Lockout Timer
Dedicated
timers
Lockout Delay--Prevents
Rapid Recycling of a
Compressor
Low Voltage Brownout
Protection
Circuitry to Activate the
Cooling Anticipator (24 V AC
Models)
Eliminates Nuisance Service
Calls Due to Blown Fuse or
Tripped Breakers
TA Series
HVAC/R Timer
Description
The TA Series prevents rapid recycling of a compressor. A lockout delay is started when the thermostat
opens, or input voltage is lost. Eliminates tripped circuit breakers or blown fuses caused by a locked rotor
during short cycling. The TA will not allow the compressor to start when the line voltage is low. Chatter of
the compressor relay is eliminated. Because of the fast initiate time, bounce of the thermostat will not be
transmitted to the compressor relay coil. A 30 second delay provides anti-reversing protection for scroll
compressors.
Operation
On initial closure of the S1, the compressor relay
energizes immediately. When S1 opens or input voltage
is interrupted, a lockout time delay is initiated. During
this lockout time delay, the compressor relay cannot
be energized. The low voltage (brownout) protection
prevents energization of the compressor when the line
voltage is low.
Reset: The lockout time delay cannot be reset.
Function
V = Voltage S1 = Initiate Switch or Thermostat
L = Load (CR) E = Ready R = Reset
TD = Time Delay
Approvals:
(24 V AC only)
Connection
Accessories
Female quick connect
P/N:
P1015-64
(AWG 14/16)
Quick connect to
screw adaptor
P/N: P1015-18
Mounting bracket
P/N: P1023-6
DIN rail P/Ns:
017322005 (Steel)
C103PM (Al)
←
→
DIN rail adaptor
P/N: P1023-20
See accessory pages for
speci cations.
5.166 Low Voltage Products & Systems
1TRC 001 009 C0202 ABB Inc. • 888-385-1221 • Technical assistance 800-377-7722 • www.ssac.com
Dashed lines are internal connections.
S1 = Initiate Switch, Contact, or Thermostat
CR = Compressor Relay (Load) CA = Optional Cooling Anticipator
Ordering Table
24 V AC
24 V AC
24 V AC
24 V AC
12 V DC
24 V DC
24 V DC
24 V DC
24 V DC
30 s
2 m
3 m
5 m
1 m
30 s
2 m
3 m
5 m
Part NumberInput Time Delay
T
A24A0.5
TA24A2
TA24A3
TA24A5
TA12D1
TA24D0.5
TA24D2
TA24D3
TA24D5
TA002B01 01.05.05
Lockout Timer
TA Series
HVAC/R Timer
Technical Data
Input
Voltage/Frequency 12 or 24 V DC; 24 V AC, 50 ... 60 Hz
Impedance 450 Ω (anticipator by-pass)
Output
Minimum Load Current 75 mA
Maximum Load Current 1 A at 60°C
V
oltage Drop ≤ 1.25 V
Time Delay
Initiate Time ≅ 16 ms
Lockout Time Fixed 0.5, 1, 2, 3, or 5 m
Tolerance -15% ... +35%
Protection
Circuitry Encapsulated
Low Voltage Protection ≅ 20 V: 24 V AC/DC; ≅ 9 V: 12 V DC
Dielectric Breakdown ≥ 2000 V RMS terminals to mounting surface
Insulation Resistance ≥ 100 MΩ
Mechanical
Mounting Surface mount with one #10 (M5 x 0.8) screw
Package 2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm)
Termination 0.25 in. (6.35 mm) male quick connect terminals
Environmental
Operating Temperature -40°C ... +70°C
Storage Temperature -40°C ... +85°C
Humidity 95% relative, non-condensing
Weight ≅ 2.4 oz (68 g)
Thermostat
Cooling Anticipator Resistor ≥ 1800 Ω