STIEBEL ELTRON WPL 10 I, WPL 10 IK 3 Operation And Installation

OPERATION AND INSTALLAT ION
Compact air source heat pump
» WPL 10 I » WPL 10 IK 3
2 | WPL 10 www.stiebel-eltron.com
SPECIAL INFORMATION
OPERATION
1. General information �����������������������������������������3
1.1 Relevant documents_____________________________________________ 3
1.2 Safety instructions _______________________________________________ 3
1.3 Other symbols in this documentation _______________________ 4
1.4 Units of measurement __________________________________________ 4
1.5 Standardised output data ______________________________________ 4
2. Safety ���������������������������������������������������������� 4
2.1 Intended use ______________________________________________________ 4
2.2 General safety instructions ____________________________________ 4
2.3 Test symbols ______________________________________________________ 4
3. Appliance description ���������������������������������������4
3.1 Properties _________________________________________________________ 4
3.2 Function ___________________________________________________________ 5
4. Settings ������������������������������������������������������� 5
5. Maintenance and care ���������������������������������������5
6. Troubleshooting ����������������������������������������������5
INSTALLATION
7. Safety ���������������������������������������������������������� 6
7.1 General safety instructions ____________________________________ 6
7.2 Instructions, standards and regulations ____________________ 6
8. Appliance description ���������������������������������������6
8.1 Standard delivery ________________________________________________ 6
8.2 Accessories ________________________________________________________ 6
8.3 Details on energy consumption _______________________________ 6
9. Preparations �������������������������������������������������� 7
9.1 Electrical installation____________________________________________ 8
10. Installation ����������������������������������������������������8
10.1 Transport __________________________________________________________ 8
10.2 Siting _______________________________________________________________ 8
10.3 Heating water connection ______________________________________ 8
10.4 Oxygen diffusion _________________________________________________ 9
10.5 Filling the heating system _____________________________________ 9
10.6 Venting the heating system ____________________________________ 9
10.7 Safety temperature controller for underfloor heating system _____________________________________________________________ 9
10.8 Buffer cylinders __________________________________________________ 9
10.9 Flow rate, heating side ________________________________________ 10
10.10 Condensate drain _______________________________________________ 11
10.11 Second heat generator ________________________________________ 11
10.12 Removing the casing parts ___________________________________ 11
11. Power supply ����������������������������������������������� 12
11.1 General ___________________________________________________________ 12
11.2 Electrical connection WPL10I _______________________________ 12
11.3 Electrical connection WPL10IK3 ___________________________ 12
11.4 Connecting compressor and electric emergency/ booster heater ___________________________________________________ 13
11.5 Control voltage connection ___________________________________ 14
11.6 Low voltage connection _______________________________________ 14
12. Fitting casing components �������������������������������� 14
13. Fitting air hoses �������������������������������������������� 15
13.1 WPL 10 I ___________________________________________________________ 15
13.2 WPL 10 IK 3 _______________________________________________________16
14. Commissioning ��������������������������������������������� 16
14.1 Checks before commissioning the heat pump manager 16
14.2 Commissioning the heat pump manager __________________ 16
14.3 Initial start-up ___________________________________________________ 16
15. Shutdown ��������������������������������������������������� 17
15.1 Standby mode ___________________________________________________ 17
15.2 Power interruption _____________________________________________ 17
16. Appliance handover ���������������������������������������� 17
17. Troubleshooting �������������������������������������������� 18
17.1 Controls on the IWS ____________________________________________ 18
17.2 Fan noise _________________________________________________________ 18
18. Maintenance ������������������������������������������������ 18
19. Specification ������������������������������������������������ 19
19.1 Dimensions and connections WPL10I _____________________ 19
19.2 Dimensions and connections WPL10IK3 _________________ 20
19.3 Wiring diagram WPL10I ______________________________________ 21
19.4 Wiring diagram WPL10IK3 __________________________________ 22
19.5 Output diagrams WPL10I | WPL10IK3 ___________________ 23
19.6 Data table ________________________________________________________ 24
GUARANTEE
ENVIRONMENT AND RECYCLING
www.stiebel-eltron.com WPL 10 | 3
SPECIAL INFORMATION | OPERATION
General information
SPECIAL INFORMATION
- The appliance may be used by children aged8 and up and persons with reduced physical, sen­sory or mental capabilities or a lack of experience and know-how, provided that they are supervised or they have been instructed on how to use the appliance safely and have understood the result­ing risks. Children must never play with the ap­pliance. Children must never clean the appliance or perform user maintenance unless they are supervised.
- The connection to the power supply must be in the form of a permanent connection. Ensure the appliance can be separated from the power sup­ply by an isolator that disconnects all poles with at least 3mm contact separation.
- Maintain the minimum clearances to ensure trou­ble-free operation of the appliance and facilitate maintenance work.
- Never interrupt the heat pump power supply, even outside the heating season. Otherwise, sys­tem frost protection is not guaranteed.
- The heat pump manager automatically switches the heat pump to summer or winter mode.
- If the heat pump and frost protection are com­pletely switched off, drain the system on the water side.
OPERATION
1. General information
The chapters "Special Information" and "Operation" are intended for both the user and qualified contractors.
The chapter "Installation" is intended for qualified contractors.
Note
Read these instructions carefully before using the appli­ance and retain them for future reference. Pass on the instructions to any new user where appro­priate.
1.1 Relevant documents
Operating and installation instructions for the WPM heat
pump manager
Operating and installation instructions of all other com-
ponents in the system
1.2 Safety instructions
1.2.1 Structure of safety instructions
!
KEYWORD Type of risk Here, possible consequences are listed that may result from failure to observe the safety instructions.
Steps to prevent the risk are listed.
1.2.2 Symbols, type of risk
Symbol Type of risk
Injury
Electrocution
1.2.3 Keywords
KEYWORD Meaning
DANGER Failure to observe this information will result in serious
injury or death.
WARNING Failure to observe this information may result in serious
injury or death.
CAUTION Failure to observe this information may result in non-seri-
ous or minor injury.
!
OPERATION
Safety
4 | WPL 10 www.stiebel-eltron.com
1.3 Other symbols in this documentation
Note
General information is identified by the adjacent symbol.
Read these texts carefully.
Symbol Meaning
Material losses (appliance damage, consequential losses and environmen­tal pollution)
Appliance disposal
This symbol indicates that you have to do something. The ac-
tion you need to take is described step by step.
1.4 Units of measurement
Note
All measurements are given in mm unless stated oth­erwise.
1.5 Standardised output data
Explanations to determine and interpret the specified standardised output data.
1.5.1 Standard: EN 14511
The output data specifically mentioned in text, diagrams and technical datasheets has been calculated according to the test conditions of the standard shown in the heading of this section.
Generally, these standardised test conditions will not fully meet the conditions found at the installation site of the system user.
Depending on the chosen test method and the extent to which this method deviates from the conditions defined in the norm shown in the heading of this section, any deviations can have a considerable impact.
Further factors that have an influence on the test values are the measuring equipment, the system configuration, the age of the system and the flow rates.
A confirmation of the specified output data can only be obtained if the test conducted for this purpose is also performed in ac­cordance with the conditions defined in the norm shown in the heading of this section.
2. Safety
2.1 Intended use
This appliance is intended for domestic use. It can be used safely by untrained persons. The appliance can also be used in a non-do­mestic environment, e.g. in a small business, as long as it is used in the same way.
Any other use beyond that described shall be deemed inappropri­ate. Observation of these instructions and of instructions for any accessories used is also part of the correct use of this appliance.
2.2 General safety instructions
!
WARNING Injury The appliance may be used by children aged 8 and older and persons with reduced physical, sensory or mental capabilities or a lack of experience and know-how, pro­vided that they are supervised or they have been in­structed on how to use the appliance safely and have understood the resulting risks. Children must never play with the appliance. Children must never clean the ap­pliance or perform user maintenance unless they are supervised.
2.3 Test symbols
See type plate on the appliance.
3. Appliance description
3.1 Properties
The appliance is an air source heat pump designed for use as a heating heat pump. The appliance extracts heat from the outdoor air at a low temperature level and trans­fers it to the heating water at a higher temperature level. The heating water can be heated up to a flow temperature of 60 °C.
The appliance is equipped with an electric emergency/booster heater (DHC). If the dual mode point is undershot in mono mode operation, the electric emergency/booster heater is activated to safeguard heating operation and the provision of high DHW tem­peratures. In such a case in mono energetic operation, the electric emergency/booster heater is activated as a booster heater.
This appliance has further operational characteristics:
- Suitable for underfloor and radiator heating.
- Preferred for low temperature heating systems.
- Extracts heat from the outdoor air even at outside tempera­tures of -20 °C.
- Corrosion-protected, external casing made from hot-dipped galvanised sheet steel plus stove-enamelled finish.
- Comprises all components and safety equipment required for operation.
- Filled with non-combustible safety refrigerant.
Note
For centralised control of the heating system, you would need the WPM heat pump manager.
!
OPERATION
Settings
www.stiebel-eltron.com WPL 10 | 5
3.2 Function
Heat is extracted from the outdoor air via the heat exchanger (evaporator) on the air side. The refrigerant evaporates and is compressed by a compressor. This process requires electrical energy.
The refrigerant is then at a higher temperature level and transfers the heat drawn from the air to the heating system via an additional heat exchanger (condenser). During this process, the refrigerant expands and the cycle begins again.
At air temperatures below approx. 7°C, the humidity in the air condenses as hoarfrost on the evaporator fins. Any hoarfrost is au­tomatically defrosted. Water created from this defrosting process collects in the defrost pan and is drained off via a hose.
In the defrost cycle, the fan is switched OFF and the heat pump circuit is reversed. The heat required for defrosting is drawn from the buffer cylinder or heating circuit. The heat pump automatically reverts to heating mode at the end of the defrost cycle.
Special features of the WPL10IK3
The WPL10IK3 is equipped as standard with the WPM heat pump
manager. It is also equipped with a heating circuit pump, an expansion
vessel and a three-way valve for changeover between the heating circuit and DHW heating. The standard delivery also includes the air hoses and their fixing materials.
4. Settings
The system is operated exclusively with the WPM heat pump man­ager.
Please observe the heat pump manager operating and instal-
lation instructions.
5. Maintenance and care
!
Damage to the appliance and environment pollution
Maintenance work, such as checking the electrical safety, must only be carried out by a qualified contractor.
Protect the appliance from dust and dirt ingress dur-
ing building work.
A damp cloth is sufficient for cleaning all plastic and sheet metal parts. Never use abrasive or corrosive cleaning agents.
Every month, check that the condensate drain is working
correctly (visual inspection). When doing so, check whether water is collecting below or next to the appliance. Observe the "Troubleshooting" chapter.
We recommend an annual inspection (to establish the current condition of the system), and service by a contractor if required (to return the system into its original condition).
6. Troubleshooting
Fault Cause
Remedy
There is no hot water or the heating system stays cold.
No power at the appli­ance.
Check the fuses/ MCBs in your fuse box/distribution panel. If required, reset the MCBs. If the MCBs trip again after being reset, notify your contractor.
Water is leaking from the appli­ance.
The condensate drain may be blocked.
Call your contractor to have the condensate drain cleaned out.
Condensate is collecting on the outside of the appliance or the air hoses.
The drying out phase of the building is not yet complete.
If the room is sufficiently well ventilated and dehumidified, this condensate should no longer form on the appliance ap­prox.two years af ter the house was built.
The relative humidity in the air is high (≥60%).
A change in weather conditions should no longer cause conden­sation to form on the appliance.
The appliance is sited in a damp room. Damp rooms are those where humidity in the air is high due to the drying of laun­dry, for example.
Ensure that the room is ade­quately ventilated and dehumid­ified. If necessary, hang your laundry in a different room. Use a vented tumble dryer. Please note that condenser tumble dryers do not reduce the humidity in the air.
The air hoses are incor­rectly fitted or poorly sealed. Cold air escapes.
Check whether the air hoses are correctly fitted and sealed. If necessary, refer to your con­tractor.
If you cannot remedy the fault, notify your contractor. To facilitate and speed up your enquiry, please provide the serial number from the type plate. The type plate is located at the front top, on the right or left hand side of the casing.
Sample type plate
Montageanweisung beachten! Dichtheit geprüft!
Made in Germany
*xxxxxxxxxxxxxxxxxx*
26_03_01_1736
1
1 Number on the type plate
6 | WPL 10 www.stiebel-eltron.com
INSTALLATION
Safety
INSTALLATION
7. Safety
Only a qualified contractor should carry out installation, commis­sioning, maintenance and repair of the appliance.
7.1 General safety instructions
We guarantee the trouble-free function and operational reliabil­ity only if original accessories and spare parts intended for the appliance are used.
7.2 Instructions, standards and regulations
Note
Observe all applicable national and regional regulations and instructions.
8. Appliance description
For outdoor installation the appliance offers additional frost pro­tection of the heating water pipes. The integral frost protection circuit starts the heating circuit pump in the heat pump circuit automatically at +8°C condenser temperature, and thereby en­sures circulation in all water-filled sections.
The heat pump starts automatically when the temperature in the heat pump circuit drops below +5°C.
8.1 Standard delivery
8.1.1 WPL 10 I
The following are delivered with the appliance:
- Wiring diagram
8.1.2 WPL 10 IK 3
The following are delivered with the appliance:
- 2 x air hose with fixing materials
- Wiring diagram
8.2 Accessories
Designation
Heat pump manager in wall mounted enclosure, WPMW (WPL10I only) Pressure hoses SD25 or SD32 Wall duct with external wall grille AWG315SR Wall duct with external wall grille AWG315GL
Thermally insulated air hose, 4m (WPL10I only) Hose connection panel Condensate pump PK10 Cylinder SBP200E Cylinder SBP400E Cylinder SBP700E Heat pump manager in wall mounted enclosure, WPMW (WPL10I only) Heat pump manager as control panel mounted version, WPMS (WPL10I only) Mixer module with wall mounting enclosure, MSMW
Designation
Mixer module as control panel mounted version, MSMS Pressure hose G 1¼” x 1m Pressure hose G 1¼” x 2 m Pressure hose G 1¼” x 5 m Pressure hose G 1¼” x 10 m Heat pump compact installation WPKI 5 UP kit 25 / 7E (for WPKI5) Remote control for heating systems FE 7 Contact sensor AVF 6 Immersion sensor TF 6
STB-FB safety temperature controller for underfloor heating Filter assembly 22 mm (FS-WP 22) Filter assembly 28 mm (FS-WP 28)
www.stiebel-eltron.com WPL 10 | 7
INSTALLATION
Preparations
9. Preparations
Note
The appliance is designed for internal installation, except in damp areas.
- Never install on joists. Never install the appliance directly below or next to living
rooms or bedrooms.
Never direct the air intake and discharge apertures in exter-
nal walls towards neighbouring windows or living rooms/ bedrooms.
Protect pipe transitions through walls and ceilings with an-
ti-vibration insulation.
Note
For details regarding the sound power level, see chapter "Specification / Data table".
The room in which the appliance is to be installed must meet the following conditions:
- Free from the risk of frost.
- The room must not be subject to a risk of explosions arising
from dust, gases or vapours.
- When installing the appliance in a boiler room together with
other heating equipment, ensure that the operation of other heating equipment will not be impaired.
- Minimum volume of the installation room. The minimum
volume of the installation room is assured if the minimum clearances are observed.
- Load-bearing floor (for the weight of the appliance, see
chapter "Specification / Data table").
For installation on floating screeds, make provisions for a
quiet heat pump operation.
Isolate the mounting surface around the heat pump by a re-
cess. After completing the installation, seal the recess with a water-impervious and sound insulating material, such as silicone for example.
1 2 3 54
26_03_01_1466
1 Concrete base 2 Impact sound insulation 3 Floating screed 4 Floor covering 5 Recess
Minimum clearances WPL10I
≥500
≥200
≥600
≥500
≥1000
D0000019289
Minimum clearances WPL10IK3
≥500
≥200
≥500
≥500
≥1000
D0000019298
Maintain the minimum clearances to ensure trouble-free op-
eration of the appliance and facilitate maintenance work.
8 | WPL 10 www.stiebel-eltron.com
INSTALLATION
Installation
9.1 Electrical installation
DANGER Electrocution Carry out all electrical connection and installation work in accordance with national and regional regulations.
DANGER Electrocution The connection to the power supply must be in the form of a permanent connection. Ensure the appliance can be separated from the power supply by an isolator that disconnects all poles with at least 3mm contact separa­tion. This requirement can be met with contactors, circuit breakers, fuses/MCBs, etc.
Note
The specified voltage must match the mains voltage. Ob­serve the type plate.
Install cables with the following cross-sections in accordance with the respective fuse rating:
MCB/fuse rating
Assignment Cable cross-section
C 16 A Compressor 2.5 mm² B 16 A
Electric emergency/ booster heater (BH)
2.5 mm²
1.5 mm² with only two live cores and routing on a wall or in an electrical con­duit on a wall.
B 16 A Control cable 1.5 mm²
The electrical data is provided in the "Specification" chapter. For the WPL10I, you require a J-Y (St) 2x2x0.8mm² electric BUS cable.
!
Material losses
Provide separate fuses/MCBs for the two power circuits, i.e. for the compressor and the electricemergency/boost­er heater circuits.
10. Installation
10.1 Transport
Pay attention to the appliance's centre of gravity when trans-
porting the appliance.
- The centre of gravity is in the area where the compressor is located.
- With the WPL10IK3, ensure that the control fascia is at the top during transport.
- Lifting slings for handling the standard appliance can be hooked in anywhere on the bottom of the frame.
Protect the appliance against heavy impact during transport.
- If the appliance needs to be tilted during transport only do so for a short time on one of its longitudinal sides.
- The longer the appliance is tilted, the greater the distribution of refrigerant oil in the system.
Wait approximately 30minutes before starting the appliance
after it has been tilted.
10.2 Siting
Remove the packaging film and the top and side EPS
padding.
D0000051813
1
2
1 Appliance foot 2 Sliding block
Undo the four fixing screws underneath the pallet.Remove the appliance feet from the pack. Fully turn the feet
onto the appliance, without removing the appliance from the pallet.
Take the appliance off the pallet and set it down on the pre-
pared base. If required, use the sliding blocks provided to help you position the appliance.
Observe minimum distances (see the "Preparations / Mini-
mum clearances" chapter).
Level the appliance horizontally by adjusting the feet.
10.3 Heating water connection
The heating system to which the heat pump is connected must be installed by a qualified contractor in accordance with the water installation diagrams that are part of the technical guides.
In dual mode operation, return water from the second heat gen­erator may flow through the heat pump. The return water tem­perature must not exceed 60°C.
Thoroughly flush the pipework before connecting the heat
pump. Foreign bodies, such as rust, sand and sealant, can impair the operational reliability of the heat pump. We rec­ommend installing our filter assembly in the heating return (see chapter "Accessories").
On the WPL10I, connect one flexible pressure hose each to
the heating flow and heating return connections to act as an anti-vibration mount. The pressure hoses are part of the standard delivery. Anti-vibration mounts are already fitted to the WPL10IK3.
Ensure the correct connection of the heating flow and return.Check for tightness.When sizing the heating circuit, observe the maximum avail-
able external pressure differential (see the "Specification / Data table" chapter).
Provide thermal insulation in accordance with applicable
regulations.
www.stiebel-eltron.com WPL 10 | 9
INSTALLATION
Installation
10.4 Oxygen diffusion
!
Material losses
Avoid using open vented heating systems or steel pipe­work in conjunction with underfloor heating systems with plastic pipes that are permeable to oxygen.
In open vented heating systems or in underfloor heating systems with permeable plastic pipes, oxygen diffusion can cause corro­sion on steel components such as internal cylinders, steel heating elements or steel pipes.
The products of corrosion, e.g. rusty sludge, can settle inside the heat pump condenser and reduce its cross-section, resulting in a lower output or in the high pressure switch triggering a shutdown.
10.5 Filling the heating system
Heating water quality
Carry out a fill water analysis before the system is filled. This may, for example, be requested by the relevant water supply utility.
!
Material losses
To avoid damage as a result of scaling, it may be neces­sary to soften or desalinate the fill water. Always observe the fill water limits specified in the "Specification / Data table" chapter.
Recheck these limits 8 - 12 weeks after commission-
ing and as part of the annual system service.
Note
With a conductivity >1000μS/cm, desalination treatment is recommended in order to avoid corrosion.
Note
Suitable appliances for water softening and desalinating, as well as for charging and flushing heating systems, can be obtained from trade suppliers.
Note
If you treat the fill water with inhibitors or additives, the same limits as for desalination apply.
10.6 Venting the heating system
Vent the heating system thoroughly.
10.7 Safety temperature controller for underfloor heating system
!
Material losses
In order to prevent excessively high flow temperatures in the underfloor heating system in the event of a fault, we always recommend using a safety temperature controller to limit the system temperature.
10.8 Buffer cylinders
10.8.1 Installation with buffer cylinder
A buffer cylinder is recommended to ensure a trouble-free heat pump operation. The buffer cylinder (cylinder SBP) is not only installed as an hydraulic separator for volume flow in the heat pump and heating circuits, but primarily as energy source for defrosting the evaporator.
If a buffer cylinder is used, remove the jumper across terminals X4/5 (pump) and X4/8 (HCP) when commissioning the WPL...IK.
Remove return sensor B2 connected to terminals X2/2(B2) and X2/3(B2) from the sleeve in the heat pump return and insert it into the buffer cylinder sensor well.
10.8.2 Installation without buffer cylinder
!
Material losses
For operation without a buffer cylinder, set parameter BUFFER OPERATION in menu SETTINGS / HEATING / STANDARD SETTING to OFF.
Loading...
+ 19 hidden pages