Owner’s Manual
SCT Series
Portable Air Conditioner
1420 Century Dr., Suite 800
Carrollton, TX 75006
Telephone: 972-242-0007
6116 Westline Drive
Houston, TX 77036
Telephone: 713-673-0001
1-800-683-7768 Fax 972-242-0378
THANK YOU!
Thank you for choosing Spot Cooling System’s SCT series of
portable air conditioners. Spot Cooling is a solutions-based
manufacturer dedicated to the development of high-performance air
conditioners.
Please read This Manual which will describes the unit features and
explains how to set-up, operate and maintain your SCT series air
conditioner.
If you have comments or suggestions on how to improve the SCT
series of portable air conditioners please let us know. Our most
important source of information for product improvement is from our
customers. Please give us a call at 972-242-0007 or email us,
sales@extracooler.com.
Warning!
Improper installation, adjustment, alteration, service, or maintenance
can cause injury or property damage. Please read this instruction
manual before installing, operating or servicing the Extracooler SCT
Series unit.
This manual is the property of the owner. Leave this manual with the unit when set-up
and start-up are complete. SpotCooling Systems reserves the right to change design and
specifications without prior notice.
TABLE OF CONTENTS
Unit Specifications ....................................................................... 1
SCT Series Components .............................................................. 2
Equipment Checklist .................................................................... 3
Standard Features........................................................................ 5
Optional Features ......................................................................... 6
Installation Instructions ............................................................... 7
Unit Operation ............................................................................... 8
Preventative Maintenance .......................................................... 9
Troubleshooting Guide .............................................................. 11
Installing Replacement Parts ................................................... 14
Accessories ................................................................................. 16
Schematics .................................................................................. 18
Warranty ...................................................................................... 22
i
1
UNIT SPECIFICATIONS
Rating Information
Specification SCT-14 SCT-18 SCT-30 SCT-42 SCT-83
SCT-83B
Cooling Capacity,
BTU/hr
1 (
(Ton)
14,000
(1T)
17,600
(1.5T)
29,700
(2.5T)
42,200
(3.5T)
83,500
(6.9T)
Power Supply2,
volt/hertz/phase/amps
115/60/1/15 115/60/1/15 230/60/1/20 230/60/1/30 230/60/1/60
460/60/3/20
Thermostat Control
Mechanical Mechanical Mechanical Mechanical Mechanical
Metering Device
TX Valve TX Valve TX Valve TX Valve TX Valve
Total Power
Consumption, kW
1.3 1.4 2.9 4.2 8.7
9.3
Current Consumption, amps
11.7 12.0 12.5 18.3 37.8
13.2
Recommended Circuit amps
15 15 20 30 60
20
NEMA plug type
5-15P 5-15P 6-20P 6-30P Hard wired
Energy Efficiency
Rating
10.4 12.8 10.3 10.0 8.9
8.3
Evaporator CFM,
free discharge
350 600 750 1,200 2,300
Condenser CFM
500 1,000 1,000 1,500 3,900
Compressor Type
Hermetic
rotary
Hermetic
rotary
Hermetic
rotary
Hermetic
rotary
Hermetic
scroll
Maximum esp, in wc 0.10 0.10 0.10 0.10 0.50
Maximum Duct
Length, ft
40 40 40 40 40
Condensate-pump
head, ft
15 15 15 15 15
Operating Limits
(min-max) °F
65-105 65-110 65-105 65-105 65-110
Sound Level, dB 57 63 63 67 71
R-22 Charge, oz 32 52 54 80 110
L x W x H, in 26 x 20 x 34 29 x 28 x 41 29 x 28 x 41 30 x 28 x 51 42 x 30 x 70
Weight, net/ship lb 163/205 232/286 251/305 336/395 650/685
1—Rating conditions: 95°F at 60% RH. 2—Electrical ratings based on UL 484.
Limited
Warranty
Spot Cooling warrants to its authorized distributor or end-user,
each new SCT series portable air conditioner to be free from
defects in material and workmanship for a period of one (1)
year from date of purchase. The sole obligation of Spot Cooling under this warranty will be to furnish, without charge, a
replacement part for a defective part.
This warranty does not include installation, transportation, or
postage costs associated with installing the replacement part.
This warranty does not apply to equipment that has been damaged by accident, negligence, or misapplication or has been
altered or modified in any way. This warranty only applies to
the original purchaser.
In order for this warranty to become effective, the warranty
registration card, delivered with the unit, must be completed
and returned to Spot Cooling within 30 days of purchase and
delivery. Any claim under this warranty should be first
presented to and processed by the authorized distributor from
whom the equipment was purchased.
To the extent permitted by law, this warranty is expressly in
lieu of any other warranties, either expressed or implied, made
by Spot Cooling, Incorporated. Spot Cooling assumes no
liability in any event for lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data,
costs of substitutes, claims by third parties, or otherwise. This
warranty gives you specific legal rights and you may also have
other rights, which may vary from state to state.
WARRANTY
22