Before installation of this product please read these instructions fully.
It is very important to also understand the requirements of the UK Building Regulations
(England and Wales – Document J / Scotland - Part F), along with any local regulations that
may apply. Should any conflict occur between these instructions and these regulations the
regulations shall apply.
Your local Building Control Officer would be happy to advise should questions arise regarding
the requirements of the regulations.
The Stockton stove should be fitted by a HETAS approved installer, or approved by your local
Building Control Officer. Your Stovax dealer should be able to arrange this service for you.
A faulty installation could cause danger to the inhabitants and structure of the building.
All heating systems should be designed by a competent heating engineer, and be suitable
for a Solid Fuel appliance.
1. FLUE AND CHIMNEY
The construction of the Flue or Chimney system should meet the requirements of the Building
Regulations.
The minimum flue sizes required are:-
Stockton 8150mm (6”) diameter or 135 (5
If a suitable approved factory made system is to be used it should be installed to the
manufacturer’s instructions. Do not connect to systems containing large voids, or over 230mm
square (9” square).
The minimum height of the Flue or Chimney must be 4m (13’) when measured from the
hearth to the top of the flue, with no horizontal sections, and the maximum of 4 bends with
angles of less than 45 degrees.
The flue exit from the building should be positioned to comply with the requirements of the
Building Regulations.
The Flue or Chimney must be free from any obstruction of any kind.
The Flue or Chimney must be clean and sound, and should be swept before re
Ensure no other heating appliances are connected to the same Flue or Chimney system.
1
/
”) square
2
-use.
3
PRE-INSTALLATION CHECKS
Check that the Flue or Chimney is structurally sound. In particular, it should not be possible
for products of combustion to come into contact with combustible materials in the structure of
the building.
Check the flue draught. This should be done with all windows and doors closed and any
extraction fans in adjoining rooms running at maximum speed. (See next section for additional
ventilation requirements)
Note: A guide containing general information on Chimneys and Flues is obtainable from: -
The British Flue & Chimney Manufacturers’ Association,
FETA
2 Waltham Court
Milley Lane
Hare Hatch
Reading
Bucks RG10 8TH
01189 403416 e-mail :- info@feta.co.uk
Tel :-
2. ADDITIONAL VENTILATION
Additional ventilation will be required to comply with the requirements of the Building
Regulations. This should be provided using a permanently open vent, of the size listed, which
is positioned so that it is not liable to be blocked, both inside and outside the building.
2
Area:Stockton 8 Integral Boiler- 1650mm
Extractor fans or cooker hoods should not be placed in the same room or space as the
Stockton stove.
If any of these checks reveal problems do not proceed with the fitting of the stove until
they have been rectified.
(16.5cm2)
4
INSTALLATION
3. HEATING CIRCUIT
All water heating installations should be designed, before product installation, and installed by
a competent heating engineer in conjunction with the requirements detailed in the following:
The Building Regulations
The Local Water Authority Bylaws
IEE Wiring Regulations
BS 5449: 1
Any other relevant Local Authority Regulations
BS 5449: 1 gives detailed recommendations of water circulation systems.
This manual gives only give basic advice about system design. The full system should be
designed with regard to individual requirements of the installation.
Sizing Radiators
The size of radiator required for a room depends the following factors.
a) The temperature that you want it to be able to maintain, the table below is a guide:
Ideal Room Temperatures: -
Lounge 21 C
Dining Room 21 C
Kitchen 16 C
Bedrooms 15 C
Bathroom 23 C
Stairs 18 C
b) The heat loss from the room.
The calculations for this depend upon the size of room, number of windows, numbers of
doors and, the construction materials used in the building. Too big and the system will
overshoot its temperature and be less economical to run, too small and it won't reach its
desired temperature. The calculation produces a heat loss figure in watts, of how much heat
you need to warm that room up to the design temperature. The calculation can be done by
using the radiator manufacturer's heat loss calculators, and should be completed by a qualified
heating engineer
.
5
INSTALLATION
Hot water
An allowance should be made in any calculation for the heat requirement for any hot water
tank fitted to the system.
Pipe losses
Consideration should be given heat loses through the pipework used in the heating circuit.
6
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.