Stovax Logic Hotbox Convector Fire User Manual

Logic Hotbox & Convector Fire
With upgradable control valve
Instructions for Use,
Installation and Servicing
For use in GB, IE (Great Britain and Eire)
PR0696 Issue 2 (October 2003)
IMPORTANT
A suitable guard should be used for the protection of young children, the elderly or infirm.
This appliance is intended for decorative purposes only.
Please read these instructions carefully and keep them in a safe place.
They will be needed when servicing the fire.
The commissioning sheet on page 3 MUST be completed by the Installer.
This appliance has been certified for use in countries other than those stated. To install this appliance in these countries, it is essential to obtain the translat-
ed instructions and in some cases the appliance will require modification. Contact Gazco for further information.
2
CONTENTS
PAGE
APPLIANCE COMMISSIONING CHECKLIST 3
USER INSTRUCTIONS 4
INSTALLATION INSTRUCTIONS 8
Technical Specifications 8
Site Requirements 10
Installation 11
Commisioning 17
SERVICING INSTRUCTIONS 18
Servicing Requirements 18
Fault Finding 19
How to replace parts 21
Basic spare parts list 23
Covering the following models
Hotbox Convector
8306PBUC 8308PBUC
P80306PBUC P8308PBUC
8306MCUC 8308MCUC
P8306MCUC P8308MCUC
3
FLUE CHECK PASS FAIL
1. Flue is correct for appliance
2. Flue flow test
3. Spillage test
GAS CHECK
1. Gas soundness & let by test
2. Standing pressure test mb
3. Appliance working pressure (on High Setting) mb
NB All other gas appliances must be operating on full
4. Gas rate m3/h
5. Does ventilation meet appliance requirements
6. Have controls been upgraded (Upgradeable models only) 8455 Standard YES NO
APPLIANCE COMMISSIONING CHECKLIST
Dealer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contact No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Date of Purchase. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Model No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Serial No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Company. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Engineer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contact No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Corgi Reg No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Date of Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IMPORTANT NOTICE
Explain the operation of the appliance to the end user, hand the completed instructions to them for safe keeping,
as the information will be required when making any guaranteed claims.
DEALER AND INSTALLER INFORMATION
1. GENERAL
2. LIGHTING THE FIRE
3. TURNING THE FIRE OFF
4. LIGHTING THE FIRE WITH A MATCH
5. UPGRADING YOUR FIRE
USER INSTRUCTIONS
2
1
4
1.1 Installation and servicing must only be carried out by a competent person.
1.2 In all correspondence, please quote the appliance type and serial number, which can be found on the databadge adjacent to the control knob.
1.3 Ensure that curtains are not positioned above the fire, and that there is a 300mm minimum clearance between the sides of the fire and any curtains.
1.4 This product is guaranteed for 12 months from the date of installation, as set out in the terms and conditions of sale between Gazco and your local Gazco dealer. Please consult with your local Gazco dealer if you have any questions. In all correspondence always quote the Model Number and Serial Number.
1.5 Parts of this appliance become hot during normal use. It is therefore recommended that a suitable fire guard be used for protection of young children and the infirm.
2.1 Locate the control valve on the appliance. There are two
control knobs on the valve, the right hand knob controls the pilot ignition and the left hand knob controls the main burner.
2.2 If your appliance has already been upgraded to battery remote control, please refer to the instructions provided with the upgrade to operate the remote control. The following instructions will work for either situation.
2.3 Ensure that the left-hand control knob is pointing to off ( ).
2.4 Ensure that the right hand control knob is pointing to off ( ).
2.5 Press in the right hand control knob and rotate it anti-clockwise
until a click is heard (keep pressing in) and the knob is pointing to pilot ( ). The pilot should now light. If the pilot has not lit, repeat the procedure until it does.
2.6 Keep the control knob pressed for 10 seconds and then
release it, the pilot should stay alight. If the pilot goes out, repeat the procedures until it does.
2.7 If the pilot will not light after repeated attempts, contact the
retailer or installer from whom the appliance was purchased.
2.8 Turn the right hand control to point to main burner ( ). The appliance can now be controlled using the left hand control knob.
2.9 Turn the left hand control knob to point to low fire ( ), the main burner will light on low. The burner can now be controlled between low and high settings. Turn the control
knob anticlockwise increase the flame height and clockwise to decrease the flame height.
THE YELLOW FLAMES WILL APPEAR WHEN THE FIRE HAS GAINED SUFFICIENT HEAT - TYPICALLY 10 TO 20 MINUTES.
3.1 To turn the fire off, locate the control valve, turn the left-hand control knob until it points to off ( ). The main burner will go out leaving the pilot burning.
3.2 To turn the pilot off, locate the control valve, turn the right
hand control knob until it points to off ( ), the pilot will go out.
If the pilot does not ignite as described in Section 2, please consult your GAZCO dealer to rectify the problem. However, the appliance may be lit as a temporary measure using the following procedure:
4.1 Press in the right hand control knob and rotate it anti­clockwise until a click is heard (keep pressing in) and the knob is pointing to pilot ( ), apply a lighted match to the pilot hood, see diagram 2.
4.2 When the pilot is alight, extinguish the match and continue
to depress for 5 to 10 seconds.
4.3 The fire may now be controlled as previously described.
5.1 Your fire is fitted with a control valve that can easily be
upgraded to battery powered remote control. This upgrade can be fitted by anyone capable of simple DIY jobs and requires no special training. This upgrade can be obtained through your local Gazco stockist.
5.2 STANDARD REMOTE CONTROL This remote control can
control the fire after the pilot has been lit. It can turn the main burner on and regulate it from low through to high and back again. It can turn the main burner off leaving the pilot burning GAZCO PART NUMBER 8455.
5.3 IMPORTANT - there is a thermostatic version of the upgrade but this is NOT SUITABLE for open flame fires like the Logic.
6. CLEANING THE FIRE
USER INSTRUCTIONS
5
7. ARRANGEMENT OF FUEL BED COMPONENTS
6.1 Remove the ceramic coals or pebblesand place on a dry, clean surface. Remove the fuelbed and the burner cover gasket.
6.2 Clean the burner and tray assembly using a vacuum cleaner with soft brush attachment, ensure all debris is removed from the burner ports.
6.3 Replace the ceramics by referring to section 7.
NOTE: CERAMIC PARTS ARE FRAGILE. THE SIDE AND REAR PANELS ARE REVERSIBLE. ONE SIDE IS PLAIN, THE OTHER SIDE IS REEDED. ASK THE CUSTOMER WHICH SIDE IS PREFERRED AT THIS STAGE.
ONLY USE THE CORRECT TYPE AND QUANTITY OF CERAMIC COMPONENTS. POINTS 7.1 TO 7.5 ARE COMMON TO ALL FUEL TYPES AND LAYOUTS.
7.1 Position the burner cover gasket on the burner skin ensuring the holes align with the ports. Take care as the front left-hand hole is offset compared to the others. See diagram 3, arrow A.
7.2 Position the flame baffle centrally on the tray and ensure the stepped lower edge engages against the rear edge of the burner skin. See diagram 4.
7.3 Place the rear panel against the rear of the box and slide the side panels on either side of the flame baffle. Ensure they
locate in the brackets at the top of the firebox. DO NOT
SLIDE THEM ALL THE WAY BACK. See diagram 5.
7.4 Locate the top panel on top of the rear and side panels.
Finally push the sides fully towards the rear panel. This will retain the top panel. See diagram 6.
7.5 Place the front coal centrally in the channel at the front of
the tray. See diagram 7. The relationship between the front coal and flame baffle is shown in diagram 7.
3
4
5
6
7
USER INSTRUCTIONS
COAL LAYOUT
NOTE: THERE ARE TWO LARGE COALS IN A BAG INSIDE THE MAIN BAG. THESE ARE ONLY TO BE USED WHEN A CURVED FRONT SUCH AS THE HOLYROOD AND RICHMOND ARE USED. DO NOT USE THE TWO LARGE COALS WHEN USING A FLAT FRONTED FRAME.
A) FRONT ROW COAL LAYOUT USING FLAT FIRE FRONTS
7.6 The front row is the only difference in coal layout. Place one large coal centrally on the front coal resting against the frame. Then place three small coals either side. See diagram 8.
B) FRONT ROW COAL LAYOUT USING CURVED FIRE FRONTS.
7.7 Place three large coals resting on top of the front coal and
against the front of the frame, then place two small coals either side of the large ones. See diagram 9
C) COAL LAYOUT CONTINUED FROM FRONT ROW
7.7 Place four large coals behind the first row and one small coal either end resting up against the side panels. See diagram 10
7.8 Place one small coal either side on top of the flame baffle in each rear corner. Then place two large coals in between the two small coals. These coals should touch the rear panel. See diagram 11.
7.9 Finally place five large coals between the second and rear row of coals. See diagram 12.
7.10 It is essential that gaps are left between the coals to maximise
the performance of the appliance.
8
9
10
11
12
6
7
PEBBLE LAYOUT - CURVED AND FLAT FRONTS
7.12 ALL THE PEBBLES HAVE AN IDENTIFICATION ON THE UNDERSIDE. ENSURE THE PEBBLES ARE PLACED ONLY IN THEIR CORRECT POSITIONS.
7.13 Place the first row of pebbles on top of the front coal resting against the frame front. All the identifications are placed
face down so they cannot be seen. See diagram 13.
7.14 Working from the outside of the appliance, place the second
row of pebbles against the rear of the first row. Note the orientation of each pebble, as this is important to the
performance of the fire. See diagram 14.
7.15 Place the rear row of pebbles on top of the flame baffle,
these must touch the rear panel. See diagram 15.
7.16 Place the remaining five pebbles between the second and rear rows. See diagram 16.
13
14
15
8.1 The appliance is fitted with an oxygen sensitive pilot system will act to cut off the gas supply to the fire should the
oxygen in the room fall below its normal level. If the fire is turned off by this device, it usually indicates that there is a problem with the flue system, and this should be inspected by a qualified engineer. Do not attempt to use the fire
until an engineer says it is safe to do so.
This device is not a substitute for an independently mounted carbon monoxide detector.
9.1 This is a safety feature incorporated in all GAZCO fires which automatically switches off the gas supply if the pilot
light goes out and fails to heat the thermocouple.
10.1 The surface coating on the coals used in your GAZCO fire
will ‘burn off’ during the first few hours of use, producing a harmless and temporary odour. This will disappear after a short period of use. If the odour persists, ask your installer for advice.
11.1 This fire must be serviced every 12 months by a qualified
Gas Engineer. In all correspondence, always quote the appliance type and serial number, which may be found on the databadge located on a chain beneath the control valve.
12.1 Any purpose provided ventilation should be checked
periodically to ensure that it is free from obstruction.
13.1 To assist in any future correspondence, your installer should
have completed this commissioning sheet, this records, the essential installation details of the appliance. In all correspondence always quote the Model Number and Serial Number.
16
8. OXYGEN DEPLETION SENSOR
9. FLAME FAILURE DEVICE
11. SERVICING
10. ‘RUNNING IN’
12. VENTILATION
13. INSTALLATION DETAILS
USER INSTRUCTIONS
2 2 4 5
AR1173
6 5 4 5 2
AR1174
INSTALLATION INSTRUCTIONS
TECHNICAL SPECIFICATION
Covering the following models
Hotbox Convector
8306PBUC 8308PBUC
P80306PBUC P8308PBUC
8306MCUC 8308MCUC
P8306MCUC P8308MCUC
GAS CATEGORY 1
2h
1
3+
Natural Butane Propane
Gas Type G20 G30 G31
Working Pressure 20 mb 29 mb 37 mb
Gross Input kW High 6.7 6.7 6.7
Low 3.0 3.0 3.0
Gas Rate m3/hr High 0.64 0.192 0.252
Low 0.29 0.086 0.113
Nox Class 1 1
Injector size 400 180
6x5 Rear
Aeration Size 6x15
23x15 Front
Min flue size 5” diameter
Min Flue size - Pre cast 90mm x 183 mm (16,500mm2min)
Min flue specifacation T160 / N2 / 0 /D / 1
Gas Inlet 8mm
Weight (Gross) 19Kg
APPLICABLE FRONTS
FRONT HOTBOX CONVECTOR
DESIGNIO 8251MA 8251MA
EVOLUTION 8255MB, 8255BS 8257MB, 8257BS
HOLYROOD
8391 8397 8150
8391 8397 8150
INFINITI 8249BS 8249BS
PROGRESS 8253BS 8253BS
RICHMOND N/A 8678
SPANISH 8382, 8385
8388, 8153
8382, 8385 8388, 8153
VICTORIAN
CONVECTOR
N/A 4262, 4263
ART NOUVEAU
CONVECTOR
N/A 4264, 4265
COMBINATION
CONVECTOR
N/A 4362, 4363
8
INSTALLATION INSTRUCTIONS
TECHNICAL SPECIFICATION
OVERALL EXTERNAL DIMENSIONS SIDE VIEW
MINIMUM DEBRIS COLLECTION
SPACE REQUIREMENTS-
(EXISTING MASONRY CHIMNEYS ONLY)
OVERALL EXTERNAL DIMENSIONS PLAN VIEW
9
1
2
3
10
INSTALLATION INSTRUCTIONS
SITE REQUIREMENTS
1.1 The chimney or flue system must comply with the rules in force, and must be a minimum of 125mm (5”) in diameter. Pre cast flues must conform to BS1289: 1986. The cross sectional area of the flue must be 16500 mm
2
with a
minimum dimension of 90mm.
*When fitting the appliance to a pre cast flue, the total minimum depth of fire opening necessary is (D) 215mm. This allows a 25mm space behind the appliance for debris, required on this type of flue system. This is achieved either by using = (A) a 115mm deep starter block + (B) a 25mm plasterboard and sealed space + (C) 75mm Gazco space (part number 8315) with a marble slip or similar, inserted behind the spacer front flange, see diagram 1.
Or the total dept can be achieved by using a deeper starter block, remedial building work to the front of the fireplace opening, and a marble slip or similar, or a combination of this.
NEVER PLASTER DIRECT TO THE FACE OF A PRECAST FLUE. USE ADHESIVE TO FIX THE PLASTERBOARD TO THE FACE OF THE FLUE AND FINALLY SKIM THE PLASTERBOARD.
When fitting the Logic Convector fire and a Stovax Cast Iron Convector fireplace to a pre-cast letterbox flue with a standard starter block, the 8315 spacer kit will be required, together with an extra deep 142mm rebate surround.
The Combination Convector breast. Fireplace requires a 75mm stud-work chimney breast.
The appliance can also be fitted into a metal fluebox with a 5” (125mm) diameter flexible liner. In this installation a 1” (25mm) rebated fire surround must be used. Refer to diagram 2 for dimensions.
Class 1 flues. Chimneys over 9” x 9” must be lined.
A flue restrictor is provided with the Logic convector. This must be fitted when the flue is 9” x 9” or when the flue pull is excessive. This is fitted from inside the appliance across the outlet at the top of the convector box with two screws provided.
1.2 The minimum effective height of the flue or chimney must be 3 m (10ft).
1.3 The chimney or flue must be free from any obstruction. Any damper plates should be removed or secured in the fully open position, and no restrictor plates should be fitted.
1.4 The chimney should be swept immediately prior to the installation of the appliance - unless it can be seen to be clean and unobstructed throughout its entire length.
1.5 Ensure that there is a smooth taper transition from the fireplace opening into the chimney or flue.
1.6 The flue pull should be checked prior to installation of the appliance. Apply a smoke pellet to the flue or chimney opening and ensure that the smoke is drawn into the opening. If there is not a definite flow, pre-heat the chimney for a few minutes and re-test the flow.
IF THERE IS STILL NO DEFINITE FLOW, THE CHIMNEY MAY REQUIRE ATTENTION - SEEK EXPERT ADVICE.
2.1 This appliance must stand on a non-combustible hearth
that is at least 12mm thick and 50mm thick at least at the periphery.
2.2 It must be fitted into a non-combustible opening.
2.3 These appliances must be hearth mounted into a fireplace
opening conforming to National Standards. The minimum dimensions shall be as shown in diagram 2.
1. FLUE AND CHIMNEY REQUIREMENTS
1
A = Minimum precast flue starter block depth (115mm).
B = Plasterboard and adhesive seal all around fire opening.
C = Gazco spacer (8315)
D = Minimum total depth including 25mm for debris.
A
B
C
D
Hearth level
2. APPLIANCE LOCATION
AR1217
11
INSTALLATION INSTRUCTIONS
SITE REQUIREMENTS
2.4 Ensure that no naked flame or incandescent part of the fire bed projects beyond the vertical plane of the fireplace opening.
2.5 The appliance must not be installed in any room that contains a bath or shower.
2.6 Ensure clearances to combustible materials - see diagram 3
3.1 Before installation, ensure that the local distribution
conditions (identifaction of gas and pressure) and the adjustment of the appliance are compatible.
3.2 Ensure that the gas supply is capable of delivering the
required amount of gas, and is in accordance with the rules in force.
3.3 This appliance is supplied complete with a factory fitted
isolation device incorporated into the inlet connection, no further isolation device is therefore required.
It is important to ensure that any national ventilation requirements are taken into account during the installation of this appliance.
4.1 This appliance has a norminal input not exceeding 7.0kw and therefore does not normally require ant additional permanent ventilation.
If, however, spillage is detected when commissioning the appliance, there may be insufficient natural ventilation and additional ventilation may be required.
For ventilation requirements im thr Republic of Ireland, it will be necessary to refer to the relavant rules in force.
AIR VENTS MUST NOT BE RESTRICTED.
3
3. GAS SUPPLY
4. VENTILATION
2
215
12
1.1 Remove the appliance from its packaging, and check that it is complete and undamaged.
1.2 Put the loose ceramic parts to one side so that they are not damaged during installation.
2.1 Your fire is fitted with a control valve that can be easily
upgraded to battery powered remote control. This upgrade can be fitted by anyone capable of simple DIY jobs and requires no special training. This upgrade can be obtained through your local Gazco stockist.
2.2 STANDARD REMOTE CONTROL This remote control can
control the fire after the pilot has been lit. It can turn the main burner on and regulate it from low through to high and back again. It can turn the main burner off leaving the pilot burning. GAZCO PART NUMBER 8455.
2.3 IMPORTANT - there is a thermostatic version of the upgrade
but this is NOT SUITABLE for open flame fires like the Logic.
3.1 This appliance must be installed in accordance with the rules
in force, and used only in a sufficiently ventilated space. Please read all instructions before installation and use of this appliance.
3.2 These instructions must be left intact with the user.
3.3 Do not attempt to burn rubbish on this appliance.
3.4 In your own interest, and those of safety, this appliance must
be installed by a competent person in accordance with local and national codes of practice. Failure to install the appliance correctly could lead to prosecution.
3.5 Keep all plastic bags away from young children.
NATURAL GAS @ 20mbar BUTANE @ 29mbar
PROPANE @ 37mbar
8306MCUC 8306PCUC P8306MCUC P8308MCUC 8308MCUC 8308PBUC P8308MCUC P8308PBUC
TO CHANGE FROM ONE GAS TYPE TO ANOTHER A COMPLETE ENGINE ASSEMBLY WILL BE REQUIRED. SEE SECTION 7 SERVICING INSTRUCTIONS.
4.1 Before installation, ensure that the local distribution conditions (identification of the type of gas and pressure) and the adjustment of the appliance are compatible. See table above.
INSTALLATION INSTRUCTIONS
INSTALLATION
1. UNPACKING
2. CONTROL UPGRADE
3. SAFTEY PRECAUTIONS
4. INSTALLATION OF THE GAS SUPPLY
4.2 Ensure that the gas supply is capable of delivering the required amount of gas, and is in accordance with the rules in force. Please refer to the technical specification for the correct working pressure for the gas used.
4.3 Soft copper tubing and soft soldered joints can be used but must not be closer than 50mm (2”) to the underside of the burner.
4.4 An isolation device is provided with the appliance.
4.5 All supply gas pipes must be purged of any debris that may have entered, prior to connection to the appliance.
5.1 Remove the 6 burner retaining screws and withdraw the
burner unit from its location. See diagram 1, arrows B
5.2 Decide on the retention method. If cable fixings are to be
used, remove the two knockout holes on the rear of the box, using a sharp hammer blow. See diagram 2.
5.3 Remove the backing from the self-adhesive silicone sealing
strip and apply to the rear flange of the firebox ensuring that it is positioned as close to the outer edge as is practically possible. See diagram 3.
5. PREPARING THE APPLIANCE
1
2
13
5.4 Gas pipe entry must come through the right hand side of the box. The rubber seal must be cut using a sharp knife to allow the isolating elbow to pass through it. Ensure the rubber is not damaged when doing this.
A means of isolation is provided with the appliance. This must be fitted to the supply pipe prior to installing the firebox.
6.4 Pass the cables vertically through the 2 sets of eyebolts and thread the ends through the holes in the lower back of the firebox. Pass the gas supply pipe through the hole in the rubber seal (refer to section 5.2) and push the appliance into place.
6.5 Thread the cables through the tensioner bolts and push the threaded portions through the holes in the firebox so that the lock nut sits against the back wall (ensure that the nut is screwed fully up to the head of the tensioner to allow maximum adjustment).
6.6 Slide the locking nipples onto the cables, pull the cables taut and tighten the locking screw. Adjust the lock nuts using a 10mm spanner until the silicone sealing strip forms a tight seal between the fireplace opening and the firebox flange. See diagram 6.
6.7 Coil up the surplus cable and locate in the back of the
firebox.
NEVER SHORTEN THE CABLES, THEY WILL BE REQUIRED WHEN SERVICING THE APPLIANCE.
INSTALLATION INSTRUCTIONS
INSTALLATION
3
6.INSTALLATION OF THE APPLIANCE
6.1 Ensure that the fireplace opening is in compliance with the requirements of section 2 Site Requirements then proceed as follows:
A) CABLE RETENTION METHOD
6.2 Mark the position of the 4 fixing holes on the rear of the fireplace opening and drill the holes using a No. 12 masonry drill bit. Insert the 4 fibre rawlplugs and screw the eyebolts
in as far as possible leaving the eye horizontal. See diagram 4.
6.3 Pass the 2 cables through the holes in the bracket on the back of the firebox and pull taut so that the stop ends sit tightly against the top of the bracket. See diagram 5.
4
5
6
14
B) SCREW FIXING METHOD
6.8 Alternatively, this appliance can be secured back to the fireplace opening using the screws and rawlplugs provided.
Place the firebox centrally in the opening and mark the
positions of the 4 fixing holes. Drill the holes and insert the 4 rawlplugs. See diagram 7.
6.9 Offer the firebox into the opening and ensure that the gas
supply pipe passes through the rubber seal.
6.10 Refit the burner assembly and secure the 6 pozidriv screws. Connect the gas supply to the inlet connection on the burner unit and tighten. It may be necessary to support the inlet connection with another spanner whilst tightening this joint. See diagram 8.
6.11 Turn on the gas supply to the appliance and check for leaks.
Light the fire and check all joints on the appliance for leaks.
6.12 Remove the sealing screw from the inlet connection and
connect a suitable “U” gauge manometer. Light the fire and turn to the maximum position, refer to the databadge and ensure that the running pressure is correct. If the pressure varies significantly from that on the databadge, this may indicate a supply problem and will require immediate attention.
6.13 Turn the appliance off, disconnect the “U” gauge and
replace the sealing screw. Relight the appliance and check the sealing screw for leaks.
INSTALLATION INSTRUCTIONS
INSTALLATION
7
8
NOTE: CERAMIC PARTS ARE FRAGILE. THE SIDE AND REAR PANELS ARE REVERSIBLE. ONE SIDE IS PLAIN, THE OTHER SIDE IS REEDED. ASK THE CUSTOMER WHICH SIDE IS PREFERRED AT THIS STAGE.
ONLY USE THE CORRECT TYPE AND QUANTITY OF CERAMIC COMPONENTS. POINTS 7.1 TO 7.5 ARE COMMON TO ALL FULE TYPES AND LAYOUTS.
7.1 Position the burner cover gasket on the burner skin ensuring the holes align with the ports. Take care as the front left-hand hole is offset compared to the others. See diagram 9, arrow A.
7.2 Position the flame baffle centrally on the tray and ensure the stepped lower edge engages against the rear edge of the burner skin. See diagram 10.
7. ARRANGEMENT OF FUEL BED COMPONENTS
9
10
15
INSTALLATION INSTRUCTIONS
INSTALLATION
7.3 Place the rear panel against the rear of the box and slide the side panels on either side of the flame baffle. Ensure they locate in the brackets at the top of the firebox. DO NOT SLIDE THEM ALL THE WAY BACK. See diagram 11.
7.4 Locate the top panel on top of the rear and side panels.
Finally push the sides fully towards the rear panel. This will retain the top panel. See diagram 12.
7.5 Place the front coal centrally in the channel at the front of
the tray. See diagram 13. The relationship between the front coal and flame baffle is shown in diagram 13.
11
12
13
COAL LAYOUT
NOTE: THERE ARE TWO LARGE COALS IN A BAG INSIDE
THE MAIN BAG. THESE ARE ONLY TO BE USED WHEN A CURVED FRONT SUCH AS THE HOLYROOD AND RICHMOND ARE USED. DO NOT USE THE TWO LARGE COALS WHEN USING A FLAT FRONTED FRAME.
FRONT ROW COAL LAYOUT USING FLAT FIRE FRONTS
7.6 The front row is the only difference in coal layout. Place one large coal centrally on the front coal resting against the frame. Then place three small coals either side. See diagram 14.
FRONT ROW COAL LAYOUT USING CURVED FIRE FRONTS.
7.7 Place three large coals resting on top of the front coal and
against the front of the frame, then place two small coals either side of the large ones. See diagram 15.
COAL LAYOUT CONTINUED FROM FRONT ROW
7.8 Place four large coals behind the first row and one small coal either end resting up against the side panels.
See diagram 16.
14
15
16
16
INSTALLATION INSTRUCTIONS
INSTALLATION
7.9 Place one small coal either side on top of the flame baffle in each rear corner. Then place two large coals in between the
two small coals. These coals should touch the rear panel. See diagram 17.
7.10 Finally place five large coals between the second and rear
row of coals. See diagram 18.
7.11 It is essential that gaps are left between the coals to maximise
the performance of the appliance.
PEBBLE LAYOUT - CURVED AND FLAT FRONTS
7.12 ALL THE PEBBLES HAVE AN IDENTIFICATION ON THE UNDERSIDE. ENSURE THE PEBBLES ARE PLACED ONLY IN THEIR CORRECT POSITIONS.
7.13 Place the first row of pebbles on top of the front coal resting against the frame front. All the identifications are placed
face down so they cannot be seen. See diagram 19.
17
18
19
7.14 Working from the outside of the appliance, place the second row of pebbles against the rear of the first row. Note the orientation of each pebble, as this is important to the performance of the fire. See diagram 20.
7.15 Place the rear row of pebbles on top of the flame baffle, these must touch the rear panel. See diagram 21.
7.16 Place the remaining five pebbles between the second and
rear rows. See diagram 22
20
6 5 4 5 2
AR1174
22
21
2 2 4 5
AR1173
17
INSTALLATION INSTRUCTIONS
INSTALLATION / COMMISSIONING
11.1 Locate the control valve on the appliance. There are two control knobs on the valve, the right hand knob controls the pilot ignition and the left hand knob controls the main burner.
11.2 If your appliance has already been upgraded to battery remote control, please refer to the instructions provided with the upgrade to operate the remote control. The following instructions will work for either situation.
11.3 Ensure that the left-hand control knob is pointing to off ( ).
11.4 Ensure that the right hand control knob is pointing to off ( ).
11.5 Press in the right hand control knob and rotate it anti-
clockwise until a click is heard (keep pressing in) and the knob is pointing to pilot ( ). The pilot should now light. If the pilot has not lit, repeat the procedure until it does.
11.6 Keep the control knob pressed for 10 seconds and then
release it, the pilot should stay alight. If the pilot goes out, repeat the procedures until it does.
11.7 If the pilot will not light after repeated attempts, contact the
retailer or installer from whom the appliance was purchased.
11.8 Turn the right hand control to point to main burner ( ). The
appliance can now be controlled using the left hand control
knob.
11.9 Turn the left hand control knob to point to low fire ( ), the
main burner will light on low. The burner can now be controlled between low and high settings. Turn the control knob anticlockwise increase the flame height and clockwise
to decrease the flame height.
THE YELLOW FLAMES WILL APPEAR WHEN THE FIRE HAS GAINED SUFFICIENT HEAT - TYPICALLY 10 TO 20 MINUTES.
11. LIGHTING THE FIRE
1.1 Close all windows and doors to the room, check all controls, and allow fire to burn on maximum for 5 minutes. Test for spillage of flue products using a smoke match. Pass the lighted smoke match along the top front edge just inside the opening or canopy. See diagram 1.
1.2 If the fire spills, run for a further 10 minutes and re-check. If
the flue restrictor plate has been fitted to the fire this can be removed to assist flue flow if required. ( Convector only)
1.3 If there are extractor fans in the room or adjacent rooms, the
spillage test must be repeated with the extractors running on maximum.
IF SPILLAGE PERSISTS, DISCONNECT THE APPLIANCE AND SEEK EXPERT ADVICE.
For future reference record the installation details on the commissioning sheet on page 3 of these instructions.
1. COMMISSIONING
1
1
HOTBOX
SERVICING INSTRUCTIONS
SERVICING
18
This appliance must be serviced at least once a year by a competent person.
All tests must be serviced by best practice as described by the current CORGI recommendations.
1.1 Before any tests are undertaken on the appliance, conduct a gas soundness test for the property to ensure that there are no gas leaks prior to starting work.
1.2 Before any tests are undertaken on the appliance it is also recommended to fully check the operation of the appliance.
1.3 Special checks
1.3.1 Clean any lint or fluff from the pilot - pay particular
attention to the aeration hole in the side of the pilot.
1.3.2 Clean away any fluff or lint from under the burner
1.3.3 Check that the spark gap on the pilot is correct.
1.4 Correct any faults found during the initial tests and then recommission the appliance conducting the usual safety checks.
1.5 Advise the customer of any remedial action taken.
1.6 As part of the annual service, the space behind the firebox must be inspected for any debris, which may have fallen down the chimney.
1.7 Remove the gas fire from the firebox as detailed below.
1.8 Inspect the space behind the firebox for debris and the condition of the chimney, the flue flow test should be carried out now. Remove any debris and carry out any necessary remedial work.
1. SERVICING REQUIREMENTS
SERVICING INSTRUCTIONS
FAULT FINDING CHARTS
19
IGNITION FUNCTIONAL CHECK 1
PILOT WILL NOT LIGHT
Ensure there is no debris around the pilot assembly, e.g. coal, soot, etc
which could short the spark, clean the area. Check for fluff in the pilot
aeration hole. See diagram 7.
There is a blokage in the system, check the inlet test point, the mag
seating, valve and pilot filter
Operate the valve.
Is there a spark?
Does the pilot light?
Is the control being
operated correctly?
Will the pilot light
with a match?
Is the gas turned on to
the appliance?
Is the gas pressure
correct?
Has the system got
any air in it?
SYSTEM O.K
Consult users book
and retry
Check isolation tap
and gas meter, retry.
Correct and retry.
Purge the gas pipes
and retry
See “No Spark”
Chart *
Ensure gap between the
electrode and thermocouple
is as Dia. 8 and retry.
If gap is O.K then first
change the ignition lead and
retry.
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
IGNITION FUNCTIONAL CHECK 2
NO SPARK
Ensure there is no debris around the pilot assembly, e.g. coal, soot, etc
which could short the spark, clean the area.
Consult users
instructions, retry
Is the valve being
operated correctly?
Reset the pilot
burner
Correct and retry
Check for defective or
damaged control knob
spindle or cam operation.
Check for the correct
location of piezo
components. Correct and
retry.
Remove the electrode lead
from the piezo. Operate
the valve. Does a spark
jump from the piezo to
the valve body?
Operate the valve to
light the pilot, does the
valve ‘click’?
Has ignition lead become
detached or is connection
poor?
Remove the electrode lead
from electrode with
insulated pliers hold the tip
3.5mm from the pilot pipework,is there a spark
when the valve ‘clicks’?
Is the electrode wire
detached from the piezo
valve?
Replace the ODA unit
Replace the electrode
lead and retry
Replace the
control valve
Is the gap between electrode
and thermocouple
as in Dia 7?
NO
NO
NO
YES
YES
YES
NO
YES
YES
YES
*
SERVICING INSTRUCTIONS
FAULT FINDING CHARTS
20
FLAME FAILURE FUNCTIONAL CHECK
PILOT WILL NOT STAY LIT OR FIRE GOES OUT
If the appliance goes out in use continually, this may mean that the
oxygen depletion sensor has been activated. The appliance should not be used
untill the cause has been found and rectified.
Ensure there is no debris arounfd the pilot assembly, e.g. coal, soot, etc.
Check for fluff in the pilot aeration hole. See diagram 7.
Light the pilot and keep the control knob pushed in at least
10 seconds before letting go
With the pilot
running is the
gas pressure as
stated on the
datanadge?
Is the pilot
flame of the correct length? See diagram 7.
Is thermocouple
connection good
in back of valve
Replace
ODS unit
Change the
ODS unit
SYSTEM O.K
Tighten the
connection and
retry
With the fire
running on full is
the gas at the
pressure stated
on the datanadge
Problem is with
the pipework or
fittings which lead
to the fire. Correct
and retry
Run for 60 sec’s.,
turn off, time
interval until mag
unit shuts with a
click. Is this greater
than 7 seconds?
Run for 60 sec’s.,
turn off, time
interval until mag
unit shuts with a
click. Is this greater
than 7 seconds?
Will the pilot
stay lit?
Will the pilot
stay lit?
Change
mag unit
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
SERVICING INSTRUCTIONS
REPLACING PARTS
1. GENERAL
2. IGNITION LEAD
3. PIEZO
4. ODS PILOT UNIT
21
In order to service any of the following parts on the appliance, it will be necessary to remove the burner unit from the firebox. To remove the burner unit proceed as follows.
1.1 Turn off the gas supply at the isolation device located under the appliance.
1.2 Disconnect the gas supply pipe leaving the isolation device on the supply pipe and not the appliance.
1.3 Remove the loose coals or pebbles and place on a dry clean
surface.
1.4 Remove the decorative frame, fret and ash cover. There are two screws securing the frame to the appliance. Refer to frame instructions.
1.5 Remove the front coal, flame baffle and all the ceramic liners. All these items are very fragile so store them carefully.
1.6 Remove the six screws securing the burner unit to the fire firebox. See diagram 1.
1.7 The burner unit can now be removed.
2.1 Remove the fire. Refer to section 1.
2.2 Undo the single screw that secures the left hand side of the control cover. See diagram 2.
2.3 To release the right hand side of the control cover insert the narrow blade screwdriver into the slot shown in diagram 3, lever it gently and pull from the right hand side at the same time. The cover will now come off, there is a small cylindrical metal spacer inside the cover, this must be kept and replaced on the fixing screw during re-assembly.
2.4 Disconnect the ignition lead from the gas valve and the pilot. See diagram 4 arrow A.
2.5 Replace with a new ignition lead following the same route as the old one. Replace the valve cover and the pilot assembly.
2.6 Check the operation of the new ignition lead.
2.7 Replace the fret.
3.1 The piezo assembly used on this appliance is not serviceable and is unlikely to fail. If a new piezo is required it will be necessary to change the gas valve, refer to section 5.
Note: The pilot unit on the appliance is a non serviceable unit due to the complex nature of its manufacture. Replacement of the complete unit must be carried out when one of the following items becomes faulty:
Pilot injector
Ignition electrode
Thermocouple
1
2
3
4
4.5 Replace with a new pilot assembly, set the spark gap. See
diagram 8.
4.6 After reassembly, check for gas soundness and carry out a
flame failure functional check details in the flow chart, especially the mag drop out time.
5.1 Remove the fire, refer to section 1.
5.2 Disconnect the 2x8mm and 1x4mm gas pipe fittings at the
back of the gas valve and also disconnect the thermocouple, see diagram 9 arrows B and E.
5.3 Disconnect the injector nut. See diagram 10 arrow D.
5.4 Undo the two bolts securing the gas valve to the appliance
and remove the valve.
5.5 Replace in reverse order.
5.6 Check all joints for gas leaks, check operation of the
thermocouple and ignition lead.
SERVICING INSTRUCTIONS
REPLACING PARTS
5. GAS VALVE
22
4.1 Remove the fire, refer to section 1.
4.2 Gently pull the ignition lead off the electrode. See diagram 5 arrow A.
4.3 Remove the two screws securing the pilot assembly. See
diagram 6 arrow B.
4.4 Undo the thermocouple connection at the back of the gas valve and the pilot pipe at the pilot elbow. See diagram 7 arrows B and C.
5
6
7
8
9
10
B
B
C
E B
D
6.1 Remove the fire, refer to section 1.
6.2 Under the thermocouple nut. See diagram 11 arrow B.
6.3 Undo the mag unit retaining nut at the back of the control valve behind the thermocouple nut.
6.4 After removing the retaining nut, the mag unit can be tapped out and a replacement fitted.
6.5 Replace the mag unit retaining nut and tighten. Note - this is a gas-tight seal.
6.6 Replace the thermocouple and check for gas leaks.
6.7 After reassembly, carry out the flame failure functional check as detailed in the flow chart, especially the mag unit drop out
time.
7.1 Remove the fire, refer to section 1.
7.2 With the fire removed, undo the injector compression nut and valve nut (see diagram 12 arrows D and E), pull the pipe clear of the injector body.
7.3 Rotate the injector until it is fully removed.
7.4 Replace with the correct replacement injector. When
ordering, always state the model, gas type and serial number.
7.5 Reassemble and turn the gas supply on, check for any leaks.
The following parts must be changed when converting an appliance from one gas type to another:
Burner assembly NGA8306
LPGAP8306
Databadge PR0393L
Note: The control valve will be set for the particular
appliance and gas type. In all instances, when ordering new parts, be sure to quote the appliance type and serial number.
Use only genuine Gazco replacement parts. Non-standard components will invalidate the guarantee and may be dangerous.
SERVICING INSTRUCTIONS
REPLACING PARTS
6. MAG UNIT
7. MAIN INJECTOR
8. CHANGING BETWEEN GAS TYPES
9. SPARES PART LISTS
23
CERAMIC PARTS
FRONT COAL. BLACK CE0400
FRONT COAL. GREY CE0401
FLAME BAFFLE. BLACK CE0402
FLAME BAFFLE. GREY CE0403
BURNER COVER GASKET CE0273
CONVECTOR SIDE LH CE0408
CONVECTOR SIDE RH CE0409
CONVECTOR REAR PANEL CE0410
CONVECTOR TOP PANEL CE0411
HOTBOX SIDE LH CE0404
HOTBOX SIDE RH CE0405
HOTBOX REAR PANEL CE0406
HOTBOX TOP PANEL CE0407
COAL SET CE0412
PEBBLE SET CE0455
NATURAL GAS PARTS
MAIN INJECTOR IN0007
PILOT ASSEMBLY PI0037
GAS VALVE GC0088
LPG PARTS
MAIN INJECTOR IN0025
PILOT ASSEMBLY PI0037
GAS VALVE GC0088
MISCELLANEOUS
IGNITION LEAD GC0090
MAG UNIT GC0092
CONTROL COVER GC0087
UPGRADE KIT 8445
11
B
12
D
E
Gazco Limited, Osprey Road, Sowton Industrial Estate, Exeter, Devon, England EX2 7JG
Te l: (01392) 261999 Fax: (01392) 444148 E-Mail: info@gazco.com
Loading...