Sterlco Royal Series Compact Temperature Control Unit User Manual

Page 1
Operation and Installation Manual
Royal Series
Water Temperature
Control Units
Important! Read Carefully Before Attempting to Install or Operate Equipment
Part No. 682.88105.00 Revision G Bulletin No. SC1-610.8
Page 2
Write down your unit serial number(s) ________________ ________________ here for future reference ________________ ________________ ________________ ________________ ________________ ________________
Sterling/Sterlco is committed
to a continuing program of product improvement.
Specifications, appearance, and dimensions described in this manual
are subject to change without notice.
© Copyright Sterling/Sterlco 2008 All rights reserved. Effective 4/15/08 Part No. 682.88105.00 Revision G Bulletin No. SC1-610.7
Page 2 Royal Series Water Temperature Control Units
Page 3
Safety Considerations
Sterling Royal Series temperature control units are designed to provide safe and reliable operation when installed and operated within design specifications, following national and local safety codes.
To avoid possible personnel injury or equipment damage when installing, operating, or maintaining this equipment, use good judgment and follow these safe practices:
Only PROPERLY TRAINED personnel familiar with the
information within this manual should work on this equipment.
Follow all local SAFETY CODES. Royal Series cabinets and piping are hot and are a BURN
HAZARD.
Do not operate a Royal Series system without all outer panels
installed. Pressurized hot water leaks can cause serious injury.
Wear SAFETY GLASSES and WORK GLOVES. Use care when LOADING, UNLOADING, RIGGING, or
MOVING this equipment.
Operate this equipment within design specifications. OPEN, TAG, and LOCK ALL DISCONNECTS before
working on equipment. Sterling recommends following OSHA Lock-Out/Tag-Out Standard 29 CFR 1910.147.
Make sure the unit is properly GROUNDED before switching
power on.
When welding or brazing in or around this equipment, be sure
VENTILATION is ADEQUATE. PROTECT adjacent materials from flame or sparks by shielding with sheet metal. An approved FIRE EXTINGUISHER should be close at hand and ready for use if needed.
Do not jump or bypass any electrical safety control. Do not restore power until all tools, test equipment, etc. have
been removed and the panels replaced.
Royal Series Water Temperature Control Units Page 3
Page 4
Table of Contents
1 General Information ................................................6
1-1 Introduction..................................................................................... 6
1-3 Models Covered..............................................................................7
1-4 Standard Royal Series Features..................................................... 7
1-5 Available Options............................................................................ 8
2 Shipping Information .............................................12
2-1 Unpacking and Inspection.............................................................12
2-2 In the Event of Shipping Damages................................................12
2-3 If the Shipment is Not Complete....................................................13
2-4 If the Shipment is Not Correct....................................................... 13
2-5 Returns ......................................................................................... 13
2-6 Uncrating Your New Royal Series System.................................... 14
3 Installation...............................................................16
3-1 Installation Location Considerations.............................................. 16
3-2 Process Approach Temperature Considerations........................... 16
3-3 External Piping Sizing Considerations .......................................... 16
3-4 Piping Considerations for Permanent Installations........................ 17
3-5 Piping Considerations for High Mobility Installations.....................18
3-6 Process Water Considerations...................................................... 18
3-7 Making Process Water Connections............................................. 19
3-8 Making Cooling Water Connections.............................................. 20
3-9 Making System Purge Connections..............................................21
3-10 Making Electrical Connections...................................................... 24
4 Identifying Controls and Features........................27
4-1 Identifying Mechanical Controls and Features .............................. 27
4-2 The Microprocessor Controller...................................................... 31
4-3 Operating the Unit with the Controller........................................... 31
4-4 Communications ...........................................................................32
5 Startup and Operation............................................33
5-1 Introduction................................................................................... 33
5-2 Startup Checklist........................................................................... 33
5-3 Starting the Temperature Control Unit .......................................... 34
5-4 Sequence of Operation................................................................. 35
5-5 Checking Motor Rotation Direction................................................ 36
5-6 Shutting Down the Temperature Control Unit ............................... 36
6 Unit Maintenance....................................................38
6-1 Preventive Maintenance................................................................ 38
Page 4 Royal Series Water Temperature Control Units
Page 5
6-2 Corrective Maintenance................................................................ 39
6-3 Restoring the Controller to Factory Setup..................................... 41
6-4 Electrical Connections................................................................... 41
6-5 Safety Devices.............................................................................. 42
6-6 Cleaning and Storage ................................................................... 44
7 Troubleshooting .....................................................45
I Index ........................................................................48
Royal Series Water Temperature Control Units Page 5
Page 6
1 General Information
1-1 Introduction
Sterling/Sterlco Royal Series water temperature control units are reliable, accurate, and easy-to-use process temperature control units. They are self-contained, portable, and shipped ready to use.
The Royal Series water temperature control unit is designed to circulate water through your process and to precisely, automatically, and reliably maintain it at a specified temperature. Standard unit operating range is from 0ºF (-17ºC) to 250°F (121°C), or up to 300°F (149°C) as an option. The unit is suited for use with city water, water from portable or central chillers or towers, or well water.
These units are designed for rapid recirculation of a relatively small amount of water to provide close and uniform temperature relation between To Process and From Process lines. This performance, of course, depends on the configuration of your process and any restrictions within the mold. The recirculation, combined with the large immersion heater and cooling capability, gives fast and accurate response to bring the water up to temperature or to changes in the settings when needed.
The 2010 Series water temperature control unit is a self-contained system consisting of a centrifugal pump, electric immersion heater, cool/vent solenoid valve, and electrical control, including a PID microprocessor controller and thermocouple. It is designed for use in process temperature control applications using water or a water/glycol mix. Any other use or fluid is prohibited. Some standard safety devices include a mechanical overtemperature safety thermostat, a pressure relief valve, motor overload protection, a low pressure cutout switch, branch fusing, and non-fused lockable rotary disconnect.
A properly installed, operated, and maintained Royal Series system provides years of reliable operation. Please read and follow the instructions in this manual to get the most satisfaction from your Royal Series system.
Page 6 Royal Series Water Temperature Control Units
Page 7
1-2 Necessary Documents
The following documents are necessary for the operation, installation, and maintenance of Sterling/Sterlco Royal Series water temperature control units. Additional copies are available from Sterling.
Familiarize the appropriate personnel with these documents:
This manual. The controller operation manual. The electrical schematic and connection diagram placed inside
the control enclosure.
The operation and installation manuals for accessories and
options selected by the customer.
The Customer Parts List included in the information packet.
1-3 Models Covered
This manual provides operation, installation, and maintenance instructions for the Royal Series water temperature control unit.
Model numbers are listed on the serial tag. A model number followed by Q indicates a specially constructed unit, and not all information in this manual may apply. Make sure that you know the model number, serial number, and operating voltage of your temperature control unit if you contact Sterling.
1-4 Standard Royal Series Features
• Compact, rugged cabinet with easy-access side panels
• Cast-and-flange design to reduce connection points
• Half- and full-heat automatic switching capability
• Dual stage Incoloy™ immersion heater with IEC contactors
• NEMA 12 electrical enclosure
• Microprocessor controller with fuzzy logic; includes
diagnostics features with indicator and warning status lights; CE and
UL
C
Royal Series Water Temperature Control Units Page 7
Page 8
• Forward-facing liquid-filled To and From Process pressure
gauges
• Independent high temperature safety thermostat
• Non-fused lockable rotary disconnect
• Branch fusing
• ¼” cooling solenoid valve on ¾ to 3 hp (0.56 to 2.24 kW)
models; ½” slow-close cooling solenoid valve on 5, 7½, & 10 hp (3.73, 5.60, & 7.46 kW) models
• EPDM/NI-Resist pump seal
• Adjustable low supply water pressure switch; factory-set at
16 psig (110 kPa/1.1 bars)
• 150 psig (1,034 kPa/10.3 bars) pressure relief valve
• Choice of 230 or 460 operating voltages
• ¾” water supply and drain connections; 1½” process
connections
• Automatic vent sequence
• 3” (76 mm) casters
• Operating range of 0ºF to 250ºF (-17ºC to 121ºC)
• Three (3) -year parts and labor warranty at the factory; five
(5) -year controller warranty, and limited lifetime warranty on wetted pump components and pump seal; subject to factory review
1-5 Available Options
Royal Series systems are available with options to tailor the unit to your requirements. Some are factory installed; some can be retro­fitted in the field. Consult your Sterling sales representative for more information. Available Royal Series options include:
• Controller with integral flow meter; with: Up to 30 gpm (114 lpm) flow indicator
- or -
30 to 75 gpm (114 to 284 lpm) flow indicator 0-20 mA and 4-20 mA current control output
Page 8 Royal Series Water Temperature Control Units
Page 9
Remote set point and retransmission; 0-20 mA and 4-20
mA
RS-232 or RS-485 communications Remote sensor; 10 ft. (3 m)
• Remote controller enclosure
• Heaters available in 12 kW, 18 kW, 24 kW, 36 kW, and 48
kW on direct-injection compact models; 36 kW and 48 kW heaters available on direct-injection upright models
• Closed-loop heat exchanger available in 3.7 sq. ft. (0.344 sq.
m) on compact models; 3.7, 7.4, 11.2, 18.1, and 27.0 sq. ft. (0.135, 0.688, 1.042, 1.683, and 2.511 sq. m) on upright models
• Quick Cool function
• Auto system water purge (mold purge)
• Y-strainer
• Hammer arrestor (water hammer shock stop)
• Remote start/stop control
• Rubber feet; available in lieu of casters
• Non-ferrous brass construction
• Slow-close cooling solenoid valves available in 1/2” x 9/16”
(CV = 3.5) and 3/4” x 3/4” (CV = 5.5)
• Modulating valves available in 1/2” (CV = 0.4, 1.3, 2.2,
or 4.4), 3/4” (CV = 5.5 or 7.5), 1” (CV = 10 or 14),
1
/4” (CV = 20)
and 1
• Two-zone stack rack with casters, common wiring and piping
available; compact units only
• 300ºF (149ºC) operation; includes graphite-impregnated
silicon carbide seal
• Audible and visual general fault alarm
• Electrical operation available in 208, 230, 460, and 575 volts,
60 Hz; 200, 380, and 415 volts, 50 Hz
• UL/CUL-listed electrical subpanel
Royal Series Water Temperature Control Units Page 9
Page 10
Figure 1
Typical Royal Series Water Temperature Control Unit and Specifications
Direct Injection
FROM PROCESS
COOLING WATER OUT
COOLING WATER IN

                        
TO PROCESS
28 3/4"
3 3/4"
13"
THIS EQUIPMENT CONTAINS FLUID, PIPING AND CONNECTIONS WHICH MAY BE EXTR EMELY HOT AND COUL D CAUSE SERIOUS BURNS AND PERSONAL INJURY. RECOGNITION OF AND COMPLIANCE WITH THE FOLLOWING PRECAUTIONS ARE THE SOLE RESPONSIBILITY OF THE USER OF THIS EQUIPMENT.
1. EQUIPMENT MUST BE PROPERLY GROUNDED.
2. ELECTRIC POWER SUPPLY WIRING AND DEVICES MUST BE PROPERLY FUSED AND SIZED TO MEET REQUIREMENTS OF THIS EQUIPMENT, AND ALL APPLICABLE CODES.
3. ELECTRIC POWER SOURCE MUST BE DISCONNECTED PRIOR TO OPENING ANY ELECTRIC ENCLOSURE OR WORKI N G ON ANY ELECTRIC COMPONENTS.
4. ALL CONTROL DEVICES MUST BE MAINTAINED IN PROPER WORKING CONDITION TO AVOID ACCIDENTAL OVERHEATING OR DANGER TO OPERATING PERSONNEL.
5. THIS EQUIPMENT MUST NOT BE US E D WHILE UNATTENDED.
6. VENT AND DRAIN PROVISIONS MUST NOT BE RESTRICTED.
7. AIR AND FLUID SUPP LY SERVICE PROVISIONS MUST ALWAYS BE SHUT OFF BEFORE DISCONNECTING O R SE RV IC IN G THIS EQUIPMENT. THIS SIGN MUST NOT BE REMOVED OR CAMOUFLAGED DURING USE OF THIS EQUIPMENT.

ESTE EQUIPO CONTIENE FLUIDO, TUBERIA Y CONEXIONES QUE PUEDEN ESTAR PELIGROSAMENTE CALIENTES!
CONOCIMIENTO Y CUMPLI MIENTO CON LAS SIGUI ENTES PRECAU­CIONES SON LA RESPONSABILI DA D EX CLUSIVA DEL USUARIO DE ESTE EQUIPO.
1. EL EQUIPO DEBE ESTAR CONECTADO A TIERRA EN FORMA DEBIDA.
2. EL ALAMBRADO PARA EL SUMINISTRO DE LA FUERZA ELECTRICA Y DISPOSITIVOS CORRESPONDIENTES DEBEN
TENER SUS FUSIBLES Y SER DEL TAMANO O CAPACIDAD
QUE CORRESPONDE A ESTE EQUIPO.
3. DEBE DESCONECTARSE LA FUERZA ELECT RICA ANTES
DE ABRIR LAS CAJAS ELECTRICAS O HACER CUALQUIER TRABAJO EN LOS COMPONENTES ELECTRICO S.
4. LOS DISPOSITIVOS DE MANDO DEBEN MAN TENERSE EN PER-
FECTO ESTADO DE FUNCIONAMIENTO PARA EVITAR EL SOBRECALENTAMIENTO ACCIDENTAL O EL DA N O AL PERSONAL QUE ATEINDE EL EQUIPO.
5. ESTE EQUIPO NO DEBE SER USADO CUANDO NO HAY QUIEN
LO ATIENDA.
6. LAS DISPOSICIONES SOBRE EL SERVICIO DE DRENAJE
O PURGA NO ESTAN RESTRINGIDAS UNICAMENTE AL FLUJO CORRECTO DEL FLUIDO.
7. LAS DISPOSICIONES O CONEXIONES DE SUMINISTRO
DE FLUIDO Y AIRE DEBEN CERRARSE SIEMPRE ANTES DE DESCONECT AR O SERVIR EL EQUIPO.
ESTA ADVERTENCIA O SENAL NO DEBE QUITARSE
O TAPARSE MIENTRAS SE USA EL EQUIPO.
PART NO. 522-00205-00
PART NO. 522-00205-01
21 7/16"
15 1/8"
6 7/16"
28"
2 3/4"
2 3/4"
11 3/4"
Closed Circuit
COOLING WATER OUT
COOLING WATER IN
3 9/16"
1 15/16"
FROM PROCESS
TO PROCESS
28 3/4"
3 3/4"
 
ESTE EQUIPO CONTIENE FLUIDO, TUBERIA Y CONEXIONE S QU E
THIS EQUIPMENT CO NTAINS FLUID, PIP ING AND CONNECTIONS
PUEDEN ESTAR PELIGROSAMENTE CALIENTES! WHICH MAY BE EXTREMELY HOT AN D C OULD CAUSE SERIOUS BURNS AND PERSONAL INJURY.
CONOCIMIENTO Y CUMPLIMIENTO CON LAS SIGUIENTES P RECAU­RECOGNITION OF AND COMPLIANCE WITH THE FOLLOWING
CIONES SON LA RESPONSABILIDAD EXCLUSIVA DEL USU ARIO DE PRECAUTIONS ARE THE SOLE RESPONSIBILITY O F T HE US ER
ESTE EQUIPO. OF THIS EQUIPMENT.
1. EL EQUIPO DEBE ESTAR CON ECTADO A TIERRA EN FORMA DEBIDA.
1. EQUIPMENT MUST BE PRO PERLY GROUNDED.
2. EL ALAMBRADO PARA EL SUMI NISTRO DE LA FUERZA
2. ELECTRIC POWER SUPPLY WIRING AND DEVICES MUST BE ELECTRICA Y DISPOSITIVOS CORRESPONDIENTES DEBEN
PROPERLY FUSED AND SIZED TO MEET REQUIREMENTS OF
TENER SUS FUSIBLES Y SER DEL TAMANO O CAPACIDAD
THIS EQUIPMENT, AND ALL APP L ICABLE CODES.
QUE CORRESPONDE A ESTE EQUIPO.
3. DEBE DESCONECTARSE LA FUERZA ELECTRICA ANTES
3. ELECTRIC POWER SOURCE MU ST BE DISCONNECTED PRIO R
DE ABRIR LAS CAJAS ELEC TRICAS O HACER CUALQUIER
TO OPENING ANY ELECTRIC ENCLOSURE OR WORKING ON
TRABAJO EN LOS COMPONENTE S ELECTRICOS.
ANY ELECTRIC COMPONENTS.
4. LOS DISPOSITIVOS DE MAND O D EBEN MANTENERSE EN PER-
4. ALL CONTROL DEVICES MUST BE MAINTAINED IN PROPER
FECTO ESTADO DE FUNCIONAMIENTO PARA EVITAR EL
WORKING CONDITION TO AVOID ACCIDENTAL OVERHEATING
SOBRECALENTAMIENTO ACC IDENTAL O EL DANO AL
OR DANGER TO OPERATING PE RSONNEL.
PERSONAL QUE ATEINDE EL EQUIPO.
5. THIS EQUIPMENT MUST NOT BE USED WHILE UNATTENDED.
5. ESTE EQUIPO NO DEBE SER USADO CUANDO NO HAY QUIEN
6. VENT AND DRAIN PROVISIO NS MUST NOT BE RESTRICTED .
LO ATIENDA.
6. LAS DISPOSICIONES SOBRE EL SERVICIO DE DRENAJ E
7. AIR AND FLUID SUPPLY SE RVICE PROVISIONS MUST ALWAYS
O PURGA NO ESTAN RESTRINGIDAS UNICAMENTE AL FLUJO
BE SHUT OFF BEFORE DISCONNECTING OR SERVICING THIS
CORRECTO DEL FLUIDO.
EQUIPMENT.
7. LAS DISPOSICIONES O CONEXIO NES DE SUMINISTRO
THIS SIGN MUST NOT BE REMOVED OR CAMOUFLAGED
DE FLUIDO Y AIRE DEBEN CERRARSE SIEMPRE ANTES
DURING USE OF T HIS EQUIPMENT.
DE DESCONECTAR O SERVIR EL EQUIPO.
ESTA ADVERTENCIA O SENAL NO DEBE QUITARSE
O TAPARSE MIENTRAS SE USA EL EQUIPO.
PART NO. 522-00205-01
PART NO. 522-00205-00
13"
28"
27 1/8"
26 1/16"
21 7/16"
15 1/8"
6 7/16"
2 3/4"

         
              
11 3/4"
PROCESS WATER VENT
PROCESS WATER IN
2 3/4"
Model Dimensions Shipping
number Pump H W D weight
460 / 230 hp
2010,
9 kW heater
¾ 1 2 3 5 7½
kW
0.56
0.75
1.50
2.24
3.73
5.60
gpm
30 35 50 60 75 90
lpm
113.6
132.5
189.3
227.1
283.9
454.2
psig
25 30 30 35 54 63
kPa
172.4
206.9
206.9
241.3
372.3
434.4
in.
28¾”
cm
73.0
in.
13”
cm
33
in.
28”
cm
71.1
lbs.
210
240
Kg
96
109
Page 10 Royal Series Water Temperature Control Units
Page 11
Figure 2
Typical Royal Upright Series Water Temperature Control Unit and Specifications

     
                   

497/8”
48"
3 3/4"
13"
28"
Model Dimensions Shipping
number Pump H W D weight
460 230 letter hp
C ¾ D 1
2012,
9 kW heater
F 2 G 3 H 5
J 7½
K 10
kW
0.56
0.75
1.50
2.24
3.73
5.60
7.46
gpm
30 35 50 60 75
90
120
lpm
113.6
132.5
189.3
227.1
283.9
340.7
454.2
psig
25 30 30 35 54
63 55
kPa
172.4
206.9
206.9
241.3
372.3
434.4
379.2
in.
48
cm
122
in.
13
cm
33
in.
28
cm
71.1
lbs.
210
240 270
Kg
96
109 123
Figure 3
Royal Series Unit Full-Load Amps
Model Full-load amps at 460 volts
hp kW 9 kW heater 12 kW heater 18 kW heater 24 kW heater 36 kW heater 48 kW heater
0.75 hp
1.00 hp
2.00 hp
3.00 hp
5.00 hp
7.50 hp
10.00 hp
0.56 kW
0.75 kW
1.50 kW
2.24 kW
3.73 kW
5.60 kW
7.46 kW
12.7 amps 16.5 amps 24.0 amps 31.6 amps 47.4 amps 62.4 amps
13.1 amps 16.9 amps 24.4 amps 32.0 amps 47.8 amps 62.8 amps
14.7 amps 18.5 amps 26.0 amps 33.6 amps 49.4 amps 64.4 amps
16.1 amps 19.9 amps 27.4 amps 35.0 amps 50.8 amps 65.8 amps
18.9 amps 22.7 amps 30.2 amps 37.8 amps 56.6 amps 71.6 amps
22.3 amps 26.1 amps 33.6 amps 41.2 amps 57.0 amps 72.0 amps
26.0 amps 30.0 amps 37.0 amps 45.0 amps 60.0 amps 75.0 amps
Royal Series Water Temperature Control Units Page 11
Page 12
2 Shipping Information
2-1 Unpacking and Inspection
You should inspect your Sterling/Sterlco Royal Series temperature control unit for possible shipping damage. If the container and packing materials are in re-usable condition, save them for reshipment if necessary.
Thoroughly check the equipment for any damage that might have occurred in transit, such as broken or loose wiring and components, loose hardware and mounting screws, etc. In case of breakage, damage, shortage, or incorrect shipment, refer to the following sections.
2-2 In the Event of Shipping Damages
Important!
According to the contract terms and conditions of the Carrier,
the responsibility of the Shipper ends at the time and place of shipment.
Notify the transportation company’s local agent if you discover
damage.
Hold the damaged goods and packing material for the
examining agent’s inspection. Do not return any goods to
Sterling before the transportation company inspection and authorization.
File a claim against the transportation company. Substantiate
the claim by referring to the agent’s report. A certified copy of our invoice is available upon request. The original Bill of Lading is attached to our original invoice. If the shipment was prepaid, contact Sterling at (262) 641-8610 for a receipted transportation bill.
Advise Sterling regarding your request for assistance and
to obtain an RGA (return goods authorization) number.
Page 12 Royal Series Water Temperature Control Units
Page 13
2-3 If the Shipment is Not Complete
Check the packing list. The apparent shortage may be intentional. Back-ordered items are noted on the packing list. You should have:
Sterling/Sterlco Royal Series water temperature control unit Bill of lading Packing list Operating and Installation packet Electrical schematic and panel layout drawings Component instruction manuals
Re-inspect the container and packing material to see if you missed any smaller items during unpacking. Determine that the item was not inadvertently taken from the area before you checked in the shipment. Notify Sterling immediately of the shortage.
2-4 If the Shipment is Not Correct
2-5 Returns
Do not return any damaged or incorrect items
until you receive shipping instructions from Sterling.
If the shipment is not what you ordered, contact the parts and service department immediately at (262) 641-8610. Have the
order number and item number available. Hold the items until you receive shipping instructions.
Important!
Royal Series Water Temperature Control Units Page 13
Page 14
2-6 Uncrating Your New Royal Series System
Royal Series water temperature control units are shipped
fastened to a skid and covered with a cardboard box.
Carefully remove the staples on the bottom of the box, lift off
the box, and remove the bolts holding the unit to the skid.
Caution!
Be careful when cutting straps.
Straps may spring back and cause injury!
From the side, slip two lifting straps between the skid and
temperature control unit. Spread the straps from the center line so it is balanced.
Loop the straps over a fork truck fork. Lift slowly and only
high enough to clear the skid. Use a pry bar if necessary to remove the skid from the unit.
Carefully slide the skid from beneath the unit and lower the
unit. Lower slowly. The unit should land on its casters and can be rolled into position.
Retain the crating in case reshipment is necessary due to
hidden shipping damage.
Page 14 Royal Series Water Temperature Control Units
Page 15
- Notes -
Royal Series Water Temperature Control Units Page 15
Page 16
3 Installation
3-1 Installation Location Considerations
Royal Series systems are portable and can be installed almost anywhere. As with all equipment installations, follow all applicable codes and regulations.
The recommended ambient temperature range for Royal Series
installations is from +14ºF (-10ºC) to a maximum operating ambient temperature of 131°F (55ºC). Recommended ambient storage temperature range is from -13ºF to 149ºF (-25ºC to 65ºC). If storing the unit below freezing temperatures, make sure the unit has an antifreeze mixture circulated inside.
Provide a minimum of twelve inches (12” or about 30 cm)
clearance on all sides of the cabinet to allow circulation of cooling air.
Locate the unit as close to the process as is practical.
3-2 Process Approach Temperature Considerations
If the differential (U) between COOLING WATER IN and TO
PROCESS
Department for advice on how to control low approach applications.
temperatures is less than 10°F (7ºC), consult our Sales
3-3 External Piping Sizing Considerations
All external hose and piping should be adequately sized to
assure minimum external pressure drop.
Low external piping pressure drop is needed for best operation.
Page 16 Royal Series Water Temperature Control Units
Page 17
Note: Use a backup wrench to support Royal Series system
piping when making process piping connections.
! CAUTION
All external valves, fittings, and hoses must be rated at a minimum of
150 psig and 250°F (1,034.25 kPa/10.34 bars and 121ºC).
The exception is when the temperature control unit
is optionally rated for 300ºF (149ºC) operation;
external valves fittings and hoses must then be rated at a minimum of
150 psig and 300ºF (1,034.25 kPa/10.34 bars and 121ºC).
3-4 Piping Considerations for Permanent
Installations
Sterling recommends an optional (or customer-installed) strainer on the COOLING WATER IN inlet.
The unit must have at least 16 psig (110.32 kPa/1.1 bars) water supply pressure to prevent pump cavitation that can be caused by the water “flashing” to steam. To avoid damage to the pump or other components, make sure that maximum supply pressure does not exceed 55 psig (379.2 kPa/3.79 bars).
Keep restrictions to a minimum by using proper inlet pipe sizing. If the water supply piping is larger than ¾”, reduce the size at the unit. The table below contains the pipe sizes that are used in the unit.
Pipe sizes for ¾ hp to 10 hp (0.56 kW to 7.46 kW) units
Location Size in inches NPT
To Process 1½” From Process 1½” Cooling Water In ¾” Cooling Water Out
Common black pipe is recommended for permanent installations. Royal Series water circuit piping is primarily ferrous (iron) and reacts electro-chemically with non-ferrous metallic materials such as copper. Some water contains dissolved minerals that greatly accelerates the reaction between dissimilar metals.
- depends on solenoid used -
Royal Series Water Temperature Control Units Page 17
Page 18
Ferrous piping is recommended to minimize galvanic action. If piping must be copper, use dielectric unions at the unit.
3-5 Piping Considerations for High Mobility
Installations
Mobile Royal Series systems must use high quality hose rated for at least 150 psig and 250°F (1,034.25 kPa/10.34 bars and 121ºC). Special 300°F (149ºC) high temperature Royal Series systems must use hosing rated at 150 psig and 300°F (1,034.25 kPa/10.34
bars and 149ºC) or greater.
Quick disconnects may be used for mobility, although they cause a drop in pressure. If used, they must be sized carefully to minimize pressure drop. Don’t use quick disconnects with check valves unless absolutely necessary.
! CAUTION
Non-relieving quick connect fittings or check valves on the water supply
must have a pressure relief piped to the drain.
Failure to do so could result in a dangerous over-pressure condition!
3-6 Process Water Considerations
Raw Water
Water treatment is vital in any piping system. In some cases, raw water may be used in the system without problems; in other cases, it can result in large deposits of scale and corrosion.
Sterling offers a complete line of water treatment equipment. Contact your Sterling sales representative for water testing and treatment options.
Distilled Water
Non-ferrous (brass, copper, or high-temperature plastic) piping is recommended for distilled water processes.
Page 18 Royal Series Water Temperature Control Units
Page 19
Deionized Water
Stainless steel (316 SS minimum) or PVC plastic components must be used with deionized water. Sterling recommends stainless steel because of the temperature constraints with plastic.
3-7 Making Process Water Connections
Closed Circuit/Direct Injection
On the back of each unit, the connections are labeled appropriately. For Direct Injection units connect the TO PROCESS hookup to the entrance of the process and the the exit of the process. Connect the
IN
to your plant water supply. Connect the COOLING WATER
OUT
line to an open drain, or to the return line of
your central water system.
For Closed Circuit units make the connections as stated above, and if there is a separate supply for the process and cooling make the following connections. Connect the PROCESS WATER
SUPPLY hookup to the water source for the process. Connect the PROCESS WATER VENT hookup to return the water back to
the process source.
Make sure you carefully select the connecting lines and connectors between the temperature control unit and the process to suit the needs and requirements of your application.
If your unit has a maximum operating temperature of 250ºF (121ºC), the connecting lines and connectors should have a service rating of at least 250ºF (121ºC) and 150 psig (1,034.25 kPa/10.34 bars). If it has a maximum temperature of 300ºF (149ºC), the lines and connectors should have a service rating of at least 300ºF (149ºC) and 150 psig (1,034.25 kPa/10.34 bars).
TO PROCESS — 1½” NPT
FROM PROCESS hookup to
COOLING WATER
This is the outlet for the tempered water leading to the process being controlled.
Royal Series Water Temperature Control Units Page 19
Page 20
FROM PROCESS — 1½” NPT
Water from the process re-enters the Royal Series system to be tempered and re-circulated back into the process.
3-8 Making Cooling Water Connections
WATER IN — ¾”
The cooling water supply inlet from a cooling tower, a chiller, or a city water supply.
! CAUTION
If a non-relieving device such as a regulator, ball valve,
or check valve is installed on the WATER IN line,
you MUST install an expansion tank
of at least ½ gallon (about 2 liters) capacity.
Failure to do so can result in system overpressure from thermal expansion.
Install the tank configured as shown below:
Expansion
tank
Royal Series
unit
Non-relieving
device
Check the expansion tank frequently to make sure it is not flooded.
Page 20 Royal Series Water Temperature Control Units
Page 21
Water Out
Size Depends on Solenoid Used
The cooling water outlet leading back to the cooling tower, chiller, or drain.
Net supply pressure must be between 25 psig and 55 psig (172.38 kPa/1.72 bars and 379.2 kPa/3.79 bars). Net supply below 15 psig (103.43 kPa/1.03 bars) may allow water to flash to steam, cavitate the impeller, and damage the pump, which prevents the unit from cooling properly. Operation above 55 psig (379.2 kPa/3.79 bars) may cause premature opening of the relief valve from pump pressure and pressure surges.
PRESSURE RELIEF — ¾”
The pressure relief valve, located at the back of the unit, is pre­piped to approximately four inches (4” or 10 cm) above the floor. This piping reduces the chance of scalding nearby personnel if the relief valve should trip.
3-9 Making System Purge Connections
Royal Series systems equipped with the System Purge option have a compressed air inlet marked MOLD PURGE. Connect to a clean, dry 100 psig (689.50 kPa/6.90 bars) air line. Install your own shutoff valve to prevent process liquid from backing up into the plant air piping if the compressed air is turned off and the check valve fails. Don’t depend on the solenoid valve to hold water
pressure in the temperature control unit.
Royal Series Water Temperature Control Units Page 21
Page 22
Figure 4
Typical Piping Schematic
M
Page 22 Royal Series Water Temperature Control Units
Page 23
Figure 5
Pump Curves; 60 Hz


Pump Curves; 50 Hz • Consult Factory for 10 hp Curves
Figure 6
Pressure Drops
Model Pressure drop flow and loss
hp kW 9 kW htr flow gpm
0.75 hp
1.00 hp
2.00 hp
3.00 hp
5.00 hp
7.50 hp
10.00 hp
0.56 kW
0.75 kW
1.50 kW
2.24 kW
3.73 kW
5.60 kW
7.46 kW
12.7 amps 30.0 gpm
13.1 amps 35.0 gpm
14.7 amps 50.0 gpm
16.1 amps 60.0 gpm
18.9 amps 75.0 gpm
22.3 amps 90.0 gpm
26.0 amps 120.0 gpm
flow lpm
113.6 lpm
132.5 lpm
189.3 lpm
227.1 lpm
283.9 lpm
340.7 lpm
454.2 lpm


loss psi
0.0 psi
1.0 psi
1.5 psi
2.0 psi
2.5 psi
5.0 psi
5.0 psi
loss kPa
0.0 kPa
6.9 kPa
10.3 kPa
13.8 kPa
17.2 kPa
34.4 kPa
34.4 kPa
Royal Series Water Temperature Control Units Page 23
Page 24
3-10 Making Electrical Connections
Royal Series systems are designed for three-phase voltage operation. Refer to the unit nameplate for proper voltage and amperage requirements.
Make sure you provide a correctly sized and protected supply of electrical power to the unit.
Important!
Refer to National Electric Code (NEC) Article 430-24 through 430-26
for proper feeder conductor and supply disconnect sizing.
Maintain a safe ground and disconnect the power supply before servicing the unit. A qualified electrician should make electrical connections, and disconnect and lock out electricity using OSHA 29CFR 1910.147 standards when you need a service call.
Check serial tag voltage and amperage requirements and make sure your electrical service conforms before making any electrical connections. Total running amps for Royal Series systems are listed on the nameplate. Customer connections can be run to the supply terminals from either side of the unit. Make sure that all three phases are wired correctly. If not wired properly, the unit will run backwards. Again, check the unit nameplate for correct
voltage and amperage.
! DANGER
Improper electrical connections can damage the unit and cause serious operator injury or death!
Page 24 Royal Series Water Temperature Control Units
Page 25
Bring properly sized power leads and ground from a fused disconnect (installed by your electrician) to the unit. Provide external overcurrent protection to the unit, using circuit breakers or fuses. If you use fuses, make sure that they are dual-element time­delay fuses, sized according to your electrical code. Make sure that all electrical connections are tight.
Important!
1. Electrical connections must comply with all applicable electrical codes.
2. The temperature control unit must be grounded in accordance with NEC Article 250.
3. Voltage must be within plus or minus ten percent (±10%) of the nameplate rating.
4. Make sure your installer provides external protection.
Royal Series Water Temperature Control Units Page 25
Page 26
Figure 7
Typical Electrical Wiring Schematic
Please refer to the electrical wiring diagrams supplied
with your unit’s Customer Information Packet.
Page 26 Royal Series Water Temperature Control Units
Page 27
4 Identifying Controls and Features
4-1 Identifying Mechanical Controls and Features
To and From Process Probes
Two (2) 1,000-ohm (1 KΩ) platinum RTD probes are included with your Royal temperature control unit. One is located downstream from the heater to sense To Process temperature; the other probe is located upstream from the pump to sense From Process temperature.
Safety Thermostat
The safety thermostat mounted on the side of the heater tank protects against thermal runaway. The thermostat guards against the unlikely event of “runaway” heating. If overheating occurs, the safety thermostat shuts down heater outputs. The unit continues to pump water through the system to prevent heater damage. Sterling recommends that you install an audible or visual alarm to the terminals provided. Factory installed alarms are available; see the electrical schematics in your Installation Packet for more information.
Pressure Relief Valve
If the combined pressure of the cooling supply water and pump discharge exceeds 150 psig (1,034.25 kPa/10.34 bars), the pressure relief valve opens and relieves the pressure. This is a non­adjustable ASME construction valve with a stainless steel spring.
Important!
Route a pipe from the pressure relief valve
to a suitable drain to reduce potential scalding hazard.
The drain line must not have any restrictions or back pressure.
Royal Series Water Temperature Control Units Page 27
Page 28
Low Pressure Cutout Switch
This switch, set at 16 psig with a 2 psig differential (110.3 kPa/
1.10 bars with a 13.79 kPa/0.14 bars differential) shuts down the unit if the COOLING WATER IN or MAKEUP water pressure drops below 16 psig (110.3 kPa/1.10 bars).
Pumps
Pumps range in power from ¾ hp to 10 hp (0.56 kW to 7.46 kW) and are equipped with 3-phase ODP motors and seal flush lines as standard.
The pump is a bronze-fitted close-coupled centrifugal type. It features a split case design to facilitate replacement of the seal. It has a high output capacity with excellent discharge pressure helping it facilitate turbulence to maximize heat transfer, and is well suited for the conditions under which it was designed to operate.
Heaters
Solenoid Valves
The specially designed 9 kW three-phase low watt density electrical immersion heater heats the water, and the controller regulates the temperature. The standard heater has an incolloy sheath for best heat transfer and low fouling properties.
Low watt density immersion heaters at 12 kW, 18, 24 kW, 36 kW, and 48 kW are available options for these models, depending upon the heating needs of the process. All models are built to provide full or partial heat as required by the process and determined by the controller, providing more precise temperature control.
Royal Series systems use rugged, industrial design solenoids with replaceable coils and/or internal components. Depending on required cooling capacity, solenoid valves are available in sizes ranging from
1
/4” to 3/4”; 1/2” x 9/16” and 3/4” x 3/4” solenoid valves are
slow-closing.
Page 28 Royal Series Water Temperature Control Units
Page 29
Motorized Modulating Valves
Optional
Optional motorized modulating valves are recommended for large cooling applications where the process temperature is very near the cooling water supply temperature and the temperature controller unit pump is used as a booster. The gradual shutoff they provide also eliminates water hammer. The option includes a complete valve and motor package in place of a long-life solenoid valve.
The motorized modulating valve has infinite positioning. It fully opens in one (1) minute and fully closes in 15 seconds.
Water Hammer Arrestor (Shock Stop)
Optional
Shock waves from fast-operating solenoid valves may damage some process systems. For these applications, a welded metal bellows-type shock stop with a pre-charged and sealed nitrogen blanket can be installed in the cooling piping.
Pump Starter
Transformer
Heater Contactor
Royal Series high quality IEC-rated pump motor starters are industrial grade motor controls with overload protection and manual reset.
High quality industrial design transformers are specified to suit incoming voltage on the application and provide 115 VAC control voltage. The 115 VAC circuit is protected by primary fusing and secondary grounding.
Your Royal Series unit uses high-quality IEC-rated industrial­grade electromechanical contactors for heater controls.
Royal Series Water Temperature Control Units Page 29
Page 30
Cooling
Electricals
The controller automatically regulates cooling by opening and closing the solenoid valve or modulating valve. For direct injection, the unit cools by removing the required amount of warm water from the system. This process permits an equal amount of cool plant water to enter the system well ahead of the pump, allowing it to blend with the system water. The water supply temperature governs the minimum operating temperature of the unit.
For closed circuit operation, the unit cools by automatically releasing cooling water through the tubes of the specially designed tube bundle heat exchanger in each zone. The process fluid, such as water, glycol, or other similar fluid, is circulated through the shell of the heat exchanger.
Note: The plant water supply temperature governs the minimum
operating temperature of the unit.
Automatic Vent
The pump motor and the immersion heater operate on three-phase 50/60 cycle nominal voltages with the control circuit operating at 115V single phase. The control circuit voltage is provided by a single phase machine tool transformer with a grounded secondary.
The 115V control circuit and controller outputs are fuse protected. The pump motor is controlled by a full voltage magnetic non­reversing motor starter, with fused branch circuit overcurrent and thermal overload protection.
This feature automatically triggers the purging of air from the system before you start the unit. The vent actuates the solenoid valve, and forces trapped air and water out through the drain, properly filling and priming the unit prior to startup. Complete venting is necessary to prevent damage to the pump and heater.
The vent process is controlled through a timer. If you have a large process, you may need to complete the venting process by pressing the
VENT button on the front-mounted switch panel.
Page 30 Royal Series Water Temperature Control Units
Page 31
Pressure Switch
A pressure switch built into each unit keeps the system from starting until the water supply is turned
On and subjected to the
minimum water supply pressure. This feature protects the pump seal and the heater from damage through attempted operation without water. The pressure switch is set at approximately 16 psig (110.32 kPa/1.10 bars) for 250°F (121ºC) units or 55 psig (379.23 kPa/3.79 bars) for 300°F (149ºC) units prior to leaving the factory.
4-2 The Microprocessor Controller
These temperature control units can be manufactured with different controllers (M2B, M2B+, or any off-the-shelf PID controller). Please refer to your enclosed controller manual for a detailed description of the operation of the controller.
4-3 Operating the Unit with the Controller
M2B
Start Up
1. Turn disconnect switch to ON position.
2. Press START. The unit will automatically vent for approximately o ne minute.
3.
4. If needed, press and hold the vent button to purge any additional air from the process loop.
5. Set process temperature (SETPOINT) by pressing the Arrow or
6. If the unit does not maintain its process value, allow your process to reach the set point temperature. Refer to the controller manual should the controller need to be tuned.
Down Arrow keys.
Disconnect Switch
Up
Shut Down
1. Push STOP button.
2. Turn disconnect switch to OFF position.
Royal Series Water Temperature Control Units Page 31
Page 32
M2B+
Start Up
1. Turn disconnect switch to ON position.
2. Press START. The unit will automatically vent for approximately o ne minute.
3. If needed, press and hold the vent button to purge any additional air from the process loop.
4. Set process temperature (SETPOINT) by pressing the Arrow or
5. If the unit does not maintain its process value, allow your process to reach the set point temperature. Then Autotune the control by
pressing
Shut Down
1. Push STOP button.
2. Turn disconnect switch to OFF position.
4-4 Communications
Disconnect Switch
Up
Down Arrow keys.
key.
A connection port on the electrical cabinet permits easy hook-up to the host computer for RS-232C and RS-485 communications. The connection port is a direct pin-to-pin extension from the back of the controller. For pin outs, consult the enclosed controller owner’s manual.
Page 32 Royal Series Water Temperature Control Units
Page 33
5 Startup and Operation
5-1 Introduction
The checklist below outlines start-up procedures for Royal Series water temperature control units. This list assumes that installation information located in this manual has been read and followed.
5-2 Startup Checklist
Check the shipping papers against the serial tag to make sure
that system size, type, and voltage is correct for the process under control.
Check the transformer primary voltage connections to be sure
they are configured for the electrical power you are using. The voltage at the main power connection must be within plus or minus ten percent (±10%) of the voltage listed on the serial tag. Electrical connections must conform to all applicable codes. Make sure that a qualified electrician checks all electrical connections.
The safety thermostat is preset at the factory to 250ºF or 300ºF
(121ºC or 149ºC), depending on configuration. It trips at 265ºF or 315ºF (129ºC or 157ºC), depending on configuration.
The relief valve should be piped to an open, unrestricted drain. TO PROCESS, FROM PROCESS, WATER IN, WATER OUT,
MOLD PURGE connections should be complete.
and
! CAUTION
Only use components rated at a minimum of
150 psig and 250°F (1,034.25 kPa/10.34 bars and 121ºC).
All outer panels must be in place.  All external process valving should be set for proper operation
of the unit.
Cooling and/or makeup water between 16 psig and 55 psig
(110.32 kPa/1.1 bars and 379.2 kPa/3.79 bars) must be available for the unit to operate properly.
Royal Series Water Temperature Control Units Page 33
Page 34
Connect the main power to the unit disconnect switch, and
press the START switch to check for proper pump rotation direction as described in Section 5-6. Pump rotation should be clockwise, viewed from the motor end.
Check your work and proceed to the Startup Procedure
section on the following page.
5-3 Starting the Temperature Control Unit
Turn ON the water supply, turn the rotary disconnect to the ON
position, and push the START button.
The unit automatically executes a one-minute venting sequence
to expel air trapped in the process piping. Sterling recommends a longer venting sequence on larger process systems. Press and hold the VENT button to force the cooling/vent valve open and eliminate air trapped in the process piping in larger process systems.
The controller is OFF and the Vent Cycle indicator is lighted during the vent sequence.
Set the controller to the process temperature. Refer to the enclosed controller manual for details regarding
the auto-tuning process.
Watch the drain for any bubbles or erratic flow, which
indicates if the system has been properly vented. If the stream is steady, the unit was properly vented and all air is out of the system.
Operate the unit, checking for anything unusual that could
indicate improper operation.
Note: You can stop the Royal Series temperature control unit at
any time by pressing the
STOP button.
Page 34 Royal Series Water Temperature Control Units
Page 35
! CAUTION
1) Your Royal Series system operates with hot water under pressure. To reduce the risk of scalding:
• Always wear work gloves and safety glasses when operating the unit.
• Never operate the unit with panels or shields removed.
• Pipe the relief valve to an open drain.
• Never install a fitting or hose that is rated less than 150 psig and 250°F
(1,034.25 kPa/10.34 bars and 121ºC).
2) To reduce the risk of electrical shock:
• All electrical installation and repairs should be done by a qualified electrician.
• Ground the unit in accordance with electrical codes.
• Never attempt any repairs without first opening and locking out the main
disconnect.
• Never deactivate or neutralize any safety device.
5-4 Sequence of Operation
The simplicity of design and the highly engineered controller make this unit almost self-operating. The START, STOP, and VENT buttons and the temperature controller buttons are all that is required to operate this unit.
After you complete all connections, turn the water supply ON, then turn control power time of one (1) minute. If you need additional vent time, press the
VENT button on the control panel.
As the water comes in the water supply line, the water must enter the pump, up through the tank and out through the TO PROCESS line, through the process, back through the FROM PROCESS line, and through the solenoid line and out the drain line.
At this time, watching the drain for bubbles or erratic flow will indicate whether or not the system has been properly vented. If a steady stream flows from the drain line, it is certain that all the air is out of the system. If you have the unit connected to a central system, watch the pressure gauges for erratic pressure changes. If the gauge is steady, all the air is out of the system.
ON. The unit automatically vents for a preset
Royal Series Water Temperature Control Units Page 35
Page 36
TCU systems provide temperature control on processes by
directly heating the process water and injecting cooling water into the process water.
When the unit is energized, the pump starts and a one minute
vent sequence opens the cooling/vent valve to remove any air trapped in the process piping.
If the cooling water supply pressure is insufficient, the low
cooling water pressure cutout switch (set at 16 psig, 10 psig differential [110.32 kPa/1.10 bars, 68.95 kPa/0.69 bars differential]) opens, the LOW WATER PRESSURE indicator lights, and the unit does not operate until the pressure is 16 psig (110.32 kPa/1.10 bars) or more. You need at least 16 psig (110.32 kPa/1.10 bars) for the best cooling capacity and to prevent water boiling in the process circuit at high temperatures, particularly at the pump suction.
After venting, the microprocessor controller monitors the TO
PROCESS
discharge warm water or energizing the immersion heater to maintain the process set temperature.
RTD probe, cycling open the cooling/vent valve to
5-5 Checking Motor Rotation Direction
Check for correct pump rotation direction by looking at the top of the motor. Press the START button and the STOP button, and note the direction that the motor turns. Rotation should be clockwise when viewed from the motor end.
Note: Make sure that a qualified electrician performs the
following steps.
To change rotation direction:
1. Disconnect and lock out power at the fused disconnect.
2. Reverse any two incoming leads at the power terminal
blocks.
3. Do not switch leads at the motor or motor starters.
5-6 Shutting Down the Temperature Control Unit
Cool the unit down by selecting a set point of zero (0 ). Let the unit stabilize at one temperature close to the incoming water temperature, then press the STOP button. Now press the VENT button to relieve any remaining pressure in the system.
Page 36 Royal Series Water Temperature Control Units
Page 37
- Notes -
Royal Series Water Temperature Control Units Page 37
Page 38
6 Unit Maintenance
! CAUTION
Never attempt to service a unit until a qualified
electrician has opened and locked out the main
The water supply should be turned off and internal pressure should be relieved before you remove panels.
All electrical connections must be done by a qualified electrician.
disconnect using OSHA 1910.147 standards.
! WARNING
Disconnect all power to the unit, let the unit cool down, and turn off the water prior to any
servicing. Failure to do so can result in SERIOUS INJURY
OR DEATH!
6-1 Preventive Maintenance
Draining
Drain the unit thoroughly if you are taking it out of service for a long period of time, or you expose it to freezing. Drain plugs are provided at the base of the heater tank and at the base of the pump.
Page 38 Royal Series Water Temperature Control Units
Page 39
Periodic Checks
Every Six Months
Inspect all electrical connections for secure attachment and for safe and secure ground connections. Inspect the power cable, especially at the entrance point to the unit. This inspection should be made by a qualified electrician. Check for leaks, especially under the pump, as it may indicate a worn pump seal.
6-2 Corrective Maintenance
Pumps and Seals
Before leaving our factory, we test each unit extensively, then we calibrate each unit. Afterwards, the unit is drained and blown out with air to remove water from piping systems. If the unit is allowed to stand idle for a long time before being installed in your factory, the housing gasket at the pump can dry out and can possibly leak when the unit is started. In most cases these gaskets will soon swell and form a tight seal. In other cases, it may be necessary for you to tighten the pump bolts to stop a leaking condition.
Pump seal surfaces can separate slightly because of rough handling or from vibration during transit. This could cause a leak at the pump seal when the pump is started, but in most cases the surfaces will mate again after the pump is allowed to run for a short period of time. If they do not reseal, you may need to open the pump and free the seal by hand. It is seldom necessary to install a replacement seal in a new unit unless the seal has been damaged because the unit was started without water.
Our pump seals have a long period of service life. Some conditions, of course, can shorten seal life, including the presence of grit, operation of the unit without water, sustained high water temperature, or presence of certain chemicals in the water. Our pump seal assembly has been developed to resist abrasive particles that are present in many water systems. This is done by a special flushing system that uses water exiting the pump to constantly wash the seal area.
Royal Series Water Temperature Control Units Page 39
Page 40
It is also fitted with high temperature flexible components for maximum heat resistance. These same components remain flexible even at low temperatures. Thus, the standard seal is a fine combination of heat resistant and wear resistant components. Unfortunately, even under normal use, the seal will eventually wear and require replacement.
A small puddle underneath the unit is a sign of rotary seal wear, and if investigation confirms the pump as the source, the seal should be replaced as soon as practical. The water slinger is intended to provide temporary protection against this, but a continued and substantial leak will ruin the motor bearing and cause further damage.
After the unit has been in service for a period of years where abrasive conditions are present, you may find that the pump bracket (the top half of the pump casting), can be eroded away in the area around the seat of the rotary seal. This area should provide a straight, smooth bearing surface for the cup seal. Should your casting show signs of erosion in this area, the casting needs to be replaced. The replacement cost of the casting is very modest compared to the down time and maintenance cost for frequently replacing the seal.
Under some conditions, the pump may not start. After turning off the power supply, check the motor shaft to be certain it is free to turn. By removing the drip cover on top of the motor, you’ll have access to the end of the shaft. It has been slotted to make it easy to turn with a screwdriver. If the shaft is free to turn, next check that the motor overloads are set, check for blown fuses, and finally check the power supply on each leg to the motor. A qualified electrician should check the motor and its circuit.
Important!
If the pump motor wiring is disconnected for removal from the unit,
make sure that you check the actual rotation direction
when the motor is rewired to the unit.
A phase sensor does not always indicate proper rotation
if motor wire leads are reversed at installation.
Consult the elementary wiring diagram for more information.
Page 40 Royal Series Water Temperature Control Units
Page 41
Heaters
Heaters may need to be cleaned chemically or mechanically to remove deposits and dirt that reduce heat transfer and cause hot spots. Hot spots cause premature heater failure. Install a new gasket when reassembling. Make sure a qualified electrician disconnects and reconnects heater wires.
Solenoid Valves
Clean annually, more often if using high mineral content water
or on high service level units.
Sluggish operation, excessive leakage, and/or noise indicate
cleaning is necessary. Inspect the components for excessive wear while the valve is disassembled.
Rebuild kits are available from the Sterling Parts Department.
6-3 Restoring the Controller to Factory Setup
If the preset parameters on the controller have been tampered with and it no longer properly controls temperature, you can restore the controller to factory setup parameters. For more information on controller restoration, consult the enclosed controller owner’s manual.
6-4 Electrical Connections
Make sure that a qualified electrician inspects all electrical components and connections every six (6) months for secure attachment and ground connections. Inspect all wiring for fraying or damage, especially power lines where they enter the unit. All
wiring connections must be tight.
Royal Series Water Temperature Control Units Page 41
Page 42
6-5 Safety Devices
Make sure that only qualified electricians test safety devices!
Safety devices should be tested for function every six (6) months. Perform the following procedures for testing:
Motor Overload
Disconnect main power. Open the electrical enclosure and rotate the manual TEST button on the motor overload to the tripped position. Close the enclosure and reconnect main power. Push the
START button. The unit should not start and the Pump Overload
indicator should illuminate.
Press the RESET button. The unit is now ready for operation.
Pressure Switch
Caution!
With the unit running, program a set point of 30ºF (-1ºC). Allow the process temperature to drop under 100ºF (38ºC). When the process temperature reaches that point, turn off the water supply. The pump should stop and the Low Water Pressure indicator should illuminate. Turn the water supply on to reset the pressure switch.
Adjusting the Pressure Switch
The pressure switch used in your Royal Series water temperature control unit is factory set at 16 psig (110.3 kPa/1.1 bars). However, if the process does not require the unit to operate at 250ºF (121ºC), you can adjust the switch to meet your process needs.
Tools Required
• Small flat blade screwdriver
• #2 Phillips head screwdriver
Page 42 Royal Series Water Temperature Control Units
Page 43
! CAUTION
HAZARDOUS ELECTRICAL CURRENT PRESENT. Maintain a safe ground and disconnect the power
supply before servicing the unit.
Make sure a qualified electrician makes electrical
connections; disconnect/lock out electricity using
OSHA 20CFR 1910.147 standards when servicing the
To adjust the pressure switch: Using a small, flat-blade screwdriver, carefully remove the
plug at the top of the switch.
Figure 9
Pressure Switch
Side View and Top View
unit.
Phillips head screw
Under the plug is a Phillips-head adjusting screw: Turn the screw counterclockwise to reduce the pressure.
- or -
Turn the screw clockwise to increase the pressure.
A quarter turn (90º rotation) approximates 15 psi (103.4 kPa/
1.0 bars).
Replace the plug on the top of the switch.
If the plug gets damaged, the switch is still sealed internally.
Royal Series Water Temperature Control Units Page 43
Page 44
Safety Thermostat
Make sure that the high limit on the controller is set to the values listed in the following table, based on the switch adjustment. This prevents the pump from cavitating and damaging the seal, the switch, and heater element(s).
psig kPa Max. temp. ºF Max. temp. ºC
5 psig 34.4 kPa 227ºF 108ºC 10 psig 68.9 kPa 240ºF 116ºC 15 psig 103.4 kPa 250ºF 121ºC
Disconnect main power. Open the electrical enclosure and disconnect the neutral lead on the safety thermostat from the terminal strip. Protect the stripped lead to prevent short circuits. Close the enclosure, reconnect main power, and push the START button. The heater should not turn on and the Over Temperature indicator should illuminate. Disconnect main power before reconnecting the thermostat lead.
6-6 Cleaning and Storage
• Inspect the unit daily for leaks. Wipe down the unit
periodically to remove dirt and dust buildup, especially the motor casing.
• Drain and flush the unit every six (6) months to remove
sediment buildup.
• Completely drain the unit and carefully blow out the piping
with pressurized air before placing the unit in storage.
Page 44 Royal Series Water Temperature Control Units
Page 45
7 Troubleshooting
Condition Possible cause Solution
Check main disconnect, fuses, wiring, and power lead to unit. Voltage must be within plus or minus 10% of nameplate rating.
Locate and repair. Repair or replace.
Check for at least 16 psig (110.32 kPa/1.1 bars) water pressure on
WATER MAKEUP.
Open water supply. Reset and test each leg for
balanced amp draws. Verify proper rotation. If not
clockwise, reverse any two incoming power leads.
As long as there is satisfactory process temperature control there is no problem.
Clean the system. Check for closed valves etc. Be
sure all lines are properly sized. As long as there is satisfactory
process temperature control there is no problem.
Check for 25 psig (172.38 kPa/1.72 bars) water pressure on WATER IN or CITY WATER MAKEUP.
Jump power across switch and see if unit starts. Replace switch if needed.
WATER IN or CITY
Unit does not turn on.
Unit does not run.
Low pump pressure.
High pump pressure.
Pressure switch circuit is open.
No power. Wrong voltage supplied to unit.
Defective on/off switch. Replace. Control circuit fuse blown. Replace. Defective control transformer. Check transformer. Broken or loose wire in pump motor control circuit. Pump motor contactor holding coil is open.
Low water pressure light on.
Water supply to unit is turned off.
Pump overload light on.
Pump running in reverse. Foreign matter in the system. Clean the system.
System has minimal back pressure, and is operating at the far end of the pump curve.
Foreign matter obstructing system.
Restricted water flow. System has high back pressure,
and is operating at the near end of the pump curve; a low flow condition.
Insufficient cooling or makeup water pressure.
Switch is broken.
Royal Series Water Temperature Control Units Page 45
Page 46
Condition Possible cause Solution
Temperature fluctuations/ rapid cycling from hot to cold.
Unit overheats or does not cool.
Relief valve leaks.
Unit runs continuously cooling or heating, and cannot attain set point.
Undersized connectors/ water lines. Long connecting lines between unit and mold.
Serpentine flow through mold. Blocked water line in mold.
Quick disconnect fitting with check valve.
Increase size of connectors/ water lines. Move the unit closer to the mold and shorten connecting lines. Connect lines for parallel flow instead of series flow. Check mold for metal chips or lime buildup. Clean mold. Remove and replace fitting or valve.
Lime buildup in unit piping. Clean or replace.
Check unit by connecting ¾” line directly from To Process to From
Faulty TCU.
Process line. Run unit to determine if TCU controls set
point temperature. Reversed probes. Drain is plugged or excessive
back pressure is in drain line.
Switch To and From Process
probes.
Clear drain line or eliminate
back pressure condition.
Test solenoid valve by pressing Faulty solenoid valve.
VENT button and listen for valve
operation. Replace if faulty. Controller Cool output relay
open. Solenoid valve is not operating,
but
COOL LED is on.
Solenoid coil circuit is open.
Modulating valve is not operating, but OUT2 LED is on.
Insufficient pressure differential between cooling
OUT lines.
WATER IN and
Cooling valve is undersize. Foreign material under valve
seat. High system pressure.
Replace output relay.
Set process temperature to
minimum and check for
magnetism on solenoid coil top.
Check coil resistance. If MΩ
range, replace solenoid coil.
Set process temperature to
minimum and check for
complete travel of valve; .
Find a means to get less back
pressure in the
WATER OUT line.
Replace cooling valve with a
larger valve.
Manually open valve to clear
seat of material.
Reduce
WATER IN or MAKEUP
water pressure. Unit under-sized for application. Call sales representative.
Page 46 Royal Series Water Temperature Control Units
Page 47
Condition Possible cause Solution
Unit does not heat/cannot achieve set point.
Visually inspect coil and Defective heater contactor.
contacts; repair/replace
defective contactors.
Check resistance on all three (3) Defective immersion heater.
legs of the heater with an ohm
meter. If not all equal, contact
factory for replacement heater.
Check the heater output with an
ohm meter to ground. It should Controller heat output open.
read in the mega-ohm range.
Infinite or zero readings indicate
a defective output. Heater contactor is not
energizing, but
HEAT LED is on.
Immersion heater elements dirty.
Set process temperature to
maximum and check for control
voltage at heater contactor.
Remove heater and clean
elements.
Check heater tank for
scorched/discolored paint.
Check resistance on all three (3)
legs of the heater with an ohm Immersion heater element is burned out.
meter. Replace heater as
required.
Check for balanced amp draws,
and supply voltage. If not
present replace immersion
heater.
OUT1 indicator is on, but no
voltage on heater contact.
Replace relay board on
controller. Cooling valve is leaking. Dismantle valve and clean out.
Set process temperature to Solenoid valve is not operating, but
COOL LED is on.
minimum and check for
magnetism on top of solenoid
coil. Magnetism on coil. Clean coil.
Press
Faulty/dirty solenoid valve.
VENT button several times
to flush the valve.
Royal Series Water Temperature Control Units Page 47
Page 48
I Index
Automatic vent, 30 Available options, 8–9
Checking motor rotation
direction, 35
Cleaning and storage, 43 Closed circuit/direct injection
connections, 19 Communications, 31 Controller operation, 31 Cooling regulation, 30 Cooling water connections, 20
Copyright information, 2 Corrective maintenance, 38–40 Cutout switch, low pressure,
28 Deionized water applications,
19 Disclaimer information, 2
Distilled water applications, 18 Draining, 37
Electrical connections, 24, 40
Electrical subpanel, 26 Electricals, 30 Expansion tank, 20
External piping sizing
considerations, 16
General information
Available options, 8–9
Models covered, 7
Necessary documents, 6–7
Standard features, 8
Heater contactor, 29 Heaters, 28 High-mobility piping
considerations, 18
Identifying controls and features,
27–31
Communications, 31
Controller operation, 31
Identifying mechanical
controls and features, 27– 31
Identifying mechanical controls
and features, 27–31
Incomplete shipment, 13 Incorrect shipment, 13 Installation information, 16–26
Cooling water connections,
20
Electrical connections, 24
External piping sizing
considerations, 16
High-mobility piping
considerations, 18
Location considerations, 16 Permanent piping
considerations, 17
Process approach
temperature considerations, 16
Process water connections,
19
Process water
considerations, 18
System purge connections,
21
Location considerations, 16 Low pressure cutout switch,
28
Maintenance
Cleaning and storage, 43
Corrective maintenance, 38–
40
Draining, 37 Electrical connections, 40 Heaters, 40 Motor overload, 41 Periodic checks, 38 Pressure switch, 41 Preventive maintenance, 37 Pumps and seals, 38 Safety devices, 41, 40–43 Safety thermostat, 43
Solenoid valves, 40 Models covered, 7 Motorized modulating valves,
29 Necessary documents, 6–7 Options, 8–9
Periodic checks, 38 Permanent piping
considerations, 17
Pipe sizes for ¾ hp to 7½ hp
units, 17 Pressure drops, 23
Pressure relief valve, 27 Pressure switch, 31 Preventive maintenance, 37 Process approach
temperature
considerations, 16 Process water connections, 19
Process water considerations,
18
Pump curves
50 Hz pump curves, 23 60 Hz pump curves, 23
Pump starter, 29 Pumps, 28 Pumps and seals, 38
Raw water treatment, 18 Returns, 13
Safety considerations, 3 Safety devices, 40–43
Safety thermostat, 27 Sequence of operation, 34 Shipping damages, 12 Shipping information
Incomplete shipment, 13 Incorrect shipment, 13 Returns, 13 Shipping damages, 12 Uncrating, 14 Unpacking and inspection,
12
Shock stop, 29 Shutting down the unit, 35 Solenoid valves, 28
Specifications, 11 Standard features, 7–8
Starting the unit, 33 Startup and operation
Checking motor rotation
direction, 35 Sequence of operation, 34 Shutting down the unit, 35 Starting the unit, 33 Startup checklist, 32
Startup checklist, 32
Subpanel, 26 System purge connections, 21 TCU drawing, 10 TCU specifications, 11 TCU Upright drawing, 11
Thermocouple, 27 Thermostat, 27 To Process thermocouple, 27 Transformer, 29
Troubleshooting, 45–47 Typical piping schematic, 22 Uncrating, 14 Unit drawing, 10, 11
Unpacking and inspection, 12 Water hammer arrestor, 29
Page 48 Royal Series Water Temperature Control Units
Page 49
Parts Department
Call toll-free 7am–5pm CST [800] 423-3183 or call [262] 641-8610, Fax [262] 641-8653 The ACS Customer Service Group will provide your company with genuine OEM quality parts manufactured to engineering design specific ations, which will maximize your equipment’s performa nce and efficiency. To assist in expediting your phone or fax order, please have the model and serial number of your unit when you contact us. A customer replacement parts list is included in this manu al for your convenience. ACS welcomes inquiries on all your parts needs and is dedic ated to providing excellent customer service.
Service Department
Call toll-free 8am–5pm CST [800] 233-4819 or call [262] 641-8610 Emergencies after 5pm CST, call [847] 439-5655 We have a qualified service department ready to help. Service contracts are available for most products.
Sales Department
Call [262] 641-8610 Monday–Friday, 8am–5pm CST Our products are sold by a worldwide network of independent sales representatives. Contact our Sales Department for the name of the sales representative nearest you.
Contract Department
Call [262] 641-8610 Monday–Friday, 8am–5pm CST Let us install your system. The Contract Department offers any or all of these services: project planning; system packages including drawings; equipment, labor, and construction materials; and union or non­union installations.
[262]
2900 S. 160th Street
New Berlin, WI 53151
641-8610 • Fax
[262]
641-8653
www.sterlco.com
Royal Series Water Temperature Control Units Page 49
Loading...