STIEBEL ELTRON SBP 100 Komfort, WPKI-H E, WPKI-P E, WPKI-W E, WPKI-V Operating And Installation Instructions

...
Operating and installatiOn instructiOns
Buffer cylinder with booster heater ange/heat pump compact installation set
» SBP 100 Komfort » sBp-HF » WpK i-H e » WpK i-p e » WpK i-W e » WpK i-V
0
bar
2
4
1
3
65°C
20
0
40
60
80
100
120
°C
20
0
40
60
80
100
120
°C
20
0
40
60
80
100
120
°C
2
Dimensions in mm
Inhalt
1 Operating instructions 3 2 Installation instructions SBP 100 Komfort 3 3
Installation instructions SBF-HF 5
4
Installation instructions WPKI-H E,
WPKI-P E, WPKI-W E 6
5 Installation instructions WPKI-H E
and WPKI-V 10 6 Specification 12 Warranty 13
Environment and recycling 13
26_03_01_0345
280
880
510
562
510
350
45 °
10
26_03_01_0340
min. 2200
8
1
9
5
4
510
2
7
562
510
350
6
3
955
880
280
ca.100
282
756
45 °
52
10
26_03_01_0337
Dimensions in mm
3
2 Installation instructions SBP 100 Komfort for heating contractors
Safety
Intended use
The sealed wall mounted cylinder with 100 l capacity acts as buffer cylinder for heat pumps.
Observe the application limits listed in the chapter „Specification / Data table“.
The appliance is intended for domestic use, i.e. it can be used safely by untrained persons. The appliance can also be used in a non-domestic environment, e.g. in a small business, as long as it is used in the same way.
Any other use beyond that described shall be deemed inappropriate. Observation of these instructions and of instructions for any accessories used is also part of the correct use of this appliance.
Subject to the relevant system, observe the installation instructions of the components of which the system comprises.
WARNING Injury
The appliance may be used by children aged 8 and up and persons with reduced physical, sensory or mental capabilities or a lack of experience provided that they are supervised or they have been instructed on how to use the appliance safely and have understood the resulting risks. Children must never play with the appliance. Children must never clean the appliance or perform user maintenance unless they are supervised.
Equipment description
A buffer cylinder is recommended to ensure trouble-free heat pump operation. In addition, they are designed to separate both heat pump and heating circuit volume flows.
Equipment layout
There are four G 1 ¼” equipment connections at the back of the cylinder, which are
matched to the WPKI- .... heat pump compact
installation set. A G 1/2” connection is provided at the top of the equipment for the air vent valve supplied with the cylinder. At the bottom of the equipment, an aperture is provided for the electric booster heater.
1 Air vent valve 2 G 1 ¼” flow connector heat pump
compact installation set
3 G 1 ¼” return connector heat
pump compact installation set 4 G 1 ¼” heating flow connector 5 G 1 ¼” heating return connector 6 Type plate SBP 100 7 Cleaning aperture 8 Fill & drain valve 9 Panel 10 Connector with sensor well for return
temperature sensor
Special accessories
Heat pump compact installation sets
The heat pump compact installation sets WPKI-P, WPKI-H, WPKI-W and WPKI-V are components of the heat pump system and are specifically designed for the SBP 100 buffer cylinder.
Keep these instructions safely and
pass them on to any new user, should the equipment change hands. Let your contractor check their content in conjunction with any maintenance or repair work.
1 Operating instructions for users and contractors
Safety
Only a qualified contractor should carry out installation, commissioning, maintenance and repair of the appliance.
General safety instructions
We guarantee trouble-free function and operational reliability only if the original accessories and spare parts intended for the appliance are used.
Instructions, standards and regulations
Observe all applicable national and regional regulations and instructions.
Transport and packaging
This wall mounted cylinder can be transported vertically or horizontally.
To prevent cylinder damage, remove the packaging only at the place of
installation.
Place of installation
The installation location should be protected from frost. If the system is not in use at times when a frost is likely, drain the cylinder and all connected systems to prevent damage. The room must be at least 2.2 m high.
Ensure that the wall at the installation location is capable of bearing the full weight of the cylinder. Install the cylinder vertically, as shown in and .
Cylinder installation
Prior to fitting the cylinder to the wall, insert the connector with the sensor well for the return temperature sensor into the cylinder body
-10 and -10. It is recommended that the components in the WPKl set and the respective circulation pump are fitted to the cylinder and hand tightened before the installation. Fit the heat pump compact installation set with circulation pumps (see page 6 section 3 “Installation instructions for accessories WPKI-P, WPKI-H, WPKI-W” and page 11 section 4 “Installation instructions for accessory WPKI-V”.
Fit the wall mounting panel or mounting brackets to the respective wall and hook the cylinder into one or the other fitting.
Observe the gap between the heat pump and the cylinder .
Select fixing materials in accordance with the wall construction/condition.
Fit the air vent valve into the top of the cylinder
-1.
Maintenance
Regularly vent the safety valve until water
streams from it. Close the safety valve after checking.
Commissioning
(only by a qualified contractor)
1. Fill and vent the cylinder.
2. Check the safety valve function.
Water connection
For connector allocation, see equipment layout. Implement the water connections in accordance with the installation drawings in the heat pump installation instructions.
For filling, venting and draining the
system, open the non-return valves of the heat pump compact installation set, i.e. set them to
. Then return them
into position
. The setting screw of the WPKI-H non-return valve is located behind the thermometer.
4
21
8
4
9
7
6 5
2
11
600
710
78.5 110
High limit safety cut-out Controller
1
13
C26_03_01_0336
13
8
10
12
C26_03_01_0339
26_03_01_0342
C26_03_01_0341
D0000035884
20
0
40
60
80
100
120
°C
5
Installing the electric booster heater
SBP-HF Part no. 074252
Instructions and regulations
– DIN VDE 100 – DIN VDE 0701 – Regulations of your local electricity supply
company
– The equipment type plate
The wall mounted cylinder with electric booster heater is only designed for a permanently connected power supply in conjunction with the knock-out cable entry. The equipment must be able to be separated from the mains supply, for example by fuses, which disconnect all poles with at least 3 mm contact separation. Fitting the booster heater flange:
– Open the control chamber lid (
).
– When retrofitting the heater:
Drain the water from the cylinder, release the pipe fittings and remove the
equipment from the wall. – Remove the drain valve (to be re-used). – Remove the flange plate. The semi-shells,
pressure plate and insulating plate will
be re-used. – Install the booster heater flange into the
cylinder ( ), use new gaskets, push on
the insulating plate, position the pressure
plate inside the recess ( -12) of the
plastic casing, and tighten 10 screws
( -4) with 8 Nm. – Fit the drain valve ( -2) with a new
flange gasket and tighten with 20 Nm.
Fit the wiring set: – Fit the component support with 3 screws
( -1).
– Fit the terminals ( -5 and 6).
– Secure the earth strap with a self-tapping
screw (M5) (
-9) on the cylinder tab
( -10).
– Secure the straps in the strap holders
( -8).
– Insert the controller bulbs into the sensor
pipe ( -11) until the limiter clicks into place ( ).
– Push the red plug onto the booster heater
flange.
Mount the cylinder on the wall. Install the heat pump compact installation
set WPKI-...
Fill the cylinder or the complete system with
water.
Power supply preparation
250 mm
26_03_01_0338
Route the power supply cable through the
PG21 fitting of the strain relief ( -7) and connect in accordance with the connection diagram (see wiring diagram ) at the terminal strip ( -5).
Remove the knock-out in the strain relief
( -7) for the control cable from the heat pump manager, and route the control cable via the PG11 fitting into the cylinder. Connect the control cable at the terminal strip ( -6) at terminals 8-9.
Control chamber cover
– Remove the adhesive cover strip. – Affix a new adhesive cover strip and push
firmly down.
– Affix the wiring diagram pad to the
interior of the control chamber cover.
– Undo the controller screws ( -2) from
the support and remove the temperature selector (to be re-used later).
– Position the control chamber cover and
secure with 4 screws.
– Secure the controller to the control
chamber cover with the previously undone screws.
– Push the temperature selector ( -3)
onto the controller axis.
26_03_01_0343
65°C
– Affix the rating plate of the booster heater
flange set on the l.h. side of the casing ( -13) and tick the selected output.
Install the safety valve into the heating flow.
The safety valve must not be able to be
closed towards the cylinder. The blow-off aperture of the safety valve must remain open towards the atmosphere. When using the heat pump compact installation set WPKI-H, the safety valve can be inserted into the threaded hole provided for this purpose in the upper pipe bend (
).
Before and after fitting the control
chamber cover, the contractor must carry out the following checks in accordance with DIN VDE 0701 [or local regulations] after fitting the electric booster heater:
Visual inspection of: – The condition and security of the control
chamber cover, the adhesive strip and
the temperature selector. – Connecting cables. – Strain relief and cable routing. – Cable routing. – Positioning of the capillary tubes from
the temperature controller and the
temperature limiter.
Check the earth connection Check the ionisation resistance Check the system for leaks Check the safety valve function Check the safety labels Function check
Check the heating up and the first
switching of the temperature controller.
26_03_01_0344
3 Installation instructions SBF-HF for heating contractors
Loading...
+ 11 hidden pages