STIEBEL ELTRON WWK 300 A, WWK 300 AP, WWK 300 AH, WWK 300 AHP Operating And Installation Instructions

www.kvacontrol.co.za
Operating and installatiOn instructiOns
Supplied by K.V.A.Control cc
dHW Heat pumps
» WWK 300 a » WWK 300 ap » WWK 300 aH » WWK 300 aHp
www.kvacontrol.co.za
Contents
Observe the following safety instructions:
Please note: Warning about possible dangers.
Note: Important information and tips
1. Operating instructions for users and contractors
1.1 Operation and control ......................................................................................................................... 3
1.2 Device description
1.3 Correct operation
1.4 Incorrect operation
1.5 Function description
1.6 Operation with active defrost feature WWK 300 A and WWK 300 AH
1.7 Operation with passive defrost feature WWK 300 AP and WWK 300 AHP
1.8 Maintenance and cleaning
1.9 Troubleshooting by the user ............................................................................................................... 4
2. Installation instructions for contractors
2.1 Regulations and standards ................................................................................................................. 5
2.2 Installation ......................................................................................................................................... 6
2.3 Water connection
2.4 Power supply ...................................................................................................................................... 7
2.5 Commissioning ................................................................................................................................... 8
2.6 Safety equipment and maintenance
2.7 Specification ....................................................................................................................................... 9
Where children or persons with limited physical, sensory or mental capabilities are to be allowed to control this equipment ensure that this will only happen under supervision or after appropriate instructions by a person responsible for their safety. Children should be supervised to ensure that they do not play with the equipment.
Symbols used in these instructions
www.kvacontrol.co.za
3
1. Operating instructions for users and contractors
Supplied by K.V.A.Control cc
1.1 Operation and control
The Stiebel Eltron domestic hot water heat pump WWK 300 A/AP/AH/AHP (DHW) is a DHW generator that operates automatically and has a capacity of approx. 300 L. The water temperature is permanently set to 60 °C.
The device is installed, connected and handed over ready for use by a qualified contractor. Nevertheless, you should familiarise yourself with the most important technical features of your heat pump.
1.2 Device description
The device extracts heat from the ambient air. This energy is used to heat the water inside the cylinder. Where the device is installed inside a room, this is cooled down through the heat extraction by approx. 1 to 3 °C. The device also extracts moisture from the ambient air that creates condensate, which must be drained off. For this purpose, a condensate drain with closure incl. a strainer is integrated in the floor of the device.
Special features of the WWK 300 AH and WWK 300 AHP
An electric booster heater is integrated for heating approx. 100 litres of water in the upper sector of the DHW cylinder.
1.3 Correct operation
The DHW heat pump is designed for extracting heat from the ambient air and the utilisation of that energy for heating domestic hot water. The DHW heat pump can be installed in the open as well as in enclosed spaces.
1.4 Incorrect operation
The following are not permitted:
The utilisation of greasy extract air.
The heating of liquids other than domestic hot water.
The installation of the equipment:
in rooms where the temperature is a) below the freezing point.
in rooms where the device is at risk b) from explosions as a result of dust, gases or vapours.
Operation of the device with an empty cylinder.
1.5 Function description
Heat pump operation
This is the standard operating mode, to which the limits of scope of the heat pump apply (see: Specification). To heat up the cylinder capacity of approx. 300 litres of water in accordance with EN 255 part 3 to 60 °C, the WWK 300 requires ... :
τ
Heat-upϑRoomFrelϑCold water
10.1 h 15 °C 70 % 15 °C 3.19
5 h 42 °C 70 % 15 °C 5.61
If the heat pump is switched OFF and ON again, for instance after a
power failure, the compressor will only re-start (after approx. 3 minutes), when the pressure inside the refrigerant circuit has normalised again.
Electric booster heater (only for the WWK 300 AH and WWK 300 AHP)
If there is a higher DHW demand or when the WWK was switched OFF and you require hot water quickly, you can accelerate the heat-up process by means of the electric booster heater. For reasons of saving energy, the electric booster heater will only heat up approx. 100 litres of water in the upper section of the cylinder.
The control thermostat of the electric booster heater is preset to 60 °C and will be restarted when the DHW temperature falls below 45 °C. This safeguards not only that primarily the heat pump provides hot water, but also that you enjoy a high level of DHW convenience when large amounts of hot water are drawn.
COP (t)
1.6 Operation with active defrost feature
WWK 300 A and WWK 300 AH
Subject to the relative humidity and the DHW temperature, the evaporator begins to build up hoar frost at an ambient temperature of below 6 °C.
If the evaporator is covered in hoar frost, the frost monitor N2 (see wiring diagram Fig. 6 and 7) switches the fan OFF, whilst the compressor continues to run, and the changeover valve V2 routes the hot gas directly to the evaporator. For this, the condenser is shut off by changeover valve V1 (see Fig. 4) When the temperature at the evaporator fins rises above 3 °C, the fan is started again, and DHW heating continues.
The DHW heat pump can be operated at ambient temperatures as low as 0 °C. The evaporator is defrosted according to demand in the temperature range 0 °C to +6 °C. This extends the heat-up time.
Ambient temperature
The heat pump must not be
installed in areas where ambient temperatures frequently exceed 42 °C or areas where temperatures frequently drop below 0 °C
1.7 Operation with passive defrost feature
WWK 300 AP and WWK 300 AHP
The limit of application of the WWK AP / AHP (without hot gas defrost feature) is set to 6 °C.
However, with this limit of application, the evaporator may build up hoar frost subject to air temperature and relative humidity, particularly when the DHW temperature is low. The compressor will be switched OFF as soon as the evaporation temperature lies below ­7 °C for any length of time. When the temperature at the evaporator fins rises above 3 °C, the compressor are started again, and the DHW heating continues.
Ambient temperature
The heat pump must not be installed in areas where ambient
temperatures frequently exceed 42 °C or areas where temperatures frequently drop below 6 °C
1.8 Maintenance and cleaning
The device is generally maintenance free, with the exception of cleaning the strainer in the condensate drain.
Sand and dust can result in sludge building up inside the strainer. Therefore, clean the strainer at least twice per annum or in accordance with demand.
A damp cloth is sufficient for cleaning all plastic parts. Never use scouring or solvent-based cleaning agents.
Please note: Maintenance work, e.g. checking the electrical safety,
must only be carried out by a qualified contractor.
Check the condensate drain at least z monthly at the bottom strainer outlet and at the top condensate pan drain (visual check, see Fig. 4, pos 16).
Loading...
+ 7 hidden pages