door
closed and protect any nished ooring.
Use an appliance dolly to move the unit near the opening.
If the unit has been on its back or side, it must stand upright
for a minimum of 24 hours before connecting power.
If the unit will be connected to a home security system, run
lead wires through the compressor compartment prior to
positioning the unit. Refer to page 13. Once the unit is in
position, wiring connection can be completed from the front.
Plug the power cord into the grounded (earthed) outlet, then
roll the unit into position. Verify the anti-tip brackets are
properly engaged.
IMPORTANT NOTE: If used, side panels will need to be
installed before the unit is placed in its final position.
Alignment
LEVELING
Once the unit is in position, turn the front leveling legs
clockwise to adjust the height. The rear height adjustment
can be made from the front of the roller base. Using a
socket, turn the
3
/8" hex bolt clockwise to raise the unit or
counterclockwise to lower. Use the lowest torque setting
when using a power drill. Do not turn the rear leveling legs
by hand. Refer to the illustration below.
When the unit is properly leveled, door adjustments are less
likely to be necessary.
IMPORTANT NOTE: Level the unit to the floor, not sur-
rounding cabinetry. This could affect the operation of the
unit, such as door closing.
WARNING
To reduce the possibility of the unit tipping forward, the
front leveling legs must be in contact with the oor.
FRONT
LEVELING LEG
REAR
ADJUSTMENT
Leveling.
3
/8"
DOOR ADJUSTMENT
The door can be adjusted in and out, side to side tilt and up
and down.
To make adjustments, slightly loosening the two upper hinge
bolts on the upper hinge plate using a
1
/2" wrench. Refer to
the illustration below.
5
In and out adjustment | For a left-hinge door, using a
/32"
allen wrench, turn the adjustment bolt clockwise to bring
the handle side of the door inward, and counterclockwise
to move the handle side outward. Reverse directions for a
right-hinge door.
Side to side tilt adjustment | For a left-hinge door, using a
3
/8" wrench, turn the adjustment bolt clockwise to raise the
handle side of the door, and counterclockwise to lower the
handle side. Reverse directions for a right-hinge door.
Up and down adjustment | For a left-hinge door, using a
1
/4" allen wrench, turn the adjustment bolt clockwise to raise
the door and counterclockwise to lower. Refer to the illustration below. Reverse directions for a right-hinge door.
UPPER
HINGE BOLTS
IN-AND-OUT
ADJUSTMENT
SIDE-TO-SIDE
TILT ADJUSTMENT
Door adjustment bolts.
Up and down door adjustment.
Completion
GRILLE INSTALLATION
Install the grille assembly and check for proper fit. The grille
is designed to rest on the upper door hinge to minimize the
reveal between the top of the door and bottom of the grille.
To eliminate interference, the grille height can be adjusted.
Loosen the four grille adjustment screws (two on each side)
and adjust the grille height as needed. Refer to the illustration below.
GRILLE
BACK GRILLE
SCREW
Grille height adjustment.
ADJUSTMENT
FRONT
GRILLE SCREW
SCREWS
12 | English
MODEL ICBBW-30 INSTALLATION
Completion
HOME SECURITY CONNECTION
If the unit will be connected to a home security system,
make connections to the leads shown in the illustration
below. Refer to the following color codes:
• Normally open contacts—white with red stripe wire.
• Normally closed contacts—white with blue stripe wire.
• Common—gray with white stripe wire.
Use the spade terminals or wire nuts provided to make
proper wiring connections.
CAUTION
The alarm circuit in the unit is intended as a lowvoltage, low-current device only. It should not be used
to switch line power. Any unused terminals should be
completely insulated and all wires should be secured
away from conductive or moving components.
ANCHORING
After the unit has been leveled and door adjustment completed, anchor the unit to the opening to ensure a proper fit
and secure installation.
To anchor the top of the unit, open the grille and install the
screws provided, through the grille frame into cabinetry.
There are several hole locations. Refer to the illustration
below. Check for proper door clearance by opening the
door.
To anchor the bottom of the unit, drive a screw through the
side hole inside each roller base assembly. The screw will
need to go in at an angle to attach properly. Refer to the
illustration below. Additional material may be needed behind
the cleat to ensure sufficient anchoring.
CAUTION
If the screws provided are not suitable for the installation, use adequate screws.
KICKPLATE INSTALLATION
Reinstall the drain pan and verify it is in the proper position.
Install the kickplate using screws to attach it to brackets on
the inside of each roller base. Refer to the illustration below.
The kickplate must be removable for service. The floor
cannot interfere with removal. Refer to the label mounted on
the kickplate support for height clearance.
Turn power on by touching POWER on the control panel.
90° DOOR STOP
The door opens to 110°. A 90° door stop is provided with
the unit (located behind the grille). Additional 90° door stop
kits are available through an authorized Sub-Zero dealer.
WARNING
Follow all local laws when storing, recycling or discarding unused refrigerators and freezers.
HOME SECURITY
LEADS
Home security connection.
Kickplate installation.
ANCHORING
SCREWS
Top anchoring.
Bottom anchoring.
ANCHORING
SCREW
Sub-Zero, Sub-Zero & Design, Dual Refrigeration, The Living Kitchen, Great American Kitchens The Fine Art of Kitchen Design, and Ingredients are registered trademarks and
service marks of Sub-Zero, Inc. Wolf, Wolf & Design, Wolf Gourmet, W & Design and the color red as applied to knobs are registered trademarks and service marks of Wolf Appli
ance, Inc. (collectively, the “Company Marks.”) All other trademarks or registered trademarks are property of their respective owners in the United States and other countries.
-
subzero.com | 13
CONSERVADORES DE VINO
Contenido
2 Conservador de vino
3 Preparación del sitio del modelo ICBUW-24 /
ICBUW-24FS
4 Instalación del modelo ICBUW-24 / ICBUW-24FS
7 Preparación del sitio del modelo ICBBW-30
10 Instalación del modelo ICBBW-30
Las características y especificaciones están sujetas a cambios sin previo aviso.
Nota importante:
Para garantizar que este producto se instala y funciona de
la forma más eficaz y segura posible, tenga en cuenta la
información que se destaca en esta guía:
NOTA IMPORTANTE se utiliza para resaltar información que
resulta especialmente importante.
PRECAUCIÓN indica una situación en la que se pueden
sufrir heridas leves o provocar daños al producto si no se
siguen las instrucciones.
AVISO indica el peligro de que se produzcan heridas graves
o incluso la muerte si no se respetan las precauciones.
NOTA IMPORTANTE: conserve estas instrucciones para el
inspector eléctrico local.
Información sobre el producto
En la placa de datos del producto encontrará información
importante, incluyendo el modelo y el número de serie. La
placa de datos está ubicada en la parte inferior izquierda del
panel de control. Observe las siguientes ilustraciones.
Si necesita recurrir a un servicio técnico, póngase en contacto con un servicio de Sub-Zero certificado con el modelo
y el número de serie.
PLACA DE DATOS
PLACA DE DATOS
Modelos ICBUW-24 y
ICBUW-24FS.
Modelo ICBBW-30.
Herramientas y materiales
• Destornilladores: estándar, Phillips y Torx.
• Taladro.
• Brocas (se necesitarán brocas de mampostería para la
instalación en hormigón).
• Juego de llaves y llaves de vaso estándar.
• Niveles de 0,6 m y 1,2 m.
• Material para proteger la casa, el suelo y los armarios de
cocina durante la instalación.
2 | Español
PREPARACIÓN DEL SITIO DEL MODELO ICBUW-24 / ICBUW-24FS
Medidas de la cavidad
MODELO ICBUW-24
610 mm
DE PROFUNDIDAD
DE LA CAVIDAD
VISTA SUPERIOR
876 mm
ALTURA DE
LA CAVIDAD
VISTA LATERALVISTA FRONTAL
ANCHURA DE LA CAVIDADAnch.
ICBUW-24610 mm
Dos modelos de 610 mm*1.222 mm
*Para esta instalación se necesita un kit de instalación doble.
Anch.
ANCHURA DE LA CAVIDAD
INSTALACIÓN DOBLE
Si va a instalar dos unidades una junto a la otra, puede
que sea necesario un kit de instalación doble. Asimismo,
las instalaciones que no utilicen un embellecedor a medida
necesitarán un kit de instalación doble. Si no se especifica
el kit de instalación doble, se recomienda utilizar un embellecedor de 51 mm entre las unidades. Las instalaciones
dobles sin embellecedor solamente se pueden llevar a cabo
con dos unidades con las bisagras opuestas. Observe las
siguientes ilustraciones.
Podrá encontrar los kits de instalación doble en un distribuidor de Sub-Zero autorizado.
SIN EMBELLECEDOR
Bisagras opuestas.
EMBELLECEDOR
Bisagras al mismo lado.
Potencia
La instalación debe cumplir con todas las normativas eléctricas aplicables y debe estar correctamente conectada a
tierra.
La toma eléctrica debe situarse en el área sombreada en la
siguiente ilustración. Se necesita un circuito independiente
para esta unidad. No se recomienda utilizar un interruptor
de circuito de fallos de toma de tierra (GFCI), ya que puede
interrumpir el funcionamiento de la unidad.
REQUISITOS ELÉCTRICOS
Alimentación eléctrica 220-240 V CA, 50/60 Hz
Magnetotérmico10 amperios
Enchufecon toma de tierra
PRECAUCIÓN
La toma de corriente debe ser revisada por un electricista cualicado para comprobar que la conexión se ha
realizado con la polaridad correcta. Compruebe que la
toma de corriente está conectada a tierra de manera
correcta.
LADO IZQUIERDO
DE LA CAVIDAD
51
394 mm
mm
E
SUELO
76 mm
Preparación
Para que funcione correctamente, la puerta debe abrirse un
mínimo de 90°. Utilice un embellecedor de al menos 76 mm
cuando instale el aparato en esquinas, con el fin de que se
pueda abrir la puerta a 90°.
Desembale la unidad y compruebe si tiene algún daño o
desperfecto. Quite y recicle los materiales de embalaje. No
tire el zócalo, el soporte antivuelco, las piezas de montaje ni
las patas de nivelación que sujetan la base de madera a la
parte inferior de la unidad.
Ubicación de la alimentación
eléctrica.
Potencia
Descarga
Eléctrica
Enchufe el cable eléctrico directamente en una
toma con conexión a tierra.
No manipule la conexión a tierra del enchufe.
No utilice adaptadores ni alargadores.
Si no sigue estas instrucciones, existe riesgo de
que se produzcan heridas graves o incluso la
muerte.
Ver instrucciones de instalación
subzero.com | 3
PREPARACIÓN DEL SITIO DEL MODELO ICBUW-24 / ICBUW-24FSINSTALACIÓN DEL MODELO ICBUW-24 / ICBUW-24FS
Soporte antivuelco
AVISO
Debe instalarse el soporte antivuelco para evitar que la
unidad se incline hacia adelante.
MODELO ICBUW-24
El soporte antivuelco debe quedar fijado a la pared
situada detrás del aparato con la placa del soporte que
se encuentra a 6 mm por encima del aparato. Observe la
siguiente ilustración. Si no coloca bien el soporte antivuelco,
es posible que no quede bien fijado.
En las instalaciones en las que no se pueda colocar el
soporte antivuelvo, se suministra un soporte bajo la encimera para fijar la unidad a la encimera. Observe la siguiente
ilustración.
6 mm
Soporte antivuelco (ICBUW-24). Soporte de encimera.
SOPORTE
DE ENCIMERA
MODELO ICBUW-24FS
La parte trasera del soporte antivuelco debe instalarse a
625 mm de la parte delantera de la unidad y quedar centrada detrás de esta. Observe la siguiente ilustración. Para
aplicaciones en suelos de madera y de hormigón, consulte
la página 10.
SOPORTE ANTIVUELCO
Soporte antivuelco
(ICBUW-24FS).
Panel fabricado a medida
MODELO ICBUW-24
Para aplicaciones revestibles, se debe instalar un panel de
puerta a medida. El tamaño del panel es fundamental para
que se ajuste correctamente. Para comprobar las medidas
y los requisitos del panel, consulte la guía de diseño de
Sub-Zero.
Realice el acabado de todos los lados del panel a medida,
pues son áreas que pueden resultar muy visibles al abrir la
puerta o a través de los cristales.
El panel de puerta revestible a medida se fija con los tornillos suministrados, en el marco de la puerta. Las ubicaciones de los tornillos están marcadas en la parte posterior
del panel a medida con centros de espiga insertados en
orificios del marco de la puerta.
Con la unidad fijada y la puerta cerrada, coloque el panel
a medida en la posición deseada en la puerta. Golpee con
suavidad la parte frontal del panel para localizar las posiciones de montaje. Retire los centros de espiga. Observe la
siguiente ilustración.
El marco de la puerta tiene orificios de montaje para instalar
los tiradores de Sub-Zero que se distribuyen como accesorios. Si no se utilizan los orificios de montaje para los
tiradores, este debe fijarse al panel a medida antes del montaje. Para una alineación correcta, puede que sea necesario
encastar las cabezas de los tornillos en el panel.
PANEL
MARCO DE
LA PUERTA
JUNTA
11 mm
DE DIÁMETRO
Para montar el panel a medida, abra la puerta y utilice los
orificios ya perforados para colocar el panel. Inserte los tornillos en el panel a través de la cinta negra en el marco de la
puerta. Los orificios de los tornillos quedan ocultos detrás
de la junta de la puerta. Utilice todos los tornillos necesarios para sujetar el panel a medida. Observe la siguiente
ilustración.
Es posible realizar ajustes al panel a medida con unos
pocos tornillos de montaje, colocados pero sin estar completamente apretados. Cuando haya alcanzado la posición
adecuada, instale y fije los tornillos.
Cubra los orificios en el interior del marco de la puerta con
las cubiertas o tapones suministrados.
PRECAUCIÓN
No se puede instalar un panel sólido en una puerta de
cristal. La puerta sólida está disponible en los distribuidores de Sub-Zero autorizados.
4 | Español
CENTRO DE ESPIGA
Centro de espiga.
CRISTAL
6 mm
DE DIÁMETRO
Vista transversal del marco de
la puerta.
INSTALACIÓN DEL MODELO ICBUW-24 / ICBUW-24FS
Colocación
PRECAUCIÓN
Antes de desplazar la unidad para colocarla en su sitio,
asegúrese de que la puerta esté cerrada y proteja el
acabado del suelo.
Utilice una plataforma rodante para desplazar la unidad
hasta la cavidad.
Si la unidad ha estado boca abajo o sobre uno de los lados,
debe permanecer en posición vertical como mínimo 24
horas antes de conectarla a la alimentación.
Si se desea conectar la unidad al sistema de seguridad de
la casa, es necesario instalar cables por el compartimiento
del compresor antes de colocar la unidad. Una vez colocada la unidad, la conexión de los cables se puede realizar
desde la parte delantera.
Alineación
NIVELADO
Nivele la unidad antes de desplazarla para colocarlo en su
sitio. Gire cada una de las cuatro patas de nivelación en
el sentido de las agujas del reloj para levantar el aparato y
gírelas en sentido contrario para bajar la unidad. Observe la
siguiente ilustración.
PATAS DE
NIVELACIÓN
Nivelado.
Comprobación
Enchufe el cable eléctrico en la toma de conexión a tierra y
deslice la unidad en la posición adecuada. Compruebe que
el soporte antivuelco esté bien fijado.
Puede que sea necesario instalar la unidad de forma que
sobresalga 6 mm de la superficie frontal de los muebles
circundantes, para evitar la interferencia cuando la puerta
se abre a 145º. Consulte la plantilla a escala real de la
página6.
CONEXIÓN AL SISTEMA DE SEGURIDAD DE LA CASA
Si se desea conectar la unidad al sistema de seguridad de
la casa, conecte los cables conforme a la siguiente ilustración. Consulte los siguientes códigos de color:
• Contactos que suelen estar abiertos: cable blanco con
raya roja.
• Contactos que suelen estar cerrados: cable blanco con
raya azul.
• Común: cable gris con raya blanca.
Utilice los terminales en horquilla o las tuercas incluidas
para realizar las conexiones de cables correctamente.
PRECAUCIÓN
El circuito de alarma en el aparato solo constituye
un dispositivo de bajo voltaje y corriente débil. No se
debe utilizar para encender o apagar la conexión de
la línea. Todos los terminales sin utilizar deben quedar
aislados por completo y todos los cables deben
quedar jados lejos de componentes de conducción o
desplazamiento.
ANCLAJE
Para el anclaje, utilice el soporte de encimera suministrado para fijar la unidad a la parte inferior de la encimera.
Observe la siguiente ilustración. Si el soporte de encimera
no se puede utilizar, instale chapas a lo largo de los lados y
la parte superior de la unidad.
INSTALACIÓN DEL ZÓCALO
Instale el zócalo utilizando los dos tornillos suministrados.
Observe la siguiente ilustración. El zócalo debe ser extraíble
para permitir sacarlo en caso de avería. El suelo no puede
ser un impedimento para llevar a cabo esta operación. No
cubra la parte tipo persiana del zócalo.
SOPORTE
DE ENCIMERA
ZÓCALO
Anclaje.
Instalación del zócalo.
CABLES DEL SISTEMA
DE SEGURIDAD
DE LA CASA
Conexión al sistema de seguridad de la casa.
subzero.com | 5
INSTALACIÓN DEL MODELO ICBUW-24 / ICBUW-24FS
Margen de apertura de la puerta
PLANTILLA A ESCALA REAL
Para permitir una apertura de la puerta de
145º, la unidad debe sobresalir un mínimo
de 6 mm de la superficie frontal de los
muebles circundantes. La unidad puede
instalarse empotrada, aunque es posible
que interfiera con el panel si la puerta se
abre más de 90°.
MUEBLES
ADYACENTES
13 mm
6
mm
3 mm
BISAGRA A UNA
APERTURA DE 145º
(LA PUERTA DE
ABRE PASADOS145º)
6 | Español
25 mm0 mm
ESCALA
Apertura de la puerta de 145º (vista superior).
UNIDAD BAJO
LA ENCIMERA
PUERTA CERRADA
19 mm
DE PANEL DE
LA PUERTA
PREPARACIÓN DEL SITIO DEL MODELO ICBBW-30
VIST
Medidas de la cavidad
INSTALACIÓN ESTÁNDAR
610 mm
DE PROFUNDIDAD
DE LA CAVIDAD
2127 mm
ALTURA DE
LA CAVIDAD
NOTA: las líneas sombreadas representan el perfil de la unidad.
VISTA SUPERIOR
Anch.
ANCHURA DE LA CAVIDAD
VISTA FRONTALVISTA LATERAL
Medidas de la cavidad
INSTALACIÓN EMPOTRABLE
665 mm
DE
PROFUNDIDAD
EMPOTRABLE
56 mm
6 mm
2134 mm
ALTURA DE
INSTALACIÓN
EMPOTRABLE
A LATERAL
*76 mm de profundidad estándar. las áreas sombreadas serán visibles y deberán acabarse para que coincidan con los muebles.
NOTA: las líneas sombreadas representan el perfil de la unidad con un panel de 19 mm.
32 mm
ANCHURA DE INSTALACIÓN
LISTONES
ACABADOS*
VISTA SUPERIOR
Anch.
EMPOTRABLE
VISTA FRONTAL
102 mm
ESTÁNDAR
mm
mm*
32
56
76
mm
ANCHURA DE LA CAVIDADAnch.
ICBBW-30749 mm
Si va a instalar dos unidades una junto a la otra, consulte la
página 8.
ANCHURA DE INSTALACIÓN EMPOTRABLE Anch.
ICBBW-30813 mm
Las medidas están calculadas con un panel de 19 mm de
grosor. Si va a instalar dos unidades una junto a la otra,
consulte la página 8.
subzero.com | 7
PREPARACIÓN DEL SITIO DEL MODELO ICBBW-30
VIST
Medidas de la cavidad
INSTALACIÓN DOBLE ESTÁNDAR
610 mm
DE PROFUNDIDAD
DE LA CAVIDAD
2127 mm
ALTURA DE
LA CAVIDAD
NOTA: las líneas sombreadas representan el perfil de la unidad.
VISTA SUPERIOR
Anch.
ANCHURA DE LA CAVIDAD
VISTA FRONTALVISTA LATERAL
Medidas de la cavidad
INSTALACIÓN DOBLE EMPOTRABLE
665 mm
DE
PROFUNDIDAD
EMPOTRABLE
56 mm
VISTA SUPERIOR
6 mm
2134 mm
ALTURA DE
INSTALACIÓN
EMPOTRABLE
A LATERAL
*76 mm de profundidad estándar. las áreas sombreadas serán visibles y deberán acabarse para que coincidan con los muebles.
NOTA: las líneas sombreadas representan el perfil de la unidad con un panel de 19 mm.
32 mm
ANCHURA DE INSTALACIÓN EMPOTRABLE
Anch.
VISTA FRONTAL
LISTONES
ACABADOS*
102 mm
32
mm
76
mm*
ESTÁNDAR
mm
56
ANCHURA DE LA CAVIDADAnch.
Modelo empotrable de 762 mm e ICBBW-30 1518 mm
Modelo empotrable de 914 mm e ICBBW-30 1670 mm
8 | Español
Para esta instalación se necesita un kit de instalación doble.
ANCHURA DE INSTALACIÓN EMPOTRABLE Anch.
Modelo empotrable de 762 mm e ICBBW-30 1581 mm
Modelo empotrable de 914 mm e ICBBW-30 1734 mm
Las medidas están calculadas con un panel de 19 mm de
grosor. Para esta instalación se necesita un kit de instalación doble.
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.