SSAC TA Series Data Sheet

Lockout Timer
Dedicated
timers
Lockout Delay--Prevents Rapid Recycling of a Compressor
Low Voltage Brownout Protection
Circuitry to Activate the Cooling Anticipator (24 V AC Models)
Eliminates Nuisance Service Calls Due to Blown Fuse or Tripped Breakers
TA Series HVAC/R Timer
Description
The TA Series prevents rapid recycling of a compressor. A lockout delay is started when the thermostat opens, or input voltage is lost. Eliminates tripped circuit breakers or blown fuses caused by a locked rotor during short cycling. The TA will not allow the compressor to start when the line voltage is low. Chatter of the compressor relay is eliminated. Because of the fast initiate time, bounce of the thermostat will not be transmitted to the compressor relay coil. A 30 second delay provides anti-reversing protection for scroll compressors.
Operation
On initial closure of the S1, the compressor relay energizes immediately. When S1 opens or input voltage is interrupted, a lockout time delay is initiated. During this lockout time delay, the compressor relay cannot be energized. The low voltage (brownout) protection prevents energization of the compressor when the line voltage is low.
Reset: The lockout time delay cannot be reset.
Function
V = Voltage S1 = Initiate Switch or Thermostat L = Load (CR) E = Ready R = Reset TD = Time Delay
Approvals:
(24 V AC only)
Connection
Accessories
Female quick connect P/N:
P1015-64
(AWG 14/16)
Quick connect to screw adaptor P/N: P1015-18
Mounting bracket P/N: P1023-6
DIN rail P/Ns:
017322005 (Steel) C103PM (Al)
DIN rail adaptor P/N: P1023-20
See accessory pages for speci cations.
5.166 Low Voltage Products & Systems
1TRC 001 009 C0202 ABB Inc. • 888-385-1221 • Technical assistance 800-377-7722 • www.ssac.com
Dashed lines are internal connections.
S1 = Initiate Switch, Contact, or Thermostat CR = Compressor Relay (Load) CA = Optional Cooling Anticipator
Ordering Table
24 V AC 24 V AC 24 V AC 24 V AC 12 V DC 24 V DC 24 V DC 24 V DC 24 V DC
30 s 2 m 3 m 5 m 1 m 30 s 2 m 3 m 5 m
Part NumberInput Time Delay
T
A24A0.5 TA24A2 TA24A3 TA24A5 TA12D1 TA24D0.5 TA24D2 TA24D3 TA24D5
TA002B01 01.05.05
Lockout Timer
TA Series HVAC/R Timer
Technical Data
Input
Voltage/Frequency 12 or 24 V DC; 24 V AC, 50 ... 60 Hz Impedance 450 Ω (anticipator by-pass)
Output
Minimum Load Current 75 mA Maximum Load Current 1 A at 60°C V
oltage Drop 1.25 V
Time Delay
Initiate Time 16 ms Lockout Time Fixed 0.5, 1, 2, 3, or 5 m Tolerance -15% ... +35%
Protection
Circuitry Encapsulated Low Voltage Protection 20 V: 24 V AC/DC; 9 V: 12 V DC Dielectric Breakdown 2000 V RMS terminals to mounting surface Insulation Resistance 100 MΩ
Mechanical
Mounting Surface mount with one #10 (M5 x 0.8) screw Package 2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm) Termination 0.25 in. (6.35 mm) male quick connect terminals
Environmental
Operating Temperature -40°C ... +70°C Storage Temperature -40°C ... +85°C Humidity 95% relative, non-condensing Weight 2.4 oz (68 g)
Thermostat
Cooling Anticipator Resistor 1800 Ω
Dedicated
timers
Mechanical View
Inches (Millimeters)
TA002B01 01.05.05
Low Voltage Products & Systems 5.167
ABB Inc. • 888-385-1221 • Technical assistance 800-377-7722 • www.ssac.com 1TRC 001 009 C0202