you MUST use a GFCI breaker in lieu of a GFCI receptacle.
WIRING DIAGRAM
Each case has its own wiring diagram folded and in its
own packet.
Wiring diagram placement may vary; it may be placed
near ballast box, field wiring box, raceway cover, or
other related location.
CAUTION
CAUTION! POWER CORD AND PLUG MAINTENANCE
Risk of electric shock. If cord or plug becomes damaged,
replace only with cord and plug of same type.
CAUTION! ADVERSE CONDITIONS / SPACING ISSUES
Performance issues caused by adverse conditions are NOT warranted.
End panels must be tightly joined or kept at least 6-inches away from
any structure to prevent condensation.
Unit must be kept at least 15-feet from exterior doors, overhead HVAC
vents or any air curtain disruption to maintain proper temperatures.
Unit must not be exposed to direct sunlight or any heat source
(ovens, fryers, etc.).
CAUTION! CHECK CONDENSATE PAN POSITION & PLUG
Water on flooring can cause extensive damage!
Before powering up unit, check and confirm the following:
Condensate pan must be DIRECTLY UNDER condensate drain.
Condensate pan plug must be securely plugged into receptacle.
Overflow pan must have plug connected to its box. Units with
optional Clean Sweep™ MUST HAVE 2 plugs connected.
4
Page 5
INSTALLATION: SHIPPING BRACKETS / SKID REMOVAL
1. Removing Case Shipping Brackets That
Are Attached To Skid
Remove screws holding Case Shipping Brackets to
skid.
Remove Case Shipping Brackets from Skid.
See illustrations below. Note: Shipping Brackets
will vary in size, shape, material and location
depending upon case type and model.
Various Types Of
Case Shipping
Brackets
Case
Shipping
Brackets
2. Remove Unit From Skid
Slide unit to rear of skid; tip backward off skid.
Make certain to maintain appropriate support to
prevent Case from tipping over and falling.
Note:
Case can be repositioned with pallet truck when
front lower panel is removed.
Blocking may be necessary to obtain adequate
height.
Unit will have either levelers or casters.
If unit has levelers, see next page for
instructions.
Maintain Appropriate
Support to prevent
Case from tipping
over and falling.
Before adjusting levelers, make certain that the
case is in proper position and, if required, aligned
with adjoining cases.
This may require the repositioning of the case you
are installing or
4. Adjust Levelers
the already positioned cases.
After case is in proper position, adjust case so it is
level and plumb (see illustration at right).
You may need to remove front and/or rear toe-kick
to access levelers.
Use adjustable wrench to adjust leveler.
Depending upon case weight it may be necessary
to use a Pry Bar to accomplish this task.
Do not use Pry Bar on Toe-Kick as it may buckle.
Do not use Pry Bar on End Panel as it may chip.
Use Pry Bar ONLY on Base Frame to avoid dam-
aging case.
See illustration and photos at right.
5. Cases With Casters: Lock and Unlock
To lock casters, press down on lever.
To unlock casters, pull lever up.
See illustration at right.
Pry Bar
d
e
k
c
o
L
Adjustable
Wrench
Leveler
U
o
l
n
d
e
k
c
Base
Frame
Toe-Kick
6
Page 7
START-UP AND OPERATION
Merchandiser Start-Up
Turn main power on. Switch is located at Rear
Lower section of Case, next to light switch.
See illustration at right.
The temperature controller will illuminate.
Coil fans should turn on. From inside of case,
check for discharge air from front baffle, to
confirm that the fans are functioning properly.
When the case is in a start up mode or has been
idle for a long period of time, the unit will require
75 minutes run-time in order to pull-down
temperature.
Turn lights on. All of the lights should come on at
the same time. First time lighting may require a
short warm up period for the bulbs. Slightly dim
or a flickering of new bulbs is normal. If lights do
not turn on, check that all of the light plugs are in.
The lighting is wired in series so all lights must be plugged in or receptacles capped in order
for the case to light.
Be certain that nothing obstructs rear air flow.
Warranty will be voided if malfunction occurs due
to obstructed airflow.
The interior case temperature reaches 2° C / 35°
F to 5° C / 41°F. Note
: The case temperature is
set at the factory, as determined by the case
size. The temperature is controlled by a
thermostat. If a temperature setting change is
required, refer to the instructions for your
particular Temperature Control Programming
operating section of this manual.
Note: Set point should be –7°C 20°F. This will
maintain the product temperature range.
Settings lower than 7°C / 20°F can cause food
items to freeze
.
Note: Rocker
Switch illustrated at
right reflects type of
Light Switch and
On/Off Switch
Temp.
Controller
Light
Switch
Illustration at right
shows Ballast Box
after Rear Grille
Cover is removed.
Discharge Air Duct
ON
OFF
Main Power
Switch
Temp. Controller
Light
Switch
Ballast Box
Rocker Switch
Rear
Grille
Main
Power
Switch
7
Cap
Plug
Receptacle
Page 8
ANTI-THEFT SECURITY GRID
Anti-Theft Grid Installation (Optional Item)
Position Anti-Theft Grid so that the locking rods extend down pointing towards the floor and the forming of
the angled grid is pointing away from the case.
Insert grid extensions into the forward air return lover.
With “U” shackle released from the padlock base, insert the locking “U” of the padlocks through the
stationary locking bracket.
Rotate “U” shackle 90 degrees and pull up through the grid and secure “U” shackle into padlock base.
Note: Illustration below may not reflect exact representation of every Case and/or Anti-Theft Grid.
Locking Brackets
Grid Extensions
Return Grille
8
Page 9
MAINTENANCE AND OPERATION
1. Removing the Rear Doors
Move the rear doors toward the center of the
case.
Individually lift each door up into the upper door
frame track at the top of the case.
Pivot the bottom of the door out.
Slip out of the upper door frame track.
2. Installing the Rear Doors
Doors are not interchangeable, and must be
installed as labeled.
Note: Doors are labeled in the lower corners
to identify their proximity to the interior of the
case (inner or outer door).
The inner door must be installed first in the inner
door track.
Insure that the door pull handle is to the outside
and to the left of the case.
Insert the door into the upper inside track and
lower door onto the inside lower track.
Move inner door to the left.
Install the outer door with the door pull handle to
the right and the chrome door stop to the inside
lower right.
Insert the door into the upper and outer track and
lower door onto the outer lower track.
3. Removing Interior Shelving
Remove the glass or ABS shelving.
Carefully set aside.
Unplug shelf light.
Remove rear shelf support.
Remove brackets.
Use even pressure to slide bracket up.
Pull forward to disengage from support pins.
Glass or ABS Shelves
Light Shelf
Shelf Bracket
Rear Shelf Support
Shelf Bracket Removal
9
Page 10
MAINTENANCE AND OPERATION, CONTINUED
4. Light Fixture
Removal of lamp:
Rotate lamp (1/4 turn) either direction to
disengage (upper or lower) pins/contacts from
lamp mounting sockets.
Remove bulb buy applying even pressure from
the back side at the bulb ends and pulling the
remaining contact from the sockets.
Installation of lamp:
Align pins with slot.
Insert pins into socket by rotating the bulb 1/4
turn to secure either the (upper or lower) pined
contacts into the sockets.
Rotate the remaining bulb contacts (1/4 turn)
into the remaining lamp mounting socket
contacts.
Light Socket
Lamp Pins
Light Fixture
Standard
Fluorescent
Light Fixtures
10
Page 11
MAINTENANCE AND OPERATION, CONTINUED
5. Inserts Application
Place (large) lower step with air duct up with
grill facing to the front of case.
Place (small) top step above lower step
(grille forward) and fully covering the air duct
in the lower step.
Position steps all the way to the back of case
(see illustrations).
6. Honeycomb Air Diffuser Removal
Honeycomb is located in discharge air duct.
From inside the unit’s lower refrigerated
area, locate the two most forward screws
which secure the lower light and discharge
panel.
Remove the two most forward screws and
allow the panel to hang down supported by
the rear screws.
Do not force panel lower.
Using long-nose pliers, pliers, wedge the
instrument between the honeycomb and the
end panel. Be careful to avoid scraping or
marring the case.
Apply pressure to collapse the honeycomb
and pry downward and away from the lower
light & discharge panel.
Pull honeycomb out fully buy grasping with
fingers and pulling downward.
7. Honeycomb Air Diffuser Installation
Insert honeycomb up into honeycomb
retainer first.
Replace the two screws that secure the
leading edge of lower light & discharge
panel.
Air Duct
Grille
Discharge Air Duct
Discharge Air Duct
Lower Step
Top Step
Honeycomb
—— Photo of Honeycomb ——
Remove Two Front Screws
11
Page 12
MAINTENANCE AND OPERATION, CONTINUED
8. Middle Service Area, Ambient / Refrigerated
Rear baffle also serves as a collector of crumbs.
When removing baffle, be careful to avoid tipping baffle to the degree that crumbs fall into case.
To convert middle Service Area from Ambient to Refrigerated, follow these instructions.
Warning, disconnect power before providing
maintenance and service to unit.
Temperature & Defrost Control
The case temperature Set Point is set at the
factory, as determined by the case size and
sensor probe location.
The temperature is controlled by a thermostat.
If a temperature setting change is required,
follow the instructions for your particular
Temperature Controller in the technical
information section of this operating manual.
If service is required to the temperature
control unit, call Structural Concepts
Corporation. This maintenance should be
performed by a certified technician.
Ballast access
Remove screws from rear wireway cover and
slide Ballast Box out to access electrical
connections and ballasts.
Evaporator fans and coil access
Remove lower decking using finger hole to lift
up and pulling out.
Removing fan assembly
Unplug the fan.
Remove screws from around the fan duct.
Light
Switch
Temp.
Controller
Note: Above illustration is of case rear
with Rear Grille removed
Lower Decking
Coil
Main Power
Switch
Ballast
Box
13
Evaporator
Fan
Page 14
REFRIGERATION FUNDAMENTALS
1. Refrigeration: Access, Connections & Removal
Remove Rear Grille by removing the (4) connecting
Screws .
Insure that the flexible drain hose is guided when
removed from the slot of hose support.
Note: During installation insure that the flexible
drain hose is fully reinserted into the slot of hose
support for proper drainage.
Assembly or disassembly and servicing to be
accomplished by licensed refrigeration contractor.
The control module has “quick disconnect” electrical
fittings to the LED face control and to the refrigeration
unit. Insure that cords remain clear of the evaporator
pans heating element.
Warning
! While pulling or pushing unit in or out from under
the case:
Be careful to avoid damaging condensate drain.
Use caution to avoid damage to copper refrigeration
lines and hoses.
Insure that the flexible drain hose is properly positioned
for proper drainage.
Exercise care to prevent condenser unit from dropping.
There are no rollers, levelers or stops preventing
condenser unit from coming entirely free from case
when pulled out.
Removable, Magnetized
Condenser Coil Filter
(Optional). Note
Placed over Rear Grille
: Filter is
Rear Grille
Electric Coil Refrigeration
Package Shown. See Next
Page For Hot Gas Condensate
Refrigeration Package.
14
Page 15
REFRIGERATION FUNDAMENTALS, CONTINUED
2. Refrigeration Package Configuration
Refrigeration package shown below is designed for Model C3Z4867.5884A.
Note: Your particular compressor may have slightly different refrigeration package/layout.
See previous page for electric coil condensate refrigeration package.
Condenser Coil
Fans / Motors
Condenser Coil
Tubing
Compressor
Filter Dryer
Sight Glass
Hot Gas Loop
Evaporator Coils
15
Hot Gas Loop
Evaporator Pan
Electrical Box
[Over Overflow
Condensate Pan]
Page 16
SERIAL LABEL LOCATION & INFORMATION LISTED / TECHNICAL INFO & SERVICE
TROUBLESHOOTING
Serial Label Location & Information Listed / Technical Information & Service
Serial labels are located near the electrical access on your case.
Serial labels contain electrical, temperature & refrigeration information, as well as regulatory
For additional technical information and service, see the TECHNICAL SERVICE page in this
See images below for samples of both refrigerated and non-refrigerated serial labels.
Product is Drying Out.
Water on the Floor.
standards to which the case conforms.
manual for instructions on contacting Structural Concepts’ Technical Service Department.
Excessive Fan Noise.
System is not Operating.
Check the relative humidity in the store.
Check that the drain trap is free of debris.
Check that the drain trap is correctly positioned.Check evaporator pan float for proper operation.The evaporator pan is not heating properly.
Check that the case is aligned, level and plumb.
Check that nothing is obstructing the blade rota-tion.
Check that the fan shroud is properly secured.
S
A
M
P
E
L
L
P
M
A
S
Check that the utility power is on.
Check that the MAIN power switch is on.
Check the circuit breaker box for tripped cir-cuits.
E
O
N
O
L
N
Y
L
Y
LED CPC has No illumination.
LE
P
M
A
S
Fans Not Working.
Case Lights Not Working.
----- Sample Serial Label For Refrigerated Case -----
Check connections on power supply contactor
N
O
board.
Check fuse on power supply contactor board.
S
Check that the power is on.
Check that fans are plugged in at the fan shroud.
Faulty motor.
Check that ALL of the lights are plugged in or
receptacles capped.
Check bulbs for proper installation and connec-tion.
Check for burned out bulbs.
Clean dirt and dust from the bulbs to prevent flickering.
Faulty ballast.
L
A
Y
M
S
SA
P
A
L
M
M
PL
E
P
O
L
E ON
E
N
O
L
N
Y
L
L
Y
Y
----- Sample Serial Label For Non-Refrigerated Case -----
16
16
Page 17
CLEANING SCHEDULE - BY STORE PERSONNEL: DAILY “D” / WEEKLY “W” / MONTHLY “M”
Cleaning D W M Task
Clean Case Exterior X
X Clean wood, laminate and painted surfaces with a warm soap and
X Removable, magnetized condenser coil filter (attached to outside
X Remove rear doors and clean with a household or commercial
Clean Case Interior X
X Remove the deck and clean with soap and water solution and soft
Clean side glass, front glass, top glass and sliding rear doors
(glass) with household or commercial glass cleaner and soft cloth.
water solution and soft cloth. Never use wire cloth or abrasive
cleaners on case.
of condenser coil):
Always clean air filter AT LEAST weekly.
Remove from case. Submerse in warm, soapy water. Use
soft-bristled brush to remove dust, grease and grime that can
collect on filter. Rinse thoroughly. After filter has dried, return
to case.
See REFRIGERATION FUNDAMENTALS section in this
manual for illustration of magnetized condenser coil filter and
its attachment location to grille.
glass cleaner. Wipe down door tracks with a warm soap and
water solution and soft cloth.
The deck can be wiped down with a warm soap and water solution
and soft cloth.
cloth.
X Clean the acrylic air deflector (at case front) with soap and water
solution and soft cloth. Never use ammonia-based cleaners on
acrylic or Plexi-glas.
X To clean crumbs and residue from upper section, remove baffle
from case, brush out crumbs or residue. Wipe down with clean
rag dipped in mild soap and water solution.
X Lower Section Only: Remove step assembly from unit and clean
with mild soap and warm water solution and brush. Dry thoroughly
and return to case. Caution
! Remove (and return) step assembly
carefully to avoid scratching or marring inside of case.
X Condenser unit coils at case rear: Remove rear panel (by sliding
up and away from case). Use an industrial strength vacuum with
brush. Clean dust collecting on the condenser coils. Caution
! Do
not damage fins on condenser coil while cleaning.
X Under-case cleaning: Remove front and/or rear toe-kick. Use
vacuum with hose attachment to clean under case.
17
Page 18
PREVENTIVE MAINTENANCE [TO BE PERFORMED BY TRAINED SERVICE PROVIDER] - Page 1 of 3
PREVENTIVE
MAINTENANCE
Case Exterior Monthly Condensing Coil:
Quarterly Optional Clean Sweep™ Condensing Coil: Disconnect power from
FREQUENCY INSTRUCTIONS
Remove rear grille (by removing 4 screws).
Use air pressure or industrial strength vacuum; clean dust and dirt
that may collect on the Condenser Coil. See illustration below.
Caution! Coil fins are sharp. Handle with care!
Replace Rear Grille to case (4 screws).
See illustration below.
case before cleaning Clean Sweep™ Condenser Coil!
Remove Rear Grille (by removing 4 screws).
Slide/Roll out condensing unit assembly.
Remove the four (4) screws holding the Clean Sweep™ rails intact.
Remove the Clean Sweep™ rail.
Wash rails’ brushes in hot water and mild soap solution.
If brushes are worn, they must be replaced. Call Technical Service
Department to replace. Toll-Free number is listed at end of manual.
Clean Condensing Coil: Use air pressure or industrial strength
vacuum; clean the dust and dirt that may collect on the Condenser
Coil.
Caution! Coil fins are sharp. Handle with care!
Reattach Clean Sweep rail to condensing unit (4 screws).
Slide/Roll Condensing Unit Assembly back under case.
Replace Rear Grille to case (4 screws).
See photos below.
ng
i
s
n
de
n
o
C
(4) Screws
--- Above photos are taken after rear grille has been removed from case ---
18
l
oi
C
Brushes
Rail
Page 19
PREVENTIVE MAINTENANCE [TO BE PERFORMED BY TRAINED SERVICE PROVIDER] - Page 2 of 3
WARNING! TURN OFF CASE BEFORE PERFORMING PREVENTIVE MAINTENANCE!
PREVENTIVE
FREQUENCY INSTRUCTIONS
MAINTENANCE
Case Exterior Quarterly Condensate Package: Disconnect power from case before cleaning
Condenser Coil!
Slide/Roll out from under case.
Use moist cloth to wipe off dust & debris that collects on various
parts.
Quarterly
Under Case Cleaning: Once refrigeration package is clear of unit,
vacuum under case to remove all dust and dirt that may collect under
case.
Case Interior Quarterly Drain, Coil, Fan Blades, Motors, Brackets:
Disconnect power from the case before cleaning the Drain, Coil, Fan
Blades, Motors and Brackets!
Remove Decking, Sub-Deck and Fan Shroud.
Use vacuum to clean Evaporator Coils.
Clean Tub, Coil and Drain with warm water, clean cloth, brush
and mild soap solution.
See below for specific tub flushing instructions.
Remove any debris that may clog drain.
Clean Fan Blades, Motors and Brackets by wiping down with
moist cloth.
Quarterly Tub:
Disconnect power from the case before cleaning the tub!
Vacuum tub under deck or flush with water if necessary. To flush out
the tub, disconnect power to the case. Remove the deck and fan
shroud. Direct drain to floor drain or a bucket and hose out the tub.
Run hose into the drain to flush out debris.
Quarterly
Honeycomb: Remove the honeycomb. Vacuum, then clean with
warm water and soap. See instructions in case operation section of
this manual. See PREVENTIVE MAINTENANCE [TO BE
PERFORMED BY TRAINED SERVICE PROVIDER] - Page 3 of 3
in this manual for specifics.
19
Page 20
PREVENTIVE MAINTENANCE [TO BE PERFORMED BY TRAINED SERVICE PROVIDER] - Page 3 of 3
Preventive maintenance should be performed every
30 days unless conditions warrant a more frequent
replacement cycle.
1. Honeycomb Air Diffuser Removal
A. Wedge non-metallic device of suitable strength (such
as a ballpoint pen) between honeycomb and end panel.
Caution
prevent condensation).
B. Apply pressure to collapse the honeycomb to allow it to
be pulled out of honeycomb retainer.
C. Pry downward and away from honeycomb retainer.
Clean honeycomb with warm water and soap solution.
Submerse if necessary. Use brush to dislodge stubborn
or sticky residue. Dry by using vacuum’s ‘blow mode’.
2. Honeycomb Air Diffuser Installation
D. Squeeze honeycomb into the honeycomb retainer.
E. Carefully slide honeycomb into place.
F. Adjust honeycomb so that it fits flat
It must not be wavy or out of position.
Note: For honeycomb air diffusers in other locations, these
same general instructions apply.
3. Air Duct - Upper Section (Top-Right Illustration)
Depending upon model, Upper Section Air Duct may be
If Upper Section Air Duct is not removable from case,
Clean with brush or vacuum with brush attachment.
Wipe down with moist cloth.
! Do not dislodge the heating wire (that helps
against retainer.
removable for cleaning. If so, simply lift Air Duct up and
out of chamber to access area to clean.
Honeycomb removal will allow access to area.
Discharge Air Duct
Honeycomb
Remove Two Front Screws
A
B
F
D
C
E
20
Page 21
TROUBLESHOOTING [GENERAL OVERVIEW]
Product is Drying Out
Doors/Glass Won’t Shut
Properly
Case Not Properly Lining
Up
System is not Operating
Condensing Unit Not
Operating.
Case Lights Not Working
TSP*: Check the relative humidity in the store.
TSP*: Confirm that the case is aligned, level and plumb. Check that residue
or sticky substances are not preventing proper closure.
TSP*: See Installation section of Manual for instructions on properly aligning
case and adjusting levelers (alongside other cases).
Confirm that the utility power is on.
Confirm that the MAIN power switch is on.
TSP*: Check the circuit breaker box for tripped circuits.
If cord is used, confirm that unit is properly plugged in.
Controller is in defrost mode (not an alarm). Compressor is running in a
normal condition. See the Temperature Controller section of this Manual.
Check that the power is turned on.
TSP*: Review factory time settings on the Temperature Controller.
Be sure ALL lights are plugged in or receptacles capped.
Check bulbs for proper installation and connection.
Check for burned out bulbs.
Fans Not Working
Not Holding Temperature
Clean dirt and dust from the bulbs to prevent flickering.
After performing all other checkpoints, if lights are still not working check for
faulty ballasts; this should be performed by a certified electrician.
TSP*: Check that fans are plugged in at the fan shroud.
TSP*: Check for foreign material obstructing fan performance.
The temperature will change during defrost mode but will return to normal.
Warm product may have been added to the case. Note: Product must be
pre-chilled to 41 °F [5 °C] or less prior to being placed in merchandiser.
Discharge air must not be disrupted or blocked by product.
TSP*: Check that the coil fans are working.
TSP*: Check the evaporator coil for ice build up.
Check that the case is not in the sun or near a heat or air-conditioning vent.
Check that case is NOT located near outside doors. Wide temperature
fluctuation can challenge case’s ability to hold internal product temperatures.
Check that the condenser coil is clean (self contained unit).
See pages that follow for troubleshooting instructions.
Refrigeration unit pulls out from back of unit for service.
Only refrigeration contractors are to access refrigeration package.
NOTE: THE BELOW
ILLUSTRATION MAY
NOT EXACTLY REFLECT
YOUR PARTICULAR
CASE’S FEATURES OR
OPTIONS.
Condenser Coil
Fans & Blades
Condenser
Coil Cover
Electric Coil
Overflow Pan
& Electrical
Box
Compressor
and Start
Components
Filter
Dryer
Sight Glass
22
Compressor Electrical
Box (Containing
Start Relay)
Condenser
Pan
Page 23
Read And Save These Instructions - Page 1 of 3
Integrated Electronic
Microprocessor Controller
Programming The Instrument
How To Modify The Setpoint
Press and hold the “SET” key for at least 1 second.
Set
Prg
mute
Set
▲
aux
def
▼
How To Modify The Defrost, Differential
Or Other Parameters
Prg
mute
Set
▲
aux
Set
▲
aux
Set
Prg
mute
1. Press & hold “Prg” and “SET” keys together
Set
for at least 5 seconds; the display will show the
number “0”, representing the password prompt.
2. Confirm by pressing “SET” key.
3. Press ▲ or ▼ to reach the
def
category to be modified.
▼
4. Press “SET” to modify this selected parameter.
5. Increase or decrease the value using
def
the ▲ or ▼ button respectively.
▼
6. Press the “SET” key to temporarily save the new
value and return to the display of the parameter.
7. Press & hold the “Prg” key for at least 5 seconds
to save changes. This action will also mute the
audible alarm (buzzer) & deactivate the alarm relay.
Prg
mute
Set
▲
aux
Set
▲
aux
Set
Prg
mute
Warning! Save Your Parameter Settings!
1. To store the new parameter values, PRESS and HOLD the “Prg” key for at least 5 seconds.
2. All modifications made to parameters will be lost if you do NOT press a button within 60 seconds. Should
this “timeout” occur, normal operational settings (prior to modifications being made) will resume.
3. If the instrument is switched off before pressing the “Prg” key, all modifications to parameters will be lost.
How To Activate Manual Defrost
def
Press and hold the “def” key for at least 5 seconds.
▼
How To Activate / Deactivate Auxiliary Output
▲
Press and hold the “aux” key for at least 1 second.
aux
How To Change Reading From
Fahrenheit (°F) To Celcius (°C)
1. Press and hold “Prg” and “SET” keys
Set
together for at least 5 seconds; display will
2. Confirm by pressing “SET” key.
4. Press “SET” to modify this selected parameter.
show “0”, representing password prompt.
def
3. Press ▲ or ▼ until reaching the
parameter “/ 5”.
▼
5. Press ▲ or ▼ to change value to desired
def
setting: “0” for Celcius (°C) or “1” for
▼
Fahrenheit (°F).
6. Press “SET” key to temporarily save the new
value and return to the display of the parameter.
7. Press & hold “Prg” key for at least 5 seconds to
save changes.
convert to new scale. No conversion is required.
Note! All values will automatically
How To Reset Any Alarms With Manual Reset
Prg
mute
▲
Press and hold the “Prg” and “aux” key for at least 1 second.
aux
Structural Concepts Corp., 888 E. Porter Rd · Muskegon, MI 49441
Ph: 231.798.8888 / Fax: 231-798-0393 / www.structuralconcepts.com
All sales by Structural Concepts Corporation (SCC) are subject to the following limited warranty. “Goods” refers to the product or products being sold by SCC.
Warranty Scope: Warranty is for equipment sold in the United States, Canada, Mexico and Puerto Rico. Equipment sold elsewhere may carry modified warranty.
Warranty; Remedies; Limitations. SCC warrants that if any Goods are found by an authorized representative of SCC not to be of good material or workmanship within one
year of the date of shipments SCC will, at its option after inspection by an authorized representative, replace any defective Good or pay the reasonable cost of replacement for
any such defective Goods, provided that written notice of the defect is given to SCC within 30 days of the appearance of such defect. If notice is not given within such period, any
claim for breach of warranty shall be conclusively deemed to have been waived and SCC shall not be liable under this warranty. If SCC is unable to repair or replace the defective
Goods, SCC shall issue a credit to the Purchaser for all or part of the purchase price, as SCC shall determine. The replacement or payment in the manner described above shall
be the sole and exclusive remedy of Purchaser for a breach of this warranty. If any Goods are defective or fail to conform to this warranty, SCC will furnish instructions for their
disposition. No Goods shall be returned to SCC without its prior consent.
SCC’s liability for any defect in the Goods shall not exceed the purchase price of the Goods. SCC SHALL HAVE NO LIABILITY TO PURCHASE FOR CONSEQUENTIAL
DAMAGES OF ANY KIND WHATSOEVER, INCLUDING, BUT NOT LIMITED TO, PERSONAL INJURY, PROPERTY DAMAGE, LOST PROFITS, OR OTHER ECONOMIC
INJURY DUE TO ANY DEFECT IN THE GOODS OR ANY BREACH OF SCC, SCC SHALL NOT BE LIABLE TO THE PURCHASER IN TORT FOR ANY NEGLIGENT DESIGN
OR MANUFACTURE OF THE GOODS, OR FOR THE OMISSION OF ANY WARNING THEREFROM.
SCC shall have no obligation or liability under this warranty for claims arising from any other party’s (including Purchaser’s) negligence or misuse of the Goods or environmental
conditions. This warranty does not apply to any claim or damage arising for or cause by improper storage, handling, installation, maintenance, or from fire, flood, accidents,
structural defects, building settlement or movement, acts of God, or other causes beyond SCC’s control.
Except as expressly stated herein, SCC makes no warranty, express, implied, statutory or otherwise as to any parts or goods not manufactured by SCC. SCC shall warrant such
parts or Goods only (I) against such defects, (II) for such periods of time, and (III) with such remedies, as are expressly warranted by the manufacturer of such parts of Goods.
Notwithstanding the foregoing, any warranty with respect to such parts of Goods and any remedies available as a result of a breach thereof shall be subject to all of the
procedures, limitations, and exclusions set forth herein.
THE WARRANTIES HEREIN ARE IN LIEU OF ALL WARRANTIES, EXPRESS, IMPLIED, STATUTORY, OR OTHERWISE. IN PARTICULAR, SCC MAKES NO WARRANTY
OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
No representative, agent or dealer of SCC has authority to modify, expand, or ext end this Warranty, to waive any of the limitations or exclusions, or to make any different or
additional warranties with respect to Goods.
Period of Limitations. No claim, suit or other proceeding may be brought by Purchaser for any breach of the foregoing warranty or this Agreement by SCC or in any way arising
out of this Agreement or relating to the Goods after one year from the date of the breach. In the interpretation of this limitation on action for a breach by SCC, it is expressly
agreed that there are no warranties of future performance of the goods that would extend that period of limitation herein contained for bringing an action.
Indemnifications. Purchaser agrees to indemnify, hold harmless, and defend SCC if so requested, from any and all liabilities, as defined herein, suffered, or incurred by SCC as
a result of, or in connection with, any act, omission, or use of the Goods by Purchaser, its employees or customers, or any breach of this Agreement by Purchaser. Liabilities
shall include all costs, claims, damages, judgments, and expenses (including reasonable attorney fees and costs).
Remedies of SCC. SCC’s rights and remedies shall be cumulative and may be exercised from time to time. In a proceeding or action relating to the breach of this Agreement by
Purchaser, Purchaser shall reimburse SCC for reasonable costs and attorney’s fees incurred by SCC. No waiver by SCC of any breach of Purchaser shall be effective unless in
writing nor operate as a waiver of any other breach of the same term thereafter. SCC shall not lose any right because it has not exercised it in the past.
Applicable Law. This Agreement is made in Michigan and shall be governed by and interpreted according to Michigan law. Any lawsuit arising out of this Agreement or the Goods
may be handled by a federal or state court whose district includes Muskegon County, Michigan, and Purchaser consents that such court shall have personal jurisdiction over
Purchaser.
Miscellaneous. If any provision of this Agreement is found to be invalid or unenforceable under any law, the provision shall be ineffective to that extent and for the duration of
the illegality, but the remaining provisions shall be unaffected. Purchaser shall not assign any of its rights nor delegate any of this obligations under this Agreement without prior
written of SCC. This Agreement shall be binding upon and inure to the benefit of SCC and Purchaser and each of their legal representatives, successors and assigns.
SCC warrants its products to be free of defects in materials and workmanship under normal use and service for a period of one (1) year from the date of delivery.
This warranty is extended only to the original purchaser for use of the Goods. It does not cover normal wear parts such as plastic tongs, tong holders, tong cables, bag holders,
or acrylic dividers.
General Conditions. All service labor and/or parts charges are subject to approval by SCC. Contact the Customer Service Department in writing or call 231-798-8888.
All claims must contain the following information: (1) model & serial code number of equipment; (2) the date and place of installation; (3) the name and address of the agency
which performed the installation; (4) the date of the equipment failure; and (5) a complete description of the equipment failure and all circumstances relating to that failure.
Once the claim has been determined to be a true warranty claim by SCC’s Customer Service Department, the following procedure will be taken: (1) replacement parts will be sent
at no charge from SCC on a freight prepaid basis; (2) reimbursement for service labor will be paid if the following conditions have been met - (a) prior approval of service agency
was awarded from the Customer Service Department; and (b) an itemized statement of all labor charges incurred is received by th e Customer Service Department. The cost of
the service labor reimbursement will be based on straight time rates and reasonable time for the repair of the defect.
If problems occur with any compressor, notify SCC’s Customer Service Department immediately. Any attempt to repair or alter the unit without prior consent from the Customer
Service Department will render any warranty claim null and void. This warranty and protection plan does not apply to any condensing unit or any part thereof which has been
subject to accident, negligence, misuse, or abuse, or which has not been operated in accordance with the manufacturer’s recommendations or if the serial number of the unit has
been altered, defaced, or removed.
Limit of Liability. The limit of liability of SCC toward the exchange cost of the original condensing unit, F.O.B. SCC, Norton Shores, MI, of each motor-compressor assembly
replaced during the warranty shall not exceed manufacturer's current established wholesaler’s exchange price and in no case shall the labor of removing or replacing the
motor-compressor or parts thereof be the responsibility of SCC.
26
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.