Stuart D4000/EURO, D4000 Instruction Manual

Distinction Water Still
D4000 & D4000/EURO
Instruction Manual
Manuel d’utilisation
700596 / 03 2017
water still Distinction D4000
ON
2
Before use
If the equipment is not used in the manner described in this manual the protection provided by the equipment may be impaired.
N.B. The Distinction Water Still is classified as “Permanently Connected Equipment” and should be connected to the electricity supply by a qualified electrician in the manner described in the electrical installation section of this manual.
The Distinction Water Still is designed to operate under the following conditions:
For indoor use onlyAmbient temperature range +5°C to +40°CAltitude up to 2000mRelative humidity not exceeding 80%Mains supply voltage fluctuations not greater than
±10% of nominal
Overvoltage category II IEC60364-4-443Pollution degree 2 IEC664
Distinction Water Still D4000 & D4000/Euro
Figure 1 General assembly
Thermostat reset buttons
Boiler thermostat tube
On/Off switch
Clip
Reservoir level control
Heater Gaskets
and flange
Distillate
outlet tube
Boiler
Stand
Stopcock
To drain
Constant level control
Wall mounting screw holes
Condenser cooling water inlet
Condenser thermostat tube
Condenser outlet (upper)
Straps
Condenser
Condenser thermostat
Boiler
thermostat
probe
ON
OFF
water still Dis
Hose assembly 2
Hose assembly 1
Outlet
Earth point for earthed pipe straps
3
2. Remove the end cover from the electrical compartment by undoing the retaining screws in the left hand panel.
3. Take the metal stand and place in the desired location. Note
that 2 screw holes are provided for wall mounting.
If wall mounting you must ensure you use appropriate wall fixings that can hold a minimum weight of 80KG. If you are in any doubt seek professional advice.
4. Take the boiler, the heater and the gasket kit and assemble as shown in figure 2.
i) Place the bolts through the metal flange in the manner
shown and then place the metal flange over the tapered glass tube of the boiler.
ii) Take the plastic insert and bend it round the glass tube
and into the metal flange. Pull the flange and insert towards the open end of the glass tube until the insert presses on the glass.
iii) Place the aluminium plate, followed by the silicone ring
over the heating element and locate approximately 40-45mm from the end with the electric cable, see fig. 2.
iv) Insert the heating element through the tapered glass tube
and into the boiler – ensure that there is clearance at the inside end and no danger of the end of the element pressing against the end of the boiler.
v) Insert the three bolts into the threaded holes in the
aluminium plate and evenly tighten. Check element is secure and horizontal but do not over tighten bolts.
vi) Ensure the heating element is horizontal within the boiler
5. Take the two metal straps and attach the springs to the rear of the “cradles” on the stand. Place the assembled boiler and element onto the “cradle” of the stand. Slide the assembly along until the protruding end of the element is located inside the electrical compartment.
N.B. A “pip” on the bottom of the boiler locates in a hole in
the right-hand cradle.
Ensure that the boiler thermostat probe is located in the
thermostat tube.
Attach the free ends of the straps to the front of the cradle to
secure the boiler in place.
Location
The Distinction Water Still can be wall or bench mounted. Select a convenient location which has access to the following services:-
Electricity Supply
Before connection please ensure that the line supply is suitable. The Distinction Water Still is available in two models, model no. D4000 for supplies rated at 3kW, 220-240V 50/60 Hz single phase and model no. D4000/EURO for supplies rated at 3kW, 200-230V, 50/60Hz, single phase. All units should be connected to the mains supply via a double pole 30mA RCD isolating circuit breaker rated at 15A
Water Supply
A cold water supply capable of providing a minimum flow rate of 60 l/hr.
Drain
A waste water drain located below the level of the Still so that the drain pipe can fall away straight without kinks or bends, to allow an unimpeded flow. All water supplies and drainage systems should be properly earth bonded.
Reservoir
A distillate collection reservoir should be located beneath the Still.
Assembly
1. Unpack the Still and identify the following components:-
Qty. Component Catalogue No.
1 Support Stand ­1 Boiler D4000/B 1 Condenser WC48/M2 1 Heating element D240H for D4000 D220H for D4000/EURO 1 Hose kit W4000/HK 1 Gasket kit D4000/GK 1 Boiler thermostat tube WTT48 1 Condenser thermostat tube A515414 2 Plastic connecting caps QC18/11 2 Silicone rubber rings QR18/7 and QR18/10 1 P.T.F.E washer QW18/7 1 Reservoir level control WLS
Figure 2 Heater and thermostat tube assembly
Heater
Aluminium
plate
Silicone
ring
Plastic
insert
Metal
flange
Bolts
Boiler
Screwcap
Tapered glass tube
Boiler
thermostat
tube
40-45mm
4
Identify the “condenser” thermostat and place the free end of
its probe into the thermostat tube. Carefully bend the capillary to ensure that it does not obstruct access to the thermostat reset buttons. - see figure 1.
13. Refer to fig. 3e. Connect the cooling water inlet of the condenser to the connector of the 8mm bore hose of hose assembly 2. Connect the free end of the earthed spigot of hose assembly 2 to the cold water feed.
Select good quality tubing and secure all connections with hose
clips.
6. Connect the heater cable as shown in figure 3a.
- Push wires fully into block.
- Ensure screw terminations are tight.
7. Ensure that the sealing o-ring and stabilising o-ring are correctly positioned, as shown in Figure 3c. Fit the condenser WC48/M2 by mounting it onto the vapour tube of the boiler. Ensure the distillate outlet tube of the condenser faces the front and the cooling outlet faces parallel to the unit.
8. From the hose kit take the length of 8mm bore hose fitted with the plastic screwthread connectors at either end. Referring to figure 1, screw one end of the hose to the condenser outlet (upper) and the other end to the glass thread on the constant level control.
09. Refer to fig. 3d. Carefully attach the end of the short 16mm
bore hose of hose assembly 1 to the outlet of the constant level control. From the hose kit take the 1000mm length of 16mm bore hose and attach to the free end of the earthed spigot. For ease of connection, first warm the end of the hose with hot water. Secure with the tie strap provided.
10. Lead the free end of the hose to drain, ensuring it falls away from the Still with no kinks or bends to impede the water flow.
11. Ensure that the stopcock on the constant level control is closed.
12. Assemble the condenser thermostat tube A515414 connecting cap QC18/11, silicone rubber ring QR18/7 as shown in figure 4a.
If the cap is left loose the assembly may now be carefully slid
over the air vent on the distillate outlet - see figure 4a.
Tighten up the cap once the tube is in place.
Figure 4a
Assembly of condenser thermostat tube
Condenser thermostat
Condenser thermostat tube
Screwcap
Air vent
Distillate outlet
Figure 3a
Heater electrical connections
Brown
Brown
Blue
Blue
Heater cable
Heater
3kW 220/240V
Front panel
Yellow/green
Mains cable
Brown
Blue
N
L
Figure 3b
Figure 3c
Cooling water outlet
Outlet tube
Condenser
Sealing o-ring
Vapour tube
Stabilising o-ring
Figure 3d: Hose assembly 1
Connection to outlet of constant level control
Free end
Tie-strap
Figure 3e: Hose assembly 2
Free end
Tie-strap
Connector
Mains electrical connections
5
14. Connect the distillate outlet of the condenser to a suitable
collection reservoir, using a suitable length of 9mm tubing.
A glass reservoir system is available from Cole-Parmer
(Catalogue No. WR20). Please contact the sales office for details.
15. Replace the end panel on to the unit.
16. Take the reservoir control WLS and push the free end of the rubber tubing onto the nozzle on the left hand end of the unit
- see figure 1.
Use the clip provided to mount the glass pressure bell in the
neck of the distillate reservoir.
Adjust the height of the pressure bell so that the open end is
approx. 140mm below the maximum distillate level.
Fitting the Reservoir Control WLS to Collection Vessels
- Position the distillate collection reservoir in a suitable location. This should be below the water still so that the vinyl rubber tubing transporting the distilled water from the still can fall down to the reservoir without restrictions, kinks or U bends.
- Take the Reservoir Level Control WLS and connect the free end of the rubber tubing to the nozzle, of the reservoir pressure switch located on the side of the stand.
- Use the metal clip to fit the glass pressure bell inside the distillate collection reservoir. Refer to fig. 4b.
- Position the bell so that the open end is 140mm below the desired distillate level.
17. Ensure that the earthed spigot wires are connected to the earth point see fig 1.
18. Turn on the water supply to fill boiler and check for leaks then turn off the water supply.
Fig 4b WLS Reservoir level control
140mm
Electrical installation
THIS EQUIPMENT MUST BE EARTHED!
The electrical installation should be carried out by a qualified electrician. The following method is recommended.
The earthed spigots should pass a high current (i.e. >200mA) earth continuity test.
The equipment is supplied with 1.5m of PVC/PVC flexible, triple core, circular cable with the following specification, 1.5mm
2
to BS
6500 or equivalent and <HAR> or BASEC approved.
The cable gland is designed to accept cable whose diameter is >7.0mm and <10.5mm. It is recommended that, at the connection to the mains electrical supply, there is fitted a 30mA RCD circuit breaker with a continuous current carrying capacity of 15 amps at 250V, and rated at an overcurrent protection level of 15A . These devices should be sited near to the equipment and be clearly marked “Disconnect device for ‘Distinction’ Water Still”.
NOTE: Do not connect to electricity supply with a 13 amp plug.
Cable connections are shown in figures 3a and 3b. Connect to the line supply noting that the wires in the instrument lead are coloured in accordance with the following code:
Blue - Neutral Brown - Live Green & Yellow - Earth
Mains Cable Replacement
If the mains cable requires replacement, only cable with the specification given above should be used.
For live and neutral leads use bootlace crimps, size 1.5mm, with a performance conforming to BS 4G178 part 1, 1984 and part 2,
1986.
For the earth lead use 1.5mm, M4 eyelet crimps with a performance conforming to BS 4G178 part 1, 1984 and part 2, 1986. A suitable crimp tool should be used.
Operation
1. Turn on the cold water supply and adjust the flow to approx. 60 l/ hr. Observe that the water flows via the condenser and into the boiler. Wait until the boiler has attained its correct operating level and make sure that the excess water is flowing freely to drain.
1. For hose assembly 1 follow fitting instruction 9.
2. Ensure that the earth wire is connected correctly to the earth post - see figs 1 and 4c.
3. For hose assembly 2, please follow fitting instruction 13.
4. Ensure that the earth wire is connected to the earth post - see figs. 1 and 4c.
Replacing earthed hose assemblies
Hose assembly 2
Figure 4c Earth post connection
Nut
Hose assembly 1
Shake proof washers
Loading...
+ 11 hidden pages