Please read the following information carefully before
installing and operating the controller. In this way damage
to the solar system caused by wrong installation will be
avoided. Please make sure that the mounting is adapted to
the characteristics of the building, that the local regulations
are respected and is conform with the technical rules.
Please pay attention to the following safety advice in order
to avoid danger and damage to people and property.
6 Functions and options ..................................... 75
6.1 Status level .............................................................. 75
3 x screw and wall plug
8 x strain relief and screw
Additionally included in the full kit:
2 x FKP6 sensor
2 x FRP6 sensor
Note:
For more information about accessories, see
p. 101.
Note:
The SD card is not included with the controller
Technical data
Housing:
plastic, PC-ABS and PMMA
Protection type: IP 20 / EN 60 529
Protection class: I
Ambient temp.: 32 ... 104 °F
Dimensions: 204 x 170 x 47 mm
Mounting: wall mounting, also suitable for mounting into
patch panels
Display: System-Monitoring-Display for system visuali-
zation, 16-segment display, 7-segment display, 8 symbols,
control lamp (directional pad) and background illumination
Operation: 7 push buttons at the front of the housing
Functions: System controller for solar and heating sys-
tems. Functions such as: DT control, pump speed control,
Inputs:
5 inputs for Pt1000 temperature sensors, inputs for 1
Grundfos Direct Sensor™ VFS and 1 Grundfos Direct
Sensor™ RPS, 1 Impulse input V40
The controller is supplied with power via a power supply
cable. The power supply of the device must be 100 ... 240V~
(50 ... 60 Hz).
The controller is equipped with 4 relays in total to which
loads such as a pump, a valve, etc. can be connected:
• Relays R1 ... R3 are semiconductor relays, designed for
pump speed control
Conductor R1... R3
Note:
Connecting the device to the power supply must
always be the last step of the installation!
Neutral conductor N
Ground terminal
• Relay 4 is a standard relay
Conductor R4
Neutral conductor N
Ground terminal
Depending on the product version, power supply cable and
sensor cables are already connected to the device. If that is
not the case, please proceed as follows:
Connect the temperature sensors (S1 to S5) to the
corresponding terminals with either polarity:
S1 = sensor 1 (collector sensor )
S2 = sensor 2 (e. g. tank sensor bottom)
S3 = sensor 3 (e. g. tank sensor top)
S4 = sensor 4 (e. g. tank sensor tank 2)
Note:
The connection depends on the system selected,
see chap. 2.6. “System layouts”
S5 = sensor 5 (e. g. collector sensor collector 2)
Connect the Grundfos sensors to the VFS and RPS inputs.
A V40owmeter can be connected to the terminals V40
and GND (either polarity).
The terminals marked “PWM” are control outputs for a
WARNING!Electric shock!
L' is a fused contact permanently
carrying voltage
Î Always disconnect the control-
ler from power supply before
opening the housing!
high-efciency pump (PWM1 is allocated to R1 and PWM2
is allocated to R2).
The power supply connection is at the terminals:
Neutral conductor N
Conductor L
Conductor L' (L' is not connected with the power supply
cable. L' is a fused contact permanently carrying voltage)
Note:
Ground terminal
For more details about the initial commissioning
procedure, see chap. 5, page 73.
The controller is equipped with the VBus® for data transfer
with and energy supply to external modules. The connection is carried out at the two terminals marked “VBus” and
GND (any polarity). One or more VBus® modules can be
connected via this data bus, such as:
• GA3 Large display module / Smart Display SD3
• AM1 Alarm module
• DL2 Datalogger
Furthermore, the controller can be connected to a PC
via the VBus
included with the SOM 9s). With the ServiceCenter Software (RSC), measured values can be read, processed and
visualized. The software allows easier function control and
adjustment of the system.
®
/USB or VBus®/LAN interface adapter (not
Note:
For more information about accessories, see
p. 101.
2.4 SD card slot
The controller is equipped with an SD card slot for storing
system data onto an SD card. The values can be opened and
visualized, e. g. in a spreadsheet programme.
Note:
Do not use an SD-HC card!
A standard SD card is not included with the SOM 9s.
For more information about using an SD card, see chap. 6.2
The controller calculates the temperature difference between collector sensor S1 and tank sensor S2. If the difference is larger than or identical to the adjusted switch-on
S1
temperature difference, the pump (R1) will be switched on
and the tank will be loaded until the switch-off temperature
difference or the maximum tank temperature is reached.
DT O12 °RSwitch-on temperature difference78
DT F8 °RSwitch-off temperature difference78
DT S20 °RSet temperature difference78
RIS4 °RRise78
S MAX140 °FTank maximum limitation78
SMAXS2Sensor tank max79
COL >Collector
CEM270 °FCollector emergency temperature 80
OCCO**OFFOption collector cooling80
System 2
Solar system with 2 tanks and heat exchange
The controller calculates the temperature difference between collector sensor S1 and tank sensor S2. If the difference is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on
and the tank will be loaded until the switch-off temperature
difference or the maximum tank temperature is reached.
Heat exchange between S3 and S4 is possible.
Sensor/Terminal
S1TCOLTemperature collector
S2TST1BTemperature tank 1 bottom
S3TST1TTemperature tank 1 top
S4TST2BTemperature tank 2 top
S5Optional sensor for measurement
VFS
RPS
DT O12 °RSwitch-on temperature difference78
DT F8 °RSwitch-off temperature difference78
DT S20 °RSet temperature difference78
RIS4 °RRise78
S MAX140 °FTank maximum limitation79
SMAXS2Sensor tank max79
COL >Collector
CEM270 °FCollector emergency temperature 80
OCCO**OFFOption collector cooling80
System 3
Solar system with 1 tank and backup heating
The controller calculates the temperature difference between collector sensor S1 and tank sensor S2. If the difference is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on
and the tank will be loaded until the switch-off temperature
difference or the maximum tank temperature is reached.
Domestic hot water backup heating (R4) can be carried out
with a thermostat function (S3). If the value at S3 reaches
the switch-on temperature for the backup heating, the relay
is energized. If the value exceeds the switch-off temperature
for the backup heating, the relay is switched off again.
R1
VFS
RPS
Te mp. Sensor
Pt1000
S1
S2
S3
S1
S4
S5
GND
outin
PWM 1
PWM 2
L
V40
VBus
S3
R4
R4
L'
R1
R3
R2
N
S2
Sensor/Terminal
S1TCOLTemperature collector
S2TSTBTemperature tank bottom
S3TSTTTemperature tank top
S4Optional sensor for measurement
S5
VFS
RPS
V40
AH O110 °FBackup heating switch-on temperature87
AH F120 °FBackup heating switch-off temperature87
t1O06:00Switch-on time 188
t1F22:00Switch-off time 188
t2O00:00Switch-on time 288
t2F00:00Switch-off time 288
t3O00:00Switch-on time 388
t3F00:00Switch-off time 388
System 4
Solar system with 1 tank and 3-port valve for vertical tank loading
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S3. If the measured
temperature differences are higher than the adjusted switchon temperature differences, the pump (R1) will be activated
and the corresponding tank zone will be loaded up to the
adjusted maximum temperature via the valve (R3). The priority logic effects prior loading of the upper zone of the tank.
Note: 3-port valve normally open - tank bottom
RelayDescription
R1Solar pump
R2/R4optional:
Thermal disinfection
Parallel relay
Heat dump
R33-port valve tank top/bottom
Change toDescriptionPage
Sensor/Terminal
S1TCOLTemperature collector
S2TSTBTemperature tank bottom
S3TSTTTemperature tank top
S4Optional sensor for measurement
S5
DT1O12 °RSwitch-on temperature difference 178
DT1F8 °RSwitch-off temperature difference 178
DT1S20 °RSet temperature difference 178
RIS14 °RRise 178
S1MAX140 °FTank maximum limitation 178
SMXS12Sensor tank max 179
LOAD2 >Loading 2
DT2O12 °RSwitch-on temperature difference 278
DT2F8 °RSwitch-off temperature difference 278
DT2S20 °RSet temperature difference 278
RIS24 °RRise 278
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S4. If the measured temperature differences are higher than the adjusted switch-on
temperature differences, the pump (R1) will be activated and
the corresponding tank will be loaded up to the adjusted
maximum temperature via the valve (R3). Tank 1 is loaded
with priority.
Note: 3-port valve normally open - tank 1 (S2)
Sensor/Terminal
S1TCOLTemperature collector
S2TST1BTemperature tank 1 bottom
S3Optional sensor for measurement
S4TST2BTemperature tank 2 bottom
S5Optional sensor for measurement
VFS
RPS
V40
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S4. If the measured
temperature differences are higher than the adjusted switchon temperature differences, the pump (R1 and R2) will be
activated and the corresponding tank will be loaded up to
the adjusted maximum temperature at most.
Sensor/Terminal
S1TCOLTemperature collector
S2TST1BTemperature tank 1 bottom
S3Optional sensor for measurement
S4TST2BTemperature tank 2 bottom
S5Optional sensor for measurement
VFS
DesignationDescription
purposes or options
purposes or options
RelayDescription
R1Solar pump tank 1
R2Solar pump tank 2
DT1O12 °RSwitch-on temperature difference 178
DT1F8 °RSwitch-off temperature difference 178
DT1S20 °RSet temperature difference 178
RIS14 °RRise 178
S1MAX140 °FTank maximum limitation 178
SMXS12Sensor tank max 179
LOAD2 >Loading 2
DT2O12 °RSwitch-on temperature difference 278
DT2F8 °RSwitch-off temperature difference 278
DT2S20 °RSet temperature difference 278
CFR O40 °FAntifreeze temperature collector on82
CFR F42 °FAntifreeze temperature collector off82
FRPST 1Antifreeze tank selection82
LLOGI >Loading logic
PRIOPriority logic82
PRIO1Priority logic82
OSTSOFFTank set option83
TST1120 °FSet tank temperature tank 183
TST2120 °FSet tank temperature tank 283
OSEOFFSpread function option83
The controller compares the temperatures at the collector
sensors S1 and S5 to the tank temperature at sensor S2.
If one of the measured temperature differences is higher
than the adjusted switch-on temperature differences, the
corresponding pump (R1, R2) will be activated and the tank
will be loaded.
S1
S5
R2R1
Sensor/Terminal
S1TCOL1Temperature collector 1
S2TSTBTemperature tank bottom
S3Optional sensor for measurement
S4
S5TCOL2Temperature collector 2
VFSOptional sensor for measurement
RPS
V40
DT O12 °RSwitch-on temperature difference 78
DT F8 °RSwitch-off temperature difference 78
DT1S20 °RSet temperature difference78
RIS4 °RRise 78
S MAX140 °FTank maximum limitation 78
SMAXS2Sensor tank max 79
COL 1 >Collector 1
CEM1270 °FCollector emergency temperature 1 80
OCCO1**OFFOption collector cooling 180
System 8
Solar system with 1 tank and backup heating with solid fuel boiler
The controller calculates the temperature difference between collector sensor S1 and tank sensor S2. If the difference is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on
and the tank will be loaded until the switch-off temperature
difference or the maximum tank temperature is reached.
With another temperature differential function (S4/S3),
backup heating of the tank can be carried out with a solid
fuel boiler (R3).
R1
VFS
RPS
Te mp. Sensor
Pt1000
S1
S2
S3
S1
S4
S5
GND
outin
PWM 1
PWM 2
L
V40
VBus
R4
L'
R1
R3
R2
N
S4
S3
R3
S2
Sensor/Ter-
DesignationDescription
minal
S1TCOLTemperature collector
S2TSTBTemperature tank bottom
S3TSTTTemperature tank top
S4TSFBTemperature solid fuel boiler
S5Optional sensor for measurement
VFS
DT O12 °RSwitch-on temperature difference 78
DT F8 °RSwitch-off temperature difference 78
DT S20 °RSet temperature difference78
RIS 4 °RRise 78
S MAX140 °FTank maximum limitation 78
SMAXS2Sensor tank max 79
COL >Collector
CEM270 °FCollector emergency temperature 80
OCCO**OFFOption collector cooling80
System 9
Solar system with 1 tank and heating circuit return preheating
The controller calculates the temperature difference between collector sensor S1 and tank sensor S2. If the difference is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on
and the tank will be loaded until the switch-off temperature
difference or the maximum tank temperature is reached.
With another temperature differential function (S3/S4)
heating circuit return preheating (heating circuit backup) is
possible via a valve (R2).
R1
VFS
RPS
Te mp. Sensor
Pt1000
S1
S2
S3
S1
S4
S5
GND
outin
PWM 1
PWM 2
L
V40
VBus
R4
L'
R3
R2
R1
N
S3
S4
S2
R2
Sensor/Terminal
S1TCOLTemperature collector
S2TSTBTemperature tank bottom
S3TSTRTemp. tank return preheating
S4TRETTemperature - return
S5Optional sensor for measurement
VFS
DT O12 °RSwitch-on temperature difference 78
DT F8 °RSwitch-off temperature difference 78
DT S20 °RSet temperature difference78
RIS4 °RRise 78
S MAX140 °FTank maximum limitation 78
SMAXS2Sensor tank max 79
COL >Collector
CEM270 °FCollector emergency temperature 80
OCCO**OFFOption collector cooling80
The controller calculates the temperature difference between collector sensor S1 and tank sensor S2. If the difference is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on
and the tank will be loaded until the switch-off temperature
difference or the maximum tank temperature is reached.
With another temperature differential function (S3/S4)
heating circuit backup (heating circuit return preheating) is
possible via a valve (R2). With a thermostat function (S3)
domestic hot water backup heating (R4) can be carried out.
Sensor/Terminal
S1TCOLTemperature collector
S2TSTBTemperature tank bottom
S3TSTT/TSTR Temperature tank top/
S4TRETTemperature - return
S5Optional sensor for measurement
VFS
AH O110 °FBackup heating switch-on temperature87
AH F120 °FBackup heating switch-off temperature87
t1O06:00Switch-on time 188
t1F22:00Switch-off time 188
t2O00:00Switch-on time 288
t2F00:00Switch-off time 288
t3O00:00Switch-on time 388
t3F00:00Switch-off time 388
System 11
Solar system with vertical tank loading and heat exchange control
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S3. If the measured
temperature differences are higher than the adjusted switchon temperature differences, the pump (R1) will be activated
and the corresponding tank zone will be loaded up to the
adjusted maximum temperature via the valve (R3).
The priority logic effects prior loading of the upper zone
of the tank.
Heat exchange control to an existent tank via an additional
pump (R2) can be carried out with another temperature
differential function (S3 heat source/S4 heat sink).
Te mp.Sensor
S1
Pt1000
S2
VFS
RPS
S1
R3
R1
Note: 3-port valve normally open - tank bottom
outin
L
S3
S4
S5
PWM 1
PWM 2
V40
GND
VBus
R4
L'
R1
R3
R2
N
S3
R2
S4
S2
Sensor/Terminal
S1TCOLTemperature collector
S2TST1BTemperature tank 1 bottom
S3TSTTTemperature tank 1 top
S4TST2BTemperature tank 2 bottom
S5Optional sensor for measurement
VFS
DT1O12 °RSwitch-on temperature difference 178
DT1F8 °RSwitch-off temperature difference 178
DT1S20 °RSet temperature difference 178
RIS14 °RRise 178
S1MAX140 °FTank maximum limitation 178
SMXS12Sensor tank max 179
LOAD2 >Loading 2
DT2O12 °RSwitch-on temperature difference 278
DT2F8 °RSwitch-off temperature difference 278
DT2S20 °RSet temperature difference 278
RIS24 °RRise 278
System 12
Solar system with vertical tank loading and thermostatic backup heating
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S3. If the measured
temperature differences are higher than the adjusted switchon temperature differences, the pump (R1) will be activated
and the corresponding tank zone will be loaded up to the
adjusted maximum temperature via the valve (R3). The priority logic effects prior loading of the upper zone of the tank.
Domestic hot water backup heating (R4) can be carried out
with a thermostat function (S3).
Note: 3-port valve normally open - tank bottom
Sensor/Terminal
S1TCOLTemperature collector
S2TSTBTemperature tank bottom
S3TSTTTemperature tank top
S4Optional sensor for measurement
S5
VFS
RPS
V40
DT1O12 °RSwitch-on temperature difference 178
DT1F8 °RSwitch-off temperature difference 178
DT1S20 °RSet temperature difference 178
RIS14 °RRise 178
S1MAX60Tank maximum limitation 178
SMXS12Sensor tank max 179
DT2O12 °RSwitch-on temperature difference 278
DT2F8 °RSwitch-off temperature difference 278
DT2S20 °RSet temperature difference 278
RIS24 °RRise 278
AH O110 °FBackup heating switch-on temperature87
AH F120 °FBackup heating switch-off temperature87
t1O06:00Switch-on time 188
t1F22:00Switch-off time 188
t2O00:00Switch-on time 288
t2F00:00Switch-off time 288
t3O00:00Switch-on time 388
t3F00:00Switch-off time 388
System 13
Solar system with vertical tank loading and backup heating with solid fuel boiler
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S3. If the measured temperature differences are higher than the adjusted switch-on
temperature differences, the pump (R1) will be activated and
the corresponding tank zone will be loaded up to the adju-
sted maximum temperature via the valve (R4). The priority
logic effects prior loading of the upper zone of the tank.
With another temperature differential function (S4/S3),
backup heating of the tank can be carried out with a solid
fuel boiler (R3).
Note: 3-port valve normally open - tank bottom
Sensor/Terminal
S1TCOLTemperature collector
S2TSTBTemperature tank bottom
S3TSTTTemperature tank top
S4TSFBTemperature solid fuel boiler
S5Optional sensor for measurement
VFS
RPS
V40
DT1O12 °RSwitch-on temperature difference 178
DT1F8 °RSwitch-off temperature difference 178
DT1S20 °R Set temperature difference 178
RIS14 °RRise 178
S1MAX140 °FTank maximum limitation 178
SMXS12Sensor tank max 179
DT2O12 °RSwitch-on temperature difference 278
DT2F8 °RSwitch-off temperature difference 278
DT2S20 °RSet temperature difference 278
RIS24 °RRise 278
S2MAX140 °FTank maximum limitation 278
BLPR >OFFBlocking protection88
OTDIS >OFFThermal disinfection option89
OPARR >OFFParallel relay option90
OHQM >OFFEnergy metering option90
GFDS >OFFRegistration Grundfos sensors 90
PRS* >OFFPressure monitoring option92
DATE>Enter date92
LANG >EnLanguage93
UNIT >°FUnit92
OSDC >SD card option93
CODE0000User code96
RESETOFFFactory setting
* This channel is only available if the Grundfos sensors have been registered in the GFDS channel.
System 14
Solar system with vertical tank loading and return preheating
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S3. If the measured
temperature differences are higher than the adjusted switchon temperature differences, the pump (R1) will be activated
and the corresponding tank zone will be loaded up to the
adjusted maximum temperature via the valve (R3). The priority logic effects prior loading of the upper zone of the tank.
With another temperature differential function (S3-heat
source/S4-heat sink) heating circuit return preheating (heating circuit backup) is possible via another valve (R2).
Note: 3-port valve normally open - tank bottom
Sensor/Terminal
S1TCOLTemperature collector
S2TSTBTemperature tank bottom
S3TSTT/TSTR Temperature tank top/
S4TRETTemperature return
S5Optional sensor for measurement
VFS
RPS
V40
Adjustment channels
ChannelSub channel 1 Sub channel 2 Factory
RelayDescription
R1Solar pump
R2Return preheating
R33-port valve tank top/bottom
R4optional:
Thermal disinfection
Parallel relay
Heat dump
Temp. tank return preheating
purposes or options
Change to DescriptionPage
setting
DT1O12 °RSwitch-on temperature difference 178
DT1F8 °RSwitch-off temperature difference 178
DT1S20 °RSet temperature difference 178
RIS14 °RRise 178
S1MAX140 °FTank maximum limitation 178
SMXS12Sensor tank max 179
DT2O12 °RSwitch-on temperature difference 278
DT2F8 °RSwitch-off temperature difference 278
DT2S20 °RSet temperature difference 278
RIS24 °RRise 278
35 |
Page 36
SOM 9s
Adjustment channels
ChannelSub channel 1 Sub channel 2 Factory
S2MAX140 °FTank maximum limitation 278
LST2ONLoading tank 279
COL >Collector
CEM270 °FCollector emergency temperature 80
OCCO**OFFOption collector cooling80
CMAX230 °FMaximum collector temperature80
OCMIOFFOption collector minimum limitation 80
CMIN50 °FMinimum collector temperature80
OTCOOFFOption evacuated evacuated tube collector function 81
System 15
Solar system with vertical tank loading and backup heating via heating backup
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S3. If the measured
temperature differences are higher than the adjusted switchon temperature differences, the pump (R1) will be activated
and the corresponding tank zone will be loaded up to the
adjusted maximum temperature at most via the valve (R3).
The priority logic effects prior loading of the upper zone
of the tank.
With another temperature differential function (S3-heat
source/S4-heat sink) heating circuit return preheating (heating circuit backup) is possible via another valve (R2). Domestic hot water backup heating (R4) can be carried out
with a thermostat function (S3).
R1
VFS
RPS
Te mp. Sensor
Pt1000
S1
S2
S3
S1
R3
S4
S5
GND
outin
PWM 1
PWM 2
L
V40
VBus
S3
R4
R4
L'
R3
R2
R1
N
S4
S2
R2
Note: 3-port valve normally open - tank bottom
Sensor/Ter-
DesignationDescription
minal
S1TCOLTemperature collector
S2TSTBTemperature tank bottom
S3TSTT/TSTR Temperature tank top/
Temp. tank return preheating
S4TRETTemperature return
S5Optional sensor for measurement
VFS
DT1O12 °RSwitch-on temperature difference 178
DT1F8 °RSwitch-off temperature difference 178
DT1S20 °RSet temperature difference 178
RIS14 °RRise 178
S1MAX140 °FTank maximum limitation 178
SMXS12Sensor tank max 179
AH O110 °FBackup heating switch-on temperature87
AH F120 °FBackup heating switch-off temperature87
t1O06:00Switch-on time 188
t1F22:00Switch-off time 188
t2O00:00Switch-on time 288
t2F00:00Switch-off time 288
t3O00:00Switch-on time 388
t3F00:00Switch-off time 388
System 16
2-tank solar system with valve logic and heat exchange control
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S4. If the measured
temperature differences are higher than the adjusted switchon temperature differences, the pump (R1) will be activated
and the corresponding tank zone will be loaded up to the
adjusted maximum temperature via the valve (R3). Tank 1
is loaded with priority. Heat exchange from tank 1 to tank
2 (R2) is possible with another temperature differential
function (S3-heat source/S4-heat sink).
Note: 3-port valve normally open
- tank 1 (S2)
Sensor/Terminal
S1TCOLTemperature collector
S2TST1BTemperature tank 1 bottom
S3TSTTTemperature tank 1 top
S4TST2BTemperature tank 2 bottom
S5Optional sensor for measurement
VFS
RPS
V40
DT1O12 °RSwitch-on temperature difference 178
DT1F8 °RSwitch-off temperature difference 178
DT1S20 °RSet temperature difference 178
RIS14 °RRise 178
S1MAX140 °FTank maximum limitation 178
SMXS12Sensor tank max 179
DT2O12 °RSwitch-on temperature difference 278
DT2F8 °RSwitch-off temperature difference 278
DT2S20 °RSet temperature difference 278
RIS24 °Rrise 278
S2MAX140 °FTank maximum limitation 278
SMXS24Sensor tank max 279
LST2ONLoading tank 279
System 17
2-tank solar system with pump logic and heat exchange control
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S4. If the measured
temperature differences are higher than the adjusted switchon temperature differences, the pump (R1 and R2) will be
activated and the corresponding tank will be loaded up to
the adjusted maximum temperature. Tank 1 is loaded with
priority.
Heat exchange from tank 1 to tank 2 (R3) is possible with
another temperature differential function (S3-heat source/
S4-heat sink).
VFS
RPS
Te mp. Sensor
S1
S1
R2R1
Pt1000
S2
S3
S4
S5
GND
outin
PWM 1
PWM 2
L
VBus
V40
S3
R3
R4
L'
R3
R2
R1
N
S4
S2
Sensor/Terminal
S1TCOLTemperature collector
S2TST1BTemperature tank 1 bottom
S3TSTTTemperature tank 1 top
S4TST2BTemperature tank 2 bottom
S5Optional sensor for measurement
VFS
DesignationDescription
purposes or options
RelayDescription
R1Solar pump tank 1
R2Solar pump tank 2
R3Heat exchange pump
R4optional:
DT1O12 °RSwitch-on temperature difference 178
DT1F8 °RSwitch-off temperature difference 178
DT1S20 °RSet temperature difference 178
RIS14 °RRise 178
S1MAX140 °FTank maximum limitation 178
SMXS12Sensor tank max 179
LOAD2 >Loading 2
DT2O12 °RSwitch-on temperature difference 278
DT2F8 °RSwitch-off temperature difference 278
DT2S20 °RSet temperature difference 278
CFR O40 °FAntifreeze temperature collector on82
CFR F42 °FAntifreeze temperature collector off82
FRPST1Antifreeze tank selection82
LLOGI >Loading logic
PRIOPriority logic82
PRIO1Priority logic82
OSTSOFFTank set option83
TST1120 °FSet tank temperature tank 183
TST2120 °FSet tank temperature tank 283
OSEOFFSpread function option83
System 18
Solar system with east-/west collectors and heat exchange control
The controller compares the temperatures at the collector sensors S1 and S5 to the tank temperature at
sensor S2. If one of the measured temperature differences is higher than the adjusted switch-on temperature differences, the corresponding pump (R1, R2) or
both pumps will be activated and the tank will be loaded.
Heat transfer control to an existent tank (R3) can be carried
out with another temperature differential function (S3-heat
source/S4-heat sink).
Sensor/Terminal
S1TCOL1Temperature collector 1
S2TST1BTemperature tank 1 bottom
S3TSTTTemperature tank 1 top
S4TST2BTemperature tank 2 bottom
S5TCOL2Temperature collector 2
VFSOptional sensor for measurement
RPS
DT O12 °RSwitch-on temperature difference78
DT F8 °RSwitch-off temperature difference78
DT S20 °RSet temperature difference78
RIS4 °RRise78
S MAX140 °FTank maximum limitation78
SMAXS2Sensor tank max79
COL 1 >Collector 1
CEM1270 °FCollector emergency temperature 180
OCCO1**OFFOption collector cooling 180
System 19
Solar system with east-/west collectors and thermostatic backup heating
The controller compares the temperatures at the collector
sensors S1 and S5 to the tank temperature at sensor S2. If
one of the measured temperature differences is higher than
the adjusted switch-on temperature differences, the corre-
sponding pump (R1, R2) or both pumps will be activated and
the tank will be loaded. Domestic hot water backup heating
(R4) can be carried out with a thermostat function (S3).
VFS
RPS
Te mp. Sensor
S1
S1
R2R1
Pt1000
S2
S3
S4
S5
S5
GND
outin
PWM 1
PWM 2
L
V40
VBus
S3
R4
R4
L'
R1
R3
R2
N
S2
Sensor/Terminal
S1TCOL1Temperature collector 1
S2TSTBTemperature tank bottom
S3TSTTTemperature tank top
S4Optional sensor for measurement
S5TCOL2Temperature collector 2
VFSOptional sensor for measurement
RPS
V40
DT O12 °RSwitch-on temperature difference78
DT F8 °RSwitch-off temperature difference78
DT S20 °RSet temperature difference78
RIS4 °RRise78
S MAX140 °FTank maximum limitation78
SMAXS2Sensor tank max79
CEM1270 °FCollector emergency temperature 180
OCCO1**OFFOption collector cooling 180
The controller compares the temperatures at the collector
sensors S1 and S5 to the tank temperature at sensor S2. If
one of the measured temperature differences is higher than
the adjusted switch-on temperature differences, the corresponding pump (R1, R2) or both pumps will be activated and
the tank will be loaded.
With another temperature differential function (S3-heat
source/S4-heat sink) heating circuit return preheating (heating circuit backup) is possible with another valve (R3).
Domestic hot water backup heating (R4) can be carried out
with a thermostat function (S3).
Note: 3-port valve normally open - tank bottom
Sensor/Terminal
S1TCOL1Temperature collector 1
S2TSTBTemperature tank bottom
S3TSTT/TSTR Temperature tank top/
DT O12 °RSwitch-on temperature difference78
DT F8 °RSwitch-off temperature difference78
DT S20 °RSet temperature difference78
RIS4 °RRise78
S MAX140 °FTank maximum limitation78
SMAXS2Sensor tank max79
CEM1270 °FCollector emergency temperature 1 80
OCCO1**OFFOption collector cooling 180
System 21
Solar system with east-/west collectors and heating circuit return preheating
The controller compares the temperatures at the collector
sensors S1 and S5 to the tank temperature at sensor S2. If
one of the measured temperature differences is higher than
the adjusted switch-on temperature differences, the corresponding pump (R1, R2) or both pumps will be activated and
the tank will be loaded.
With another temperature differential function (S3-heat
source/S4-heat sink) heating circuit return preheating (heating circuit backup) is possible with another valve (R3).
VFS
RPS
Te mp. Sensor
S1
S1
R2R1
Pt1000
S2
S3
S4
S5
S5
GND
outin
PWM 1
PWM 2
L
V40
VBus
R4
L'
R3
R2
R1
N
S3
S4
S2
R3
Sensor/Ter-
DesignationDescription
minal
S1TCOL1Temperature collector 1
S2TSTBTemperature tank bottom
S3TSTTTemperature tank top
S4TRETTemperature - return
S5TCOL2Temperature collector 2
VFSOptional sensor for measurement
RPS
DT O12 °RSwitch-on temperature difference78
DT F8 °RSwitch-off temperature difference78
DT S20 °RSet temperature difference78
RIS4 °RRise78
S MAX140 °FTank maximum limitation78
SMAXS2Sensor tank max79
COL 1 >Collector 1
CEM1270 °FCollector emergency temperature 180
OCCO1**OFFOption collector cooling 180
System 22
Solar system with vertical tank loading and east-/west collectors
The controller compares the temperatures at the collector
sensors S1 and S5 to the tank temperatures at the sensors
S2 and S3. If one of the measured temperature differences is
higher than the adjusted switch-on temperature differences,
the corresponding pump (R1, R2) or both pumps will be
activated and the corresponding tank zone will be loaded
up to the adjusted maximum temperature via the valve (R3).
The priority logic effects prior loading of the upper zone
of the tank.
DT1O12 °RSwitch-on temperature difference 178
DT1F8 °RSwitch-off temperature difference 178
DT1S20 °RSet temperature difference 178
RIS14 °RRise 178
S1MAX140 °FTank maximum limitation 178
SMXS12Sensor tank max 179
System 23
Solar system with east-/west collectors and 2 tanks (valve logic)
The controller compares the temperatures at the collector
sensors S1 and S5 to the temperatures at S2 and S4. If one
of the measured temperature differences is higher than the
adjusted switch-on temperature differences, the correspon-
ding pump (R1, R2) or both pumps will be activated and
the corresponding tank will be loaded up to the adjusted
maximum temperature via the valve (R3).
Note: 3-port valve normally open
- tank 1 (S2)
Sensor/Terminal
S1TCOL1Temperature collector 1
S2TST1BTemperature tank 1 bottom
S3Optional sensor for measurement
DesignationDescription
purposes or options
S4TST2BTemperature tank 2 bottom
S5TCOL2Temperature collector 2
VFSOptional sensor for measurement
RPS
DT1O12 °RSwitch-on temperature difference 178
DT1F8 °RSwitch-off temperature difference 178
DT1S20 °RSet temperature difference 178
RIS14 °RRise 178
S1MAX140 °FTank maximum limitation 178
SMXS12Sensor tank max 179
LOAD2 >Loading 2
DT2O12 °RSwitch-on temperature difference 278
DT2F8 °RSwitch-off temperature difference 278
DT2S20 °RSet temperature difference 278
The controller compares the temperatures at the collector
sensors S1 and S5 to the temperatures at S2 and S3. If one
of the measured temperature differences is higher than the
adjusted switch-on temperature differences, the corresponding pump (R1, R2) or both pumps will be activated and the
corresponding tank zone will be loaded up to the adjusted
maximum temperature via the valve (R3). The upper tank
zone is be loaded with priority. Heat exchange from tank 1
to tank 2 (R4) is possible with another temperature differential function (S3-heat source/S4-heat sink).
VFS
RPS
Te mp. Sensor
S1
S1
R3
R2R1
Pt1000
S2
S3
S4
S5
S5
GND
outin
PWM 1
PWM 2
L
V40
VBus
S3
R4
R4
L'
R1
R3
R2
N
S4
S2
Note: 3-port valve normally open - tank bottom
Sensor/Terminal
S1TCOL1Temperature collector 1
S2TSTBTemperature tank bottom
S3TSTTTemperature tank top
S4TST2BTemperature tank 2 bottom
S5TCOL2Temperature collector 2
VFSOptional sensor for measurement
RPS
V40
DT1O12 °RSwitch-on temperature difference 178
DT1F8 °RSwitch-off temperature difference 178
DT1S20 °RSet temperature difference 178
RIS14 °RRise 178
S1MAX140 °FTank maximum limitation 178
SMXS12Sensor tank max 179
DT2O12 °RSwitch-on temperature difference 278
DT2F8 °RSwitch-off temperature difference 278
DT2S20 °RSet temperature difference 278
The controller compares the temperatures at the collector
sensors S1 and S5 to the tank temperatures at the sensors
S2 and S3. If one of the measured temperature differences is
higher than the adjusted switch-on temperature differences,
the corresponding pump (R1, R2) or both pumps will be
activated and the corresponding tank zone will be loaded
up to the adjusted maximum temperature via the valve (R3).
The priority logic effects prior loading of the upper zone
of the tank.
Domestic hot water backup heating (R4) can be carried out
with a thermostat function (S3).
VFS
RPS
Te mp. Sensor
S1
S1
R3
R2R1
Pt1000
S2
S3
S4
S5
S5
GND
outin
PWM 1
PWM 2
L
V40
VBus
S3
R4
R4
L'
R1
R3
R2
N
S2
Note: 3-port valve normally open - tank bottom
Sensor/Terminal
S1TCOL1Temperature collector 1
S2TSTBTemperature tank bottom
S3TSTTTemperature tank top
S4Optional sensor for measurement
S5TCOL2Temperature collector 2
VFSOptional sensor for measurement
RPS
V40
DT1O12 °RSwitch-on temperature difference 178
DT1F8 °RSwitch-off temperature difference 178
DT1S20 °RSet temperature difference 178
RIS14 °RRise 178
S1MAX140 °FTank maximum limitation 178
SMXS12Sensor tank max 179
AH O110 °FBackup heating switch-on temperature87
AH F120 °FBackup heating switch-off temperature87
t1O06:00Switch-on time 188
t1F22:00Switch-off time 188
t2O00:00Switch-on time 288
t2F00:00Switch-off time 288
t3O00:00Switch-on time 388
t3F00:00Switch-off time 388
The controller compares the temperatures at the collector
sensors S1 and S5 to the tank temperatures at the sensors
S2 and S3. If one of the measured temperature differences is
higher than the adjusted switch-on temperature differences,
the corresponding pump (R1, R2) or both pumps will be
activated and the corresponding tank zone will be loaded
up to the adjusted maximum temperature via the valve (R4).
The priority logic effects prior loading of the upper zone
of the tank.
With another temperature differential function (S4/S3),
backup heating of the tank can be carried out with a solid
fuel boiler (R3).
VFS
RPS
Te mp. Sensor
S1
S1
R4
R2R1
Pt1000
S2
S3
S4
S5
S5
GND
outin
PWM 1
PWM 2
L
V40
VBus
R4
L'
R1
R3
R2
N
S4
S3
R3
S2
Note: 3-port valve normally open - tank bottom
Sensor/Ter-
DesignationDescription
minal
S1TCOL1Temperature collector 1
S2TSTBTemperature tank bottom
S3TSTTTemperature tank top
DT1O12 °RSwitch-on temperature difference 178
DT1F8 °RSwitch-off temperature difference 178
DT1S20 °RSet temperature difference 178
RIS14 °RRise 178
S1MAX140 °FTank maximum limitation 178
SMXS12Sensor tank max 179
Speed control of a HE pump is possible via a PWM signal.
For this purpose, the pump has to be connected to the relay
as well as to one of the PWM outputs of the controller (see
S1
page 4). In the PUMP adjustment channel one of the
PWM control types has to be selected.
R1
Note:
For more information about pump control, see
page 79.
The controller is operated via the 7 buttons next to the
display. They have the following functions:
1
Button
Button
Button
Button
Button
Button
- scrolling upwards
3
- scrolling downwards
2
- increasing adjustment values
4
- reducing adjustment values
5
- conrming
6
- menu button for changing between the
status and the menu level
Button
7
- escape button for changing into the previous menu
During normal operation of the controller, the display is in
the status level.
In order to leave the status level and access the menu level,
press button 6.
The display indicates the level with the selectable menus. In
order to change the parameters of a menu item, select the
menu item and press button 5. The display changes to the
adjustment level. The adjustment channels are characterized
by the indication
Î Select the desired channel by pressing the buttons
3
and
.
1
Î Confirm the selection with button 5, flashes
(adjustment mode)
Î Adjust the value, the function or the option using the
buttons
2
and
4
Î Conrm the selection with button 5, permanently
appears, the adjustment has been saved.
If no button has been pressed within a couple of minutes,
the adjustment is cancelled and the previous value is
retained.
3.3 Menu structure
The menu structure of the controller consists of 3 levels:
the status level, the menu level and the adjustment level.
Status level
INIT
FLLT
STAB
TCOL
TSRE
...
The status level consists of different display channels which
indicate display values and messages.
The menu level consists of different menu items each of
which is divided into sub-menus and adjustment channels.
Each of these menu items represents a function or option
which can be selected. If a function or option is selected,
the controller changes to the adjustment level in which the
Adjustment level
DT O
DT F
DT S
RIS
S MAX
SMAXS
...
corresponding parameters of the function or option are
available.
In order to activate or deactivate a function, it must be
selected in the menu level. The display changes to the adjustment menu in which all adjustments required can be
carried out.
During normal operation of the controller, the display is in
the status level.
69 |
Page 70
SOM 9s
Note:
Some of the menu items depend on the selected
system and the adjusted options. Therefore, they
are only displayed if they are available.
Note:
The abstract from the menu structure shown
above is for information on the structure of the
controller menu and is therefore not complete.
Menu level
If it is possible to jump into a menu, PUSH is indicated
below the menu item. Use button
to access the menu.
5
In order to leave the menu, press button 7.
If an option is deactivated, it will appear in the menu level
with the addition OFF.
3.4 Indications and system monitoring display
The system monitoring display consists of 3 areas:
channel display, tool bar and system screen.
Channel display
Tool bar
The additional symbols in the tool bar indicate the
current system state.
The channel display consists of 2 lines. The upper display line
is an alphanumeric 16-segment display. In this line, mainly
channel names and menu items are displayed. In the lower
7-segment display, channel values and the adjustment parameters are displayed.
Temperatures and temperature differences are indicated
with the unit (°C / °F or K / °R respectively).
Symbolnormalashing
COM
+
+
+
Relay active
Maximum tank limitation
active / maximum tank
temperature exceeded
Antifreeze function activated
SD card is being usedSD card is full
Indication of the buttons
available in the menu item
Normal operation
Collector cooling function
active
System cooling, tank cooling
active
Collector minimum limitation active
Antifreeze function active
Collector emergency shutdown
Sensor fault
Manual mode active
Tank emergency shutdown
active
Adjustment channel is
being changed (set mode)
The system selected is indicated in the system monitoring
display. It consists of several system component symbols
which are – depending on the current status of the system
– either ashing, permanently shown or “hidden”.
Collector 1
Valve
Pumps
Tank heat exchanger
Sensors
Collector 2
Tank
Upper tank
sensor
Tank 2 or backup heating/solid fuel boiler
(with additional symbol)
When the hydronic system is lled and ready for operation,
connect the controller to the power supply.
The controller runs an initialization phase in which all
symbols are indicated in the display. The directional pad
ashes red.
Commissioning menu
The commissioning menu consists of the channels described in the following. In order to make an adjustment, push
button
5
. The set symbol ashes and the adjustment can
When the controller is commissioned for the rst time or
when it is reset, it will run a commissioning menu after the
initialization phase. The commissioning menu leads the user
through the most important adjustment channels needed
for operating the system and starts with the indication of
the BX version number.
be made. Conrm the adjustment with button
button
, the next channel will appear in the display.
3
5
. Push
1. Language:
Î Adjust the desired menu language.
2. Unit:
Î Adjust the desired unit.
3. Time:
Î Adjust the clock time. First of all adjust the hours,
then the minutes.
4. Date:
Î Adjust the date. First of all adjust the year, then the
month and then the day.
Buttonnavigation
adjustment mode
5
changing a value
2
4
conrming a value
5
to the next para-
3
meter
5. System:
Î Adjust the desired system.
6. Maximum tank temperature:
Î Adjust the maximum tank temperature.
In 2-tank systems, the adjustment has to be carried
out for S1MAX and S2MAX as well.
The values and adjustment channels shown
depend on the selected system, the functions
and options and will only be displayed in the
expert level.
In order to protect the pumps against blocking after standstill, the controller is equipped with a blocking protection
function. This function switches on the relays every day at
12:00 a.m. for 10 s at 100%.
Indicates the time adjusted in tDTO, running backwards.
Indicates the time adjusted in tFLL, running backwards.
Indicates the time adjusted in tSTB, running backwards.
STAB
Stabilization
Display of collector temperatures
TCOL(1, 2)
Collector temperature
Display range: -40 ... +500 °F
Display of tank temperatures
TST (1, 2)B, TST (1)T
Tank temperatures
Display range : -40 ... +500 °F
DisplayoftemperaturesatS3,S4andS5
S3, S4, S5
Sensor temperatures
Display range : -40 ... +500 °F
Displays the current collector temperature.
• TCOL : Collector temperature (1-collector system)
• TCOL1 : Collector temperature 1 (2-collector system)
• TCOL2 : Collector temperature 2 (2-collector system)
Displays the current tank temperature.
• TSTB : Tank temperature bottom
• TSTT : Tank temperature top
in 2-tank systems (only if available):
• TST1T : Temperature tank 1 top
• TST1B : Temperature tank 1 bottom
• TST2T : Temperature tank 2 top
• TST2B : Temperature tank 2 bottom
Indicates the current temperature at the corresponding
additional sensor (without control function).
• S3 : Temperature sensor 3
• S4 : Temperature sensor 4
• S5 : Temperature sensor 5
Note:
Only if temperature sensors are connected, will
S3, S4 and S5 be displayed.
Note:
In systems with return preheating, S3/S5 is used
Indicates the heat quantity produced in the system. For this
purpose, the energy metering option has to be enabled.
The ow rate as well as the values of the reference sensors
S1 (ow) and S4 (return) are used for calculating the heat
quantity supplied. It is shown in kWh in the channel kWh
and in MWh in the channel MWh . The overall heat quantity
results from the sum of both values.
The accumulated heat quantity can be set back to 0. As
soon as one of the display channels of the heat quantity is
selected, the symbol
Î In order to access the RESET-mode of the counter, press
the set button
The display symbol
be set to 0.
Î Conrm the reset with the set button in order to nish
the reset.
In order to interrupt the RESET process, no button should
be pressed for about 5 s. The display returns to the display
mode.
is displayed.
5
for approx. 2 s.
will ash and the heat quantity will
CDIS
Countdown of monitoring
period
Display range:
0 ... 30:0 ... 24 (dd:hh)
Display of starting time
SDIS
Starting point
Display range:
0:00 ... 24:00 (time)
Display of heating period
DDIS
Heating period
Display range:
0:00 ... 23:59 (hh:mm)
If the thermal disinfection option (OTDIS) is activated
and the monitoring period is in progress, the remaining
time of the monitoring period is displayed as CDIS (in
hours and minutes), counting backwards.
If the thermal disinfection option (OTDIS) is activated
and starting delay time has been adjusted, the adjusted
delay time is displayed (ashing) in this channel.
If the thermal disinfection option (OTDIS) is activated
and the heating period is in progress, the remaining time
of the heating period is displayed (in hours and minutes)
in this channel, counting backwards.
System
Adjustment range: 1 ... 26
Factory setting: 1
DT-regulation
LOAD(1, 2) / DT(1, 2) O
Switch-on temperature
difference
Adjustment range: 2.0 ... 90.0 °R
in steps of 1.0 °R
Factory setting: 12.0 °R
LOAD 2) / DT(1, 2,) F
Switch-off temperature
difference
Adjustment range: 1.0 ... 89.0 °R
in steps of 1.0 °R
Factory setting: 8.0 °R
Note:
If the controller is commissioned for the rst
time, the commissioning menu will start. The
subsequent selection of a new system will reset
all other adjustments to the factory settings.
Selection of the appropriate system. Each system has
pre-programmed options and adjustments which can be
activated or changed respectively if necessary. Select the
system rst (see chap. 3).
The controller works as a standard differential controller. If
the switch-on difference is reached, the pump is activated.
When the temperature difference reaches or falls below the
adjusted switch-off temperature difference, the respective
relay switches off.
Note:
The switch-on temperature difference is blocked
against the switch-off temperature difference by
1 °R. DT O must be at least 1 °R higher than
DT F. The set temperature difference must be
at least 1 °R higher than the switch-on temperature difference.
Speed control
LOAD(1, 2) / DT(1, 2,) S
Set temperature difference
Adjustment range: 3.0... 90.0 °R
in steps of 1.0 °R
Factory setting: 20.0 °R
LOAD(1, 2) / RIS(1, 2)
Rise
Adjustment range: 2.0 ... 40 °R
in steps of 2 °R
Factory setting: 4 °R
Maximum tank temperature
LOAD(1, 1.2) / S(1,2) MAX
Maximum tank temperature
Adjustment range: 40 ... 200 °F
in steps of 2 °F
Factory setting: 140 °F
| 78
Note:
To enable speed control, the corresponding relay has to be set to “Auto” (adjustment channel
MAN) and the pump control type has to be set
to Puls, A, b, or C (adjustment channel PUMP).
When the switch-on temperature difference is reached, the
pump is activated at 100% speed for 10 s. Then, the speed is
reduced to the minimum pump speed value.
If the temperature difference reaches the adjusted nominal
value (DT S), the pump speed increases by one step (10 %).
The response of the controller can be adapted via the parameter “Rise”. If the difference increases by the adjustable
rise value RIS, the pump speed increases by 10 % until the
maximum pump speed of 100 % is reached. If, at decreasing
temperatures, the temperature difference decreases by
the adjustable rise value RIS, the pump speed decreases
by 10 %.
If the tank temperature reaches the adjusted maximum
temperature, the tank will no longer be loaded in order to
avoid damage caused by overheating. If the maximum tank
temperature is exceeded,
The corresponding reference sensor can be chosen, see
“Sensor maximum tank temperature”.
Loading tank 2
Selection: ON / OFF
Factory setting: ON
Pump control
PUMP / PUMP1 (2, 3,)
Pump control
Selection: OnOF, Puls, PWM A,
PWM b, PWM C,
Factory setting: OnOF
Allocation of the sensor for tank maximum limitation. The
maximum limitation always refers to the sensor selected.
If S3 is selected, the differential control will be carried out
using S1 and S2. The temperature at S2 can exceed the
adjusted limit temperature, the system will not switch off.
If the value at S3 reaches the limit temperature, the system
will be switched off.
Note:
In 1-tank systems with sensor S3 as the reference
sensor, loading will be switched off if the temperature at S2 or S3 reaches the tank emergency
shutdown temperature.
In 2-tank systems, loading will be switched off
if the temperature at S4 or S5 reaches the tank
emergency shutdown temperature.
In a 2-tank system, the second tank can be switched off for
loading via the parameter LST2.
If LST2 is adjusted to OFF, the system runs like a 1-tank
system. The representation in the display does not change.
With this parameter, the pump control type can be adjusted.
The following types can be selected:
Adjustment for standard pump without speed control
• OnOF (pump on / pump off)
Adjustment for standard pump with speed control
• PULS (pulse packet control via semiconductor relay)
Adjustment for high efciency pump (HE pump)
• PWM A (Wilo)
• PWM b (Grundfos)
• PWM C (Laing)
Note:
For more information about connecting HE
pumps, see page 68.
Note:
PUMP3 can only be set to OnOf or PULS.
Minimum speed
PUMP1 (2, 3) / n1 (2, 3 LO
Speed control
Adjustment range: 20 ... 100 %
in steps of 5%
Factory setting: 30 %
Maximum speed
PUMP1 (2, 3) / n1 (2, 3) HI
Speed control
Adjustment range: 20 ... 100 %
in steps of 5%
Factory setting: 100 %
In the adjustment channel n1(2,3)LO, a relative minimum
speed for connected pumps can be allocated to the outputs
R1, R2 and R3.
Note:
When loads which are not speed-controlled (e. g.
valves) are used, the value of the corresponding
relay (n1, n2, n3) must be set to 100% or the
pump control type must be set to OnOF in
order to deactivate pump speed control.
In the adjustment channel n1(2,3)HI, a relative maximum
speed for connected pumps can be allocated to the outputs
R1, R2 and R3.
Note:
When loads which are not speed-controlled (e. g.
valves) are used, the value of the corresponding
relay (n1, n2, n3) must be set to 100% or the
pump control type must be set to OnOF in
order to deactivate pump speed control.
79 |
Page 80
SOM 9s
Collector emergency shutdown
COL(1,2) / CEM(1,2)
Collector emergency
temperature
Adjustment range: 170 ... 390 °F
in steps of 2 °F
Factory setting: 270 °F
Switch-on hysteresis: -10 °R
When the collector temperature exceeds the adjusted collector emergency temperature (CEM / CEM1 / CEM2), the
solar pump (R1 / R2) is switched off in order to protect the
system components against overheating (collector emergency shutdown). If the maximum collector temperature is
exceeded,
WARNING!Danger of injury and system da-
is displayed (ashing).
Note:
If the drainback option ODB is activated, the
adjustment range of the collector emergency
temperature is changed to 170 ... 200 °F. Factory
setting in that case is 200 °F.
mage through pressure surges!
If water is used as a heat transfer
medium in a pressure-less system, the
water will start boiling at 212 °F
Î If a pressure-less drainback
system is used with water as a
heattransfermedium,do not
adjust the collector temperature limitation CEM to more
than 200 °F
Collector cooling
COL(1,2) / OCCO(1,2)
Adjustment range ON / OFF
Factory setting: OFF
COL (1,2) / OCCO(1,2) /
CMAX(1,2)
Collector maximum temp.
Adjustment range: 150 ... 320 °F
in steps of 2 °F
Factory setting: 230 °F
Switch-on hysteresis: -10 °R
Minimum collector limitation
COL(1,2) / OCMI(1,2)
Collector minimum temp.
Adjustment range: ON / OFF
Factory setting: OFF
COL (1,2) / OCMI(1,2) /
CMIN(1,2)
Collector minimum temp.
Adjustment range: 50 ... 190 °F
in steps of 2 °F
Factory setting: 50 °F
This function is used for keeping the system temperatures
and consequently the thermal load as low as possible.
When the tank temperature exceeds the adjusted maximum
tank temperature, the system stagnates. If the collector
temperature increases to the adjusted maximum collector
temperature, the solar pump is activated until the collector
temperature falls below the maximum collector temperature. The tank temperature may then exceed the maximum
temperature, but only up to 200 °F (emergency shutdown
of the tank).
If the collector cooling is active,
Note:
This function is only available, if the system
cooling function and the heat dump function
are deactivated.
The minimum collector temperature is the minimum switchon temperature which must be exceeded for the solar pump
(R1 / R2) to switch on. The minimum temperature prevents
the pump from being switched on too often at low collector
temperatures. If the collector temperature falls below the
adjusted minimum temperature,
Evacuated tube collector
function
Selection: ON / OFF
Factory setting: OFF
COL / OTCO (1, 2) / TCST
(1, 2)
Starting time
Adjustment range:
00:00 ... 23:00
Factory setting: 07:00
COL / OTCO (1, 2) / TCEN (1, 2)
Ending time
Adjustment range:
00:30 ... 23:30
in steps of 00:30
Factory setting: 19:00
COL / OTCO (1, 2) / TCRU (1, 2)
Runtime
Adjustment range: 30 ... 300 s
in steps of 5 s
Factory setting 30 s
COL / OTCO (1, 2) / TCIN (1, 2)
Standstill interval
Adjustment range: 5 ... 60 min
in steps of 00:01
Factory setting: 30 min
This function helps overcome the non-ideal sensor position
with some evacuated tube collectors.
This function operates within an adjusted time frame,
beginning at TCST and ending at TCEN. It activates the
collector circuit pump for an adjustable runtime (TCRU)
between adjustable standstill intervals (TCIN) in order to
compensate for the delayed temperature measurement.
If the runtime TCRU is set to more than ten seconds, the
pump will be run at 100 % for the rst 10 s of the runtime.
For the remaining runtime, the pump will be run at the
adjusted minimum speed nLO.
If the collector sensor is defective or the collector is blocked,
this function is suppressed or switched off.
2-collector systems
In 2-collector systems, the evacuated tube collector function
is available for each collector eld (OTCO2).
If one of the collector elds is being loaded, the heat transfer
uid ows through the inactive eld and only the correspon-
ding relay is energized.
Multi-tank systems
If the evacuated tube collector function is activated, the
speed of the solar pump will decrease to nLO during the
loading break time. The solar loading of the subordinate
tank will continue.
In 2-collector systems, during the loading break time the
collector eld which has been active before the loading
break time remains active during the loading break time,
unless the evacuated tube collector function of the inactive
eld becomes active.
Note:
If the drainback option ODB is activated, the
evacuated tube collector function OTCO will
not be available.
Antifreeze function
Selection: ON / OFF
Factory setting: OFF
COL (1) / OCFR / CFR O
Antifreeze temperature on
Adjustment range: -40...+46 °F
Factory setting: 40 °F
COL (1) / OCFR / CFR F
Antifreeze temperature off
Adjustment range: -39...+48 °F
Factory setting: 42 °F
COL (1) / OCFR / FRPST
Sensor selection
Selection: 1, 2
Factory setting: 1
in 2-tank systems only
Priority logic
The antifreeze function activates the loading circuit between
the collector and the tank when the temperature falls below
the adjusted temperature CFR O. This will protect the uid
against freezing or coagulating. If CFR F is exceeded, the
solar pump will be switched off again.
The antifreeze function will be suppressed if the tank temperature of the selected tank falls below 42 °F. In 2-tank
systems, the function will switch to the second tank, in systems with vertical tank loading, it will switch to the upper
tank zone. If the temperature of the second tank (or of the
upper tank zone respectively) also falls below 42 °F, the
system will be switched off.
Note:
Since this function uses the limited heat quantity
of the tank, the antifreeze function should be
used in regions with few days of temperatures
around the freezing point.
Note:
This function can only become active if the
tank temperature is higher than the collector
temperature.
Note:
Priority logic can be used in 2-tank systems or
systems with vertical tank loading only.
Loading break time
Adjustment range: 1 ... 30 min
Factory setting: 2 min
LLOGI / tRUN
Oscillating loading time
Adjustment range: 1 ... 30 min
Factory setting: 15 min
Note:
If priority Su 1 or Su 2 is adjusted, solar loading
of the subordinate tank will be interrupted, if
the temperature of the priority tank (tank1 for
Su 1, tank 2 for Su 2) falls below its adjusted
maximum temperature. If, in that case, the temperature difference between the priority tank
and the collector is not sufciently high, solar
loading will be stopped completely.
| 82
Priority logic can be used in 2-tank systems or systems with
vertical tank loading only and determines how the heat is
divided between the tanks. Different types of priority logic
are adjustable:
tank sequence control (1 and 2)
successive loading (Su 1 and Su 2)
parallel loading (0)
1. If PRIO 1 or PRIO 2 is adjusted, the corresponding
tank (1=tank 1; 2=tank 2) will be loaded with priority if its
switch-on conditions are fullled and if it is not blocked. If
the priority tank is not blocked but its switch-on conditions
are not fullled, the tank sequence control starts provided
that the switch-on conditions of the subordinate tank are
fullled.
If a subordinate tank can be loaded, it will be loaded for
the oscillating loading time tRUN. After the loading time
has ended, the pump is switched off for the loading break
tLB. If during this time the priority tank can be loaded, it
will be loaded. If the priority tank has reached its maximum
temperature, the subordinate tank will be loaded up to its
maximum temperature without oscillating loading logic.
2. If priority Su 1 or Su 2 is adjusted, the priority tank will
be loaded up to its maximum temperature. If the maximum
temperature is reached, the second tank will be loaded. If
the temperature of the rst tank falls below SMAX, the
second tank will no longer be loaded, regardless of whether
the switch-on conditions of the priority tank or of the sub-
ordinate tank are fullled or not.
3. In systems with 2 pumps, both tanks will be loaded if the corresponding switch-on conditions are fullled if PRIO 0
is adjusted.
In systems with 3-port valves, the tank with the lowest
temperature will be loaded rst until its temperature is by
10 °R above the other tank. Loading will be switched to the
other tank. Then, the 2 tanks will be loaded alternately in
steps of 10 °R.
Additionally, the following options can be activated:
Tank set option OSTS: If the selected priority tank
reaches its set temperature, the subordinate tank will be
loaded until it reaches its set temperature. After that, the
priority tank will be loaded up to its maximum tank temperature, then the subordinate tank. This function is available
in all 2-tank systems.
Spreaded loading option OSE: In 2-tank systems with 2
pumps, a spreaded loading function can be activated.
As soon as the adjustable spread difference DTSE between
the collector and the priority tank is reached, the second
tank will be loaded in parallel unless it is blocked. If the
temperature difference falls by 4 °R below DTSE, the pump
is switched off.
The collector temperature has to be higher than the tank
temperature.
Pause control
LLOGI / PSPEE
Pause speed
Selection: ON / OFF
Factory setting: OFF
LLOGI / PDELA
Pump delay
Selection: ON / OFF
Factory setting: OFF
This function takes into account the actuation times of
valves and switches on the pump with a delay.
If the pause speed is activated, the relay of the tank which
has been loaded last remains switched on during the loading
break time. Speed is determined by the value adjusted in
nLO.
If the pump delay is activated, the corresponding relay for
the valve will be energized rst. The pump(s) will be activated with the delay time (200s).
Note:
In systems with pump logic, the parameter
PDELA is not available.
Drainback option
Selection: ON / OFF
Factory setting: OFF
A drainback system permits the heat transfer uid to drain
back into the holding tank when solar energy is not coll-
ected. The drainback option will initiate the lling of the
system when solar loading begins. If the function is activated,
the menu items described in the following (tDTO, tFLL
and tSTB) have to be adjusted:
Note:
A drainback system requires additional com-
ponents such as a holding tank. The drainback
option should only be activated if all components
required are properly installed.
Note:
If the drainback option ODB is activated, the
cooling functions and the antifreeze function will
not be available.
Time period - switch-on condition
LLOGI/ODB/tDTO
Time period - switch-on
condition
Adjustment range: 1 ... 100 s
in steps of 1 s
Factory setting: 60 s
Filling time
LLOGI/ODB/tFLL
Filling time
Adjustment range:
1.0 ... 30.0 min
in steps of 0.5 min
Factory setting: 5.0 min
Note:
The drainback option is only available in system
with one tank and one collector eld and if no
cooling function is activated.
Note:
If the drainback option ODB is activated, the
factory settings of the parameters DT O,
DT F and DT S will be adapted to values suiting
drainback systems. Additionally, the adjustment
range and the factory setting of the collector
emergency shutdown CEM will change.
Previous adjustments made in these channels
will be overridden and have to be entered again
if ODB is deactivated later on.
The parameter tDTO is used for adjusting the time period
during which the switch-on condition DT O must be per-
manentely fullled.
The lling time can be adjusted using the parameter tFLL.
During this period, the pump runs at 100 % speed.
Stabilization
LLOGI/ODB/tSTB
Stabilization
Adjustment range:
1.0 ... 15.0 min
in steps of 0.5 min
Factory setting: 2 min
Boosterfunction
LLOGI/ODB/OBST
Booster function
Adjustment range: ON / OFF
Factory setting: OFF
Overrun
LLOGI/OOVRU
Selection: ON / OFF
Factory setting: OFF
| 84
The parameter tSTBis used for adjusting the time period
during which the switch-off condition DT F will be ignored
after the lling time has ended.
This function is used for switching on a second pump when
lling the solar system. When solar loading starts, R3/R4 is
energized in parallel to R1. After the lling time (tFLL) has
ended, R2 is switched off.
Note:
The booster function is available in systems 1, 3,
8, 9, and 10 only.
By means of this function, tank loading continues after the
temperature difference between the collector and the tank
has fallen below the switch-off difference. Tank loading is
stopped if the adjusted DT overrun difference between ow
and return sensor is underrun.
Pump or valve logic
Selection: ON / OFF
Factory setting: OFF
Different cooling functions can be activated: system cooling,
tank cooling and heat dump.
The system cooling function aims to keep the solar system
operational for a longer time. The function overrides the
maximum tank temperature to provide thermal relief of
the collector eld and the heat transfer uid on hot days.
If the tank temperature is higher than the adjusted maximum
tank temperature and the switch-on temperature difference
DTCO is reached, the solar system remains activated or
is switched on. Solar loading is continued until either the
temperature difference falls below the adjusted value DTCF
or the collector emergency shutdown temperature CEM
is reached.
If the system cooling function is active,
display (ashing).
When the tank cooling function is activated, the controller
aims to cool down the tank during the night in order to
prepare it for solar loading on the following day.
If the adjusted maximum tank temperature (S MAX / S1MAX / S2MAX) is exceeded and the collector temperature falls below the tank temperature, the system will be
reactivated in order to cool down the tank.
Reference temperature differences are DT O and DT F.
If the heat dump function OHDP is activated, the selected
relay is energized with 100%, if the collector temperature
reaches the adjusted collector overtemperature OTCL.
If the collector temperature falls by 10 °R below the adjusted collector overtemperature OTCL, the relay will be
switched off.
A selection can be made between pump logic and valve logic
(OTPUM ON = pump logic, OTPUM OFF = valve logic).
If pump logic is selected, the relay for solar loading switches
off and the relay for heat dump remains switched on.
The relay for the heat dump function can be selected in the
HDREL channel.
COOL / HDREL
Relay heat dump function
Selection: system dependent
Factory setting: 3
Note:
The overrun function is only available, if both
Grundfos sensors (VFS and RPS) are used.
Note:
If the temperature at the tank sensor reaches
200 °F, all cooling functions will be blocked. The
switch-on hysteresis is 10 °R.
is shown on the
Note:
This function will only be available if the collector cooling function, the heat dump function, and
the drainback option are deactivated.
Note:
The adjustable value OTCL is locked against
the collector emergency temperature CEM
by 20 °R. The heat dump will only be available
if the collector cooling function, the system
cooling function, and the drainback option are
deactivated.
85 |
Page 86
SOM 9s
Heat exchange function / solid fuel boiler / return
preheating
DT3 / DT3O
Switch-on temperature diff.
Adjustment range: 2.0 ... 90.0 °R
in steps of 1.0 °R
Factory setting: 12.0 °R
DT3 / DT3F
Switch-off temperature diff.
Adjustment range: 1.0 ... 89.0 °R
in steps of 1.0 °R
Factory setting: 8.0 °R
DT3 / DT3S
Set temperature diff.
Adjustment range: 3.0 ... 90.0 °R
in steps of 1.0 °R
Factory setting: 20.0 °R
DT3 / RIS3
Rise
Adjustment range: 2 ... 40 °R
in steps of 2 °R
Factory setting: 4 °R
The heat exchange function is used for transporting heat
from tank 1 to tank 2.
Additionally, minimum and maximum temperature limits and
the corresponding switch-on and switch-off differences can
be set for the independent temperature differential control.
Both switch-on and switch-off temperature differences
DT3O and DT3F as well as the set temperature difference
DT3S and rise RIS3 are valid.
If the adjusted value MAX3O is exceeded, the relay will
be switched off. If the temperature falls below the adjusted
value MAX3F, the relay will be energized.
Reference sensor:
S3 for ARR 8, 13, 26 (TSTT)
S4 for ARR 2, 11, 16, 17, 18, 24 (TST2B)
If the temperature falls below the adjusted value MIN3O,
the relay will be switched off. If the adjusted value MIN3F
is exceeded, the relay will be energized.
Reference sensor:
S3 for ARR 8, 13, 26 (TSFB)
S4 for ARR 2, 11, 16, 17, 18, 24 (TSTT)
The reference sensor for the heat exchange function (heat
source) for tank 1 is sensor S3 (TSTT). The reference sensor
(heat sink) for tank 2 (S2DT3) is S4. It can be changed to S5
and is used for the differential function and the maximum
limitation.
For the solid fuel boiler function, the reference sensor (heat
source) for the solid fuel boiler is sensor S4. The reference
sensor (heat sink) for the tank is S3, but it can be changed
to S2.
Allocation of a sensor for the minimum and maximum limitation, instead of S4/S3.
In order to heat the heating circuit return by means of heat
supplied by the solar circuit, the controller is equipped with
a return preheating function.
If the switch-on temperature difference DT3O between
the sensors S3 or S5 (TSTR) and S4 (TRET) is exceeded, a
3-port valve for heating circuit backup is controlled via the
relay output R2/R3. Free sensors (S3 or S5) can be allocated
for this function (S2DT3).
Note:
In systems with east-/west collectors, S5 is not
available.
Thermostat function
Backup heatingUse of surplus energy
AH / AH O
Thermostat switch-on temp.
Adjustment range: 30...480 °F
in steps of 1 °F
Factory setting: 110 °F
AH / AH F
Thermostat switch-off temp.
Adjustment range:30...480 °F
in steps of 1 °F
Factory setting: 120 °F
The thermostat function works independently from the
solar operation and can be used for using surplus energy
or for backup heating.
• AH O < AH F
thermostat function for backup heating
• AH O > AH F
thermostat function for using surplus energy
Adjustment range:
Auto, ON, OFF, nLO, nHI
Factory setting: Auto
In order to block the thermostat function for a certain
period, there are three time frames t1 ... t3. The switch-on
and switch-off times can be adjusted in steps of 15 minutes.
If the switch-on and the switch-off time are identical, the
time frame is inactive.
If the thermostat function should run from 06:00 a.m. and
09:00 a.m. only, adjust t1O to 06:00 a.m. and t1F to 09:00
a.m.
The rst time frame is factory set from 06:00 to 22:00.
If all time frames are set to 00:00, the thermostat function
is solely temperature dependent.
For control and service work, the operating mode of the
controller can be manually adjusted. For this purpose, select
the adjustment value MAN. The following adjustments can
be carried out:
MAN / MAN4
Adjustment range:
Auto, ON, OFF
Factory setting: Auto
Note:
Always adjust the operating mode back to “Auto”
when the control and service work is completed
Otherwise normal operation will not be possible.
Blockingprotectionoption
Blockingprotection
BLPR1(2, 3)
Blocking protection
Selection: ON / OFF
Factory setting: OFF
Auto : relay in automatic mode
ON : relay is switched on
OFF : relay is switched off
nLO : relay is switched with adjusted minimum speed
nHI : relay is switched with adjusted maximum speed
In order to protect the pumps against blocking after standstill, the controller is equipped with a blocking protection
function. This function switches on the relays 1-3 every day
at 12:00 a.m. for 10 s at 100%.
Heating period
Adjustment range:
00:00...23:59
Factory setting: 01:00
OTDES / TDIS
Disinfection temperature
Adjustment range: 30...200 °F
in steps of 2 °F
Factory setting: 140 °F
Note:
If the thermal disinfection option OTDIS is acti-
vated, the display channels TDIS and CDIS will
be displayed. TDIS will be displayed regardless
of the temperature measured at the reference
sensor.
Thermal disinfection with starting delay
OTDIS / SDIS
Starting time
Adjustment range:
00:00 ... 24:00
Factory setting: 18:00
(6:00 p.m.) full hours only
Reference sensor for the thermal disinfection is S3!
It is possible to adjust this sensor in the channel
TSDIS.
This function is used for protecting the upper tank zone
against legionella by activating the backup heating. For
thermal disinfection, the temperature in the upper DHW
tank zone has to be monitored. This protection is ensured
when, during the monitoring period PDIS, the disinfection
temperature TDIS is continuously exceeded for the entire
heating period DDIS. S3 is used as the reference sensor
and displayed as TSTT.
If OTD is activated, PDIS will start as soon as the tempe-
rature at S3 falls below TDIS. The display channel CDIS
appears, counting backwards the remaining time of PDIS.
If, during the monitoring period, the temperature at S3 exceeds TDIS continuously for the duration of DDIS, thermal
disinfection is considered complete and a new monitoring
period begins.
If CDIS counts down to 00:00, relay 2 will be operated in
order to use the backup heating for thermal disinfection.
CDIS will then be replaced with a display channel DDIS
showing the adjusted heating period. DDIS will start counting down the heating period as soon as TDIS is exceeded
at S3. As long as DDIS is active, the temperature at S3 will
be displayed as TDIS instead of TSTT.
If, during DDIS, the temperature at S3 exceeds TDIS by
more than 10 °R, relay 2 is switched off until the temperature falls below TDIS + 4 °R.
If, during DDIS, the temperature at S3 falls below TDIS,
the heating period will restart. DDIS can only be completed
when TDIS is exceeded without interruption.
Due to the exible control logic, the exact time of thermal
disinfection is not predictable. In order to set a xed time
for the disinfection to be run, the starting delay SDIS must
be used:
When a starting time for thermal disinfection with starting
delay is adjusted in SDIS, the thermal disinfection will be delayed until that time, even after the CDIS has counted down
to 00:00. If CDIS ends, for example, at 12:00, and SDIS has
been set to 18:00 (6:00 p.m.), relay 2 will be operated with a
delay of 6 hours at 18:00 (6:00 p.m.) instead of 12:00.
During the waiting time, SDIS is displayed with the adjusted
starting time (ashing).
If, during the waiting time, the temperature at S3 exceeds
TDIS for the adjusted heating period DDIS, thermal
disinfection is considered complete and a new monitoring
period begins.
If the starting time is adjusted to 00:00 (factory setting), the
delay function is inactive.
Upon delivery, OTDIS is deactivated. The adjustment values PDIS,TDIS,DDIS and SDIS are displayed after the
option has been activated. After the thermal disinfection
function has been completed, the values will be “hidden”
and the monitoring period will be displayed.
Parallel relay
Adjustment range 2, 3, 4
Factory setting:
system-dependent
Energy metering
For this function, free sensors at an appropriate position can
be selected. Reference sensor for the thermal disinfection
is S3.
The relay for the thermal disinfection function can be selected.
With this function, e. g. a valve can be controlled in parallel
to the pump via a separate relay PARRE.
If solar loading takes place (R1 and/or R2) or if a solar
function is active, the relay selected will be energized. The
parallel relay can also be energized inversely (INVER).
Note:
If R1 and/or R2 are in the manual mode, the se-
lected parallel relay will not be energized.
OHQM
Energy metering
Adjustment range: ON / OFF
Factory setting: OFF
Overpressure
Adjustment range: ON / OFF
Factory setting: OFF
PRS / OVPRO
on at
Adjustment range: 0.6 ... 6.0 bar
Factory setting: 5.5 bar
If the system pressure exceeds the adjustable maximum
value OVPRO, an error message will appear. If the system
pressure exceeds or falls below the switch-off threshold, the
relay will be deblocked.
In the case of an overpressure, the message EPRES will
be displayed.
PRS / OVPRF
off at
Adjustment range: 0.3 ... 5.7 bar
Factory setting: 5.0 bar
Low pressure (leakage)
PRS / OLEAK
Low pressure
Adjustment range: ON / OFF
Factory setting: OFF
PRS / LEAKO
on at
Adjustment range: 0.3 ... 5.7 bar
Factory setting 0.7 bar
PRS / LEAKF
off at
Adjustment range: 0.6 ... 6.0 bar
Factory setting: 1.0 bar
Time and date.
DatE/Time
Time
Adjustment range:
00:00...23:59
Factory setting: 12:00
Note:
The monitoring function is only available, if the
Grundfos sensor RPS is used.
The switch-on threshold (factory setting 0.7 bar) can be
adjusted. If the system pressure falls below the adjusted value, the error message is displayed until the system pressure
exceeds the switch-off threshold (factory setting 1.0 bar).
In the case of low pressure, the message ELEAK will be
displayed.
Note:
The monitoring function is only available, if the
Grundfos sensor RPS is used.
The date and time can be entered. Both are required for the
thermostat function.
In the display, the upper line indicates the day followed by
the month. The lower line indicates the year.
Temperature unit
UNIT
Temperature unit
Selection: °C, °F
Factory setting: °F
| 92
In this adjustment channel the temperature unit can be
chosen.
The unit can be switched between °C and °F during operation.
In this adjustment channel, the menu language can be
chosen.
• dE : German
• En : English
If an SD card is used,
card is full,
COM
COM
is ashing.
is shown on the display. If the SD
OSDC / OSDC
SD card
Selection: ON / OFF
Factory setting: OFF
OSDC / LOGI
Logging interval
Adjustment range: 1 ... 1200 s
Factory setting: 60 s
OSDC / LLOG
Linear logging
Selection: ON / OFF
Factory setting: OFF
OSDC / REMC
Safely remove card
Selection: ON / OFF
Factory setting: OFF
OSDC / FORM
Format card
Starting the logging
Î Insert the SD card into the slot
Logging will start immediately.
Î Adjust the desired logging interval
When LLOG is activated, data logging will stop if the capacity limit is reached. The message CFULL will be displayed.
When LLOG (linear logging) is deactivated, the oldest data
logged onto the SD card will be overwritten as soon as the
capacity limit is reached.
Completing the logging process
Î Select the menu item REMCÎ After -REM is displayed remove the card from the slot
Formatting the SD card
Î Select the menu item FORM
During the formatting process, --FORM will be displayed.
The content of the card will be deleted and the card will be
formatted with the FAT le system.
Messages possibleDescription
FSYSFile system error
CTYPCard type is not supported
WRITError during writing
NOCRDNo card in slot
LOGGLogging is possible
WRITPCard is write-protected
CFULLCard full
RTIMERemaining logging time in days
PDIS01:00Monitoring period (interval)
DDIS01:00Heating period (duration of disinfection)
TDIS140 °FDisinfection temperature
SDIS00:00Starting time
TSDIS3Temperature sensor for disinfection
OTDISONDeactivation Thermal disinfection
OPARR >Parallel relay option
PARRE2Parallel relay
INVEROFFInversion
OHQM >Energy metering option
FTYPE1Flow rate detection type
FMAX6 l/minAdjustable maximum ow rate
FIMP1 l/lmpPulse rate
MEDT1Antifreeze type
MED%40Antifreeze concentration
SFHQM1Sensor ow HQM
SRHQM4Sensor return HQM
GFDS >Registration Grundfos sensors
VFSOFFRange of ow rate sensor
RPSOFFRange of pressure sensor
OFLOWOFFFlow rate monitoring option
PRS* >Pressure monitoring option
OOVPROFFOverpressure
OVPRO5.5 barOverpressure - switch-on value
The access to some adjustment values can be restricted via
a user code (customer). For safety reasons, the user code
should generally be set to the customer code before the
controller is handed to the customer!
1. Expert 0262 (Factory setting)
All menus and adjustment values are shown and all values
can be altered.
2. Customer 0000
The expert level is not shown, adjustment values can be
changed partly (see below)
Î In order to restrict the access, enter 0000 in the menu
item CODE.
The display changes to the status level. If the adjustment
channel is selected afterwards, the short menu shown below
will be available. The short menu suits the selected system.
Î In order to authorize the access, enter 0262 in the menu
item CODE.
ChannelFactory settingAdjustment rangeDescription
TIME12:0000:00 ... 23:59Time
DT O12 °R2.0 ... 90.0 °RSwitch-on temperature difference tank
DT F8 °R1.0 ... 89.0 °RSwitch-off temperature difference tank
DT S20 °R3.0 ... 90.0 °RSet temperature difference tank
S MAX140 °F40 ... 200 °FTank maximum limitation
DT1O12 °R2.0 ... 90.0 °RSwitch-on temperature difference tank 1
DT1F8 °R1.0 ... 89.0 °RSwitch-off temperature difference tank 1
DT 1S20 °R3.0 ... 90.0 °RSet temperature difference tank 1
S1MAX140 °F40 ... 200 °FTank maximum limitation tank 1
DT2O12 °R2.0 ... 90.0 °RSwitch-on temperature difference tank 2
DT2F8 °R1.0 ... 89.0 °RSwitch-off temperature difference tank 2
DT 2S20 °R3.0 ... 90.0 °RSet temperature difference tank 2
S2MAX140 °F40 ... 200 °FTank maximum limitation tank 2
LST2ONON / OFFLoading tank 2 on
MAN1AutoAuto / ON / OFF / n LO / n HI Manual operation pump 1
MAN2AutoAuto / ON / OFF / n LO / n HI Manual operation pump 2
MAN3AutoAuto / ON / OFF / n LO / n HI Manual operation pump 3
MAN4AutoAuto / ON / OFF Manual operation pump 4
CODE00000000 / 0262User code
In the case of an error, the directional pad ashes red and a
message is indicated in the status display. A warning triangle
is additionally indicated. If more than one error or fault condition has occurred, only the one with the highest priority
will be displayed as a message in the status display.
In the case of a sensor error, the system is switched off, and
a message appears on the display marked by an “E”. Additionally, a corresponding value for the error type assumed
is indicated.
After the error has been removed, the error message disappears.
Error messageValueDescriptionSolution
FS1...7
FS6, 8
EVFS9999Error at VFS sensorSensor fault. Check and, if necessary, corERPS9999Error at RPS sensor
ELEAKMeasured minimum
EPRESMeasured maximum
EFLOWError ow rate
PARAMRemote parametrizationDo not parametrize the controller via the
-88.8Short circuit at sensor 1...7Check the cable
888.8Broken cable at sensor 6, 8
rect the connection of the sensor plugs. If
a sensor signal does not appear, the sensor
has to be replaced
Leakage errorCheck the system for a leakage
pressure
Error pressureCheck the functioning of the valves and
pressure
Threshold values for VFS 1-10: 1,0-1,1 l/min
Threshold values for VFS 2-40: 2,0-2,1 l/min
The controller is protected by a fuse. The fuse holder (which
also holds the spare fuse) becomes accessible when the
cover is removed. To replace the fuse, pull the fuse holder
from the bottom.
The display is permanently off.
Press button
Check the power supply of the controller. Is it disconnected?
The fuse of the controller
could be blown. The fuse
holder (which holds the
spare fuse) becomes accessible when the cover
is removed. The fuse can
then be replaced.
Pump is overheated, but no heat transfer from the collector to the tank, ow and return have the same temperature; perhaps also bubble in the lines.
Air in the system?
noyes
Are valves or non-return
valves defective?
yes
Pump starts up very late.
Air the system; increase
the system pressure to
at least static primary
pressure plus 0,5 bar; if
necessary continue to
increase pressure; switch
the pump off and on for a
short time.
Replace them
Pump starts for a short moment, switches off, switches
on again, etc.
Temperature difference at
the controller too small?
noyes
Wrong position of collector sensors?
no
Plausibility control of
the option evacuated
tube collector function,
antifreeze function
The temperature diffrence between tank and collector increases enormously during operation; the collector circuit
cannot dissipate the heat.
yes
Change ∆Ton and ∆Toff
correspondingly.
o.k.no
Mount the collector sensor at solar flow (warmest collector output);
use immersion sleeve of
the respective collector.
Switch-on temperature
difference ∆Ton to large?
noyes
Wrong position of collector
sensors (e. g. atscrew sensor instead of sensor with
immersion sleeve)?
no
Minimum limitation active
yes
Change ∆Ton and ∆Toff
correspondingly.
Activate evacuated tube
collector function if necessary.
Control the non-return
valve in warm water circulation - o.k.
yesno
Further pumps which are
connected to the solar
tank must also be checked.
noyes
Collector temperature is
at night higher than the
outdoor temperature.
noyes
Sufcient tank insulation?
yesno
Insulation close enough to
the tank?
yesno
Are the tank connections
insulated?
yesno
Warm water outow upwards?
noyes
Does the warm water
circulation run for a very
long time?
noyes
Circulation pump and
blocking valve should be
switched-off for 1 night;
less tank losses?
yesno
a
Check controller
Check the non-return
valve in the ow and the
return pipe with regard to
the functional efciency.
Increase insulation.
Replace insulation or increase it.
Insulate the connections.
Change connection and
let the water flow sidewards or through a siphon
(downwards); less tank
losses now ?
noyes
o.k.
Use the circulation pump
with timer and switch-off
thermostat (energy efcient circulation).
Check whether the pumps
of the backup heating circuit run at night; check
whether the non-return
valve is defective; problem
solved ?
no
The gravitation circulation in the circulation
line is too strong; insert
a stronger valve in the
non-return valve or an
electrical 2-port valve
behind the circulation
pump; the 2-port valve is
open when the pump is
activated, otherwise it is
The solar circuit pump does not work, although the collector is considerably warmer than the tank.
Display illuminated? If not,
press button 5. Display
illuminated now?
yesno
Does the pump start up in
manual operation?
no
Is the pump current
enabled by the controller?
no
yes
yes
Clean or replace it.
closed; connect pump and
2-port valve electrically in
parallel; activate the circulation again. Speed control
has to be deactivated.
There is no current; check
fuses / replace them and
check power supply.
The adjusted temperature
difference for starting the
pump is too high; choose
a value which makes more
sense.
Is the pump stuck?
yes
Turn the pump shaft using
a screwdriver; now passable?