INSTALLATION: POSITIONING / ALIGNING / FRAME SUPPORT RAILS / LEVELERS ...…….….….
INSTALLATION, CONTINUED: BOLTING & CAULKING UNITS TOGETHER ……………………..…..
ELECTRICAL CONNECTIONS (SELF-CONTAINED vs. REMOTE UNITS) ….…………………..…….
REFRIGERATED REAR STORAGE AREAS (NOT ON ALL MODELS) …………………………………
OPTIONAL REAR ‘PUSH-UP’ WORK COUNTER …………………………………………………..……..
ADJUSTABLE SCALE STAND (GLDSS10R.5255) / REAR OUTLETS (GLDSS443R.5951) …………
START-UP AND OPERATION …...…...…..…………………………...………….……...….……………...
MAINTENANCE FUNDAMENTALS …………………………………………..……………………...……...
HONEYCOMB AIR DIFFUSERS (SERVICE TECHNICIANS ONLY) …………………………………….
START-UP & OPERATION - THERMO-SIMPLE 2 (TS.2) DIGITAL THERMOMETER ALARM ……...
SERIAL LABEL INFORMATION & LOCATION ..……...…………………..…………………..…….….…..
CLEANING SCHEDULE (TO BE PERFORMED BY STORE PERSONNEL) ………...…..……...….....
CLEANING SCHEDULE: STAINLESS STEEL (TO BE PERFORMED BY STORE PERSONNEL) ….
BUTCHER BLOCK CLEANING INSTRUCTIONS (TO BE PERFORMED BY STORE PERSONNEL)
CAESARSTONE® SOLID SURFACE (TO BE PERFORMED BY STORE PERSONNEL) …………...
PREVENTIVE MAINTENANCE (TO BE PERFORMED BY TRAINED SERVICE PROVIDER) …..…..
TROUBLESHOOTING (TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY) …….....
TROUBLESHOOTING (BY TRAINED SERVICE PROVIDERS ONLY) - CONDENSING SYSTEM ….
TROUBLESHOOTING (BY TRAINED SERVICE PROVIDERS ONLY) - EVAPORATOR SYSTEM ....
CAREL® CONTROLLER - PROGRAMMING THE INSTRUMENT…...………………………….……....
CAREL® CONTROLLER - USER INTERFACE, SUMMARY TABLES OF ALARMS & SIGNALS ..….
CAREL® CONTROLLER - Summary Table of Operating Parameters (After Programming Key) ...…..
TECHNICAL SERVICE CONTACT INFORMATION & WARRANTY INFORMATION …….…..............
2
3-4
5
6
7
8
9
10
11
12
13-18
19-20
21-22
23
24
25
26
27
28-29
30-32
33
34
35
36
37
38
This Operating Manual is Applicable To The Following G-Series
you MUST use a GFCI breaker in lieu of a GFCI receptacle.
CAUTION
Performance issues caused by adverse conditions are NOT cov ered by
warranty.
End panels must be tightly joined or kept at least 6-inches
structure to prevent condensation.
Unit must be kept at least 15-feet
or any air curtain disruption to maintain proper temperatures.
Unit must not be exposed to direct sunlight or any heat source (ovens,
fryers, etc.).
Tile floors, low ceilings or small rooms will increase noise level. Whisper Cool
compressor blanket or remote unit may resolve noise level issues.
Keep at least 8-inch
units only).
CAUTION! ADVERSE CONDITIONS / SPACING ISSUES
WIRING DIAGRAM
Each case has its own wiring diagram folded and in its
own packet.
Wiring diagram placement may vary; it may be placed
near ballast box, field wiring box, raceway cover, or
other related location.
away from any
from exterior doors, overhead HVAC vents
clearance above unit for air discharge (self-contained
CAUTION! POWER CORD AND PLUG MAINTENANCE
Risk of electric shock. If cord or plug becomes damaged,
replace only with cord and plug of same type.
WIRING DIAGRAM FORMAT & LOCATION
Each case has its own wiring diagram folded and in its own packet.
Wiring diagram placement may vary; it may be placed near ballast box, field
wiring box, raceway cover, or other related location.
CAUTION! CHECK CONDENSATE PAN POSITION & PLUG
Water on flooring can cause extensive damage!
Before powering up unit, check and confirm the following:
Condensate pan must be DIRECTLY UNDER condensate drain.
Condensate pan plug must be securely plugged into receptacle.
Overflow pan must have plug connected to its box. Units with
optional Clean Sweep™ MUST HAVE 2 plugs connected.
4
REMOVAL FROM SKID
CASE REMOVAL FROM SKID (CASTERS, LEVELERS OR FRAME SUPPORT RAILS)
1. Removing Case Shipping Brackets That Are Attached To Skid
Remove screws holding Case Shipping Brackets to skid.
Remove Case Shipping Brackets from Skid.
See illustrations below.
Note: Shipping Brackets will vary in size, shape, material and
Note: Units shown may
not depict an exact
representation of your
particular unit being installed.
location depending upon case type and model.
Various Types Of
Case Shipping
Brackets
2. Remove Case (With Levelers or Frame Support
Rails) From Skid
To prevent damage, support case while sliding it
toward edge of skid.
When case is at edge of skid, carefully lower to
floor so that two levelers (or one frame support
rail) rests on floor.
Carefully slide skid out from under case.
After case is off skid, place into position.
Note: Illustration below reflects general outline of
sample case and does not reflect any particular
model or options).
Support
case
while
Carefully
Slide Skid
Out From
Under Case
removing
from skid
3. Remove Case (With Casters) From Skid
A. Place ramp up against skid (to allow case to
smoothly slide off from skid).
B. Maintain support of case at all times or center
of gravity may cause case to fall.
C. Unlock Casters. Slide unit to rear of skid. Slide
down ramp and off from skid.
Note: Illustrations reflect general outline of
sample case and may not reflect your particular
model or options).
Support
case
while
sliding
down
ramp.
Ramp
5
5
INSTALLATION: POSITIONING / ALIGNING / FRAME SUPPORT RAILS / LEVELERS
Note: Units shown may not depict an exact representation of your particular unit being installed.
1. Position & Align Case Alongside Other Cases
Before adjusting levelers (or shimming frame
support rails), make certain that the case is in
proper position and, if required, aligned with
adjoining case.
This may require the repositioning of the case
you are installing or
case.
2. Cases With Frame Support Rails: Shim
Illustration at top right shows case with frame
the already positioned
support rails.
Shims will be provided with all cases that have
frame support rails.
Use shims to level case.
Note: After case is in position, it must be
sealed to floor to prevent entry or leakage
of liquid or moisture.
3. Cases With Levelers: Adjust Levelers
After case is in position, adjust case so it is level
and plumb (see illustration at right).
You may need to remove front and/or rear
Frame Support
Rails
Toe-Kick to access levelers.
Use adjustable wrench (and possibly a pry bar)
to adjust leveler.
Do not use Pry Bar on Toe-Kick as it may
buckle.
Do not use Pry Bar on End Panel as it may
chip.
Use Pry Bar ONLY on Base Frame to avoid
Adjustable
Wrench
damaging case.
See illustration and photos below and at lower
right.
6
Pry Bar
Leveler
Base
Frame
Toe-Kick
INSTALLATION, CONTINUED: BOLTING & CAULKING UNITS
4. Bolting & Caulking Units Together
Note: Unit shown may not depict an exact
representation of your particular unit being installed.
Follow these steps to assure a secure, level lineup.
A. Begin all lineups leveling from highest point of
floor.
B. After the ’first’ case is level, apply industrial
grade butyl caulk on non-visible areas (at case
end). Use industrial grade silicone sealant on
visible areas (at case end).
C. Form Two (2) Caulk/Sealant Lines
: (Sanitation
and Refrigeration). See illustration below for
outline of caulk/sealant lines.
D. Line up ‘second’ case bolt-hole to bolt-hole to
‘first’ case.
Approximate hole
locations pointed
at with arrows
( ) for bolting
units together.
Sanitation Bead
E. Using SCC-supplied bolts (found in packet),
insert bolts in bolt hole locations (shown below).
You may need to remove decking to access lower
bolt holes.
F. Caution!
Front of cases MUST be flush with each
other! After leveling, all cases to be same height.
G. Using SCC-supplied nuts & bolts, lightly tighten
each of the 5 to 8 bolts in a cross-wise pattern.
Work your way around the pattern, tightening
more firmly at each pass. Do not
firmly tighten
one bolt and then start on the next!
H. After the cases are bolted together, level the
‘second’ case. Repeat this process for each
case to be adjoined.
I. After all lined-up cases are level, seal all seams
with industrial grade silicone sealant.
Refrigeration Bead
Note: Illustration shown
may not exactly reflect
every feature or option of
your particular case.
Refrigeration
Bead
Sanitation
Bead
Deck
Refrigeration
Bead
7
ELECTRICAL CONNECTIONS (SELF-CONTAINED vs. REMOTE UNITS)
1. Electrical Connections
(Self-Contained Units)
Field wiring hook-up/electrical access
locations are shown in illustrations below
(may not exactly reflect your particular unit).
Single phase leads are provided.
See Technical Information Sheet for
more information.
2. Electrical Connections (Remote
Units)
Field wiring hook-up / electrical
access locations are shown in
illustrations below (may not reflect
your particular unit).
Single phase leads are provided.
See Technical Information Sheet
for more information.
Note: Illustration at right may not
exactly reflect your particular unit.
Note: Rear of case is shown with
rear grille lifted up and off.
Field Wiring Hookup (for
Self-Contained Cases)
Note: Illustration shown
may not exactly reflect
every feature or option of
your particular case.
Electrical Box
Location
(Remote Units)
8
REFRIGERATED REAR STORAGE AREAS (NOT ON ALL MODELS)
Refrigerated Rear Storage Areas (Not on All Models)
Refrigerated rear storage area illustrations show
transparent doors (or removed doors) for illustrative
purpose only.
Most models have rear refrigerated storage part of