18.9 Data table WPC... ����������������������������������������������� 64
18.10 Data table WPC...cool ������������������������������������������ 66
GUARANTEE
ENVIRONMENT AND RECYCLING
2 | WPC | WPC cool www.stiebel-eltron.com
Page 3
Special information
SPECIAL INFORMATION
- The appliance may be used by children aged8
and up and persons with reduced physical, sensory or mental capabilities or a lack of experience
and know-how, provided that they are supervised
or they have been instructed on how to use the
appliance safely and have understood the resulting risks. Children must never play with the appliance. Children must never clean the appliance
or perform user maintenance unless they are
supervised.
- Use a permanent connection to the power supply.
Ensure the appliance can be separated from the
power supply by an isolator that disconnects all
poles with at least 3mm contact separation.
- Maintain the minimum clearances to ensure trouble-free operation of the appliance and facilitate
maintenance work.
- There is no need to shut the system down in
summer. The heat pump manager has an automatic summer/winter changeover.
DHW cylinders
- Regularly activate the safety valve to prevent
it from becoming blocked e.g. by limescale
deposits.
- Drain the DHW cylinder as described in the chapter "Installation/ Maintenance/ Draining the
DHW cylinder".
- Install a type-tested safety valve in the cold water
supply line. For this bear in mind that, depending
on the static pressure, you may also need a pressure reducing valve.
- The safety valve discharge aperture must remain
open to the atmosphere.
- Install the safety valve discharge pipe with a constant fall to the discharge outlet.
- In dual mode operation, return water from the
second heat generator may flow through the heat
pump. Please note that the return water temperature may be a maximum of 60°C.
- Cooling mode is only possible in conjunction with
the WPAC 1 cooling module. Set parameter COOLING to ACTIVE COOLING. The COOLING parameter
will only be shown if a FEK or FE 7 remote control
is connected. Cooling mode is only possible in
summer mode.
- The air outlet in the knurled cap of the quick-action air vent valve must not point towards the
MFG PCB. Close the quick-action air vent valve
again after venting.
- Maintenance work, such as checking the electrical safety, must only be carried out by a qualified
contractor.
- We recommend an annual inspection (to establish
the system's current condition), and maintenance
by a qualified contractor if required (to return the
system to the desired condition).
- Size the discharge outlet so that water can drain
off unimpeded when the safety valve is fully
opened.
- Never interrupt the power supply, even outside
the heating period. The system's active frost protection is not guaranteed if the power supply is
interrupted.
www.stiebel-eltron.com WPF | 3
Page 4
OPERATION
General information
OPERATION
1. General information
The chapters "Special Information" and "Operation" are intended
for both the user and qualified contractors.
The chapter "Installation" is intended for qualified contractors.
Note
Read these instructions carefully before using the appliance and retain them for future reference.
Pass on the instructions to a new user if required.
1.1 Safety instructions
1.1.1 Structure of safety instructions
KEYWORD Type of risk
!
Here, possible consequences are listed that may result
from failure to observe the safety instructions.
Steps to prevent the risk are listed.
1.1.2 Symbols, type of risk
SymbolType of risk
!
1.1.3 Keywords
KEYWORDMeaning
DANGER Failure to observe this information will result in serious
WARNING Failure to observe this information may result in serious
CAUTION Failure to observe this information may result in non-seri-
Injury
Electrocution
Burns
(burns, scalding)
injury or death.
injury or death.
ous or minor injury.
1.2 Other symbols in this documentation
Note
General information is identified by the symbol shown
on the left.
Read these texts carefully.
SymbolMeaning
!
This symbol indicates that you have to do something. The ac-
tion you need to take is described step by step.
Material losses
(appliance and consequential losses, environmental pollution)
Appliance disposal
1.3 Units of measurement
Note
All measurements are given in mm unless stated otherwise.
2. Safety
2.1 Intended use
The appliance is designed for:
- heating rooms
- DHW heating
Observe the operating limits listed in chapter "Specification".
This appliance is intended for domestic use. It can be used safely
by untrained persons. The appliance can also be used in a non-domestic environment, e.g. in a small business, as long as it is used
in the same way.
Any other use beyond that described shall be deemed inappropriate. Observation of these instructions and of instructions for any
accessories used is also part of the correct use of this appliance.
2.2 General safety instructions
2.3 Safety instructions
- The electrical installation and installation of the heating circuit must only be carried out by a recognised, qualified contractor or by our customer service engineers.
- The qualified contractor is responsible for adherence to all
currently applicable instructions during installation and
commissioning.
- Operate the appliance only when fully installed and with all
safety equipment fitted.
- Protect the appliance from dust and dirt ingress during
building work.
4 | WPC | WPC cool www.stiebel-eltron.com
Page 5
OPERATION
Appliance description
WARNING Injury
!
The appliance may be used by children aged 8 and up and
persons with reduced physical, sensory or mental capabilities or a lack of experience and know-how, provided
that they are supervised or they have been instructed on
how to use the appliance safely and have understood
the resulting risks. Children must never play with the
appliance. Children must never clean the appliance or
perform user maintenance unless they are supervised.
Note
Do not change any system-specific settings at the control
unit. Your contractor has set the control unit to match
the local conditions for your building and your individual
requirements. The system-specific parameters are protected by a code to prevent unintentional modifications.
The parameters that serve to adapt the appliance to your
personal requirements are not protected by a code.
CE designation
The CE designation shows that the appliance meets all essential
requirements according to the:
- Electromagnetic Compatibility Directive
- Low Voltage Directive
bled. If the DHW learning function is enabled, DHW heating will
cease and the set DHW value is overwritten with the actual DHW
temperature achieved.
The WPM3i also controls the integral electric emergency/booster
heater. No further heat generator can be switched.
3.1 Special features of the WPC...cool
An additional heat exchanger and 3-way diverter valve for changing over between heating and cooling are integrated into the
WPC...cool.
To cool the living space, the brine is pumped though the additional
heat exchanger, where heat is extracted from the heating water
to be released into the cooler zones underground.
The compressor does not run during cooling.
2.4 Test symbols
See type plate on the appliance.
3. Appliance description
The appliance is a heating heat pump suitable for operation as a
brine/water heat pump. The heat pump extracts energy from the
heat source medium at a low temperature level. This extracted
energy is then transferred to the heating water at a higher level,
augmented by the electric energy drawn by the compressor. The
heating water is heated to a flow temperature of up to 60 °C,
depending on the heat source temperature.
A heating circuit pump and a multi function assembly (MFG) with
safety assembly and 3-way diverter valve have been integrated
in the appliance for directing the flow either to the heating circuit
or the DHW circuit. To heat the DHW, the heating water that has
been heated by the heat pump is directed through an indirect coil
in the DHW cylinder, where it transfers its energy to the DHW.
The appliance is equipped with an electric emergency/booster
heater (DHC). If the dual mode point can no longer be maintained
in mono mode operation, the electric emergency/booster heater
is activated to safeguard heating operation and the provision of
high DHW temperatures. In mono energetic operation the electric
emergency/booster heater is then activated as a booster heater.
The appliance is regulated by an integral, weather-compensated
return temperature controller (WPM3i heat pump manager).
The WPM3i also regulates the DHW heating to the required temperature. If either the high pressure sensor or the hot gas limiter
of the heat pump responds during DHW heating, then DHW heating
will automatically be completed by an integral electric emergency/
booster heater, subject to the DHW learning function being disa-
www.stiebel-eltron.com WPC | WPC cool | 5
Page 6
OPERATION
Operation
4. Operation
4.1 Controls
WEDNESDAY 12.JUN 1310: 23 TIME
OUTSIDE TEMPERATURE
1
2
3
1 Display
2 MENU key
3 Scroll wheel
4 OK key
You control the system with the programming unit of the heat
pump manager. Use the scroll wheel and the MENU and OK keys
to navigate through the menu structure.
ACTUAL DHW TEMP
ACTUAL RETURN TEMP
ECO MODE
27. 0 °C
35.0 °C
28.0 °C
4
Activation
If the scroll wheel and keys/fields are not used for 5minutes,
the programming unit is locked.
WEDNESDAY 12.JUN 1310:23 TIME
OUTSIDE TEMPERATURE
To activate please
ACTUAL DHW TEMP
ACTUAL RETURN TEMP
press MENU for 3 s.
27.0 ° C
35.0°C
28.0 °C
.
ECO MODE
Press MENU for 3 seconds to activate the programming unit.
Selection indicator
26�04�01�0309
An indicator shows the current position within the menu structure
at all times. The currently selected menu item is indicated by a
dark background. The current menu level is indicated at the top
of the display.
4.1.2 Scroll wheel
26�04�01�0292
4.1.1 Display
The programming unit display shows the current state of the system and provides messages and information.
Start screen
1
2
3
4
1 Date and time
2 Temperature display
3 Operating mode
4 System status picture symbols
The start screen is divided into four sections. The top field displays
the date and time. The field below displays the outside temperature along with the actual DHW temperature and the actual return
temperature. The third section is for selecting and displaying the
operating modes. In the fourth section, picture symbols indicate
the current system state.
WEDNESDAY 12.JUN 1310:23 TIME
OUTSIDE TEMPERATURE
ACTUAL DHW TEMP
ACTUAL RETURN TEMP
ECO MODE
27.0 °C
35.0 °C
28.0 °C
26�04�01�0292
The scroll wheel consists of a touch-sensitive sensor. To the left
and right of it there is one key each. All required appliance functions are controlled and checked with the scroll wheel and the
keys.
Note Sensor responsiveness
Wearing gloves, wet hands or a damp programming unit
impede the recognition of your touch and the execution
of the action you require.
26�04�01�0329
Your contractor can set the sensitivity to touch using the TOUCH
SENSITIVITY parameter under MAIN MENU / COMMISSIONING.
6 | WPC | WPC cool www.stiebel-eltron.com
Page 7
OPERATION
Operation
Circular movement
Move one finger clockwise over the scroll wheel to move the indicator downwards or to the right in the list, depending on how the
menu options are arranged. An anti-clockwise rotation moves the
selection indicator to the left or upwards in the list.
Alongside navigation within the menu structure, the scroll wheel
is also used to set parameters. Clockwise rotation increases the
values. Anti-clockwise rotation decreases values.
4.1.3 Keys
Note
Press the keys only briefly to initiate the required action.
If a key is touched for too long, the programming unit
does not respond.
MENU key
The MENU key has two functions:
- On the start screen, touch the MENU key to navigate to the
first of the 5 menu structure levels.
- Touching the MENU key while in the menu structure will return you to the previous menu level.
Example 1
Adjusting the set room temperature.
MAIN MENU
SETTINGS
+
21.7
21
-
To enter set temperatures, a number surrounded by a circle appears on the display. This indicates that you can change the value
by turning the scroll wheel.
Example 2
Setting the time and date.
MAIN MENU
SETTINGS
HEATING CIRCUIT 1
HEATING HC1
°C SET ROOM TEMP COMFORT
TIME /DATE
GENERAL
SET ROOM TEMP CO
SET CLOCK
26�04�01�0347
OK key
The OK key has four functions:
- On the start screen, touching the OK key will activate the
required operating mode previously selected with the scroll
wheel.
- Within the menu structure, touching the OK key confirms the
selected menu option and takes you to the next lower menu
level.
- If you are already at parameter level, touching the OK key
saves the currently set parameter.
- At every menu level, you will see the entry BACK. Selecting
BACK takes you to the next higher menu level.
If there is no user action for more than five minutes, no rotation
and neither
display automatically jumps back to the start screen.
Any recent parameter changes which had not yet been confirmed
with OK are lost. The parameters retain the values previously
saved.
4.1.4 Contractor access
MENU nor OK are pressed, the programming unit
Note
Some menu options are protected by a code and can only
be viewed and adjusted by a qualified contractor.
15.
DAY MONTH YEAR Hour Minute
On activation, the selection indicator is over the position MONTH.
Confirm with OK. Set the current month with the scroll wheel and
confirm with OK. A calendar page is displayed. Move the indicated
field to the required day using the scroll wheel and confirm with
OK. The new value is saved when you confirm with OK. Set the
year, hours and minutes the same way.
09 08:23
Jun
13
26�04�01�0296
4.2 Entering parameters
Parameters are changed by rotating the scroll wheel. To save the
new value, touch OK.
If you want to cancel the entry, touch
tains the previously saved value.
www.stiebel-eltron.com WPC | WPC cool | 7
MENU. The parameter re-
Page 8
OPERATION
Operation
4.3 Selecting operating modes
When activating the start screen, the current operating mode is
displayed. If you want to select another operating mode, turn the
scroll wheel. This takes you through the list of possible operating
modes. The current choice (list entry) is shown in the shaded
selection field.
Note
To change the appliance to this new operating mode,
confirm with OK.
WEDNESDAY 12.JUN 1310:23 TIME
OUTSIDE TEMPERATURE
ACTUAL DHW TEMP
ACTUAL RETURN TEMP
ECO MODE
Since navigation to a new operating mode is always made from the
currently enabled mode, you may need to move in an anti-clockwise direction. All operating modes, apart from DHW mode, apply
to both central heating and DHW.
Standby mode
Frost protection is activated for heating and DHW mode. The set
DHW value is fixed at 10°C, the set heating flow value is calculated
based on a set room value of 5°C.
Application: During prolonged periods of absence, e.g. holidays.
27. 0 ° C
35.0 °C
28.0 °C
DHW mode
DHW heating according to time switch program. If a time program
is active, the water inside the DHW cylinder is heated to the set
comfort temperature. At all other times, the water is heated to
the set ECO temperature. Frost protection is activated for heating
operation.
Application: The heating season has ended; only DHW should be
provided (summer mode).
Emergency mode
In this operating mode, the heat pump is blocked. The BH stages
(electric booster stages) of the emergency/booster heater heat
according to the selected time program for heating and DHW operation.
Inform your contractor immediately.
4.4 Picture symbols
At the lower edge of the display, symbols provide information
about the current appliance operating status.
26�04�01�0292
Heating circuit pump
The pump symbol is displayed when a heating circuit
pump is running.
Mixer circuit pump
The mixer symbol is displayed when a mixer circuit pump
is running.
Heat-up program
This symbol is displayed when the heat-up program is
running.
Programmed operation
Heating in line with the time switch program (applies to heating
circuits1 and2). Changeover between Comfort temperature and
ECO temperature.
DHW heating in line with the time switch program; changeover
between Comfort temperature and ECO temperature.
The remote control is only active in this operating mode.
Application: When DHW and central heating are required.
Comfort mode
The heating circuit (HC) is constantly held at the comfort temperature (HC1 and HC2). DHW heating according to time switch
program.
Application: Low energy houses without setback mode.
ECO mode
The heating circuit is constantly held at the ECO temperature (applicable to HC1 and HC2). DHW heating according to time switch
program.
Application: During weekends away.
Electric emergency/booster heater
The electric emergency/booster heater has started up.
This occurs, for example, when the outside temperature
has fallen below the dual mode point.
Heating
The heating symbol is displayed when the appliance is
in heating mode.
DHW heating
This symbol indicates that the heat pump is heating DHW.
Compressor
The symbol is displayed when the compressor is running.
Summer mode
The symbol is displayed when the appliance is in summer
mode.
Cooling
The symbol is displayed when the appliance is in cooling
mode.
8 | WPC | WPC cool www.stiebel-eltron.com
Page 9
OPERATION
Menu structure
5. Menu structure
After activating the programming unit, you can use the scroll
wheel to select other operating modes, or you can use the menu
key to jump to a level from which you can navigate to a specific
appliance parameter.
Level 1Level 2
INFOSYSTEM
HEAT PUMP
DIAGNOSISSYSTEM STATUS
HEAT PUMP STATUS
SYSTEM
INTERNAL CALCULATION
FAULT LIST
RELAY TEST SYSTEM
PROGRAMSHEATING PROGRAM
DHW PROGRAM
PARTY PROGRAM
HOLIDAY PROGRAM
HEAT-UP PROGRAM
SETTINGSGENERAL
HEATING
DHW
COOLING
COMMISSIONINGENTER CODE
LANGUAGE
SOURCE
HEATING
DHW
COMPRESSOR
EMERGENCY OPR
HEAT PUMP RESET
FAULT LIST RESET
SYSTEM RESET
Level 3
SET TEMPERATURE FEK
Set room temperature for heating circuit 1 or heating circuit 2
(is only displayed if the FE7 remote control is connected)
REL HUMIDITY%
DEW POINT TEMPERATURE
Dew point temperature (is only displayed if the FEK remote control is
connected)
HEAT ING
OUTSIDE TEMPERATURE°C
ACTUAL TEMPERATURE HC 1
Actual heating circuit temperature, heating circuit 1
SET TEMPERATURE HC 1
Set heating circuit temperature, heating circuit 1 (HC1). With fixed
value control, the set fixed temperature is displayed.
ACTUAL TEMPERATURE HC 2
Actual heating circuit temperature, heating circuit 2
SET TEMPERATURE HC 2
Set heating circuit temperature, heating circuit 1 (HC1). With fixed
value control, the set fixed temperature is displayed.
ACTUAL FLOW TEMPERATURE HP
Actual heat pump flow temperature
ACTUAL FLOW TEMPERATURE BH
Actual flow temperature of electric emergency/booster heater
ACTUAL RETURN TEMP°C
SET FIXED TEMPERATURE°C
ACTUAL BUFFER TEMPERATURE
Actual buffer cylinder temperature
SET BUFFER TEMPERATURE
Set buffer cylinder temperature
HEATING PRESbar
FLOW RAT El/min
SYST FROST PRO
System frost protection temperature
DHW
ACTUAL TEMPERATURE
ACTUAL DHW TEMPERATURE
SET TEMPERATURE
SET DHW TEMPERATURE
FLOW RAT El/min
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
5.1 INFO menu
In the INFO menu you can check comparisons of set and actual
values for temperatures, flow rates and pressures of the heating
system and the heat pump.
Note
Please note that actual and set values can only be displayed if the appropriate sensors are connected.
5.1.1 INFO SYSTEM
Level 3
ROOM TEMPERATURE
ACTUAL TEMPERATURE FE7
Actual room temperature for heating circuit 1 (HC1) or heating circuit
2 (HC2)
(is only displayed if the FE7 remote control is connected)
SET TEMPERATURE FE7
Set room temperature for heating circuit 1 or heating circuit 2
(is only displayed if the FE7 remote control is connected)
ACTUAL TEMPERATURE FEK
Actual room temperature for heating circuit 1 or heating circuit 2
(is only displayed if the FEK remote control is connected)
°C
°C
°C
COOLING
ACTUAL TEMPERATURE FAN°C
SET TEMPERATURE FAN°C
ACTUAL TEMPERATURE AREA°C
SET TEMPERATURE AREA°C
SOURCE TEMPERATURE°C
SOURCE TEMPERATURE MIN°C
SOURCE PRESSUREbar
°C
°C
°C
°C
www.stiebel-eltron.com WPC | WPC cool | 9
Page 10
OPERATION
Menu structure
5.1.2 INFO HEAT PUMP
Level 3
PROCESS DATA
HOT GAS TEMPERATURE
Compressor outlet temperature
HIGH PRESSUREbar
LOW PRESSUREbar
AMOUNT OF HEAT
COMPRESSOR HEATING DAY
Amount of compressor heat generated in heating mode since 00:00
h of current day, in kWh.
COMPRESSOR HEATING TOTAL
Total amount of compressor heat generated in heating mode, in
MWh.
COMPRESSOR DHW DAY
Amount of compressor heat generated in DHW mode since 00:00 h
of current day, in kWh.
COMPRESSOR DHW TOTAL
Total amount of compressor heat generated in DHW mode, in MWh.
BH HEATING TOTAL
Total amount of heat generated by the electric emergency/booster
heater in heating mode, in MWh.
BH DHW TOTAL
Total amount of heat generated by the electric emergency/booster
heater in DHW mode, in MWh.
°C
kWh
MWh
kWh
MWh
MWh
MWh
POWER CONSUMPTION
COMPRESSOR HEATING DAY
Electrical output of compressor in heating mode since 0:00 h today.
COMPRESSOR HEATING TOTAL
otal electrical output of compressor in heating mode.
COMPRESSOR DHW DAY
Electrical output of compressor in DHW mode since 0:00 h today.
COMPRESSOR DHW TOTAL
Total electrical output of compressor in DHW mode
RUNTIMES in hours
HEATING COMPRESSOR 1
Runtime of compressor 1 in heating mode.
DHW COMPRESSOR 1
Runtime of compressor 1 in DHW mode.
COOLING COMPRESSOR 1
Runtime of compressor 1 in cooling mode.
BH 1
Runtime of electric emergency/booster heater in booster stage 1.
BH 2
Runtime of electric emergency/booster heater in booster stage 2.
BH 1/2
Runtime of electric emergency/booster heater in booster stages 1
and 2.
kWh
MWh
kWh
MWh
Hours
Hours
Hours
Hours
Hours
Hours
10 | WPC | WPC cool www.stiebel-eltron.com
Page 11
OPERATION
Menu structure
5.2 DIAGNOSIS menu
For heating system and heat pump troubleshooting and analysis,
you can query all important process data and bus subscribers
under DIAGNOSIS and carry out a relay test.
Note
The menu item RELAY TEST SYSTEM is protected by a
code and can only be accessed by a qualified contractor.
Level 2Level 3Level 4
SYSTEM STATUSBUFFER CHARGING PUMP
DHW VALVE
HTG CIRC PUMP
MIXER PUMP
MIXER OPEN
MIXER CLOSED
SOURCE PUMP
COOLING MODE
POWER BLOCKED
HEAT PUMP STATUSREM IDLE TIME in minutes
COMPRESSOR
BH 1
BH 2
SYSTEMBUS SUBSCRIBERSUBSCRIBER
SOFTWARE NO.
HEAT PUMP TYPEHEAT PUMP
5.2.1 Fault list
The fault list provides an overview of the faults most recently
registered by the appliance. The fault list contains up to 20 fault
messages. The display, however, can show only 2. Turn the scroll
wheel to access the other entries in the fault list.
MAIN MENUDIAGNOSIS
FAULT LIST 1/1
01.SENSOR BREAK E 71
10:26 14.JUN 13
02.MIN SRCE TEMP
17:45 25. JUN 13
5.2.2 Fault message
If the appliance registers a fault, this is clearly displayed with the
message shown below.
If more than one fault occurs, the most recent fault is always
shown. Notify your qualified contractor.
5.2.3 Relay test
All relay outputs of the controller can be individually switched
from here.
www.stiebel-eltron.com WPC | WPC cool | 11
Page 12
OPERATION
Menu structure
5.3 PROGRAMS menu
All set times for heating, DHW, holiday and party modes can be
adjusted here, in addition, the heat-up program can be started.
Level 2Level 3Level 4
HEATING PROGRAMHEAT CIRCUIT 1
HEAT CIRCUIT 2
DHW PROGRAM
PARTY PROGRAMHOURS
HOLIDAY PROGRAMHOLS BEGINNING
HOLIDAYS ENDING
HEAT-UP PROGRAMON / OFFLOW END TEMPERA-
TURE
TEMP. RISE PERIOD
MAXIMUM TEMPERA-
TURE
MAX TEMPERATURE
DURAT ION
RISE PER DAY
5.3.1 HEATING PROGRAM
In the menu item HEATING PROGRAM you can determine when
and how often the appliance heats to the set comfort values for
heating circuit1 and heating circuit2. At all other times, the appliance heats to the set ECO value. You can adjust the set values under
menu item SETTINGS / HEATING / HEAT CIRCUIT1 or HEAT CIRCUIT2. Below is an explanation of how to define a time program.
First, select the days on which you want to enable the HEATING
function:
MAIN MENU
PROGRAMS
HEATING PROGRAM
HEAT CIRCUIT 1
MONDAY
07:00 - 20:00
- -:- - - - -:- -
- -:- - - - -:- -
In this example, only one switching time pair has so far been
programmed. For switching time pairs 2 and 3, short dashes are
displayed instead of times. These switching time pairs are still
empty. Select one of the free switching time pairs with OK to reach
the level where you can set the associated start and end time.
Pressing OK brings up the display shown below. Set the required
time with the scroll wheel.
MAIN MENU
PROGRAMS
HEATING PROGRAM
- -:- -
Start
Times can be entered in intervals of 15 minutes. You can set 16:30
or 16:45 h, but not 16:37 h. Confirm your entry with OK.
HEAT CIRCUIT 1
HH
- -:- -
End
26�04�01�0299
26�04�01�0302
MAIN MENU
PROGRAMS
HEATING PROGRAM
HEAT CIRCUIT 1
+
Monday
Mon
-
You can set your heating system as follows:
- For each individual day of the week (Monday - Sunday)
- Monday to Friday (Mon - Fri)
- Saturday and Sunday (Sat - Sun)
- The whole week (Mon - Sun)
Monday is initially offered.
Turn the scroll wheel to select another day or group of days.
Confirm your selection with OK.
You can now set three switching time pairs. The three switching
time pairs are shown on the display, to the right of the clock. A
switching time pair comprises the start time and end point, at
which the appliance returns to its previous state.
Periods around midnight
Assume, for example, you want heating mode to be enabled from
22:00 h for four hours every Wednesday evening. This means the
period does not expire until the next day, Thursday, at 02:00 h.
Since the day ends at 00:00, two switching time pairs are necessary
for the required program. First, program the period 22:00 to 00:00
h for Wednesday, then 00:00 to 02:00 h for Thursday.
5.3.2 DHW PROGRAM
26�04�01�0301
In the menu item DHW PROGRAM you can determine the times
during which DHW heating with the set comfort value should take
place. At all other times, DHW is heated to the set ECO value. You
can select the set values under menu item SETTINGS/DHW/DHW
TEMPERATURES.
You can set your DHW heating as follows:
- For each individual day of the week (Monday - Sunday)
- Monday to Friday (Mon - Fri)
- Saturday and Sunday (Sat - Sun)
- The whole week (Mon - Sun)
You can set three switching time pairs for each of these options.
Exception: If you want to heat DHW from 22:00 h until 06:00 h the
following day you will need two switching time pairs.
Example:
12 | WPC | WPC cool www.stiebel-eltron.com
Page 13
OPERATION
Menu structure
You would like to heat DHW twice daily, from 22:00 h until 06:00 h
the following day, and then from 08:00 h until 09:00 h.
As the day begins at 00:00 h, programming for this example must
again start at 00:00 h.
- The first switching time pair runs from 00:00 h until 06:00 h.
- The second switching time pair runs from 08:00 h until 09:00
h.
- The third switching time pair runs from 22:00 h until 24:00 h.
5.3.3 PARTY PROGRAM
In the party program you can extend the comfort mode for heating
by a few hours.
5.3.4 HOLIDAY PROGRAM
In the holiday program, the heat pump system runs in ECO mode
and frost protection for DHW heating is enabled.
For both the start and end of the holiday, enter the year, month
and day. The start time is 0:00 h on the first day of the holiday. The
end time is 24:00 h on the day the holiday ends. After the holiday
period has expired, the heat pump system switches back to the
previous heating and DHW program.
5.3.5 HEAT-UP PROGRAM
Note
The menu item HEAT-UP PROGRAM is protected by a
code and can only be accessed and set by a qualified
contractor.
3
1
2
6
Y Temperature
X Time
1 Maximum temperature
2 Low end temperature
3 Low end temperature duration
4 Increase K/day
5 Maximum temperature duration
6 Start
7 End
Please note that only the mixer circuit pump is running when
operating with 2 heating circuits.
If only direct heating circuit 1 is operational, the return sensor is
again used for control. As the actual temperature inside the buffer
cylinder is higher at the heating flow, this configuration results in
5 K being deducted from the set heat-up program values (low end
and maximum temperatures).
45
7
84�03�01�0038
Heat-up program for underfloor heating systems
Never use the heat pump for drying screed, as this places an
excessive demand on the heat source and may cause it to be
damaged. Use the electric emergency/booster heater for the
heat-up program. For this, set LOWERAPPLIMITHEATING and
DUALMODETEMPHEATING parameters to 30°C and start the
heat-up program.
Emergency mode cannot be enabled in the heat-up program.
There are a total of 6 parameters for the heat-up program. These
6 parameters can be adjusted in sequence as soon as the heat-up
program is activated. The program is started with the HEAT-UP
PROGRAM parameter and with the setting ON. The system then
heats to the selected low end temperature. The low end temperature is held for the set period (parameter TEMPRISEPERIOD).
After expiry of this period, the system heats to the maximum low
end temperature (parameter MAXIMUMTEMPERATURE) using an
increase K/day (parameter RISEPER DAY) and holds this maximum temperature for the selected time (parameter MAXTEMPERATURE DURATION). The system subsequently returns to the
low end temperature using the same steps as for heat-up. This
concludes the heat-up program. As soon as 2 heating circuits
are operational, both will be operated in line with the heat-up
program (operation with buffer cylinder and mixer circuit). Direct
heating circuit1 (buffer circuit with return sensor) adopts the
set values of the heat-up program. Since this is regulated via the
return sensor, the actual temperature inside the buffer cylinder is
higher at the heating flow. The mixer (heating circuit 2) regulates
the temperature back down to the set values selected in the heatup program (low end temperature and maximum temperature).
The summer logic is disabled whilst the heat-up program runs.
www.stiebel-eltron.com WPC | WPC cool | 13
Page 14
OPERATION
Menu structure
5.4 SETTINGS menu
Here you can select all system-specific parameters for heating, cooling and DHW modes as well as general settings such as the time.
Note
Some menu options are protected by a code and can only be viewed and adjusted by a qualified contractor.
Level 2Level 3Level 4Level 5
GENERALTIME / DATETIME
YEAR
MONTH
DAY
SETTING SUMMER TIMEDAY BEGINNING
DAY ENDING
CONTRAST
BRIGHTNESS
TOUCH SENSITIVITY
TOUCH ACCELERATION
HEATINGHEAT CIRCUIT 1SET ROOM TEMP COMFORT
SET ROOM TEMP ECO
HEATING CURVE RISE
HEATING CURVE
HEAT CIRCUIT 2SET ROOM TEMP COMFORT
SET ROOM TEMP ECO
HEATING CURVE RISE
HEATING CURVE
STANDARD SETTINGBUFFER OPERAT
SUMMER MODEOUTSIDE TEMPERATURE
MAXIMUM RETURN TEMP
MAXIMUM FLOW TEMP
MIXER DYNAMICS
MAXIMUM MIXER TEMPERATURE
FIXED VALUE OPERATION
HEATING CIRCUIT OPTIMAL
FROST PROTECT
REMOTE CONTROL FE7HEATING CIRC PRESELECTION
ROOM INFLUENCE
ROOM CORRECTION
PUMPCYCLESON / OFF
BUILDING HEAT BUFFER
ELECTRIC REHEATINGDUAL MODE TEMP HEATING
LOWER APP LIMIT HEATING
DHWDHW TEMPERATURESSET DHW TEMP COMFORT
SET DHW TEMP ECO
STANDARD SETTINGDHW HYSTERESIS
DHW LEARNING FUNCTION
DHW CORRECTION
COMBI CYLINDER
PASTEURISATIONON / OFF
ELECTRIC REHEATINGDUAL MODE TEMP DHW
LOWER APP LIMIT DHW
14 | WPC | WPC cool www.stiebel-eltron.com
Page 15
OPERATION
Menu structure
COOLINGCOOLINGON / OFF
COOLING MODEPASSIVE COOLING / ACTIVE COOLING
ACTIVE COOLINGAREA COOLINGSET FLOW TEMPERATURE
FAN COOLINGSET FLOW TEMPERATURE
PASSIV E COOLINGAREA COOLINGSET FLOW TEMPERATURE
FAN COOLINGSET FLOW TEMPERATURE
FLOW TEMP HYSTERESIS
SET ROOM TEMPERATURE
DYNAMIC
FLOW TEMP HYSTERESIS
SET ROOM TEMPERATURE
DYNAMIC
FLOW TEMP HYSTERESIS
SET ROOM TEMPERATURE
FLOW TEMP HYSTERESIS
SET ROOM TEMPERATURE
5.4.1 GENERAL
TIME / DATE
Here you can set the time, year, month and day.
SETTING SUMMER TIME
Here you can adjust the settings for summer time.
Summer time is factory set to begin on 25March and to end on
25October.
CONTRAST
Here you can adjust the display contrast.
BRIGHTNESS
Here you can adjust the display brightness.
TOUCHSENSITIVITY and TOUCH ACCELERATION
A code is required for this adjustment.
5.4.2 HEATING
HEAT CIRCUIT 1 and HEAT CIRCUIT 2
SET ROOM TEMP COMFORT and SET ROOM TEMP ECO
Here you can select the set room temperatures for comfort mode
and ECO mode as well as the heating curve rise for heating circuit1
and heating circuit2.
Changing the set room temperature results in a parallel shift of
the heating curve.
As soon as the FE7 remote control has been connected and allocated to heating circuit 1, the actual room temperature can also
be scanned.
As soon as the FE7 or FEK remote control has been connected
and allocated to heating circuit2, the actual room temperature
can also be scanned.
The display HEAT CIRCUIT2 only appears if the mixer flow sensor
for heating circuit2 has been connected.
HEATING CURVE RISE
The menu item HEATING CURVE RISE enables you to set one heating curve each for heating circuits1 and 2.
Note: Your contractor will have set a building and system-specific
optimum heating curve for every heating circuit. For heating circuit 1 the curve relates to the heat pump return temperature, for
heating circuit 2 to the mixer flow temperature.
When you adjust the heating curve on the heat pump manager, the
calculated set return or flow temperature, subject to the outside
temperature and the set room temperature, will be shown at the
top of the display.
As soon as you have preselected a temperature in menu SETTINGS
/ HEATING / STANDARD SETTING under parameter FIXED VALUE
OPERATION, heating curve 1 is hidden from view and the display
showsSETFIXED TEMPERATURE with the relevant temperature.
www.stiebel-eltron.com WPC | WPC cool | 15
Page 16
OPERATION
Menu structure
HEATING CURVE
Adjustment of programmed changeover between Comfort and
ECO mode
The figure shows the diagram with the set heating curve relating
to a set room temperature for comfort mode. The second, dashed
line relates to a set room temperature for ECO mode.
60
40
20
0
20151050-5-10-15-20
1
2
Y Return / flow temperature [°C]
X Outside temperature [°C]
1 Comfort mode
2 ECO mode
Adapting a heating curve
Example:
With heating systems, the temperature in a building during the
transitional periods (spring and autumn) is too low when outside
temperatures are between 5 °C and 15°C, despite open radiator
valves, but is OK at outside temperatures ≤ 0°C. This problem can
be remedied with a parallel shift and a simultaneous reduction
of the heating curve.
Heating curve 1.0 was initially adjusted relative to a set room temperature of 20 °C. The dotted line indicates the modified heating
curve at 0.83 and a modified set room temperature of 23.2°C.
60
40
20
0
20151050-5-10-15-20
Y Return / flow temperature [°C]
X Outside temperature [°C]
STANDARD SETTING
BUFFER OPERAT
When using a buffer cylinder, set this parameter to ON.
SUMMER MODE
Parameter SUMMER MODE enables you to define the point at
which the heating system is to switch to summer mode. Summer
mode can be switched on or off. There are 2 adjustable parameters
for this function.
-Parameter OUTSIDE TEMPERATURE:
Outside temperature adjustable from 10 °C to 30 °C
26�03�01�1915
-Parameter BUILDING HEAT BUFFER
This parameter lets you choose whether an average outside temperature should be determined, according to the type of building.
You can choose from 3 settings.
Setting "1": Minor insulation towards outside temperatures (averaging over a 24 h period), e.g.for timber construction with rapid
heat transfer.
Setting "2": Moderate insulation towards outside temperatures
(averaging over a 48 h period), e.g. brick construction with thermal
insulation and average heat transfer.
Setting "3": Strong insulation towards outside temperatures (averaging over a 72 h period). House with slow heat transfer.
If the determined outside temperature is ≥ than the selected outside temperature, both heating circuits (if installed) enter summer
mode; reverse hysteresis –1 K.
With fixed-value control, summer mode is disabled for heating
circuit 1.
MAXIMUM RETURN TEMP
Setting range 20 °C to 55 °C.
If the temperature at the return sensor reaches this set value dur-
26�03�01�1916+
ing heating operation, the heat pump is immediately switched
off. This safety function prevents the high pressure switch from
responding. No fault message is issued when this value is reached.
During DHW operation the return temperature is not scanned.
MAXIMUM FLOW TEMP
Maximum heat pump flow temperature for central heating
Setting range 20 °C to 65°C.
This setting limits the flow temperature of the heat pump and the
electric emergency/booster heater in heating mode.
MIXER DYNAMICS
Mixer runtime
Setting range 60 to 240
You can use this setting to adapt the mixer characteristics. The
setting 60 to 240 means 6 K to 24 K control deviation.
16 | WPC | WPC cool www.stiebel-eltron.com
Page 17
OPERATION
Menu structure
The scan rate is 10 s and the minimum on time for the mixer is
0.5 s. The mixer does not respond in the dead zone of ±1 K from
the set value.
Example for the setting 100 = 10 K
The control deviation (set mixer temperature – actual mixer temperature) is 5K. The mixer opens for 5 s, then pauses for 5 s and
starts again.
The control deviation (set mixer temperature – actual mixer temperature) is 7.5 K. The mixer opens for 7.5 s, then pauses for 2.5
s and starts again.
The smaller the control deviation, the shorter the mixer on time
and the longer the pauses.
A reduction of the MIXER DYNAMIC value with the control deviation unchanged increases the on duration and reduces pauses.
Example for setting 100 and a current control deviation of 5 K.
5 K of 10 K = 50% = on duration
Example: Control deviation
1
± 1 K
HEATING CIRCUIT OPTIMAL
When an Uponor DEM-WP module is connected, the heating curve
is dynamically optimised for the heat demand of individual rooms.
This involves modifying the preset heating curve by up to 50%
of its original value.
The parameter HEATINGCIRCUITOPTIMAL is only displayed when
the buffer operation parameter is set to "OFF" and neither a mixer
sensor nor an FE7 remote control are connected.
The parameter HEATINGCIRCUITOPTIMAL can be set to "ON" or
"OFF". The default value is "OFF".
This parameter may only be set to "ON" when an Uponor DEM WP
module is connected.
This function is only active in comfort mode, ECO mode and programmed operation.
FROST PROTECT
To protect the heating system from frost, start the heating circuit
pumps at the selected frost protection temperature; the reverse
hysteresis is 1K.
2
4
3
1 Setting 100 = control deviation 10 K
2 Control deviation 5 K
3 Control deviation in K
4 On time in %
MAXIMUM MIXER TEMPERATURE
Setting range 20 °C to 90°C.
This setting limits the flow temperature of the mixer circuit. For
example, if a higher set flow temperature is calculated from the
mixer circuit data, the max. set mixer flow temperature will be
used to control and regulate to this value.
FIXED VALUE OPERATION
The heat pump return is regulated to the set fixed value. The
switching time program will then be ignored. The various positions of the program selector will then only affect the mixer circuit
(if installed). When the program selector is set to standby and a
fixed temperature has been selected the frost protection is activated and the compressor is switched off. Summer logic remains
disabled with fixed temperature control. This means that the heating circuit pump is not switched off for the direct heating circuit.
26�03�01�1067
www.stiebel-eltron.com WPC | WPC cool | 17
Page 18
OPERATION
Menu structure
REMOTE CONTROL FE7
This menu item is only displayed when the FE7 remote control is
connected.
HEATING CIRC PRESELECTION
The FE7 remote control can be selected for both heating circuits.
This parameter lets you choose which heating circuit the remote
control is to act on. Depending on the remote control preselection,
the actual room temperature can be checked under INFO / SYSTEM
/ ROOM TEMPERATURE.
ROOM INFLUENCE
Standard setting 5 adjustable from ---- via 0 to 20 Dashes (----)
in the display:
With the FE7 remote control connected, the room temperature
sensor only serves to record and display the actual room temperature; it has no influence on the actual control. The remote control
can be used to adjust the room temperature for heating circuit 1
or 2 by ± 5 °C in automatic mode only. This set value adjustment
applies to the current heating time, not to the setback time.
At the same time, the setting "0 to 20" serves to control the room
temperature-dependent night setback. This means that the heating circuit pump is switched off at the point of changeover from the
heating into the setback phase. It remains off until the actual room
temperature falls below the set room temperature. After this, the
system continues to regulate in weather-compensated mode.
If you want the room temperature to be taken into account, set
the room temperature sensor influence to a value > 0. The room
sensor influence has the same effect as the outside temperature
sensor has on the return temperature, except that the effect is 1
to 20 times greater, depending on the factor set.
-Room temperature-dependent return / flow temperature
with weather compensation
With this type of control, a control cascade is formed from both
weather-compensated and room temperature dependent return/
flow temperature control. This means that the weather-compensated return/flow temperature control sets a default return/flow
temperature that is corrected by the overriding room temperature
control in accordance with the following formula:
∆ϕ
= (ϕ
R
RSOLL
− ϕ
RIST
) * S * K
Because a substantial proportion of the control is already handled by the weather-compensated control, the room temperature
sensor compensation factor K can be set lower than with pure
room temperature control (K=20). The figure indicates the control
method with the set factor K=10 (room influence) and a heating
curve S=1.2.
-Room temperature control with weather-compensation
This type of control offers two main benefits:
Incorrectly set heating curves are corrected by the room sensor
influence K; whilst the smaller factor K means the control unit
works in a more stable manner.
However, observe the following for all control units with room
temperature sensor influence:
- The room temperature sensor must capture the room temperature accurately.
- Open doors and windows greatly affect the control result.
- All radiator valves in the lead room must be fully open at all
times.
- The temperature inside the lead room affects the entire heating circuit.
If you want the room temperature to be taken into account, set the
room temperature sensor influence to a value > 0.
90
80
70
1
60
1
50
1
40
30
20
10
Y
0
X 1
20
1917 1821 22 23 24 25
3
4
5
Y
X 2
10
15
20
2
-10
-5
0
5
-20
-15
Y Flow temperature [°C]
X 1 Room temperature [°C]
X 2 Outside temperature [°C]
1 Room temperature sensor influence at K = 10 and S = 1.2
and control deviation +/- 2 K
2 Heating curve S = 1.2
3 Weather-compensated set flow temperature at ϕA = - 10
°C
4 Weather-compensated set flow temperature at ϕA = 0 °C
5 Weather-compensated set flow temperature at ϕA = + 10
°C
ROOM CORRECTION
You can use this parameter to calibrate the measured room temperature.
PUMPCYCLES
-Heating circuit pump control
The PUMP CYCLES parameter only applies to the direct heating
circuit1, i.e. for heating circuit pump 1.
This parameter can be switched ON or OFF. In the OFF position,
the heating circuit pump will not cycle. It will operate constantly.
It is only switched off in summer mode.
As soon as you set the parameter to ON, the heating circuit pump
will be switched in line with a fixed temperature curve for the
outside temperature.
The heating circuit pump start pulse is always 5minutes.
The heating circuit pump for heating circuit 1 always starts with
each heat pump start. The pump runs on for 5 minutes after the
heat pump has been shut down. This is where the start-up duration is brought to bear, e.g.at an outside temperature of 5°C, the
pump starts 3 times per hour for 5minutes respectively.
26�03�01�1917
18 | WPC | WPC cool www.stiebel-eltron.com
Page 19
OPERATION
Menu structure
5.4.3 DHW
< -10
-10
-5
0
5
Y
10
0102030405060
1
2
Y Outside temperature in °C
X Time in minutes
1 Pause
2 Pump run time
-Pump kick
To prevent the pumps seizing up, for example over summer, the
pumps are switched on for 10 seconds after every 24 hour period
of inactivity. This applies to all pumps.
-Heating circuit pump control with FE7 / FEK remote control
connected
In conjunction with the FE7 or FEK remote control, the switching
condition
ϕ
ACTUAL room
>ϕ
SET room
+ 1K
causes the respective heating circuit pump to be switched off,
while the mixer moves to CLOSE. This only applies if the room
sensor influence is set to K > 0. Reverse switching is subject to
the following condition:
ϕ
ACTUAL room
>ϕ
SET room
The summer mode is also effective for the respective heating circuit when operating with a FE7 or FEK remote control.
DHW TEMPERATURES
SET DHW TEMP COMFORT and SET DHW TEMP ECO
Here you can select the set DHW temperatures for Comfort and
ECO mode.
STANDARD SETTING
DHW HYSTERESIS
This is where you determine the switching hysteresis for DHW
heating.
- Starting DHW heating at the set DHW temperature minus the
84�03�01�0039
hysteresis value.
DHW LEARNING FUNCTION
Setting OFF
When heating DHW, the system automatically adjusts itself to the
required DHW temperature (self-learning function).
The electric emergency/booster heater will be added as a booster
stage as soon as the heat pump is shut down in DHW mode via
the HP sensor or via the hot gas temperature limit (130 °C). If the
flow temperature of 70°C is achieved in this operating mode,
DHW heating will be terminated, and the set DHW temperature is
overwritten with the actual DHW temperature.
Setting ON
As soon as the heat pump is shut down in DHW mode via the HP
sensor or the hot gas temperature limit (130 °C), DHW heating is
terminated and the set DHW temperature will be overwritten with
the current actual DHW temperature. This operating mode saves
energy, as DHW is exclusively heated by heat pump.
DHW CORRECTION
The DHW temperature is measured in the bottom third of the
cylinder. The DHW outlet temperature is approx.3K higher than
the measured temperature. This deviation is corrected and can be
calibrated if necessary.
ELECTRIC REHEATING
DUAL MODE TEMP HEATING
Dual mode temperature of the heat pump for heating operation
COMBI CYLINDER
As soon as you set the parameter to ON, the heating circuit pumps
are switched off during DHW heating.
(Only in conjunction with the SBS instantaneous water cylinder)
Below this outside temperature, the electric emergency/booster
heater is switched on for heating operation, subject to load.
LOWER APP LIMIT HEATING
Heat pump application limit
PASTEURISATION
The DHW cylinder is heated daily at 01:00 h to 60 °C if pasteurisation has been enabled. Pasteurisation only takes place when the
electric emergency/booster heater is connected.
The heat pump is switched off if the outside temperature drops
below the selected lower application limit for heating.
The electric emergency/booster heater alone provides central
heating.
www.stiebel-eltron.com WPC | WPC cool | 19
Page 20
OPERATION
Menu structure
ELECTRIC REHEATING
DUAL MODE TEMP DHW
Dual mode temperature of the heat pump for DHW heating.
Below this outside temperature, the electric emergency/booster
heater is switched on for DHW heating, subject to load.
LOWER APP LIMIT DHW
Lower application limit of the heat pump for DHW heating.
The heat pump is switched off at outside temperatures below the
selected lower DHW application limit.
The electric emergency/booster heater alone provides DHW heating.
5.4.4 COOLING
The appliance is designed for DHW and central heating. Passive
cooling is possible in conjunction with the WPC cool. In the delivered condition, the COOLING parameter is set to OFF. Active
cooling mode is only possible in conjunction with the WPAC 2
cooling module.
COOLING
On / OFF
COOLING MODE
PASSIVE COOLING / ACTIVE COOLING
ACTIVE COOLING
AREA COOLING
- FLOW TEMPERATURE
- FLOW TEMP HYSTERESIS
- SET ROOM TEMPERATURE
- DYNAMIC
FAN COOLING
- FLOW TEMPERATURE
- FLOW TEMP HYSTERESIS
- SET ROOM TEMPERATURE
- DYNAMIC
PASSIVE COOLING
AREA COOLING
- FLOW TEMPERATURE
- FLOW TEMP HYSTERESIS
- SET ROOM TEMPERATURE
FAN COOLING
- FLOW TEMPERATURE
- FLOW TEMP HYSTERESIS
- SET ROOM TEMPERATURE
Appliance and system damage
!
You must not enable the COOLING parameter without a
cooling module.
WPC 04 - 16 with WPAC 2 cooling module
Appliance and system damage
!
Set the COOLING parameter to ACTIVE COOLING.
Note
The COOLING parameter will only be shown if an FEK or
FE7 remote control is connected. Cooling mode is only
possible in summer mode.
The WPC with the WPAC 2 cools in 2 stages:
Stage 1 (source pump)
Heat is extracted from the heating circuit and is passed to the
heat source system.
Stage 2 (source pump + compressor)
In addition, the refrigerant circuit extracts heat from the heating
circuit and transfers it to the heat source system.
DHW heating
DHW heating always has priority. As long as the actual temperature has not dropped below the set flow or room temperature, active cooling continues even during DHW heating, and any extracted
heat is transferred to the DHW. If there is no cooling demand, DHW
is conventionally heated via the heat source system.
Cooling mode with the FE7
The FE7 remote control is not equipped with dew point monitoring. It can therefore only be used in conjunction with fan convectors with condensate drain. The cooling mode parameter must
be set to FAN.
Cooling mode with the FEK
The FEK remote control is equipped with dew point monitoring,
and can therefore be used with area heating systems (e.g. underfloor/wall heating systems, etc.). The COOLING parameter must be
set to AREA COOLING. The set flow temperature is compared with
the captured dew point temperature, so the actual temperature
never drops below the dew point. When using fan convectors
with the FEK remote control, set the COOLING parameter to FAN
COOLING.
In the COOLINGparameter, you can select the following cooling
modes for the FE7 and the FEK:
- Room temperature
Cooling mode starts when the selected room temperature is
exceeded (output COOLING=230 V).
Cooling mode is stopped when the actual room temperature
drops 2K below the set temperature. (output COOLING=0 V)
20 | WPC | WPC cool www.stiebel-eltron.com
Page 21
OPERATION
Menu structure
- Flow temperature and hysteresis
Cooling mode is regulated via the selected flow temperature.
The brine pump starts at:
[Flow temperature + hysteresis]
Brine pump off when the actual temperature drops below the
flow temperature.
The [flow temperature+hysteresis] should be at least 3 K <
room temperature. Lower flow temperatures cause a more
rapid cooling of the room.
On the setting AREA COOLING, as soon as the determined
dew point temperature is + 2 K higher than the set flow temperature, that temperature will be overridden with the dew
point temperature and acts as control variable. The brine
pump starts at [entered or newly determined flow temperature + hysteresis].
If the actual flow temperature drops below the entered or
newly determined flow temperature, the source pump stops
and cooling mode is terminated. The cooling signal remains
active.
- Dynamic
The Dynamic can be adjusted from 1 to 10. It describes the
delay and changeover between passive cooling and active
cooling, whereby active cooling is started sooner, the smaller
the value.
5.5 FE7 remote control
5.6 FEK remote control
The FEK remote control allows you to:
- Change the set room temperature for heating in heating circuit1 or2 by ±5°C.
- Change the operating mode.
The FEK features the following controls:
- Rotary selector for changing the set room temperature
- "Away" button
- "Info" button
- Button for selecting the following operating modes:
-
Standby mode
-
Automatic mode
-
Constant day mode
-
Constant setback mode
PIC00000704
The FE7 remote control allows you to:
- Change the set room temperature for heating in heating circuit1 or2 by ±5°C.
- Change the operating mode.
The FE7 remote control features the following controls:
- Rotary selector for changing the set room temperature
- Rotary selector with the following positions
-
Automatic mode
-
Constant setback mode
-
Constant day mode
Note
The remote control is only active in the automatic mode
of the heat pump manager.
Note
If the FEK is preselected for a specific heating circuit,
the heating curve, room temperature and heating program parameters are not shown at the WPM3i heat pump
manager.
PIC00000609
5.7 Internet Service Gateway (ISG)
The Internet Service Gateway (ISG) is an Ethernet gateway in a
wall mounted casing and is connected into the LAN (local area
network).
It enables the convenient operation, adjustment and checking of
heat pump system data via the browser of a computer, laptop or
tablet in the local home network.
If required by the customer, appliance data can be automatically
transmitted to the appliance manufacturer's SERVICEWELT portal
via the internet.
Via SERVICES you can access additional options such as system
operation on the go with a smartphone as well as remote setting
of parameters and remote diagnosis, etc.
You can find the current services on our homepage.
PIC00001002
www.stiebel-eltron.com WPC | WPC cool | 21
Page 22
OPERATION
Maintenance and care
6. Maintenance and care
Appliance and system damage
!
Maintenance work, such as checking the electrical safety,
must only be carried out by a qualified contractor.
A damp cloth is sufficient for cleaning all plastic and sheet metal
parts. Never use abrasive or corrosive cleaning agents.
We recommend an annual inspection (to establish the system's
current condition), and maintenance by a qualified contractor if
required (to return the system to the desired condition).
7. Troubleshooting
FaultCause
There is no hot water or
the heating system stays
cold.
The fuse/MCB has blown/
responded.
Remedy
Check the fuses/MCBs in
your fuse box.
7.1 Other problems
If you cannot remedy the fault, notify your qualified contractor.
To facilitate and speed up your enquiry, please provide the serial
number from the type plate. The type plate is located at the front
top, on the right or left hand side of the casing.
Sample type plate
1
Montageanweisung beachten! Dichtheit geprüft!
1 Number on the type plate
*xxxxxxxxxxxxxxxxxx*
Made in Germany
26�03�01�1570
22 | WPC | WPC cool www.stiebel-eltron.com
Page 23
INSTALLATION
Safety
INSTALLATION
- FEK remote control
10. Preparations
8. Safety
Only a qualified contractor should carry out installation, commissioning, maintenance and repair of the appliance.
8.1 General safety instructions
We guarantee trouble-free function and operational reliability only
if original accessories and spare parts intended for the appliance
are used.
8.2 Instructions, standards and regulations
Note
Observe all applicable national and regional regulations
and instructions.
9. Appliance description
9.1 Mode of operation
The heat exchanger on the heat source side (evaporator) extracts
natural heat from the heat source. This extracted energy and the
energy drawn by the compressor drive is transferred to the heating
water by a heat exchanger on the heating water side (condenser).
Subject to the heat load, the heating water is heated up to +60°C.
The DHW is heated via the internal indirect coil inside the DHW
cylinder.
The electric emergency/booster heater starts if the high pressure
sensor or the hot gas limiter responds during DHW heating. In
addition it covers any residual heat demand, if the heating system
demand exceeds the heat pump output.
Note
The appliance is designed for internal installation, except
in wet areas.
Never install the appliance directly below or next to
bedrooms.
Protect pipe transitions through walls and ceilings with an-
ti-vibration insulation.
The room in which the appliance is to be installed must meet the
following conditions:
- No risk from frost.
- The room must not be subject to a risk of explosions arising
from dust, gases or vapours.
- When installing the appliance in a boiler room together with
other heating equipment, ensure that the operation of other
heating equipment will not be impaired.
- The volume of the installation room should be at least
13.8m³.
- Load-bearing floor (for the weight of the unit, see chapter
"Specification / Data table").
For installation on floating screeds, make provisions for a
quiet heat pump operation.
Isolate the installation surface.
1234
9.2 Special features of the WPC...cool
For cooling, the brine is pumped through a 3-way diverter valve
and a second heat exchanger, where the energy is extracted from
the heating water.
WARNING Electrocution
The appliance contains inverters (e.g. variable speed
compressors, high efficiency circulation pumps or high
efficiency fans). In case of a fault inverters can cause DC
residual currents. If RCDs are provided, they have to be
type B AC/DC-sensitive.
A DC residual current can block type A RCDs.
Make sure that the appliance power supply is dis-
connected from the fuse board/distribution panel.
Note
The specified voltage must match the mains voltage. Observe the type plate.
Install cables with the following cross-sections in accordance with
the respective fuse rating:
Fuse/MCB
rating
C 16 ACompressor2.5mm²
B 16 A
B 16 AControl unit1.5 mm²
The electrical data is provided in the chapter "Specification / Data
table".
AssignmentCable cross-section
Electric emergency/
booster heater (BH)
2.5mm²
1.5 mm² with only two live cores and
routing on a wall or in an electrical conduit on a wall.
≥500
≥1000
Maintain the minimum clearances to ensure trouble-free op-
eration of the appliance and facilitate maintenance work.
≥500
10.1 Electrical installation
DANGER Electrocution
Carry out all electrical connection and installation work
in accordance with national and regional regulations.
DANGER Electrocution
Use a permanent connection to the power supply. Ensure
the appliance can be separated from the power supply by
an isolator that disconnects all poles with at least 3mm
contact separation. This requirement can be met with
contactors, circuit breakers, fuses, etc.
Material losses
!
Provide separate fuses/MCBs for the two power circuits
of the compressor and the electricemergency/booster
heater.
D0000034469
11. Installation
11.1 Transport
Transport the appliance in its packaging to protect it against
damage.
Protect the appliance against heavy impact during transport.
- If the appliance needs to be tilted during transport only do so
for a short time to one of its longitudinal sides.
The longer the appliance is tilted, the greater the distribution
of refrigerant oil in the system.
- Storage and transport at temperatures below -20°C and
above +50°C are not permissible.
To facilitate transportation you can also divide the appliance by
removing the refrigeration unit.
11.1.1 Dividing the appliance
Proceed as follows:
Remove the upper packaging.
24 | WPC | WPC cool www.stiebel-eltron.com
Page 25
INSTALLATION
Installation
Remove the lower fascia.
To do this you will need to remove a fixing bracket component, as
shown in the following diagram.
Remove the fixing screw from under the fascia.
3.
2.
1.
>120°
Flip up the upper front panel.
Undo the cable ties and pull the BUS cable connector from
the programming unit.
Place the connector safely in the refrigeration unit.
Remove the upper front panel.
D0000037448
1
1 Fixing bracket component
2 Screw with serrated washer
The serrated washer provides an electrical connection. It must be
remounted when the appliance is installed.
D0000037450
2
D0000037452
2.
1.
2.
1.
2.
1.
Remove the lower front panel.
D0000037451
Remove the side panels.
www.stiebel-eltron.com WPC | WPC cool | 25
D0000037453
Page 26
INSTALLATION
Installation
Remove the DHW temperature sensor from the immersion
pipe of the DHW cylinder.
Mark the immersion pipe.
Place the DHW temperature sensor safely in the refrigerant
circuit.
2
1 Fixing screw
2 Handle
Remove the four fixing screws.
Lift the refrigeration unit off the DHW cylinder. To do this, use
the four handles in the base plate.
Position the DHW cylinder on the prepared base (see chapter
"Installation / Siting").
Reassemble the appliance in reverse order. Be sure to place
D0000037447
the DHW temperature sensor back in the marked sensor well.
11.2 Siting
Remove the packaging film and the top and side EPS
padding.
1
D0000037499
1
2
1 Appliance foot
2 Sliding block
Undo the four fixing screws underneath the non-returnable
pallet.
Remove the appliance feet from the pack. Fully screw the feet
onto the appliance, without removing the appliance from the
pallet.
Take the appliance off the pallet and set it down on the pre-
pared base. If required, use the sliding blocks provided to
4x
help you position the appliance.
For lifting, use the handles provided on the back panel and
the front adjustable rubber feet at the bottom.
Observe minimum distances (see chapter "Preparations /
Minimum clearances").
D0000037500
Level the appliance horizontally by adjusting the feet.
Undo the hydraulic connection lines.
26 | WPC | WPC cool www.stiebel-eltron.com
26�03�01�1764
Page 27
INSTALLATION
Installation
11.3 Opening the appliance
Remove the fixing screw from under the fascia.
Lift the upper front panel.
Secure the upper front panel, as shown in the following di-
agram, using the support attached to the casing. Ensure the
support is placed correctly.
11.4.3 Connection and filling with brine
Thoroughly flush the pipework before connecting the heat
pump to the heat source circuit. Foreign bodies, such as rust,
sand and sealant, can impair the operational reliability of the
heat pump. We recommend installing our Brine charging unit
WPSF in the heat source inlet (see chapter "Accessories").
To facilitate the connection to the heat source system, elbow pushfit connectors are enclosed with the appliance (see chapter "Fitting
the push-fit connectors").
Connect one flexible pressure hose each to act as an anti-vi-
bration mount to the "heat source flow" and "heat source
return" connections. The pressure hoses are included as part
of the standard delivery.
The brine volume of the heat pump under operating conditions can
be found in the data table (see chapter "Specification").
The overall volume is equal to the required amount of brine made
D0000037448
by mixing undiluted ethylene glycol and water. The chloride content of the water must not exceed 300 ppm.
Mixing ratio
The brine concentration varies depending on whether a ground
collector or a geothermal probe is used as the heat source.
For the mixing ratio see the table below.
Ethylene glycolWater
Geothermal probe25 %75 %
Ground collector33 %67 %
2.
4.
1.
3.
11.4 Installing the heat source system
Engineer the heat source system for the ground source heat pump
according to the technical guides.
11.4.1 Permitted brine:
- Heat transfer medium as concentrate on an ethylene glycol
base, part no: 231109 (10 l)
- Heat transfer medium as concentrate on an ethylene glycol
base, part no: 161696 (30l)
11.4.2 Circulation pump and required flow rate
See "COMMISSIONING/ SOURCE/ BRINE PUMP RATING" in the Commissioning chapter.
Filling the brine circuit
D0000037449
1
1 Drain, brine side
Fill the brine circuit via the drain.
After filling the system with brine and prior to commissioning,
open the drain until brine runs out of it. No water must remain in
the pipe run to the drain.
D0000037501
www.stiebel-eltron.com WPC | WPC cool | 27
Page 28
INSTALLATION
Installation
Checking the brine concentration:
Determine the density of the ethylene glycol/water mixture,
e.g. with a hydrometer.
Using the actual density and temperature, you can check the actual
concentration in the diagram.
1,10
1,09
1,08
1,07
1,06
1,05
1,04
1,03
1,02
1,01
50 Vol.-%
40
33
30
25
20
10
11.5 Heating water connection
The heating system to which the heat pump is connected must be
installed by a qualified contractor in accordance with the water
installation diagrams that are part of the technical guides.
Thoroughly flush the pipework before connecting the heat
pump to the heat source circuit. Foreign bodies, such as rust,
sand and sealant, can impair the operational reliability of the
heat pump. We recommend installing our Brine filling unit
WPSF in the heat source inlet (see chapter “Accessories”).
To facilitate the connection to the heating system, elbow push-fit
connectors are enclosed with the appliance (see chapter "Fitting
the push-fit connectors").
Connect one flexible pressure hose each to act as an anti-vi-
bration mount to the "heating flow" and "heating return"
connections. The pressure hoses are included as part of the
standard delivery.
Ensure the correct connection of the heating flow and return.
Check for tightness.
When sizing the heating circuit, observe the maximum avail-
able external pressure differential (see chapter "Specification
/ Data table").
Provide thermal insulation in accordance with applicable
regulations.
A
1,00
0,99
0,98
-20020406080100
X Temperature [°C]
Y Density [g/cm³]
A Frost protection [°C]
Note
The quoted performance data relates to ethylene glycol
(see "Specification").
Fit all brine pipes with diffusion-proof thermal insulation.
0
Safety valve
26�03�01�1914
1
2
D0000037505
1 Drain
2 Discharge outlet
Size the discharge outlet so that water can drain off unim-
peded when the safety valve is fully opened.
Ensure that the safety valve drain is open to the outside.
Install the safety valve drain with a constant fall to the dis-
charge outlet. When installing the drain, never kink the pipe.
11.6 Oxygen diffusion
Material losses
!
Avoid using open vented heating systems or steel pipework in conjunction with underfloor heating systems with
plastic pipes that are permeable to oxygen.
In open vented heating systems or in underfloor heating systems
with permeable plastic pipes, oxygen diffusion can cause corro-
28 | WPC | WPC cool www.stiebel-eltron.com
Page 29
CONTENTS
Installation
sion on steel components such as internal cylinders, steel heating
elements or steel pipes.
The products of corrosion, e.g. rusty sludge, can settle inside the
heat pump condenser and reduce the cross-section, resulting in a
lower output or in the high pressure switch triggering a shutdown.
11.7 Filling the heating system
The system pressure can be read on the programming unit display.
For this, connect the control voltage (see chapter "Power supply
/ Control voltage"). Alternatively you can install a pressure gauge
on site.
1.
2.
D0000037538
Remove the screws on the control panel.
Pivot the control panel to the side.
1
1
1 Drain, heating side
Fill the heating system via the drain.
Water quality
A fill water analysis must be carried out before the system is
filled. This may, for example, be requested from the relevant water
supply utility.
Material losses
!
To avoid damage as a result of scaling, it may be necessary to soften or desalinate the fill water. The fill water
limits specified in chapter "Specification / Data table"
must always be observed.
Recheck these limits 8-12 weeks after commission-
ing and as part of the annual system maintenance.
Note
With a conductivity >1000μS/cm, desalination treatment
is recommended in order to avoid corrosion.
Note
Suitable appliances for water softening and desalinating,
as well as for charging and flushing heating systems, can
be obtained via trade suppliers.
D0000037501
1 Quick-action air vent valve
2 PCB
Open the quick-action air vent valve.
Material losses
!
The air outlet in the knurled cap of the quick-action air
vent valve must not point towards the MFG PCB.
Turn the air outlet in the direction shown in the fol-
lowing diagram.
2
D0000037502
D0000037503
Note
If you treat the fill water with inhibitors or additives, the
same limits as for desalination apply.
11.8 Venting the heating system
Prior to venting the heating system, open the quick-action air vent
valve in the multi function assembly (MFG).
The multi function assembly is located behind the control panel.
www.stiebel-eltron.com WPC | WPC cool | 29
11.9 DHW connection
To connect the DHW, remove the lower front panel (see chapter
"Installation / Maintenance / Removing the lower front panel").
Material losses
!
Close the quick-action air vent valve again after
venting.
Page 30
INSTALLATION
Installation
Material losses
!
Carry out all water connection and installation work in
accordance with regulations.
Material losses
!
The "DHW outlet" connection is pre-fitted with a plastic
union nut and a soft rubber gasket.
The torque of the plastic union nut depends on the gasket
used.
15Nm = pre-fitted soft rubber gasket.
25Nm = alternative hard gasket.
Keep to the permissible torque.
Material losses
!
Operate the appliance only with pressure-tested taps.
11.9.1 Permissible materials
Cold water line
Galvanised steel, stainless steel, copper and plastic are approved
materials.
DHW line
Stainless steel, copper and plastic pipework are approved materials.
Material losses
!
The maximum permissible pressure must not be exceeded (see chapter "Specification/ Data table").
Install a type-tested safety valve in the cold water supply
line. For this bear in mind that, depending on the static pressure, you may also need a pressure reducing valve.
The safety valve discharge aperture must remain open to the
atmosphere.
Install the safety valve discharge pipe with a constant fall to
the discharge outlet.
Size the discharge outlet so that water can drain off unim-
peded when the safety valve is fully opened.
Flush the pipes thoroughly.
Open all downstream draw-off valves until the appliance is
full and the pipework is free of air.
Carry out a tightness check.
11.10 DHW circulation connection
The DHW circulation connector is located at the back of the appliance (see chapter “Specification/ Dimensions and connections”)
1
1 Cap
Detach the panel.
Remove the foam parts.
Unscrew the cap.
Re-insert the foam parts.
Connect the DHW circulation line.
11.11 Operation with buffer cylinder
Install the TF6 return sensor supplied.
Connect the return sensor to the control panel.
At the heat pump manager, set parameter BUFFER MODE to
ON.
11.12 Fitting the push-fit connectors
Material losses
!
Tighten the screw cap of the push-fit connector by hand.
Never use a tool.
D0000039219
The push-fit connectors are equipped with a retainer with stainless steel serrations and an O-ring for sealing. In addition, they
1
1 Drain (DHW cylinder)
Fill the DHW cylinder via the drain.
30 | WPC | WPC cool www.stiebel-eltron.com
are equipped with the "twist and lock" function. Simply turning
the screw cap by hand will secure the pipe in the connector and
push the O-ring against the pipe to seal it.
Material losses
!
Support sleeves are required when using plastic pipes.
Making the connection
The connector must be in its relaxed position before the pipe is
inserted. In this position, there is a small gap between the screw
26�03�01�1758
cap and connector body.
Page 31
INSTALLATION
Power supply
1
1 Gap between screw cap and connector body
Pipe Ø22 mm28 mm
Depth of insertion A35mm44mm
Trim the pipe to the required length using only a pipe cutter.
Push the burr-free pipe past the O-ring into the connector as
far as it will go.
Tighten the screw cap fully to the casing. This presses the
O-ring against the pipe and locks the connector.
Releasing the connection
12.2 Power supply
Note
The heating system needs to be filled before making the
electrical connection (see chapter "Heating water con-
26�03�01�0693
The terminals are located at the appliance control panel behind
the top fascia.
Use appropriate cables in accordance with local regulations for
all connections.
The control panel must be accessible for maintenance and repair
work (see chapter "Venting the heating system").
26�03�01�0693
nection").
Route all cables and sensor leads through the knock-outs
provided in the back panel (see chapter "Specification / Dimensions and connections").
Ensure an adequate length of cables and sensor leads.
Route cables and leads through the strain reliefs.
Check the function of the strain relief fittings.
Undo the screw cap until a small gap appears.
Press the retainer back with your fingers and hold on to it.
The inserted pipe can now be pulled out.
12. Power supply
12.1 General
WARNING Electrocution
Before working on the control panel, isolate the
appliance from the power supply.
Connection work must only be carried out by a qualified contractor
and in accordance with these instructions.
Permission to connect the appliance may need to be obtained from
your local power supply utility.
12.2.1 Compressor and electric emergency/booster heater
Appliance damage
The compressor must only rotate in one direction. If the
fault NO POWER appears in the WPM3i display when the
compressor starts, change the direction of rotation by
interchanging two phases.
Appliance
function
Mono energetic operation
Emergency
mode
Effect of the electric emergency/booster heater
If the heat pump cannot reach the dual mode point, the electric emergency/booster heater ensures both the heating operation and the provision of high DHW temperatures.
Should the heat pump suffer a fault that prevents its continued operation, the heating output will be covered by the electric emergency/booster heater.
Connect cables according to the following diagram.
12.2.2 Control voltage
X4 Control voltage (control outputs)
ON
KS
KUE
MKP
M(A)
M(Z)
HKP
UP
WW
X4 Control voltage (control inputs)
L, L, N, PE Power supply
EVUEnable signal
Compressor signal
Brine pump signal
Cooling
Mixer circuit pump and N (X25), PE
Mixer open
Mixer closed
Heating circuit pump and N, PE
Pump
DHW
D0000037507
X3 Electric emergency/booster heater (DHC)
L1, L2, L3, N, PE
Connected loadTerminal allocation
2.9kWL1PE
5.8kWL1L2PE
8.8kWL1L2L3PE
X3 Compressor (HP)
L1, L2, L3, N, PE
D0000037506
!
Do not connect a high efficiency circulation pump directly to control output UP.
Use an external relay with a breaking capacity of at least
10A/250VAC or our relay set WPM-RBS.
If no voltage is applied to the power supply utility enable signal,
the heat pump will not start. The message “power-OFF” appears
on the controller. In this event, install a jumper across “EVU” and
pha s e “ L”.
Material losses
32 | WPC | WPC cool www.stiebel-eltron.com
Page 33
INSTALLATION
Power supply
12.2.3 Low voltage, BUS cable
X2 Low voltage
B1Temperature sensor, heat pump flow
B2Temperature sensor, heat pump return
T (WW)DHW cylinder sensor and earth (X26)
T(A)Outside temperature sensor and earth (X26)
T(MK)Mixer circuit temperature sensor and earth (X26)
Fernb. 3Connection for FE 7
Fernb. 1Connection for FE 7 and uponor DEM WP module
+CAN bus for remote control
⊥
L
H
GND Ground for temperature sensor
12.3 Sensor installation
Outside temperature sensor AFS 2 (included in the pack
supplied)
The temperature sensors have a significant influence on the function of your heating system. Therefore ensure the sensors are
correctly positioned and well insulated.
Install the outside temperature sensor on a north or north-eastern
wall. Minimum clearances: 2.5 m above the ground, and 1 m to
the side of windows and doors. The outside temperature sensor
should be freely exposed to the elements but not placed in direct
sunlight. Never mount the outside temperature sensor above windows, doors or flues.
D0000037508
Connect the outside temperature sensor to terminal X2(T(A)) and
to the earth block for low voltage X26 of the appliance.
Installation:
Remove the cover.
Secure the base with the screw supplied.
Connect the cable.
Replace the cover. The cover must audibly click into place.
Contact sensor AVF 6
This sensor is required when using a mixer circuit.
Installation information:
26�03�21�0052
Clean the pipe.
Apply heat conducting paste.
Secure the sensor with a cable tie.
When an Uponor DEM-WP module is connected, the heating curve
is dynamically optimised for the heat demand of individual rooms.
This involves modifying the preset heating curve by up to 50%
of its original value.
The Uponor DEM WP module is connected as an alternative to an
FE7 remote control. Operation with both devices is not possible.
Connect the Uponor DEM WP module to terminals Fernb.1 and
to terminal block X2 of the appliance.
Also observe the operating instructions for the Uponor DEM
WP module.
12.8 Internet Service Gateway ISG
The Internet Service Gateway ISG enables you to operate the heat
pump in your local home network and via the internet when on
the go. Connect the Internet-Service-Gateway to terminals H, L,
and to terminal block X2 of the appliance.
The ISG power supply is not made via the heat pump.
Also observe the ISG operating instructions.
1 2 3
3
1
The FE7 remote control enables you to adjust the set room temperature for heating circuit 1 or heating circuit 2 by ± 5 °C in automatic
mode only. You can also change the operating mode. Connect the
remote control to terminals Fernb.1 and Fernb.3 at terminal block
X2 and to the earth block for low voltage X26 of the appliance.
12.6 FEK remote control
Connection array FEK
6
2 3 4
+
L
5
1
H
26�21�01�0008
26�03�01�0094
The FEK remote control enables you to change the set room temperature for heating circuit 1 or heating circuit 2 by ± 5 °C as well
as the operating mode. Connect the remote control to terminals
H, L, and + at terminal block X2 of the appliance.
Also observe the FEK operating instructions.
34 | WPC | WPC cool www.stiebel-eltron.com
Page 35
INSTALLATION
Commissioning
13. Commissioning
Only qualified contractors may carry out adjustments on the heat
pump manager commissioning report, commission the appliance
and instruct the owner in its use.
Commissioning should be carried out in accordance with these
operating and installation instructions. Our customer service can
assist with commissioning, which is a chargeable service.
Where this appliance is intended for commercial use, the rules of
the relevant Health & Safety at Work Act may be applicable for
commissioning. For further details, check your local authorising
body.
13.1 Checks before commissioning
Before commissioning check the points detailed below.
13.1.1 Heating system
- Have you filled the heating system to the correct pressure?
- Have you closed the quick-action air vent valve of the multi
function assembly (MFG) again after venting?
Material losses
!
Observe the maximum system temperature in underfloor
heating systems.
13.1.2 Heat source
Material losses
!
With an underfloor heating system, never use the heat
pump to dry the screed as this places such a high demand
on the heat source that the frost protection function may
kick in. See menu "PROGRAMS / HEAT-UP PROGRAM".
13.1.3 Temperature sensor
- Have you correctly positioned and connected the outside
temperature sensor and the return temperature sensor (in
conjunction with a buffer cylinder)?
13.1.4 High limit safety cut-out
At ambient temperatures below -15 °C the high limit safety cut-out
of the multi function assembly may respond.
Check whether the high limit safety cut-out has tripped.
1
13.1.5 Power supply
- Have you correctly connected the power supply?
- If no fault message is displayed when voltage is applied to
the heat pump power supply (mains), then the rotating field
is correctly connected. If the fault message NO OUTPUT appears, reverse the rotational direction of the compressor.
13.2 Heating curve adjustment during
commissioning
The efficiency of a heat pump decreases as the flow temperature
rises. Therefore adjust the heating curve with care. A heating
curve that is set too high leads to the zone or thermostatic valves
closing and the minimum flow rate required for the heating circuit
may not be achieved.
The following steps will help you to adjust the heating curve correctly:
Fully open thermostatic or zone valves in a lead room (e.g.
living room or bathroom).
We do not recommend installing thermostatic or zone valves
in the lead room. Control the temperature for these rooms
via remote control.
At different outside temperatures (e.g. -10 °C and +10 °C),
adjust the heating curve so the required temperature is
achieved in the lead room.
Standard values to begin with:
ParameterUnderfloor heating
system
Heating curve0.40.8
Control dynamic515
Room temperature20°C20°C
If the room temperature in spring and autumn is too low (outside
temperature approx. 10 °C ), the SET ROOM TEMP parameter must
be raised.
Note
If no remote control is installed, raising the SET ROOM
TEMP parameter leads to a parallel offset of the heating
curve.
If the room temperature is not high enough at low outside temperatures, increase the heating curve parameter.
If the heating curve parameter has been raised, adjust the zone
valve or thermostatic valve in the lead room to the required temperature when outside temperatures are high.
Radiator heating
system
Note
Never reduce the temperature in the entire building by
closing all zone or thermostatic valves, instead use the
setback programs.
2
1 Electric emergency/booster heater
2 High limit safety cut-out reset button
Reset the high limit safety cut-out by pressing the reset
button.
www.stiebel-eltron.com WPC | WPC cool | 35
D0000037504
Page 36
INSTALLATION
Commissioning
13.3 COMMISSIONING menu
Note
All menu points are protected by a code and can only be
viewed and adjusted by a qualified contractor.
If the actual temperature drops below the minimum source temperature, the compressor is switched off and the idle time is set.
The compressor is enabled again after the idle time has expired
and the fixed hysteresis of 2 K has been exceeded.
This fault, i.e. MIN SOURCE T, is indicated in the display by a flashing warning triangle, and entered into the fault list.
The source pump is always started 30 seconds earlier than the
compressor, which starts when there is a heat demand coming
from the central heating or DHW side.
Note
The source pump runs on for 60 seconds after the heat
pump has been shut down.
BRINE PUMP RATING
Here you can set the brine pump flow rate.
The heat source flow rate is set via the temperature differential of
the heat source circuit.
Operate the appliance in heating or DHW mode. To
do so, switch on the appliance using the parameter
BRINEPUMPRATING in the COMMISSIONING / SOURCE
menu.
Start the setting of the source pump after the heat pump has
been running for around 10 minutes.
Select the brine pump rating so that the value is equal to or lower
than the temperature differential on the brine side.
The flow rate on the brine side is not displayed.
Max. temperature differential of the heat source circuit
EMERGENCY OPRON / OFF
HEAT PUMP RESETON / OFF
FAULT LIST RESETON / OFF
SYSTEM RESETON / OFF
13.3.1 ENTER CODE
To change parameters you need to set the correct four-digit code.
The factory-set code is 1000
.
13.3.2 LANGUAGE
Here you can select the menu language.
13.3.3 SOURCE
SOURCE TEMPERATURE MIN
Setting range -10 °C to +10 °C and setting OFF.
Material losses
!
Never operate the appliance with source temperatures
below -9 °C.
6
5
4
3
2
1
-505101520
Y Max. temperature differential [K]
X Source inlet temperature [°C]
1 Heating flow 35 °C
2 Heating flow 50°C
Note
The source outlet temperature is shown on the heat pump
manager display under menu item INFOTEMPERATURES.
1
2
84�03�01�0017
When set to OFF, the temperature at the source sensor is not
scanned.
36 | WPC | WPC cool www.stiebel-eltron.com
Page 37
INSTALLATION
Commissioning
Brine pump run-on time with extractor module
400
350
300
250
200
150
100
50
0
-6 -5 -4 -3 -2 -1 012345678 9 10
4
3
2
1
Y Brine pump run-on time [minutes]
X Brine inlet temperature [°C]
1 EXTRACT MODULE 30
2 EXTRACT MODULE 60
3 EXTRACT MODULE 120
4 EXTRACT MODULE 180
SOURCE MEDIUM
ETHYLENE GLYCO
POTASSIUM CARBONATE
WATER
GROUNDWATER MODULE
EXTRACT MODULE 0, 30, 60, 120 and 180
(Only in conjunction with the extractor module LWM 250)
At a brine inlet temperature <10°C, a regeneration of the heat
source system can be implemented in conjunction with the extractor module and ethylene glycol or propylene glycol as brine.
The settings enable you to determine the run-on time of
the brine pump after the heat pump has been shut down.
The values stated correspond to the run-on time in minutes at an
average brine inlet temperature of 0 °C.
If the brine inlet temperature rises, the run-on time of the source
pump is reduced as a result. If the brine inlet temperature drops,
the run-on time increases. From a brine inlet temperature of 10
°C, the run-on time will always be at least one minute.
Note
The heat pump can only be operated as a ground source
heat pump.
13.3.4 HEATING
CNTRL DYNAMIC
Setting range 0 to 30
The selected control dynamic is a measure of the switching interval between the compressor and the electric emergency/booster
heater. Normally, the preselected dynamic must be sufficiently fast
and without oscillation. Heating systems that respond quickly require a lower value, whilst very slow responding systems require
a higher value to be set.
HP SENSOR MAX
Maximum high pressure
Setting range 38 bar to 40 bar.
84�03�01�0016
This setting limits the high pressure during DHW or central heating. The system implements a controlled shutdown when the
maximum high pressure is reached.
See also DHW learning function.
Heating circuit pump rating
Here you set the “Rated heating flow rate” (see chapter “Specification / Data table”).
13.3.5 DHW
DHW circuit pump rating
Set the maximum flow rate here. If this is noisy, reduce the flow
rate.
13.3.6 COMPRESSOR
IDLE TIME
After a heat pump has been shut down, an idle time is set to protect the compressor. The default idle time of 20 minutes should
normally not be reduced. Where a reduction is required because
of adjustments or repair work, reset the idle time again to 20
minutes after completing the necessary work.
SINGLE PHASE OPERATION
This parameter must always be set to OFF.
QUICK START
During commissioning, you can test the heat pump function by
triggering a heat pump quick start. When navigating to this parameter, OFF is shown on the display. If you set it to ON and press
"OK", a quick start is initiated. The respective pumps are switched
on after the heat pump has started. The value of 60 seconds is
visibly counted down to 0 on the display; then the display shows
ON when the quick start begins.
After that, the heat pump and the associated buffer charging pump
are switched on.
www.stiebel-eltron.com WPC | WPC cool | 37
Page 38
INSTALLATION
Commissioning
13.3.7 EMERGENCY OPR
Characteristics when "Fatal Error" fault occurs in conjunction with
emergency operation:
The EMERGENCY OPR parameter can be set to ON or OFF.
Emergency operation set to ON:
The program selector automatically changes over to emergency
mode as soon as faults occur and the heat pump fails.
Emergency operation set to OFF:
As soon as faults occur and the heat pump fails, the electric emergency/booster heater takes over the frost protection of the central
heating system. Users can then independently select emergency
mode.
13.3.8 HEAT PUMP RESET
If a fault occurs the heat pump can be reset. Setting it to ON resets
the fault that has occurred. The compressor starts again. The fault
remains stored in the fault list.
13.3.9 FAULT LIST RESET
ON / OFF
The entire fault list is deleted.
13.3.10 SYSTEM RESET
A system reset will reset the heat pump manager to its delivered
condition (factory settings).
You will need to select the corresponding heat pump type
again.
Please read carefully
The heat pump can only be operated as a ground source
heat pump.
Heat pump type WPCMFG must be set.
38 | WPC | WPC cool www.stiebel-eltron.com
Page 39
INSTALLATION
Commissioning
13.4 WPM3i commissioning report
The following lists the parameters that can be adjusted via the programming unit.
Programs / heat-up programSett ing rangeStandardSystem value
LOW END TEMPERATURE20..40 °C25.0°C
TEMP. RISE PERIOD0 to 5 days2 days
MAXIMUM TEMPERATURE20...50°C, inc 0.5K40.0°C
MAX TEMPERATURE DURATION0 to 10 days0 days
RISE PER DAY1 to 10 K/day1 K/day
Settings / generalSett ing rangeStandardSystem value
CONTRAST01 to 105
BRIGHTNESS0 to 100 % 50 %
TOUCH SENSITIVITY01 to 1004
TOUCH ACCELERATION02 to 1006
Settings / heating / heating circuit 1Sett ing rangeStandardSystem value
SET ROOM TEMP COMFORT5 to 30 °C 20°C
SET ROOM TEMP ECO5 to 30 °C 20°C
HEATING CURVE RISE0.2 to 3 0.6
Settings / heating / heating circuit 2Sett ing rangeStandardSystem value
SET ROOM TEMP COMFORT5 to 30 °C 20°C
SET ROOM TEMP ECO5 to 30 °C 20°C
HEATING CURVE RISE0.2 to 3 0.2
Settings / heat ing / standard settingSetting rangeStandardSystem value
BUFFER OPERATON / OFF OFF
SUMMER MODE ON / OFF ON
OUTSIDE TEMPERATURE3 to 30 °C 20°C
BUILDING HEAT BUFFER1 to 3 1
MAXIMUM RETURN TEMP20 to 55°C 55°C
MAXIMUM FLOW TEMP20 to 65°C 60 °C
MIXER DYNAMICS30 to 240 100
MAXIMUM MIXER TEMPERATURE20 to 90°C 50 °C
FIXED VALUE OPERATIONOFF / 20 ..50 °C OFF
OPTIMUM HEATING CURVEOFF / 0.01 ..0.1 OFF
FROST PROTECT-10 to 10°C 4°C
Settings / heat ing / FE7 remote controlSett ing rangeStandardSystem value
HEATING CIRC PRESELECTION1 / 2 heating circuits Heating circuit 1
ROOM INFLUENCEOFF / 0 to 20 5
ROOM CORRECTION-5 to 5 K 0
Settings / heat ing / pump cyclesSett ing rangeStandardSystem value
PUMPCYCLESON / OFF OFF
Settings / heating / electric reheatingSett ing rangeStandardSystem value
DUAL MODE TEMP HEATING-40 to 40°C -20°C
LOWER APP LIMIT HEATINGOFF / -39.5 to 40°C -20°C
Settings / DHW / DHW temperaturesSetting rangeStandardSyst em value
SET DHW TEMP COMFORT10 to 60°C 50 °C
SET DHW TEMP ECO10 to 60°C 50 °C
Settings / DHW / standard sett ingSett ing rangeStandardSystem value
DHW HYSTERESIS1 to 10K 5K
DHW LEARNING FUNCTIONON / OFF OFF
DHW CORRECTION0 to 5 °C 3°C
COMBI CYLINDERON / OFF OFF
PASTEURISATIONON / OFF OFF
Settings / DHW / elec tric reheatingSett ing rangeStandardSystem value
DUAL MODE TEMP DHW-40 to 40°C-20°C
LOWER APP LIMIT DHWOFF / -39.5 to 40°C-20°C
www.stiebel-eltron.com WPC | WPC cool | 39
Page 40
INSTALLATION
Commissioning
Settings / cooling / standard settingSetting rangeStandardSystem value
COOLINGON / OFFOFF
COOLING MODEPASSIVE / ACTIVE
Settings / cooling / active cooling / AREA COOLINGSetting rangeStandardSystem value
SET FLOW TEMPERATURE7 to 25°C 15°C
FLOW TEMP HYSTERESIS1 to 5 K 5K
SET ROOM TEMPERATURE20 to 30 °C 25°C
DYNAMIC1 to 1010
Settings / cooling / active cooling / fan coolingSetting rangeStandardSystem value
SET FLOW TEMPERATURE7 to 25°C 15°C
FLOW TEMP HYSTERESIS1 to 5 K 5K
SET ROOM TEMPERATURE20 to 30 °C 25°C
DYNAMIC1 to 1010
Settings / cooling / passive cooling / AREA COOL INGSetting rangeStandardSystem value
SET FLOW TEMPERATURE7 to 25°C 15°C
FLOW TEMP HYSTERESIS1 to 5 K 5K
SET ROOM TEMPERATURE20 to 30 °C 25°C
Settings / cooling / passive cooling / fan coolingSet ting rangeStandardSystem value
SET FLOW TEMPERATURE7 to 25°C 15°C
FLOW TEMP HYSTERESIS1 to 5 K 5K
SET ROOM TEMPERATURE20 to 30 °C 25°C
CommissioningSetting rangeStandardSystem value
ENTER CODE0000 to 99991000
LANGUAGEEnglish
SourceSett ing rangeStandardSystem value
SOURCE TEMPERATURE MINOFF / -10 to 10°C-9°C
BRINE PUMP RATING20 to 100% 100 %
SOURCE MEDIUMEthylene glycol
HeatingSet ting rangeStandardSystem value
HP SENSOR MAX38 to 40 bar40
CNTRL DYNAMIC1 to 3010
HEATING CIRCT PUMP RATING20 to 100% 100 %
DHWSetting rangeStandardSystem value
DHW CIRCUIT PUMP RATING20 to 100% 100 %
CompressorSett ing rangeStandardSystem value
IDLE TIME1 to 120 minutes 20 minutes
SINGLE PHASE OPERATIONON / OFF OFF
QUICK STARTON / OFF OFF
EMERGENCY OPRON / OFFOFF
HEAT PUMP RESETON / OFFOFF
FAULT LIST RESETON / OFFOFF
SYSTEM RESETON / OFFOFF
40 | WPC | WPC cool www.stiebel-eltron.com
Page 41
INSTALLATION
Settings
14. Settings
14.1 Standard settings
At the factory, the heat pump manager is programmed with the
following standard settings:
Switching times for heating circuit1 and2 (day mode)
only the 1stsw itching pair is pre-programmed.
Room temperature 1 / 2
Standard sett ings without night setback.
Room temperature in day mode20°C5 - 30°C
Room temperature in night mode20°C5 - 30°C
DHW program switching times
Monday - Sunday0:00 - 24:000:00 - 23:59
DHW temperature
DHW day temperature50 °COFF / 50 - 70°C
DHW night temperature50 °COFF / 50 - 70°C
Heating curve slope
Heating curve 10.60 - 5
Heating curve 20.20 - 5
14.2 Heating and DHW programs
You may enter your individual programs into the following tables.
14.2.1 Heating program, heating circuit 1
Switching time
pair I
Mon
Tue
Wed
Thu
Fri
Sat
Sun
Mon - Fri
Sat - Sun
Mon-Sun
Switching time
pair II
Switching time
pair III
14.2.2 Heating program, heating circuit 2
Switching time
pair I
Mon
Tue
Wed
Thu
Fri
Sat
Sun
Mon - Fri
Sat - Sun
Mon-Sun
Switching time
pair II
Switching time
pair III
14.2.3 DHW program
Switching time
pair I
Mon
Tue
Wed
Thu
Fri
Sat
Sun
Mon - Fri
Sat - Sun
Mon-Sun
14.3 Appliance handover
Explain the function of the appliance to users and familiarise them
with its operation.
Switching time
pair II
Switching time
pair III
Note
Hand over these operating and installation instructions
to the user for safe-keeping. Always carefully observe all
information in these instructions. They provide information on safety, operation, installation and maintenance
of the appliance.
www.stiebel-eltron.com WPC | WPC cool | 41
Page 42
INSTALLATION
Shutting down
15. Shutting down
If the system is to be taken out of use, set the heat pump manager
to standby. This retains the safety functions designed to protect
the system (e.g. frost protection).
There is no need to shut the system down in summer. The heat
pump manager has an automatic summer / winter changeover.
Material losses
!
Never interrupt the power supply, even outside the heating period. The system's active frost protection is not
guaranteed if the power supply is interrupted.
Material losses
!
Observe the temperature application limits and the minimum circulation volume on the heat consumer side (see
chapter "Specification / Data table").
Material losses
!
If the heat pump and frost protection are completely
switched off, drain the system on the water side.
16. Troubleshooting
WARNING Electrocution
Isolate the appliance from the power supply when
carrying out any work.
16.1 Fault display
Faults/errors in the system or in the heat pump are indicated on
the display. For heating system and heat pump troubleshooting
and analysis, all important process data and bus subscribers can
be called up under DIAGNOSIS and a relay test can be carried out.
For troubleshooting, analyse all available parameters before
opening the heat pump control panel.
The heat pump manager will not indicate whether the electric
emergency/booster heater high limit safety cut-out has responded. The high limit safety cut-out can be reset by your contractor
through pressing the reset button. The high limit safety cut-out
response is generally caused by air in the heating circuit or an
inadequate heating flow rate.
Check the heating flow rate and ventilate the heating system.
16.2 Fault message
If the appliance registers a fault, this is clearly displayed with the
message shown below.
TUESDAY 25.JUN 1316:27 TIME
!
FAULT
SENSOR BREAK E 71
COMFORT MODE
If more than one fault occurs, the most recent fault is always
shown. Notify your qualified contractor.
16.2.1 Heat pump-specific or hardware faults
See chapter "Fault table".
16.2.2 The heat pump is not running
The heat pump is in standby mode [
Change the system over to programmed operation.
The power supply has been blocked, POWER-OFF is displayed.
Wait for the blocking time to elapse. The heat pump will au-
tomatically start up again.
There is no heat demand.
Check the set and actual values under the INFO menu item.
There may be an incorrect fuse rating.
See chapter "Specification / Data table".
Note
The heat pump can only be restarted after the fault has
been removed and the heat pump has been reset (heat
pump reset parameter).
Additional parameters available for system analysis:
- QUICK START: The quick start must only be carried out by our
customer support. The heat pump compressor is checked
during a quick start.
- RELAY TEST: Test for all relays in the heat pump manager.
].
42 | WPC | WPC cool www.stiebel-eltron.com
Page 43
INSTALLATION
Troubleshooting
16.3 Resetting the high limit safety cut-out
If the heating water temperature exceeds 95°C, the electric emergency/booster heater shuts down.
1
2
1 Electric emergency/booster heater
2 High limit safety cut-out reset button
Remove the cause of the fault.
Reset the high limit safety cut-out by pressing the reset but-
ton. To do so, use a pointed object.
Check whether the heating water is being circulated at a suf-
ficiently high flow rate.
16.4 Resetting the compressor high limit safety cutout
If the hot gas temperature exceeds 140°C, the compressor shuts
down.
D0000037504
1 High limit safety cut-out reset button
Isolate the appliance from the power supply.
Remove the cause of the fault.
Reset the high limit safety cut-out by pressing the reset
button.
1
D0000037511
www.stiebel-eltron.com WPC | WPC cool | 43
Page 44
INSTALLATION
Troubleshooting
16.5 Fault table
Fault displayCauseRemedy
SENSOR BREAK E 70The mixer sensor is faulty.Check the sensor terminal on the MFG or replace sensor.
SENSOR BREAK E 71The source sensor is faulty.Check the sensor terminal on the MFG or replace sensor.
SENSOR BREAK E 72The flow sensor is faulty.Check the sensor terminal on the MFG or replace sensor.
SENSOR BREAK E 73The return sensor is faulty.Check the sensor terminal on the MFG or replace sensor.
SENSOR BREAK E 75The external sensor is fault y.Check the sensor terminal on the MFG or replace sensor.
SENSOR BREAK E 76The DHW sensor is faulty.Check the sensor terminal on the MFG or replace sensor.
SENSOR BREAK E 80The remote control is faulty.Check the sensor terminal on the MFG or replace sensor.
SENSOR BREAK E 130The HP sensor is faulty.Check the sensor terminal on the MFG or replace sensor.
SENSOR BREAK E 128The LP sensor is faulty.Check the sensor terminal on the MFG or replace sensor.
ERR T FLO BH MFG The flow sensor of the electric emergency/booster heater in the MFG is
ERR T FLO HP MFGThe heat pump flow sensor on the MFG is faulty.Check the sensor terminal on the MFG or replace sensor.
ERR T RTRN MFG The return sensor on the MFG is faulty.Check the sensor terminal on the MFG or replace sensor.
ERR T DHW MFG The DHW sensor on the MFG is faulty.Check the sensor terminal on the MFG or replace sensor.
HP SENSOR MAX
MAX HOT GAS T
HIGH PRESSURE
LOW PRESSURE
MIN SRCE TEMP
CONTACTOR STUCK
NO OUTPUT
TO T FLO BH MFG The flow sensor of the electric emergency/booster heater in the MFG is
TO T FLO HP MFG The heat pump flow sensor on the MFG is faulty. Check the communication cable terminal or replace the com-
TO T RET MFG The return sensor on the MFG is faulty. Check the communication cable terminal or replace the com-
TO T DHW MFG The DHW sensor on the MFG is faulty. Check the communication cable terminal or replace the com-
TO FL RATE HC MFG Faulty communication with the MFG. Check the communication cable terminal or replace the com-
TO PRES HC MFG Faulty communication with the MFG. Check the communication cable terminal or replace the com-
TO P SOL MFG Faulty communication with the MFG. Check the communication cable terminal or replace the com-
TO PUMP HC MFG Faulty communication between heating circuit pump and MFG. Check the communication cable terminal or replace the com-
TO P BRINE MFG Faulty communication between brine circuit pump and MFG. Check the communication cable terminal or replace the com-
TO VALVE MFG Faulty communication between 3-way diverter valve and MFG. Check the communication cable terminal or replace the com-
TO BH MFG Communication of the electric emergency/booster heater in the MFG is
faulty.
Fatal error in heating mode only; 5 faults within 5 minutes of compressor
runtime.
If the system has been shut down five times within the operating time (5
minutes), the fault will be added to the fault list and the system will be
permanently shut down. Generally, a shutdown via HP SENSOR MAX is a
controlled shutdown that is only displayed for information and for the duration of the idle time, i.e. it is not entered into the fault list. Only frequent
shutdowns over a short period of time point towards a fault and are therefore entered into the fault list.
The compressor will be stopped for the minimum idle time if a hot gas
temperature of 120°C is exceeded. This is a normal controlled shutdown
that is not entered into the fault list. The reason for the shutdown is displayed for information during the idle time.
After the compressor has started and a delay of 15 seconds has elapsed,
the system checks whether relay K9 is open. If this is the case, a HP limit
switch has responded. The fault is added to the fault list and the system is
permanently shut down.
The system will be permanently shut down after the fault has occurred
five times within the operating time (idle time x 50 plus 20 minutes). The
fault is added to the fault list after it has occurred for the first time.
Minimum source temperature
The defined minimum source temperature was not reached.
The fault is added to the fault list. The compressor starts again after the
selected idle time has expired.
Each time the compressor is switched off, the system checks af ter 10
seconds whether the relay K9 is open. If this is the case, then a contactor
is stuck. The fault is added to the fault list and the system is permanently
shut down.
After the compressor has started, the pressure must have risen by 2 bar
within 10 seconds. If this is not the case, a fault has occurred. The fault is
added to the fault list if this is its first occurrence, and the system is permanently shut down.
faulty.
incorrect.
Check the sensor terminal in the MFG or replace sensor.
Only when a fault has been entered into the fault list: Monitor
the flow temperature and check the HP sensor. Check the flow
rate and the temperature on the heating side.
This requires no action, as it is a controlled shutdown.
Monitor the flow temperature and check the HP sensor.
Check the flow rate and the temperature on the heating side.
Check the flow rate and the layout of the source side.
Check the refrigerant level.
Check the minimum source temperature and change it if required. Check the source flow rate: Check source design.
Check contactors K1 and K2 and replace if required.
Compressor is turning in the wrong rotational direction.
Change the rotational direction by interchanging two supply
cores.
Check the communication cable terminal or replace the communication cable.
munication cable.
munication cable.
munication cable.
munication cable.
munication cable.
munication cable.
munication cable.
munication cable.
munication cable.
Check the communication cable terminal or replace the com-
munication cable.
44 | WPC | WPC cool www.stiebel-eltron.com
Page 45
INSTALLATION
Troubleshooting
Fault displayCauseRemedy
TO MFG Timeout MFG Check the communication cable terminal or replace the com-
ERR BH MFG The electric emergency/booster heater in the MFG is faulty. Check the communication cable terminal or replace the com-
ERR PU SOL MFG Error brine pump MFG. Check the communication cable terminal or replace the com-
ERR VALVE MFG Error 3-way diverter valve MFG. Check the communication cable terminal or replace the com-
ERR PU HC MFG Error heating circuit pump MFG. Check the communication cable terminal or replace the com-
munication cable.
munication cable.
munication cable.
munication cable.
munication cable.
www.stiebel-eltron.com WPC | WPC cool | 45
Page 46
INSTALLATION
Maintenance
17. Maintenance
We recommend that you perform an annual inspection (to establish the current condition of the system), and carry out any maintenance as required (to return the system to its original condition).
DANGER Electrocution
Prior to maintenance work, isolate the appliance from
its power supply.
17.1 DHW cylinders
Regularly vent the safety valve until a full stream of water
flows from it. Close the safety valve following inspection.
Opening the appliance
Removing the lower front panel
To do this you will need to remove a fixing bracket component, as
shown in the following diagram.
2
1
D0000037452
1 Fixing bracket component
2 Screw with serrated washer
The serrated washer provides an electrical connection. It must be
remounted when the appliance is installed.
Remove the fixing screw from under the fascia.
Lift the fascia upwards.
Secure the upper front panel, as shown in the following di-
agram, using the support attached to the casing. Ensure the
support is placed correctly.
2.
4.
1.
3.
D0000037448
2.
1.
D0000037453
Remove the lower front panel.
D0000037449
46 | WPC | WPC cool www.stiebel-eltron.com
Page 47
INSTALLATION
Maintenance
Draining the DHW cylinder
WARNING Burns
Hot water may escape when draining the DHW cylinder.
Close the shut-off valve in the cold water line.
Open the hot water taps on all draw-off points.
1
1 Drain
Empty the DHW cylinder via the drain.
Please note that some residual water will remain in the bottom
of the cylinder.
1 Protective anode without consumption indicator
2 Protective anode with consumption indicator
Material losses
!
Install the protective anodes as shown in the diagram.
26�03�01�1758
1
2
26�03�01�1758
Cleaning and descaling
Remove the flange plate.
Clean the DHW cylinder through the inspection port.
Never use descaling pumps. Never use descaling agents to
clean the enamel coating and protective anodes.
Replacing the protective anodes
Two protective anodes are installed in the DHW cylinder to protect
it against corrosion. One of the protective anodes has a consumption indicator. Check the protective anodes at regular intervals.
We recommend checking the protective anodes at the latest two
years after commissioning.
Remove the lower front panel of the appliance.
Material losses
!
Replace the protective anodes when the colour of the
protective anode with the consumption indicator changes
from white to red.
1
2
26�03�01�1345
1 white = protective anode OK
2 red = replace protective anodes
A1 Heat pump manager WPM 3i
A2 Programming unit
A5 MFG PCB
A6 Power supply unit
B1 Temperature sensor, heat pump flow
B2 Temperature sensor, heat pump return
B3 Temperature sensor, heat source return
B4 Temperature sensor, DHW cylinder
B5 Temperature sensor, hot gas
B6 Pressure sensor, heating circuit
B7 Pressure sensor, brine circuit
B8 Heating circuit flow rate and temperature
B9 (Not assigned) brine circuit flow rate and temperature
E1 Instantaneous water heater MFG
F2 High pressure switch
F4 Compressor high limit safety cut-out
F5 MFG high limit safety cut-out
K1 Contactor
K2 Contactor, compressor start
K3 Brine diverter valve relay
K5 MFG relay
K6 MFG relay
K7 MFG relay
K9 Contactor stuck relay
K10 HKP relay
K11 MKP relay
M1 Compressor motor
M2 Heating pump motor
M3 Heating/DHW MFG diverter valve motor
M4 Brine pump motor
M5 Heating/cooling diverter valve motor
P1 High pressure sensor
P3 Low pressure sensor
R1 Start-up resistance
R2 Start-up resistance
R3 Start-up resistance
X1 Internal terminal block 14-pin
X2 Terminals, external low voltage
X3 Terminals, external power
X4 Terminals, external control
X11 Plug, temperature sensor WPM3i
X12 Plug, heat source temperature WPM3i
X13 Plug, mixer circuit temperature WPM3i
X14 Plug, remote control WPM3i
X15 Plug, bus WPM3i
X20 Plug, pumps and power-OFF WPMm3i
X21 Plug, mixer control WPMm3i
X22 Plug, control
X23 Earth block, power supply
X24 Earth block, control unit
X25 N block, control unit
X26 Earth block, LV
X27 Terminals, programming unit
X28 Terminals, internal low voltage
X29 Power supply unit power supply
X30 Power supply unit CAN bus connection
X31 Power supply unit CAN bus connection
X59 Terminal block, MFG load side
X60 Rast 2.5 connector (HP flow temperature)
X61 Rast 2.5 connector (HP return temperature)
X62 Not assigned (HS return temperature)
X63 Temperature, DHW cylinder
X64 Rast 2.5 connector (heating system temperature and flow
rate)
X65 Not assigned (heat source system temperature and flow
rate)
X66 Rast 2.5 connector (heating system pressure)
X67 Rast 2.5 connector (heat source system pressure)
X68 Rast 2.5 connector (control of motorised valve heating /
DHW)
X69 Not assigned
X70 Rast 2.5 connector (control of heating pump PWM or
1-10V)
X71 Rast 2.5 connector (control of heat source pump PWM or
1-10V)
X72 Rast 2.5 connector (CAN bus)
X73 Push-fit connector (in cable trunking)
X74 Push-fit connector (in cable trunking)
A1 Heat pump manager WPM 3i
A2 Programming unit
A5 MFG PCB
A6 Power supply unit
B1 Temperature sensor, heat pump flow
B2 Temperature sensor, heat pump return
B3 Temperature sensor, heat source return
B4 Temperature sensor, DHW cylinder
B5 Temperature sensor, hot gas
B6 Pressure sensor, heating circuit
B7 Pressure sensor, brine circuit
B8 Heating circuit flow rate and temperature
B9 (Not assigned) brine circuit flow rate and temperature
E1 Instantaneous water heater MFG
F2 High pressure switch
F4 Compressor high limit safety cut-out
F5 MFG high limit safety cut-out
K1 Contactor
K2 Contactor, compressor start
K3 Brine diverter valve relay
K5 MFG relay
K6 MFG relay
K7 MFG relay
K9 Contactor stuck relay
K10 HKP relay
K11 MKP relay
M1 Compressor motor
M2 Heating pump motor
M3 Heating/DHW MFG diverter valve motor
M4 Brine pump motor
M5 Heating/cooling diverter valve motor
P1 High pressure sensor
P3 Low pressure sensor
R1 Start-up resistance
R2 Start-up resistance
R3 Start-up resistance
X1 Internal terminal block 14-pin
X2 Terminals, external low voltage
X3 Terminals, external power
X4 Terminals, external control
X11 Plug, temperature sensor WPM3i
X12 Plug, heat source temperature WPM3i
X13 Plug, mixer circuit temperature WPM3i
X14 Plug, remote control WPM3i
X15 Plug, bus WPM3i
X20 Plug, pumps and power-OFF WPMm3i
X21 Plug, mixer control WPMm3i
X22 Plug, control
X23 Earth block, power supply
X24 Earth block, control unit
X25 N block, control unit
X26 Earth block, LV
X27 Terminals, programming unit
X28 Terminals, internal low voltage
X29 Power supply unit power supply
X30 Power supply unit CAN bus connection
X31 Power supply unit CAN bus connection
X59 Terminal block, MFG load side
X60 Rast 2.5 connector (HP flow temperature)
X61 Rast 2.5 connector (HP return temperature)
X62 Not assigned (HS return temperature)
X63 Temperature, DHW cylinder
X64 Rast 2.5 connector (heating system temperature and flow
rate)
X65 Not assigned (heat source system temperature and flow
rate)
X66 Rast 2.5 connector (heating system pressure)
X67 Rast 2.5 connector (heat source system pressure)
X68 Rast 2.5 connector (control of motorised valve heating /
DHW)
X69 Not assigned
X70 Rast 2.5 connector (control of heating pump PWM or
1-10V)
X71 Rast 2.5 connector (control of heat source pump PWM or
1-10V)
X72 Rast 2.5 connector (CAN bus)
www.stiebel-eltron.com WPC | WPC cool | 53
Page 54
INSTALLATION
1
2
3
2
3
4
Specication
18.4 Output diagrams WPC 04 | WPC 04 cool
Key to output diagrams
Y Heating output [kW] / power consumption [kW] / coefficient of performance e [-]
X Inlet temperature of the WQA medium [°C]
1 Flow temperature 35 °C
2 Flow temperature 45°C
3 Flow temperature 55°C
4 Flow temperature 60°C
Heating output
8
7
6
5
4
3
2
1
0
-505101520
Power consumption
2
1
4
D0000033166
1
0
-505101520
54 | WPC | WPC cool www.stiebel-eltron.com
D0000033166
Page 55
INSTALLATION
3
4
Specication
COP
8
7
6
5
4
3
2
1
2
1
0
-505101520
D0000033166
www.stiebel-eltron.com WPC | WPC cool | 55
Page 56
INSTALLATION
3
4
4
Specication
18.5 Output diagrams WPC 05 | WPC 05 cool
Key to output diagrams
Y Heating output [kW] / power consumption [kW] / coefficient of performance e [-]
X Inlet temperature of the WQA medium [°C]
1 Flow temperature 35 °C
2 Flow temperature 45°C
3 Flow temperature 55°C
4 Flow temperature 60°C
Heating output
10
9
8
7
6
5
4
3
2
1
0
-505101520
Power consumption
3
2
1
1
2
D0000033166
1
2
3
0
-505101520
56 | WPC | WPC cool www.stiebel-eltron.com
D0000033166
Page 57
INSTALLATION
3
4
Specication
COP
8
7
6
5
4
3
2
1
2
1
0
-505101520
D0000033166
www.stiebel-eltron.com WPC | WPC cool | 57
Page 58
INSTALLATION
4
2
3
4
Specication
18.6 Output diagrams WPC 07 | WPC 07 cool
Key to output diagrams
Y Heating output [kW] / power consumption [kW] / coefficient of performance e [-]
X Inlet temperature of the WQA medium [°C]
1 Flow temperature 35 °C
2 Flow temperature 45°C
3 Flow temperature 55°C
4 Flow temperature 60°C
Heating output
14
12
10
8
6
4
2
0
-505101520
Power consumption
3
2
1
1
2
3
D0000033166
1
0
-505101520
58 | WPC | WPC cool www.stiebel-eltron.com
D0000033166
Page 59
INSTALLATION
1
Specication
COP
8
7
6
5
4
3
2
1
0
-505101520
2
3
4
D0000033166
www.stiebel-eltron.com WPC | WPC cool | 59
Page 60
Notes
1
4
18.7 Output diagrams WPC 10 | WPC 10 cool
Key to output diagrams
Y Heating output [kW] / power consumption [kW] / coefficient of performance e [-]
X Inlet temperature of the WQA medium [°C]
1 Flow temperature 35 °C
2 Flow temperature 45°C
3 Flow temperature 55°C
4 Flow temperature 60°C
Heating output
18
16
14
12
10
8
6
4
2
0
-505101520
Power consumption
5
4
3
2
2
3
4
D0000033166
1
2
3
1
0
-505101520
60 | WPC | WPC cool www.stiebel-eltron.com
D0000033166
Page 61
Notes
2
3
4
COP
8
7
6
5
4
3
2
1
0
-505101520
1
D0000033166
www.stiebel-eltron.com WPC | WPC cool | 61
Page 62
INSTALLATION
3
4
1
Specication
18.8 Output diagrams WPC 13 | WPC 13 cool
Key to output diagrams
Y Heating output [kW] / power consumption [kW] / coefficient of performance e [-]
X Inlet temperature of the WQA medium [°C]
1 Flow temperature 35 °C
2 Flow temperature 45°C
3 Flow temperature 55°C
4 Flow temperature 60°C
Heating output
25
20
15
10
5
0
-505101520
Power consumption
5
4
3
2
1
1
2
D0000033166
2
3
4
0
-505101520
62 | WPC | WPC cool www.stiebel-eltron.com
D0000033166
Page 63
INSTALLATION
2
3
4
Specication
COP
8
7
6
5
4
3
2
1
1
0
-505101520
D0000033166
www.stiebel-eltron.com WPC | WPC cool | 63
Page 64
INSTALLATION
Specication
18.9 Data table WPC...
Output details apply to new appliances with clean heat exchangers.
The power consumption figures for the integral auxiliary drives are maximum values and may vary subject to operating point.
The power consumption of the integral auxiliary drives is included in the output details of the heat pump (to EN 14511).
WPC 04WPC 05WPC 07WPC 10WPC 13
232926232927232928232929232930
Outputs to EN 14511
Output at B0/W35 (EN 14511)kW4.775.827. 5010.3113.21
Power consumption
Power consumption, emergency/booster heaterkW8.88.88.88.88.8
Max. power consumption, circulation pump, source sideW7676130130130
Max. power consumption, circulation pump, heating sideW4545457272
Power consumptions to EN 14511
Power consumption at B0/W35 (EN 14511)kW1.061.211.552.052.73
Coeff icients of performance to EN 14511
Coeff icient of performance at B0/W35 (EN 14511)4.524.794.855.024.83
Sound data
Sound power level (EN 12102)dB(A)4243444850
Sound pressure level at 1 m distance in a free fielddB(A)3435364042
Sound pressure level at 5 m distance in a free fielddB(A)2021222628
Application limits
Permissible operating pressure, cylinderMPa11111
Min. application limit on the heating side°C1515151515
Max. application limit on the heating side°C6060606060
Heat source application limit (min.)°C-5-5-5-5-5
Heat source application limit (max.)°C2020202020
Water hardness°dH≤3≤3≤3≤3≤3
pH value (with aluminium compounds)mg/l8.0-8.58.0-8.58.0-8.58.0-8.58.0-8.5
pH value (without aluminium compounds)mg/l8.0-10.08.0-10.08.0-10.08.0-10.08.0-10.0
Chloridemg/l<30<30<30<30<30
Conductivity (softening)μS/cm<1000<1000<1000<1000<1000
Conductivity (desalinating)μS/cm20-1002 0-10 02 0-10 02 0-10 020-100
Oxygen 8-12 weeks after filling (desalinating)mg/l<0.1<0.1<0.1<0.1<0.1
Oxygen 8-12 weeks after filling (softening)mg/l<0.02<0.02<0.02<0.02<0.02
Hydraulic data
Cylinder capacityl175175175162162
Available external pressure differential; heat sourcehPa610630755660395
Available external pressure differential, heating systemhPa690525465440180
Electrical details
Rated compressor voltageV400400400400400
FrequencyHz5050505050
Fuse - compressorA3 x C 163 x C 163 x C 163 x C 163 x C 16
Control circuit fuseA1 x B 161 x B 161 x B 161 x B 161 x B 16
Emergency/booster heater fuseA3 x B 163 x B 163 x B 163 x B 163 x B 16
Compressor phases3/N/PE3/N/PE3/N/PE3/N/PE3/N/PE
Control phases1/N/PE1/N/PE1/N/PE1/N/PE1/N/PE
Phases, emergency/booster heater3/N/PE3/N/PE3/N/PE3/N/PE3/N/PE
Rated control voltageV230230230230230
Rated voltage, emergency/booster heaterV400400400400400
Current (with/without softstarter)A2828<30<30<30
Versions
RefrigerantR410 AR410 AR410 AR410 AR410 A
Refrigerant capacitykg1.051.401.902.252.30
Compressor oil Emkarate RL 32
Condenser material1.4401/Cu1.4401/Cu1.4401/Cu1.4401/Cu1.4401/Cu
Evaporator material1.4401/Cu1.4401/Cu1.4401/Cu1.4401/Cu1.4401/Cu
Type circulation pump heating side Yonos PARA
Type circulation pump soruce side Yonos PARA RS
25/7.5 PWM GT
3MAF
25/7.0
Emkarate RL 32
3MAF
Yonos PARA
25/7.0
Yonos PARA RS
25/7.5 PWM GT
Emkarate RL 32
3MAF
Yonos PARA
25/7.0
Stratos PARA
25/1-8
Emkarate RL 32
3MAF
Yonos PARA
25/7.5
Stratos PARA
25/1-8
Emkarate RL 32
3MAF
Yonos PARA
25/7.5
Stratos PARA
25/1-8
64 | WPC | WPC cool www.stiebel-eltron.com
Page 65
INSTALLATION
Specication
WPC 04WPC 05WPC 07WPC 10WPC 13
Dimensions
Heightmm19251925192519251925
Widthmm600600600600600
Depthmm700700700700700
Height of unit when tiltedmm20202020202020202020
Weights
Weight (dry)kg243246259277283
Weight (wet)kg418421434439445
Connections
Heat source flow/return plug-in connection28 mm28 mm28 mm28 mm28 mm
DHW flow/return plug-in connection22 mm22 mm22 mm22 mm22 mm
Heating flow/return plug-in connection22 mm22 mm22 mm22 mm22 mm
DHW circulation connection1/2”1/2”1/2”1/2”1/2”
Values
Flow rate, heat source sidem³/h1.151.411.822.613.22
Rated heating flow ratem³/h0.590.710.921.261.64
Heating flow rate (min.)m³/h0.470.570.751.001.29
Heating flow rate (EN 14511) at A7/W35, B0/W35 and 5 Km³/h0.781.041.281.782.28
Permissible operating pressure - heating circuitMPa0.30.30.30.30.3
Conversion: 1 m3/h = 16.67 l/min
www.stiebel-eltron.com WPC | WPC cool | 65
Page 66
INSTALLATION
Specication
18.10 Data table WPC...cool
Output details apply to new appliances with clean heat exchangers.
The power consumption figures for the integral auxiliary drives are maximum values and may vary subject to operating point.
The power consumption of the integral auxiliary drives is included in the output details of the heat pump (to EN 14511).
232931232932232933232934232935
Outputs to EN 14511
Output at B0/W35 (EN 14511)kW4.775.827. 5010.3113.21
Cooling capacity at B15/W23kW3.003.805.206.008.50
Power consumption
Power consumption, emergency/booster heaterkW8.88.88.88.88.8
Max. power consumption, circulation pump, source sideW7676130130130
Max. power consumption, circulation pump, heating sideW4545457272
Power consumptions to EN 14511
Power consumption at B0/W35 (EN 14511)kW1.061.211.552.052.73
Coeff icients of performance to EN 14511
Coeff icient of performance at B0/W35 (EN 14511)4.524.794.855.024.83
Sound data
Sound power level (EN 12102)dB(A)4243444850
Sound pressure level at 1 m distance in a free fielddB(A)3435364042
Sound pressure level at 5 m distance in a free fielddB(A)2021222628
Application limits
Permissible operating pressure, cylinderMPa11111
Min. application limit on the heating side°C1515151515
Max. application limit on the heating side°C6060606060
Heat source application limit (min.)°C-5-5-5-5-5
Heat source application limit (max.)°C2020202020
Water hardness°dH≤3≤3≤3≤3≤3
pH value (with aluminium compounds)mg/l8.0-8.58.0-8.58.0-8.58.0-8.58.0-8.5
pH value (without aluminium compounds)mg/l8.0-10.08.0-10.08.0-10.08.0-10.08.0-10.0
Chloridemg/l<30<30<30<30<30
Conductivity (softening)μS/cm<1000<1000<1000<1000<1000
Conductivity (desalinating)μS/cm20-1002 0-10 02 0-10 02 0-10 020-100
Oxygen 8-12 weeks after filling (desalinating)mg/l<0.1<0.1<0.1<0.1<0.1
Oxygen 8-12 weeks after filling (softening)mg/l<0.02<0.02<0.02<0.02<0.02
Hydraulic data
Cylinder capacityl175175175162162
Available external pressure differential; heat sourcehPa610630755660395
Available external pressure differential, heating systemhPa690525465440180
Electrical details
Rated compressor voltageV400400400400400
FrequencyHz5050505050
Fuse - compressorA3 x C 163 x C 163 x C 163 x C 163 x C 16
Control circuit fuseA1 x B 161 x B 161 x B 161 x B 161 x B 16
Emergency/booster heater fuseA3 x B 163 x B 163 x B 163 x B 163 x B 16
Compressor phases3/N/PE3/N/PE3/N/PE3/N/PE3/N/PE
Control phases1/N/PE1/N/PE1/N/PE1/N/PE1/N/PE
Phases, emergency/booster heater3/N/PE3/N/PE3/N/PE3/N/PE3/N/PE
Rated control voltageV230230230230230
Rated voltage, emergency/booster heaterV400400400400400
Current (with/without softstarter)A2828<30<30<30
Versions
RefrigerantR410 AR410 AR410 AR410 AR410 A
Refrigerant capacitykg1.051.401.902.252.30
Compressor oil Emkarate RL 32
Condenser material1.4401/Cu1.4401/Cu1.4401/Cu1.4401/Cu1.4401/Cu
Evaporator material1.4401/Cu1.4401/Cu1.4401/Cu1.4401/Cu1.4401/Cu
Type circulation pump heating side Yonos PARA
Dimensions
Heightmm19251925192519251925
Widthmm600600600600600
Depthmm700700700700700
Height of unit when tiltedmm20202020202020202020
Weights
Weight (dry)kg243246259277283
Weight (wet)kg423426439445450
Connections
Heat source flow/return plug-in connection28 mm28 mm28 mm28 mm28 mm
DHW flow/return plug-in connection22 mm22 mm22 mm22 mm22 mm
Heating flow/return plug-in connection22 mm22 mm22 mm22 mm22 mm
DHW circulation connection1/2”1/2”1/2”1/2”1/2”
Values
Flow rate, heat source sidem³/h1.151.411.822.613.22
Rated heating flow ratem³/h0.590.710.921.261.64
Heating flow rate (min.)m³/h0.470.570.751.001.29
Heating flow rate (EN 14511) at A7/W35, B0/W35 and 5 Km³/h0.781.041.281.782.28
Permissible operating pressure - heating circuitMPa0.30.30.30.30.3
Conversion: 1 m3/h = 16.67 l/min
www.stiebel-eltron.com WPC | WPC cool | 67
Page 68
Notes
68 | WPC | WPC cool www.stiebel-eltron.com
Page 69
Notes
www.stiebel-eltron.com WPC | WPC cool | 69
Page 70
Notes
70 | WPC | WPC cool www.stiebel-eltron.com
Page 71
Guarantee | environment and recyclinG
Warranty
The warranty conditions of our German companies do not
apply to appliances acquired outside of Germany. In countries
where our subsidiaries sell our products, it is increasingly the
case that warranties can only be issued by those subsidiaries.
Such warranties are only granted if the subsidiary has issued
its own terms of warranty. No other warranty will be granted.
We shall not provide any warranty for appliances acquired in
countries where we have no subsidiary to sell our products.
This will not aect warranties issued by any importers.
Environment and recycling
We would ask you to help protect the environment. After use,
dispose of the various materials in accordance with national
regulations.
KYOTO | R410A
This device is filled with refrigerant R410A.
Refrigerant R410A is a CFC greenhouse gas mentioned in the Kyoto
protocol with a global greenhouse potential (GWP) = 1925.
STIEBEL ELTRON, Inc.
17 West Street | 01088 West Hatfield MA
Tel. 0413 247-3380 | Fax 0413 247-3369
info@stiebel-eltron-usa.com
www.stiebel-eltron-usa.com
4<AMHCMO=aeidhe>
Irrtum und technische Änderungen vorbehalten! | Subject to errors and technical changes! | Sous réserve
d‘erreurs et de modifications techniques! | Onder voorbehoud van ver
Salvo error o modificación técnica! | Excepto erro ou alteração técnica | Zastrzeżone zmian
ewentualne błędy | Omyly a technické změny jsou vyhrazeny! | A muszaki változtatások és tévedések jogát
fenntartjuk! |
technické zmeny sú vyhradené! Stand 8870
Отсутствие ошибок не гарантируется. Возможны технические изменения.
issingen en technische wijzigingen! |
techniczne i
| Chyby a
A 304837-37632-8863
B 304835-37632-8863
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.