STIEBEL ELTRON WPL E, WPL cool Series, WPL 13 E, WPL 13 cool, 227756 Series Manual

...
CONTENTS
SPECIAL INFORMATION
OPERATION
1. General information �����������������������������������������3
1.1 Relevant documents_____________________________________________ 3
1.2 Safety instructions _______________________________________________ 3
1.3 Other symbols in this documentation _______________________ 4
1.4 Units of measurement __________________________________________ 4
1.5 Standardised output data ______________________________________ 4
2. Safety ���������������������������������������������������������� 4
2.1 Intended use ______________________________________________________ 4
2.2 Safety instructions _______________________________________________ 4
2.3 Test symbols ______________________________________________________ 4
3. Appliance description ���������������������������������������5
3.1 Function ___________________________________________________________ 5
4. Settings �������������������������������������������������������5
5. Maintenance and care ���������������������������������������5
6. Troubleshooting ����������������������������������������������6
7. Safety ���������������������������������������������������������� 7
7.1 General safety instructions ____________________________________ 7
7.2 Instructions, standards and regulations ____________________ 7
7.3 Operation of the appliance in buildings with combustion equipment _________________________________________ 7
8. Appliance description ���������������������������������������7
8.1 Standard delivery ________________________________________________ 7
8.2 Required accessories ___________________________________________ 7
8.3 Additional accessories __________________________________________ 7
9. Preparations �������������������������������������������������� 8
9.1 Sound emissions _________________________________________________ 8
9.2 Minimum clearances ____________________________________________ 8
9.3 Preparation of the installation site ___________________________ 9
9.4 Electrical installation___________________________________________ 10
9.5 Buffer cylinder __________________________________________________ 11
10. Installation �������������������������������������������������� 11
10.1 Transport _________________________________________________________ 11
10.2 Siting and connecting the appliance ________________________ 11
10.3 Heating water connection _____________________________________ 13
10.4 Second heat source_____________________________________________ 13
10.5 Filling the heating system ____________________________________ 14
10.6 Minimum flow rate _____________________________________________ 14
10.7 Condensate drain _______________________________________________ 15
10.8 Checking the draining of condensate _______________________ 16
10.9 High limit safety cut-out for underfloor heating systems ___________________________________________________________ 16
11. Power supply ����������������������������������������������� 16
11.1 Control panel ____________________________________________________ 16
12. Fitting casing components �������������������������������� 18
12.1 Outdoor installation ____________________________________________ 18
12.2 Indoor installation ______________________________________________ 19
13. Commissioning ��������������������������������������������� 21
13.1 Check before commissioning the heat pump manager _21
13.2 Commissioning the heat pump manager __________________ 22
13.3 Initial start-up ___________________________________________________ 22
13.4 Settings ___________________________________________________________ 23
14. Appliance shutdown ��������������������������������������� 23
14.1 Standby mode ___________________________________________________ 23
14.2 Power interruption _____________________________________________ 23
15. Appliance handover ���������������������������������������� 24
16. Troubleshooting �������������������������������������������� 24
16.1 Controls on the IWS ____________________________________________ 24
16.2 Resetting the high limit safety cut-out _____________________ 24
16.3 Fan noise _________________________________________________________ 25
17. Maintenance ������������������������������������������������ 25
17.1 Clean condensate pan and drain ____________________________25
18. Specification ������������������������������������������������ 26
18.1 Dimensions and connections ________________________________ 26
18.2 Wiring diagram _________________________________________________ 28
18.3 Output diagrams ________________________________________________ 30
18.4 Data table ________________________________________________________ 36
GUARANTEE
ENVIRONMENT AND RECYCLING
2 | WPL E | WPL cool www.stiebel-eltron.com
SPECIAL INFORMATION
General information
SPECIAL INFORMATION
- The appliance may be used by children aged8 and older and persons with reduced physical, sensory or mental capabilities or a lack of ex­perience and know-how, provided that they are supervised or they have been instructed on how to use the appliance safely and have understood the potential risks. Children must never play with the appliance. Children must never clean the ap­pliance or perform user maintenance unless they are supervised.
- The connection to the power supply must be in the form of a permanent connection. Ensure the appliance can be separated from the power sup­ply by an isolator that disconnects all poles with at least 3mm contact separation.
- Maintain the minimum clearances to ensure trou­ble-free operation of the appliance and facilitate maintenance work.
OPERATION
1. General information
The chapters "Special information" and "Operation" are intended for both users and qualified contractors.
The chapter "Installation" is intended for qualified contractors.
Note
Read these instructions carefully before using the appli­ance and retain them for future reference. Pass on the instructions to a new user if required.
1.1 Relevant documents
Operating and installation instructions for the WPM heat
pump manager
Operating and installation instructions for system
components
1.2 Safety instructions
1.2.1 Structure of safety instructions
- Maintenance work, such as checking the electri­cal safety, must only be carried out by a qualified contractor.
- We recommend an annual inspection (to establish the current condition of the system), and main­tenance by a qualified contractor if required (to return the system to its original condition).
- Never interrupt the power supply, even outside the heating season. The system's active frost pro­tection is not guaranteed if the power supply is interrupted.
- The heat pump manager automatically switches the heat pump to summer or winter mode.
- If the heat pump is completely switched off and there is a risk of frost, drain the system on the water side.
KEYWORD Type of risk
!
Here, possible consequences are listed that may result from failure to observe the safety instructions.
Steps to prevent the risk are listed.
1.2.2 Symbols, type of risk
Symbol Type of risk
!
1.2.3 Keywords
KEYWORD Meaning
DANGER Failure to observe this information will result in serious
WARNING Failure to observe this information may result in serious
CAUTION Failure to observe this information may result in non-seri-
Injury
Electrocution
injury or death.
injury or death.
ous or minor injury.
www.stiebel-eltron.com WPL E | WPL cool | 3
OPERATION
Safety
1.3 Other symbols in this documentation
Note
General information is identified by the adjacent symbol.
Read these texts carefully.
Symbol Meaning
!
0
Material losses (appliance damage, consequential losses and environmen­tal pollution)
Appliance disposal
:a
This symbol indicates that you have to do something. The ac-
tion you need to take is described step by step.
1.4 Units of measurement
Note
All measurements are given in mm unless stated oth­erwise.
1.5 Standardised output data
Information on determining and interpreting the specified stand­ardised output data.
1.5.1 Standard: EN 14511
The output data specifically mentioned in text, diagrams and technical datasheets has been calculated according to the test conditions of the standard shown in the heading of this section.
Generally, these standardised test conditions will not fully meet the conditions found at the installation site of the system user.
Depending on the chosen test method and the extent to which this method deviates from the conditions defined in the norm shown in the heading of this section, any deviations can have a considerable impact.
Additional factors that have an influence on the test values are the measuring equipment, the system configuration, the age of the system and the flow rates.
A confirmation of the specified output data can only be obtained if the test conducted for this purpose is also performed in ac­cordance with the conditions defined in the norm shown in the heading of this section.
2. Safety
2.1 Intended use
The WPLE appliance is designed for central heating within the application limits given in the specification.
The WPLcool appliance is designed for central heating and cooling within the application limits given in the specification.
The appliance is intended for domestic use. It can be used safely by untrained persons. The appliance can also be used in non-do­mestic environments, e.g. in small businesses, as long as it is used in the same way.
Any other use beyond that described shall be deemed inappro­priate. Observation of this document is also part of the correct use of the unit.
2.2 Safety instructions
Observe the following safety instructions and regulations.
- Only qualified contractors are permitted to carry out electri­cal work and the installation of the heating circuit.
- The qualified contractor is responsible for adherence to all applicable regulations during installation and commissioning.
- The appliance should only be operated once it is fully in­stalled and all safety equipment has been fitted.
- Protect the appliance from dust and dirt during building work.
WARNING Injury
!
The appliance may be used by children over 8years of age and persons with reduced physical, sensory or men­tal capabilities or a lack of experience and expertise, provided that they are supervised or they have been instructed on how to use the appliance safely and have understood the potential risks. Children must never play with the appliance. Children must never clean the ap­pliance or perform user maintenance unless they are supervised.
WARNING Injury
!
For safety reasons, only operate the appliance with
the casing closed.
2.3 Test symbols
See type plate on the appliance.
4 | WPL E | WPL cool www.stiebel-eltron.com
OPERATION
Appliance description
3. Appliance description
The appliance is an air | water heat pump that oper­ates as a heating heat pump. The appliance extracts heat from the outdoor air at a low temperature level and trans­fers it to the heating water at a higher temperature level. The heating water can be heated up to a flow temperature of 60 °C.
With the appropriate accessories, this appliance may be installed internally or externally.
The appliance is equipped with an electric emergency/booster heater (DHC). If the dual mode point is undershot in mono mode operation, the electric emergency/booster heater is activated to safeguard heating operation and the provision of high DHW tem­peratures. In such a case in mono energetic operation, the electric emergency/booster heater is activated as a booster heater.
Additional features
- Suitable for underfloor and radiator heating systems
- Preferred for low temperature heating systems
- Still extracts heat from the outdoor air at – 20°C outside temperature
- Corrosion-protected, external casing made from hot-dipped galvanised sheet steel plus stove-enamelled finish
- Comprises all components and safety equipment required for operation
- Filled with non-combustible safety refrigerant
3.1.2 Cooling (WPLcool only)
Material losses
!
The heat pump is not suitable for continuous, year-round
0
cooling.
Observe the application limits (see chapter "Specifi-
cation/ Data table").
Rooms are cooled by reversing the heat pump circuit. Heat is extracted from the heating water and the evaporator transfers this heat to the outdoor air.
Area cooling requires the installation of the FEK remote control unit in a reference room to capture the relative humidity and the room temperature as part of dew point monitoring.
Heat pump application limit
The heat pump is switched off if the outside temperature falls below the selected lower application limit for cooling (LIMITCOOL­ING parameter).
4. Settings
The appliance is controlled with the heat pump manager and re­quires no special operation.
Please observe the heat pump manager operating and instal-
lation instructions.
Note
To control the heating system, you will need the WPM heat pump manager.
=
[]]
:_______
3.1 Function
3.1.1 Heating
Heat is extracted from the outdoor air via the heat exchanger (evaporator) on the air side. The refrigerant evaporates and is compressed by a compressor. This process requires electrical energy.
The refrigerant is then at a higher temperature level and transfers the heat drawn from the air to the heating system via an additional heat exchanger (condenser). The refrigerant then expands and the cycle begins again.
At air temperatures below approx. 7°C, the humidity in the air condenses as hoarfrost on the evaporator fins. This hoarfrost is automatically defrosted. Water created by this defrosting process collects in the defrost pan and is drained off via a hose.
During the defrost cycle, the fan is switched off and the heat pump circuit is reversed. The heat required for defrosting is drawn from the buffer cylinder. The heat pump automatically reverts to heating mode at the end of the defrost cycle.
5. Maintenance and care
Material losses
!
Maintenance work, such as checking the electrical safety,
0
[]]
A damp cloth is sufficient for cleaning all plastic and sheet metal parts. Never use abrasive or corrosive cleaning agents.
Protect the appliance from dust and dirt during building
Every month, check that the condensate drain is working
We recommend a regular inspection (to establish the current con­dition of the system), and maintenance by a qualified contractor if required (to return the system to its original condition).
~~~~
must only be carried out by a qualified contractor.
Note
Keep the air discharge and intake apertures free
from snow and leaves.
work.
correctly (visual inspection). When doing so, check for water collecting below or next to the appliance. For further infor­mation, see chapter "Troubleshooting".
Material losses
!
In dual mode operation, return water from the second
0
heat generator may flow through the heat pump. Please note that the return temperature must be no higher than 60 °C.
www.stiebel-eltron.com WPL E | WPL cool | 5
OPERATION
Troubleshooting
6. Troubleshooting
Fault Cause Remedy
There is no hot water or the heating system remains cold.
Water is leaking from the appli­ance.
Indoor installa­tion: Condensate is collecting on the outside of the appliance or on the air hoses.
Outdoor installa­tion: Condensate is collecting on the outside of the appliance.
No power at the appli­ance.
The condensate drain may be blocked.
The drying out phase of the building is not yet complete.
The relative humidity in the air is high (≥60%).
The appliance is sited in a damp room. Damp rooms are those where humidity in the air is high. They may, for ex­ample, be used for drying laundry.
The air hoses are incor­rectly fitted or poorly sealed. Cold air is escaping.
The heat pump is extract­ing heat from the outdoor air to heat the building. This can cause the hu­midity in the outdoor air to accumulate as dew or frost on the cooled heat pump casing. This is not a defect.
Check the fuses/MCBs in your distribution board. Replace the fuses/reset the MCBs if required. Notify your qualified contractor if the fuses/MCBs blow/trip again.
Call your contractor to have the condensate drain cleaned out.
This condensate should no longer form on the appliance after the house is approx.two years old, providing the room is sufficiently well ventilated and dehumidified.
A change in weather conditions should no longer cause conden­sation to form on the appliance.
Ensure that the room is ade­quately ventilated and dehumid­ified. If necessary, hang your laundry in a different room. Use a vented tumble dryer. Please note that condenser tum­ble dryers do not reduce the level of humidity in the air.
Check that the air hoses are correctly fitted and sealed. If necessary, contact your qualified contractor.
Note
Even when the condensate is draining away correctly, expect water to drip from the appliance onto the floor.
If you cannot remedy the fault, notify your qualified contractor. To facilitate and speed up your enquiry, please provide the serial number from the type plate (000000-0000-000000).
Sample type plate
Montageanweisung beachten! Dichtheit geprüft!
Made in Germany
*xxxxxxxxxxxxxxxxxx*
1(
-
1
1 Number on the type plate
26_03_01_1736
6 | WPL E | WPL cool www.stiebel-eltron.com
INSTALL ATION
Safety
INSTALLATION
7. Safety
Only a qualified contractor should carry out installation, commis­sioning, maintenance and repair of the appliance.
7.1 General safety instructions
We guarantee trouble-free function and operational reliability only if original accessories and spare parts intended for the appliance are used.
8.1.2 Casing components – outdoor installation
- Hood – outdoor installation
- Front panel
- Back panel
- Pipe bend for heating circuit flow
- Pipe bend for heating circuit return
8.1.3 Casing components for indoor installation
- Cover - indoor installation
- Front panel
- Back panel
- Pipe bend for heating circuit return
7.2 Instructions, standards and regulations
Note
Observe all applicable national and regional regulations and instructions.
7.3 Operation of the appliance in buildings with combustion equipment
As the appliance can produce negative pressure in the installation room, we recommend using a tightly sealing door between the installation room and the living space for operation with com­bustion equipment.
If, due to its use, the installation room is connected to the ex­tract air system, you must also allow for a supply air valve in the installation room in this particular case to prevent any further increase in the negative pressure in the installation room. The negative pressure created by the appliance in the installation room is heavily influenced by the pressure drop in the outdoor air line. For this reason, the outdoor air line in particular should be as short as possible.
8. Appliance description
For outdoor installation the appliance offers additional frost pro­tection of the heating water pipes. The integral frost protection circuit starts the heating circulation pump in the heat pump circuit automatically at +8°C condenser temperature, and in doing so ensures circulation in all water-filled sections.
The heat pump starts automatically when the temperature in the heat pump circuit drops below +5°C.
8.1 Standard delivery
The casing components for the appliance are delivered in a sep­arate packing unit.
8.1.1 Standard appliance
- Type plate
8.2 Required accessories
8.2.1 Outdoor installation
- WPM3 heat pump manager
- Accessories – outdoor installation
- Pressure hoses SD25 or SD32
8.2.2 Indoor installation
- WPM3 heat pump manager
- Accessories – indoor installation
- Pressure hoses SD25 or SD32
8.2.3 Cooling
- Remote control for heating systems FEK
8.3 Additional accessories
8.3.1 Outdoor installation
- Remote control for FE7 heating systems
- Water softening fitting HZEA
- SP cool distributor strip
- Internet Service Gateway ISG
8.3.2 Indoor installation
- Air hose DN 560 x 4 m
- Hose connection panel 560
- Wall outlet AWG 560 H-SR
- Wall outlet AWG 560 H-GL
- Wall outlet AWG 560 V-SR
- Wall outlet AWG 560 V-GL
- Wall outlet AWG 560 L
- Wall outlet AWG 600 L
- Remote control for FE7 heating systems
- Condensate pump PK 10
- Water softening fitting HZEA
- SP cool distributor strip
- Internet Service Gateway ISG
www.stiebel-eltron.com WPL E | WPL cool | 7
INSTALL ATION
Preparations
9. Preparations
9.1 Sound emissions
The appliance is louder on the air intake and air discharge sides than on the two enclosed sides. Take the following information into account when selecting the installation location.
Note
For details regarding the sound power level, see chapter "Specification / Data table".
9.1.1 Sound emissions for outdoor installation
- Lawn areas and shrubs help reduce the spread of noise.
- Noise propagation can also be reduced through dense pali­sades or similar.
Ensure that the entire appliance frame is in full contact
with the substrate. Uneven substrates can increase sound emissions.
Ensure that the air intake direction is the same as the dom-
inant wind direction. Air should not be drawn in against the wind.
Ensure that the air intake and air discharge are never direct-
ed towards noise-sensitive rooms of the house, e.g. bed­rooms, or neighbouring houses.
Avoid installation on large, echoing floor areas, e.g. tiled
floors.
Avoid installation between reflective building walls. Reflect-
ing building walls can increase the noise level.
9.2 Minimum clearances
9.2.1 Outdoor installation
≥700
\
≥500
Maintain the minimum clearances to ensure trouble-free op-
eration of the appliance and facilitate maintenance work.
Never install the appliance in a recess. Two sides of the ap-
pliance must remain exposed.
In order to prevent air "short circuits", maintain the minimum
clearances in the case of surrounding structures and in par­ticular in the case of cascades. Maintain the flow rate on the heat source side (see chapter "Specification / data table").
≥2000
≥500
≥1000
D0000019241
91_00_00_0036
9.1.2 Sound emissions for indoor installation
- Never install on joists.
Ensure that the entire appliance frame is in full contact
with the substrate. Uneven substrates can increase sound emissions.
Never install the appliance directly below or next to a living
room or bedroom.
Never direct the air intake and discharge apertures in exter-
nal walls towards neighbouring windows or living rooms/ bedrooms.
Protect pipe outlets through walls and ceilings with anti-vi-
bration insulation.
Material losses
!
Please note that both the flow of outdoor air into the
0
appliance, and the flow of exhaust air from the appliance must be unimpeded. If the air intake and discharge of the appliance are ob­structed by surrounding objects, this may cause a thermal short-circuit.
Ensure that the appliance is not fully enclosed by objects
such as buildings, walls or fences.
If the air discharge side of the appliance faces the wall of a house, the cool air from the air discharge may cause condensate to form on this wall.
Material losses
!
The air flow rate through the appliance must not fall
0
below the minimum level. If the air flow rate falls below the minimum level, trouble-free operation of the appli­ance is not guaranteed.
Ensure that the minimum air flow rate is maintained
(see chapter “Specification/ Data table”).
8 | WPL E | WPL cool www.stiebel-eltron.com
INSTALL ATION
1
6
Preparations
9.2.2 Indoor installation
≥500
1//////////f'///////P
≥300
≥500
0 0
I
≥1000
Maintain the minimum clearances to ensure trouble-free op-
eration of the appliance and facilitate maintenance work.
≥500
I
9.3 Preparation of the installation site
9.3.1 Outdoor installation
Provide a recess (space) in the base to enable supply pipes/
cables to be routed into the appliance from below.
Foundations with recess
1240
260 70
r-----
4
L_f~i
d01d02
...,.
____
-
0 0 0 0
2
1 Air discharge 2 Air intake
D0000019242
3 Main wind direction 4 Recess d01 Heat pump flow d02 Heat pump return
Ensure that the foundations offer an adequate recess.
I
_J
3
50
130
800
D0000056558
General information
See chapter "Sound emissions".Ensure that the appliance is accessible from all sides.Ensure that the substrate is level, even, solid and permanent.
Example: Routing pipes in the base
4
3
5
A Depth of frost line 1 Heating circuit flow 2 Heating circuit return 3 Conduit for supply lines/cables 4 Foundation 5 Gravel bed 6 Drainage pipe 7 Condensate drain hose 8 Electrical cables/leads
8
A
1 2
7
D0000019237
www.stiebel-eltron.com WPL E | WPL cool | 9
INSTALL ATION
Preparations
Observe the following information:
- Also protect all supply lines/cables against humidity, damage and UV radiation by means of a conduit.
- Allow the conduits for the supply lines to protrude slightly above the foundations. Ensure that no water can enter the conduits.
- To facilitate connection to the appliance, we recommend using flexible supply pipes/cables in the case of outdoor installation.
- Only use weather-resistant cables.
- Protect the heating circuit flow and return lines against frost with sufficient thermal insulation. Provide thermal insulation in accordance with applicable regulations.
Note
When routing the condensate drain hose, observe chapter "Installation / Condensate drain".
9.3.2 Indoor installation
Material losses
!
The installation room floor must be water resistant. Dur-
0
ing appliance operation, the outdoor air releases up to 50l of condensate per day. If humidity levels in the in­stallation room are high, condensate may form on the appliance and air hoses. If the condensate drain is not installed correctly or if maintenance is not carried out properly, water may escape. We recommend installing a drain in the installation room floor.
The room where the appliance is installed must meet the following conditions:
- free from the risk of frost
- The room must not be subject to a risk of explosions arising from dust, gases or vapours.
- If installing the appliance in a plant room together with other heating equipment, ensure that the operation of other heat­ing equipment will not be compromised.
- Minimum volume of the installation room. The minimum volume of the installation room is assured if the minimum clearances are observed.
- Load bearing floor (for the weight of the appliance, see chap­ter "Specification/ Data table").
For installation on floating screeds, make provisions for quiet
heat pump operation.
-----
/
1 2 3 54
1 Concrete base 2 Impact sound insulation 3 Floating screed 4 Floor covering 5 Recess
Isolate the installation surface around the heat pump by
means of a recess. After completing the installation, seal the recess with a water-impervious and sound insulating materi­al, such as silicone for example.
Observe the following information:
- Connect the heating circuit flow and return lines via flexible pressure hoses. Suitable pressure hoses are listed in chap­ter "Appliance description / Required accessories for indoor installation".
Note
For details of the dimensions and positions of the air intake and discharge apertures, as well as the outlets for hydraulic lines and power cables, see chapter "Specifica­tion / Dimensions and connections / indoor installation".
9.4 Electrical installation
WARNING Electrocution Carry out all electrical connection and installation work
&
in accordance with national and regional regulations.
-_-_-_-_-_-_-_-_-_-_-_-_-_-_-_-_-_-_-_-_-_-_-_-_-_-_-_-_----:::::::
WARNING Electrocution Only use a permanent connection to the power supply.
&
Ensure the appliance can be separated from the power supply by an isolator that disconnects all poles with at least 3mm contact separation. This requirement can be met with contactors, circuit breakers, fuses/MCBs, etc.
-----
26_03_01_1466
Note
The specified voltage must match the mains voltage.
Observe the type plate.
For wiring, use cable with the relevant cross-sections. Ob-
serve the applicable national and regional regulations.
MCB/fuse rating
16 A
-
10 | WPL E | WPL cool www.stiebel-eltron.com
Conductor cross-section
2.5 mm²
1.5 mm² for only two live wires and routing on a wall or in an electrical conduit on a wall.
INSTALL ATION
Installation
The electrical data can be found in the chapter "Specification". The bus requires a J-Y (St) 2x2x0.8mm² cable.
====----
Material losses
!
Provide separate fuses/MCBs for the three power circuits, i.e. those of the appliance, the control unit and the elec­tricemergency/booster heater.
0
::::::::::C---=~==::;;::::::====:::::::::=---=--~
Material losses
!
Provide common fuses/MCBs for the control cable of the appliance and the heat pump manager.
o
9.5 Buffer cylinder
The installation of a buffer cylinder is essential to ensure trou­ble-free operation of the appliance.
The buffer cylinder provides hydraulic separation of the volume flows in the heat pump circuit and heating circuit, and also serves as an energy source for defrosting.
0
====----
Material losses
!
A buffer cylinder with diffusion-proof insulation is essen­tial for cooling mode.
--====
10.2 Siting and connecting the appliance
Note
ill]
- Two screws are available at the top of the appliance frame to secure the cover.
- At the bottom of the frame, one screw is available on each side to secure the side panels.
Wind the sixscrews out of the appliance frame and keep
them safe.
WPLcool
Material losses
!
With these appliances, the heating circuit flow and re-
0
turn lines must be insulated with vapour diffusion-proof material.
10.2.1 Outdoor installation
10. Installation
10.1 Transport
When transporting the appliance, be aware of its centre of
gravity.
- The centre of gravity is in the area where the compressor is located.
- Lifting slings for handling the standard appliance can be hooked in anywhere on the bottom of the frame.
Protect the appliance against heavy impact during transport.
- If the appliance needs to be tilted during transport, this must only be for a short time and it must only be titled on one of its longitudinal sides. When transporting the appliance, en­sure the compressor is on the upper appliance side.
- The longer the appliance is tilted, the greater the distribution of refrigerant oil in the system.
Wait approximately 30minutes before starting the appliance
after it has been tilted.
1
26_03_01_1727_
1 Knock-out "supply line entry"
Remove the knock-out "supply line entry" in the bottom of
the appliance.
Position the standard appliance on the prepared substrate. Observe minimum clearances (see chapter "Preparations/
Minimum clearances").
D0000071298
www.stiebel-eltron.com WPL E | WPL cool | 11
INSTALL ATION
Installation
1
2
3
5
6
1 Pipe bend for heating circuit flow 2 Pipe bend for heating circuit return 3 Cable duct 4 Condensate drain hose 5 Concrete foundation 6 Coarse gravel back filling
Fit the pipe bends "heating circuit flow" and "heating circuit
return".
Route the supply pipes/cables from below through the knock-
out in the bottom and into the appliance.
Route the electrical cables in a cable duct.
4
10.2.2 Indoor installation
Position the standard appliance on the prepared substrate.Pay attention to the air discharge direction.Place the casing cover on the appliance and secure with two
screws.
6
5
4
3
1 "Heating flow" connection 2 "Heating return" connection 3 BUS cable 4 Control cable
26_03_01_0958_
5 Electric emergency/booster heater power cable 6 Appliance power cable
In the cover, cut out the pipe outlets for the "heating flow"
and "heating return" connections.
Route the pressure hoses from above through the cover and
into the appliance.
Route the electrical cables from above through the cable en-
tries and into the appliance.
With the indoor installation, rotate the connector for the "heating flow" connection through approx.145°.
1
2
26_03_01_0170
Material losses
!
Rodents may get into the appliance through the knock-
0
out aperture.
Close off the knock-out aperture.
12 | WPL E | WPL cool www.stiebel-eltron.com
INSTALL ATION
Installation
/
/
I
\
1 Connector 2 Union nut
Loosen the union nut.Rotate the connector.Retighten the union nut.
c
=:,,
dl,.<i;
~
1
10.3 Heating water connection
2
j
Structure-borne noise is largely prevented by the anti-vibration construction of the heat pump and by the flexible pressure hoses, which act as anti-vibration mounts.
26_03_01_0947_
10.3.1 Oxygen diffusion
Material losses
!
The heating system to which the heat pump is connected
0
must be installed by a qualified contractor in accordance with the water installation drawings that are part of the technical guides.
Before connecting the heat pump, flush the pipework thor-
oughly with suitable water. Foreign bodies, such as rust, sand or sealant can impair the operational reliability of the heat pump.
Connect the heat pump on the heating water side. Check for
tightness.
Connect the flexible pressure hoses to the connectors. The
pressure hoses must be at least 1 metre long.
Ensure that the heating flow and return are connected
correctly.
Provide thermal insulation in accordance with applicable
regulations.
When sizing the heating circuit, observe the internal pressure
differential (see chapter "Specification / Data table").
Material losses
!
Avoid open vented heating systems and underfloor heat-
0
ing systems with plastic pipes which are permeable to oxygen.
1
1 Pipe bend for heating circuit return
Fit the "heating circuit return" pipe bend.
In underfloor heating systems with plastic pipes that are per­meable to oxygen and in open vented heating systems, oxygen diffusion may lead to corrosion on the steel components of the heating system (e.g.on the indirect coil of the DHW cylinder, on buffer cylinders, steel radiators or steel pipes).
With heating systems that are permeable to oxygen, separate
the heating system between the heating circuit and the buff­er cylinder.
Material losses
!
The products of corrosion (e.g.rusty sludge) can set-
0
tle in the heating system components, which may re­sult in a lower output or fault shutdowns due to reduced cross-sections.
10.4 Second heat source
For dual mode systems, always connect the heat pump into the return of the second external heat source, e.g. oil boiler.
26_03_01_0173_
www.stiebel-eltron.com WPL E | WPL cool | 13
Loading...
+ 27 hidden pages