Sterling QVEB User Manual

INSTALLATION INSTRUCTIONS & PARTS LIST
POWER VENTED GAS FIRED BLOWER UNIT HEATERS
ATTENTION: READ THIS MANUAL AND ALL LABELS ATTACHED TO THE UNIT CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THESE UNITS! CHECK UNIT DATA PLATE FOR TYPE OF GAS AND ELECTRICAL SPECIFICATIONS AND MAKE CERTAIN THAT THESE AGREE WITH THOSE AT POINT OF INSTALLATION. RECORD THE UNIT MODEL AND SERIAL No.(s) IN THE SPACE PROVIDED. RETAIN FOR FUTURE REFERENCE.
IIEB-11
J30-05390
Model No.
Serial No.
FOR Y OUR SAFETY
R
T
E
E
K
T
N
I
FOR Y OUR SAFETY
If you smell gas:
1. Open windows.
2. Don’t touch electrical switches.
3. Extinguish any open fl ame.
V
D
E
E
R
I
I
F
ENERGY
PERFORMANCE
CM
VERIFIED
RENDEMENT
ENERGETIQUE
VERIFIE
4. Immediately call your gas supplier.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment
APPROVED FOR USE IN CALIFORNIA
Install, operate and maintain unit in accordance with manufacturer's instructions to avoid exposure to fuel substances or substances from incomplete combustion which can cause death or serious illness. The state of California has determined that these substances may cause cancer, birth defects, or other reproductive harm.
08/12
INSTALLER'S RESPONSIBILITY
Installer Please Note: This equipment has been test fired and inspected. It has been
shipped free from defects from our factory. However, dur ing shipment and installation, problems such as loose wires, leaks or loose fasteners may occur. It is the installer's
responsibility to inspect and correct any problems that may be found.
RECEIVING INSTRUCTIONS
Inspect shipment immediately when received to determine if any damage has occurred to the unit during shipment. After the unit has been uncrated, check for any visible damage to the unit. If an y damage is found, the consignee should sign the bill of lading indicating such damage and immediately file claim for damage with the transportation company.
260 NORTH ELM ST., WESTFIELD, MA 01085
TEL: (413) 568-9571 FAX: (413) 562-8437
www.mestek.com
TABLE OF CONTENTS
SPECIFICATIONS
Basic Description ....................................................2
Performance & Specifi cation Data ..........................4
GENERAL SAFETY INFORMATION
Installation Codes ...............................................2, 3
Special Precautions ............................................2, 3
INSTALLATION
Locating Units .....................................................5, 6
Proper Clearances ..............................................5, 6
Suspension of Units ............................................5, 6
Air for Combustion .................................................6
Gas Supply Piping/Sizing .......................................7
Pipe Installation .....................................................8
Blower Set-up and Adjustment ........................9, 10
DESCRIPTION
The Power Vented Gas Blower Unit Heater is a factory assembled, high static pressure type, centrifugal blower unit designed for heavy duty applications such as continuous operation or where a single unit heater must do the entire heating job in a large area. These blower type unit heaters may be used with the standard adjustable louvers or with short duct runs
ELECTRICAL CONNECTIONS ................................11
VENTING .................................................12, 13, 14, 15
OPERATION
Spark Ignition ..................................................16, 17
Main Burner Orifi ce Schedule ...............................18
Adjustments ..........................................................18
MAINTENANCE
Servicing & Cleaning ............................................19
TROUBLESHOOTING GUIDE ...............20, 21, 22, 23
IDENTIFICATION OF PARTS ........................24, 25, 26
Replacement Parts ...............................................27
WARRANTY ..............................................................27
INSPECTION SHEET ................................................28
UNIT NUMBER DESCRIPTION ................................29
and discharge nozzles for spot heating. These blower type unit heaters may be used where low sound levels ar e r e q ui r e d. The designs are certified by ETL as providing a minimum of 80% thermal efficiency, and approved for use in California. Do not alter these units in any way. If you have any questions after reading this manual, contact the manufacturer.
Figure 1 - Power Vented Blower Unit Heaters
Front View
The following terms are used throughout this manual, in addition to ETL requirements, to bring attention to the presence of potential hazards or to important information concerning the product:
See Identifi cation of Parts Section
for unit components.
Rear View
Indicates an imminently hazardous situation which, if not av oided, will result in death, serious injury or substantial property damage.
Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial property damage.
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or property damage.
NOTICE: Used to notify of special instructions on installation, operation or maintenance which are important to equipment but not related to personal injury hazards.
2
GENERAL SAFETY INFORMATION
Failure to comply with the general safety information may result in extensive property damage, severe personal injury or death.
This pr oduct must be installed b y a licensed plumber or gas fi tter when installed within the Commonwealth of Massachusetts.
Installation must be made in accordance with local codes, or in absence of local codes, with the latest edition of ANSI Standard Z223.1 (N.F.P.A. No.54) National Fuel Gas Code. All of the ANSI
and NFPA Standards referred to in these installation instructions are those that were applicable at the time the design of this appliance was certified. The ANSI Standards are available from the American National Standards Institute, Inc., www.ansi.org. The NFPA Standards are available from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. These unit heaters are designed for use in airplane hangars when installed in accordance with ANSI/NFPA No. 409 and in public garages when installed in accordance with NFP A No . 88A and NFP A No . 88B.
If installed in Canada, the installation must conform with local building codes, or in absence of local building codes, with CSA-B149.1 “Installation Codes for Natural Gas Burning Appliances and Equipment" or CSA-B149.2 “Installation Codes for Propane Gas Burning Appliances and Equipment”. These Unit Heaters hav e been designed and certifi ed to comply with CSA 2.6. Also see sections on installation in AIRCRAFT HANGARS and PUBLIC GARAGES.
Use only the fuel for which the heater is designed (see rating plate). Using LP gas in a heater that requires natural gas, or vice versa, will create the risk of gas leaks, carbon monoxide poisoning and explosion.
Do not attempt to convert the heater for use with a fuel other than the one intended. Such conversion is dangerous, as it will create the risks listed previously.
Make certain that the power source conforms to the electrical requirements of the heater.
Do not depend upon a thermostat or other switch as sole means of disconnecting power when installing or servicing heater. Always disconnect power at main circuit breaker as described above. Failure to do so could result in fatal electric shock.
Special attention must be given to any grounding information pertaining to this heater. To prevent the risk of electrocution, the heater must be securely and adequately grounded. This should be accomplished by connecting a grounded conductor between the service panel and the heater. To ensure a proper ground, the grounding means must be tested by a qualifi ed electrician.
Do not insert fi ngers or foreign objects into the heater or its air moving device. Do not block or tamper with the heater in any manner while in operation or just after it has been turned off, as some parts may be hot enough to cause injury .
Do not alter the unit heater in any way or damage to the unit and/or severe personal injury or death may occur!
Disconnect all power and gas supplies before installing or servicing the heater . If the power disconnect is out of sight, lock it in the open position and tag it to prevent unexpected application of power. Failure to do so could result in fatal electric shock, or severe personal injury.
Ensure that all power sources conform to the requirements of the unit heater or damage to the unit will result!
Follow installation instructions CAREFULLY to avoid creating unsafe conditions. All wiring should be done and checked by a qualified electrician, using copper wire only. All gas connections should be made and leak­tested by a suitably qualifi ed individual, per instructions in this manual. Also follow procedures listed on the “Gas Equipment Start-Up Sheet” located in this manual.
This heater is intended for general heating applications ONLY. It must NOT be used in potentially dangerous locations such as fl ammable, explosive, chemical-laden or wet atmospheres.
In cases in which property damage may result from malfunction of the heater, a backup system or a temperature sensitive alarm should be used.
The open end of piping systems being purged shall not discharge into areas where there are sources of ignition or into confi ned spaces UNLESS precautions are taken as follows: (1) by ventilation of the space, (2) control of purging rate, (3) elimination of all hazardous conditions. All precautions m ust be taken to perform this operation in a safe manner!
Unless otherwise specifi ed, the following conversions may be used for calculating SI unit measurements: 1 foot = 0.305 m 1 inch = 25.4 mm 1 psig = 6.894 kPa 1 pound = 0.453 kg 1 gallon = 3.785 L 1 cubic foot = 0.028 m
1 inch water column = 0.249 kPa 1000 Btu/Cu. Ft. = 37.5 MJ/m
3
1000 Btu per hour = 0.293 kW liter/second = CFM x 0.472 meter/second = FPM ÷ 196.8
3
3
T able 1 – Perf ormance and Dimensional Data – Power V ented Blower Unit Heater
Unit Size 100 125 150 175 200 225 250 300 350 400 PERFORMANCE DATA ‡
Input BTU/Hr 100,000 125,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000 (kW) (29.3) (36.6) (43.9) (51.2) (58.6) (65.9) (73.2) (87.8) (102.5) (117.1) Output BTU/Hr 80,000 100,000 120,000 140,000 160,000 180,000 200,000 240,000 280,000 320,000 (kW) (23.4) (29.3) (35.1) (41.0) (46.9) (52.7) (58.6) (70.3) (82.0) (93.7) Thermal Effi ciency (%) 80 80 80 80 80 80 80 80 80 80 Free Air Delivery CFM 1,200 1,575 1,975 2,300 2,400 2,600 2,850 3,950 4,600 4,800 (cu. m/s) (0.566) (0.743) (0.932) (1.086) (1.133) (1.227) (1.345) (1.864) (2.171) (2.266) Air Temperature Rise F Deg. 62 59 56 56 62 64 65 56 56 62 (C Deg.) (34) (33) (31) (31) (34) (36) (36) (31) (31) (34) Outlet Velocity FPM 880 950 1,030 1,045 965 935 930 1,080 1,090 1,000 (m/s) (4.47) (4.83) (5.23) (5.31) (4.90) (4.75) (4.72) (5.49) (5.54) (5.08) Full Load Amps at 115V 8.3 9.8 10.6 10.6 15.2 15.2 15.2 15.2 18.6 18.6 MOTOR DATA : Motor HP 1/4 1/3 1/2 1/2 3/4 3/4 3/4 3/4 1 1 Motor (kW) (0.19) (0.25) (0.37) (0.37) (0.56) (0.56) (0.56) (0.56) (0.75) (0.75) Motor Type SPH SPH SPH SPH SPH SPH SPH SPH cap.start cap.start R.P.M. 1,725 1,725 1,725 1,725 1,725 1,725 1,725 1,725 1,725 1,725 Amps @ 115V 5.1 6.6 7.4 7.4 12.0 12.0 12.0 12.0 15.4 15.4 DIMENSIONAL DATA in. (mm) “A” Height to Top of Unit 31-1/4 31-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4 (794) (794) (921) (921) (921) (921) (921) (921) (921) (921) “B” Width of Unit 17-7/8 20-5/8 20-5/8 23-3/8 26-1/8 28-7/8 31-5/8 37-1/8 42-5/8 48-1/8 (454) (524) (524) (594) (664) (733) (803) (943) (1083) (1222) “C” Height to Top of Hanger 34-1/8 34-1/8 39-1/8 39-1/8 39-1/8 39-1/8 39-1/8 39-1/8 39-1/8 39-1/8 (867) (867) (994) (994) (994) (994) (994) (994) (994) (994) “D” Depth to Rear of Housing 42-5/8 44-1/4 44-1/4 47 47 51 51 48-1/4 51 51 (1083) (1124) (1124) (1194) (1194) (1295) (1295) (1226) (1295) (1295) “E” Hanging Distance Width 14-1/2 17-1/4 17-1/4 20 22-3/4 25-1/2 28-1/4 33-3/4 39-1/4 44-3/4 (368) (438) (438) (508) (578) (648) (718) (857) (997) (1137) “F” Discharge Opening Width 15-3/8 18-1/8 18-1/8 20-7/8 23-5/8 26-3/8 29-1/8 34-5/8 40-1/8 45-5/8 (391) (460) (460) (530) (600) (670) (740) (879) (1019) (1159) “J” to Centerline of Flue 5-7/8 7-1/4 7-1/4 8-5/8 10 11-1/4 12-3/4 15-1/2 18-1/4 21 (149) (184) (184) (219) (254) (286) (324) (394) (464) (533) “L” Hanger Location 16-3/8 16-3/8 16-3/8 16-3/8 16-3/8 16-3/8 16-3/8 16-3/8 16-3/8 16-3/8 (416) (416) (416) (416) (416) (416) (416) (416) (416) (416) “M” Hanging Distance Depth 16-3/8 16-3/8 16-3/8 17-7/8 17-7/8 21-7/8 21-7/8 21-7/8 21-7/8 21-7/8 (416) (416) (416) (454) (454) (556) (556) (556) (556) (556) Flue Size Dia-in. * 4 4 4 4 5 5 5 6 6 6 (Dia-mm) (102) (102) (102) (102) (127) (127) (127) (152) (152) (152) Blower Size-in. 9 10 10 12 12 12 12 (2) 10 (2) 12 (2) 12 Gas Inlet-Natural Gas-in. 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4 Gas Inlet-LP Gas-in. 1/2 1/2 1/2 1/2 1/2 1/2 OR 3/4 Approx. Shipping Wt. lb. 262 279 314 336 363 408 427 471 561 594 (kg) (119) (127) (142) (152) (165) (185) (194) (214) (254) (269)
‡ Ratings shown are for unit installations at elevations between 0 and 2000 ft. (610m). For installations in USA above 2000 ft. (610m), the unit input must be derated 4% for each 1000 ft. (305m) above
sea level; refer to local codes, or in absence of local codes, refer to the latest edition of the National Fuel Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54).
For installations in Canada, any references to deration at altitudes of 2000 ft. (610m) are to be ignored. At altitudes of 2000 to 4500 ft. (610 to 1372m), the unit must be derated to 90% of the normal
altitude rating, and be so marked in accordance with the ETL certifi cation.
LEGEND: SPH = SPLIT PHASE CAP. START = CAPACITOR START
Figure 2 ­Unit Dimensions
DIMENSIONS .XXX STANDARD UNITS DIMENSIONS IN PARENTHESIS (XXX) MILLIMETERS
4
INSTALLATION
Do not install unit heaters in corrosive or fl ammable atmospheres! Premature failure of, or severe dama ge to the unit will result!
Avoid locations where extreme drafts can affect burner operation. Unit heaters must not be installed in locations where air for combustion would contain chlorinated, halogenated or acidic vapors. If located in such an environment, premature failure of the unit will occur!
Since the unit is equipped with an automatic gas ignition system, the unit heater must be installed such that the gas ignition control system is not directly exposed to water spray, rain or dripping water.
NOTE: Location of unit heaters is related directly to the selection of sizes. Basic rules are as follows:
MOUNTING HEIGHT: Unit Heaters must be installed at
a minimum of 8 feet (2.4m) above the fl oor, measured to the bottom of the unit. At heights above 8 feet (2.4m), less effi cient air distribution will result. Occasionally unit heaters must be mounted at heights of 12 to 16 feet (3.7 to 4.9m) in order to clear obstacles. When this is the case, it is advisable to use centrifugal blower unit heaters.
AIRCRAFT HANGARS: Unit Heaters must be installed in aircraft hangars and public garages as follows: In aircraft hangars, unit heaters must be at least 10 feet (3.05m) above the upper surface of wings or engine enclosures of the highest aircraft to be stored in the hangar and 8 feet (2.44m) above the fl oor in shops, offi ces and other sections of the hangar where aircraft are not stored or housed. Refer to current ANSI/NFPA No. 409, Aircraft Hangars. In Canada, installation is suitable in aircraft hangars when acceptable to the enforcing authorities.
PUBLIC GARAGES: In repair garages, unit heaters must be at least 8 feet (2.4m) above the fl oor. Refer to the latest edition of NFPA No. 88B, Repair Garages.
In parking structures, unit heaters must be installed so that the burner fl ames are located a minimum of 18 inches (457mm) above the fl oor or protected by a partion not less than 18 inches (457mm) high. However, any unit heater mounted in a parking structure less than 8 feet (2.4m) above the fl oor must be equipped with an OSHA approved fan guard. Refer to the latest edition of NFPA 88A, Parking Structures.
In Canada, installation must be in accordance with the latest edition of CSA-B149 “Installation Codes for Gas Burning Appliances and Equipment.”
AIR DISTRIBUTION: Direct air towards areas of maximum heat loss. When multiple heaters are involved, circulation of air around the perimeter is recommended where heated air fl ows along exposed walls. Satisfactory results can also be obtained where multiple heaters are located toward the center of the area with heated air directed toward the outside walls. Be careful to avoid all obstacles and obstructions which could impede the warm air distribution patterns. Heat throw distances are presented in Figure 3 and Table 2.
Figure 3 - Heat Throw Distances
Table 2 - Standard Applications - Heat Throw Distances (Approximate)
“H” Distance From Floor to Bottom of Unit
ft. 100,000 125,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000
(m) (29.3) (36.6) (43.9) (51.2) (58.6) (65.9) (73.2) (87.8) (102.5) (117.1)
8 60 65 70 75 80 85 90 105 110 120 (2.4) (18.3) (19.8) (21.3) (22.9) (24.4) (25.9) (27.4) (32.0) (33.5) (36.6) 10 54 56 60 64 68 72 78 90 95 100 (3.0) (16.5) (17.1) (18.3) (19.5) (20.7) (21.9) (23.8) (27.4) (29.0) (30.5) 12 44 46 49 57 61 65 68 80 84 90 (3.7) (13.4) (14.0) (20.7) (17.4) (18.6) (19.8) (20.7) (24.4) (25.6) (27.4) 15 NR NR 45 49 52 56 60 70 74 80 (4.6) NR NR (22.6) (14.9) (15.8) (17.1) (18.3) (21.3) (22.6) (24.4) 20 NR NR NR NR 46 50 54 63 66 70
(6.1) NR NR NR NR (14.0) (15.2) (16.5) (19.2) (20.1) (21.3)
NR = Not recommended
UNIT SIZE BTU/Hr (kW)
5
INSTALLATION (continued)
The installation is to be adjusted to obtain an air throughput within the range specifi ed on the rating plate.
Unit heaters should not be installed to maintain low temperatures and/or freeze protection of buildings. A minimum of 50°F (10°C) thermostat setting must be maintained. If unit heaters are operated to maintain
lower than 50°F (10°C), hot fl ue gases are cooled inside the heat exchanger to a point where water vapor (a fl ue gas by-product) condenses onto the heat exchanger walls. The result is a mildly corrosive acid that prematurely corrodes the aluminized heat exchanger and can actually drip water down from the unit heater onto floor surface. Additional unit heaters should be installed if a minimum 50°F (10°C) thermostat setting cannot be maintained.
AIR FOR COMBUSTION: The Unit Heater shall be installed in a location in which the facilities for ventilation permit satisfactory combustion of gas, proper venting, and the maintenance of ambient temperature at safe limits under normal conditions of use. The Unit Heater shall be located in such a
manner as not to interfere with proper circulation of air within the confi ned space. When buildings are so tight that normal infi ltration does not meet air requirements, outside air shall be introduced per Sections 1.3.4.2 and
1.3.4.3 of ANSI Z223.1 for combustion requirements. A permanent opening or openings having a total free area of not less than one square inch per 5,000 BTU/HR. (1.5 Kw) of total input rating of all appliances within the space shall be provided.
Make certain that the lifting methods used to lift the unit heater and the structure to which the heater is to be mounted is capable of safely supporting its weight. Under no circumstances must the gas lines, venting system or the electrical conduit be used to support the heater or should any other objects (ie. ladder/person) lean against the heater, gas lines or electrical conduit for support. Failure to heed these warnings may result in property damage, personal injury or death.
Unit heaters must be hung level from side to side and from front to back; see Figures 2, 4 and 5. Failure to do so will result in poor performance and or premature failure of the unit.
Insure that all hardware used in the suspension of each unit heater is more than adequate for the installation. Failure to do so may result in extensive property damage, severe personal injury or death!
Refer to Figures 4 and 5, and dimensional data per Table 1 and Figure 2 for suspension of units.
Figure 4 - Heater Mounting*
NOTICE: Unit heater sizing should be based on heat loss calculations where the unit heater output equals or exceeds heat loss.
CLEARANCES: Each Gas Unit Heater shall be located
with respect to building construction and other equipment so as to permit access to the Unit Heater. Clearance between walls and the vertical sides of the Unit Heater shall be no less than 18 inches (457 mm). A minimum clearance of 6 inches (152 mm) must be maintained between the top of the Unit Heater and the ceiling. The bottom of the Unit Heater must be no less than 12 inches (305 mm) from any combustible. However, in order to ensure access to the burner compartment, a minimum distance of 21 inches (533 mm) is required. The distance between the flue collector and any combustible must be no less than 6 inches (152 mm). Also see AIR FOR COMBUSTION and VENTING sections.
NOTICE: Increasing the clearance distances may be necessary if there is a possibility of distortion or discoloration of adjacent materials.
*All hanging hardware and wood is not included with the unit (To be fi eld supplied).
Figure 5 - Heater Mounting 100/400 MBTU Sizes
Unit Sizes
6
INSTALLATION – GAS SUPPLY PIPING/SIZING
To avoid equipment damage or possible personal injury, do not connect gas piping to this unit until a supply line pressure/leak test has been completed. Connecting the unit before completing the pressure/leak test may damage the unit gas valve and result in a fi re hazard.
Do not rely on shut off valve to isolate the unit while conducting gas pressure/leak tests. These valves may not be completely shut off, exposing the unit gas valve to excessive pressure and damage.
PIPE SIZING
To provide adequate gas pressure at the gas unit heater, size the gas piping as follows:
NOTICE: If more than one gas unit heater is to be served by the same piping arrangement, the total cu ft/hr input and length of pipe must be considered.
1. Find the cu ft/hr by using the following formula: Input
Cu ft/hr =
Btu per Cu ft
2. Refer to Table 3. Match “Pipe Run in Feet” with appropriate “Gas Input - Cu Ft/Hr” fi gure. This fi gure can then be matched to the pipe size at the end of the column.
Example: It is determined that a 67 foot (20.4m) run of gas pipe is required to connect a 200 MBTU gas unit heater to a 1,000 Btu/cu. ft (0.29 kW) natur al gas supply.
200,000 Btu/hr
= 200 Cu ft/hr
1,000 Btu/cu ft Using Table 3, a 1 inch pipe is needed.
NOTICE: If the gas unit heater is to be fi red with LP gas, consult the local LP gas dealer for pipe size information.
NOTE: HEATER INSTALLATION FOR USE WITH PROPANE (BOTTLED) GAS MUST BE MADE BY A QUALIFIED L.P. GAS DEALER OR INSTALLER. HE WILL ENSURE THAT PROPER JOINT COMPOUNDS ARE USED FOR MAKING PIPE CONNECTIONS; THAT AIR IS PURGED FROM LINES; THAT A THOROUGH TEST IS MADE FOR LEAKS BEFORE OPERATING HEATER; AND THAT IT IS PROPERLY CONNECTED TO PROPANE GAS SUPPLY SYSTEM.
Before any connection is made to an existing line supplying other gas appliances, contact the local gas
NOTICE: See General Safety Information section for english/SI (metric) unit conversion factors.
company to make certain that the existing line is of adequate size to handle the combined load.
Table 3 - Gas Pipe Size
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour (Cubic Meters per Hour) for Gas Pressures of 0.5 psig (3.5 kPa) or Less, and a Pressure Drop of 0.5 Inch Water Column (124.4 Pa) (Based on a 0.60 Specifi c Gravity Gas) Nominal
Iron Internal Length of Pipe, Feet (meters) Pipe Size
Dia. 10 20 30 40 50 60 70 80 90 100 125 150 175 200 in. in. (3.0) (6.1) (9.1) (12.2) (15.2) (18.3) (21.3) (24.4) (27.4) (30.5) (38.1) (45.7) (53.3) (61.0) 1/2 0.622 175 120 97 82 73 66 61 57 53 50 44 40 37 35 (4.96) (3.40) (2.75) (2.32) (2.07) (1.87) (1.73) (1.61) (1.50) (1.42) (1.25) (1.13) (1.05) (0.99) 3/4 0.824 360 250 200 170 151 138 125 118 110 103 93 84 77 72 (10.2) (7.08) (5.66) (4.81) (4.28) (3.91) (3.54) (3.34) (3.11) (2.92) (2.63) (2.38) (2.18) (2.04) 1 1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 135 (19.3) (13.2) (10.6) (9.06) (8.07) (7.36) (6.80) (6.23) (5.80) (5.52) (4.96) (4.53) (4.11) (3.82) 1 1/4 1.380 1400 950 770 660 580 530 490 460 430 400 360 325 300 280 (39.6) (26.9) (21.8) (18.7) (16.4) (15.0) (13.9) (13.0) (12.2) (11.3) (10.2) (9.20) (8.50) (7.93) 1 1/2 1.610 2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430 (59.5) (41.3) (33.4) (28.0) (25.5) (22.9) (21.2) (19.5) (18.4) (17.6) (15.6) (14.2) (13.0) (12.2) 2 2.067 3950 2750 2200 1900 1680 1520 1400 1300 1220 1150 1020 950 850 800 (112) (77.9) (62.3) (53.8) (47.6) (43.0) (39.6) (36.8) (34.5) (32.6) (28.9) (26.9) (24.1) (22.7) 2 1/2 2.469 6300 4350 3520 3000 2650 2400 2250 2050 1950 1850 1650 1500 1370 1280 (178) (123) (99.7) (85.0) (75.0) (68.0) (63.7) (58.0) (55.2) (52.4) (46.7) (42.5) (38.8) (36.2) 3 3.068 11000 7700 6250 5300 4750 4300 3900 3700 3450 3250 2950 2650 2450 2280 (311) (218) (177) (150) (135) (122) (110) (105) (97.7) (92.0) (83.5) (75.0) (69.4) (64.6) 4 4.026 23000 15800 12800 10900 9700 8800 8100 7500 7200 6700 6000 5500 5000 4600 (651) (447) (362) (309) (275) (249) (229) (212) (204) (190) (170) (156) (142) (130)
1. Determine the required Cu. Ft. / Hr. by dividing the rated heater input by 1000. For SI / Metric measurements: Convert unit Btu. / Hr. to kilowatts. Multiply the unit input (kW) by 0.0965 to determine Cubic Meters / Hour. 2. FOR NATURAL GAS: Select the pipe size directly from the table. 3. FOR PROPANE GAS: Multiply the Cu. Ft. / Hr. (Cubic Meters per Hour) value by 0.633; then use the table. 4. Refer to the metric conversion factors listed in General Safety section for more SI unit measurements/conversions.
7
PIPE INSTALLATION
D3631C
1. Install the gas piping in accordance with applicable
local codes.
2. Check gas supply pressure. Each unit heater
must be connected to a manifold pressure and a gas supply capable of supplying its full rated capacity as specified in Table 4. A field LP tank regulator must be used to limit the supply pressure to maximum of 14 inches W.C. (3.5 kPa). All piping should be sized in accordance with the latest edition of ANSI Standard Z223.1 National Fuel Gas Code; in Canada, according to CSA B149. See Tables 1 and 3 for correct gas supply piping size. If gas pressure is excessive on natural gas applications, install a pressure regulating valve in the line upstream from the main shutoff valve.
3. Adequately support the piping to prevent strain on
the gas manifold and controls.
4. To prevent the mixing of moisture with gas, run the
take-off piping from the top, or side, of the main.
5. Standard gas unit heaters, optional two-stage units,
and hydraulic modulating units are supplied with a combination valve which includes:
(a) Manual “A” valve (b) Manual “B” valve
(c) Solenoid valve (d) Pilot safety (e) Pressure regulator
Pipe directly in to combination valve (see Figure 4).
6. A 1/8 inch N.P.T . plugged tapping, accessib le for test
gauge connection, must be installed immediately upstream of the gas supply connection to the appliance
7. Provide a drip leg in the gas piping near the gas
unit heater. A ground joint union and a manual gas shutoff valve should be installed ahead of the unit heater controls to permit servicing. The manual main shutoff valve must be located exter nal to the jacket. See Figure 6.
8. Make certain that all connections have been
adequately doped and tightened.
Check all pipe joints for leakage using a soap solution or other approved method. Never use an open flame or severe personal injury or death may occur.
Figure 6 - Pipe Installation, Standard Controls
Never use an open fl ame to detect gas leaks. Explosive conditions may e xist which would result in personal injury or death.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
CAUTION: Do not over tighten the inlet gas piping into the valve. This may cause stresses that would crack the valve!
NOTICE: Use pipe joint sealant resistant to the action of liquefied petroleum gases regardless of gas conducted.
Table 4 - Gas Piping Requirements*
Gas Type
Manifold
Pressure
Supply Inlet
Pressure
Natural Gas
3.5 in. W.C. (0.9 kPa)
14 in. W.C. Max.
(3.5 kPa)
5.0 in W.C. Min. (1.2 kPa)
Propane (LP) Gas
10.0 in. W.C. (2.5 kPa)
14 in. W.C. Max.
(3.5 kPa)
11.0 in W.C. Min. (2.7 kPa)
*For single stage applications only at normal altitudes.
8
INSTALLATION (continued)
BLOWER SET UP
BLOWER DRIVE ADJUSTMENT
The drive ratio of the motor and blower sheaves has been preset at the factory for a temperature rise of 65°F at 0 inch W.C. If the unit is to be operated under different air fl ow or pressure requirements, the drive ratio must be altered by means of the adjustable sheave on the
belt without fi rst disconnecting all electrical power to the unit or severe personal injury may result!
Never attempt to adjust the drive
blower motor, Figure 7.
1. Ensure that all packing material, support blocks, etc. have been removed from the unit.
2. Adjust the blower drive belt tension by means of the two tension bolts on the blower motor base. When proper tension has been achieved, the mid-point defl ection of the belt will be 3/4 inch when subjected to a 5 lb. force.
3. Recheck all electrical connections.
4. When power is applied, ensure that the motor and blower are rotating in a clockwise direction when viewed from the drive side.
1. Remove the belt guard and loosen the belt tension bolts on the blower motor base.
2. Loosen the set screw on the adjustable half of the motor sheave. To increase the blower speed, turn the adjustable half of the sheave clockwise, counter clockwise to slow the blower. Retighten the set screw.
3. Realign the blower and motor sheaves if necessary.
4. Adjust the belt tension as specifi ed in the BLOWER SET UP section under step 2.
5. Replace the belt guard.
5. Measure the current draw of the motor.
Never operate the unit without
The "at speed" current draw of the
motor must never exceed that specified on the
the belt guard in place or severe personal injury
may result! motor rating plate or severe damage to the motor will result!
6. Check that the air flow of the unit, the rpm and current draw of the blower motor and the temperature rise are within the limits specified in Table 1, the blower motor rating plate and the rating plate on the unit, respectively (also see Motor Data on page 10).
Figure 7 - Motor & Blower Assembly *
* PART DESCRIPTION A. Blower Housing B. Blower Wheel C. Blower Shaft D. Bearings (sets only) E. Drive Pulley (standard) F. Driven Pulley (standard) G. V-Belt H. Motor
Never operate the unit beyond the specified limits or severe damage to, and or premature failure of, the unit will result!
* NOTICE: THE BLOWER ASSEMBLY FOR THE 100/250 UNITS CONSISTS OF 1 WHEEL, 1 HOUSING, 1 SHAFT AND 1 BEARING SET. FOR 300/400 UNITS THE BLOWER ASSEMBLY CONSISTS OF 2 WHEELS, 2 HOUSINGS, 1 SHAFT AND 1 BEARING SET.
9
Table 5 - Motor Data
H.P.
VOLTAGE
PH
RPM
SHAFT
FRAME
STARTER
SIZE
1/2 1/2 3/4 3/4
1
1 1-1/2 1-1/2
2
3
NOTES: 1. Motors are typically permanent lube, ball bearing drive with class “B” windings.
2. All motors through 3 H.P. are equipped with auto reset overloads.
3. Single phase motors 1-1/2 H.P. and larger and all 3 phase motors require a contactor (or starter if specifi ed).
4. Motor frame must not exceed NEMA frame 56.
115/230
208/230/460
115/230
208/230/460
115/230
208/230/460
115/230 208/230/460 208/230/460 208/230/460
1 3 1 3 1 3 1 3 3 3
1725 1725 1725 1725 1725 1725 1725 1725 1725 1725
5/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8
56 56 56 56 56 56 56 56 56 56
0/00
Table 6 - Motor Full Load Amps*
VOLTAGE – PHASE
H.P.
1/2 3/4
1
1-1/2
2 3
115-1
9.8
13.8
16.0 — — —
208-1
5.4
7.6
8.4
10.5
12.6
17.8
*Average value, all speeds and frequencies.
230-1
4.9
6.9
8.0
10.0
12.0
17.0
208-3
2.2
3.1
4.1
6.0
7.8
11.0
230-3
2.0
2.8
3.5
5.0
6.5
9.0
460-3
1.0
1.4
1.8
2.5
3.3
4.5
— 00 — 00 — 00 — 00
0
Table 7 - Pulley Table 1725 RPM Motors (1/3 to 3 H.P.)
MOTOR PULLEYS
IVL34
1.9-2.9
IVL44
2.8-3.8
AK51
4.7
AK56
5.2
Turns Open
5 4-1/2 4 3-1/2 3 2-1/2 2 1-1/2 1 1/2 0
5 4-1/2 4 3-1/2 3 2-1/2 2 1-1/2 1 1/2 0
697 734 771 807 844 880 918 954
991 1027 1064 1101 1137 1174 1211 1247 1284 1321 1357 1394
630 663 697 730 763 796 829 863 896 928 962
995 1028 1061 1094 1127 1161 1194 1227 1260
BLOWER PULLEYS
AL64
6.0
546 575 603 633 661 690 719 748 776 805 834 863 891 920 949
978 1006 1035 1064 1093
AL74
7.0
468 493 517 542 567 591 616 641 665 690 715 739 764 789 813 838 863 887 912 936
AL84
8.0
410 431 453 474 496 517 539 560 582 604 625 647 668 690 712 733 755 776 798 819
AL104
10.0
327 345 362 380 397 414 431 448 466 483 500 518 535 552 569 587 604 621 638 656
10
Loading...
+ 22 hidden pages