State SDV7570PE Installation Manual

Instruction Manual for Light Duty Commercial Power Direct Vent Gas Water Heaters
ALL TECHNICAL AND WARRANTY QUESTIONS: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM
WHOM THE WATER HEATER WAS PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER.
–Do not store or use gasoline or other
–WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
–Installation and service must be performed
by a qualified installer, service agency or the gas supplier.
WARNING: If the information in these instructions are not followed exactly, a fire or explosion may result, causing property damage, personal injury or death.
Improper installation, adjustment, alter­ation, service or maintenance can cause DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE. Refer to this manual for assistance or consult the local gas utility for further information.
WARNING
Flammable vapors may be drawn by air cur­rents from other areas of the structure to this appliance.
WARNING
READ THE GENERAL SAFETY SECTION BEGINNING ON INSIDE COVER AND THEN THIS ENTIRE MANUAL BEFORE INSTALLING OR OPERATING THIS WATER HEATER.
WARNING
Save this Manual for Future Reference.
For Your Safety
AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER
0002917270-1
General Safety
2
WARNING
WATER HEATERS EQUIPPED FOR ONE TYPE GAS ONLY: This water heater is equipped for one type gas only. Check the model rating plate near the gas control valve for the correct gas. DO NOT USE THIS WATER HEATER WITH ANY GAS OTHER THAN THE ONE SHOWN ON THE MODEL RATING PLATE. Failure to use the correct gas can cause problems which can result in DEATH, SERI­OUS BODILY INJURY, OR PROPERTY DAMAGE. If you have any questions or doubts consult your gas supplier or local utility.
WARNING
A fire can start if combustible materials such as clothing, cleaning materials, or flammable liquids are placed against or next to the water heater.
WARNING
INSTALLATIONS IN AREAS WHERE FLAMMABLE LIQUIDS (VAPORS) ARE LIKELY TO BE PRESENT OR STORED (GARAGES, STORAGE, AND UTILITY AREAS, ETC): Flammable liquids (such as gasoline, solvents, propane (LP) or butane, etc.), all of which emit flammable vapors, may be improperly stored or used in such areas. The gas water heater ignitor or main burner can ignite such vapors. The resulting flashback and fire can cause death or serious burns to anyone in the area, as well as property damage. If installation in such areas is your only option, then the installation must be accomplished in a way that the ignitor and main burner flame are elevated from the floor at least 18 inches. While this may reduce the chances of flammable vapors from a floor spill being ignited, gasoline and other flammable substances should never be stored or used in the same room or area containing a gas water heater or other open flame or spark producing appliance. NOTE: Flammable vapors may be drawn by air currents from other areas of the structure to the appliance.
WARNING
HOTTER WATER CAN SCALD: Water heaters are intended to pro­duce hot water. Water heated to a temperature which will satisfy clothes washing, dish washing, and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infirm, or physically/mentally handicapped. If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible tem­perature setting that satisfies your hot water needs, some type of tempering device, such as a mixing valve, should be used at the hot water taps used by these people or at the water heater. Mixing valves are available at plumbing supply or hardware stores. Follow manufacturers instructions for installation of the valves. Before changing the factory setting on the thermostat, read the “Temperature Regulation” section in this manual.
WARNING
BEFORE LIGHTING [PROPANE (L.P.) GAS WATER HEATERS]: Propane (L.P.) gas is heavier than air. Should there be a leak in the system, the gas will settle near the ground. Basements or crawl spaces, closets and areas below ground level will serve as pockets for the accumulation of this gas. Before attempting to operate the water heater or turning on a nearby electrical light switch, be abso­lutely sure there is no accumulated gas in the area. Search for odor of gas by sniffing at ground level in the vicinity of the appliance. If odor is detected, follow steps indicated at “For Your Safety” on the cover page of this manual then leave the premises.
WARNING
Improper installation, adjustment, alteration, service or main­tenance can cause DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE. Refer to this manual or consult your local gas utility for further assistance.
WARNING
At the time of manufacture this water heater was provided with a combination temperature-pressure relief valve certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or mate­rials, as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, and the latest edition of ANSI Z21.22 and the code require­ments of ASME. If replaced, the valve must meet the require­ments of local codes, but not less than a combination temper­ature and pressure relief valve certified as meeting the require­ments for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22 by a nationally rec­ognized testing laboratory that maintains periodic inspection of production of listed equipment or materials. The valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 lbs. p.s.i.) and a discharge capacity not less than the water heater input rate as shown on the model rating plate. (Electric heaters - watts divided by 1000 x 3412 equal BTU/Hr. rate.) Your local jurisdictional authority, while mandating the use of a temperature-pressure relief valve complying with ANSI Z21.22 and ASME, may require a valve model different from the one furnished with the water heater. Compliance with such local requirements must be satisfied by the installer or end user of the water heater with a locally pre­scribed temperature-pressure relief valve installed in the des­ignated opening in the water heater in place of the factory fur­nished valve. For safe operation of the water heater, the relief valve must not be removed from it’s designated opening or plugged. The temperature-pressure relief valve must be installed direct­ly into the fitting of the water heater designated for the relief valve. Position the valve downward and provide tubing so that any discharge will exit only within 6 inches above, or at any distance below the structural floor. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circum­stances. Excessive length, over 30 feet, or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve. No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6″air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connect­ed to a drain or other suitable means, the water flow may cause property damage. The Discharge Pipe: —Must not be smaller in size than the outlet pipe size of the
valve, or have any reducing couplings or other restrictions. —Must not be plugged or blocked. —Must be of material listed for hot water distribution. —Must be installed so as to allow complete drainage of both
the temperature-pressure relief valve, and the discharge
pipe. —Must terminate at an adequate drain. —Must not have any valve between the relief valve and tank.
General Safety (cont’d)
3
WARNING
This water heater must not be installed directly on carpeting. Car­peting must be protected by a metal or wood panel beneath the ap­pliance extending beyond the full width and depth of the appliance by at least 3 inches (76.2mm) in any direction, or if the appliance is installed in an alcove or closet, the entire floor must be covered by the panel. Failure to heed this warning may result in a fire hazard.
WARNING
Do not install in a confined area such as a closet, unless you provide ventilation air as shown in the “Locating The New Water Heater” section. Never obstruct the flow of ventilation air. If you have any doubts or questions at all, call your gas company. Failure to pro­vide ventilation air can result in a fire or explosion and can cause DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
WARNING
If this water heater will be used in beauty shops, barber shops, clean­ing establishments, or self-service laundries with dry cleaning equip­ment, it is imperative that the water heater or water heaters be in­stalled so that combustion and ventilation air be taken from outside these areas. Refer to the “Locating The New Water Heater” section of this manual and also the latest edition of the National Fuel Gas Code, ANSI Z223.1, also referred to as NFPA 54 for specifics provided con­cerning air required.
WARNING
The power direct vent water heater requires its own (separate) venting system. It cannot be connected to an existing vent pipe or chimney. It must be terminated to the outdoors. Failure to properly install the venting system can result in asphyxiation, a fire or explosion and can cause DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
WARNING
No vent damper installation is compatible with this power vented water heater design. No vent damper, whether it is operated ther­mally or otherwise is to be installed on this power vented water heater. Alteration of any part of the factory-furnished vent assembly could result in improper operation due to restriction of flue gases, spillage of flue gases and may cause carbon monoxide poisoning.
WARNING
1. The appliance and its individual shutoff valve must be discon-
nected from the gas supply piping system during any pressure testing of the gas system at test pressures in excess of
1
2 pound
per square inch (3.5kPa).
2. The appliance must be isolated from the gas supply piping sys-
tem by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal or less than 1⁄2 pound per square inch (3.5kPa).
WARNING
Soot build-up indicates a problem that requires correction before further use. Turn “OFF” gas to water heater and leave “OFF” until repairs are made, because failure to correct the cause of the sooting can result in a fire or explosion causing DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
WARNING
The water heater must be properly vented outdoors. Never operate the water heater unless it is vented to the outdoors and has adequate air supply to avoid risks of improper operation, explosion or asphyxiation.
WARNING
Vent termination must not be within 4 feet of any items such as gas meters, gas valves or other gas regulating equipment.
WARNING
Obstructed or deteriorated vent systems may present a serious health risk or asphyxiation.
WARNING
Chemical vapor corrosion of the flue and vent system may occur if air for combustion contains certain chemical vapors. Spray can pro­pellants, cleaning solvents, refrigerator and air conditioner refrig­erants, swimming pool chemicals, calcium and sodium chloride, waxes, bleach, and process chemicals are typical compounds which are potentially corrosive.
WARNING
Minimum clearances between the water heater and combustible and non-combustible construction are: 0 inches from sides, 0 inch­es from back, 6 inches from front of jacket to closet door and 12 inches from top of jacket to combustible and non-combustible material. Minimum vent clearance: 0 inches. Provide 24 inches front clearance for servicing and adequate clearance between the jacket top and ceiling for servicing the flue area.
WARNING
HYDROGEN GAS: Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable and explosive. To prevent the possibility of injury under these condi­tions, we recommend the hot water faucet be opened for several minutes at the kitchen sink before any electrical appliances which are connected to the hot water system are used (such as a dish­washer or washing machine). If hydrogen gas is present, there will probably be an unusual sound similar to air escaping through the pipe as the hot water faucet is opened. There must be no smoking or open flame near the faucet at the time it is open.
WARNING
INSULATING JACKETS: When installing an external water heater insulation jacket on a gas water heater: a. DO NOT cover the temperature-pressure relief valve. b. DO NOT put insulation over any part of the top of the gas water
heater.
c. DO NOT put insulation over the gas control valve or gas con-
trol valve/burner cover, or any access areas to the burner.
d. DO NOT let insulation around the gas water heater to get with-
in 8 inches of the floor (air must get to the burner).
e. DO NOT cover or remove operating instructions, and safety
related warning labels and materials affixed to the water heater.
Failure to heed this will result in the possibility of a fire or explosion.
WARNING
Flood damage to a water heater may not be readily visible or imme­diately detectible. However, over a period of time a flooded water heater will create dangerous conditions which can cause DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE. Call a qual­ified service technician or contractor to replace a flooded water heater. Do not attempt to repair the unit! It must be replaced!
CAUTION
WATER HEATERS EVENTUALLY LEAK: Installation of the water heater must be accomplished in such a manner that if the tank or any connections should leak, the flow of water will not cause dam­age to the structure. For this reason, it is not advisable to install the water heater in an attic or upper floor. When such locations cannot be avoided, a suitable drain pan should be installed under the water heater. Drain pans are available at your local hardware store. Such a drain pan must have a minimum length and width of at least 2 inches greater than the water heater dimensions and must be piped to an adequate drain. Drain pan depth must allow for access to the outer doors for servicing the ignitor and burner. Under no circum­stances is the manufacturer to be held liable for any water damage in connection with this water heater.
General Safety...............................................................................................................................2-3
Table of Contents .........................................................................................................................4
Introduction.........................................................................................................................................5
Preparing for the New Installation..................................................................5
Typical Installation.....................................................................................................................6
Locating the New Water Heater......................................................................7-9
Facts to Consider About Location.......................................................................................................................7-8
Combustion Air and Ventilation .........................................................................................................................8-9
Venting Clearances ..........................................................................................................................................8-9
Air for Ventilation for Appliances Located in Confined Spaces ..............................................................................9
Installing the New Water Heater................................................................10-20
Water Piping .......................................................................................................................................................10
Temperature-Pressure Relief Valve ......................................................................................................................11
Filling the Water Heater ......................................................................................................................................12
Wiring............................................................................................................................................................12-13
Optional Field Installed Wiring ....................................................................................................................12-13
Wiring Diagram.................................................................................................................................................13
Venting ..........................................................................................................................................................13-18
Gas Piping......................................................................................................................................................18-19
Installation Checklist ...........................................................................................................................................20
Operating..........................................................................................................................................21-23
Temperature Regulation..................................................................................................24
For Your Information......................................................................................................25-26
Start Up Conditions .............................................................................................................................................25
Condensation ....................................................................................................................................................25
Smoke/Odor......................................................................................................................................................25
Thermal Expansion............................................................................................................................................25
Strange Sounds..................................................................................................................................................25
Operational Conditions..................................................................................................................................25-26
Smelly Water.....................................................................................................................................................25
"Air” In Hot Water Faucets ................................................................................................................................26
High Temperature Shut Off System....................................................................................................................26
Venting Manual Reset Switch ............................................................................................................................26
Not Enough or No Hot Water............................................................................................................................26
Water Is Too Hot...............................................................................................................................................26
Periodic Maintenance....................................................................................................27-28
Venting System Inspection...................................................................................................................................27
Burner Inspection ................................................................................................................................................27
Burner Cleaning ..................................................................................................................................................27
L.P. Gas Control Valve & Burner Assembly Replacement Information .................................................................27
Housekeeping .....................................................................................................................................................28
Oiling Instructions...............................................................................................................................................28
Temperature-Pressure Relief Valve Operation......................................................................................................28
Draining..............................................................................................................................................................28
Service ................................................................................................................................................................28
Leakage Checkpoints............................................................................................................29
Troubleshooting.......................................................................................................................30-33
Installation Diagrams.....................................................................................................34-35
Repair Parts....................................................................................................................................36-37
Table of Contents
4
Abbreviations Found In This Instruction Manual
CSA - Canadian Standards Association ANSI - American National Standards Institute NFPA - National Fire Protection Association
3. If after reading this manual you have any questions or do not understand any portion of the instructions, call the local gas utility or the manufacturer whose name appears on the rating plate.
4. Carefully plan the place where you are going to put the water heater. Correct combustion, vent action, and intake air and exhaust vent pipe installation are very important in preventing death from possible carbon monoxide poisoning and fires.
Examine the location to ensure the water heater com­plies with the “Locating the New Water Heater” section in this manual.
5.
For California installation this water heater must be braced, anchored, or strapped to avoid falling or moving during an earthquake. See instructions for correct installation pro­cedures. Instructions may be obtained from your local dealer, wholesaler, public utilities or California Office of the State Architect, 400 P Street, Sacramento, CA 95814.
6. Massachusetts Code requires this water heater to be installed in accordance with Massachusetts 248-CMR
2.00: State Plumbing Code and 248-CMR 5.00.
7. Complies with SCAQMD rule #1121 and districts having equivalent NOx requirements.
Introduction
Thank You for purchasing this water heater. When
installed according to State and Local Codes and main­tained according to the manufacturers instructions, it should give you years of trouble free service.
1. Read the “General Safety” section, pages 2 and 3 of this manual first and then the entire manual carefully. If you don’t follow the safety rules, the water heater will not operate properly. It could cause DEATH, SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE. This manual contains instructions for the installation, operation, and maintenance of the gas-fired water heater. It also contains warnings through out the manu­al that you must read and be aware of. All warnings and all instructions are essential to the proper operation of the water heater and your safety. Since we cannot put everything on the first few pages, READ THE ENTIRE
MANUAL BEFORE ATTEMPTING TO INSTALL OR OPERATE THE WATER HEATER.
2. The installation must conform with the instructions in this manual; gas company rules; and Local Codes, or in the absence of Local Codes, with the latest edition of the National Fuel Gas code, ANSI Z223.1, also referred to as NFPA 54. This publication is available from your local government or public library or gas company or by writ­ing NFPA, Batterymarch Park, Quincy, MA 02269.
Preparing for the New Installation
5
WARNING
This gas-fired water heater is design certified by CSA INTERNATIONAL under American National Standard/CSA Standard for Gas Water Heaters, ANS Z21.10.3 • CSA 4.3 (latest edition). The installation must conform with this manual, Local Codes and with the lat­est edition of the National Fuel Gas Code, ANSI Z223.1. This publication is available from your local government or public library, gas company, or by writing NFPA, Batterymarch Park, Quincy, MA 02269.
WARNING
Toxic chemicals such as used for treatment of boilers or non-potable water heating appliances shall never be intro­duced into a potable water space heating system.
WARNING
This water heater shall not be connected to any heating systems or component(s) previously used with a non­potable water heating appliance. If this water heater is also used for space heating applica­tions, all piping and components connected to the water heater shall be suitable for use with potable water.
Typical Installation
6
COLD WATER INLET
HOT WATER OUTLET
TEMPERED
WATER OUTLET
EXHAUST
VENT TO
OUTDOORS
GAS
SUPPLY
TEMPERATURE-
PRESSURE RELIEF
VALVE
MIXING
VALVE
DISCHARGE PIPE
(Do not cap or plug)
PROVIDE A 6″AIR GAP BETWEEN THE END OF
THE DISCHARGE PIPE
AND DRAIN
7' POWER CORD (Factory supplied)
INTAKE FOR
COMBUSTION
AIR
FLUE PRODUCTS DISCHARGE PIPE
AIR INTAKE PIPE
Vacuum Relief required by some codes (refer to local codes)
SHUTOFF VALVE
NOTE: To protect against untimely corrosion of hot and cold water fittings, it is strongly recommended that di-electric unions or couplings be installed on this water heater when connected to copper pipe.
This appliance has been design certified as complying with American National Standard/CSA Standard for water heaters and is con­sidered suitable for:
Water (Potable) Heating: All models are “considered suitable for water (potable) heating.” Water (Potable) Heating and Space Heating: Certain models are “considered suitable for water (potable) heating and space heating.”
Refer to the model and rating plate of the water heater.
WARNING
If this water heater is to be used for multiple location users, such as for apartments, hotels, motel, duplexes, a tempering device should be used at each point of use (sink, shower, tub, etc.) to limit the maximum temperature of the hot water to 125°F. This will help to reduce, but not eliminate the risk of scald or serious burn injury form exposure to hot water. Water at a temperature above 125°F, can cause 3rd degree burn injuries which are the most serious burns and require skin grafts and results in permanent scarring or even death. Some people are more likely to be permanently injured by hot water than others; these include the elderly, children, the infirm, or the physically/mentally handi­capped. Before immersing yourself or anyone else in hot water, be sure to check the water temperature. WARNING: HOTTER WATER INCREASES THE RISK OF SCALD INJURY. (Also see “Temperature Regulation” section) Mixing valves are available at plumbing supply or hardware stores. Follow manufacturer’s instructions for installation of these valves.
7
Facts to Consider About the Location
You should carefully choose an indoor location for the new water heater, because the placement is a very important consideration for the safety of the occupants in the building and for the most econom­ical use of the appliance. This water heater is not for use in manu-
factured (mobile) homes or outdoor installation.
Whether replacing an old water heater or installing the water heater in a new location, the following critical points must be observed.
1. The location selected should be indoors as close as practical to the vent termination point, and as centralized with the water pip­ing system as possible. The water heater, as all water heaters, will eventually leak. Do not install without adequate drainage provi­sions where water flow will cause damage.
2. If vented through an outside wall or through the roof using 3vent piping, the total vent run (vertical and horizontal) cannot exceed a total of 45 feet with one elbow. If more elbows are required, the venting distance must be reduced 5 feet for every 90° elbow. See page 15 for vent chart.
3. Vent piping cannot slope downward and horizontal runs require
1
8per five foot rise. All horizontal runs require adequate support
at 31⁄2 foot intervals and vertical runs supported at 5 foot intervals.
4. The water heater requires its own (separate) venting system. It cannot be connected to an existing vent pipe or chimney. It must terminate to the outdoors. Whenever possible terminate the vent on the leeward side of the building through an outside wall. Note:
Condensation may be created, at times, as the combustion gases exit the vent cap and discoloration of surfaces in proximity to the vent cap may occur.
5. The water heater comes equipped with a 7 foot power cord which can be used to connect to a 110/120 volt power source if (1) local codes allow, and (2) there is a three prong receptacle available.
Locating the New Water Heater
6. The location selection must provide adequate clearances for servicing and proper operation of the water heater.
Figure 1
WARNING
This water heater must not be installed directly on carpeting. Carpeting must be protected by a metal or wood panel beneath the appliance extending beyond the full width and depth of the appliance by at least 3 inches (76.2mm) in any direction, or if the appliance is installed in an alcove or clos­et, the entire floor must be covered by the panel. Failure to heed this warning may result in a fire hazard.
WARNING
Minimum clearances between the water heater and combustible and non-combustible construction are: 0 inches from sides, 0 inches from back, 6 inches from front of jacket to closet door and 12 inches from top of jacket to combustible and non-com­bustible material. Minimum vent clearance: 0 inches. Provide 24 inches front clearance for servicing and adequate clearance between the jacket top and ceiling for servicing the flue area.
WARNING
Propellants of aerosol sprays and volatile compounds, (cleaners, chlorine based chemicals, refrigerants, etc.) in addition to being highly flammable in many cases, will also change to corrosive hydrochloric acid when exposed to the combustion products of the water heater. The results can be hazardous, and also cause product failure.
WARNING
INSTALLATION IN AREAS WHERE FLAMMABLE LIQUIDS (VAPORS) ARE LIKELY TO BE PRESENT OR STORED (GARAGES, STORAGE AND UTILITY AREAS, ETC): Flammable liquids (such as gasoline, solvents, propane (LP) or butane, etc.) or other substances (such as adhesives, etc.), all of which emit flammable vapors, may be improperly stored or used in such areas. The gas water heater ignitor or main burner can ignite such vapors. The resulting flash­back and fire can cause death or serious burns to anyone in the area, as well as property damage. If installation in such areas is your only option, then the installation must be accomplished in a way that the ignitor and main burner flame are elevated from the floor at least 18 inches. While this may reduce the chances of flammable vapors from a floor spill being ignited, gasoline and other flammable substances should never be stored or used in the same room or area containing a gas water heater or other open flame or spark producing appliance. Also, the water heater must be located and/or protected so it is not subject to physical damage by a moving vehicle. NOTE: Flammable vapors may be drawn by air currents from other areas of the structure to the appliance.
CAUTION
WATER HEATERS EVENTUALLY LEAK: Installation of the water heater must be accomplished in such a manner that if the tank or any connections should leak, the flow of water will not cause damage to the structure. When such locations cannot be avoid­ed, a suitable drain pan should be installed under the water heater. Drain pans are available at your local hardware store. Such a drain pan must have a minimum length and width of at least 2 inches greater than the water heater dimensions and must be piped to an adequate drain. Drain pan depth must allow for access to the outer doors for servicing the ignitor and burner. Under no circumstances is the manufacturer to be held liable for any water damage in connection with this water heater.
WARNING
Do not use an extension cord. If there is not a suitable recepta­cle with ground and/or local codes prohibit use of a power cord, field wiring must be provided.
WARNING
The power direct vent water heater requires its own (separate) venting system. It cannot be connected to an existing vent pipe or chimney. It must be terminated to the outdoors. Failure to properly install the venting system can result in asphyxia­tion, a fire or explosion and can cause DEATH, SERIOUS BOD­ILY INJURY, OR PROPERTY DAMAGE.
12min.
FORCED AIR
INLET
12min.
36min. IF “A” DIMENSION
IS LESS THAN 120
12min.
PD VENT
TERMINAL
PD VENT
TERMINAL
12min.
GRADE
“A”
CORNER INSTALLATION
OF INLET AND OUTLET
NOT RECOMMENDED
8
Locating the New Water Heater (cont’d)
Figure 2
Combustion Air and Exhaust
Venting Through an Outside Wall – Clearances
0clearance for 3PVC, ABS, or CPVC Schedule 40 piping from combustible surfaces.
18minimum in all directions from any obstruction, such as a wall, that may interfere.
12minimum from the ground and corners, 9ceiling over­hangs. Figure 2.
The Power Direct Vent outlet terminal shall terminate at least 36above any forced air inlet located within 10 feet. Figure 3.
The Power Direct Vent outlet terminal shall terminate at least 12below 12horizontally from or 12above any door, win­dow or gravity air inlet into the building. Figure 3.
18minimum from other natural draft (gravity) direct vent, power vent or power direct vent appliance inlet and/or outlet vent(s) when directly above or 135° to either side of center line. Figure 4, page 9.
24minimum from any appliance inlet and/or outlet vents when directly below or 45° to either side of center line. Figure 4, page 9.
The location selection must provide clearances for servicing and proper operation of the water heater. Figure 5.
Vent termination must not be within 4 feet of any items such as gas meters, gas valves or other gas regulating equipment.
The venting system must be installed in a manner which allows inspection of the installation of the venting pipes and joints as well as periodic inspection after installation as required by the National Fuel Gas Code ANSI Z223.1.
Facts to Consider About the Location (cont’d)
Figure 3
WARNING
Failure to have required clearances between water heater and combustible material will result in a fire hazard.
WARNING
Vent termination must not be within 4 feet of any items such as gas meters, gas valves or other gas regulating equipment.
WARNING
When determining the installation location for a power direct vent water heater, snow accumulation and drift­ing should be considered in areas where applicable.
WARNING
If this water heater will be used in beauty shops, barber shops, cleaning establishments, or self-service laundries with dry clean­ing equipment, it is imperative that the water heater or water heaters be installed so that combustion and ventilation air be taken from outside these areas. Refer to the “Locating The New Water Heater” section of this manual and also the latest edition of the National Fuel Gas Code, ANSI Z223.1, also referred to as NFPA 54 for specifics provided concerning air required.
WARNING
Do not install in a confined area such a closet, unless you provide ventilation air as shown in the “Locating The New Water Heater” section. Never obstruct the flow of ventila­tion air. If you have any doubts or questions at all, call your gas company. Failure to provide ventilation air can result in a fire or explosion and can cause DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
C
Lof Flue
9min. from any overhang
12min.
12min.
Must maintain adequate service and maintenance accessibility.
Range of degrees available for vent pipe installation.
Figure 5
Figure 7
Locating the New Water Heater (cont’d)
9
Figure 6
Air for Ventilation for Appliances Located in Confined Spaces
Air for ventilation should be provided if installed in a confined space. Refer to the National Fuel Gas Code, ANSI Z223.1.
Figure 4
WIRE FENCE
When the water heater outlet terminal is low enough to be touched accidentally, or is accessible to small children, a wire mesh chain link fence (as shown in Figure 6) may be used. Care should be taken to maintain adequate ventila­tion around the outlet terminal. If a chain link fence is installed, it must not be used as a storage area for items that may block proper ventilation.
NOT TO BE USED AS
A STORAGE AREA
Venting Through Roof – Clearances
0clearance for 3PVC, ABS, or CPVC Schedule 40 piping from combustible surfaces.
The Vent Exhaust outlet and air inlet terminals shall terminate at least 18 inches above the roof surface. Figure 7.
The venting system must be installed in a manner which allows inspection of the installation of the venting pipes and joints as well as periodic inspection after installation as required by ANSI Standards.
24
NATURAL DRAFT (GRAVITY) DIRECT VENT, POWER VENT, OR POWER DIRECT VENT APPLIANCE INLET AND/OR OUTLET VENT(S).
VENT OUTLET AIR INTAKE
18
61⁄2MIN. 24MAX.
18
45˚
18
45° VENT CAP
W/SCREEN
90° STREET ELL
Installing the New Water Heater
SHUTOFF
VALVE
COLD INLET WATER LINE
HOT OUTLET
TO HOUSE
TEMPERATURE-
PRESSURE RELIEF
VALVE
DISCHARGE PIPE
(Do not cap or plug)
PROVIDE A 6″AIR
GAP BETWEEN THE
END OF THE
DISCHARGE PIPE
AND DRAIN
EXHAUST VENT
TO OUTDOORS
INTAKE FOR
COMBUSTION
AIR
GAS
SUPPLY
Water Piping
This water heater shall not be connected to any heating systems or component(s) used with a non-potable water heating appliance.
If a water heater is installed in a closed water supply sys­tem; such as one having a back-flow preventer, check valve, water meter with a check valve, etc. in the cold water supply; means shall be provided to control thermal expansion. Contact the water supplier or plumbing con­tractor on how to control this situation.
NOTE: To protect against untimely corrosion of hot and cold water fittings, it is strongly recommended that dielec­tric unions or couplings be installed on this water heater when connected to copper pipe.
The illustration shows the attachment of the water piping to the water heater. The water heater is equipped with 3/4 inch water connections.
NOTE: If using copper tubing, solder tubing to an adapter before attaching the adapter to the cold water inlet con­nection. Do not solder the cold water supply line directly to the cold water inlet or it will harm the dip tube.
NOTE: This water heater is insulated to minimize heat loss from the tank. Further reduction in heat loss can be accomplished by insulating the hot water lines from the water heater.
10
FLUE PRODUCTS DISCHARGE PIPE
AIR INTAKE PIPE
WARNING
HOTTER WATER CAN SCALD: Water heaters are intend­ed to produce hot water. Water heated to a temperature which will satisfy clothes washing, dish washing, and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infirm, or physical­ly/mentally handicapped. If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible tem­perature setting that satisfies your hot water needs, some type of tempering device, such as a mixing valve, should be used at the hot water taps used by these people or at the water heater. Mixing valves are available at plumbing supply or hardware stores. Follow manufacturers instruc­tions for installation of the valves. Before changing the factory setting on the thermostat, read the “Temperature Regulation” section in this manual.
Temperature-Pressure Relief Valve
Installing the New Water Heater (cont’d)
TEMPERATURE-
PRESSURE RELIEF
VALVE
DISCHARGE PIPE
(Do not cap or plug)
PROVIDE A 6″AIR
GAP BETWEEN THE
END OF THE
DISCHARGE PIPE
AND DRAIN
11
COLD
TEMPERED
WATER
OUTLET
HOT
WARNING
The temperature-pressure relief valve must be manually oper­ated at least once a year. Caution should be taken to ensure that (1) no one is in front of or around the outlet of the tem­perature-pressure relief valve discharge line, and (2) the water manually discharged will not cause any bodily injury or prop­erty damage because the water may be extremely hot.
If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instruc­tions, and replace the temperature-pressure relief valve with a new one.
WARNING
At the time of manufacture this water heater was provided with a combination temperature-pressure relief valve certi­fied by a nationally recognized testing laboratory that main­tains periodic inspection of production of listed equipment or materials, as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, and the latest edition of ANSI Z21.22 and the code requirements of ASME. If replaced, the valve must meet the requirements of local codes, but not less than a combina­tion temperature and pressure relief valve certified as meet­ing the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22 by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equip­ment or materials. The valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 lbs. p.s.i.) and a discharge capacity not less than the water heater input rate as shown on the model rating plate. (Electric heaters - watts divided by 1000 x
3412) equal BTU/Hr. rate. Your local jurisdictional authority, while mandating the use of a temperature-pressure relief valve complying with ANSI Z21.22 and ASME, may require a valve model different from the one furnished with the water heater. Compliance with such local requirements must be satisfied by the installer or end user of the water heater with a local­ly prescribed temperature-pressure relief valve installed in the designated opening in the water heater in place of the factory furnished valve. For safe operation of the water heater, the relief valve must not be removed from it’s designated opening or plugged. The temperature-pressure relief valve must be installed directly into the fitting of the water heater designated for the relief valve. Position the valve downward and provide tubing so that any discharge will exit only within 6 inches above, or at any distance below the structural floor. Be cer­tain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet, or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve. No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6″air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage. The discharge pipe: —Must not be smaller in size than the outlet pipe size of
the valve, or have any reducing couplings or other restric-
tion. —Must not be plugged or blocked. —Must be of material listed for hot water distribution. —
Must be installed so as to allow complete drainage of both
the temperature-pressure relief valve, and the discharge pipe. —Must terminate at an adequate drain. —Must not have any valve between the relief valve and tank.
RELIEF VALVE OPENING
“THIS WATER HEATER IS PROVIDED WITH A COMBINATION TEMPER­ATURE-PRESSURE RELIEF VALVE. FOR SAFE OPERATION OF THE WATER HEATER, THE RELIEF VALVE(S) MUST NOT BE REMOVED FROM ITS DESIGNATED POINT OF INSTALLATION OR PLUGGED.”
YOUR LOCAL JURISDICTIONAL AUTHORITY, WHILE MANDATING THE USE OF A TEMPERATURE-PRESSURE RELIEF VALVE COMPLYING WITH ANSI Z21.22 AND ASME, MAY REQUIRE A VALVE MODEL DIF­FERENT FROM THE ONE FURNISHED WITH THE WATER HEATER.
COMPLIANCE WITH SUCH LOCAL REQUIREMENTS MUST BE SATIS­FIED BY THE INSTALLER OR END USER OF THE WATER HEATER WITH A LOCALLY PRESCRIBED TEMPERATURE-PRESSURE RELIEF VALVE INSTALLED IN THE DESIGNATED OPENING IN THE WATER HEATER.
SEE MANUAL HEADING—“TEMPERATURE-PRESSURE RELIEF VALVES” FOR INSTALLATION AND MAINTENANCE OF RELIEF VALVE, DISCHARGE LINE AND OTHER SAFETY PRECAUTIONS.
Installing the New Water Heater (cont’d)
12
Filling the Water Heater
To fill the water heater with water:
1. Close the water heater drain valve by turning the handle to the right (clockwise). The drain valve is on the lower front of the water heater.
2. Open the cold water supply valve to the water heater.
NOTE: The cold water supply valve must be left open when the water heater is in use.
3. To insure complete filling of the tank, allow air to exit by opening the nearest hot water faucet. Allow water to run until a constant flow is obtained. This will let air out of the water heater and the piping.
4. Check all new water piping for leaks. Repair as needed.
Wiring
The water heater comes equipped with a 7 foot power cord which can be used to connect to a 110/120 volt power source if, (1) local codes allow, and (2) there is a three prong receptacle available.
This unit must have a grounded
outlet to operate.
You must provide all wiring, (1) to a receptacle or, (2) between the water heater and junction box when the power cord is not used.
OPTIONAL Field Installed Wiring
1. Provide a way to easily shut off the electric power when working on the water heater. This could be with a cir­cuit breaker or fuse block in the entrance box or a sepa­rate disconnect switch.
2. Install and connect a circuit directly from the main fuse or circuit breaker box. This circuit must be the right size and have its own fuse or circuit breaker.
WIRE NUTS
GREEN
GROUND SCREW
CONDUIT
You must provide all wiring of the proper size outside of the water heater. You must obey local codes and electric company requirements when you install this wiring.
If you are not familiar with electric codes and practices, or if you have any doubt in your ability to connect the wiring to this water heater, obtain the service of a competent elec­trician. Contact a local electrical contractor and/or the local electric utility.
7’ MAXIMUM
CORD LENGTH
(Factory Supplied)
3. A standard 1⁄2conduit opening has been made in the water heater junction box for the conduit connection.
4. Use wire nuts and connect the power supply wiring to the wires inside the water heater’s junction box.
CAUTION
If wiring from the fuse box or circuit breaker box was aluminum for the old water heater, replace it with copper wire. If you wish to reuse the existing aluminum wire, have the connection at the water heater made by a competent electrician. Contact a local electrical contractor and/or the local electric utility.
WARNING
WATER HEATERS EQUIPPED FOR ONE TYPE VOLTAGE ONLY: This water heater is equipped for 110/120 volts only. DO NOT USE THIS WATER HEATER WITH ANY VOLTAGE OTHER THAN THE ONE SHOWN ABOVE. Failure to use the correct voltage can cause problems which can result in DEATH, SERIOUS BODILY INJURY OR PROPERTY DAMAGE. If you have nay questions or doubts consult your electric company.
WARNING
This appliance must be grounded for safety and to insure proper operation. Failure to do so could result in DEATH, SERIOUS BODILY INJURY OR PROPERTY DAMAGE.
WARNING
Do not use an extension cord. If there is not a suitable receptacle and/or local codes prohibit use of a power cord, field wiring must be provided.
CAUTION
Never use this water heater unless it is completely filled with water. To prevent damage to the tank, the tank must be filled with water. Water must flow from the hot water faucet before turning “ON” gas to the water heater.