Structural Concepts GLDSS12R Installation Manual

READ AND SAVE THESE INSTRUCTIONS
INSTALLATION &
G-SERIES
SELF-SERVICE REFRIGERATED SINGLE DECK MERCHANDISERS - LOW CAPACITY
GLDSS10R.5240
OPERATING MANUAL
GLDSS6R.5322
(With Steps)
PN 5-7277
GLSS8R.4960
GLSS12R.4935 & GLSS12R.4958
GLSSX9R.4934
& GLSSX9R.4959
GLDSS12R.5070D
GLDSS9036RG.5655
GLDSS4R
GLDSS6R.5070A
GLDSSX239R
GLDSS8R.5070B
GLDSS443R
888 E. Porter Road · Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com
G-Series\G-Series_Self-Service_Refrigerated_Single_Deck_Manual_5-7277.pub ||||| Rev X: 3.20.2014
Note: See next page for a
complete list of models
represented by this manual.
TABLE OF CONTENTS / MODEL APPLICABILITY
TABLE OF CONTENTS / MODEL APPLICABILITY …………………………………………………….....
OVERVIEW / TYPE / COMPLIANCE / WARNINGS / PRECAUTIONS / WIRING / PLUGS ………….. SKID REMOVAL ……………………………………………………………………………………………….
INSTALLATION: POSITIONING / ALIGNING / FRAME SUPPORT RAILS / LEVELERS ...…….….…. INSTALLATION, CONTINUED: BOLTING & CAULKING UNITS TOGETHER ……………………..…..
ELECTRICAL CONNECTIONS (SELF-CONTAINED vs. REMOTE UNITS) ….…………………..……. REFRIGERATED REAR STORAGE AREAS (NOT ON ALL MODELS) ………………………………… OPTIONAL REAR ‘PUSH-UP’ WORK COUNTER …………………………………………………..…….. ADJUSTABLE SCALE STAND (GLDSS10R.5255) / REAR OUTLETS (GLDSS443R.5951) ………… START-UP AND OPERATION …...…...…..…………………………...………….……...….……………...
MAINTENANCE FUNDAMENTALS …………………………………………..……………………...……... HONEYCOMB AIR DIFFUSERS (SERVICE TECHNICIANS ONLY) ……………………………………. START-UP & OPERATION - THERMO-SIMPLE 2 (TS.2) DIGITAL THERMOMETER ALARM ……... SERIAL LABEL INFORMATION & LOCATION ..……...…………………..…………………..…….….…..
CLEANING SCHEDULE (TO BE PERFORMED BY STORE PERSONNEL) ………...…..……...….....
CLEANING SCHEDULE: STAINLESS STEEL (TO BE PERFORMED BY STORE PERSONNEL) …. BUTCHER BLOCK CLEANING INSTRUCTIONS (TO BE PERFORMED BY STORE PERSONNEL) CAESARSTONE® SOLID SURFACE (TO BE PERFORMED BY STORE PERSONNEL) …………...
PREVENTIVE MAINTENANCE (TO BE PERFORMED BY TRAINED SERVICE PROVIDER) …..…..
TROUBLESHOOTING (TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY) …….....
TROUBLESHOOTING (BY TRAINED SERVICE PROVIDERS ONLY) - CONDENSING SYSTEM ….
TROUBLESHOOTING (BY TRAINED SERVICE PROVIDERS ONLY) - EVAPORATOR SYSTEM ....
CAREL® CONTROLLER - PROGRAMMING THE INSTRUMENT…...………………………….……....
CAREL® CONTROLLER - USER INTERFACE, SUMMARY TABLES OF ALARMS & SIGNALS ..…. CAREL® CONTROLLER - Summary Table of Operating Parameters (After Programming Key) ...…..
TECHNICAL SERVICE CONTACT INFORMATION & WARRANTY INFORMATION …….…..............
2
3-4
5
6 7
8
9 10 11 12
13-18 19-20 21-22
23
24 25 26 27
28-29
30-32
33 34
35 36 37
38
This Operating Manual is Applicable To The Following G-Series
GLDSSN2R GLDSSN4R GLDSSN9R GLDSS439R GLDSS443R GLDSS443R.5951 GLDSS639R GLDSS643R
GLDSS839R GLDSS9036RG.5655 GLDSS1039R GLDSS1043R GLDSS1043R.5951D GLDSS1239R GLDSS4R
GLDSS6R.5070 GLDSS6R.5179 GLDSS6R.5238 GLDSS6R.5322 GLDSS6R.5454A GLDSS8R GLDSS8R.5070B
Self-Service Refrigerated Single Deck Merchandiser Models:
GLDSS4R.5070 GLDSS4R.5322B GLDSS4R.5454 GLDSS6R GLSS6R.4933 GLSS6R.4957 GLDSS6R.5069
GLDSS8R.5178 GLDSS8R.5245 GLDSS8R.5322A GLDSS8R.5454B GLDSS8R.5454SB GLDSS12R.5070D
GLDSS12R.5375 GLDSS12R.5454D GLDSS843R GLDSS843R.5440 GLDSS1243R GLDSSN943R.5951H
GLDSSX2R GLDSSX4R GLDSSX9R GLDSSX9R.5239 GLDSSX9R.5323 GLSS8R.4960 GLDSS10R.5454C
GLSS12R.4935 GLSS12R.4958 GLDSS12R.5454D GLDSSX239R GLSSX9R.4934 GLSSX9R.4959
GLSSX9R.5177 GLDSSX9R.5239 GLDSSX9R.5454AA GLDSSX943R GLDSSX940R.5570 GMDS6R.5241
GMDS10R.5243 GMDS10R.5255 SO96R.5440
2
OVERVIEW / TYPE / COMPLIANCE / WARNINGS / PRECAUTIONS / CORDS / WIRING - PG 1 of 2
OVERVIEW
 These Structural Concepts merchandisers are
designed to merchandise packaged products at 41 °F (5 °C) or less product temperatures (unless custom cases with wire rack shelving).
 Products must be pre-chilled to 41 °F (5 °C) or less
prior to being placed in merchandiser.
 Cases should be installed and operated according to
this operating manual’s instructions to ensure proper performance.
 Improper use will void warranty.
TYPE 1 vs. TYPE 2 CONDITIONS
This unit is designed for the display of products in ambient store conditions where temperatures and humidity are maintained within a specific range.
 For Type 1 Conditions (most cases): ambient
conditions are to be at 55% maximum humidity and maximum temperatures of 75 °F (24 °C).
 Type 2 Conditions: ambient conditions are to be at
60% maximum humidity and maximum temperatures of 80 °F (27 °C).
 If unsure if unit is Type 1 or 2, see tag next to serial
label. See SERIAL LABEL LOCATION & INFORMATION LISTED / TECH INFO & SERVICE section in this manual for sample serial labels).
COMPLIANCE
 Performance issues when in violation of applicable
NEC, federal, state and local electrical and plumbing codes are not covered by warranty.
 See below compliance guideline.
WARNINGS
 This page contains important warnings to prevent
injury or death.
 Please read carefully!
PRECAUTIONS and WIRING DIAGRAMS
 See next page for PRECAUTIONS and WIRING
DIAGRAM information.
WARNING
ELECTRICAL
HAZARD
WARNING
KEEP HANDS CLEAR
WARNING
HOT
SURFACE
COMPLIANCE
This equipment MUST be installed in compliance with
all applicable NEC, federal, state and local
electrical and plumbing codes.
WARNING
Risk of electric shock. Disconnect power before servicing unit.
CAUTION! More than one source of electrical supply is
employed with units that have separate circuits.
Disconnect ALL ELECTRICAL SOURCES before servicing.
WARNING
Hazardous moving parts. Do not operate unit with covers removed.
Fan blades may be exposed when deck panel is removed.
Disconnect power before removing deck panel.
WARNING
Condensate Pan is Hot!
Disconnect and allow to cool
before cleaning or removing from case.
3
OVERVIEW / TYPE / COMPLIANCE / WARNINGS / PRECAUTIONS / CORDS / WIRING - PG 2 of 2
PRECAUTIONS
 Following are important precautions to prevent
damage to unit or merchandise.
 Please read carefully!
 See previous page for specifics on OVERVIEW,
CONDITION TYPE, COMPLIANCE and WARNINGS.
CAUTION! GFCI BREAKER REQUIREMENT
If N.E.C. (National Electric Code) or your local code
requires GFCI (Ground Fault Circuit Interrupter) protection,
you MUST use a GFCI breaker in lieu of a GFCI receptacle.
CAUTION
 Performance issues caused by adverse conditions are NOT cov ered by
warranty.
 End panels must be tightly joined or kept at least 6-inches
structure to prevent condensation.
 Unit must be kept at least 15-feet
or any air curtain disruption to maintain proper temperatures.
 Unit must not be exposed to direct sunlight or any heat source (ovens,
fryers, etc.).
 Tile floors, low ceilings or small rooms will increase noise level. Whisper Cool
compressor blanket or remote unit may resolve noise level issues.
 Keep at least 8-inch
units only).
CAUTION! ADVERSE CONDITIONS / SPACING ISSUES
WIRING DIAGRAM
 Each case has its own wiring diagram folded and in its
own packet.
 Wiring diagram placement may vary; it may be placed
near ballast box, field wiring box, raceway cover, or other related location.
away from any
from exterior doors, overhead HVAC vents
clearance above unit for air discharge (self-contained
CAUTION! POWER CORD AND PLUG MAINTENANCE
Risk of electric shock. If cord or plug becomes damaged,
replace only with cord and plug of same type.
WIRING DIAGRAM FORMAT & LOCATION
 Each case has its own wiring diagram folded and in its own packet.  Wiring diagram placement may vary; it may be placed near ballast box, field
wiring box, raceway cover, or other related location.
CAUTION! CHECK CONDENSATE PAN POSITION & PLUG
Water on flooring can cause extensive damage!
Before powering up unit, check and confirm the following:
 Condensate pan must be DIRECTLY UNDER condensate drain.  Condensate pan plug must be securely plugged into receptacle.  Overflow pan must have plug connected to its box. Units with
optional Clean Sweep™ MUST HAVE 2 plugs connected.
4
REMOVAL FROM SKID
CASE REMOVAL FROM SKID (CASTERS, LEVELERS OR FRAME SUPPORT RAILS)
1. Removing Case Shipping Brackets That Are Attached To Skid
 Remove screws holding Case Shipping Brackets to skid.  Remove Case Shipping Brackets from Skid.  See illustrations below.  Note: Shipping Brackets will vary in size, shape, material and
Note: Units shown may
not depict an exact
representation of your
particular unit being installed.
location depending upon case type and model.
Various Types Of
Case Shipping
Brackets
2. Remove Case (With Levelers or Frame Support Rails) From Skid
 To prevent damage, support case while sliding it
toward edge of skid.
 When case is at edge of skid, carefully lower to
floor so that two levelers (or one frame support
rail) rests on floor.
 Carefully slide skid out from under case.  After case is off skid, place into position.
 Note: Illustration below reflects general outline of
sample case and does not reflect any particular
model or options).
Support
case
while
Carefully
Slide Skid
Out From
Under Case
removing from skid
3. Remove Case (With Casters) From Skid
A. Place ramp up against skid (to allow case to
smoothly slide off from skid).
B. Maintain support of case at all times or center
of gravity may cause case to fall.
C. Unlock Casters. Slide unit to rear of skid. Slide
down ramp and off from skid.
 Note: Illustrations reflect general outline of
sample case and may not reflect your particular model or options).
Support
case
while
sliding
down
ramp.
Ramp
5
5
INSTALLATION: POSITIONING / ALIGNING / FRAME SUPPORT RAILS / LEVELERS
Note: Units shown may not depict an exact representation of your particular unit being installed.
1. Position & Align Case Alongside Other Cases
 Before adjusting levelers (or shimming frame
support rails), make certain that the case is in
proper position and, if required, aligned with
adjoining case.
 This may require the repositioning of the case
you are installing or
case.
2. Cases With Frame Support Rails: Shim
 Illustration at top right shows case with frame
the already positioned
support rails.
 Shims will be provided with all cases that have
frame support rails.
 Use shims to level case.
 Note: After case is in position, it must be
sealed to floor to prevent entry or leakage
of liquid or moisture.
3. Cases With Levelers: Adjust Levelers
 After case is in position, adjust case so it is level
and plumb (see illustration at right).
 You may need to remove front and/or rear
Frame Support
Rails
Toe-Kick to access levelers.
 Use adjustable wrench (and possibly a pry bar)
to adjust leveler.
 Do not use Pry Bar on Toe-Kick as it may
buckle.
 Do not use Pry Bar on End Panel as it may
chip.
 Use Pry Bar ONLY on Base Frame to avoid
Adjustable
Wrench
damaging case.
 See illustration and photos below and at lower
right.
6
Pry Bar
Leveler
Base
Frame
Toe-Kick
INSTALLATION, CONTINUED: BOLTING & CAULKING UNITS
4. Bolting & Caulking Units Together
Note: Unit shown may not depict an exact representation of your particular unit being installed.
Follow these steps to assure a secure, level lineup.
A. Begin all lineups leveling from highest point of
floor.
B. After the ’first’ case is level, apply industrial
grade butyl caulk on non-visible areas (at case
end). Use industrial grade silicone sealant on
visible areas (at case end).
C. Form Two (2) Caulk/Sealant Lines
: (Sanitation and Refrigeration). See illustration below for outline of caulk/sealant lines.
D. Line up ‘second’ case bolt-hole to bolt-hole to
‘first’ case.
Approximate hole
locations pointed
at with arrows
( ) for bolting
units together.
Sanitation Bead
E. Using SCC-supplied bolts (found in packet),
insert bolts in bolt hole locations (shown below). You may need to remove decking to access lower bolt holes.
F. Caution!
Front of cases MUST be flush with each
other! After leveling, all cases to be same height.
G. Using SCC-supplied nuts & bolts, lightly tighten
each of the 5 to 8 bolts in a cross-wise pattern. Work your way around the pattern, tightening more firmly at each pass. Do not
firmly tighten
one bolt and then start on the next!
H. After the cases are bolted together, level the
‘second’ case. Repeat this process for each case to be adjoined.
I. After all lined-up cases are level, seal all seams
with industrial grade silicone sealant.
Refrigeration Bead
Note: Illustration shown
may not exactly reflect
every feature or option of
your particular case.
Refrigeration
Bead
Sanitation
Bead
Deck
Refrigeration
Bead
7
ELECTRICAL CONNECTIONS (SELF-CONTAINED vs. REMOTE UNITS)
1. Electrical Connections (Self-Contained Units)
Field wiring hook-up/electrical access locations are shown in illustrations below (may not exactly reflect your particular unit).
 Single phase leads are provided.
 See Technical Information Sheet for
more information.
2. Electrical Connections (Remote Units)
Field wiring hook-up / electrical access locations are shown in illustrations below (may not reflect your particular unit).
 Single phase leads are provided.
 See Technical Information Sheet
for more information.
 Note: Illustration at right may not
exactly reflect your particular unit.
Note: Rear of case is shown with
rear grille lifted up and off.
Field Wiring Hookup (for
Self-Contained Cases)
Note: Illustration shown
may not exactly reflect
every feature or option of
your particular case.
Electrical Box
Location
(Remote Units)
8
REFRIGERATED REAR STORAGE AREAS (NOT ON ALL MODELS)
Refrigerated Rear Storage Areas (Not on All Models)
 Refrigerated rear storage area illustrations show
transparent doors (or removed doors) for illustrative purpose only.
 Most models have rear refrigerated storage part of
standard model.
 Optional: Customer specified rear refrigerated storage
units are entirely separate from merchandiser (as shown directly below).
 Adjustable shelves and cooling fan(s) are inside storage
area.
 See CLEANING SCHEDULE (TO BE PERFORMED
BY STORE PERSONNEL) section in this manual for
cleaning schedule and procedure.
Optional Refrigerated Supplies Organizer (SO96R.5440)
To Attach to Rear of Customer Specific Cases Only
(e.g. GLDSS843R). Rear Sliding Doors Removed
For Illustrative Purposes Only
Model GLDSS12R.5375
Sliding doors on these models are shown
transparent. Depending upon model,
some cases may be opaque.
Is Shown Above
9
OPTIONAL REAR ‘PUSH-UP’ WORK COUNTER
Note: Units shown may not depict an exact representation of your particular unit being installed.
1. Optional Rear ‘Push-up’ Work Counter (And Its Accompanying Sneeze Guard’) - ISO View
 View shown at right is illustrated
with optional rear pushup work counter.
 Note: Illustration at right is of
sample model. Your model will vary in appearance.
Optional Rear Pushup Work Counter
2. Optional Rear ‘Push-up’ Work Counter (And Its Accompanying ‘Sneeze Guard’) - Rear View
 View shown at right is of self-contained
unit with optional rear ‘push-up’ work counter in place.
 Sliding doors will allow access to storage
shelf and allow for refrigeration maintenance.
Note: Illustrations shown
may not exactly reflect
every feature or option of
your particular case.
Above view shown with sliding doors transparent (for illustrative
purposes only). Sliding doors are not transparent.
10
ADJUSTABLE SCALE STAND (GLDSS10R.5255) / REAR OUTLETS (GLDSS443R.5951)
If adjustable scale stand material is butcher block,
Adjustable Scale Stand
 View shown below is illustrated with optional rear
pushup work counter.
 Entire adjustable scale stand may be removed

see BUTCHER BLOCK CLEANING INSTRUCTIONS section in this manual.
from case for cleaning purposes. See CLEAN­ING SCHEDULE (TO BE PERFORMED BY STORE PERSONNEL) for instruction on
removing scale stand and cleaning specifics.
Outer Retaining Screws (For
Adjustable Scale Stand) Typ.
Inner Retaining Screws (For
Adjustable Scale Stand) Typ.
Adjustable
Scale Stand
Support Bracket (For Adjustable Scale Stand)
Locking Pad (For
Thumbscrew Pressure)
Thumbscrew (For
Adjustable Scale Stand)
Rear Outlet
Model
GLDSS443R.5951
Rear Outlet
Model
GLDSS10R.5255
11
START-UP AND OPERATION
1. Merchandiser Refrigeration Assembly Pan Slide-Out Feature
 Retaining screws must be removed to allow
refrigeration assembly to be slid out (for servicing and/or cleaning).
 See illustration at top-right.  Note: Two addition screws must be removed from
top of rails for pan to slide out allowing refrigeration assembly access. See illustration at mid-right.
2. Merchandiser Start-Up - Refrigeration
 Self-Contained Only: Before turning on Main Power
switch, remove front panel (by lifting up and off; no screw removal required).
 Caution! Check that the condensate pan is
positioned directly under the drain BEFORE turning on Main Power!
 Return front panel to the case in same manner it
was removed. See below illustration.
3. Merchandiser Start-Up - Electrical
 Remote Units: Case is hard-wired. When power is
supplied, case will power-up.
 Self-Contained: Main Power switch is located at
case rear-right. See illustration at top right (rear panel is removed to show main power switch and temperature controller).
 Rear panel is designed to be lifted up and off without
screws.
Main Power Switch
(Self-Contained Only)
Refrigeration Assembly Pan
Retaining Screws
Two additional
screws must be
removed from top of rails for
pan to slide out.
Temperature
Controller
Refrigeration Package
View of Case Front
Condensate Pan (Electric Coil Evaporation Units)
12
Note: Illustrations
shown may not exactly
reflect every feature
or option of your
particular case.
Front Panel (Lift Up and Off). No Screw Removal Required
Loading...
+ 26 hidden pages