State SBD85 500NE Service Manual

Instruction Manual
COMMERCIAL GAS WATER HEATERS
MODELS SBD85500NE &
SBD85500PE
SERIES 120/121
INSTALLATION - OPERATION - SERVICE
500 Tennessee Waltz Pkwy
Ashland City, TN 37015
- MAINTENANCE - LIMITED WARRANTY
ANSI / NSF 5
ASME CRN
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do
not use any phone in your building.
Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier,
call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Thank you for buying this energy effi cient water heater. We appreciate your confi dence in our products.
PLACE THESE INSTRUCTIONS ADJACENT TO HEATER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.
PRINTED IN THE U.S.A. 0510 318298-000
Read and understand this instruction manual and the safety messages herein before installing, operating or servicing this water heater.
Failure to follow these instructions and safety messages could result in death or serious injury.
This manual must remain with the water heater.
TABLE OF CONTENTS
SAFE INSTALLATION, USE AND SERVICE.......................................... 3
GENERAL SAFETY INFORMATION ................................................... 4-5
Precautions ........................................................................................ 4
INTRODUCTION .................................................................................... 6
Qualifi cations ..................................................................................... 6
FEATURES AND COMPONENTS ......................................................... 7
The Eliminator (Self Cleaning System) .............................................. 7
High Limit Switch ............................................................................... 7
Electronic Ignition Control .................................................................. 7
Exhaust Inducer (blower Assy.) ......................................................... 7
Uncrating ........................................................................................... 7
INSTALLATION CONSIDERATIONS ................................................ 8-11
Rough In Dimensions ........................................................................ 8
Recovery Capacities .......................................................................... 8
Gas and Electrical Characteristics ..................................................... 8
Locating The Water Heater ................................................................ 9
Leveling ............................................................................................. 9
Clearances ........................................................................................ 9
Installation on Combustible Flooring ............................................... 10
Insulation Blanket ............................................................................ 10
Hard Water ...................................................................................... 10
Circulation Pumps ...................................................................... 10-11
INSTALLATION REQUIREMENTS ................................................. 11-14
Supply Gas Regulator ......................................................................11
Power Supply ...................................................................................11
Mixing Valves ....................................................................................11
Dishwashing Machines .................................................................... 12
Closed Water Systems .................................................................... 12
Thermal Expansion .......................................................................... 12
Temperature-Pressure Relief Valve ............................................ 12-13
Contaminated Air ............................................................................. 13
Air Requirements ............................................................................. 13
Unconfi ned Space ...........................................................................14
Confi ned Space ............................................................................... 14
Exhaust Fans ............................................................................................ 14
Louvers and Grilles ................................................................................... 14
Vent Reducer ................................................................................... 14
VENTING INSTALLATION .............................................................. 14-18
Venting ............................................................................................. 14
Multiple Heater Manifold .................................................................. 15
Fresh Air Opening for Confi ned Spaces .......................................... 15
Outdoor Air Through Two Openings ................................................ 15
Outdoor Air Through One Opening .................................................. 15
Outdoor Air Through Two Horizontal Ducts ..................................... 15
Outdoor Air Through Two Vertical Ducts .......................................... 16
Air From Other Indoor Spaces ......................................................... 16
Technical Data Venting ............................................................... 17-18
WATER HEATER INSTALLATION ...................................................19-22
Water Line Connections .................................................................. 19
Water (Potable) Heating and Space Heating............................................19
Thermometer (Not Supplied) ....................................................................19
Water Piping Diagrams ............................................................................. 19
T&P Valve Discharge Pipe ............................................................... 19
Installation Diagrams ....................................................................... 20
Code Restrictions ............................................................................ 20
Heater Wiring ................................................................................... 21
Gas Piping ....................................................................................... 22
Purging ............................................................................................ 22
Gas Pressure Regulator .................................................................. 22
OPERATION ......................................................................................... 23
General ............................................................................................ 23
Filling ............................................................................................... 23
Adjustments ..................................................................................... 23
SEQUENCE OF OPERATION ............................................................. 23
Lighting & Operation Label .............................................................. 24
Checking Venting ............................................................................. 25
Checking the Igniter Assembly ........................................................ 25
Igniter Assembly .............................................................................. 25
Main Burner ..................................................................................... 25
Gas Valves ....................................................................................... 25
Checking the Input ........................................................................... 26
MAINTENANCE ................................................................................... 26
Venting System ................................................................................ 26
Remote Storage Tank Temperature Control .................................... 26
Temperature-Pressure Relief Valve Test ......................................... 26
Hot Water Odor ................................................................................ 27
Anode Rod Inspection ..................................................................... 27
Draining and Flushing ...................................................................... 27
To Drain the Water Heater Storage Tank ..................................................27
To Flush the Water Heater Storage Tank ..................................................27
Recommended Procedure for Periodic Removal or Lime Deposits
from the Tank Type\ Commercial Water Heaters ............................. 28
DeLiming Solvents ........................................................................... 28
Tank Cleanout Procedure ...........................................................28-29
Ignition Module System ................................................................... 29
SERVICE .............................................................................................. 29
Electrical Servicing .......................................................................... 29
FOR YOUR INFORMATION ................................................................. 30
Start up Conditions .......................................................................... 30
Operational Conditions .................................................................... 30
"Air" in the Water Faucets .........................................................................30
High Water Temperature Shut off System ................................................30
Sequence of Operation Flow Chart ................................................. 31
Operational Checklist ...................................................................... 32
WATER PIPING DIAGRAMS ........................................................... 33-47
WARRANTY ......................................................................................... 48
2
SAFE INSTALLATION, USE AND SERVICE
The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others.
Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the meaning of each safety message is understood by you and others who install, use, or service this water heater.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates an imminently
DANGER
WARNING
CAUTION
hazardous situation which, if not avoided, will result in injury or death.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in injury or death.
CAUTION indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury.
CAUTION used without the safety alert
CAUTION
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message, and how to avoid the risk of injury.
The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of potential exposure to such substances.
This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm. This appliance can cause low level exposure to some of the substances listed in the Act.
symbol indicates a potentially hazardous situation which, if not avoided, could result in property damage.
APPROVALS
ASME CRN
ANSI / NSF 5
3
GENERAL SAFETY INFORMATION
Fire or Explosion Hazard
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Avoid all ignition sources if you smell gas.
Do not expose water heater controls to excessive gas pressure.
Use only the gas shown on the water heater rating label. Maintain required clearances to combustibles.
Keep ignition sources away from faucets after extended periods of non-use.
Read instruction manual before
installing, using or servicing
water heater.
Breathing Hazard - Carbon Monoxide Gas
Do not obstruct water heater air intake with insulating blanket.
Gas and carbon monoxide detectors are available.
Install water heater in accordance with the instruction manual.
Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.
CAUTION
Property Damage Hazard
Fire Hazard
For continued protection against risk of fire:
Do not install water heater on carpeted floor.
Do not operate water heater if flood damaged.
Fire and Explosion Hazard
Use joint compound or Teflon tape compatible with propane gas.
Leak test before placing the water heater in operation.
Disconnect gas piping and main gas shutoff valve before leak testing.
Install sediment trap in accordance with NFPA 54.
Fire and Explosion Hazard
Do not use water heater with any gas other than the gas shown on the rating label.
Excessive gas pressure to gas valve can cause serious injury or death.
Turn off gas lines during installation. Contact a qualified installer or service
agency for installation and service.
All water heaters eventually leak.
Do not install without adequate drainage.
Electrical Shock Hazard
Turn off power to the water heater
before performing any service.
Label all wires prior to disconnecting
when performing service. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
Failure to follow these instructions can
result in personal injury or death.
Jumping out control circuits or components can
result in property damage, personal injury or death.
Service should only be performed by a qualified service
agent using proper test equipment.
Altering the water heater controls and/or wiring in any way
could result in permanent damage to the controls or water heater and is not covered under the limited warranty.
Altering the water heater controls and/or wiring in any way
could result in altering the ignition sequence allowing gas to flow to the main burner before the hot surface igniter is at ignition temperature causing delayed ignition which can cause a fire or explosion.
Any bypass or alteration of the water
heater controls and/or wiring will result
in voiding the appliance warranty.
4
GENERAL SAFETY INFORMATION
Read and understand this instruction manual and the safety messages herein before installing, operating or servicing this water heater.
Failure to follow these instructions and safety messages could result in death or serious injury.
This manual must remain with the water heater.
Water temperature over 125°F (52°C) can cause severe burns instantly resulting in severe injury or death.
Children, the elderly and the physically or mentally disabled are at highest risk for scald injury.
Feel water before bathing or showering.
Temperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures.
Explosion Hazard
Overheated water can cause water tank explosion.
Properly sized temperature and pressure relief valve must be installed in the opening provided.
CAUTION
Improper installation, use and service may result
in property damage.
Do not operate water heater if flood damaged.
Inspect and anode rods regularly, replace if damaged.
Install in location with drainage.
Fill tank with water before operation.
Properly sized thermal expansion tanks are required on all
closed water systems.
Refer to this manual for installation and service.
Verify the power to the water heater is turned off before performing any service procedures.
GENERAL SAFETY INFORMATION
PRECAUTIONS
DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN UNDER WATER. Immediately call a qualifi ed service agency to inspect the appliance and to make a determination on what steps should be taken next.
If the unit is exposed to the following, do not operate heater until all corrective steps have been made by a qualified service agency.
External fi re.1.
Damage.2.
Firing without water.3.
GROUNDING INSTRUCTIONS
This water heater must be grounded in accordance with the National Electrical Code and/or local codes. These must be followed in all cases.
This water heater must be connected to a grounded metal, permanent wiring system; or an equipment grounding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the water heater, see Figure 20.
HYDROGEN GAS FLAMMABLE
Explosion Hazard
Flammable hydrogen gases may be present.
Keep all ignition sources away from faucet when turning on hot water.
Hydrogen gas can be produced in a hot water system served by this appliance that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely ammable. To reduce the risk of injury under these conditions, it is recommended that a hot water faucet served by this appliance be opened for several minutes before using any electrical appliance connected to the hot water system. If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to fl ow. THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN.
5
INTRODUCTION
Thank You for purchasing this water heater. Properly installed and maintained, it should give you years of trouble free service.
ABBREVIATIONS USED
Abbreviations found in this Instruction Manual include :
ANSI - American National Standards Institute• ASME - American Society of Mechanical Engineers• GAMA - Gas Appliance Manufacturer’s Association• NEC - National Electrical Code• NFPA - National Fire Protection Association• UL - Underwriters Laboratory• CSA - Canadian Standards Association
QUALIFICATIONS
QUALIFIED INSTALLER OR SERVICE AGENCY
Installation and service of this water heater requires ability equivalent to that of a Qualifi ed Agency (as defi ned by ANSI
below) in the fi eld involved. Installation skills such as plumbing, air supply, venting, gas supply and electrical supply are required in addition to electrical testing skills when performing service.
ANSI Z223.1 2006 Sec. 3.3.83: “Qualifi ed Agency” - “Any individual, fi rm, corporation or company that either in person or through a representative is engaged in and is responsible for (a) the installation, testing or replacement of gas piping or (b) the connection, installation, testing, repair or servicing of appliances and equipment; that is experienced in such work; that is familiar with all precautions required; and that has complied with all the requirements of the authority having jurisdiction.”
If you are not qualifi ed (as defi ned by ANSI above) and licensed or certifi ed as required by the authority having jurisdiction to perform a given task do not attempt to perform any of the procedures described in this manual. If you do not understand the instructions given in this manual do not attempt to perform any procedures outlined in this manual.
6
FEATURES AND COMPONENTS
THE ELIMINATOR (SELF-CLEANING SYSTEM)
These units include The Eliminator (Self-Cleaning System) installed in the front water inlet, See Figure 1. The Eliminator must be oriented correctly for proper function. There is a marked range on the pipe nipple portion of the Eliminator, that must be aligned with the top of the inlet spud. A label above the jacket hole has an arrow that will point to the marked portion of the pipe nipple if the orientation is correct. If the arrow does not point within the marked range on the pipe nipple, adjust the pipe nipple to correct. A pipe union is supplied with the Eliminator to reduce the probability of misaligning the Eliminator accidentally while tightening the connection to the inlet water supply line. Improper orientation of the Eliminator can cause poor performance of the heater and can signifi cantly reduce outlet water temperatures during heavy draws.
Note: The inlet tube may have 1, 3 or 7 cross tubes.
FIGURE 1
For proper function, the Eliminator must be oriented correctly. There is a marked range on the pipe nipple that must be aligned with the top of the inlet spud (check for label on the appliance) to assure proper operation. Please check to confirm that the marked range is in alignment with the top of the spud. A pipe union is supplied with the Eliminator to help eliminate the possibility of changing the orientation by accidentally overtightening the inlet supply. Improper orientation of the Eliminator may cause temperature buildup issues or spells of colder than usual water temperatures.
HIGH LIMIT SWITCH
The digital thermostat (Figure 2) contains the high limit (energy cutoff) sensor. The high limit switch interrupts main burner gas ow should the water temperature reach 203°F (95°C).
In the event of high limit switch operation, the appliance cannot be restarted unless the water temperature is reduced to approximately 120°F (49°C). The high limit reset button on the front of the control then needs to be depressed.
Continued manual resetting of high limit control, preceded by higher than usual water temperature is evidence of high limit switch operation. The following is a possible reason for high limit switch operation:
• A malfunction in the thermostatic controls would allow the gas valve to remain open causing water temperature to exceed the thermostat setting. The water temperature would continue to rise until high limit switch operation.
Contact your dealer or service agent if continued high limit switch operation occurs.
ELECTRONIC IGNITION CONTROL
Each heater is equipped with a ignition module. The solid sate ignition control (Figure 3), ignites the main burner by utilizing a silicone nitride ignitor. The silicone nitride ignitor shuts off during the heating cycle and the main burner fl ame is sensed through a remote fl ame sensor integral to the silicone nitride ignitor assembly.
The ignition control will try to ignite the main burner three times before lockout. Then it waits one hour before trying again to ignite the main burners. This is a continuous cycle.
IGNITION CONTROL BOARD
FIGURE 3
EXHAUST INDUCER (BLOWER ASSY.)
The SBD85500NE/SBD85500PE models are equipped with an exhaust inducer. The inducer assists in drawing in fresh air to the unit for combustion and then assists in dispensing the combustion by-products into the venting leading outside.
The exhaust inducer is equipped with a gravity controlled damper to reduce the amount of heat loss through the fl ue, improving effi ciency.
DIGITAL THERMOSTAT
FIGURE 2
EXHAUST INDUCER
FIGURE 4
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN SERIOUS PERSONAL INJURY OR DEATH.
UNCRATING
The heater is shipped with the inducer already installed. The wiring conduit runs from the thermostat to the inducer. Before turning unit on, check to make sure the wiring conduit is securely plugged into the inducer.
7
ROUGH IN DIMENSIONS
INSTALLATION CONSIDERATIONS
FRONT VIEW
TOP
OUTLET
1 1/2” NPT
TOP
F
INLET
1 1/2” NPT
BACK VIEW
TOP VIEW
TABLE 1. ROUGH-IN-DIMENSIONS
FIGURE 5
Connections
Inlet (NPT) Outlet (NPT)
Approx. Ship Weight
Lbs/ Kgs.
745 857
338 389
Model
SBD85500NE/
SBD85500PE
SBD85500NE/
SBD85500PE
Input Rate
Btu/Hr Kw/Hr
500,000 85
Approximate
Tank Cap
147 322
Dimensions in Inches/cm
Gas
G/L
ABCDEF
81.50 17.50 77.25 67.50 27.13 21.00 1.00 67.50 8.00 27.75
207 44 196 171 69 53 3 171 20 70
Inlet
GH
Vent
Dia
IJ
Top Front Back Top Front Back Std.
1.50 1.50 1.50 1.50 1.50 1.50
1.50 1.50 1.50 1.50 1.50 1.50
TABLE 2. RECOVERY CAPACITIES, based on 80% effi ciency
Input Rate
Model
SBD85500NE/
SBD85500PE 500,000 85 1616 1212 970 808 693 606 539 485 441 404 373 346
SBD85500NE/
SBD85500PE 147 322 6118 4588 3671 3059 2622 2294 2039 1835 1668 1529 1412 1311
Btu/Hr Kw/Hr
Approximate
Tank Cap
G/L
30°F 40°F 50°F 60°F 70°F 80°F 90°F 100°F 110°F 120°F 130°F 140°F
(-1)°C 4°C 10°C 15°C 21°C 27°C 32°C 38°C 43°C 49°C 54°C 60°C
Recovery Rating Capacities (GPH and LPH)
TABLE 3. GAS AND ELECTRICAL CHARACTERISTICS
Model Type of Gas Inches of W.C. kPA Volts/Hz Amperes SBD85500NE/SBD85500PE Natural 3.50" 0.87 120/60 <5 SBD85500NE/SBD85500PE Propane 10.00" 2.48 120/60 <5
ASME
Lbs/ Kgs.
8
INSTALLATION CONSIDERATIONS
LOCATING THE WATER HEATER
CAUTION
Property Damage Hazard
All water heaters eventually leak.
Do not install without adequate drainage.
When installing the heater, consideration must be given to proper location. Location selected should be as close to the stack or chimney
as practicable, with adequate air supply and as centralized with the piping system as possible.
Fire or Explosion Hazard
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Avoid all ignition sources if you smell gas.
Do not expose water heater controls to excessive gas pressure.
Use only the gas shown on the water heater rating label. Maintain required clearances to combustibles.
Keep ignition sources away from faucets after extended periods of non-use.
Read instruction manual before
installing, using or servicing
water heater.
THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED, OPERATED OR REPAIRED. FLAMMABLE VAPORS ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE HEATER’S PILOT OR MAIN BURNER FLAMES CAUSING FIRE OR EXPLOSION. SOME LOCAL CODES PERMIT OPERATION OF GAS APPLIANCES IN SUCH AREAS IF THEY ARE INSTALLED 18” OR MORE ABOVE THE FLOOR. THIS MAY REDUCE THE RISK IF LOCATION IN SUCH AN AREA CANNOT BE AVOIDED.
DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A CARPETED FLOOR. A FIRE HAZARD MAY RESULT. Instead the water heater must be placed on a metal or wood panel extending beyond the full width and depth by at least 3 inches in any direction. If the heater is installed in a carpeted alcove, the entire fl oor shall be covered by the panel. Also, see the DRAINING requirements in MAINTENANCE Section.
THE HEATER SHALL BE LOCATED OR PROTECTED SO IT IS NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST NEVER BE PLACED ON OR ADJACENT TO THE HEATER. OPEN CONTAINERS OR FLAMMABLE MATERIAL SHOULD NOT BE STORED OR USED IN THE SAME ROOM WITH THE HEATER.
THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT WILL BE SUBJECT TO FREEZING.
LOCATE IT NEAR A FLOOR DRAIN. THE HEATER SHOULD BE LOCATED IN AN AREA WHERE LEAKAGE FROM THE HEATER OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE ADJACENT AREA OR TO LOWER FLOORS OF THE STRUCTURE.
WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE DRAIN PAN SHOULD BE INSTALLED UNDER THE HEATER. Such pans should be fabricated with sides at least 2” deep, with length and width at least 2” greater than the diameter of the heater and must be piped to an adequate drain. The pan must not restrict combustion air fl ow.
LEVELING
If the unit is not level, insert the bolts which were used in crating into the legs to correct this condition.
CLEARANCES
This water heater is approved for installation on combustible ooring (with Installation on Combustible Flooring #9003425205) in an alcove when the minimum clearance from any combustion construction are followed as indicated in Figure 7 and Table 4.
In all installations the minimum combustible clearances from vent piping shall be 6” (152mm). Vent piping passing through a combustible wall or ceiling must be a continuous run (no joints) and retain the 6” (152mm) clearance unless an approved reducing thimble is used.
A service clearance of 24” (610mm) should be maintained from serviceable parts, such as relief valves, fl ue baffl es, thermostats, cleanout openings or drain valves.
The units are approved for installation with side, rear and ceiling clearances as indicated below:
TABLE 4
MINIMUM CLEARANCES TO COMBUSTIBLES IN INCHES (mm)
"A"
RIGHT
MODEL
SBD85500NE/
SBD85500PE
SIDE
5"
(12.7 mm)
TABLE 5
MINIMUM CLEARANCES TO NONCOMBUSTIBLE CONSTRUCTION
"A"
RIGHT
MODEL
SBD85500NE/
SBD85500PE
SIDE
0 0 0 12"
"B"
LEFT
SIDE
5"
(12.7 mm)
"B"
LEFT
SIDE
"C"
BACK
5"
(12.7 mm)
"C"
BACK
"D"
CEILING
20"
(508mm)
"D"
CEILING
(305 mm)
9
.
FIGURE 6
INSTALLATION ON COMBUSTIBLE FLOORING
The SBD85500NE/SBD85500PE is approved for installations on combustible fl ooring when installed with leg kit number
9003425205.
INSULATION BLANKET
Breathing Hazard - Carbon Monoxide Gas
Do not obstruct water heater air intake with insulating blanket.
Gas and carbon monoxide detectors are available.
Install water heater in accordance with the instruction manual.
Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.
Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. The water heaters covered by this manual meet or exceed the Energy Policy Act standards with respect to insulation and standby heat loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you should follow these instructions. See the Features and Components section of this manual for identifi cation of components mentioned below. Failure to follow these instructions can restrict the air fl ow required for proper combustion, potentially resulting in fi re, asphyxiation, serious personal injury or death.
DO NOT apply insulation to the top of the water heater, as this will interfere with safe operation of the draft hood.
DO NOT cover the gas valve, thermostat or the Temperature­Pressure Relief Valve.
DO NOT allow insulation to come within 2” (5 cm) of the burners, to prevent blockage of combustion air fl ow to the burners.
DO NOT allow insulation to come within 9 inches (23 cm) of fl oor, (within 2 inches (5 cm) of bottom cover) to prevent blockage of combustion air fl ow to the burners..
DO NOT cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.
DO obtain new warning and instruction labels from the manufacturer for placement on the blanket directly over the existing labels.
DO inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air fl ow.
HARD WATER
FIGURE 7
Unit needs to be lifted in a way not to damage unit or laid 1.
on it’s side to access the bottom of the legs.
Slide leg extension under leg and the bolt up through the 2.
bottom hole located in the bottom of the leg.
Once in place, screw nut down and secure.3.
Front of leg should line up with front of leg extension as 4.
shown to make sure weight of unit is distributed through the leg extension.
Where hard water conditions exist, water softening or the threshold type of water treatment is recommended. This will protect the dishwashers, coffee urns, water heaters, water piping and other equipment.
See the Maintenance Section in this manual for sediment and lime scale removal procedures.
CIRCULATION PUMPS
A circulating pump is used when a system requires a circulating loop or there is a storage tank used in conjunction with the water heater. See Water Piping Diagrams in this manual for installation location of circulating pumps.
See the Circulation Pump Wiring Diagrams in this manual for electrical hookup information. Install in accordance with the current edition of the National Electrical Code, NFPA 70 or the Canadian Electrical Code, CSA C22.1.
All-bronze circulators are recommended for used with commercial water heaters.
10
Some circulating pumps are manufactured with sealed bearings and do not require further lubrication. Some circulating pumps must be periodically oiled. Refer to the pump manufacturer’s instructions for lubrication requirements.
CIRCULATING PUMP WIRING DIAGRAM
STORAGE TANK OR BUILDING RECIRCULATION
FIELD SUPPLIED TEMPERATURE CONTROL INSTALLED IN THE STORAGE TANK
NOTE: USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT. DO NOT SHARE POWER WITH APPLIANCE AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION.
L1 HOT
OR CIRCULATING LOOP RETURN LINE
CIRCULATING PUMP WIRING DIAGRAM
DISHWASHER LOOP WITH TOGGLE SWITCH
DISHWASHER TOGGLE SWITCH
NOTE: USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT. DO NOT SHARE POWER WITH APPLIANCE AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION.
L1 HOT
FIELD SUPPLIED TEMPERATURE CONTROL INSTALLED IN THE CIRCULATING LOOP RETURN LINE
L2 NEUTRAL
120 VAC POWER
FIGURE 8
CIRC
PUMP
MOTOR
INSTALLATION REQUIREMENTS
SUPPLY GAS REGULATOR
The water heater covered by this manual requires a supply gas regulator to be installed in the supply gas line serving the water heater for proper operation. Supply gas regulators are required on high and low pressure gas supply systems.
NOTE: On multiple water heater installations each water heater shall have its own dedicated supply gas regulator installed in the supply gas line serving the water heater.
Supply gas regulators must be rated at or above the input Btu/ hr rating of the water heater they supply. Supply gas regulators shall have inlet and outlet connections not less than the minimum supply gas line size for the water heater they serve as shown in Table 5. The Maxitrol 325-7L or equivalent is recommended.
See Supply Gas Regulator Installation on page 11.
POWER SUPPLY
The water heaters covered in this manual require a 120 VAC, 1Ø (single phase), 60Hz, 15 amp power supply and must also be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/ NFPA 70 or the Canadian Electrical Code, CSA C22.1.
MIXING VALVES
Water temperature over 125°F (52°C) can cause severe burns instantly resulting in severe injury or death.
Children, the elderly and the physically or mentally disabled are at highest risk for scald injury.
Feel water before bathing or showering.
Temperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures.
L2 NEUTRAL
120 VAC
POWER
FIGURE 9
CIRC
PUMP
MOTOR
Water heated to a temperature which will satisfy clothes washing, dish washing, and other sanitizing needs can scald and cause permanent injury upon contact. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the water heater’s temperature setting by up to 20°F (11°C).
Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infi rm and the physically/mentally disabled. Table 6 shows the approximate time-to-burn relationship for normal adult skin. If anyone using hot water provided by the water heater being installed fi ts into one of these groups or if there is a local code or state law requiring a certain water temperature at the point of use, then special precautions must be taken.
In addition to using the lowest possible temperature setting that satisfi es the demand of the application a Mixing Valve should be installed at the water heater (see Figure 10) or at the hot water taps to further reduce system water temperature.
Mixing valves are available at plumbing supply stores. Consult a Qualifi ed Installer or Service Agency. Follow mixing valve manufacturer’s instructions for installation of the valves.
TABLE 6
Water Temperature
Time to Produce 2nd & 3rd
Degree Burns on Adult Skin
180°F (82°C) Nearly instantaneous
170°F (77°C) Nearly instantaneous
160°F (71°C) About 1/2 second
150°F (66°C) About 1-1/2 seconds
140°F (60°C) Less than 5 seconds
130°F (54°C) About 30 seconds
120°F (49°C) More than 5 minutes
11
DISHWASHING MACHINES
All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water fl ow pressures between 15 and 25 pounds per square inch (103 kPa and 173 kPa). Flow pressures above 25 pounds per square inch (173 kPa), or below 15 pounds per square inch (103 kPa), will result in improperly sanitized dishes. Where pressures are high, a water pressure reducing or fl ow regulating control valve should be used in the 180°F (82°C) line to the dishwashing machine and should be adjusted to deliver water pressure between these limits.
A properly sized thermal expansion tank must be installed on all closed systems to control the harmful effects of thermal expansion. Contact a local plumbing service agency to have a thermal expansion tank installed.
See Water Line Connections on page 19 and the Water Piping Diagrams beginning on page 33.
TEMPERATURE-PRESSURE RELIEF VALVE
Explosion Hazard
HOT WATER
OUTLET
12” TO 15” (30-38 cm)
TEMPERED WATER
OUTLET
COLD
WATER
INLET
CHECK
VALV E
TO TANK
INLET
CHECK
VALV E
MIXING
VALV E
Figure 10
The National Sanitation Foundation also recommends circulation of 180°F (82°C) water. Where this is done, the circulation should be very gentle so that it does not cause any unnecessary turbulence inside the water heater. The circulation should be just enough to provide 180°F (82°C) water at the point of take-off to the dishwashing machine.
Adjust fl ow by throttling a full port ball valve installed in the circulating line on the outlet side of the pump. Never throttle fl ow on the suction side of a pump. See Water Piping Diagrams in this manual.
CLOSED WATER SYSTEMS
Water supply systems may, because of code requirements or such conditions as high line pressure, among others, have installed devices such as pressure reducing valves, check valves, and back fl ow preventers. Devices such as these cause the water system to be a closed system.
THERMAL EXPANSION
As water is heated, it expands (thermal expansion). In a closed system the volume of water will grow when it is heated. As the volume of water grows there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent Temperature-Pressure Relief Valve operation: water discharged from the valve due to excessive pressure build up. This condition is not covered under the limited warranty. The Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion.
Temperature-Pressure Relief Valve must comply with ANSI Z21.22­CSA 4.4 and ASME code.
Properly sized temperature­pressure relief valve must be installed in opening provided.
Can result in overheating and excessive tank pressure.
Can cause serious injury or death.
This water heater is provided with a properly rated/sized and certifi ed combination Temperature-Pressure Relief Valve (T&P valve) by the manufacturer. The valve is certifi ed by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, and the code requirements of ASME.
If replaced, the new T&P valve must meet the requirements of local codes, but not less than a combination Temperature­Pressure Relief Valve rated/sized and certifi ed as indicated in the above paragraph. The new valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 psi = 1,035 kPa) and a discharge capacity not less than the water heater Btu/hr or kW input rate as shown on the water heater’s model rating label.
NOTE: In addition to the factory installed Temperature-Pressure Relief Valve on the water heater, each remote storage tank that may be installed and piped to a water heating appliance must also have its own properly sized, rated and approved Temperature­Pressure Relief Valve installed. Call the toll free technical support phone number listed on the back cover of this manual for technical assistance in sizing a Temperature-Pressure Relief Valve for remote storage tanks.
For safe operation of the water heater, the Temperature-Pressure Relief Valve must not be removed from its designated opening nor plugged. The Temperature-Pressure Relief Valve must be installed directly into the fi tting of the water heater designed for the relief valve. Install discharge piping so that any discharge will exit the pipe within 6 inches (15.2 cm) above an adequate fl oor drain, or external to the building. In cold climates it is recommended that it be terminated at an adequate drain inside the building. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve.
12
No valve or other obstruction is to be placed between the Temperature-Pressure Relief Valve and the tank. Do not connect discharge piping directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water fl ow may cause property damage.
CAUTION
Water Damage Hazard
Temperature-Pressure Relief Valve discharge
pipe must terminate at adequate drain.
regarding the Temperature-Pressure Relief Valve call the toll free number listed on the back cover of this manual for technical assistance.
CONTAMINATED AIR
Breathing Hazard - Carbon Monoxide Gas
Install water heater in accordance with the Instruction Manual and NFPA 54 or CAN/CSA-B149.1.
To avoid injury, combustion and ventilation air must be taken from outdoors.
Do not place chemical vapor emitting products near water heater.
T&P Valve Discharge Pipe Requirements:
Shall not be smaller in size than the outlet pipe size of the • valve, or have any reducing couplings or other restrictions.
Shall not be plugged or blocked.• Shall not be exposed to freezing temperatures.• Shall be of material listed for hot water distribution.• Shall be installed so as to allow complete drainage of both
the Temperature-Pressure Relief Valve and the discharge pipe.
Must terminate a maximum of six inches above a fl oor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building.
Shall not have any valve or other obstruction between the • relief valve and the drain.
Burn hazard.
Hot water discharge.
Keep clear of Temperature­Pressure Relief Valve discharge outlet.
The Temperature-Pressure Relief Valve must be manually operated at least twice a year. Caution should be taken to ensure that (1) no one is in front of or around the outlet of the Temperature­Pressure Relief Valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot. If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions in this manual, and replace the Temperature-Pressure Relief Valve with a properly rated/sized new one.
NOTE: The purpose of a Temperature-Pressure Relief Valve is to prevent excessive temperatures and pressures in the storage tank. The T&P valve is not intended for the constant relief of thermal expansion. A properly sized thermal expansion tank must be installed on all closed systems to control thermal expansion, see Closed Water Systems and Thermal Expansion on page 12.
If you do not understand these instructions or have any questions
Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.
Corrosion of the fl ue ways and vent system may occur if air for combustion contains certain chemical vapors. Such corrosion may result in failure and risk of asphyxiation.
Combustion air that is contaminated can greatly diminish the life span of the water heater and water heater components such as hot surface igniters and burners. Propellants of aerosol sprays, beauty shop supplies, water softener chemicals and chemicals used in dry cleaning processes that are present in the combustion, ventilation or ambient air can cause such damage.
Do not store products of this sort near the water heater. Air which is brought in contact with the water heater should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outdoor sources. The limited warranty is voided when failure of water heater is due to a corrosive atmosphere. (See limited warranty for complete terms and conditions).
AIR REQUIREMENTS
Breathing Hazard - Carbon Monoxide Gas
Install water heater in accordance with the Instruction Manual and NFPA 54 or CAN/CSA-B149.1.
To avoid injury, combustion and ventilation air must be taken from outdoors.
Do not place chemical vapor emitting products near water heater.
Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.
For safe operation an adequate supply of fresh uncontaminated air for combustion and ventilation must be provided.
An insuffi cient supply of air can cause recirculation of combustion products resulting in contamination that may be hazardous to life. Such a condition often will result in a yellow, luminous burner
ame, causing sooting of the combustion chamber, burners and ue tubes and creates a risk of asphyxiation.
Do not install the water heater in a confi ned space unless an adequate supply of air for combustion and ventilation is brought in to that space using the methods described in the Confi ned
13
Space section that follows.
Never obstruct the fl ow of ventilation air. If you have any doubts or questions at all, call your gas supplier. Failure to provide the proper amount of combustion air can result in a fi re or explosion and cause property damage, serious bodily injury or death.
UNCONFINED SPACE
An Unconfi ned Space is one whose volume IS NOT LESS THAN 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating of all appliances installed in the space. Rooms communicating directly with the space, in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfi ned space.
Makeup air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers and fi replaces shall also be considered in determining the adequacy of a space to provide combustion, ventilation and dilution air.
UNUSUALLY TIGHT CONSTRUCTION
In unconfi ned spaces in buildings, infi ltration may be adequate to provide air for combustion, ventilation and dilution of fl ue gases. However, in buildings of unusually tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.) additional air must be provided using the methods described in the Confi ned Space section that follows.
CONFINED SPACE
through the water heater’s vent system causing poor combustion. Sooting, serious damage to the water heater and the risk of fi re or explosion may result. It can also create a risk of asphyxiation.
LOUVERS AND GRILLES
The free areas of the fresh air openings in the instructions that follow do not take in to account the presence of louvers, grilles or screens in the openings.
The required size of openings for combustion, ventilation and dilution air shall be based on the “net free area” of each opening. Where the free area through a design of louver or grille or screen is known, it shall be used in calculating the size of opening required to provide the free area specifi ed. Where the louver and grille design and free area are not known, it shall be assumed that wood louvers will have 25% free area and metal louvers and grilles will have 75% free area. Non motorized louvers and grilles shall be fi xed in the open position.
VENT REDUCER
The SBD85500NE/SBD85500PE model is shipped with a 6" to 8" diameter fl ue outlet adapter. Each adapter fi ts on top of the installed blower exhaust. Use only vent reducers supplied with the unit. The venting must comply with the NATIONAL FUEL GAS CODE, ANSI Z223.1/NFPA 54 and for Canadian installations consult the Canadian Installation Code CAN/CSA B149.1-00.
A Confi ned Space is one whose volume IS LESS THAN 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating of all appliances installed in the space.
Openings must be installed to provide fresh air for combustion, ventilation and dilution in confi ned spaces. The required size for the openings is dependent on the method used to provide fresh air to the confi ned space AND the total Btu/hr input rating of all appliances installed in the space.
EXHAUST FANS
Where exhaust fans are installed, additional air shall be provided to replace the exhausted air. When an exhaust fan is installed in the same space with a water heater, suffi cient openings to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan. Undersized openings will cause air to be drawn into the room
VENTING INSTALLATION
VENTING
THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.
Heater must be protected from freezing downdrafts.
Remove all soot or other obstructions from the chimney that will retard a free draft.
Type B venting is recommended with these heaters. For typical venting application see TECHNICAL DATA VENTING on pages 17 and 18.
This water heater must be vented in compliance with all local codes, the current revision of the National Fuel Gas Code (ANSI­Z223.1) and with the Category I Venting Tables.
If any part of the vent system are exposed to ambient temperatures below 40°F it must be insulated to prevent condensation.
Figure 11
• Do not connect the heater to a common vent or chimney with solid fuel burning equipment. This practice is prohibited by many local building codes as is the practice of venting gas red equipment to the duct work of ventilation systems.
FIGURE 12
• Where a separate vent connection is not available and the vent pipe from the heater must be connected to a common
14
vent with an oil burning furnace, the vent pipe should enter the smaller common vent or chimney at a point above the large vent pipe.
MULTIPLE HEATER MANIFOLD
Figure 13 and tables on pages 17 and 18 should be used for horizontally manifolding two or more heaters.
FIGURE 13
FRESH AIR OPENINGS FOR CONFINED SPACES
The following instructions shall be used to calculate the size, number and placement of openings providing fresh air for combustion, ventilation and dilution in confi ned spaces. The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confi ned spaces only. DO NOT refer to these illustrations for the purpose of vent installation. See Venting Installation on page 14 for complete venting installation instructions.
OUTDOOR AIR THROUGH TWO OPENINGS
OUTDOOR AIR THROUGH ONE OPENING
Figure 15
Alternatively a single permanent opening, commencing within 12 inches (300 mm) of the top of the enclosure, shall be provided. See Figure 15. The water heater shall have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (l50 mm) from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of the following:
1 square inch per 3000 Btu/hr (700 mm1.
2
per kW) of the total input
rating of all appliances located in the enclosure, and Not less than the sum of the areas of all vent connectors in the space.2.
OUTDOOR AIR THROUGH TWO HORIZONTAL DUCTS
Figure 14
The confi ned space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The openings shall communicate directly with the outdoors. See Figure 14.
Each opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm
2
per kW) of the aggregate input rating
2
).
Figure 16
The confi ned space shall be provided with two permanent horizontal ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The horizontal ducts shall communicate directly with the outdoors. See Figure 16.
Each duct opening shall have a minimum free area of 1 square inch per 2,000 Btu/hr (1100 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure.
When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches.
15
OUTDOOR AIR THROUGH TWO VERTICAL DUCTS
The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confi ned spaces only.
DO NOT refer to these illustrations for the purpose of vent installation. See Venting Installation on page 14 for complete venting installation instructions.
Figure 17
The confi ned space shall be provided with two permanent vertical ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The vertical ducts shall communicate directly with the outdoors. See Figure 17.
Each duct opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure.
When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches.
AIR FROM OTHER INDOOR SPACES
Figure 18
The confi ned space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. See Figure 18.
Each opening shall communicate directly with an additional room(s) of suffi cient volume so that the combined volume of all spaces meets the criteria for an Unconfi ned Space.
Each opening shall have a minimum free area of 1 square inch per 1,000 Btu/hr (1100 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm2).
16
Loading...
+ 36 hidden pages