STIEBEL ELTRON WPF 5 basic, WPF 7 basic, WPF 5 S basic, WPF 16 basic, WPF 7 S basic Operation And Installation

...
Page 1
OPERATION AND INSTALLAT ION
Brine | water heat pumps
» WPF 5 basic » WPF 7 basic » WPF 10 basic » WPF 13 basic » WPF 16 basic » WPF 5 S basic » WPF 7 S basic » WPF 10 S basic
Page 2
CONTENTS
SPECIAL INFORMATION
OPERATION
1. General information �����������������������������������������3
1.1 Safety instructions ����������������������������������������������� 3
1.2 Other symbols in this documentation ����������������������� 4
1.3 Units of measurement ������������������������������������������ 4
1.4 Standardised output data �������������������������������������� 4
2. Safety ���������������������������������������������������������� 4
2.1 Intended use ������������������������������������������������������ 4
2.2 Safety information ����������������������������������������������� 4
2.3 Test symbols ������������������������������������������������������ 4
3. Appliance description ���������������������������������������4
3.1 Energy saving tip ����������������������������������������������� 5
4. Operation �����������������������������������������������������5
4.1 Operation ���������������������������������������������������������� 6
4.2 Essential facts in brief ������������������������������������������ 6
4.3 Adjustments at control level 1 �������������������������������� 7
4.4 Overview of control level 2������������������������������������� 7
4.5 Adjustments at control level 2 �������������������������������� 8
4.6 Remote control FE7 �������������������������������������������� 17
4.7 Remote control FEK �������������������������������������������� 17
5. Maintenance and care ������������������������������������� 17
6. Troubleshooting �������������������������������������������� 17
6.1 Other problems ������������������������������������������������� 17
INSTALLATION
7. Safety �������������������������������������������������������� 18
7.1 General safety information ����������������������������������� 18
7.2 Instructions, standards and regulations ������������������� 18
8. Appliance description ������������������������������������� 18
8.1 Mode of operation ���������������������������������������������� 18
8.2 Standard delivery ����������������������������������������������� 18
9. Preparations ������������������������������������������������ 18
9.1 General information �������������������������������������������� 18
9.2 Electrical installation������������������������������������������� 19
9.3 Buffer cylinder �������������������������������������������������� 19
10. Mounting ���������������������������������������������������� 19
10.1 Handling ���������������������������������������������������������� 19
10.2 Positioning ������������������������������������������������������� 19
10.3 Removing the casing panels ���������������������������������� 20
10.4 Installing the heat source system ��������������������������� 20
10.5 Heating water connection ������������������������������������� 22
10.6 Oxygen diffusion ������������������������������������������������ 22
10.7 Filling the heating system ������������������������������������ 22
10.8 Venting the heating system ����������������������������������� 22
10.9 Minimum flow rate of heat sink for WPF 5-16 basic ����� 23
10.10 Flow rate of heat sink for WPF 5-10 S basic ��������������� 24
10.11 DHW heating ����������������������������������������������������� 24
10.12 Electrical connection ������������������������������������������� 24
10.13 Fitting the casing parts ���������������������������������������� 28
10.14 installation ������������������������������������������������������� 29
10.15 High limit safety cut-out for underfloor heating systems STB-FB ������������������������������������������������� 29
10.16 Remote control FE7 �������������������������������������������� 30
10.17 Remote control FEK �������������������������������������������� 30
11. Commissioning ��������������������������������������������� 30
11.1 Checks before commissioning�������������������������������� 30
11.2 Heating curve adjustment during commissioning ������� 31
11.3 Operation and control ����������������������������������������� 31
11.4 Taking the appliance out of use ������������������������������ 31
11.5 Heat pump manager commissioning summary ���������� 32
11.6 Heat pump manager commissioning ����������������������� 34
11.7 WPMiw commissioning report ������������������������������� 41
12. Settings ����������������������������������������������������� 42
12.1 Standard settings ����������������������������������������������� 42
12.2 Heating and DHW programs ����������������������������������42
12.3 Appliance handover �������������������������������������������� 42
13. Troubleshooting �������������������������������������������� 43
13.1 Fault display ����������������������������������������������������� 43
13.2 Resetting the high limit safety cut-out ��������������������� 44
13.3 Fault list parameter �������������������������������������������� 45
14. Maintenance ������������������������������������������������ 45
15. Specification ������������������������������������������������ 46
15.1 Connections ������������������������������������������������������ 46
15.2 Installation dimensions ���������������������������������������� 47
15.3 Wiring diagram WPF 5 basic ��������������������������������� 48
15.4 Wiring diagram WPF 7 basic | WPF 10 basic | WPF 13 basic | WPF 16 basic �������������������������������������������� 50
15.5 Wiring diagram WPF 5-10 S basic ��������������������������� 52
15.6 Output diagrams WPF 5 basic �������������������������������� 54
15.7 Output diagrams WPF 7 basic �������������������������������� 56
15.8 Output diagrams WPF 10 basic ������������������������������58
15.9 Output diagrams WPF 13 basic ������������������������������ 60
15.10 Output diagrams WPF 16 basic ������������������������������ 62
15.11 Output diagrams WPF 5 S basic ������������������������������ 64
15.12 Output diagrams WPF 7 S basic ������������������������������ 65
15.13 Output diagrams WPF 10 S basic ���������������������������� 66
15.14 Data table WPF 5-16 basic ������������������������������������ 67
15.15 Datentabelle WPF 5-10 S basic ������������������������������� 69
15.16 Data table WPMiw ���������������������������������������������� 70
GUARANTEE
ENVIRONMENT AND RECYCLING
2 | WPF basic www.stiebel-eltron.com
Page 3
SPECIAL INFORMATION

General information

SPECIAL INFORMATION

- The appliance may be used by children aged8 and up and persons with reduced physical, sen­sory or mental capabilities or a lack of experience and know-how, provided that they are supervised or they have been instructed on how to use the appliance safely and have understood the result­ing risks. Children must never play with the ap­pliance. Children must never clean the appliance or perform user maintenance unless they are supervised.
- Use a permanent connection to the power supply. Ensure the appliance can be separated from the power supply by an isolator that disconnects all poles with at least 3mm contact separation.
- Maintain the minimum clearances to ensure trou­ble-free operation of the appliance and facilitate maintenance work.
- The COOLING MODE parameter must only be set if there is a suitable hydraulic circuit.
- The COOLING MODE parameter will only be shown if a FEK or FE7 remote control is connect­ed. The cooling mode is only possible in summer.
- Maintenance work, such as checking the electri­cal safety, must only be carried out by a qualified contractor.

OPERATION

1. General information
The chapters „Special Information“ and „Operation“ are intended for both the user and qualified contractors.
The chapter „Installation“ is intended for qualified contractors.
Note
Read these instructions carefully before using the appli­ance and retain them for future reference. Pass these instructions on to a new user if required.

1.1 Safety instructions

1.1.1 Structure of safety instructions
KEYWORD Type of risk Here, possible consequences are listed that may result from failure to observe the safety instructions.
Steps to prevent the risk are listed.
1.1.2 Symbols, type of risk
Symbol Type of risk
1.1.3 Keywords
Injury
Electrocution
- We recommend a regular inspection (to establish the current condition of the system), and main­tenance by a qualified contractor if required (to return the system to its original condition).
- Never interrupt the power supply, even outside the heating period. The system’s active frost pro­tection is not guaranteed if the power supply is interrupted.
- There is no need to shut the system down in summer. The heat pump manager has an auto­matic summer/winter changeover.
KEYWORD Meaning
DANGER Failure to observe this information will result in serious
injury or death.
WARNING Failure to observe this information may result in serious
injury or death.
CAUTION Failure to observe this information may result in non-seri-
ous or minor injury.
www.stiebel-eltron.com WPF basic | 3
Page 4
OPERATION

Safety

1.2 Other symbols in this documentation

Note
General information is identified by the adjacent symbol.
Read these texts carefully.
Symbol Meaning
This symbol indicates that you have to do something. The ac-
tion you need to take is described step by step.
Material losses (appliance damage, consequential losses and environmen­tal pollution)
Appliance disposal

1.3 Units of measurement

Note
All measurements are given in mm unless stated oth­erwise.

1.4 Standardised output data

Explanations to determine and interpret the specified standardised output data
1.4.1 Standard: EN 14511
The output data specifically mentioned in text, diagrams and technical datasheets has been determined in line with the test conditions described in the standard shown in the heading of this chapter.
Generally, these standardised test conditions will not fully meet the conditions found at the installation site of the system user. Depending on the chosen test method and the extent to which the selected method deviates from the conditions described in the standard shown in the heading of this chapter, any deviations can have a considerable impact. Further factors that have an influence on the test values are the measuring equipment, the system con­figuration, the age of the system and the flow rates.
A confirmation of the specified output data can only be obtained if the conditions applicable to the relevant test match those of the standard shown in the heading of this chapter.
2. Safety

2.1 Intended use

The appliance is designed to:
- heat rooms.
- heat DHW.
Observe the operating limits listed in chapter “Specification”.
The appliance is intended for domestic use, i.e. h. it can be used safely by untrained persons. The appliance can also be used in a non-domestic environment, e.g. in a small business, as long as it is used in the same way.
Any other use beyond that described shall be deemed inappropri­ate. Observation of these instructions and of instructions for any accessories used is also part of the correct use of this appliance. Any changes or conversions to the appliance void any warranty.

2.2 Safety information

Observe the following safety information and regulations.
- The electrical installation and installation of the heating cir­cuit must only be carried out by a recognised, qualified con­tractor or by our customer service engineers.
- Contractors are responsible for adherence to all currently ap­plicable regulations during installation and commissioning.
- Operate the appliance only when fully installed and with all safety equipment fitted.
- Protect the appliance from dust and dirt ingress during building work.
WARNING Injury
!
The appliance may be used by children aged 8 and up and persons with reduced physical, sensory or mental capabilities or a lack of experience provided that they are supervised or they have been instructed on how to use the appliance safely and have understood the result­ing risks. Children must never play with the appliance. Children must never clean the appliance or perform user maintenance unless they are supervised.
WARNING Injury
!
For safety reasons, only operate the appliance with
the casing closed.

2.3 Test symbols

See type plate on the appliance.

3. Appliance description

The WPF is a heating heat pump designed as a ground source heat pump. The heat pump extracts energy from the heat source medium at a low temperature level. This extracted energy is then transferred to the heating water at a higher level, enriched by the electric energy drawn by the compressor. Subject to the heat source temperature, the heating water can be heated up to a flow temperature of 60 °C.
Inside the WPF, a heating circuit pump and a three-way valve have been integrated for diverting the flow either to the heating circuit
4 | WPF basic www.stiebel-eltron.com
Page 5
OPERATION

Operation

or the DHW circuit. DHW is heated by pumping the heating water, which has been heated by the heat pump, through an indirect coil in the DHW cylinder, where it transfers its energy to the DHW.
The appliance is equipped with an electric emergency/booster heater (DHC). If the dual mode point is undershot in mono mode operation, the electric emergency/booster heater is activated to safeguard heating operation and the provision of high DHW tem­peratures. If the same thing happens in mono energetic operation, the electric emergency/booster heater is activated as a booster heater.
The equipment is regulated by an integral, weather-compensated return temperature control (WPMiw heat pump manager).
The WPMiw also regulates the DHW heating to the required tem­perature. DHW heating will be completed automatically by an integral electric booster heater, if either the high pressure sensor or the hot gas limiter of the heat pump responds during DHW heating, subject to the ECO function being enabled. Subject to the ECO function being enabled, the DHW heating will terminate and the set DHW value overwritten with the actual DHW temperature that has been achieved.
The WPMiw also controls the integral electric booster heater. No other heat source can be switched.

3.1 Energy saving tip

- Heat pumps operate with particular economy and environ­mental responsibility when they work with a maximum flow temperature of 35 °C. Low flow temperatures can be achieved by using area heating systems (e.g. underfloor heating or wall heating systems).
- Size radiators so that the maximum required flow tempera­ture does not exceed 45 °C.
- Activating the control parameter “Pump cycling” can reduce the power drawn by the circulation pump. In this connection, refer to your local heating contractor.
- When activating the “DHW ECO” parameter, the heat pump heats DHW exclusively on its own, i.e. without the additional electric booster heater. In that case, the DHW temperature is automatically limited to that value, which the heat pump can actually achieve. If, for reasons of pasteurisation, you want to heat the cylinder to 60 °C at least once every day, activate the “PASTEURISATION” parameter. In this connection, refer to your local heating contractor.
Summary of WPMiw functions
- RS 232 interface for adjustment and monitoring via a PC
- System expansion through the FEK and FE7 remote control units
- Input of the system and heat pump frost protection limits
- At least 24 h power reserve for the clock
- Automatic pump kick-start
- Reset option
- Stored fault list with precise fault code indication, together with date and time display
- Fast and precise fault diagnosis with a system analyser incl. temperature scanning of heat pumps and peripherals without additional equipment
- Factory settings for time switch programs for all heating and DHW circuits
4. Operation
WPMiw heat pump manager
ROOM TEMP HCI
Time / Date
DHW temp.
Room temp. 1
Room temp. 2
Raumtemp. 1
Raumtemp. 2
Warmwassertemp.
Heizkurven
Heating curves
Zeit / Datum
Info temperatures
Heizprogramme
Holiday / Party prog.
Info Temperaturen
Ferien / Partyprog.
PRGPC Reset Auto
1 Rotary selector 2 Rotary selector Reset / Auto 3 Appliance menu 4 Programming key 5 Programming indicator 6 Optical interface RS 232
System status display
10
ROOM TEMP HCI
9 8
7 6
1 Compressor 1 2 Buffer cylinder primary pump 3 Cooling (only with a suitable hydraulic circuit) 4 Electric emergency/booster heater (DHW heating) 5 Electric emergency/booster heater (heating) 6 DHW heating 7 Circulation pump, heating circuit 1 “radiator circuit” 8 Circulation pump, heating circuit 2 “mixer circuit” 9 Mixer close 10 Mixer open
Start up
Heating prog
DHW program
Inbetriebnahme
Warmwasserprog.
2
3
1456
26�03�01�0073
1 2
3 4 5
26�03�01�1572
www.stiebel-eltron.com WPF basic | 5
Page 6
OPERATION

Operation

4.1 Operation
The operation is split over three control levels. Control levels 1 and 2 are accessible to users and contractors alike. Control level 3 is reserved for qualified contractors:
1. control level (control flap closed)
This enables the adjustment of operating modes, such as standby mode, programmed operation, constant day or setback mode, etc.
2. control level (control flap open)
This enables system parameters, such as room temperatures, DHW temperatures, heating programs, etc. to be adjusted.
3. control level (for contractors only)
This level is protected by a code and should only be used by a contractor. Here, you can determine the specific details regarding the heat pump and heating system.

4.2 Essential facts in brief

Settings
All settings follow the same pattern:
Opening the control flap toggles the manager into programming mode. An indicator symbol play at system parameter Room temp. 1. Turning the rotary selec­tor allows you to move the indicator to the system parameter you want to change.
To change the system parameter, press dicator above illuminates, you can modify the current value by turning the rotary selector . Press the key again; the indicator then extinguishes and the new set value has been saved. You can modify further values for this parameter by pressing again, if the red indicator has not been extinguished above . The pro­gramming step can only be terminated when the red indicator has extinguished.
Terminating the programming process
You can terminate the programming process after entering and sav­ing the required parameter changes by closing the control flap. If you want to make further changes, turn the rotary selector display shows BACK, then press ous level. Closing the control flap with illuminated indicator above
returns the manager into its original position. The modified
value will then not be saved.
is shown at the bottom of the dis-
. Whenever the red in-
until the
. This will return you to the previ-
Display including all display elements
2 765431
24
18
13 12 11 10 9 8
1 Heating times for central heating and DHW (black) 2 14-digit plain text display 3 Day mode for heating circuit 1 4 Compressor running 5 Switching time pairs for central heating and DHW operation 6 2. heat source running 7 Setback mode for heating circuit 1 8 DHW mode 9 Constant setback mode 10 Constant day mode 11 Automatic mode 12 Standby mode 13 Fault message (flashing)
6
12
C
V
26�03�01�0075
Note
During commissioning, a system check will be imple­mented, e.g. all sensors that are currently connected are displayed upon request. Sensors not connected before the system went ‚live‘ are not registered by the manager and are therefore not displayed. The indicator symbol skips such system parameters.
Example: The system parameters DHW TEMP and DHW PROGRAM will be skipped if, during commissioning, the DHW cylinder sensor was not connected. und Warmwasserprog. übersprungen. Values for these parameters, therefore, cannot be programmed.
6 | WPF basic www.stiebel-eltron.com
Page 7
OPERATION
Operation

4.3 Adjustments at control level 1

4.3.1 Operating modes
The operating modes are changed by turning rotary selector with the control flap closed.
Standby mode
Frost protection is activated for heating and DHW mode. The dis­play indicates frost protection when the flap is closed. The set DHW value is fixed at 10 °C, the set heating flow value is calculated based on a set room temperature of 5 °C.
Application: during holidays.
Automatic mode
Heating subject to time switch program (applies to heating circuits 1 and 2); changeover between day and setback temperatures. DHW in accordance with a time switch program; changeover between day and setback temperature, see point 4. In this operating mode, an additional sun or moon symbol is displayed to indicate whether heating circuit 1 is currently in day or setback mode. The remote control is only active in this mode.
Application: When DHW and central heating are required.
Constant day mode
The heating circuit is constantly held at the day temperature (ap­plicable to heating circuit 1 and heating circuit 2). DHW in accord­ance with a time switch program.
Application: Low energy houses without setback mode.
Constant setback mode
The heating circuit is constantly held at the setback temperature (applicable to heating circuit 1 and heating circuit 2). DHW in accordance with a time switch program.
Application: during weekends away.
DHW mode
DHW heating is regulated by a time switch program. If a time program is enabled, the water inside the DHW cylinder is heated to the set day temperature. At all other times, the water is heat­ed to the set night temperature. Frost protection is activated for heating operation.
Application: The heating season has ended; only DHW should be generated.
Fault message (flashing)
Indicates faults in the heat pump system.
Notify your local contractor

4.4 Overview of control level 2

To access control level 2,
open the control flap.Select the required parameter with the rotary selector.
The display shows the relevant parameter in plain text and an arrow indicating the parameter’s location in the control level.
ROOM TEMP HC1
Here you can select the set room temperature for day and setback mode for heating circuit 1.
ROOM TEMP HC2
Here you can select the set room temperature for day and setback mode for heating circuit 2. The display ROOM TEMP2 will only be displayed, if the mixer flow sensor for heating circuit 2 has been connected.
Note
The actual room temperature can also be scanned if the FE7 or FEK remote control has been connected and allo­cated to HC1 or HC2.
DHW TEMP
Here you can allocate a set day and night temperature to the temperature inside the DHW cylinder.
TIME/DATE
Here you can adjust the time and summertime.
At the factory, summertime is set to begin on 25 March and to end on 25 October.
HOLIDAY/PARTY
You can indicate the length of your holiday using the holiday pro­gram menu (start date, end date). The heat pump system oper­ates in setback mode for the selected period. Frost protection is activated for the DHW cylinder.
The party program menu item allows you to extend the day mode by a few hours.
Temperatures
Here you can scan the heat pump or heat pump system sensor temperatures, comparing set with actual values, the heating curve gap, etc.
HEATING CURVES
Here you can select a heating curve each for heating circuit 1 and heating circuit 2. The room temperature will only remain constant, irrespective of the outside temperature, if the correct heating curve has been selected for the relevant type of building. Selecting the correct heating curve is therefore vitally important.
HEATING PROG
Here you can adjust associated heating programs for heating cir­cuits 1 and 2.
www.stiebel-eltron.com WPF basic | 7
Page 8
OPERATION
Operation
DHW PROGRAM
Here you select the times when the appliance will control DHW heating using the set day value. At all other times, the appliance controls DHW heating using the set night value.
COMMISSIONING
Note
The commissioning level (control level 3) may only be altered by your contractor.
Here you need to determine the settings of control level 2 and the system-specific parameters. These parameters are adjusted at control level 3, access to which is protected by code.
Check all parameters in sequence, and enter all selected values into the column (system value) provided in the commissioning report.
4.4.1 Special features of the WPF in cooling mode
For the WPF in cooling mode, your qualified contractor selects the room temperature for cooling mode at control level 3. Cooling commences when the room temperature exceeds the set room temperature.
Cooling terminates when the actual room temperature is 2 K lower than the set room temperature.

4.5 Adjustments at control level 2

To make any adjustments at control level 2, open the control flap.
4.5.1 Room temperature HC 1
With menu item ROOM TEMP HC1, you can select the set room temperature for day and setback mode for heating circuit 1. Chang­ing this parameter results in a parallel offset of the heating curve.
The actual room temperature can also be scanned, as soon as the FE7 or FEK remote control has been connected and allocated to heating circuit 1.
ROOM TEMP HC1
SET ROOM T DAY
SET ROOM T DAY
Note
For cooling via cooling surfaces (underfloor heating or wall heating systems), you also require the FEK remote control. For cooling via fan-assisted convectors, you also require the FEK or FE7 remote control. Cooling via radiators would lead to moisture damage and is therefore not permissible!
SET ROOM T NGT
SET ROOM T NGT
ACTUAL ROOM T
BACK
ROOM TEMP HC1
8 | WPF basic www.stiebel-eltron.com
Page 9
OPERATION
Operation
4.5.2 Room temperature, heating circuit 2
With menu item ROOM TEMP HC2, you can select the set room temperature for day and setback mode for heating circuit 2. You can change the room temperature, if you feel rooms are either too hot or too cold. ROOM TEMP HC2 will only be displayed if the mixer flow sensor is connected.
The actual room temperature can also be scanned, as soon as the FE7 or FEK remote control has been connected and allocated to heating circuit 2.
ROOM TEMP HC2
SET ROOM T DAY
SET ROOM T DAY
4.5.3 DHW temperature
With parameter 9, you can allocate a set day and night tempera­ture to the temperature inside the DHW cylinder.
DHW TEMP
SET DHW T DAY
SET DHW T DAY
SET DHW T NGT
SET ROOM T NGT
SET ROOM T NGT
ACTUAL ROOM T
BACK
ROOM TEMP HC2
SET DHW T NGT
ACTUAL DHW T
BACK
DHW TEMP
www.stiebel-eltron.com WPF basic | 9
Page 10
OPERATION
Operation
4.5.4 Time and date
You can adjust the time and summertime with the TIME/DATE menu item.
At the factory, summertime is set to begin on 25 March and to end on 25 October.
TIME/DATE
SET CLOCK
TIME
TIME
4.5.5 Holiday and party program
In HOLIDAY MODE, the heat pump system runs in setback mode and frost protection for DHW heating is enabled. Holiday mode is displayed when the flap is closed. For the start of the holidays, the year, month and day are entered; also enter the year, month and day for the end of the holidays. The start time is 0:00 h on the first day of the holidays. The end time is 24:00 h on the day the holiday ends. After the holiday period has expired, the heat pump system operates again in accordance with the previous heating and DHW program.
In PARTY MODE, you can extend the day mode for central heating by a few hours. This is displayed with the flap closed.
HOLIDAY/PARTY
HOLIDAY
YEAR
MONTH
DAY
SET CLOCK
YEAR START
MONTH START
DAY START
YEAR END
BACK
TIME/DATE
10 | WPF basic www.stiebel-eltron.com
Page 11
OPERATION
Operation
MONTH END
DAY END
HOLIDAY
BACK
HOLIDAY/PARTY
4.5.6 Temperatures
Under menu item TEMPERATURES, you can scan values of the heat pump or heat pump system.
TEMPERATURES
OUTSIDE
BACK
TEMPERATURES
Actual or set temperatures will not be displayed if the correspond­ing sensor is not connected.
Example:
Compressor heat amount in heating mode since 0:00 h today in KWh.
HEAT AMOU DAY kwh
www.stiebel-eltron.com WPF basic | 11
Page 12
OPERATION
Operation
INFO WPM Meaning
external Outside temperature ACT ROOM T FE7 Actual room temperature for heating circuit 1 (HC1) or heating circuit 2 (HC2) (will only be displayed if the FE7 remote control is connected) SET ROOM T FE7 Set room temperature for heating circuit 1 or heating circuit 2 (will only be displayed if the FE7 remote control is connected) REL HUMIDITY Relative humidity DEW POINT TEMP Dew point temperature SET DHW TEMP Set DHW temperature ACTUAL RTRN T Actual heat pump return temperature - heating circuit 1 SET RTRN TEMP Set heat pump return temperature for heating circuit 1 (HC1). Fixed temperature is displayed for fixed temperature control ACTUAL MIXER T Actual mixer flow temperature - heating circuit 2 SET MIXER TEMP Set mixer flow temperature - heating circuit 2 FIXED VALUE Set fixed temperature for heating circuit 1 SET BUFFER T Set buffer temperature (highest set value of heating circuits H1 and H2 (H3 if MSM is installed). Fixed temperature will be displayed for
ACTUAL FLOW T Actual heat pump flow temperature SET FLOW HTG Set central heating flow temperature ACTUAL SRCE T Actual heat source temperature SET SRCE TEMP Minimum source temperature DUAL-MODE HTG Dual-mode point - central heating DUAL-MODE DHW Dual-mode point - DHW HEAT LIMIT Limit temperature - central heating DHW LIMIT Limit temperature - DHW SYST FROST PRO System frost protection temperature HOT GAS TEMP Compressor outlet temperature HIGH PRESSURE HIGH PRESSURE LOW PRESSURE Low pressure HEAT AMOU DAY Compressor heat amount in heating mode since 0:00 h today.
set-value control)
TTL HEAT AMOU Total compressor heat amount in heating mode.
HEAT AMOU DAY Compressor heat amount in DHW mode since 0:00 h today.
TTL HEAT AMOU Total compressor heat amount in DHW mode.
TTL HEAT AMOU Total heat amount of the electric booster heater in heating mode
TTL HEAT AMOU Total heat amount of the electric booster heater in DHW mode
12 | WPF basic www.stiebel-eltron.com
Page 13
OPERATION
Operation
4.5.7 HEATING CURVES
The HTG CURVE menu item enables you to adjust one HTG CURVE each for heating circuit 1 and 2.
Note: Your contractor will have set up a building and system-spe­cific optimum heating curve for every heating circuit. It relates to the heat pump return temperature for heating circuit 1 and to the mixer flow temperature for heating circuit 2.
When adjusting the heating curve on the heat pump manager, the calculated set return or flow temperature, which is subject to the outside temperature and the set room temperature, will be shown at the top of the display.
As soon as a temperature has been preselected via the fixed tem­perature parameter at control level 3, heating circuit 1 will be hidden, and the display will show FIXED VALUE with the relevant temperature.
Adjusting the heating curve
1 32
HEATING CURVES
4
1 32
1 Relative to an outside temperature of +20 °C 2 Relative to an outside temperature of 0 °C 3 Relative to an outside temperature of -20 °C 4 Day mode 5 Heating circuit 1 6 Setback mode
5
6
C26�03�01�1068
BACK
HEATING CURVES
www.stiebel-eltron.com WPF basic | 13
Page 14
OPERATION
Operation
Heating curve diagram
One heating curve can be adjusted for heating circuit 1 and heating circuit 2 respectively.
At the factory, heating curve 0.6 is set up for heating circuit 1 and heating curve 0.2 for heating circuit 2.
These heating curves relate to a set room temperature of 20 °C.
-14
-16
-18
2,53
2
1,5
1,2
1
0,8 0,6 0,4 0,2
-20
100
80
60
40
20
2018161412
86420
10
-2-4-6
-8
-10
-12
Y Heating circuit 1, heat pump return temperature [°C] Heating circuit 2, heat pump flow temperature [°C] X Outside temperature [°C]
Adjustment of programmed changeover between day and setback mode
The figure shows a standard heating curve with a slope of 0.8, rel­ative to a set room temperature for day mode of 20°C. The bottom curve is setback mode. The set room temperature is reduced to 15 °C for setback mode. The heating curve is shifted down parallel to the original curve.
Adapting a heating curve
Example:
During spring and autumn, the temperature of a building’s heating system is too low at an outside temperature between 5 °C and 15°C, despite open radiator valves, but is OK at outside tempera­tures of ≤ 0 °C. This problem can be remedied with a parallel offset and a simultaneous reduction of the heating curve.
Prior to this adjustment, heating curve 1.0 was adjusted, relative to a set room temperature of 20 °C. The dotted line indicates the modified heating curve at 0.83 and a modified set room temper­ature at 23.2 °C.
70
60
50
40
30
26�03�01�1300
20
2018161412
86420
10
-2-4-6
-8
-10
-12
-14
Y Return/flow temperature [°C] X Outside temperature [°C]
-16
-18
-20
26�03�01�1302
70
60
50
40
30
20
2018161412
86420
10
Y Return/flow temperature [°C] X Outside temperature [°C] 1 Day mode 2 Setback mode
-2-4-6
1
2
-8
-10
-12
-14
-16
-18
-20
26�03 �01�1301
14 | WPF basic www.stiebel-eltron.com
Page 15
OPERATION
Operation
4.5.8 HEATING PROG
The HEATING PROG parameter enables you to determine when and how often the appliance heats to the set day values for heating circuit 1 and 2. At all other times, the appliance heats to the set night temperature. You will have already selected the set values under menu item ROOM TEMP HC1/2.
You can adjust your heating system as follows:
- for each individual day of the week (Monday, ..., Sunday)
- Monday to Friday (Mo – Fr)
- Saturday and Sunday (Sa – Su)
- the whole week (Mo – Su)
You can adjust three switching time pairs (I, II, III) for each of these options.
Example:
For heating circuit 1, your heating system should provide heat daily from Monday to Friday at two different times, i.e. from 05:30 h until 08:30 h as well as from 14:00 h until 22:00 h. For the weekend, your heating system should provide heat from 08:30 h until 21:00 h.
HEATING PROG
HEATING START
HEATING STOP
HEATING START
SAT–SUN
HEATING CIRC
MON–FRI
HEATING START
HEATING STOP
HEATING START
HEATING STOP
HEATING START
HEATING START
SAT–SUN
BACK
www.stiebel-eltron.com WPF basic | 15
Page 16
OPERATION
Operation
BACK
HEATING PROG
DHW START
DHW STOP
4.5.9 DHW programs
The DHW PROGRAM parameter enables you to select the times when the appliance will control DHW heating using the set day value. At all other times, the appliance controls DHW heating using the set night value. You will have already selected the set values under system parameter DHW TEMP. bereits eingestellt.
You can adjust your DHW heating as follows:
- for each individual day of the week (Monday, ..., Sunday)
- Monday to Friday (Mo – Fr)
- Saturday and Sunday (Sa – Su)
- the whole week (Mo – Su)
You can adjust three switching time pairs (I, II, III) for each of these options.
Exception: You will need two switching time pairs, if you want to heat DHW from 22:00 h until 06:00 h the following day.
Example:
You want to heat up DHW daily at two different times, i.e. from 22:00 h until 06:00 h the following day, and then from 08:00 h until 09:00 h.
The day begins at 00:00 h; therefore begin programming for this example at 00:00 h. The first switching times pair runs from 00:00 until 06:00 h. The second switching time pair runs from 08:00 until 09:00 h. The third switching times pair runs from 22:00 h until 23:59 h.
DHW START
DHW STOP
DHW START
DHW STOP
MON–SUN
DHW PROGRAM
BACK
MON–SUN
16 | WPF basic www.stiebel-eltron.com
DHW PROGRAM
Page 17
OPERATION

Maintenance and care

4.6 Remote control FE7

With the FE7 remote control, the following options are available:
- changing the set room temperature for heating for heating circuit 1 or 2 by ± 5 °C.
- changing the operating mode.
It offers the following controls:
- one rotary selector for changing the set room temperature
- one rotary selector with the following positions
-
Automatic mode
-
Constant setback mode
-
Constant day mode
Note
The remote control is only active when the WPMiw is in automatic mode.

4.7 Remote control FEK

Note
The parameters heating curve, room temperature and heating program are not shown at the WPMiw heat pump manager if the FEK is pre-selected for a specific heating circuit.
5. Maintenance and care
PIC00000609
Appliance and system damage
!
Maintenance work, such as checking the electrical safety, must only be carried out by a qualified contractor.
A damp cloth is sufficient for cleaning all plastic and sheet steel parts. Never use abrasive or corrosive cleaning agents.
Protect the appliance from dust and dirt ingress during building work.
We recommend a regular inspection (to establish the current con­dition of the system), and maintenance by a qualified contractor if required (to return the system to its original condition).

6. Troubleshooting

Fault Cause Remedy
There is no hot water or the heating system stays cold.
The fuse/MCB has blown/ has responded.
Check the fuse/MCB in your fuse box/distribu­tion panel.
Note
In cooling mode, the WPF requires the FEK for area cool­ing systems, e.g. underfloor heating systems, chilled ceilings, etc. Apart from the room temperature, it also determines the dew point temperature to prevent con­densation.
With the FEK remote control, the following options are available:
- changing the set room temperature for heating for heating circuit 1 or 2 by ± 5 °C.
- changing the operating mode.
It offers the following controls:
- one rotary selector for changing the set room temperature
- one “Away” button
- one “Info” button
- one key to select the following operating modes:
-
Standby mode
-
Automatic mode
-
Constant day mode
-
Constant setback mode

6.1 Other problems

If you cannot remedy the fault, notify your heating contractor. To facilitate and speed up your enquiry, please provide the serial number from the type plate. The type plate is located on the front at the top on the right or left hand side of the casing.
Sample type plate
*xxxxxxxxxxxxxxxxxx*
PIC00000704
Montageanweisung beachten! Dichtheit geprüft!
1 Number on the type plate
Made in Germany
1
26�03�01�1736
www.stiebel-eltron.com WPF basic | 17
Page 18
INSTALLATION

Safety

INSTALLATION

7. Safety

7.1 General safety information

- Only qualified contractors should carry out installation, com­missioning, maintenance and repair of the appliance.
- We guarantee trouble-free operation and operational relia­bility only if the original accessories and spare parts intend­ed for the appliance are used.

7.2 Instructions, standards and regulations

Note
Observe all applicable national and regional regulations and instructions.
7.2.1 Electrical installation
Appliance damage
!
The specified voltage must match the mains voltage. Ob­serve the type plate.
WARNING electrocution
Carry out all electrical connection and installation work in accordance with national and regional regulations.
DANGER Electrocution
Before any work, isolate the appliance from the power supply at the control panel.
WARNING electrocution
Only use a permanent connection to the power supply. The appliance must be able to be separated from the power supply by an isolator that disconnects all poles with at least 3mm contact separation. This requirement can be met by contactors, isolators, fuses etc.

8. Appliance description

8.2 Standard delivery

Delivered with the appliance:
- 1 outside temperature sensor AFS 2

9. Preparations

9.1 General information

Note
The appliance is designed for internal installation, except in wet areas.
Never install the appliance directly below or next to
bedrooms.
Protect pipe transitions through walls and ceilings with an-
ti-vibration insulation.
The room in which the appliance is to be installed must meet the following conditions:
- No risk from frost.
- The room must not be subject to a risk of explosions arising from dust, gases or vapours.
- When installing the appliance in a boiler room together with other heating equipment, ensure that the operation of other heating equipment will not be impaired.
- The volume of the installation room should be at least
13.8m³.
- Load-bearing floor (for the weight of the internal unit, see chapter „Specification / Data table“).
For installation on floating screeds, make provisions for quiet
heat pump operation.
Isolate the mounting surface around the heat pump by re-
cesses. After completing the installation, seal these recesses with a water-impervious and sound insulating material, such as silicone for example.
1 2 3 54

8.1 Mode of operation

Environmental energy is extracted by the heat exchanger on the heat source side (evaporator). Any energy extracted is transferred, together with the energy drawn by the compressor drive, to the heating water by a heat exchanger on the heating water side (condenser). Subject to the heat load, the heating water can be heated to +60°C. The DHW is heated via the internal indirect coil inside the DHW cylinder.
The electric booster heater (internal HS 2) starts if the high pres­sure sensor or the hot gas limiter responds during DHW heating. In addition it can cover any residual heat demand, if the heating system demand exceeds the heat pump output.
18 | WPF basic www.stiebel-eltron.com
1 Concrete base 2 Impact sound insulation 3 Floating screed 4 Floor covering 5 Recess
26�03�01�1466
Page 19
INSTALLATION

Mounting

9.2 Electrical installation

In accordance with VDE 0298-4, use the following cable cross-sec­tions subject to their fuse protection:
Fuse/MCB rating
C 16 A Compressor
B 16 A
C 16 A
C 25 A
C 35 A
B 16 A Control circuit fuse
C 16 A Control circuit fuse
The electrical data is given in the “Specification” chapter.
Provide separate fuses for the two power circuits of the appliance and the control unit.
Assignment Cable cross-section
(three phase) Electric emergency/
booster heater (BH) (three phase)
Compressor WPF 5 S basic (single phase)
Compressor WPF 7 S basic / WPF 10 S basic (single phase)
Electric emergency/ booster heater (BH) (single phase)
(three phase)
(single phase)
2.5 mm²
2.5 mm²
1.5 mm² with only two live cores and routing on a wall or in an electrical con­duit on a wall.
1.5 mm² for open routing. Note the type of routing!
2.5 mm² for routing through a wall. Note the type of routing!
4.0 mm² for open routing. Note the type of routing!
6.0 mm² for routing through a wall. Note the type of routing!
4.0 mm² when routing a multi core line on a wall or in an electrical conduit on a wall.
6.0 mm² for routing through a wall. Note the type of routing!
1.5 mm²
1.5 mm²
10. Mounting
10.1 Handling
Transport the appliance in its packaging to protect it against
damage.
Protect the appliance against heavy impact during transport.
- Only allow the appliance to be tilted during transport for a short time to one of its longitudinal sides. The longer the appliance is tilted, the greater the distribution of refrigerant oil in the system.
- Storage and transport at temperatures below - 20 °C and in excess of + 50 °C are not permissible.
10.2 Positioning
Remove the packaging film and the top and side EPS
padding.
Tilt the appliance backwards slightly and remove it from the
pallet.
Position the appliance on the prepared substrate.Observe the minimum clearances (see chapter “Dimensions
and connection”).
Remove the six screws from the appliance plinth, and set
down the casing onto the floor.

9.3 Buffer cylinder

Note
In combination with the WPF 13 basic and the WPF 16 basic, it is absolutely imperative to use a buffer cylinder.
A buffer cylinder is recommended to ensure trouble-free appliance operation.
The buffer cylinder provides hydraulic separation of the flow rates in the heat pump circuit and the heating circuit.
When operating without a buffer cylinder, observe the details
specified in the chapter “Minimum flow rate without buffer cylinder”.
6x
Appliance damage
!
The casing must stand on the floor free from the refrig­eration unit. D. h. That means, the six plinth screws must not be refitted.
26�03�01�1573
www.stiebel-eltron.com WPF basic | 19
Page 20
INSTALLATION
Mounting
10.3 Removing the casing panels
When removing the front cover ensure, that the cables, which connect the heat pump manager with the control panel, are not torn off.
The same applies to the earth connection which electrically con­nects the front cover to the casing.
2x
4x
10.4.3 Connection and filling with brine
Prior to connecting the heat pump, check the heat source circuit for possible leaks, and flush thoroughly.
Calculate the volume of the heat source circuit. The brine volume of the heat pump under operating conditions can be found in the data table (see chapter “Specification”).
The overall volume is equal to the required amount of brine made by mixing undiluted ethylene glycol and water. The chloride con­tent of the water must not exceed 300 ppm.
Mixing ratio
The brine concentration varies when using a ground collector or a geothermal probe as a heat source.
The mixing ratio can be found in the table below.
Ethylene glycol Water
Geothermal probe 25 % 75 % Geothermal collector 33 % 67 %
Charging the brine circuit
Note
The WPF S series does not have a brine pressure switch.
10.4 Installing the heat source system
Design the heat source system for the ground source heat pump in accordance with the technical guides.
10.4.1 Permitted brine:
- Heat transfer medium as concentrate on an ethylene glycol base, part no: 231109
- Heat transfer medium as concentrate on an ethylene glycol base, part no: 161696
10.4.2 Circulation pump and required flow rate
Use a circulation pump with compound-filled windings to supply the brine, to prevent an earth short circuit through condensate in the electrical part of the pump (cold water version).
Size the circulation pump in accordance with the system-specific conditions, h. i.e. nominal flow rate and pressure drop must be taken into consideration (see “Specification”).
An adequate flow rate must be safeguarded at every possible brine temperature, i.e.:
Nominal flow rate at a brine temperature of 0°C with a tolerance of +10%.
Note
26�03�01�1574
The brine/water heat pump is equipped with a brine pressure switch in the brine circuit. The brine pressure switch prevents brine getting into the ground if there is a leak in the brine circuit.
If the pressure in the brine circuit falls below 0.7bar, the brine pressure switch turns the heat pump off. In order for the heat pump to be enabled again, the pressure must be raised to at least
1.5bar while the heat pump is on standby.
To prevent the brine pressure switch turning the heat pump off when there is no leak, charge the heat source side of the heat pump during installation with a minimum pressure of >1.5bar.
Fill the system according to the following curve.
Insulate the brine lines with diffusion-proof thermal
insulation.
Note
The brine pressure switch is bridged to the power supply utility contact at the factory.
To activate the brine pressure switch, remove the
jumper.
20 | WPF basic www.stiebel-eltron.com
Page 21
INSTALLATION
1
2
Mounting
3
2,5
2
1,5
1
0,5
0
0 200 400 600 800
X System volume [l] Y Charge pressure [bar] 1 Required charge pressure subject to the system volume with
33% brine
2 Required charge pressure depending on system volume with
25% brine
Check the brine concentration:
Determine the density of the ethylene glycol/water mixture,
e.g. with a hydrometer.
Using the actual density and temperature, you can check the cur­rent concentration in the diagram.
1,10
1,09
1,08
D0000058692
1,07
1,06
1,05
1,04
1,03
1,02
1,01
50 Vol.-%
40
33
30
25
20
10
1
1 Drain, brine side
Fill the brine circuit via the drain.
After filling the system with brine and prior to commissioning, open the drain until brine runs out of it. No water must remain in the pipe run to the drain.
A
1,00
0,99
0,98
26�03�01�1606
-20 0 20 40 60 80 100
0
X Temperature [°C] Y Density [g/cm³] A Frost protection [°C]
Note
The quoted details refer to ethylene glycol. These details will differ slightly (see “Specification”) when using pro­pylene glycol and the heat transfer medium as ready­mixed solution.
Thermally insulate all brine pipes with vapour-proof material.
To prevent the transmission of noise, connect the heat source circuit to the heat pump with flexible pressure hoses.
26�03�01�1914
www.stiebel-eltron.com WPF basic | 21
Page 22
INSTALLATION
Mounting
10.4.4 Checking the heat source flow rate
The heat source flow rate is set via the temperature differential of the heat source circuit.
Calculate the temperature differential. For this, operate the
appliance in heating mode or DHW mode.
Max. temperature differential of heat source circuit
6
5
4
3
2
1
-5 0 5 10 15 20
Y Max. temperature differential [K] X Source inlet temperature [°C] 1 Heating flow 35 °C 2 Heating flow 50 °C
Note
You can check the source outlet temperature on the heat pump manager display under system parameter TEM­PERATURES.
1
2
10.5 Heating water connection
The heat pump heating system must be installed by a qualified contractor in accordance with the water installation drawings that are part of the technical documents.
Thoroughly flush the pipework before connecting the heat
pump. Foreign bodies, such as welding beads, rust, sand, sealant, etc. can impair the operational reliability of the heat pump.
Connect the heat pump on the hot water side. Check for
tightness.
Ensure the correct connection of the heating flow and return.
Provide thermal insulation in accordance with applicable regu­lations.
For sizing the heating circuit, note the maximum available external pressure differential.
10.6 Oxygen diffusion
diffusion may lead to corrosion on the steel components of the heating system (e.g.on the indirect coil of the DHW cylinder, on buffer cylinders, steel radiators or steel pipes).
In the event of oxygenation, separate the heating system be-
tween the heating circuit and the buffer cylinder.
Material losses
!
The products of corrosion (e.g.rusty sludge) can set­tle in the heating system components, which may re­sult in a lower output or fault shutdowns due to reduced cross-sections.
10.7 Filling the heating system
Fill the heating system via the drain.
84�03�01�0017
1
1 Drain, heating side
Water quality
A fill water analysis must be carried out before the system is filled. This may, for example, be requested from the relevant water supply utility.
Material losses
!
To avoid damage as a result of scaling, it may be neces­sary to soften or desalinate the fill water. The fill water limits specified in chapter "Specification / Data table" must always be observed.
Recheck these limits 8-12 weeks after commission-
ing and as part of the annual system maintenance.
Note
With a conductivity >1000μS/cm, desalination treatment is recommended in order to avoid corrosion.
Note
Suitable appliances for water softening and desalinating, as well as for charging and flushing heating systems, can be obtained via trade suppliers.
26�03�01�1606
Material losses
!
Avoid open vented heating systems and underfloor heat­ing systems with plastic pipes which are permeable to oxygen.
Note
If you treat the fill water with inhibitors or additives, the same limits as for desalination apply.
10.8 Venting the heating system
In underfloor heating systems with plastic pipes that are per­meable to oxygen and in open vented heating systems, oxygen
22 | WPF basic www.stiebel-eltron.com
Vent the pipework carefully.
Page 23
INSTALLATION
Mounting
10.9 Minimum flow rate of heat sink for WPF 5-16 basic
The heat pump is designed in such a way that no buffer cylinder is required to provide hydraulic separation of the flow in the heat pump circuit and the heating circuit in conjunction with space heating systems.
However, in conjunction with radiators or an installation with several heating circuits, the use of a buffer cylinder or a low loss header is recommended.
The WPF 13 and 16 appliances must, in any case, always be op­erated with a buffer cylinder or a low loss header.
Risk of damage!
!
The minimum flow rate to ensure perfect heat pump op­eration must be maintained at every operating point of the heat pump.
10.9.1 Minimum flow rate without buffer cylinder
The minimum flow rate is set using the temperature differential of the heating system.
Set the heating circuit pump to ∆p-constant. Set ∆p-constant to a value at which the temperature reaches or falls below the maxi­mum temperature differential.
Max. temperature differential on the heating side without buffer cylinder
18
16
14
12
10
8
1
2
Set the head of the circulation pump to a level that safe-
guards the flow rate required to operate the heat pump.
Check the final setting in DHW mode and adjust if required. Fully open the overflow valve.Close the overflow valve one turn at a time until the return to
the heat pump or the installed radiators become noticeably warm.
If no overflow can be detected in the overflow valve using the temperature sensor, close the heating circuit and heating circuit valves and check the overflow valve is working.
Individual room control via remote control FE7 or FEK
In this case, one or more heating circuits in the heating system must be left open. The open heating circuit(s) should be installed in the lead room (room in which the remote control is installed, e.g. the living room). The individual room can then be controlled via the FE7 or FEK remote control, or indirectly by adjusting the heating curve. The other rooms can be equipped with zone valves or thermostatic valves.
Fully open the heating circuit(s).Isolate by temporarily removing the fuse from the second in-
ternal heat source (DHC electric booster heater).
Operate the appliance in heating mode.Set the head of the circulation pump to a level that safe-
guards the flow rate required to operate the heat pump.
Check the final setting in DHW mode and adjust if required.
10.9.2 Minimum flow rate with buffer cylinder or low loss header
The minimum flow rate is set via the temperature differential of the buffer circuit.
Set the heating circuit pump to ∆p-constant. Set ∆p-constant to a value at which the temperature reaches or falls below the maxi­mum temperature differential.
Max. temperature differential on the heating side with buffer cylinder or low loss header
6
-5 0 5 10 15 20
12
84�03�01�0091�
11
1
Y Max. temperature differential [K] X Source inlet temperature [°C] 1 Heating flow 35 °C 2 Heating flow 50 °C
In heating mode without a buffer cylinder, there are two possible ways to safeguard the minimum flow rate:
Installing an overflow valve
Install an overflow valve with an internal diameter that is matched to and sized for the heating system, and adjust it as follows:
Fully open the heating circuit(s).Isolate by temporarily removing the fuse from the second in-
ternal heat source (DHC electric booster heater).
Fully close the overflow valve.Operate the heat pump in heating mode.
10
9
8
7
6
5
4
-5 0 5 10 15 20
Y Max. temperature differential [K] X Source inlet temperature [°C] 1 Heating flow 35 °C 2 Heating flow 50 °C
2
Isolate by temporarily removing the fuse from the second in-
ternal heat source (DHC electric booster heater).
www.stiebel-eltron.com WPF basic | 23
84�03�01�0090�
Page 24
INSTALLATION
Mounting
Operate the appliance in heating mode.Set the head of the circulation pump to a level that safe-
guards the flow rate required to operate the heat pump.
Check the final setting in DHW mode and adjust the setting if
required.
10.10 Flow rate of heat sink for WPF 5-10 S basic
10.10.1 Circulation pump (cylinder primary pump)
The cylinder primary pump is integrated into the WPF. Consider the available external head of 2.8 m when sizing the anti-vibra­tion mounts and the pipework between the heat pump and the buffer cylinder.
When utilising the WPF for DHW heating, ensure that the con­nection between the heat pump and the DHW cylinder is sized so that the total pressure drop outside the heat pump is less than the available external head of 2.8 m.
10.10.2 Circulation pump (heating circuit pump)
If no cylinder (buffer cylinder) is used, consider the maximum external pressure of 280 hPa when sizing the heating circuit. Safe­guard the nominal flow rate of the heat pump under all operating conditions of the heating system by installing an overflow valve.
10.11 DHW heating
For DHW heating, a DHW cylinder with internal indirect coil is required. The minimum coil surface area required is 3 m³.
A three-way diverter valve is integrated into the WPF between the DHW heating circuit and the central heating circuit.
Connect the DHW flow of the appliance to the upper coil con-
nection of the DHW cylinder (see Specification / Connections).
Connect the DHW return of the appliance to the lower coil
connection of the DHW cylinder.
10.12 Electrical connection
Only qualified electricians must carry out the installation in ac­cordance with these instructions.
DANGER Electrocution
Before any work, isolate the appliance from the power supply at the control panel.
Permission to connect the appliance may need to be obtained from your local power supply utility.
The terminals are located in the appliance control panel.
Note
Observe the chapter “Removing the casing parts”
when the appliance is closed.
Use appropriate cables in accordance with local regulations for all connections.
Open the control panel’s cover flap. To do so, remove the fix-
ing screws on the side at the top of the control panel.
Route all connecting cables and sensor leads through the
entries in the back panel (see chapter “Connections and dimensions”).
Route all cables through the strain reliefs.Connect the cables according to the following diagrams.Then check the function of the strain relief fittings.
Material losses
!
The compressor must only rotate in one direction. Change the direction of rotation by interchanging two phases, if the fault NO POWER appears in the WPMiw display when the compressor starts.
Connected load of the electric booster heater
Connect the electric booster heater to ensure acceptable DHW convenience. Mark the box in front to the terminal ratings on the relevant label below the type plate.
Note
When closing the appliance, observe chapter “Fitting
the casing parts”.
24 | WPF basic www.stiebel-eltron.com
Page 25
INSTALLATION
L1 L2 L3 N L1 L2 L3 L1’ L2’ L3’
ONKSKühlen
F8
Mounting
10.12.1 Electrical connection WPF basic (three-phase)
Connection X3: Heat pump, electric booster heater and brine pump
L1 L2 L3 N L1 L2 L3 L1’ L2’ L3’
Heat pump power supply (compressor)
L1, L2, L3, PE
DHC power supply (electric booster heater)
L1, L2, L3, N, PE
Connected load Terminal assignment
2.6 kW L1 N PE
3.0 kW L2 N PE
3.2 kW L3 N PE
5.6 kW L1 L2 N PE
5.8 kW L1 L3 N PE
6.2 kW L2 L3 N PE
8.8 kW L1 L2 L3 N PE
Three-phase brine pump power supply
L1', L2', L3', PE
Single phase brine pump power supply
L1', N (X3/4) PE
ON
KS
Kühlen
B1
B1
1 2 3 4 5 6 7 8 9 10 11 12 13
Material losses
!
When a single phase brine pump is connected, protect the heat pump and the DHC only via one common RCD. If no electric emergency/booster heater is connected, N must be tapped from X25 for the brine pump.
Connections X4: Control unit
Mains supply: L, N, PE Outputs: ON Compressor signal
26�03�01�1579
KS Brine pump signal Cooling Cooling mode MKP Mixer circuit pump and N, PE M(A) Mixer open M(Z) Mixer closed HKP Heating circuit pump and N, PE F8 Brine pressure switch Control inputs: EVU Power supply utility enable signal
Material losses
!
Only connect energy efficient circulation pumps ap-
proved by us. When using energy efficient circulation pumps not ap­proved by us, an external relay with a breaking capacity of at least 10A/250VAC or our relay set WPM-RBS is required.
Part no.:
UP 25/7.0 E 232942 UP 25/7.5 E 232943 UP 25/7.5 PCV 235949 UP 30/7.5 E 2339 47 WPKI-HK E 233602 WPKI-HKM E 233603
D0000076045
After connecting all electrical cables, refit and seal the cover over the mains terminal strip.
www.stiebel-eltron.com WPF basic | 25
Page 26
INSTALLATION
1 2 3 4 5 6 7 8 9 10 11 12 13
B1
B1
L N R RC L L’ N L N PE
Mounting
Connections X2: Low voltage
L1 L2 L3 N L1 L2 L3 L1’ L2’ L3’
ON
KS
Kühlen
B1
B1
1 2 3 4 5 6 7 8 9 10 11 12 13
B1 Temperature sensor heat pump flow B2 Temperature sensor heat pump return T (WW) DHW temperature sensor and earth T(A) Outside temperature sensor and earth T(MK) Mixer circuit temperature sensor and earth Fernb. 1 Remote control 1 Fernb. 3 Remote control 3 H BUS high L BUS low
BUS ground
“ + “ BUS “ + “
10.12.2 Electrical connection WPF S basic (single-phase)
Connection X3: Heat pump, electric booster heater and brine pump
L N R RC L L’ N L N PE
26�03�01�1581
Heat pump power supply (compressor)
L, N, PE
Heat pump with WPAB power supply
R, RC, N, PE
DHC power supply (electric booster heater)
L, L´, N, PE
Connected load Terminal assignment
3.0 kW L N PE
3.2 kW L´ N PE
6.2 kW L L´ N PE
SONKS
Kühlen
B1
B1
1 2 3 4 5 6 7 8 9 10 11 12 13
26�03� 01�1611
Brine pump power supply
L, N, PE
Material losses
!
When a single phase brine pump is connected, protect the heat pump and the DHC only via one common RCD. If no electric emergency/booster heater is connected, N must be tapped from X25 for the brine pump.
After connecting all electrical cables, refit and seal the cover over the mains terminal strip.
26 | WPF basic www.stiebel-eltron.com
Page 27
INSTALLATION
S
ONKSKühlen
1 2 3 4 5 6 7 8 9 10 11 12 13
B1
B1
Mounting
Connections X4: Control unit
L N R RC L L’ N L N PE
SONKS
Kühlen
Mains supply: L, N, PE Outputs: S Control output for the WPAB ON Compressor signal KS Brine pump signal Cooling Cooling mode MKP Mixer circuit pump and N, PE Pump 2. Heating circuit and N, PE M(A) Mixer open M(Z) Mixer closed HKP Heating circuit pump and N, PE Control inputs: EVU Power supply utility enable signal
B1
B1
1 2 3 4 5 6 7 8 9 10 11 12 13
Connections X2: Low voltage
L N R RC L L’ N L N PE
SONKS
Kühlen
B1 Temperature sensor heat pump flow B2 Temperature sensor heat pump return
26�03�01�1612
T (WW) DHW temperature sensor and earth T(A) Outside temperature sensor and earth T(MK) Mixer circuit temperature sensor and earth Fernb. 1 Remote control 1 Fernb. 3 Remote control 3 H BUS high L BUS low
BUS ground
“ + “ BUS “ + “
B1
B1
1 2 3 4 5 6 7 8 9 10 11 12 13
26�03�01�1613
Material losses
!
Only connect energy efficient circulation pumps ap-
proved by us. When using energy efficient circulation pumps not ap­proved by us, an external relay with a breaking capacity of at least 10A/250VAC or our relay set WPM-RBS is required.
Part no.:
UP 25/7.0 E 232942 UP 25/7.5 E 232943 UP 25/7.5 PCV 235949 UP 30/7.5 E 2339 47 WPKI-HK E 233602 WPKI-HKM E 233603
www.stiebel-eltron.com WPF basic | 27
Page 28
INSTALLATION
Mounting
10.12.3 Electrical connection of WPF S basic (single phase) to heat pump starting current limiter WPAB
To limit the starting current of the WPF S basic, the WPAB can be installed in the domestic distribution board. The WPAB limits the starting current to the values listed in the specification.
Material losses
!
When a WPAB is connected to the heat pump, remove the jumper between R and RC at terminal X3.
Material losses
!
When connecting a WPAB, use the same phase for L (ter­minal X3) of the compressor and L (terminal X4) of the controller; protect the unit with an RCD.
Wire in accordance with the following diagram.
3
R
RC
L1 S
ON
N
10.13 Fitting the casing parts
When fitting the casing parts, please proceed as follows:Close the cover of the control panel.Secure the cover by firmly tightening the fixing screws with
serrated washers.
Fit the cover to the appliance.After attaching the front cover, fix it to the side panels with
screws, as shown in the diagram. When attaching the front cover, fit the tab with its screws and serrated washers. The tab, screws and serrated washers can be found in the pack.
When attaching the front cover, ensure the earth conductor is
connected correctly.
2x
4x
X3
L R RCN
2 4
1
S P C
1~
X4
6
5
3
M
M1
1 WPAB 2 Heat pump 3 Power supply 1/N/PE 230V
NONS
1
2
3
1
2
2x
26�03�01�1575
1 Tab 2 Serrated washer 3 Screw
Appliance damage
!
The casing must stand on the floor free from the refrig­eration unit. D. h. That means, the six plinth screws must not be refitted.
26�03�01�0256
28 | WPF basic www.stiebel-eltron.com
Page 29

INSTALLATION

Mounting
10.14 installation
The temperature sensors have a decisive influence on the function of your heating system. Therefore ensure the correct seating and adequate insulation of sensors.
Outside temperature sensor AFS 2 (included in the pack supplied)
Install the outside temperature sensor on a north or north-eastern wall. Minimum distances: 2.5 m from the ground, 1 m to the side of doors and windows. The outside temperature sensor should be freely exposed to the elements, but should not be installed above windows, doors or air ducts and should not be subject to direct sunlight.
Connect the outside temperature sensor to terminal X2 (T(A)) and the earth terminal block X26 of the appliance.
Installation:
Remove the cover.Secure the lower part with the screw supplied. Connect the cable.Replace the cover. The cover must audibly click into place.
PTC sensor resistance values
The sensors installed in the appliance (return, flow and source sensors), the outside temperature sensor AFS 2, the contact sen­sor AVF 6 and the PTC immersion sensor TF 6A all have identical resistance values.
Temperature in °C Resistance in Ω
-20 1367 –10 1495 0 1630 10 1772 20 1922 25 2000 30 2080 40 2245 50 2417
26�03�21�0052
60 2597 70 2785 80 2980 90 3182 100 3392
10.15 High limit safety cut-out for underfloor heating systems STB-FB
Material losses
!
In case of failure, in order to prevent an excessively high flow temperature in the underfloor heating system, we generally recommend the use of a safety temperature controller to limit the system temperature.
Contact sensor AVF 6
This sensor is required when using a mixer circuit.
Installation information:
Clean the pipe.Apply heat conducting paste.Secure the sensor with a cable tie.
26�03�01�1431
www.stiebel-eltron.com WPF basic | 29
Page 30
INSTALLATION
Fernb.3
Fernb.1

Commissioning

10.16 Remote control FE7
Connection array FE7
123
The FE 7 remote control enables you to adjust the set room tem­perature for heating circuit 1 or heating circuit 2 by ± 5 °C in automatic mode only. You can also change the operating mode. Connect it to the terminals Rem.con.1, and Rem.con.3 at terminal block X2 and the earth terminal block X26 of the appliance.
10.17 Remote control FEK
11. Commissioning
Note
Does not apply to WPF5 (S) basic. When quick start is used, the starting resistors are not patched in.
Do not use quick start when measuring the starting
current.
Only heating contractors may carry out the adjustments on the heat pump manager commissioning list, commission the appliance and instruct the owner in its use.
Commissioning is to be carried out in accordance with these instal­lation instructions and the operating and installation instructions of the heat pump manager. Our customer service can assist in the commissioning, which is chargeable.
Where this appliance is intended for commercial use, the rules of the relevant Health & Safety at Work Act may be applicable
26�21�01�0008
for commissioning. For further details, check your local author­ising body.
After commissioning, complete the commissioning report that are part of these instructions.
11.1 Checks before commissioning
Before commissioning check the points detailed below.
Appliance and system damage
!
In cooling mode, the WPF requires the FEK for area cool­ing systems, e.g. underfloor heating systems, chilled ceilings, etc. Apart from the room temperature, it also determines the dew point temperature to prevent con­densation.
Connection array FEK
2
L
3
4
+
1
H
The FEK remote control enables you to change the set room tem­perature for heating circuit 1 or heating circuit 2 by ± 5 °C as well as the operating mode. Connect it to terminals H, L, I and + at the terminal block X2 of the appliance.
5
6
11.1.1 Heating system
- Have you filled the heating system to the correct pressure, and opened the quick-acting air vent valve?
System damage
!
Observe the maximum system temperature in underfloor heating systems.
11.1.2 Heat source
System damage
!
With an underfloor heating system, never use the heat pump to dry the screed as this places such a high demand on the heat source that the frost protection function may respond. See also chapter “Commissioning the heat pump manager / Parameter HEAT-UP PROG”.)
11.1.3 High limit safety cut-out
At ambient temperatures below -15°C it may happen that the high limit safety cut-out triggers the emergency/booster heater.
Check whether the high limit safety cut-out has responded.
26�03�01�0094
30 | WPF basic www.stiebel-eltron.com
Page 31
INSTALLATION
Commissioning
1
2
1 High limit safety cut-out reset button 2 Electric emergency/booster heater
Reset the high limit safety cut-out by pressing the reset
button.
11.1.4 Temperature sensor
- Have you correctly located and connected the outside tem­perature sensor and the return temperature sensor (in con­junction with a buffer cylinder)?
11.1.5 Power supply
- Have you correctly connected the power supply?
- The compressor turns in the right direction if, when volt­age is applied to the heat pump power supply (mains), no fault message appears in the display. If the fault message NO OUTPUT appears, reverse the rotational direction of the compressor.
11.2 Heating curve adjustment during commissioning
The efficiency of a heat pump decreases with rising flow temper­ature. The heating curve should therefore be adjusted with care. Heating curves that are adjusted too high lead to the zone and thermostatic valves closing, which may lead to the minimum flow rate required for the heating circuit not being achieved.
The following steps will help you to adjust the heating curve cor­rectly:
- Fully open thermostatic or zone valves in a lead room (e.g. living room or bathroom). We do not recommend installing thermostatic or zone valves in the lead room. Control the temperature for these rooms via remote control.
- At different outside temperatures (e.g. -10 °C and +10 °C), adjust the heating curve so the required temperature is set in the lead room.
Standard values for a start:
Parameter Underfloor heating
system
Heating curve 0,4 0,8 Controller dynamics 5 15 Room temperature 20 °C 20 °C
Heating system with radiators
Note
If no remote control is installed, raising the parameter “room temperature” leads to a parallel offset of the heat­ing curve.
Increase the parameter “HEATING CURVE” if the room temperature is not high enough when outside temperatures are low.
If the parameter “Heating curve” has been raised, adjust the zone or thermostatic valve in the lead room to the required temperature at high outside temperatures.
26�03�01�1893
Note
Never reduce the temperature in the entire building by closing all zone or thermostatic valves, but by using the setback programs.
11.3 Operation and control
Appliance and system damage
!
Never interrupt the power supply outside the heating period. The system‘s active frost protection is not guar­anteed if the power supply is interrupted.
The system should not be switched off in summer. The heat pump manager has an automatic summer / winter changeover.
11.4 Taking the appliance out of use
If the appliance is to be taken out of use, set the heat pump manag­er to standby. This retains the safety functions designed to protect the system (e.g. frost protection).
Appliance and system damage
!
If the heat pump and frost protection are completely switched off, drain the system on the water side.
If the room temperature in spring and autumn is too low (approx. 10 °C outside temperature), the parameter “Room temperature” must be raised.
www.stiebel-eltron.com WPF basic | 31
Page 32
INSTALLATION
Commissioning
11.5 Heat pump manager commissioning summary
(Control level 3)
No. Parameter (shown in the display)
FIRST STARTUP
1
2
3
4
5
6
ENTER CODE
LANGUAGE GERMAN --- BACK
CONTRAST
DISPLAY ACTUAL RTRN T OUTSIDE TEMP DAY DHW TEMP MIXER TEMP
EMERG OPERTN ON / OFF
Note
The COOLING MODE parameter must only be set if there is a suitable hydraulic circuit.
COOLING OP ON / OFF PASSIVE FA N AREA BACK
COOLINGMODE
SET ROOM T SET ROOM T
SET FLOW TEMP SET FLOW TEMP
HYSTERESIS HYSTERESIS
ON / OFF ACTIVE FAN AREA BACK
SET ROOM T SET ROOM T
SET FLOW TEMP SET FLOW TEMP
HYSTERESIS HYSTERESIS
DYNAMIC DYNAMIC
HEAT-UP PROG ON / OFF LOW END TEMP LOW END DURAT MAX HEAT-UP T MAX HUT TIME
7
BACK INCREASE/DAY
SUMMER MODE ON / OFF BUILDING TYPE OUTSIDE TEMP BACK
8
PUMP CYCLES ON / OFF
9
BU PUMP CONST ON / OFF
10
11
12
13
14
15
FIXED VALUE OFF / °C
SOURCE ETHYLENE GLYCO
MIN SRCE TEMP °C
RETURN MAX °C
MAX HTG FLOW T °C
POTASS CARB
ALM 0 ALM 30 ALM 60
WATER ALM 180 ALM 120
16
32 | WPF basic www.stiebel-eltron.com
HP SENSOR BAR
Page 33
INSTALLATION
Commissioning
17
18
19
20
21
22
23
24
25
26
27
28
29
MIXER MA X °C
MIXER DYNAMIC
FROST PROTECT °C
SELECT REM CON
FE CORRECTION °C
ROOM INFLUENCE °C
HEATING LIMIT OFF / °C
DUAL-MODE HTG °C
DHW LIMIT °C
DUAL-MODE DHW °C
DHW ECO ON / OFF BACK
DHW HYSTERESIS °C
DHW CORRECTION °C
HEATING CIR-
CUIT 1
HEATING CIRCUIT 2
PASTEURISATION ON / OFF
30
CNTRL DYNAMIC
31
32
33
34
35
36
37
38
39
40
41
42
IDLE TIME MIN
REM IDLE TIME
SINGLE PHASE ON / OFF
QUICK START
RELAY TEST DHW PRIM PUMP RELAY TEST IWS ----- BRINE PUMP BACK
LCD TEST
FAULT LIST FAULT 1 --- FAULT 20 BACK
WPMIW SOFTWARE
ANALYSIS
DIAGNOSIS
HEAT P RESET
43
www.stiebel-eltron.com WPF basic | 33
RUNTIMES
BACK
Page 34
INSTALLATION
Commissioning
11.6 Heat pump manager commissioning
General information
Not only the adjustments at control level 2 but also the system-spe­cific parameters must be determined as part of commissioning the heat pump system. These parameters are adjusted at control level 3, access to which is protected by code.
Note
The heat pump manager should be in standby mode dur­ing commissioning. This prevents an uncontrolled heat pump start. Please remember to reset the system into its last operating mode.
Check all parameters in sequence, and enter all selected values into the column (system value) provided in the commissioning report.
Note
Not all adjustments take immediate effect. Some adjust­ments only become effective in certain situations or after a delay.
1 CODE
Enter the correct four-digit code to change parameters at control level 3. The factory-set code is 1 0 0 0.
After pressing PRG (indicator illuminates), the first digit can be selected by turning the rotary selector. Pressing PRG again con­firms the value, then the second digit of the code begins to flash. Turning the rotary selector enables the second digit of the code to be entered, etc. When all four digits have been entered correctly, four lines appear in the display. This enables access to control level 3, and the display shows CODE OK. Closing and re-opening the flap requires that the code is entered again. Checking settings does not require the code to be entered.
2 LANGUAGE
Here you can select the menu language.
Press PRG.Select required language.Confirm with PRG.
5 EMERGENCY MODE
Characteristics in case of “Fatal Error” conditions in conjunction with the emergency operation:
The EMERGENCY MODE parameter can be set to ON or OFF.
Emergency mode set ON:
The program selector automatically changes over to emergency mode as soon as faults occur and the heat pump fails.
Emergency mode set OFF:
The booster heater takes over the frost protection of the central heating system, as soon as faults occur and the heat pump fails. Users can then select emergency mode on their own initiative.
6 COOLING MODE
WPF 5 - 16
This equipment is designed for DHW and central heating. In the delivered condition, the COOLING MODE parameter is set to OFF. Cooling mode is only possible in conjunction with a suitable hy­draulic circuit.
Appliance and system damage
!
The COOLING MODE parameter must only be set if there is a suitable hydraulic circuit.
Note
The COOLING MODE parameter will only be shown if a FEK or FE7 remote control is connected. The cooling mode is only possible in summer.
The WPF with a suitable circuit cools in 2 stages:
Stage 1 (source pump)
Heat is extracted from the heating circuit and is passed to the heat source system.
Stage 2 (source pump + compressor)
In addition, the cooling circuit extracts heat from the heating cir­cuit and transfers it to the heat source system.
3 CONTRAST
The display contrast can be adjusted here.
Use the rotary selector to adjust the contrast.
4 DISPLAY
Select, what will be displayed when the programming unit flap is closed. The options are:
- outside temperature,
- return temperature,
- day and time,
- DHW temperature or
- mixer temperature.
34 | WPF basic www.stiebel-eltron.com
DHW heating
DHW heating always has priority. As long as the actual temper­ature has not dropped below the set flow and room tempera­ture, active cooling continues even during DHW heating, and any extracted heat is transferred to the DHW. If there is no cooling demand, DHW is conventionally heated via the heat source system.
Cooling operation with the FE 7
The FE7 is not equipped with dew point monitoring. It can there­fore only be used in conjunction with fan convectors with conden­sate drain. Set the cooling mode to FAN.
Cooling operation with the FEK
The FEK remote control is equipped with dew point monitoring, and can therefore be used with area heating systems (e.g. under­floor/wall heating systems, etc.). Set parameter 6 to AREA. The
Page 35
INSTALLATION
Commissioning
set flow temperature is compared with the captured dew point temperature, so the actual temperature never drops below the dew point. When using fan convectors with the FEK remote control, set the COOLING MODE parameter to FAN.
The following settings for the FE 7 and the FEK can be selected for the cooling operation in parameter 6:
- Room temperature Cooling starts when the selected room temperature is ex­ceeded (output COOLING=230 V). Cooling is stopped, if the actual room temperature drops 2 K below its set temperature. (output COOLING=0 V)
- Flow temperature and hysteresis The cooling operation is regulated via the selected flow tem­perature. The brine pump starts at: [flow temperature + hysteresis] Brine pump off, when the actual temperature drops below the flow temperature. The [flow temperature+hysteresis] should be at least 3 K < room temperature. Lower flow temperatures cause a more rapid cooling of the room. As soon as, with setting AREA, the determined dew point temperature is + 2 K higher than the selected flow tempera­ture, that temperature will be overridden with the dew point temperature and acts as controlled variable. The brine pump starts at [entered or newly determined flow temp. + hyster­esis]. The source pump stops and the cooling operation termi­nates, if the actual flow temperature lies below the entered or newly determined flow temperature. The cooling signal remains active.
- Dynamic Dynamics can be adjusted from 1 to 10. It describes the delay between stage 1 and stage 2, whereby the second stage is started sooner, the smaller the value.
7 HEAT-UP PROG
Heat-up program for underfloor heating systems
Never use the heat pump to dry the screed as this places such a high demand on the heat source that the frost protection function may respond. The electric emergency/booster heater must be used for the heat-up program. For this, set parameters HEATING LIMIT and DUAL-MODE HTG to 30°C and start the heat-up program.
Emergency mode cannot be enabled in the heat-up program.
There are a total of 6 parameters for the heat-up program. These 6 parameters can be adjusted in sequence as soon as the heat-up program is activated. This program is started with the parameter HEAT-UP PROG and with the setting ON. The system then heats to the selected low end temperature (parameter LOW END TEMP). The low end temperature is then held for the set period (parameter LOW END DURAT). After expiry of this period, the system heats with an increase K/day (parameter INCREASE/DAY) to the maxi­mum low end temperature (parameter MAX. HEAT-UP T) and is held at the maximum temperature via the selected time (param­eter MAX T DURATION). After expiry of this period, the system reduces the temperature back to the low end temperature in the same stages as per heat-up. This concludes the heat-up program. As soon as two heating circuits are operational, both will be op­erated in accordance with this heat-up program (operation with buffer cylinder and mixer circuit). Direct heating circuit 1 (buffer circuit with return sensor) adopts the heat-up program’s set val-
ues. The actual temperature inside the buffer cylinder is higher at the heating flow, since it is regulated via the return sensor. The mixer (heating circuit 2) regulates the temperature back down to the selected set values in the heat-up program (low end temper­ature and maximum temperature).
3
1
2
6
Y Temperature X Time 1 Maximum temperature 2 Low end temperature 3 Low end temperature rise period 4 Increase K/day 5 Maximum temperature duration 6 Start 7 End
Please note that only the mixer circuit pump is running when operating with two heating circuits.
The return sensor is again used for control, when only the direct heating circuit 1 is operational. As the actual temperature inside the buffer cylinder is higher at the heating flow, this constellation sees 5 K being deducted from the set heat-up program values (low end and maximum temperatures).
The summer logic is disabled whilst the heat-up program runs
4 5
7
8 SUMMER MODE
The summer mode parameter allows you to select the time from when the heating system should change into summer mode. Sum­mer mode can be switched ON or OFF. This function offers two adjustable parameters.
The “Building Type” parameter determines, subject to building type (setting 1, 2 or 3), an adjusted outside temperature. If the calculated outside temperature ≥ the selected outside tempera­ture, both heating circuits (if installed) switch to summer mode; reset hysteresis –1 K. SUMMER MODE is shown in the display when the flap is closed.
With set-value control, summer mode is disabled for heating cir­cuit 1.
OUTSIDE TEMP parameter:
Available outside temperature 10 °C to 30 °C
BUILDNG TYPE parameter:
Setting 1: Mild adjustment of the outside temperature (averag­ing over a 24 h period), e.g. timber construction with rapid heat transfer.
84�03�01�0038
www.stiebel-eltron.com WPF basic | 35
Page 36
INSTALLATION
Commissioning
Setting 2: Moderate adjustment of the outside temperature (av­eraging over a 48 h period), e.g. solid construction with thermal insulation and average heat transfer.
Setting 3: Severe adjustment (averaging over a 72 h period) of the outside temperature, e.g. house with slow heat transfer.
< -10
-10
9 PUMP CYCLES
Heating circuit pump control
The PUMP CYCLES parameter only applies to the direct heating circuit 1, i.e. for heating circuit pump 1.
This parameter can be set ON or OFF . In setting OFF the heating circuit pump will not cycle. Instead, it will operate constantly and is only switched off in summer mode.
The heating circuit pump start will be controlled in accordance with a fixed temperature curve of the outside temperature, as soon as this parameter is set to ON.
The heating circuit pump start pulse is always five minutes.
The heating circuit pump for heating circuit 1 always starts with each heat pump start. The pump runs on for 5 minutes after the heat pump has been switched OFF. Now the start-up duration is brought to bear, e.g. at an outside temperature of 5 °C, the pump starts three times per hour for five minutes respectively.
Pump kick
To prevent the pumps seizing up, over the summer for example, when a pump has been switched off for 24 hours it will be switched back on for 10 seconds. This applies to all pumps.
Heating circuit pump control with connected FE7/FEK remote control
In conjunction with the FE7 or FEK remote control, the respec­tive heating circuit pump is switched off and the mixer moves to “Closed” in accordance with the switching condition
ϕ
ACTUAL room >ϕSET room
the respective heating circuit pump is switched OFF and the mixer moves to “CLOSE”. This only applies if the room sensor influence is set to K > 0. Reverse control is subject to the following condition:
ϕ
ACTUAL room >ϕSET room
The summer mode also becomes effective for the respective heat­ing circuit when operating with a FE7 or FEK remote control.
+ 1 K
-5
0
5
Y
10
0 10 20 30 40 50 60
1
2
Y Outside temperature in °C X Time in minutes 1 Pause 2 Pump run time
10 BU PUMP CONST
When using a buffer cylinder, set this parameter to OFF.
11 FIXED VALUE
Fixed value temperature
The heat pump return is controlled at the set fixed value. The switching time program will then be ignored. The various program switch positions will then only affect the mixer circuit (if installed). The frost protection is activated and the compressor is switched OFF when the program selector is set to “Standby” and a fixed temperature has been selected. Summer logic remains disabled with fixed temperature control. This means that the heating circuit pump is not switched off for the direct heating circuit. With the flap closed, the display shows the fixed temperature program, in other words always showing the heating times.
12 SOURCE
Frost protection for brine|water heat pumps
The heat pump can only be operated as ground source heat pump.
Ethylene glycol as brine (including polypropylene glycol) means that the heat pump frost protection is inactive. Responses by the frost stat no longer have any influence.
Potassium carbonate as brine (STIEBEL ELTRON heat trans­fer medium) means that the heat pump frost protection is in­active. This ensures that the source pump is started at an outside temperature of -10°C, even if the heat pump is idle. It is switched OFF again at an outside temperature of – 8 °C.
ALM 0, 30, 60, 120 and 180
(Only in conjunction with the extractor module LWM 250)
At a brine inlet temperature of < 10 °C, a regeneration of the heat source system can be implemented in conjunction with the ex­tractor module and ethylene glycol or propylene glycol as brine. Settings enable the determination of the run-on time of the brine pump, after the heat pump has been shut down. The values stated correspond to the run-on time in minutes at an average brine inlet temperature of 0 °C.
84�03�01�0039
36 | WPF basic www.stiebel-eltron.com
Page 37
INSTALLATION
Commissioning
Sett ing Brine pump run-on time
ALM 0 1 minute ALM 30 30 minutes ALM 60 60 minutes ALM 120 120 minutes ALM 180 180 minutes
If the brine inlet temperature rises, the resulting run-on time of the source pump reduces accordingly. If the brine inlet temperature drops, the run-on time increases. From a brine inlet temperature of 10 °C, the run-on time will always be at least one minute.
Brine pump run-on time with extractor module
400
350
300
250
200
150
100
50
0
-6 -5 -4 -3 -2 -1 0123 4567 8 9 10
Y Brine pump run-on time [minutes] X Brine inlet temperature [°C] 1 ALM 30 2 ALM 60 3 ALM 120 4 ALM 180
1
2
3
4
13 MIN SRCE TEMP
Setting range -10 °C to +10 °C and setting OFF.
Appliance and system damage
!
Never operate the appliance with source temperatures below – 9 °C.
In the OFF position there is no scanning via the source sensor temperature.
The compressor shuts down and the idle time is set, when the ac­tual temperature drops below the minimum source temperature. The compressor is enabled again after the idle time has expired and the fixed hysteresis of 2 K has been exceeded.
This fault, i.e. MIN SRCE TEMP, will be indicated in the display by a flashing warning triangle, and will be entered into the fault list.
The source pump will always be started 30 seconds earlier than the compressor, which starts when there is a heat demand coming from the central heating or DHW side.
Note
The source pump runs on for 60 minutes after the heat pump has been switched OFF.
14 RETURN MAX
Maximum return temperature
Setting range 20 °C to 55 °C
If the temperature at the return sensor reaches this value during heating operation, the heat pump is switched OFF immediately. This safety function prevents the high pressure limiter responding. No fault message is triggered when this value is reached.
The return temperature is not scanned during DHW operation.
15 MAX HTG FLOW T
Maximum heat pump flow temperature for central heating
Setting range 20 °C to 65 °C
This setting limits the flow temperature of the heat pump and the electric booster heater during the heating operation.
16 HP SENSOR
Maximum high pressure
Setting range 38 bar to 40 bar.
This setting limits the high pressure during DHW or central heat­ing. The system implements a controlled shutdown when the maximum high pressure is reached.
See also DHW ECO.
84�03�01�0016
17 MIXER MAX
Maximum mixer flow temperature
Setting range 20 °C to 90 °C
This setting limits the mixer circuit’s flow temperature. For exam­ple, if a higher set flow temperature is calculated from the mixer circuit data, the max. set mixer flow temperature will be used to control and regulate to this value.
18 MIXER DYNAMIC
Mixer runtime
Setting range 60 to 240
This setting can be used to adapt the mixer characteristics. The setting 60 to 240 means 6 K to 24 K control deviation.
The system scans every 10 s, and the minimum ON time for the mixer is 0.5 s. The mixer does not respond inside the dead zone of ±1 K from the set value.
Example for the setting 100 = 10 K
The control deviation (set mixer temperature – actual mixer tem­perature) is 5 K. The mixer opens for 5 s, then pauses for 5 s and starts again from the beginning.
The control deviation (set mixer temperature – actual mixer tem­perature) is 7.5 K. The mixer opens for 7.5 s, then pauses for 2.5 s and starts again from the beginning.
The smaller the control deviation, the shorter the mixer ON time and the longer its pauses.
A reduction of the MIXER DYNAMIC value with static control devi­ation increases the ON duration and reduces pauses.
www.stiebel-eltron.com WPF basic | 37
Page 38
INSTALLATION
Commissioning
Example of setting 100 and a current control deviation of 5 K.
5 K of 10 K = 50% = ON duration
Example of a control deviation
1
± 1 K
2
4
3
1 Setting 100 = control deviation 10 K 2 Control deviation 5 K 3 Control deviation in K 4 ON time in %
19 FROST PROTECT
The heating circuit pumps are started at the selected frost protec­tion temperature, to prevent the heating system being damaged by frost; the reverse hysteresis is 1 K.
20 SELECT REM CON
Remote control FE7 can be selected for both heating circuits
The SELECT REM CON parameter can be used to preselect the heat­ing circuit with which the remote control is to be used. Under the parameter ROOM T 1 OR 2 at control level 2, you can scan the ac­tual room temperature, subject to the remote control preselection.
21 FE CORRECTION
This parameter enables the calibration of the actual room tem­perature.
22 ROOM INFLUENCE
Room influence for the FE 7 remote control unit
Standard setting 5 adjustable from ----via 0 to 20 dashes (----) in the display:
With the FE7 remote control connected, the room temperature sensor only serves to record and display the actual room temper­ature; it has no influence on the actual control. Only in automatic mode can the room temperature for heating circuit 1 or 2 be adjusted by ± 5 °C. This set value adjustment applies to the then current heating time, not to the setback time.
At the same time, setting “0 to 20” serves to control the room tem­perature-dependent night setback. This means that the heating circuit pump is switched OFF at the point of changeover from the heating into the setback phase. It remains OFF, until the actual room temperature falls below the set room temperature. After­wards, the system regulates in weather-compensated mode.
If you want the room temperature to be taken into account, set the room temperature sensor influence to > 0. The room sensor influence has the same effect as the outside temperature sensor has on the return temperature, only this effect is 1 to 20 times greater by the set factor.
Room temperature-dependent return/flow temperature with weather compensation
With this type of control, a control cascade is formed from a re­turn/flow temperature control that is subject to both weather and
C26�03�01�1067
room temperature. Consequently the weather-compensated re­turn/flow temperature control sets a default return/flow temper­ature that is corrected by the overriding room temperature control in accordance with the following formula:
= (ϕ
∆ϕ
R
Because a substantial proportion of the control is already handled by the weather-compensated control unit, the room temperature sensor compensation factor K can be set lower than with pure room temperature control (K = 20). The figure below indicates the control method with the set factor K=10 (room influence) and a heating curve S=1.2.
Room temperature control with weather-compensation
This type of control offers two main benefits:
Incorrectly set heating curves are corrected by the room sensor in­fluence K; whilst the smaller factor K provides more stable control.
However, observe the following for all control units with room temperature sensor influence:
- The room temperature sensor must capture the room tem­perature accurately.
- Open doors and windows greatly affect the control result.
- All radiator valves in the lead room must be fully open at all times.
- The temperature inside the lead room is the one which af­fects the entire heating circuit.
If you want the room temperature to be taken into account, set the room temperature sensor influence to > 0.
RSET
− ϕ
RACTUAL
) * S * K
38 | WPF basic www.stiebel-eltron.com
Page 39
INSTALLATION
Commissioning
90
80
70
1
60
1
50
1
40
30
20
10
Y
0
X 1
20
1917 18 21 22 23 24 25
3
4
5
Y
X 2
10
15
20
2
-10
-5
0
5
-20
-15
Y Flow temperature [°C] X 1 Room temperature [°C] X 2 Outside temperature [°C] 1 Room temperature sensor influence at K = 10 and S = 1.2
and control deviation +/- 2 K 2 Heating curve S = 1.2 3 Weather-compensated set flow temperature at ϕA = -10 °C 4 Weather-compensated set flow temperature at ϕA = 0 °C 5 Weather-compensated set flow temperature at ϕA =
+10°C
23 HEATING LIMIT
Heat pump application limit
The heat pump is switched off if the outside temperature drops below the selected lower application limit for heating.
Only the electric booster heater provides central heating.
24 DUAL-MODE HTG
The dual-mode temperature of the heat pump for heating oper­ation
Below this outside temperature, the electric booster heater is added for central heating, subject to load.
25 DHW LIMIT
Heat pump application limit
The heat pump is switched off at outside temperatures below the selected lower DHW application limit.
Only the electric booster heater provides DHW heating.
26 DUAL-MODE DHW
The dual-mode temperature of the heat pump for DHW operation
Below this outside temperature, the electric booster heater is added for DHW heating, subject to load.
27 DHW ECO
temperature of 70 °C is achieved in this operating mode, DHW heating will be terminated, and the set DHW temperature is over­written with the actual DHW temperature.
Setting ON
DHW heating will be terminated and the set DHW temperature is overwritten with the actual DHW temperature, as soon as the heat pump is shut down in DHW mode via the high pressure sensor or via the hot gas temperature limit (130 °C). This operating mode saves energy, as DHW is exclusively heated by heat pump.
28 DHW HYSTERESIS
26�03�01�1917
This determines the switching hysteresis for DHW operation.
- Starting DHW heating at the set DHW temperature minus the hysteresis value.
29 DHW CORRECTION
The DHW temperature is measured in the bottom third of the cylinder. The DHW outlet temperature is approx. 3K higher than the measured temperature. This deviation is corrected and can be calibrated, if required.
30 PASTEURISATION
The DHW cylinder is heated daily at 01:00 h to 60 °C, if pasteurisa­tion has been enabled. Pasteurisation can only be achieved with the heat pump and direct electric heating (internal DHC stages).
31 CNTRL DYNAMIC
Setting range 0 to 30
The selected control dynamic is a measure of the switching interval between the compressor and the booster heating stages. Nor­mally, the selected response time should be sufficiently fast and without oscillation. Heating systems that respond quickly require a lower value, whilst very slow responding systems require you to set a higher value.
32 COMP IDLE TIME
After a heat pump has been switched OFF, an idle time is set as protection for the compressor. The default idle time of 20 minutes should normally not be reduced. Where a reduction is required because of adjustments or repair work, reset the idle time again to 20 minutes after completing the necessary work.
33 REM IDLE TIME
Remaining idle time
Pressing PRG enables you to scan the compressor idle time.
34 SINGLE PHASE
This parameter must always be set to ON for single phase appli­ances.
DHW learning function
Setting OFF
When heating DHW, the system automatically adjusts itself to the required DHW temperature (self-learning function).
The electric booster heating system will be added as booster stage as soon as the heat pump is shut down in DHW mode via the HP sensor or via the hot gas temperature limit (130 °C). If the flow
35 QUICK START
During commissioning, you can test the heat pump function by triggering a heat pump quick start. When this parameter is start­ed, OFF appears at the bottom of the display. Pressing PRG in­itiates a quick start. The respective pumps are started after the heat pump start. The value 60 is visibly counted down to 0 on the display; then the display shows ON.
www.stiebel-eltron.com WPF basic | 39
Page 40
INSTALLATION
Commissioning
After that, the heat pump and the associated buffer primary pump are switched ON. You terminate this function by pressing PRG or by closing the control flap. OFF is displayed again.
36 RELAY TEST
Pressing PRG and continuing to turn the rotary selector allows you to control the WPMiw relay outputs individually. The individual outputs are displayed as plain text.
37 LCD TEST
Pressing PRG once initiates an LCD test. All display elements are displayed in sequence.
38 FAULT LIST
The first fault code is displayed by pressing the PRG key. The fault is described in plain text at the top of the display, the bottom shows the fault number. Continuing to turn the rotary selector still displays fault 1. As additional information, the display shows the day, month and year together with the relevant time, when the fault occurred.
In total, 20 faults can be displayed. You can reset the fault list via a hardware reset.
Example:
The high pressure switch has responded on the 07/17/09 at 14:50 h representing the latest fault in the heat pump.
pressing PRG. The compressor starts again. The fault remains stored in the fault list.
43 RUNTIMES
Under the RUNTIMES parameter, you can scan the heat pump values. These values can only be reset via a hardware reset.
WPMIW INFO Meaning
RNT COMP HTG Runtime - compressor heating mode RNT COMP DHW Runtime - compressor in DHW mode RUNTIME DHC 1 DHC runtime stage 1 RUNTIME DHC 2 DHC runtime stage 2 RUNTIME DHC 1 2 DHC runtime stage 1 and 2 RNT COMP COO Runtime - compressor in cooling mode EL OUTPUT DAY Electrical output of compressor in heating mode since
0:00 h today.
TTL EL OUTPUT Total electrical output of compressor in heating mode.
EL OUTPUT DAY Electrical output of compressor in DHW mode since
0:00 h today.
TTL EL OUTPUT Total electrical output of compressor in DHW mode
HP SENSOR MAX
39 WPMIW SOFTWARE
Display of the current software version.
40 ANALYSIS
The bottom of the display shows the enabled stages. The two-digit display shows the control unit’s internal calculation. A stage will be switched every time the counter has counted down to zero. This calculation depends on the controller dynamics and the control deviation. For this, see controller dynamics.
41 DIAGNOSIS
Pressing PRG indicates whether a FEK is connected and which heat pump type has been connected.
42 HEAT P RESET
The heat pump can be reset if a fault occurs. That fault is reset by pressing PRG and setting the system to ON, followed by repeatedly
40 | WPF basic www.stiebel-eltron.com
Page 41
INSTALLATION
Commissioning
11.7 WPMiw commissioning report
No. Parameter Sett ing range Standard System value
1 Enter code 0000 to 9999 1000 2 Language German 3 Contrast -10 to +10 0 4 Display Actual return 5 Emergency mode ON / OFF OFF 6 Cooling mode ON / OFF OFF 7 Heat-up program ON / OFF OFF 8 Summer mode ON / OFF ON 9 Pump cycles ON / OFF OFF 10 Buffer primary pump – constant run ON / OFF ON 11 SET FIXED VALUE OFF / °C OFF 12 Source Ethylene glycol 13 MIN source temperature -10 °C to 10 °C -9 °C 14 Maximum return temperature 20 °C to 55 °C 50 °C 15 Maximum heating flow temperature 20 °C to 65 °C 60 °C 16 HP sensor 38 bar to 40 bar 38 bar 17 Maximum mixer temperature 20 °C to 90 °C 50 °C 18 Mixer dynamic 30 - 240 100 19 Frost protection -10 °C to 10 °C 4 °C 20 Select remote control Heating circuit 1 21 FE correction -5 K to +5 K 0 22 Room influence 0 to 20 5 23 Temperature limit, heating OFF to 30 °C OFF 24 Dual mode temperature, heat source 2 -20 °C to 30 °C -20 °C 25 Temperature limit, DHW OFF to 30 °C OFF 26 Dual mode temperature, DHW -20 °C to 30 °C -20 °C 27 DHW eco ON / OFF OFF 28 DHW hysteresis 1 °C to 10 °C 3 °C 29 DHW correction 1 K to 5 K 3 K 30 Pasteurisation ON / OFF OFF 31 Controller dynamics 1 – 30 20 32 Idle time af ter switching the compressor OFF 1 to 120 min 20 min 33 Remaining idle time 34 Single phase ON / OFF OFF 35 Quick start 36 Relay test 37 LCD test 38 Fault list 39 WPMiw software issue 40 Analysis 41 Diagnosis 42 Heat pump reset 43 Runtimes
www.stiebel-eltron.com WPF basic | 41
Page 42
INSTALLATION

Settings

12. Settings
12.1 Standard settings
At the factory, the heat pump manager is programmed with the following standard settings:
Switching times for heating circuit 1 and 2 (day mode) Only the first switching time pair is preprogrammed.
Standard Setting range Monday - Friday 6:00 - 22:00 00:00 – 23:59 Saturday - Sunday 07:00 – 23:00 00:00 – 23:59
Room temperature 1 and 2 Standard sett ings are without night setback.
Room temperature in day mode 20 °C 5 – 30 °C Room temperature in night mode 20 °C 5 – 30 °C
DHW program switching times
Monday - Sunday 0:00 – 24:00 00:00 – 23:59
DHW temperature
DHW day temperature 47 °C 10 – 60 °C DHW night temperature 10 °C 10 – 60 °C
Heating curve slope
Heating curve 1 0,6 0 - 3 Heating curve 2 0,2 0 - 3
12.2 Heating and DHW programs
You may enter your individual programs into the following tables.
12.2.1 Heating program, heating circuit 1
12.2.2 Heating program, heating circuit 2
Switching time pair I
Mo
Tu
We
Th
Fr
Sa
Su
Mo - Fr
Sa - Su
Mo - Su
Switching time pair II
Switching time pair III
12.2.3 DHW program
Switching time pair I
Mo
Tu
We
Th
Switching time pair II
Switching time pair III
Switching time pair I
Mo
Tu
We
Th
Fr
Sa
Su
Mo - Fr
Sa - Su
Mo - Su
Switching time pair II
Switching time pair III
Fr
Sa
Su
Mo - Fr
Sa - Su
Mo - Su
12.3 Appliance handover
Explain the function of the appliance to users and familiarise them with its operation.
Note
Hand over these operating and installation instructions to the user for safe-keeping. All information in these instructions must be closely observed. The instructions provide information on safety, operation, installation and maintenance of the appliance.
42 | WPF basic www.stiebel-eltron.com
Page 43
INSTALLATION

Troubleshooting

13. Troubleshooting
13.1 Fault display
Faults/errors in the system or in the heat pump are indicated on the display. All parameters required for an in-depth system analy­sis can be checked under the system menu items COMMISSIONING and TEMPERATURES. For troubleshooting, analyse all available parameters before opening the heat pump control panel.
The controller will not indicate that the booster heater high limit safety cut-out has responded. The high limit safety cut-out can be reset by your contractor through pressing the reset button. The high limit safety cut-out response is generally caused by air in the heating circuit or an inadequate heating flow rate.
Check the heating flow rate and ventilate the heating system.
13.1.1 Heat pump-specific or hardware faults
All faults are displayed.
Example: High pressure fault
HP SENSOR MAX
Observe the list under system parameter TEMPERATURES.
Sensor Fault code
Outside temperature E 75 Remote control E 80 Actual DHW temperature E 76 Actual heat pump return temperature (H1) E 73 Actual mixer flow temperature (H2) E 70 Actual heat pump flow temperature E 72 Actual source flow temperature E 71 High pressure sensor E 130 LP sensor E 128
13.1.3 Fault message with DCO enabled
In connection with the dial-up connection controller DCO enabled, the sensor faults listed above result in the transmission of the error codes (E75 to E130) by SMS to the authorised recipient.
In addition, the following fault codes are transmitted as text mes­sage:
Contactor stuck E 20 No power E 21 Low pressure E 22 HIGH PRESSURE E 23 HP sensor max E 24
1
1 Fault message (flashing)
All faults cause the heat pump to shut down. The idle period will be set and, with the exception of MAX HOT GAS T, ALl faults are written to the fault list.
13.1.2 Sensor break = sensor fault
SENSOR BROKEN
1
1 Fault message (flashing)
Note
This fault code refers to temperature sensors that can be called up under the parameter TEMPERATURES. These faults are not entered into the fault list. The system will not be shut down. The display message will extinguish immediately after the fault has been removed.
13.1.4 Checking brine pressure
26�03� 01�1063
Check brine pressure if the heat pump is blocked for more
than three hours (standby symbol flashes [
Check the brine pipe for leaks.Remedy any leaks.Recharge the system (see chapter “Installation/ Installation/
Installing the heat source system/ Connection and brine charging/ Charging the brine circuit”).
13.1.5 The heat pump does not run
The heat pump is in standby mode [
Remedy: Change to automatic mode
The power supply has been blocked; the standby symbol flashes
]
[
26�03�01�1064
Remedy: Wait; the heat pump restarts automatically at the end of the blocking time.
There is no heat demand
Remedy: System parameter TEMPERATURES, check temperatures and compare the actual and set temperatures.
Possibly incorrect fuse rating
Remedy: See Specification
]
]).
Note
Under these circumstances, you can only restart the heat pump after the fault has been removed and the heat pump has been reset (parameter WPM RESET).
Additional parameters available for system analysis:
Quick start:
Check the heat pump compressor by implementing a quick start
www.stiebel-eltron.com WPF basic | 43
Page 44
INSTALLATION
Troubleshooting
Relay test:
Test all relays in the WPMiw
Analysis:
System analysis for checking all existing BUS subscribers
Reset HP:
Heat pump reset to clear all saved faults.
WPMiw reset options
Reset by turning the rotary selector from Auto to Reset and back again. All system-specific programs remain intact. The fault list will not be deleted.
Reset by turning the rotary selector from Auto to Reset and back again while holding down the PRG key. The display must show EEPR (EEPROM hardware reset). The WPMiw is reset into the de­livered condition. The fault list will be deleted.
After a hardware reset, if the control flap is closed, NO HEAT P PARA is displayed.
The heat pump type must be re-entered.
When the control flap is opened, HEAT PUMP is displayed. After pressing the PRG button, the heat pump type can then be selected using the rotary selector. The heat pump type must be confirmed by pressing the PRG button.
Note
The heat pump type can be found on the type plate.
The parameter SINGLE PHASE must be returned to ON on single phase appliances.
13.2 Resetting the high limit safety cut-out
If the heating water temperature exceeds 85°C, the electric emer­gency/booster heater shuts down.
1
2
1 Electric emergency/booster heater 2 High limit safety cut-out reset button
Remove the cause of the fault.Reset the high limit safety cut-out by pressing the reset but-
ton. To do so, use a pointed object.
Check whether the heating water is being circulated at a suf-
ficient flow rate.
26�03�01�1893
44 | WPF basic www.stiebel-eltron.com
Page 45
INSTALLATION

Maintenance

13.3 Fault list parameter
Check and remove all faults in the fault list.
Fault display Reason for fault code triggered by control unit: Possible cause of fault/remedy
HP sensor max Controlled shutdown; no fault
LOW PRESSURE The system will be permanently shut down after the fault has occurred five times
CONTACT STUCK Each time the compressor is switched off, the system checks af ter ten seconds,
HIGH PRESSURE After the compressor has started, and after a delay of 15 seconds, masking checks,
NO OUTPUT
POWER-OFF
MIN SRCE TEMP The defined minimum source temperature was not reached.
MAX HOT GAS T Controlled shutdown; no fault
The fault will be written to the fault list and the system will be permanently shut down after the system has been shut down five times within the operating time (5 minutes). Generally, the shutdown via the HP sensor max. is a controlled shutdown that is only displayed for information and for the duration of the idle time, i.e. it is not entered into the fault list. Only frequent shutdowns over a short period of time point towards a fault and are therefore entered into the fault list.
within the operating time (idle time x 50 plus 20 minutes). The fault will be written to the fault list after it has occurred for the first time.
whether the relay K9 is open. A contactor is stuck, if that is the case. The fault is written to the fault list, and the system is permanently shut down.
whether the relay K9 is open. A HP limit switch has responded, if that is the case. The fault is written to the fault list, and the system is permanently shut down.
After the compressor has started, the pressure must have risen by 2 bar within 10 seconds. A fault has occurred, if that is not the case, and the fault will be written into the fault list, if that is its first occurrence, and the system is permanently shut down.
The power supply utility has blocked the heat pump (see chapter “Installation/ Troubleshooting/ Fault indicators on the display/ The heat pump is not running”).
The fault is written to the fault list. The compressor starts again after the selected idle time has expired.
The compressor will be stopped for the minimum idle time if a hot gas temperature of 130 °C is exceeded. This is a normal controlled shutdown that is not entered into the fault list. The reason for the shutdown is displayed for information during the idle time.
Only when a fault has been entered into the fault list: Monitor the flow temperature and check the HP sensor. Check the flow rate and the temperature on the heating side.
Check the flow rate and the layout of the source side. Check the refrigerant level.
Check contactors K1 and K2 and replace if required.
Monitor the flow temperature and check the HP sensor. Check the flow rate and the temperature on the heating side.
Compressor turns in the wrong rotational direction. Change the rotational direction by interchanging two supply cores.
No action required. If this message is still shown despite enabling by the power supply utility, the brine pressure switch has responded. Check the brine line for leaks and remedy any that are found. Subsequently recharge the system (see chapter "Installation/ Installation/ Installing the heat source system/ Connection and brine charging/ Charging the brine circuit").
Check the minimum, source temperature and change it if required. Check the source flow rate: Check source design.
This requires no action, as it is a controlled shutdown.
14. Maintenance
We recommend a regular inspection (to establish the current con­dition of the system), and maintenance if required (to return the system to its original condition).
If heat meters are installed, their sieves should be cleaned reg­ularly.
www.stiebel-eltron.com WPF basic | 45
Page 46
INSTALLATION
510
Specication
15. Specification
15.1 Connections
85
170
255
382
340
425
680
176
100
926
f02
f01
d29
960
e01
e02
b03b02
c11
D0000016823
WPF 5
basic
b02 Entry electrical cables I b03 Entry electrical cables II c11 Safety assembly d29 Heat exchanger flow Male thread G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 e01 Heating flow Male thread G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 e02 Heating return Male thread G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 f01 Heat source flow Male thread G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 f02 Heat source return Male thread G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4
WPF 7
basic
WPF 10
basic
WPF 13
basic
WPF 16
basic
WPF5S
basic
WPF 7 S
basic
WPF 10 S
basic
46 | WPF basic www.stiebel-eltron.com
Page 47
INSTALLATION
Specication
15.2 Installation dimensions
≥500
≥500
≥500
≥50
≥1000
www.stiebel-eltron.com WPF basic | 47
D0000019257
Page 48
INSTALLATION
erdrahtungsplan WP
Specication
15.3 Wiring diagram WPF 5 basic
X3
L3
10
3 5
L2
98
1
L1
Solepumpe
7
L3
6
L2
5
L1
4
N
3
L3
2
L2
WP (Netz) DHC
1
L1
080
br
br
sw
sw
sw
ws
ws
K4
6
4
2
Z3
K5
K7
K6
1
3
1
3
3
1
F5
T >
500
31
21
11
X23
X31
510
E1
32
22
12
P3=3200W
P2=3000W
P1=2600W
620
400
420
T
T
B2
F 5 basic
X23
X26
"+"
13
12
L
11
H
10
Fernb.3
9
Fernb.1
8
T(MK)
7
T(A)
6
T(WW)
5
Kleinspannung
B2
4
B2
3
B1
2
B1
1
X2
1/810
B1
1/820
T
B3
T
B5
22
l
1
p
P3
l
1
p
P1
1234578
X28
6
4
3 5
2
1
K2
R
T3
S
T2
M
3
C
T1
M1
1/185
4 3
X15
2
X23
1
3
2
1
2 1
2 1
10 9
8
7 65
4
3
2
1
15-17 V
680
11
9
6
14
K9
K2
12
13
14
680
530
X14
X13
X12
X11
700
430
B
X22
X21
X20
A2
4
B
B
B
A2
X1
710
A1
1 2 3 4 56
7 8 9 10
2 1
5 4 3 2
1
A1
K4
1
X73
K9
A
K7K6
A
A
K5
A1
K2
A
K8
6
1
234
5
sw
bl
br
K8
3
1
X27
1/465
L`
L``
N
520
L
N
670
M3
M2
X27
650
630
690
1/420
F2
1
M
M
1
> p
X25
N
410
F8
i
10
HKP
9
Mz
87
Ma
EVU
6
MKP
5
Kühlen
4
KS
3
Steuerung
ON
21
L
X4
X24
720
g
X39
i
> p
F8
V
48 | WPF basic www.stiebel-eltron.com
D0000048149
Page 49
INSTALLATION
Specication
A1 Heat pump manager WPMi B1 Temperature sensor heat pump flow B2 Temperature sensor heat pump return B3 Temperature sensor heat source B5 Hot gas temperature sensor E1 elektr. booster heater (DHC) F1 Low pressure switch (only in WPW) F2 High pressure switch F5 High limit safety cut-out for DHC F8 Brine pressure switch K2 Compressor start contactor K4 Contactor – brine pump K5 Electric booster heater relay K6 Electric booster heater relay K7 Electric booster heater relay K8 Pump motor relay K9 Contactor relay stuck M1 Compressor motor M2 Pump motor M3 Motorised diverter valve P1 High pressure transducer P3 Low pressure transducer X1 Terminals X2 LV terminal X3 Power supply X4 Control terminals X11 Socket plug 10-PIN WPMi X12 Plug WQ temperature WPMiw X13 Plug mixer circuit temp. WPMiw X14 Plug remote control WPMiw X15 BUS plug WPMiw X20 Plug pumps and power-OFF WPMiw X21 Plug mixer control WPMiw X22 Socket plug 10-PIN control WPMi X23 Power supply earth block X24 Earth block control X25 N block control X26 Earth block LV X27 Earth plug-in block X28 Socket terminal strip X31 Electric booster heater terminal X39 Earthing the front sheet metal cover X73 Connectors in cable channel Z3 Suppressor
www.stiebel-eltron.com WPF basic | 49
Page 50
INSTALLATION
erdrahtungsplan WP
Specication
15.4 Wiring diagram WPF 7 basic | WPF 10 basic | WPF 13 basic | WPF 16 basic
080
br
br
sw
ws
ws sw
Z3
K5
K6
K7
3
1
3
1
3
1
R1
R2R3
600
6
53
1
6
4
4
2
K1
1 3 5
2
K2
610
4
3
X15
2 1
A1
3
X14
2 1
1
X22
2
2
X13
3
4
5
6
2
7
X12
1 1
8
9
10
10
9
X11
8
2
X21
7
1
6
5
4
5
3
X20
4
2
3
1
2
430
700
1
A1
A2
K4
1
4
K9
A
B
A
B
K6 K7
A
B
K5
A1
A2
K2
A1
A2
K1
A
B
K8
2
1
X1
bl
br
15-17 V
12
8
9
K9
11
530
345
F5
T >
500
31
21
11
X23
X23
510
E1
32
22
12
X31
R
T3
S
T2
M
3
C
T1
M1
1/185
X4
X24
650
630
690
6
sw
T
T
B2
X3
L3
10
L2
9
L1
8
Solepumpe
7
L3
6
L2
5
L1
4
N
32
L3
L2
WP (Netz) DHC
1
L1
400
X23
X26
420
"+"
13
12
L
11
H
10
Fernb.3
9
Fernb.1
8
T(MK)
7
T(A)
6
T(WW)
5
Kleinspannung
B2
4
B2
3
B1
2
B1
1
X2
B1
T
B3
T
B5
2
l
1
p
P3
2
l
1
p
P1
531
600
1/810
1/820
K4
6
4
2
1
X28
23567
4
P3=3200W
P2=3000W
P1=2600W
10
9
87
6
5
4
3
21
X39
j
620
X25
F8
HKP
Mz
Ma
EVU
MKP
Kühlen
KS
ON
L
N
j
Steuerung
X27
410
670
720
h
> p
F8
600
K1
K2
13
13
14
14
K1
K2
-1
-2
-1
F 7, 10, 13, 16 basic
V
50 | WPF basic www.stiebel-eltron.com
-2
610
600
K8
3
1
X27
1/465
L`
L``
N
520
L
N
1/420
M
M3
M
M2
> p
F2
1
1
D0000048087
Page 51
INSTALLATION
Specication
A1 Heat pump manager WPMi B1 Temperature sensor heat pump flow B2 Temperature sensor heat pump return B3 Temperature sensor heat source B5 Hot gas temperature sensor E1 elektr. booster heater (DHC) F1 Low pressure switch (only in WPW) F2 High pressure switch F5 High limit safety cut-out for DHC F8 Brine pressure switch K1 Contactor resistances K2 Compressor start contactor K4 Contactor – brine pump K5 Electric booster heater relay K6 Electric booster heater relay K7 Electric booster heater relay K8 Pump motor relay K9 Contactor relay stuck M1 Compressor motor M2 Pump motor M3 Motorised diverter valve P1 High pressure transducer P3 Low pressure transducer R1 Start-up resistance R2 Start-up resistance R3 Start-up resistance X1 Terminals X2 LV terminal X3 Power supply X4 Control terminals X11 Socket plug 10-PIN WPMi X12 Plug WQ temperature WPMiw X13 Plug mixer circuit temp. WPMiw X14 Plug remote control WPMiw X15 BUS plug WPMiw X20 Plug pumps and power-OFF WPMiw X21 Plug mixer control WPMiw X22 Socket plug 10-PIN control WPMi X23 Power supply earth block X24 Earth block control X25 N block control X26 Earth block LV X27 Earth plug-in block X28 Socket terminal strip X31 Electric booster heater terminal X39 Earthing the front sheet metal cover Z3 Suppressor
www.stiebel-eltron.com WPF basic | 51
Page 52
INSTALLATION
Specication
15.5 Wiring diagram WPF 5-10 S basic
52 | WPF basic www.stiebel-eltron.com
D0000048150
Page 53
INSTALLATION
Specication
A1 WPMiw heat pump manager B1 Temperature sensor heat pump flow B2 Temperature sensor heat pump return B3 Temperature sensor heat source B5 Hot gas temperature sensor E1 Emergency heater (DHC) F1 Low pressure switch F2 High pressure switch F5 High limit safety cut-out for DHC K2 Compressor start contactor K4 Contactor – brine pump K5 Emergency heater relay K6 Emergency heater relay K9 Contactor relay stuck M1 Compressor motor M2 Pump motor M3 Motorised diverter valve P1 High pressure transducer X1 Terminals X2 LV terminal X3 Power supply X4 Control terminals X11 Plug temperature sensor WPMiw X12 Plug WQ temperature WPMiw X13 Plug mixer circuit temp. WPMiw X14 Plug remote control WPMiw X15 BUS plug WPMi X20 Plug pumps and power-OFF WPMiw X21 Plug mixer control WPMiw X22 Plug external pump WPMiw X23 Power supply earth block X24 Earth block control X25 N block control X26 Earth block LV X27 Earth plug-in block X28 2-pin socket terminal strip X31 Emergency heater terminal X32 Front cover terminal. X73 Connectors in cable channel Z1 Compressor capacitor, run
www.stiebel-eltron.com WPF basic | 53
Page 54
INSTALLATION
1
2
3
4
1
2
3
4
Specication
15.6 Output diagrams WPF 5 basic
Legend for output diagrams
Y Heating output [kW] / power consumption [kW] / coefficient of performance e [-] X Inlet temperature of the WQA medium [°C] 1 Flow temperature 35 °C 2 Flow temperature 45 °C 3 Flow temperature 55 °C 4 Flow temperature 60 °C
Heating output WPF 5 basic
10
9
8
7
6
5
4
3
2
1
0
-5 0 5 10 15 20
Power consumption WPF 5 basic
3
2
D0000022775
1
0
-5 0 5 10 15 20
54 | WPF basic www.stiebel-eltron.com
D0000022775
Page 55
INSTALLATION
1
2
3
4
Specication
Coefficient of performance WPF 5 basic
8
7
6
5
4
3
2
1
0
-5 0 5 10 15 20
D0000022775
www.stiebel-eltron.com WPF basic | 55
Page 56
INSTALLATION
1
2
3
4
1
2
3
4
Specication
15.7 Output diagrams WPF 7 basic
Legend for output diagrams
Y Heating output [kW] / power consumption [kW] / coefficient of performance e [-] X Inlet temperature of the WQA medium [°C] 1 Flow temperature 35 °C 2 Flow temperature 45 °C 3 Flow temperature 55 °C 4 Flow temperature 60 °C
Heating output WPF 7 basic
14
12
10
8
6
4
2
0
-5 0 5 10 15 20
Power consumption WPF 7 basic
4
3
2
D0000022775
1
0
-5 0 5 10 15 20
56 | WPF basic www.stiebel-eltron.com
D0000022775
Page 57
INSTALLATION
1
2
3
4
Specication
Coefficient of performance WPF 7 basic
8
7
6
5
4
3
2
1
0
-5 0 5 10 15 20
D0000022775
www.stiebel-eltron.com WPF basic | 57
Page 58
INSTALLATION
1
2
3
4
1
2
3
4
Specication
15.8 Output diagrams WPF 10 basic
Legend for output diagrams
Y Heating output [kW] / power consumption [kW] / coefficient of performance e [-] X Inlet temperature of the WQA medium [°C] 1 Flow temperature 35 °C 2 Flow temperature 45 °C 3 Flow temperature 55 °C 4 Flow temperature 60 °C
Heating output WPF 10 basic
16
14
12
10
8
6
4
2
0
-5 0 5 10 15 20
Power consumption WPF 10 basic
5
4
3
D0000022775
2
1
0
-5 0 5 10 15 20
58 | WPF basic www.stiebel-eltron.com
D0000022775
Page 59
INSTALLATION
1
2
3
4
Specication
Coefficient of performance WPF 10 basic
8
7
6
5
4
3
2
1
0
-5 0 5 10 15 20
D0000022775
www.stiebel-eltron.com WPF basic | 59
Page 60
INSTALLATION
1
2
3
4
1
2
3
4
Specication
15.9 Output diagrams WPF 13 basic
Legend for output diagrams
Y Heating output [kW] / power consumption [kW] / coefficient of performance e [-] X Inlet temperature of the WQA medium [°C] 1 Flow temperature 35 °C 2 Flow temperature 45 °C 3 Flow temperature 55 °C 4 Flow temperature 60 °C
Heating output WPF 13 basic
25
20
15
10
5
0
-5 0 5 10 15 20
Power consumption WPF 13 basic
6
5
4
3
D0000022775
2
1
0
-5 0 5 10 15 20
60 | WPF basic www.stiebel-eltron.com
D0000022775
Page 61
INSTALLATION
1
2
3
4
Specication
Coefficient of performance WPF 13 basic
8
7
6
5
4
3
2
1
0
-5 0 5 10 15 20
D0000022775
www.stiebel-eltron.com WPF basic | 61
Page 62
INSTALLATION
1
2
3
4
1
2
3
4
Specication
15.10 Output diagrams WPF 16 basic
Legend for output diagrams
Y Heating output [kW] / power consumption [kW] / coefficient of performance e [-] X Inlet temperature of the WQA medium [°C] 1 Flow temperature 35 °C 2 Flow temperature 45 °C 3 Flow temperature 55 °C 4 Flow temperature 60 °C
Heating output WPF 16 basic
29
27
25
23
21
19
17
15
13
-5 0 5 10 15 20
Power consumption WPF 16 basic
8
7
6
5
D0000022775
4
3
2
1
0
-5 0 5 10 15 20
62 | WPF basic www.stiebel-eltron.com
D0000022775
Page 63
INSTALLATION
1
2
3
4
Specication
Coefficient of performance WPF 16 basic
8
7
6
5
4
3
2
1
0
-5 0 5 10 15 20
D0000022775
www.stiebel-eltron.com WPF basic | 63
Page 64
INSTALLATION
Specication
15.11 Output diagrams WPF 5 S basic
Ethylenglykol/W assergemisch mit 33 V ol.% Ethylenglykol
15
1=V orlauf temperatur 35 °C V olllast 2=V orlauf temperatur 50 °C V olllast 3=V orlauf temperatur 60 °C V olllast
10
HP
.
Q
5
Heat Output
HP
Power consumption P
0
-5 0 5
8
HP
7 6 5 4 3 2
Performance factor ε
1 Flow temperature 35 °C 2 Flow temperature 50 °C 3 Flow temperature 60 °C
10 15 20
Inlet temperature of Source Medium [°C]
°C
26�03�01�0257
64 | WPF basic www.stiebel-eltron.com
Page 65
INSTALLATION
Specication
15.12 Output diagrams WPF 7 S basic
Ethylenglykol/Wassergemisch mit 33 Vol.% Ethylenglykol
15
1 = Vorlauftemperatur 35 °C Volllast 2 = Vorlauftemperatur 50 °C Volllast 3 = Vorlauftemperatur 60 °C Volllast
10
HP
.
Q
5
Heat Output
HP
Power consumption P
0
-5 0 5
8
HP
7 6 5 4 3 2
Performance factor ε
1 Flow temperature 35 °C 2 Flow temperature 50 °C 3 Flow temperature 60 °C
10 15 20
Inlet temperature of Source Medium [°C]
°C
26�03�01�0258
www.stiebel-eltron.com WPF basic | 65
Page 66
INSTALLATION
Specication
15.13 Output diagrams WPF 10 S basic
Ethylenglykol/Wassergemisch mit 33 Vol.% Ethylenglykol
20
1=Vorlauftemperatur 35 °C Volllast 2=Vorlauftemperatur 50 °C Volllast 3=Vorlauftemperatur 60 °C Volllast
15
HP
.
Q
10
Heat Output
HP
5
Power consumption P
0
-5 05
8
HP
7 6 5 4 3 2
Performance factor ε
1 Flow temperature 35 °C 2 Flow temperature 50 °C 3 Flow temperature 60 °C
10 15 20
Inlet temperature of Source Medium [°C]
°C
26�03�01�0260
66 | WPF basic www.stiebel-eltron.com
Page 67
INSTALLATION
Specication
15.14 Data table WPF 5-16 basic
Output details apply to new appliances with clean heat exchangers.
The power consumption figures for the integral auxiliary drives are maximum values and may vary subject to operating point.
The power consumption of the integral auxiliary drives is included in the output details of the heat pump (to EN 14511).
WPF 5 basic WPF 7 basic WPF 10 basic WPF 13 basic WPF 16 basic
230944 230945 230946 230947 230948 Heating output Heating output at B0/ W35 (EN 14511) kW 5.88 7.64 9.7 12.59 16.64 Heating output at B10/W35 kW 7.62 9.82 12.44 16.37 20.88 Power consumption Power consumption at B0/W35 (EN 14511) kW 1.36 1.70 2.22 2.85 4.00 Power consumption at B10/W35 kW 1.36 1.68 2.16 2.79 4.06 Max. power consumption, circulation pump on the heating side W 70 70 70 70 70 Power consumption, emergency/booster heater kW 8.8 8.8 8.8 8.8 8.8 Coeff icient of performance COP at B0/W35 (EN 14511) 4.33 4.50 4.37 4.42 4.16 Coeff icient of performance at B10/W35 5.60 5.85 5.76 5.87 5.14 Sound emissions Sound power level (EN 12102) dB(A) 46 47 51 53 53 Sound pressure level at a distance of 1m in a free field dB(A) 38 39 43 45 45 Sound pressure level at a distance of 5m in a free field dB(A) 24 25 29 31 31 Application limits Max. permissible pressure MPa 0.3 0.3 0.3 0.3 0.3 Min. application limit on the heating side °C 15 15 15 15 15 Max. application limit on the heating side °C 60 60 60 60 60 Min. application limit, heat source °C -5 -5 -5 -5 -5 Max. application limit, heat source °C 20 20 20 20 20 Energy data Energy efficiency class A+/A++ A+/A++ A+/A++ A+/A++ A+/A++ Electrical data Frequency Hz 50 50 50 50 50 Control unit fuse/MCB A 1 x B 16 1 x B 16 1 x B 16 1 x B 16 1 x B 16 Compressor fuse/MCB A 3 x C 16 3 x C 16 3 x C 16 3 x C 16 3 x C 16 MCB/fuse protection, emergency/booster heater A 3 x B 16 3 x B 16 3 x B 16 3 x B 16 3 x B 16 Rated voltage, control unit V 230 230 230 230 230 Rated voltage, compressor V 400 400 400 400 400 Rated voltage, emergency/booster heater V 400 400 400 400 400 Control unit phases 1/N/PE 1/N/PE 1/N/PE 1/N/PE 1/N/PE Compressor phases 3/N/PE 3/N/PE 3/N/PE 3/N/PE 3/N/PE Emergency/booster heater phases 3/N/PE 3/N/PE 3/N/PE 3/N/PE 3/N/PE Starting current (with/without starting current limiter) A 26/- 30/- 27/- 28/- 29/­Versions Refrigerant R410 A R410 A R410 A R410 A R410 A Refrigerant charge kg 1.73 2 2.6 2.5 2.6 CO2 equivalent (CO2e) t 3.61 4.18 5.43 5.22 5.22 Global warming potential of the refrigerant (GWP100) 2088 2088 2088 2088 2088 Compressor oil Emkarate RL 32
Evaporator material 1.4401/Cu 1.4401/Cu 1.4401/Cu 1.4401/Cu 1.4401/Cu Condenser material 1.4401/Cu 1.4401/Cu 1.4401/Cu 1.4401/Cu 1.4401/Cu Circulation pump type on the heating side Stratos PARA
IP rating IP20 IP20 IP20 IP20 IP20 Dimensions Height mm 960 960 960 960 960 Width mm 510 510 510 510 510 Depth mm 680 680 680 680 680 Weight Weight kg 107 113 120 128 131 Connections Connection on the heating side G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 Connection on the heat source side G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4 G 1 1/4
3MAF
25/1-7
Emkarate RL 32
3MAF
Stratos PARA
25/1-7
Emkarate RL 32
3MAF
Stratos PARA
25/1-7
Emkarate RL 32
3MAF
Stratos PARA
25/1-7
Emkarate RL 32
3MAF
Stratos PARA
25/1-7
www.stiebel-eltron.com WPF basic | 67
Page 68
INSTALLATION
Specication
WPF 5 basic WPF 7 basic WPF 10 basic WPF 13 basic WPF 16 basic
Water quality requirements Water hardness °dH ≤3 ≤3 ≤3 ≤3 ≤3 pH value (with aluminium fittings) 8.0-8.5 8.0-8.5 8.0-8.5 8.0-8.5 8.0-8.5 pH value (without aluminium fittings) 8.0-10.0 8.0-10.0 8.0-10.0 8.0-10.0 8.0-10.0 Chloride mg/l <30 <30 <30 <30 <30 Conductivity (softening) μS/cm <1000 <1000 <1000 <1000 <1000 Conductivity (desalination) μS/cm 20 -100 20 -100 20-100 20-100 20-100 Oxygen 8-12 weeks after filling (desalination) mg/l <0.1 <0.1 <0.1 <0.1 <0.1 Oxygen 8-12 weeks after filling (softening) mg/l <0.02 <0.02 <0.02 <0.02 <0.02 Heat transfer medium requirements on the heat source side Ethylene glycol concentration, geothermal probe Vol.-% 25 25 25 25 25 Ethylene glycol concentration, geothermal collector Vol.-% 33 33 33 33 33 Values Nominal design heating system flow rate at B0/W35 and 7K m³/h 0.71 0.91 1.22 1.58 2.08 Min. heating flow rate m³/h 0.5 0.64 0.86 1.1 1.45 Heating flow rate (EN 14511) for A7/W35, B0/W35 and 5 k m³/h 0.99 1.27 1.71 2.21 2.91 Flow rate on heat source side m³/h 1.4 1.9 2.2 3.1 3.8 Internal volume on the heating side l 2.4 2.8 3.4 3.4 3.4 Internal volume on the source side l 2.9 3.5 4.1 4.1 4.1 Available external pressure differential, heating system hPa 350 350 260 167 63 Pressure differential on the heat source side hPa 100 110 120 230 340
68 | WPF basic www.stiebel-eltron.com
Page 69
INSTALLATION
Specication
15.15 Datentabelle WPF 5-10 S basic
Output details apply to new appliances with clean heat exchangers.
The power consumption figures for the integral auxiliary drives are maximum values and may vary subject to operating point.
The power consumption of the integral auxiliary drives is included in the output details of the heat pump (to EN 14511).
WPF 5 S basic WPF 7 S basic WPF 10 S basic
074425 074426 220819 Heating output Heating output at B0/ W35 (EN 14511) kW 5.80 7.80 9.90 Power consumption Power consumption at B0/W35 (EN 14511) kW 1.35 1.78 2.20 Max. power consumption, circulation pump on the heating side W 93 93 93 Power consumption, emergency/booster heater kW 8.8 8.8 8.8 Coeff icient of performance COP at B0/W35 (EN 14511) 4.30 4.40 4.50 Sound emissions Sound power level (EN 12102) dB(A) 46 47 51 Sound pressure level at a distance of 1m in a free field dB(A) 38 39 43 Sound pressure level at a distance of 5m in a free field dB(A) 38 39 43 Application limits Max. permissible pressure MPa 0.3 0.3 0.3 Min. application limit on the heating side °C 15 15 15 Max. application limit on the heating side °C 60 60 60 Min. application limit, heat source °C -5 -5 -5 Max. application limit, heat source °C 20 20 20 Energy data Energy efficiency class A+/A++ A+/A++ A+/A++ Electrical data Frequency Hz 50 50 50 Control unit fuse/MCB A 1 x B 16 1 x B 16 1 x B 16 Compressor fuse/MCB A 1 x C16 1 x C 25 1 x C 25 MCB/fuse protection, emergency/booster heater A 1 x C 35 1 x C 35 1 x C 35 Rated voltage, control unit V 230 230 230 Rated voltage, compressor V 230 230 230 Rated voltage, emergency/booster heater V 230 230 230 Control unit phases 1/N/PE 1/N/PE 1/N/PE Compressor phases 1/N/PE 1/N/PE 1/N/PE Emergency/booster heater phases 1/N/PE 1/N/PE 1/N/PE Starting current (with/without starting current limiter) A 29/58 32/88 41/97 Versions Refrigerant R410 A R410 A R410 A Refrigerant charge kg 1.6 2.0 2.6 CO2 equivalent (CO2e) t 3.34 4.18 5.43 Global warming potential of the refrigerant (GWP100) 2088 2088 2088 Compressor oil Emkarate RL 32 3MAF Emkarate RL 32 3MAF Emkarate RL 32 3MAF Evaporator material 1.4401/Cu 1.4401/Cu 1.4401/Cu Condenser material 1.4401/Cu 1.4401/Cu 1.4401/Cu Circulation pump type on the heating side Stratos PARA 25/1-7 Stratos PARA 25/1-7 Stratos PARA 25/1-7 Dimensions Height mm 960 960 960 Width mm 510 510 510 Depth mm 680 680 680 Weight Weight kg 107 113 120 Connections Connection on the heating side G 1 1/4 G 1 1/4 G 1 1/4 Connection on the heat source side G 1 1/4 G 1 1/4 G 1 1/4
www.stiebel-eltron.com WPF basic | 69
Page 70
INSTALLATION
Specication
WPF 5 S basic WPF 7 S basic WPF 10 S basic
Water quality requirements Water hardness °dH ≤3 ≤3 ≤3 pH value (with aluminium fittings) 8.0-8.5 8.0-8.5 8.0-8.5 pH value (without aluminium fittings) 8.0-10.0 8.0-10.0 8.0-10.0 Chloride mg/l <30 <30 <30 Conductivity (softening) μS/cm <1000 <1000 <1000 Conductivity (desalination) μS/cm 20 -100 20 -100 20-100 Oxygen 8-12 weeks after filling (desalination) mg/l <0.1 <0.1 <0.1 Oxygen 8-12 weeks after filling (softening) mg/l <0.02 <0.02 <0.02 Heat transfer medium requirements on the heat source side Ethylene glycol concentration, geothermal probe Vol.-% 25 25 25 Ethylene glycol concentration, geothermal collector Vol.-% 33 33 33 Values Nominal design heating system flow rate at B0/W35 and 7K m³/h 0.71 0.96 1.22 Min. heating flow rate m³/h 0.5 0.67 0.85 Heating flow rate (EN 14511) for A7/W35, B0/W35 and 5 k m³/h 1 1.34 1.71 Flow rate on heat source side m³/h 1.4 1.9 2.2 Internal volume on the heating side l 2.4 2.8 3.4 Internal volume on the source side l 2.9 3.5 4.1 Available external pressure differential, heating system hPa 350 350 260 Pressure differential on the heat source side hPa 100 110 120
15.16 Data table WPMiw
Electrical connection 1/N/PE ~ 230 V 50Hz Power consumption VA 8 Relay breaking capacity A 2 IP rating IP1XB Protection class II Permissible ambient temperature during operation °C 0-50 Permissible ambient temperature during storage °C -30-60 Clock power reserve, day h >10 Sensor resistances, test resistance Ω 2000 Communication system RS232 (optical), CAN Max. breaking capacity of relay output, buffer charging
pump Max. breaking capacity of relay output, heating circuit
pump Max. breaking capacity of relay output, mixer circuit
pump Max. breaking capacity of relay output, DHW charging
pump Max. breaking capacity of relay output, DHW circulation
pump Max. breaking capacity of relay output, source pump A 2 (1.5) Max. relay output breaking capacity 2nd heat generator
contact Max. breaking capacity of relay output, mixer A 2 (1.5) Max. total breaking capacity of all relay outputs A 10 (8)
A 2 (1.5)
A 2 (1.5)
A 2 (1.5)
A 2 (1.5)
A 2 (1.5)
A 2 (1.5)
70 | WPF basic www.stiebel-eltron.com
Page 71
GUARANTEE | ENVIRONMENT AND RECYCLING

Guarantee

The guarantee conditions of our German companies do not apply to appliances acquired outside of Germany. In countries where our subsidiaries sell our products a guarantee can only be issued by those subsidiaries. Such guarantee is only grant­ed if the subsidiary has issued its own terms of guarantee. No other guarantee will be granted.
We shall not provide any guarantee for appliances acquired in countries where we have no subsidiary to sell our products. This will not aect warranties issued by any importers.

Environment and recycling

We would ask you to help protect the environment. After use, dispose of the various materials in accordance with national regulations.
www.stiebel-eltron.com WPF basic | 71
Page 72
g
y
Deutschland
STIEBEL ELTRON GmbH & Co. KG Dr.-Stiebel-Straße 33 | 37603 Holzminden Tel. 05531 702-0 | Fax 05531 702-480 [email protected] www.stiebel-eltron.de
Australia
STIEBEL ELTRON Australia Pty. Ltd. 6 Prohasky Street | Port Melbourne VIC 3207 Tel. 03 9645-1833 | Fax 03 9645-4366 [email protected] www.stiebel.com.au
Austria
STIEBEL ELTRON Ges.m.b.H. Gewerbegebiet Neubau-Nord Margaritenstraße 4 A | 4063 Hörsching Tel. 07221 74600-0 | Fax 07221 74600-42 [email protected] www.stiebel-eltron.at
Belgium
STIEBEL ELTRON bvba/sprl 't Hofveld 6 - D1 | 1702 Groot-Bijgaarden Tel. 02 42322-22 | Fax 02 42322-12 [email protected] www.stiebel-eltron.be
China
STIEBEL ELTRON (Guangzhou) Electric Appliance Co., Ltd. Rm 102, F1, Yingbin-Yihao Mansion, No. 1 Yingbin Road Panyu District | 511431 Guangzhou Tel. 020 39162209 | Fax 020 39162203 [email protected] www.stiebeleltron.cn
Czech Republic
STIEBEL ELTRON spol. s r.o. K Hájům 946 | 155 00 Praha 5 - Stodůlky Tel. 251116-111 | Fax 235512-122 [email protected] www.stiebel-eltron.cz
Finland
STIEBEL ELTRON OY Kapinakuja 1 | 04600 Mäntsälä Tel. 020 720-9988 [email protected] www.stiebel-eltron.fi
Verkauf Tel. 05531 702-110 | Fax 05531 702-95108 | [email protected] Kundendienst Tel. 05531 702-111 | Fax 05531 702-95890 | [email protected] Ersatzteilverkauf Tel. 05531 702-120 | Fax 05531 702-95335 | [email protected]
France
STIEBEL ELTRON SAS 7-9, rue des Selliers B.P 85107 | 57073 Metz-Cédex 3 Tel. 0387 7438-88 | Fax 0387 7468-26 [email protected] www.stiebel-eltron.fr
Hungary
STIEBEL ELTRON Kft. Gyár u. 2 | 2040 Budaörs Tel. 01 250-6055 | Fax 01 368-8097 [email protected] www.stiebel-eltron.hu
Japan
NIHON STIEBEL Co. Ltd. Kowa Kawasaki Nishiguchi Building 8F 66-2 Horikawa-Cho Saiwai-Ku | 212-0013 Kawasaki Tel. 044 540-3200 | Fax 044 540-3210 [email protected] www.nihonstiebel.co.jp
Netherlands
STIEBEL ELTRON Nederland B.V. Daviottenweg 36 | 5222 BH 's-Hertogenbosch Tel. 073 623-0000 | Fax 073 623-1141 [email protected] www.stiebel-eltron.nl
Poland
STIEBEL ELTRON Polska Sp. z O.O. ul. Działkowa 2 | 02-234 Warszawa Tel. 022 60920-30 | Fax 022 60920-29 [email protected] www.stiebel-eltron.pl
Russia
STIEBEL ELTRON LLC RUSSIA Urzhumskaya street 4, building 2 | 129343 Moscow Tel. 0495 7753889 | Fax 0495 7753887 [email protected] www.stiebel-eltron.ru
Slovakia
TATRAMAT - ohrievače vody s.r.o. Hlavná 1 | 058 01 Poprad Tel. 052 7127-125 | Fax 052 7127-148 [email protected] www.stiebel-eltron.sk
Switzerland
STIEBEL ELTRON AG Industrie West Gass 8 | 5242 Lupfig Tel. 056 4640-500 | Fax 056 4640-501 [email protected] www.stiebel-eltron.ch
Thailand
STIEBEL ELTRON Asia Ltd. 469 Moo 2 Tambol Klong-Jik Amphur Bangpa-In | 13160 Ayutthaya Tel. 035 220088 | Fax 035 221188 [email protected] www.stiebeleltronasia.com
United Kingdom and Ireland
STIEBEL ELTRON UK Ltd. Unit 12 Stadium Court Stadium Road | CH62 3RP Bromborough Tel. 0151 346-2300 | Fax 0151 334-2913 [email protected] www.stiebel-eltron.co.uk
United States of America
STIEBEL ELTRON, Inc. 17 West Street | 01088 West Hatfield MA Tel. 0413 247-3380 | Fax 0413 247-3369 [email protected] www.stiebel-eltron-usa.com
4<AMHCMN=jdbdgd>
Irrtum und technische Änderungen vorbehalten! | Subject to errors and technical changes! | Sous réserve d‘erreurs et de modifications techniques! | Onder voorbehoud van ver Salvo error o modificación técnica! | Excepto erro ou alteração técnica | Zastrzeżone zmian ewentualne błędy | Omyly a technické změny jsou vyhrazeny! | A muszaki változtatások és tévedések jogát fenntartjuk! | technické zmeny sú vyhradené! Stand 9147
Отсутствие ошибок не гарантируется. Возможны технические изменения.
issingen en technische wijzigingen! |
techniczne i
| Chyby a
A 293136-40278-9267
B 293151-40278-9267
Loading...