Sta-Rite PID-1-10A1-01 Installation Manual

293 Wright Street, Delavan, WI 53115
INSTALLATION MANUAL
PENTEK INTELLIDRIVE
MANUEL D’INSTALLATION
PENTEK INTELLIDRIVE
MANUAL DE INSTALACIÓN
PENTEK INTELLIDRIVE
MC
Models / Modèles / Modelos
www.pumps.com
© 2010 PN895 (4/29/10)
Installation/Operation/Parts
For further operating, installation, or maintenance assistance:
Call 1-866-9PENTEK (866-973-6835)
English .................... Pages 2-16
Installation/Fonctionnement/Pièces
Pour plus de renseignements concernant l’utilisation, l’installation ou l’entretien,
Composer le
1 (866) 9PENTEK
(866-973-6835)
Français ............... Pages 17-31
Instalación/Operación/Piezas
Para mayor información sobre el funcionamiento, instalación o mantenimiento de la bomba:
Llame al 1-866-9PENTEK (866-973-6835)
Español ...............Paginas 32-46
GENERAL SAFETY
Read the Owner’s Manual and related documentation carefully before attempting to install or operate the PENTEK INTELLIDRIVE
TM
. Make sure that you have a full knowledge of the equipment, safety information, and instructions before using this product.
Carefully read and follow all safety instructions in this manual and on the VFD.
This is the safety-alert. When you see this symbol
on your VFD or in this manual, look for one of the follow­ing signal words and be alert to the potential for personal injury:
warns about hazards that will cause
serious personal injury, death or major property damage if ignored.
warns about hazards that can cause
serious personal injury, death or major property damage if ignored.
warns about hazards that will or can
cause minor personal injury or property damage if ignored. The word NOTE indicates special instructions which are
important but not related to hazards.
To avoid serious or fatal personal injury and possible property damage, carefully read and follow the safety instructions.
Risk of high-voltage electrical shock from the EMI/RFI Filter if the front cover of the VFD is open or removed while power is connected to the VFD or the VFD is running. The front cover of the VFD must be
closed during operation.
• After allowing at least 5 minutes for the EMI/RFI Filter
to discharge and before starting any wiring or inspec­tion procedures, check for residual voltage with a volt­age tester.
Risk of electrical shock if VFD is con-
nected to the power wiring before hanging the box.
Always
hang the VFD box before connecting the wires to it.
Risk of electrical shock if the VFD is
handled or serviced with wet or damp hands. Always
make sure your hands are dry before working on the VFD. Perform all operations on the HMI with dry hands.
Risk of electrical shock and hand
injury. Do not reach into or change the cooling fan while
power is on to the VFD.
Risk of electrical shock. Do not touch
the printed circuit board when power is on to the VFD.
Fire hazard if installed with incorrect or
inadequate circuit breaker protection. To make sure of
protection in the event of an internal fault in the VFD, install the VFD on an independent branch circuit protected by a circuit breaker (see Table 2, Page 6 for circuit breaker sizing), with no other appliances on the circuit.
Risk of burns. The drive can become
hot during normal operation. Allow it to cool for 10 min­utes after shut-down before handling it to avoid burns.
NOTE: To avoid damage to the drive or problems with the drive:
• Connect the output cables to 3-wire and 3-phase sub-
mersible motors as follows: Red to R, Yellow to Y, Black to B. Any other order will reverse the motor rota­tion and may damage the motor.
• Connect the output cables to 2-wire 1-phase sub-
mersible motors as follows: Connect to Y and B only. Connect Ground to Ground.
• Above ground 3-phase motors may have different lead colors. Generally connect output leads as follows: R to L1, Y to L2, B to L3. Verify rotation after startup.
• Do not modify the equipment.
• Do not use power factor correction capacitors with this VFD; they will damage both the motor and the VFD.
• Do not remove any parts unless instructed to do so in the owner’s manual.
• Do not use a magnetic contactor on the VFD for frequent starting/stopping of the VFD.
• Do not install or operate the VFD if it is damaged or parts are missing.
• Before starting a VFD that has been stored for a long time, always inspect it and test operation.
• Do not carry out a megger (insulation resistance) test on the control circuit of the VFD.
• Do not allow loose foreign objects which can conduct electricity (such as screws and metal fragments) inside the VFD box at any time. Do not allow flammable sub­stances (such as oil) inside the VFD box at any time.
• Ground the VFD according to the requirements of the National Electrical Code Section 250, IEC 536 Class 1, or the Canadian Electrical Code (as applicable), and any other codes and ordinances that apply.
• All installation, service work, and inspections must be
done by a qualified electrician.
Carefully read and follow all safety instructions in this manual or on drive.
Safety 2
Risk of high-voltage electrical shock from EMI/RFI Filter inside Drive. Make all wiring connections, then close and fasten the cover before turning on power to Drive.
DO NOT open the box when power is connected to the Drive.
Before doing any service or maintenance inside the Drive:
1. DISCONNECT power.
2. WAIT 5 minutes for
retained voltage to discharge.
3. Open box.
Before connecting or disconnecting any wires inside the Drive:
1. DISCONNECT power.
2. WAIT 5 minutes for
retained voltage to discharge.
3. Open box.
Table of Contents 3
General Safety ........................................................................................................................................... 2
Owner’s Information.................................................................................................................................. 3
Description / Typical Installation................................................................................................................ 4
Keypad Nomenclature & Functions ........................................................................................................... 5
Installation................................................................................................................................................. 5
Connections............................................................................................................................................... 6
Programming ......................................................................................................................................... 8–9
Advanced Programming....................................................................................................................... 9–11
I/O Connections........................................................................................................................................12
Troubleshooting ................................................................................................................................. 13–15
Wire Sizing Tables ................................................................................................................................... 15
Repair Parts ............................................................................................................................................. 16
Specifications............................................................................................................................................16
Warranty.................................................................................................................................................. 16
Owner’s Information
PENTEK INTELLIDRIVE Model No. _____________________________________
PENTEK INTELLIDRIVE Serial No.______________________________________
Pump Model No. ____________________________________________________
Pump Serial No._____________________________________________________
Motor Model No._____________________________________________________
Motor Service Factor Amps ____________________________________________
Pressure Tank Model No. ______________________________________________
Pressure Tank Serial No. ______________________________________________
Dealer/Installer: _____________________________________________________
__________________________________________________________________
Installer Phone No.___________________________________________________
Date of Installation ___________________________________________________
Wire Lengths in Feet (Meters)
Circuit Breaker to PENTEK INTELLIDRIVE_____________________________
PENTEK INTELLIDRIVE to Motor _______________________________________
Supply Voltage ______________________________________________________
Note: Record the data listed above for future reference. Give the manual to the owner or fasten it to the PENTEK INTELLIDRIVE when the installation is complete.
EMI/RFI Filter
Hazardous voltage. Drive internal compo-
nents retain high voltage for up to 5 minutes after input power is disconnected.
EMI/RFI Filter carries high voltage when pump is running.
Disconnect power and wait 5 minutes before opening and removing VFD cover.
PENTEK INTELLIDRIVE Includes:
• PENTEK INTELLIDRIVE
TM
• Pressure Transducer
• 10’ Pressure Transducer Cable
• Quick Start Guide
• Owner’s Manual
The PENTEK INTELLIDRIVE is specifically designed to operate 4” submersible pumps and 3-phase above ground pumps in water well and residential booster applications. Each drive is rated for maximum output amp rating. Any use of the drive outside of its intended use and design parameters will void the warranty. If the PENTEK INTELLIDRIVE is used with above ground motors not rated for VFD use, limit lead length to 25 ft. for maximum motor life. Refer to the pump owner’s manual and the National Electrical Code for proper wire size.
Transducer
The drive uses a 4-20mA, 0-100PSI pressure transducer to control the speed of the motor.
The transducer senses pressure in the pipe and converts it to an electrical signal which it sends to the drive. The drive processes the signal in the PID (Proportional, Integration, Derivative) control. When operating in PID mode the drive increases and decreases the speed of the pump motor as needed to maintain constant pressure in the system.
Fan
The PENTEK INTELLIDRIVE has a thermostatically con­trolled internal fan. The fan may not operate under normal operating conditions. It will automatically start when nec­essary to cool the drive.
Keypad
The Keypad programs the drive, monitors the status of the pump, and views faults if they occur. Each button has a unique function (see Page 5). The LCD display shows a text display of the status of the drive’s operation. Other LEDs light up to indicate when certain buttons are pressed or certain events occur.
Description / Typical Installation 4
Table 1: Model Number Structure
Vol ta ge Rating:
1 = 190–265 Volt 1-Ph. In, 3-Phase Out 6 = 190–265 Volt 1-Ph. In, 1-Phase Out
PID 1 – 10A1 – 1 – 01
PID-1- 10A1-1:
Product Family
PID = Pentek IntelliDrive
Max Amp Rating:
4A7 = 4.7 Amps 7A6 = 7.6 Amps 9A7 = 9.7 Amps 10A1 = 10.1 Amps 12A2 = 12.2 Amps
Enclosure Type:
1 = NEMA 1 (Indoor Rated) 3 = NEMA 3R (Outdoor Rated)
Revision Code:
Figure 1: Overall Layout – Typical installation
Grnd
Transducer; install in straight pipe at least one foot away from pipe fittings on each side.
6004 0509
Keypad / Installation 5
INSTALLATION
Mounting (See Figure 3)
Mount the drive in an easily accessible area with tempera­ture maintained between –4°F and 104°F (–20°C to 40°C). NEMA 1 enclosures must be mounted indoors; NEMA 3R enclosures may be mounted outdoors with the same ambi­ent temperature limits.
To mount the drive, mark the location of the top keyhole on the wall or stud. Drive a screw into the structure and hang the drive on it. Back out the screw on the bottom of the front cover and lift the cover off. Mark the locations of the bottom two mounting holes. Mount the drive with screws in all three holes.
Be sure that the ventilation holes are not blocked and that there is enough space around the drive to allow free air flow (minimum 3” clearance, top, bottom, and sides). Once the drive is mounted, you are ready to connect the wires.
Runs the Drive at 45 Hz
(with no pressure control)
to allow the installer
to pump out the well
Toggles the pressure setpoint
between 40, 60, and 70 PSI
(default is 60)
Views and changes parameters
Shows the last 15 faults
Changes the display to
the previous screen
With code, locks and unlocks the password protected keys (default password is 7777)
Selects menu items and
confirms numeric value changes
The up and down arrows scroll through the menus and change numeric values.
Toggles between English, Spanish, and French (Default is English )
The left and right arrows move the cursor.
Power is on to the Drive
The Drive is in Temporary Performance
Mode (TPM) or Jam condition
A fault has occurred
Displays the Drive’s
current operating conditions and
changes the display parameters
Checks for line fill, then starts the pump in constant pressure mode
Resets the fault that stopped the pump
Stops the motor
6007 0509
Hazardous pressure.
Do not connect to system or restrict discharge flow when running in “Pump Out” mode.
Figure 2: Keypad functions
Keypad Nomenclature and functions
5997 0509
Figure 3
Wiring
To allow for ease of wiring, the wiring area is free of elec­tronics other than the terminals. Conduit holes and knock­outs are located so that the wire can be fed straight through to the connectors, with minimal bending. The ter­minals accept 6-14 AWG wire.
NOTE: For convenience in wiring, the input and motor ter­minals unplug from the box. Pull them down to remove them for ease of access. See Figure 4.
BE SURE that when you replace them, they are completely pushed in and seated.
Note: The best practice is to connect all output wires first and all input wires last.
Output Connections (See Figure 5, Page 7):
See Tables 5 and 6, Page 15, for correct wires sizes, VFD to motor.
If the PENTEK INTELLIDRIVE is used with above ground motors not rated for VFD use, limit lead length to 25 ft. for maximum motor life. Refer to the pump owner’s manual and the National Electrical Code for proper wire size.
The output of PID-1 Series drives is 230V three phase power.
The output of PID-6 Series drives is 230V single phase power.
NOTE: PID-1 series drives will not operate single phase motors. PID-6 series drives will not operate three phase motors.
The output power terminals (motor wire connections) are located on the lower right side of the drive and are labeled R (Red), Y (Yellow), and B (Black). Feed the motor cable through the 3/4” conduit hole on the bottom right side and into the appropriate terminals. If the wire is large enough to require a larger conduit hole, remove the 1-1/4” knock­out and use the appropriate conduit connections. Attach the motor ground wire to the grounding lug, located to the upper right of the terminal block. Attach the motor power wires to the terminals as shown in Figure 5, Page 7.
Installation / Connections 6
Wire Size Minimum 240VAC Controller CB to VFD C.B. Size Generator Model No. (AWG) (Amps) Cap’y (kVA)
PID-1-4A7-X 12 20 4.2 kVA PID-1-7A6-X 10 30 6.9 PID-1-10A1-X 8 40 9.1 PID-6-9A7-X 12 20 4.4 PID6-12A2-X 10 30 7.4
Table 2: Circuit Breaker and Wire Sizes
Figure 4: Pull the input and motor terminals down to unplug them for ease of wiring.
NOTE: The circuit breaker protects the drive and is chosen independ­ently of the motor connected to the drive.
Connections 7
Pressure Tank Recommendations:
Minimum tank size is 2 gallons. Use a pre-charged pres­sure tank with the Drive. The tank size must equal at least 20% of the pump’s rated flow in gallons per minute (GPM), but cannot be less than 2 gallons capacity. For example, a pump rated at 7 GPM would require a tank of 2 gallons capacity or larger. A pump rated at 50 GPM would require a 10 gallon tank or larger. A larger tank may increase cycling of the pump.
Table 3: Control Pressure Set Point and Tank Pre-Charge Pressure Values (PSI)
NOTE: Set the pressure tank’s pre-charge to 70% of the
system operating pressure. When using an external set point as well as an internal set point, pre-charge the tank to 70% of the lower set point of the two. Some applica­tions may require a different percentage when figuring the set point.
Transducer Connections (See Figure 5):
Use the transducer provided with the drive. Install the transducer downstream of the tank. Install the transducer in a tee in a straight section of pipe with at least 1 foot of straight pipe on each side of the tee (that is, all fittings must be at least one foot away from the transducer).
Feed the transducer cable through the open 1/2” conduit hole on the bottom of the drive enclosure.
The transducer terminals, marked AI+ and AI-, are located to the left of the output terminals. Connect the red wire of the transducer cable to AI+, connect the black wire to AI–, and connect the cable shield to the metal lug to the right. NOTE: Do not use the clear wire on the transducer cable for any connections; tape the end and tie it back to the cable with electrical tape so that it does not touch any other components or connections.
Note: To connect the wires;
1. If the wire ends are not pre-stripped, strip them back about 1/2”.
2. Push the spring terminals up (back).
3. Insert the wires.
4. Release the spring terminals.
Pressure Point Precharge
Setting (PSI) Pressure (PSI)
25 18 30 21 35 25 40 28 45 32
50 35 55 39
60 (Default) 42
65 46 70 49
75 53 80 56 85 60 90 63 95 67
Figure 5: Basic Wiring Connections for Startup.
NOTE: Do not connect the clear wire on the transducer cable to any terminal; instead, tie it back with electrician’s tape so that it cannot touch any other components or connections.
Input Ground Screw
Green/Yellow (Ground)
Input Power Connections
See Figures 6–9, Page 12, for information
about I/O Connections O1, I1,V+, and V–.
Clear Wire; tape end to cable.
Red to AI+
Black to AI–
Cable Shield
Transducer Cable Connections
Submersible Motor: 3-Ph./ 3-W. 1-Ph., follow colors as above. Submersible Motor: 2-W, 1-Ph.; Connect to Y and B, any order. Above-Ground Motors: L1 to R, L2 to Y, L3 to B, verify Rotation.
Output Ground Screw
Cable Shield Lug
Red Yellow Black
Green/Yellow (Ground)
6184 0310
Input Connections (See Figure 5):
The input power terminals are located on the lower left side and marked L1 and L2 (see Figure 5); there is a ground lug for the input ground wire to the left of the con­nector. Feed the wire through the 3/4” conduit hole on the bottom left side and into the appropriate terminals. If the wire is large enough to require a larger conduit hole, remove the 1-1/4” knockout and use the appropriate con­duit connections.
To determine the correct wire sizes for your installation, see Table 2, Page 6.
NOTE: The drive only accepts 230V single phase input power. If your incoming power does not match this, have a competent electrician alter it to 230V/1Ph before connect­ing the drive.
Lightning/Surge Protection
Lightning arrestors or other surge suppressing devices can be used with this product. MOV (Metal Oxide Varistor), SOV (Silicon Oxide Varistor), or a flashover type can be used when wired between the drive and the circuit breaker. If a lightning arrestor is to be used between the drive and the motor, a flashover type arrestor is recommended.
INITIAL STARTUP PROGRAMMING PROCEDURE
Be Sure that the cover is installed before operating the drive.
Most installations will only require the initial startup set­tings. However, the installer may need to set additional parameters occasionally. See “Advanced Programming”, Page 9, for information about accessing all parameters, explanations of their functions, and procedures for chang­ing parameter values, if necessary.
1. Program the Drive: Apply power to the PENTEK
INTELLIDRIVE. “Setup Guide” will appear.
A. Service Factor Amps (See Sidebar, “Service Factor
Amps”)
1. Use DIRECTIONAL Arrows to enter the correct
service factor amps (see Table 4)
2. Press ENTER to save the entry.
B. Application Type:
1. Use DIRECTIONAL Arrows to scroll between
‘Above Ground’ and ‘Submersible’.
2. Press ENTER to save.
C. Connection Type (1-Phase only):
1. Use DIRECTIONAL Arrows to scroll between
‘3-wire’ and ‘2-wire’.
2. Press ENTER to save the entry.
D. Current Time:
1. Use DIRECTIONAL Arrows to scroll to correct
time
2. Press ENTER to save the time.
E. Current Date:
1. Use DIRECTIONAL Arrows to scroll to
correct date
2. Press ENTER to save the date.
• To change any values, press Back to return to the pre-
vious screen.
• To change any values after startup, go to Main Menu
and edit the parameters as needed.
Connections / Operation 8
Service Factor Amps (See Table 4)
To get the best performance out of your pump, be sure you enter the correct Service Factor Amps (SF Amps) in the PENTEK INTELLIDRIVE.
• Entering SF Amps
higher
than the motor rating lets the drive supply more amps to the motor than the motor is designed for and may allow the motor to overheat;
• Entering SF Amps
lower
than the motor rating lim­its the output amps to less than the motor is designed for and will reduce the performance of the pump.
• For any 1-Phase 3-Wire motor, the correct Service Factor Amp rating for the PENTEK INTELLIDRIVE is Cap Start/Cap Run amps. This may not match the motor nameplate, which (for a 3-Wire, Single Phase motor) will generally be Cap Start/ Induction Run Amps.
• For any 3-Phase or 2-Wire 1 Phase motor, use the motor nameplate Service Factor Amp rating.
NOTE: PENTEK submersible motors may differ from motors of the same horsepower from other manufac­turers. For 3-Wire, 1-Phase motors from all other
submersible motor manufacturers, enter the motor manufacturer’s CS/CR service factor amps for your motor. For 3-Phase or 2-Wire 1-Phase
motors, use the motor nameplate amps.
Part Number Volts/Hz/Ph HP S.F. Amps Three Phase Motors
P43B0010A3 230/60/3 1.0 4.7 P43B0015A3 230/60/3 1.5 6.1 P43B0020A3 230/60/3 2.0 7.6 P43B0030A3 230/60/3 3.0 10.1
3-Wire Single Phase Motors
P43B0005A2 230/60/1 0.5 4.9 P43B0007A2 230/60/1 0.75 6 .3 P43B0010A2 230/60/1 1.0 7.2 P43B0015A2 230/60/1 1.5 11.1 P43B0020A2 230/60/1 2.0 12.2
2-Wire Single Phase Motors
P42B0005A2 230/60/1 0.5 4.7 P42B0007A2 230/60/1 0.75 6.4
Table 4: Pentek Motor Service Factor Amps
Operation / Programming 9
2. 80 Hz Operation (if necessary—See “60 to 80 Hz Operation,” below):
A. Press MAIN MENU button, B. Use DIRECTIONAL Arrows to scroll to motor;
press ENTER.
C. Use DIRECTIONAL Arrows to scroll to Set Max
Frequency; press ENTER.
D. Use DIRECTIONAL Arrows to change to 80 Hz;
press ENTER.
3. Pump out the well (if necessary):
Direct the pump’s discharge to an appropriate loca­tion not connected to the system and press Pump
Out. The pump will run at 45 Hz. Adjust frequency as appropriate:
A. Press ENTER B. Change frequency value
NOTE: Above ground pumps should run at 60 Hz for this step (until pump is primed). Then adjust frequency as appropriate.
C. Press ENTER again. Run the drive in this mode until the well discharge
runs clear, then press the ‘Stop’ button to stop the drive.
Hazardous pressure. In Pumpout
mode, the pump runs at a constant speed, which can cause very high pressure if flow is restricted.
4. Check List: Make sure that the system has a properly sized relief valve and pressure tank.
Make sure that the pressure tank’s precharge is correct. See Table 3, Page 7.
Make sure that the pump discharge is connected to the system.
5. System Start: Open valves at the ends of lines so that air will
escape during pressurization. Press Auto Start; close valves at the ends of lines after
all air has escaped. The system goes into Constant Pressure Operation as
soon as the transducer registers 10 PSI. If system pres­sure does not reach 10 PSI within 3 minutes, the drive will stop. Press AutoStart again to restart line fill. If a longer priming or line fill time is required, adjust the ‘fill time’ parameter in the ‘dry run’ menu (Page 11).
60 to 80 Hz Operation (See 2, above):
When installing the PID-1 Series PENTEK INTELLIDRIVE with a motor and liquid end of the same HP rating, operate it at 60 Hz (the default value). The drive can be operated at frequencies of up to 80 Hz when the installation uses a large motor with a small pump (For example, a 1 HP pump with a 2 HP 3-Phase motor. This combination will equal the performance of a conventional 2 HP pump.).
Go to Main Menu as described in No. 2 (above). Be sure to press Enter to save the new Max Frequency selected. The drive will now use the new value selected.
NOTE: The drive will not allow the output amps to go above the Service Factor Amps selected on the keypad. Because of this, some 80 Hz operations may be limited by a
“TPM: Service Amps” warning. This protects the motor and may be a common occurance.
ADVANCED PROGRAMMING
Locking & Unlocking the Keypad
Password: The password locks or unlocks the blue buttons
on the keypad. All PENTEK IntelliDrive units are shipped from the factory with the default password ‘7777’. It can be changed to any other 1 to 4 digit number. To reset the password to a unique password for your unit, unlock the key pad (see below) and go to “SETTINGS/Password”, Page 10.
If the installer does not press the PASSWORD button, then the Keypad will automatically lock 60 minutes after the drive is powered up. The timeout period is adjustable through the Main Menu/Settings/Password.
To unlock the keypad press PASSWORD, use the direction­al arrows to enter the proper numeric code, and press ENTER.
Note: For more detailed information on Keypad functions, see the “Parameters” section.
Changing a Parameter Value:
NOTE: This procedure works for ANY parameter.
1. Find the parameter and display the current parameter value on the screen.
2. Press ENTER to enable editing of the parameter.
3. Use the UP, DOWN, LEFT, and RIGHT arrows to change the parameter values.
4. Press ENTER again to save the new parameter value.
NOTE: A “shorthand” way to remember this is:
• Press ENTER to change a value;
• Press ENTER again to save it.
• If you don’t save the new value, then as soon as you
change the screen, you lose it.
Keypad Access Parameters
Pump Out Speed: Press Pump Out. The Drive will start the
pump in a constant speed mode (default 45 Hz). The pump will run until you push Stop or Auto Start. If necessary to change the speed, Follow steps 2-4 above to change the parameter.
PSI Preset: Press PSI Preset; follow steps 2-4 above to change the parameter. The default is 60 PSI, but the parameter can be set to 40, 60, or 70 PSI.
Pressure Setpoint: Press Auto Start, then follow steps 2-4 above to change the parameter. Use the directional arrows to change the pressure by 1 or 10 PSI increments.
NOTE: This parameter allows you to change either the
Internal or the External Setpoint, depending on which one is referenced at the time you are making the change.
NOTE: To change the setpoint before starting the pump,
go to the Main Menu/Settings/Setpoints/ Internal Setpoint.
NOTE: If this value is changed from the default value of
60 PSI, you must adjust the tank pressure accordingly (see Table 3, Page 7).
Language: Press Language; follow steps 2-4 under “Changing a Parameter Value,” Page 9, using the UP or DOWN arrows to scroll through the available languages (English, French, or Spanish; default is English).
NOTE: To change the setpoint before startup, go to the
Main Menu under “Settings”.
Main Menu Parameters
The Main Menu has six secondary menus (plus a Reset) that allow access to the Advanced Programming parameters: 1) SETTINGS, 2) MOTOR, 3) SENSOR, 4) PIPE BREAK, 5) DRY RUN, 6) I/O. The basic structure and navigation instructions are listed below. Use the UP and DOWN arrows to scroll to the next secondary menu or submenu, or to a parameter. Press Enter to go into a Submenu or to edit a parameter.
1) SETTINGS: (Has 5 submenus)
Time (2 parameters):
Hour:
Allows you to change the time of day.
Date:
Allows you to change the calendar day.
PID Control: Changing these parameters is NOT recommended. These parameters control the drive’s reaction to pressure changes in the system. They should be considered as a group. If it seems necessary to alter anything in this group, please call Pentek Customer Service at 1-866-9PENTEK (1-866-973-6835) BEFORE YOU START. Also, note that the last item on the main menu resets ALL parameters to the default values.
Sleep (6 parameters plus Reset):
Boost Differential:
Raises the system pressure slightly before going into sleep mode. Units are in PSI. The default boost value is 3 PSI. (i.e., with Boost Differential set to 3 PSI and Pressure Setpoint set to 60 PSI, the system pressure will rise to 63 PSI before the drive goes to sleep). Maximum is 10 PSI, minimum is 3 PSI.
Boost Delay:
The length of time (in seconds) that the drive monitors the system before boosting the pressure. Default is 60 seconds, maximum is 300 seconds, minimum is 30 seconds.
Wakeup Differential:
The total pressure drop from the setpoint that the drive must see to come out of Sleep mode. The default setting is 5 PSI. (i.e., with the Wakeup Differential set to 5 PSI, the drive will wake up when the pressure in the system has dropped 5 PSI below the system Pressure Setpoint.) Maximum is 15 PSI, minimum is 5 PSI.
Wake Delay:
The time it takes to ramp down to the Wake Up pressure. Default is 15 seconds, maxi­mum is 120 seconds, minimum is 3 seconds.
Sleep 2 PSI:
A setting to prevent Over-Pressure. If the system pressure rises enough that the drive reaches the Sleep 2 PSI setpoint, the drive will go to sleep for one minute. Default pressure is 80 PSI, maximum is ‘Max Sensor’ value minus 3 PSI, mini­mum is 15 PSI.
NOTE: If the Internal or External Setpoint is set to
a value that is near, at, or above the Sleep 2 PSI setpoint, you may experience nuisance tripping. In this case, raise the Sleep 2 PSI setpoint until the nuisance tripping stops.
Boost Trigger:
Sets the frequency range that defines system stability. When the frequency stabilizes within this range, the drive starts the boost process. Increasing this value allows the drive to sleep under less stable conditions. The default is 3 Hz. The range is 3 to 30 Hz.
Reset to defaults:
Default value is NO. Change to YES to reset all Sleep parameters to their default values.
Password (2 parameters):
Password Timeout:
Sets the time (in minutes) that the drive takes to lock out the password-protected (blue) buttons on the keypad. The range is 1 – 360 minutes; the default is 60 minutes. When drive pro­gramming is complete, a timer starts. Once it reaches the time set in this parameter the buttons automatically lockout.
Password:
The Password locks or unlocks the blue buttons on the keypad. The password is a number (default is 7777) and can be changed to any 1- to 4-digit number.
Setpoints (2 Parameters):
Internal Setpoint:
The main pressure setting used by the drive. The default value is 60 PSI. Maximum is the ‘Max Sensor’ value minus 3 PSI, minimum is 15 PSI.
External Setpoint:
The Drive’s pressure reference when the External Input is set to External Setpoint and the proper drive is connected to it (see I/O section, Pages 11 and 12). Default is 40 PSI, Maximum is ‘Max Sensor’ minus 3 PSI, minimum is 15 PSI.
2) MOTOR (4 parameters plus Reset):
Service Factor Amps:
The service factor amps of the motor. This value is entered during the setup process and can be changed if necessary. For your PENTEK motor, use the value listed in Table 4, Page 8. This value may differ slightly from the motor’s nameplate amps. For other manufacturer’s 3-wire, 1-Phase motors, use the Cap Start/Cap Run values supplied by the motor manufacturer. For 3-Phase motors and 2-Wire 1-Phase submersible motors, use motor manufacturer’s service factor amps or nameplate amps.
Connection Type (1 Phase Only):
Select connection type which matches the motor used. Default is 3-Wire.
Min Frequency:
The minimum frequency that the drive will send to the motor (this translates to the slow­est speed at which the motor will run). The default is 30 Hz. If necessary this value can be increased, but cannot exceed the Max Frequency value.
Operation / Programming 10
Advanced Programming 11
Max Frequency:
This is the maximum frequency the drive will send to the motor (this translates to the highest speed at which the motor will run). The default is 60 Hz. If necessary the value can be raised up to 80 Hz. for 3-phase (PID-1) units pro­grammed for submersible operation.
Reset to defaults:
Default value is NO. Change to YES to reset all Motor parameters to their default values.
3) SENSOR (2 parameters plus Reset):
Min Pressure (PSI):
The minimum pressure of the transducer (0 PSI). The default is 0 PSI. Do not change this value unless you are using a transducer other than the one shipped with the drive, and the transducer being used requires a different minimum setting.
Max Pressure (PSI):
The maximum pressure of the transducer (300 PSI). The default is 100 PSI. Do not change this value unless you are using a transducer other than the one shipped with the drive, and the transducer being used requires a different maxi­mum setting.
Reset to defaults:
Default value is NO. Change to YES to reset all Sensor parameters to their default values.
4) PIPE BREAK (2 parameters):
Pipe Break Detection:
Detects a possible leak in the system. The Default value is ENABLED. Change to DISABLE to disable Pipe Break Detection.
Number of days with no sleep:
The maximum number of days that the drive will operate without going to sleep. If the maximum is exceeded, the drive stops the pump with a Pipe Break Fault. Default is one day. Range is 1–24 days.
5) DRY RUN (5 parameters):
Auto Reset Delay:
The delay (in minutes) that the drive will wait before attempting to restart after a Dry Run Fault. Default is 10 minutes. Range is 3–60 minutes.
Number of Resets:
The number of times that the drive will attempt to restart after a Dry Run Fault. Default is 3. Range is 0–5.
Detection Time:
The amount of time the drive will operate at less than 10 PSI. Default is 15 seconds. Range is 5 to 600 seconds. For self primers, increase value in the event of nuisance dry run faults.
Fill Time:
The amount of time the drive will operate in line fill mode. For self primers, increase value to allow for priming. Default is 60 seconds. Range is 15 to 600 seconds.
Reset Window (Read Only):
The time window allowed for resets after a Dry Run Fault. This is cal­culated based on the values in the two parameters above (Auto Reset Relay and Number of Resets).
6) I/O (Two Submenus):
External Input (4 parameters – see Figures 6 through 9,
Page 12). NOTE: An external device must be connected before
changing these parameters:
Unused:
The default.
Setpoint:
Used with devices like automatic sprin­kler systems that start and stop on a timeclock. When the timeclock starts the system, SETPOINT tells the drive to operate at the External Setpoint pressure (under the Settings menu) until the exter­nal device switches off.
External Fault:
Stops the pump and indicates EXTERNAL FAULT. Used to alert the user to prob­lems with external devices.
Run Enable:
Used with external switches (for example, float switches) connected to I1 to allow the drive to operate when the external switch is ON, and stops the drive when the external switch is OFF.
Relay Output (3 Settings—See Figures 6 through 9, page 12):
Unused:
Selected when nothing is connected to
the O1 terminals.
Running:
Can turn an external device on or off
when the drive is running the pump.
Fault:
Can turn an external device (such as an alarm or autodialer) on or off if the drive has a fault.
Reset to Factory defaults:
Change NO to YES to reset all the parameters in the VFD (including all sub-menus) to the factory-set default values.
NOTE: This will display the startup menu. You must re-enter the information required for startup (see “Initial Startup Programming Procedure”, Page 8).
The I/O terminals are located in the center of the wiring compartment, to the left of the transducer terminals. The Relay Output terminal is marked O1. The Relay Output terminal powers an external device (warning light, etc.). The External Input terminal is marked I1. The External Input terminal allows the Drive’s operation to be coordi­nated with or limited by an external device (float switch, etc.). Each can be programmed for use with certain exter­nal devices; see “6) I/O (Two Submenus),” Page 11, the Parameters section (Page 9) for further information.
Two 1/2” conduit knockouts are provided on the bottom of the drive enclosure for the I/O wires.
External Input Rating:
The unique design of the PENTEK INTELLIDRIVE allows this input to be 24V DC or 24-230V AC. Power can be supplied (24VDC) from terminals V+ and V– to the right of I/O terminal I1. See Figures 6 and 7.
Output Relay Rating:
The unique design of the PENTEK INTELLIDRIVE allows this output to be 24V DC or 24-230V AC. Power can be supplied (24VDC) from terminals V+ and V– to the right of I/O terminal I1. See Figures 8 and 9. The Output Relay is rated at 5A @ 30VDC or 8A @ 230VAC.
Note: To connect the wires to either terminal:
1. Strip the wires back about 1/2”.
2. Push the spring terminals up (back).
3. Insert the wires.
4. Release the spring terminals. The 24VDC supply terminals (V+ and V–) are rated for
20ma output.
I/O Connections 12
+ –
Figure 7: External Input using external power supply (can also be an A.C. source).
Figure 6: External Input using 24VDC and power from terminals V+/V–.
Figure 8: Output relay example using 24VDC supply.
+
Figure 9: Output relay example using external supply.
NOTE: The external input and output relay can accept 24VDC. It also accepts AC voltage up to 230 volts.
Troubleshooting 13
Fault Display Possible Causes Actions
Over Shorted output. Check for any shorts in the motor cables. Current Motor current exceeded the S. F. Amp Make sure that motor Service Factor Amps
are correct.
Motor oversized or pump undersized. Make sure that pump and motor are sized
correctly.
Pump Jammed or locked rotor. Pull pump; check for debris in pump
Over Power is cycling on and off. Check for a generator or for switching on Voltage the input line.
Faulty check valve on pump. Check for back flow in the system.
Under Low input voltage. Make sure that input voltage is above Voltage 190VAC
No power for a short period of time. Check for brown out conditions Excessive load current. Make sure motor is sized correctly for the
application
Loss of a motor phase. Make sure correct voltage is present on all
motor leads.
Loss of an input line. Make sure correct voltage is present on all
input lines.
Rotor Jam Exceeding S.F. Amps Make sure Service Factor Amps entered
are correct. Make sure pump and motor are correct.
Locked rotor. Pull pump; check for debris in pump.
Dry Run Well draws down too far, pump runs dry. Check water depth.
Under sized pump or motor. Make sure pump and motor are sized
correctly. Leak in the pipe system. Check system for leaks. Intermittent transducer connection. Check transducer cable for loose
connections or damaged insulation. Cannot reach pressure setpoint. May need to reduce pressure setpoint. Possible Leak Check for a broken pipe or a large leak.
Ground Ground fault sensed in motor Make sure motor cable does not exceed Fault cables or in motor. max length in specifications.
Check for damage or breaks in motor
cables.
Check motor. Motor cable too long Length of cable limited to 1,000’ unless a
filter is used to reduce capacitance
between motor wires.
Open Intermittent connection. Check transducer cable for loose Transducer connections or broken or damaged wires.
Open Connection Check transducer wires for correct
connections and verify secure cable
connection to transducer. Failed transducer. Check voltage at the transducer terminals
(12-24Vdc). If voltage is present, then
transducer is faulty. Replace the transducer.
Troubleshooting 14
Fault Display Possible Causes Actions
Shorted Short in transducer wires. Check for shorted transducer wires, Transducer reversed leads, or damaged insulation.
Failed transducer. Disconnect transducer from cable and
press auto start; if the error now reads
“Open Transducer” (and leads are not
reversed) then replace the transducer. If it
still reads “Shorted Transducer”, then the
cable has a short; replace the cable.
Hard Exceeded Max faults allowed Check Fault log for list of faults. Correct Faults in 30 minutes. issues. Press “Fault Reset”.
Any fault lasting continuously for Look in the Fault Log for the fault 30 minutes (including auto reset faults preceding the Hard Fault to determine lasting more than 30 minutes). what caused the Hard Fault; refer to that
fault’s troubleshooting section.
Over Excessive internal drive temperature. Make sure that the ambient temperature is Temperature not above 60°C (104°F)
Make sure that the fan is operational and
unobstructed.
Make sure that all vents are clear.
Drive goes into TPM and limits the motor
current until it is within the operating
temperature.
Pipe Break Leak detected. Check for any leaks in the pipe system.
Application calls for long run times. Extend run-time limitation: Go to ‘Main
Menu, Pipe Break, No. of Days without
Sleep’ to verify preset value and change if
needed.
Disable Pipe Break Fault: Go to ‘Main
Menu, Pipe Break, Disable Pipe Break
Detection’ to disable this function if
needed.
Internal Fault Internal voltages are out of range. Drive will auto reset and try to clear fault;
press Fault Reset to try to reset fault,
then try to run pump. If fault continues,
replace drive.
Hardware Internal hardware failure. Press Fault Reset to try to reset fault, then Fault try to run pump.
If fault continues, replace drive.
External Fault External device detected a fault Check the external device.
condition and closed the I1 input.
Open Lead Motor has an open lead. Make sure that all motor lead connections
are tight and secure.
Motor’s thermal overload tripped. Wait for
it to cool and then restart pump.
Over Current Motor current has exceeded S F Amps. Drive goes into TPM and limits the motor
current.
Troubleshooting / Wiring Size Charts 15
Warning Cause Drive Operation
TPM: Service Motor current has exceeded S F Amps. Drive goes into TPM and limits the motor Amps current.
TPM: Speed Drive internal temperature limit Drive goes into TPM and limits the motor Reduced exceeded. current until it is within operating
temperature range.
Jam Warning Debris in pump has locked rotor. Drive reverses or pulses motor to try to
free it.
NOTE: No user action is required when a Warning is displayed.
VFD PENTEK
Maximum Cable Length in Feet (Meters)
Model Motor H.P. Volts/Hz/Ph 14AWG 12AWG 10AWG 8AWG 6AWG
3 Phase
PID-1-4A7-01
P43B0010A3 1.0 230/60/3 449(137) 715(218) 1000(305)
PID-1-7A6-01 PID-1-7A6-01 P43B0015A3 1.5 230/60/3 346(105) 551(168) 878(268) 1000(305) PID-1-7A6-01
P43B0020A3 2.0 230/60/3 278(85) 442(135) 705(215) 1000(305)
PID-1-10A1-01 PID-1-10A1-01 P43B0030A3 3.0 230/60/3 209(64) 333(101) 530(162) 840(256) 1000(305)
Table 5: AWG Wire Sizing, VFD to 3-Phase Motor.
NOTE: Information in this Table applies ONLY to PENTEK motors. For other motors, refer to motor
manufacturer’s specifications for wire sizing.
Table 6: AWG Wire Sizing, VFD to 3-Wire, 1-Phase Motor.
NOTE: Information in this Table applies ONLY to PENTEK motors. For other motors, refer to motor
manufacturer’s specifications for wire sizing.
VFD PENTEK
Maximum Cable Length in Feet (Meters)
Model Motor H.P. Volts/Hz/Ph 14AWG 12AWG 10AWG 8AWG 6AWG
3-Wire, 1 Phase
PID-6-9A7-01 P43B0005A2 0.5 230/60/1 431 (131) 686(209) 1000(305) PID-6-9A7-01 P43B0007A2 0.75 230/60/1 335(102) 533(162) 850(259) 1000(305) PID-6-9A7-01
P43B0010A2 1.0 230/60/1 293(89) 467(142) 744(227) 1000(305)
PID-6-12A2-01 PID-6-12A2-01 P43B0015A2 1.5 230/60/1 190(58) 303(92) 483(147) 764(233) 1000(305) PID-6-12A2-01 P43B0020A2 2.0 230/60/1 173(22) 275(84) 439(134) 696(212) 1000(305)
VFD PENTEK
Maximum Cable Length in Feet (Meters)
Model Motor H.P. Volts/Hz/Ph 14AWG 12AWG 10AWG 8AWG 6AWG
2-Wire, 1 Phase
PID-6-9A7-1-01
P42B0005A2 0.5 230/60/1 449 (137) 715(218) 1000(305) P42B0007A2 0.75 230/60/1 330(101) 525(160) 837(255) 1000(305)
Table 7: AWG Wire Sizing, VFD to 2-Wire, 1-Phase Motor.
NOTE: Information in this Table applies ONLY to PENTEK motors. For other motors, refer to motor
manufacturer’s specifications for wire sizing.
Loading...
+ 32 hidden pages