State SSE5-120 User Manual

COMMERCIAL
MODELS
SSE 5 – 120
HEAVY DUTY COMMERCIAL ELECTRIC WATER HEATERS
FEATURES
ADVANCED ELECTRONIC CONTROL
State’s new proprietary electronic water heater control provides precise + or – 1°F temperature control that is ideal for industrial and food service applications where exact temperatures of hot water are needed.
iCOMM™ Compatible - Call 1.888.WATER02 for more information.
Plain English Text – Animated icons display detailed operational and diagnostic information. Fault or Alert messages appear if an operational issue occurs.
Element Sensing – Each element is constantly monitored and current on/off state is displayed, any element failure is reported and its exact location is shown. Eliminates guesswork, makes troubleshooting easy and helps keep the unit operating at maximum performance.
Low Water Cut Off – Factory standard on-board low water cutoff uses a remote electronic immersion type probe to prevent energizing of the elements in the event of low water condition and eliminates accidental dry firing.
Sequencing – Units with multiple element contactors are sequenced on with one-second delay between stages. Prevents high amp electrical loads from hitting the electric system all at once and provides a smoother operating unit. An adjustable modulating control is optional (See options).
For more information on Select® contact: State Water Heaters 500 Tennessee Waltz Parkway, Ashland City, TN 37015
800.365.0024 Toll-free USA www.statewaterheaters.com
SCESS00708 April 2011R
Economy Mode Operation – Control system automatically lowers the operating set point by a programmed value during user-defined time periods. Seven-day clock may be programmed for night set back and/or weekend shutdown to reduce operating cost and save energy.
INCOLOY IMMERSION HEATERS – Heavy-duty medium watt density elements
have incoloy sheathing and prewired leads: provides excellent protection against oxidation and scaling. Input ranges from 3kW to 90kW available (see accompanying chart).
HEAVY FOAM INSULATED – All models meet or exceed the standby loss
requirements of ASHRAE 90.1b-1992 and ASHRAE/IESNA 90.1-2004.
GLASS-LINED TANK – Glass coating provies superior protection against corrosion
and is bonded to all inner tank surfaces at 1600˚ F.
ASME TANK CONSTRUCTION – 125 psi working pressure (65 thru 120 gallons), 150
psi working pressure (5 thru 50 gallons).
THREE YEAR LIMITED WARRANTY – For complete warranty information consult
written warranty or contact State.
COMMERCIAL
FEATURES (Continued)
STANDARD VOLTAGES – 208, 240 and 480 volt single and three phase. Single phase 208 and 240 are convertible to three phase. All 208 and 240
volt at 24kW and below are supplied phase convertible (single to three and vice versa). 277 volt single phase also available. Consult factory for 120 volt power circuit availability.
TERMINAL BLOCK – To accept copper or aluminum leads (on units with more than one contactor).
120 VOLT CONTROL CIRCUIT – 120 volt control circuit powered by fused transformer.
MAGNETIC CONTACTORS – Heavy-duty UL rated for 100,000 cycles.
POWER CIRCUIT FUSING (120 AMP CURRENT DRAW AND ABOVE) – Meets National Electric Code and UL requirements
that water heaters must have internal fusing when current draw exceeds 120 amps.
SIMPLIFIED CIRCUITRY, COLOR-CODED FOR EASE OF SERVICE
BRASS DRAIN VALVE
HINGED CONTROL COMPARTMENT DOOR
CSA CERTIFIED AND ASME RATED T&P RELIEF VALVE
For more information on Select® contact: State Water Heaters 500 Tennessee Waltz Parkway, Ashland City, TN 37015
800.365.0024 Toll-free USA www.statewaterheaters.com
SCESS00708
April 2011R
COMMERCIAL
Tank Capacity
5 19 3 20 1/2 521 mm 16 1/4 412.75 mm 22 1/2 571.5 mm 5 1/4 133.35 mm 82 37.2
10 38 6 26 1/4 667 mm 18 3/4 476.25 mm 25 635 mm 5 1/4 133.35 mm 106 48.1
20 76 18 27 1/4 692 mm 20 1/2 520.7 mm 26 1/2 673.1 mm 5 3/4 146.05 mm 130 59
30 114 24 35 3/4 908 mm 20 1/2 520.7 mm 26 1/2 673.1 mm 5 3/4 146.05 mm 150 68
40 151 36 45 3/4 1,162 mm 20 1/2 520.7 mm 26 1/2 673.1 mm 5 3/4 146.05 mm 190 86.2
50 189 90 54 3/4 1,391 mm 20 1/2 520.7 mm 26 1/2 673.1 mm 5 3/4 146.05 mm 221 100.2
65 246 90 50 1/2 1,283 mm 26 1/2 673.1 mm 33 1/2 850.9 mm 7 177.8 mm 267 121.1
80 303 90 49 1/4 1,251 mm 28 711.2 mm 35 889 mm 7 177.8 mm 285 129.3
100 379 90 58 1/4 1,480 mm 28 711.2 mm 35 889 mm 7 177.8 mm 354 160.6
120 450 90 63 1/4 1,607 mm 30 762 mm 37 939.8 mm 7 1/2 190.5 mm 420 190.5
Maximum
kW Input
SSE
RECOVERY RATE IN GALLONS PER HOUR *
TEMPERATURE RISE °F
STANDARD
kW INPUT
BTU/HOUR 30° 40° 50° 60° 70° 80° 90° 100° 110° 120° 130° 140°
3 10,239 41 31 24 20 17 15 13 12 11 10 10 9
6 20,478 82 62 49 41 35 31 27 25 22 21 19 18
9 30,717 123 92 74 62 53 46 41 37 34 31 28 26
12 40,956 164 123 98 82 70 61 55 49 45 41 38 35
15 51,195 205 154 123 102 88 77 68 61 56 51 47 44
18 61,434 246 184 148 123 105 92 82 74 67 62 57 53
24 81,912 328 246 197 164 140 123 109 98 90 82 76 70
30 102,390 410 308 246 205 176 154 137 123 112 103 95 88
36 122,868 492 369 295 246 211 184 164 148 134 123 113 105
45 153,585 615 461 369 307 263 230 205 184 168 154 142 132
54 184,302 738 554 443 359 316 277 246 221 201 185 170 158
60 204,780 819 615 492 410 351 307 273 246 223 205 189 176
75 255,975 1025 768 615 512 439 384 341 307 279 256 236 219
90 307,170 1229 922 738 615 527 461 410 369 335 307 284 263
.tW gnippihS etamixorppA)mm( sehcnI ni snoisnemiD llA
.gK.sbLDCBAsretiLsnollaG
STANDARD kW INPUTS
Standard
kW Ratings
3 6
9 12 15
18 24 30
36 45 54
60** 4 15,000 4 4
75** 5 15,000 5 5 3
90** 5 18,000
* 208V models use one additional immersion heater.
** Available on 50 gallon models or larger.
*** Each immersion heater contains three electric elements.
No. of Wattage 208V 240V 480V
1 1 1 1 1
*1
2 2
*2
3 3
3,000 6,000
9,000 12,000 15,000
18,000 12,000 15,000
18,000 15,000 18,000
1
2
3
1
2
3
1
2
208V 240V 277V 480V 208V 240V 480V
14.4
28.8
43.3
57.7
72.1
86.5
115.4
144.2
173.1
216.3 N/A N/A N/A N/A
12.5
25.0
37.5
50.0
62.5
75.0
100.0
125.0
150.0
187.5
225.0
250.0 N/A N/A
10.8
21.2
32.5
43.3
54.2
65.0
86.6
108.3
130.0
162.5
194.9
216.6 N/A N/A
6.3
12.5
18.8
25.0
31.3
37.5
50.0
62.5
75.0
93.8
112.5 125 156 188
Designed for use as a recovery heater having its own storage tank or booster for supplying sanitizing rinse water for dishwashing.
For more information on Select® contact: State Water Heaters 500 Tennessee Waltz Parkway, Ashland City, TN 37015
800.365.0024 Toll-free USA www.statewaterheaters.com
SCESS00708
April 2011R
serepmA nI tnerruC daoL lluFsrotcatnoC A05 fo rebmuN***sretaeH noisremmI
8.3
16.7
25.0
33.3
41.6
50.0
66.6
83.3
99.9
124.9
149.9
166.7
208.4 250
7.2
14.4
21.7
28.9
36.1
43.3
57.7
72.2
86.6
108.3
129.9 145 181 217
esahP eerhTesahP elgniS
3.6
7.2
10.8
14.4
18.0
21.7
28.9
36.1
43.3
54.1
65.0 72 90
108
COMMERCIAL
OPTIONAL EQUIPMENT & CONSTRUCTION
STAINLESS STEEL TANK
D to the end of the model prefix for use with deionized water. For
example a SSE 100 would become a SSED 100.
(Please note: Stainless Steel units are for deionized water heating
applications only! SSED models are not approved or certified for
domestic potabalble water heating applications. To maintain
warranty for domestic potable hot water heating applications
use only the SSE glass lined models.)
– Available for deionized water. Add a
150 OR 160 PSI WORKING PRESSURE – Available when
required. Must be specified at time of order.
HANDHOLE CLEANOUT – 4”x 6” size.
COMBINATION TEMPERATURE/PRESSURE GAUGE – Dial
type combination gauge (shipped loose).
CONTROL OPTIONS
INDICATING/PILOT LIGHTS – For indicating element operation
and/or switch closure. Up to one indicating light available for each switch and/or contactor is available.
MODULATING CONTROL – The first element on is the first
element off. Not available on single element, single contactor units.
PRESSURE LIMIT SWITCHES – Both high and low pressure
limit switches available.
POWER CIRCUIT FUSING – Sub-divides internal circuitry with
maximum of 60 amp fuses. Supplied as standard when required by NEC and UL.
ALARM HORN
Horns may be furnished to warn of any condition in the heater for which sensors have been specified.
OPTIONAL INTERNATIONAL VOLTAGES – 380, 415, 575 and
600 volts three-phase available with Y connected elements.
OVERRIDE SWITCHES
or part of unit input to be controlled manually. Up to one override
switch per contactor is available.
– A simple form of load control allows all
SUGGESTED SPECIFICATION
The heater shall be a glass-lined State commercial electric model No. __________________ as manufactured by State Water Heaters. Heater should be rated at ______ kW, ______ volts, ______ phase, 50/60 cycle AC and constructed in accordance with ASME Code, shall bear appropriate symbol and be listed with the National Board as required. Heater shall be listed with Underwriters’ Laboratories and approved to The National Sanitation Foundation Standard No. 5. All internal surfaces of the tank shall be glass-lined with an alkaline borosilicate composition that has been fused-to-steel by firing at a temperature of 1600°F. Tank shall be cathodically protected with anodes. The entire vessel is to be enclosed in a round steel enclosure with baked enamel finish. Water heater shall have an electronic control with large LCD displaying current water heater status; provide real time element status and sensing, low water cutoff and economy mode operation. Shall house 120 volt control circuit transformer, transformer fusing, magnetic contactor(s), element fusing per N.E.C., and commercial grade incoloy sheathed flange mounted elements with prewired terminal leads. Temperature controls include limiting switch which will require resetting manually in the event the temperature reaches 190°F. Foam insulation exceeds the thermal efficiency and standby loss requirements of the U.S. Department of Energy and Current edition of ASHRAE/IESNA 90.1. Heater shall include CSA Certified and ASME Rated T&P relief valve and drain valve.
Water heater should incorporate the iCOMM™ system for remote monitoring, leak detection and fault alert.
For more information on Select® contact: State Water Heaters 500 Tennessee Waltz Parkway, Ashland City, TN 37015
800.365.0024 Toll-free USA www.statewaterheaters.com
SCESS00708
April 2011R
Loading...