Product Information
Subject
Use With
Electrical Specifications
*F18-25 models; *F35-50 Water Saving System models
This insert is an update to the electrical information for the Cabinet Freestanding models listed
above. The information in this insert supersedes
the information shown in the electrical specification chart, for the models listed above only, found
in the Electrical Installation Section of the
installation/maintenance manual.
Cabinet Freestanding
Electrical Specifications
Voltage Designation Standard Electric Heat
Model
Code
X 200-240 50-60 1
P* 380-415 50-60 3 3 3 15 -- 3x2.5 12 15 -- 3x2.5
18
Q 200-240 50-60 3 3 5 15 14 -- 18 20 12 --
Vo lt ag e
Cycle
Phase
32
or
Wire
3 5.56/3.89 15 14
or
Amps
Note:
The X voltage is not compatible with CE
and/or electric heat models.
IMPORTANT: For machines with X voltage: If
input power is single-phase, connect L1 to L1 of
terminal block and L2 to L2 of terminal block.
Leave L3 unconnected on the input terminal block.
If input power is three-phase, connect L1, L2 and
L3 to L1, L2 and L3 of the terminal block.
Full Load
Breaker
AWG
mm
2
2x2.5
3x2.5
Full Load
Amps
Breaker
AWG
-- -- -- --
mm
2
T* 200-240 50-60 1 2 8 15 14 -- 31 35 8 --
X 200-240 50-60 1
P* 380-415 50-60 3 3 4 15 -- 3x2.5 13 15 -- 3x2.5
25
Q 200-240 50-60 3 3 7 15 14 -- 19 20 12 --
T* 200-240 50-60 1 2 12 15 14 -- 32 35 8 --
N 440-480 50-60 3 3 6 15 14 3x2.5 32 35 8 3x10
35
WSS
WSS
Note:
* For CE and/or electric heat models only.
P 380-415 50-60 3 3 6 15 14 3x2.5 32 35 8 3x10
Q 200-240 50-60 3 3 12 15 14 3x2.5 50 50 8 3x10
N 440-480 50-60 3 3 6 15 14 3x2.5 43 50 8 3x10
50
P 380-415 50-60 3 3 6 15 14 3x2.5 43 50 8 3x10
Q 200-240 50-60 3 3 12 15 14 3x2.5 76 80 4 3x25
Wire sizes shown are for copper, THHN, 90° conductor per NEC article 310.
32
or
310.57/6.14 15 14
or
2x2.5
3x2.5
-- -- -- --
Page 1 of 1
P/N F800352R2
P/N June 2000