SpectraLink 1728, 1738EX, 1738 User Manual

REFERENCE & INSTALLATION MANUAL
SPECTRA CONTROL PANELS V2.1
1728EX and 1728 1738EX and 1738
TABLE OF CONTENTS
Introduction .......................................................................................................................................... 4
Features............................................................................................................................................................................................... 4
Specifications....................................................................................................................................................................................... 4
Detectors, Keypads and Expansion Modules ...................................................................................................................................... 5
Location and Mounting ........................................................................................................................................................................ 7
Earth Ground ....................................................................................................................................................................................... 8
AC Power............................................................................................................................................................................................. 9
Backup Battery .................................................................................................................................................................................... 9
Auxiliary Power Terminals ................................................................................................................................................................... 9
Telephone Line Connection............................................................................................................................................................... 10
Bell Output Connection...................................................................................................................................................................... 10
Programmable Output Connections................................................................................................................................................... 10
Single Zone Inputs............................................................................................................................................................................. 11
Double Zone Inputs (with ATZ Option only)....................................................................................................................................... 11
Keypad and Keypad Zone Connections ............................................................................................................................................ 12
Keyswitch Connections...................................................................................................................................................................... 13
Fire Circuits........................................................................................................................................................................................ 13
Programming Methods........................................................................................................................ 13
WinLoad Software for Windows......................................................................................................................................................... 13
Programming Using a Keypad........................................................................................................................................................... 13
Configuring The LED Keypads .......................................................................................................................................................... 14
Programming Using A Paradox Memory Key .................................................................................................................................... 16
Access Codes ..................................................................................................................................... 16
Access Code Length.......................................................................................................................................................................... 17
Installer Code (Default: 000000) ........................................................................................................................................................ 17
System Master Code (Default: 123456)............................................................................................................................................. 17
User Code Options ............................................................................................................................................................................ 17
Lock Master Code.............................................................................................................................................................................. 18
Duress Code...................................................................................................................................................................................... 18
Zone Programming.............................................................................................................................. 19
What is an Expansion Input? ............................................................................................................................................................. 19
Reassign Keypad Zone 2 .................................................................................................................................................................. 19
Reassign Zones to Expansion Inputs (1728EX & 1728 Only) ........................................................................................................... 20
Zone Programming ............................................................................................................................................................................ 20
Zone Definitions................................................................................................................................................................................. 21
Exclusive Zone Definitions................................................................................................................................................................. 22
Zone Partition Assignment................................................................................................................................................................. 23
Zone Options ..................................................................................................................................................................................... 23
Zone Speed ....................................................................................................................................................................................... 25
EOL Zones......................................................................................................................................................................................... 25
ATZ - Zone Doubling (1728 and 1738 only)....................................................................................................................................... 25
Arming and Disarming Options........................................................................................................... 27
Switch To Stay Arming....................................................................................................................................................................... 27
Stay Arming with Delay...................................................................................................................................................................... 27
Regular Arming switches to Force Arming......................................................................................................................................... 27
Restrict Arming On Battery Fail ......................................................................................................................................................... 27
Restrict Arming On Tamper Failure ................................................................................................................................................... 27
Timed Auto-Arming............................................................................................................................................................................ 28
No Movement Auto-Arming................................................................................................................................................................ 28
Auto-Arming Options.......................................................................................................................................................................... 28
One-Touch Arming............................................................................................................................................................................. 29
Exit Delay........................................................................................................................................................................................... 29
Bell Squawk On Arm/Disarm With Keypad........................................................................................................................................ 29
Bell Squawk On Arm/disarm with Remote Control ............................................................................................................................ 29
No Exit Delay When Arming with Remote Control............................................................................................................................. 29
No Exit Delay Beeps and No Bell Squawk When Stay Arming.......................................................................................................... 29
Alarm Options .................................................................................................................................... 30
Bell Cut-Off Timer .............................................................................................................................................................................. 30
Recycle Alarm.................................................................................................................................................................................... 30
Tamper Recognition........................................................................................................................................................................... 30
Keypad Panic Options ....................................................................................................................................................................... 31
Panic Lockout Timer .......................................................................................................................................................................... 31
Reporting and Dialer settings............................................................................................................. 32
Reporting/Dialer (Enable/Disable) ..................................................................................................................................................... 33
Report Codes..................................................................................................................................................................................... 33
Central Station Telephone Numbers.................................................................................................................................................. 36
Partition Account Numbers ................................................................................................................................................................ 36
Reporting Formats............................................................................................................................................................................. 36
Pager Delay ....................................................................................................................................................................................... 37
Event Call Direction ........................................................................................................................................................................... 38
Dialing Method................................................................................................................................................................................... 38
Pulse Ratio ........................................................................................................................................................................................ 38
Bell on Communication Failure.......................................................................................................................................................... 38
Dial Tone Delay ................................................................................................................................................................................. 38
Maximum Dialing Attempts ................................................................................................................................................................ 39
Delay Between Dialing Attempts........................................................................................................................................................ 39
Alternate Dial Option.......................................................................................................................................................................... 39
Recent Close Delay ........................................................................................................................................................................... 39
Auto Test Report................................................................................................................................................................................ 39
Power Failure Report Delay............................................................................................................................................................... 39
Disarm Reporting Options.................................................................................................................................................................. 40
Zone Restore Report Options............................................................................................................................................................ 40
Telephone Line Monitoring (TLM)...................................................................................................................................................... 40
Programmable Outputs ...................................................................................................................... 41
PGM Activation Event........................................................................................................................................................................ 41
PGM Deactivation Event.................................................................................................................................................................... 41
PGM Delay ........................................................................................................................................................................................ 42
PGM Normal State............................................................................................................................................................................. 42
PGM2 Strobe Options (1738EX and 1738 only) ................................................................................................................................ 42
Alarm Relay Options (1738EX and 1738 only) .................................................................................................................................. 42
System Settings .................................................................................................................................. 43
Hardware Reset................................................................................................................................................................................. 43
Installer Lock...................................................................................................................................................................................... 43
Keypad Lockout Feature.................................................................................................................................................................... 43
Battery Charge Current...................................................................................................................................................................... 43
Partitioning......................................................................................................................................................................................... 43
System Real-Time Clock ................................................................................................................................................................... 44
Clock Adjust....................................................................................................................................................................................... 44
Keypad Tamper Supervision.............................................................................................................................................................. 44
Keypad Audible Trouble Warning ...................................................................................................................................................... 44
Confidential Mode.............................................................................................................................................................................. 45
Installer Quick Functions Keys........................................................................................................................................................... 45
4-Output Bus Module Supervision ..................................................................................................................................................... 45
Printer Bus Module Supervision......................................................................................................................................................... 46
Zone Expansion Bus Module Supervision ......................................................................................................................................... 46
Wireless Bus Module Supervision ..................................................................................................................................................... 46
Wireless Transmitter Low Battery Supervision .................................................................................................................................. 46
Wireless Transmitter Supervision Options......................................................................................................................................... 46
ReProgram All Expansion Modules ................................................................................................................................................... 47
Settings for WinLoad Software........................................................................................................... 48
Panel Answer Options ....................................................................................................................................................................... 48
Panel Identifier................................................................................................................................................................................... 48
PC Password ..................................................................................................................................................................................... 48
PC Telephone Number ...................................................................................................................................................................... 48
Call WinLoad Software ...................................................................................................................................................................... 49
Answer WinLoad Software................................................................................................................................................................. 49
Auto Event Buffer Transmission ........................................................................................................................................................ 49
Call Back WinLoad............................................................................................................................................................................. 49
User Operation ................................................................................................................................... 50
Trouble Display.................................................................................................................................................................................. 50
Programming Access Codes ............................................................................................................................................................. 51
Disarming & Deactivating an Alarm ................................................................................................................................................... 52
Regular Arming.................................................................................................................................................................................. 52
Stay Arming ....................................................................................................................................................................................... 52
Instant Arming.................................................................................................................................................................................... 52
Force Arming ..................................................................................................................................................................................... 53
Manual Bypass Programming............................................................................................................................................................ 53
One-Touch Arming............................................................................................................................................................................. 54
Keyswitch Arming .............................................................................................................................................................................. 54
Panic Alarms...................................................................................................................................................................................... 54
Auto-Arming....................................................................................................................................................................................... 54
Alarm Memory Display....................................................................................................................................................................... 54
Programming Chime Zones............................................................................................................................................................... 55
Keypad Muting................................................................................................................................................................................... 55
Keypad Backlight (1686H and 1686V only) ....................................................................................................................................... 55
FCC WARNINGS .................................................................................................................................. 56
Index.................................................................................................................................................... 58
LIST OF TABLES
Transformer Requirements Table........................................................................................................................................................ 9
Current Consumption Table................................................................................................................................................................. 9
Decimal and Hexadecimal Programming Table................................................................................................................................. 14
Zone Recognition Table..................................................................................................................................................................... 19
Example............................................................................................................................................................................................. 19
Zone Display with 10-Zone LED Keypad........................................................................................................................................... 20
Special Keys for Telephone Numbers ............................................................................................................................................... 36
Reporting Formats............................................................................................................................................................................. 36
Zone Tamper Report Code for Keypad Tamper Supervision Failure ................................................................................................ 44
Trouble List ........................................................................................................................................................................................ 50
1.1 FEATURES
• Up to 16 fully programmable zones
• Two completely independent partitions. Many of the features and options in the Spectra System can be independently set for each partition such as event reporting, entry/exit delay, auto-arming and many more. All zones, the keyswitches and all user codes are assigned to specific partitions, which makes this a true partitioned system.
• Communication bus facilitates the adding, programming and monitoring of all expansion modules.
• 1 Installer Code and 48 User Codes (including: 1 System Master, 2 Masters, and 1 Duress)
• 1738/EX: 2 on-board, fully programmable outputs (PGMs) and 1 optional 5A alarm relay
• 1728/EX: 1 on-board, fully programmable output
• Simple, direct and logical programming
• Event Call Direction: The Spectra Series Control Panel events are divided into 5 groups of events. Each of these event groups can be programmed with a separate dialing sequence.
• Two 32-digit Central Station Telephone Numbers and one 32-digit Backup Telephone Number
• Contact ID, Pager Format and many more High-Speed Communication Formats
• "False Alarm Prevention" features such as: Intellizone, Auto Zone Shutdown, Beep on Exit Delay, Programmable Delay Before Alarm Transmission, and Recent Closing Report
• Regular Arming, Stay Arming, Instant Arming, Force Arming, One-Touch Arming, Auto-Arming, or Keyswitch Arming
• 256 Event Buffer with time stamp
• Telephone Line Supervision
• Keypad activated panic alarms
• Compatible with Winload Security System Management Software for Windows®
PART 1: INTRODUCTION
1.2 SPECIFICATIONS
1.2.1 SPECTRA 1728/EX AND 1738/EX CONTROL PANELS
•AC Power:* 16VAC transformer with minimum 20VA rating (Rec.: 40VA), 50 to 60Hz
Battery: 12VDC, 4Ah/7Ah
•Aux. Power:
Bell Output:
PGM Outputs: PGM1 = 150mA for 1728EX and 1728
1.2.2 SPECTRA KEYPADS (1686H, 1686V, 1689 & 1641)
Power input: 9-16VDC,
1 standard keypad zone
On-board Tamper Switch (optional)
1686H & 1686V 10-Zone LED Keypad
Current Consumption: 62 to 116mA
1689 16-Zone LED Keypad
Current Consumption: 50 to 117mA
1641 32-Character LCD Keypad
Current Consumption: 60 to 80mA
PGM: 1 with 50mA current limit
LCD: Super Twisted Nematic display (STN), Wide viewing angle, Backlight &
++
+
600mA typical, 700mA maximum, fuseless shutdown @ 1.1A 1A, fuseless shutdown @ 3A
PGM1 and PGM2 = 1A for 1738EX and 1738 only
Contrast adjustable
* Only the 16.5VAC, 40VA version is UL listed.
+
200mA typical for UL installations
++
1A for UL installations total, including PGM options
4 REFERENCE & INSTALLATION MANUAL
1.3 DETECTORS, KEYPADS AND EXPANSION MODULES
If you would like to obtain more information on our line of keypads, security system accessories or other security products, please contact your local Paradox distributor or visit our web site at http://www.paradox.ca.
1.3.1 SPECTRA 1686H AND 1686V 10-ZONE LED KEYPADS
The elegant Spectra 1686H/1686V LED keypads’ patented Key-light feature provides a user-friendly display of the system’s current status. For example, if zone 5 is open, the [5] key turns on. What could be simpler? Designed to be compatible with any Spectra Series control panel, our Euro­style Spectra keypads eliminate stocking and ordering concerns.
1.3.2 SPECTRA 1689 16-ZONE LED KEYPADS
The Spectra 1689 LED keypad’s brilliant display provides instant feedback of the system’s current status. Designed to be compatible with any Spectra Series control panel, this ergonomic and user-friendly keypad will complete any installation.
1.3.3 SPECTRA 1641 LCD KEYPAD
The 1641 is a 32-character programmable LCD keypad which includes a zone input as well as a PGM output. View zone, event and trouble status for one or more partitions, display entry/exit delay, adjust contrast, backlight, and many other features. Most messages in the LCD keypad are programmable.
1.3.4 PRINTER BUS MODULE
The Printer Module (APR3-PRT1) provides you with the ability to automatically print events as they occur in the system or the events can be stored in the module’s event buffer so you can print the events manually. The events can be sent to a dot matrix printer or can be viewed and printed from a computer. Includes a 50mA PGM output. Due to its Auto-panel Recognition feature, modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and Digiplex. Modules with the APR3- prefix are compatible with Spectra( versions 2.0 and higher), Digiplex and DigiplexNE.
1.3.5 4-OUTPUT BUS MODULE*
When connected to the Spectra communication bus, this module (APR3-PGM4) will provide four additional 5A programmable outputs to the Spectra system. Due to its Auto­panel Recognition feature, modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and Digiplex. Modules with the APR3- prefix are compatible with Spectra( versions 2.0 and higher), Digiplex and DigiplexNE.
* Not UL listed
SPECTRA SERIES 5
1.3.6 INTOUCH VOICE-ASSISTED ARM/DISARM BUS MODULE*
Using a touch-tone telephone, users can arm or disarm their security system from a distance as well as activate or deactivate the APR3-ADM2’s on-board PGM output. Due to its Auto-panel Recognition feature, modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and Digiplex. Modules with the APR3- prefix are compatible with Spectra( versions 2.0 and higher), Digiplex and DigiplexNE.
1.3.7 ZONE EXPANSION BUS MODULES*
Connected to the Spectra control panel’s communication bus, the fully supervised zone expansion modules provide you with up to 4 (SPC/APR3-ZX4) or up to eight (SPC/APR3-ZX8) additional hardwired inputs and one normally open 50mA PGM output (SPC/APR3-ZX8 only). Due to its Auto-panel Recognition feature, a module with the APR- prefix is compatible with Spectra (versions 2.0 and higher) and Digiplex. Modules with the APR3- prefix are compatible with Spectra( versions 2.0 and higher), Digiplex and DigiplexNE.
1.3.8 WIRELESS BUS MODULE*
Connected to the Spectra control panel’s communication bus, the fully supervised Wireless Bus Module (SPC-319) allows you to add up to eight fully programmable remote controls and up to eight Liberator Wireless Detectors and Contact Switches (door contacts). The SPC-319 also provides one programmable 5A relay (PGM). A second 5A programmable relay (PGM) is available as an option.
1.3.9 PARAVOXTM - VOICE DIALER*
In areas where security system monitoring is not available, let the sophisticated Paravox voice dialer take over. Compatible with any control panel, the Paravox will verbally report system status by phone, advising of detection of burglary, fire, flood or any other situation programmed to generate a report condition. Fully programmable over the telephone (no external keypad required), the Paravox guides the end user through all system functions with a full set of voice prompts. All the user needs to remember is their P.I.N. The “Key Ahead” feature eliminates the frustration and time wasted for experienced operators by allowing them to key-in selections before a prompt ends.
1.3.10 DIGITAL DETECTORS
The Paradox DigigardTM (50/60/70) digital motion detectors can immediately identify the signal produced by a moving human body and will not be triggered by any other occurrences in the protected area. False alarms are virtually eliminated. Using 100% digital detection technology and smart digital processing software leaves no room for error. With the Digigard 70, animal lovers can maximize their security protection. Thanks to the unique design of the patent-pending Digigard “pet-friendly” lens and dual “decision” optics, the Digigard 70 double-checks every movement signal.
Take all that’s good about infrared digital detection, add an advanced microwave “supervisor” and you have Digital Vision motion detectors. Once the Vision’s digital infrared detector identifies an intruder, its microwave sensor must confirm the presence of movement before an alarm is triggered.
* Not UL Listed
6 REFERENCE & INSTALLATION MANUAL
PART 2: INSTALLATION
2.1 LOCATION AND MOUNTING
Before mounting the cabinet, push the five white nylon mounting studs into the back of the cabinet. Pull all cables into the cabinet and prepare them for connection before mounting the circuit board into the back of the cabinet. Select an installation site that isn't easily accessible to intruders and leave at least 2in. (5cm) around the panel box to permit adequate ventilation and heat dissipation. The installation site should be dry and close to an AC source, ground connection and telephone line connection.
Figure 2.1: Spectra 1738EX and 1738 Control Panel Overview
For the keypad’s zone, EOL and tamper configurations, refer to Configuring The LED Keypads on page 14.
SPECTRA SERIES 7
Figure 2.2: Spectra 1728EX and 1728 Control Panel Overview
For the keypad’s zone, EOL and tamper configurations, refer to Configuring The LED Keypads on page 14.
2.2 EARTH GROUND
Connect the zone and dialer ground terminals from the control panel to the metallic enclosure and cold water pipe or grounding rod as per local electrical codes.
For maximum lightning protection, use separate earth grounds for the zone and dialer grounds as shown in Figure 2.1 on page 7. For UL installations, the metallic enclosure must be grounded to the cold water pipe.
8 REFERENCE & INSTALLATION MANUAL
2.3 AC POWER
Do not use any switch-controlled outlets to power the transformer. Connect the transformer as shown in Figure 2.1 on page 7. Use Table 1 to determine the required transformer.
Table 1:
Transformer: Amseco XP-1620 16VAC 20VA
Spectra DC Power Supply rated at: 1.2A 1.5A Auxiliary Supply can provide a maximum of: typ: 600mA, max: 700mA typ: 600mA, max: 700mA Acceptable Battery Charge Currents 350mA 350mA/700mA
Transformer Requirements Table
(Not verified by UL)
UL: Basler Electric BE156240CAA007
16.5VAC 40VA
2.4 BACKUP BATTERY
In order to provide power during a power loss, connect a 12VDC 4Ah rechargeable acid/lead or gel cell backup battery as shown in Figure 2.1 on page 7. Use a 7Ah battery to comply with UL fire requirements. Connect the backup battery after applying AC power. When installing verify proper polarity as reversed connections will blow the battery fuse. Also, refer to Battery Charge Current on page 43.
2.4.1 BATTERY TEST
If the battery is disconnected or if the battery fuse is blown, a No/Low Battery failure will appear in the keypads’ Trouble Display (see page 50). This trouble will also appear if the battery’s capacity is too low or if the voltage drops to 10.5 volts or lower while the control panel is running on the backup battery. At 8.5 volts or lower, the panel shuts down and all outputs close.
2.5 AUXILIARY POWER TERMINALS
The auxiliary power supply terminals can be used to power motion detectors, keypads and other modules or accessories in the security system. A fuseless circuit protects the power supply against current overload and automatically shuts down if the current exceeds 1.1A. If this occurs, the Maximum Auxiliary Current failure will appear in the keypads’ Trouble Display (see page 50). Therefore, the combined current consumption of devices connected to the auxiliary power supply should not exceed 700mA. If the auxiliary output is overloaded and is shut down, you must disconnect all loads from the output for at least 10 seconds before reconnecting any load back to the auxiliary output.
Modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and Digiplex. Modules with the APR3- prefix are compatible with Spectra( versions 2.0 and higher), Digiplex and DigiplexNE.
Table 2:
Modules Current Consumption
Spectra 1686H and 1686V 10-Zone LED Keypad 62mA 116mA Spectra 1689 16-Zone LED Keypad 50mA 117mA Spectra 1641 LCD Keypad 60mA 80mA Wireless Expansion Bus Module (SPC-319) 70mA 70mA 8-Zone Hardwire Bus Modules (APR3-ZX8) 30mA 30mA 4-PGM Output Bus Module (APR3-PGM4) 13mA 150mA Printer Bus Module (APR3-PRT1) 22mA 40mA 4-Zone Expansion Bus Module (SPC-ZX4) 12mA 12mA InTouch Voice-Assisted Arm/Disarm Bus Module (APR3-ADM2) 70mA 105mA Motion Detectors (see detector instructions for details) 10 to 50mA
Current Consumption Table
Typical Maximum
SPECTRA SERIES 9
2.6 TELEPHONE LINE CONNECTION
In order to report system events to the central station, you must connect the incoming telephone company wires into the TIP and RING connections of the control panel and then run the wires from T1 and R1 to the telephone or telephone system as shown in Figure 2.1 on page 7.
2.7 BELL OUTPUT CONNECTION
The BELL+ and BELL- terminals power bells, sirens and other warning devices requiring a steady voltage output during an alarm. The bell output supplies 12VDC upon alarm and can support one 30-watt or two 20-watt sirens. The bell output uses a fuseless circuit and will automatically shut down if the current exceeds 3A. When this occurs the Maximum Bell Current failure will only appear in the keypads’ Trouble Display (see page 50) during an alarm. If the load on the BELL terminals returns to normal, the control panel will re-instate power to the BELL terminals during the next alarm. When connecting sirens, please verify correct polarity. Connect the positive lead to the BELL+ terminal and the negative lead to the BELL- terminal of the control panel as shown in Figure 2.1 on page 7.
If the BELL output is not being used, the Bell Disconnected failure will remain in the keypads’ Trouble Display (see page 50). To avoid this connect a 1KΩ resistor across the BELL terminals.
2.8 PROGRAMMABLE OUTPUT CONNECTIONS
When a specific event occurs in the system, a PGM can reset smoke detectors, activate strobe lights, open/close garage doors and much more.
2.8.1 PGM FOR 1728EX AND 1728
The Spectra 1728/EX control panels include one on-board programmable output (PGM). PGM1 provides a maximum 150mA output. If the current draw on the PGM is to exceed the current output, we recommend the use of a relay as shown in Figure 2-2. For details on how to program the PGM, refer to PGM Programming on page 41.
Figure 2.3: PGM
2.8.2 ALARM RELAY AND PGMS FOR 1738EX AND 1738
The Spectra 1738/EX control panels include two on-board programmable outputs (PGMs). PGM1 and PGM2 provide up to 1A and PGM2 can be used as a strobe output (see page 42). The PGMs are limited by the power source being used. If powered by the
BELL+ terminal, the combined current consumption of the bell output and PGM must not
exceed 1A. If it is powered by the supply and PGM must not exceed 1.1A. If it is powered by an external device, PGMs can supply 1A. If the current draw on the PGM is to exceed the current output, we recommend using a relay (see Figure 2.4). For details on how to program the PGM, refer to PGM Programming on page 41.
The Spectra 1738/EX control panels also have an optional 5A relay. This relay can be connected as shown in Figure
2.4. The Alarm Relay can be programmed to follow the bell output or the activation and deactivation of the Global
PGM (see Alarm Relay Options on page 42).
AUX+, the devices connected to the auxiliary power
Figure 2.4: Relay and PGM Connections
10 REFERENCE & INSTALLATION MANUAL
2.9 SINGLE ZONE INPUTS
Detection devices such as motion detectors and door contacts are connected to the control panel's zone input terminals. Figure 2.5 on page 11 demonstrates single zone input terminal connections recognized by Spectra. Once connected, the associated zone's parameters must be defined. For details refer to Zone Programming on page 19.
Figure 2.5: Single Zone Input Connections
2.10 DOUBLE ZONE INPUTS (WITH ATZ OPTION ONLY)
Enabling the ATZ feature (see page 25) on the Spectra 1728 or 1738 allows you to install two detection devices per input terminal. The ATZ feature is a software oriented feature. Therefore, there is no need for extra modules. Simply connect the devices as shown in Figure 2.6. Devices connected to input terminals must be assigned to a zone and the zone's parameters must be defined. Refer to Zone Programming on page 19 for more information. The status of each zone will be displayed on the keypads and the control panel can send separate alarm codes for each zone.
SPECTRA SERIES 11
Figure 2.6: Double Zone (ATZ) Input Connections
2.11 KEYPAD AND KEYPAD ZONE CONNECTIONS
To connect the keypads to the control panel, remove the back cover and wire the GRN, YEL, RED, and BLK terminals of each keypad to the corresponding terminals on the control panel as shown in Figure 2.1 on page 7 or Figure 2.2 on page 8. There is no limit to the number of keypads that can be connected to the control panel so long as the current consumption does not surpass 700mA. For details on Keypad Tamper Supervision see section 10.8 on page 44.
Each keypad has one zone input terminal, allowing you to connect one motion detector or door contact directly to a keypad. The keypad can then communicate the status of the zone to the control panel. A maximum of two keypad zones can be used with each control panel. After connecting the device, the zone's parameters must be defined. For details on zone recognition and Zone Programming refer to page 19. Also, refer to the feature Reassign Keypad Zone 2 on page 19.
Example: A door contact located at the entry point of an establishment can be wired directly to the input terminal of the entry point keypad instead of wiring the door contact all the way to the control panel.
Figure 2.7: Keypad Zone Connections
12 REFERENCE & INSTALLATION MANUAL
2.12 KEYSWITCH CONNECTIONS
Fi
h
Keyswitches allow users to arm or disarm a partition by pushing a button or by activating a switch with a key. Connect the keyswitch as shown in Figure 2.8 directly to the control panel terminals. Once a keyswitch is connected, it must be assigned to a zone and its parameters must be programmed (see Zone Programming on page 19 and Keyswitch Options on page 25).
2.13 FIRE CIRCUITS
When a zone is programmed as a Fire zone, the zone becomes normally open and requires an EOL resistor. If a line short occurs or if the smoke detector becomes active, whether the system is armed or disarmed, the control panel will generate an alarm. If a trouble occurs on a Fire zone, the Fire Loop Trouble will appear in the keypads’ Trouble Display (see page 50) and the control panel can transmit the Fire Loop Trouble report, if programmed, in section [206].
2.13.1 4-WIRE INSTALLATION:
Any on-board zone can be defined as a Fire Zone (see page 21) when using the 4-wire installation. Connect the smoke detectors as shown in Figure 2.9 directly to the control panel terminals. Program the PGM with the “[
PG]/[FNC1] Key was Pressed” Activation Event (see page 41) so the
smoke detectors can be reset by pressing the [ the [
PG] or [FNC1] key will interrupt power to the smoke detectors for 4
seconds (see PGM Delay on page 42).
gure 2.8: Keyswitc
Figure 2.9: Fire Zones
PG] or [FNC1] key. Pressing
PART 3: PROGRAMMING METHODS
3.1 WINLOAD SOFTWARE FOR WINDOWS
Program the Spectra Series control panels remotely or on-site using the Winload Software for Windows®. For more information, contact your local Paradox Distributor or visit our web site at http://www.paradox.ca. If you are using the WinLoad software, you must program the features explained on pages 48 and 49.
3.2 PROGRAMMING USING A KEYPAD
Use the supplied Spectra 1728EX, 1728, 1738EX and 1738 Programming Guide to keep track of which sections were programmed and how. We recommend you read this entire manual before you begin programming.
How Do I Enter Programming Mode?
[ENTER]
[SECTION] you wish to program
[DATA]
STEP 1: Press
STEP 2: Enter your [INSTALLER CODE] (default: 000000 or 0000)
STEP 3: Enter 3-digit
STEP 4: Enter required
3.2.1 SINGLE DIGIT DATA ENTRY METHOD (HEXADECIMAL AND DECIMAL)
Single Digit Data Entry is used in all sections except those specified in the Feature Select Programming Method. After entering the programming mode as described in the shaded box above, some sections will
require that you enter Decimal values from 000 to 255. Other sections will require that you enter Hexadecimal values from 0 to F. The required data will be clearly indicated in this manual as well as in the
Spectra 1728EX, 1728, 1738EX and 1738 Programming Guide. When entering the final digit in a section, the control panel will automatically save and advance to the next section. Except sections 001 to 016, after entering the first two digits the control panel will switch to Feature Select Programming.
SPECTRA SERIES 13
Table 3:
Decimal and Hexadecimal Programming Table
Value or Action
What Do I
Press?
Values 1 to 9 [1] to [9] A (hexa only) [0] [0 (10)] [10] 0 B
(hexa only)
C
(hexa only)
D
(hexa only)
E
(hexa only)
F
(hexa only)
Exit Without Saving Insert Blank Digit Save Data
[STAY][STAY]
[BYP][BYP]
[MEM][MEM]
[TBL] / [TRBL][TBL]
[PG] / [FNC1][PG]
[
[
CLEAR]
FORCE]
[ [
ENTER]
ENTER] flashes [ARM1] & [STAY1] flash “SECTION [ ]”
Displays next digit or next section Advances to the next section
3.2.2 FEATURE SELECT PROGRAMMING METHOD
After entering sections [001] to [016], [126] to [138], and [302] to [348], each option from [1] to [8] represents a specific feature or option. Press the key corresponding to the desired option and the corresponding light will illuminate or the option number will appear in the LCD display. This means the option is on. Press the key again to extinguish the corresponding light or remove the digit from the LCD display, thereby, turning off the option. Press the [ the current section’s options are set. When the options are set, press the [ to the next section.
What Do I See?
10-Zone LED 16-Zone LED LCD
[1] to [9] [1] to [9] [1] to [9]
[11] B [12] C [13] D [14] E [15] F
FORCE] key to set all 8 options to off. Press the keys until
ENTER] key to save and advance
3.2.3 DATA DISPLAY MODE (LED KEYPADS ONLY)
In the Data Display Mode you can view the programmed contents of each section one digit at a time. After entering the desired 3-digit section (see step 3 of the shaded box on page 13), press the [ access the Data Display Mode (will not function with sections using Multiple Feature Select Programming).
Figure 3.1: Data Display Mode (LED Keypads Only)
ENTER] key to
3.3 CONFIGURING THE LED KEYPADS
Depending on the version of the keypad, two methods can be used to configure the LED keypads (1686H, 1686V and 1689):
14 REFERENCE & INSTALLATION MANUAL
3.3.1 CONFIGURING THE 1686H, 1686V AND 1689 KEYPADS V2.0 OR HIGHER
The keypad’s zone number, EOL definition and tamper switch are programmed through the control panel’s programming mode. To do so:
How Do I Configure The Keypad?
STEP 1: Press
STEP 2: Enter your [INSTALLER CODE] (default: 000000 or 0000)
STEP 3: Press the
STEP 4: Press the desired key ([1] to [3]. See below) STEP 5: Press [
PLEASE NOTE: After two minutes, the keypad exits programming mode.
Key [1] - Keypad Zone Selection
Key [1] determines whether the keypad’s zone is Keypad Zone 1 or Keypad Zone 2. When key [1] is OFF (not illuminated), the keypad’s zone is Keypad Zone 1. When key [1] is ON (illuminated), the keypad’s zone is Keypad Zone 2.
Key [1] OFF - Keypad Zone 1 (default) Key [1] ON - Keypad Zone 2
Key [2] - EOL Definition
Key [2] determines the keypad zone’s EOL definition. When key [2] is OFF (not illuminated), EOL is disabled and the keypad zone will use the on-board EOL resistor. When key [2] is ON (illuminated), EOL is enabled and the keypad zone requires that an external EOL resistor be connected (refer to Spectra
1738EX and 1738 Control Panel Overview on page 7 and Spectra 1728EX and 1728 Control Panel Overview on page 8 for more details).
Key [2] OFF - EOL disabled Key [2] ON - EOL enabled (default)
[ENTER]
[PG] (1686H/V) / [FNC1] (1689) key and hold it for 3 seconds.
ENTER] to exit programming mode
Key [3] - On-Board Tamper
Key [3] enables or disables the keypad’s on-board tamper switch. When key [3] is OFF (not illuminated), the tamper switch is disabled. When key [3] is ON (illuminated), the tamper switch is enabled.
Key [3] OFF - On-board tamper switch disabled Key [3] ON - On-board tamper switch enabled
PLEASE NOTE: The keypad can be ordered with or without a tamper switch. If the keypad has no tamper switch, key [3] will be OFF by default. If the keypad has a tamper switch, key [3] will be ON by default.
3.3.2 CONFIGURING THE 1686H, 1686V AND 1689 KEYPADS PRIOR TO V2.0
The keypad’s zone number and EOL definition are defined through the jumpers located on the PCB board. The jumpers are as follows:
J1 - Keypad Zone Select Jumper
Jumper J1 determines whether the keypad’s zone is Keypad Zone 1 or Keypad Zone 2. When the jumper is OFF, the keypad’s zone is Keypad Zone 2. When the jumper is ON, the keypad’s zone is Keypad Zone 1.
J1 OFF - Keypad Zone 2 J1 ON - Keypad Zone 1
SPECTRA SERIES 15
J2 - EOL Definition Jumper
Jumper J2 determines the keypad zone’s EOL definition. When the jumper is OFF, EOL is disabled and the keypad zone uses the on-board EOL resistor. When the jumper is ON, EOL is enabled and the keypad zone requires that an external EOL resistor be connected (refer to Spectra 1738EX and 1738 Control Panel Overview on page 7 and Spectra 1728EX and 1728 Control Panel Overview on page 8 for more details).
J2 OFF - EOL disabled J2 ON - EOL enabled
3.4 PROGRAMMING USING A PARADOX MEMORY KEY
Copy the sections of one Spectra control panel into the Paradox Memory Key (PMC-3). Then copy the contents of the Memory Key into as many Spectra control panels as needed. Each panel is programmed in less than 3 seconds.
Download to DESTINATION Control Panel
1) Remove AC and battery power from the control panel.
2) Place the Memory Key on the serial connector labeled
that is to receive the contents of the Memory Key.
3) Reapply AC and battery power.
4) In installer programming mode, enter section [900], then press [
5) When the keypad emits a Confirmation Beep, remove the Memory Key.
6) Enter section [750] to reprogram the modules with the information downloaded from the Paradox Memory Key.
Copy to Memory Key from SOURCE Control Panel
1) Remove AC and battery power from the control panel.
2) Place Memory Key on the serial connector labeled
you want to copy. Make sure the write protect jumper of the Memory Key is on.
3) Reapply AC and battery power.
4) In installer programming mode, enter section [902], then press [
5) When the keypad emits a Confirmation Beep, remove the Memory Key. Remove the
Memory Key’s jumper if you do not wish to accidentally overwrite its contents.
Figure 3.2: Paradox Memory Key
KEY of the Spectra Control Panel
ENTER] to acknowledge.
KEY of the Spectra Control Panel that
ENTER] to acknowledge.
PART 4: ACCESS CODES
The Spectra Series control panels support the following access codes:
INSTALLER CODE: Used to program all control panel settings except User Access Codes. SYSTEM MASTER CODE (001) Provides full access. Arm and disarm using any method described in the User Code
Options in section 4.4 as well as program the User Access Codes.
Master Code 1 (002): Permanently assigned to partition 1. Same as a regular User Code except it can
also program access codes for User Codes assigned to partition 1.
Master Code 2 (003): Permanently assigned to partition 2. Same as a regular User Code except it can
program access codes for User Codes assigned to partition 2. If the system is not partitioned Master Code 002 will be assigned to partition 1.
45 User Codes (004 to 048): Can arm and disarm as per User Code Options in section 4.4.
16 REFERENCE & INSTALLATION MANUAL
4.1 ACCESS CODE LENGTH
Section [127]: System Options
Option [2] OFF = 6-Digit Access Codes Option [2] ON = 4-Digit Access Codes (default)
All access codes can be set to lengths of either 4- or 6-digits. When the 4-digit option is selected, entering a 4-digit code will allow access. Using the 6-digit option, entering 6 digits is required to allow access.
If the Access Code Length is changed from four digits to six digits when access codes have already been programmed, the control panel will automatically add the last 2 digits by using the first 2 digits. For example, if the access code is 1234 and you switch to 6 digits, the code will become 123412. Be sure to verify the access codes after switching from 4-digit access codes to 6-digit codes. When switching from six digits to four digits, the control panel will simply remove the final two digits of the access code. For example, 123456 will become 1234.
4.2 INSTALLER CODE (Default: 000000 OR 0000)
The Installer Code is used to enter the control panel's programming mode (see page 13), which allows you to program all the features, options and commands of the control panel. The Installer Code can be 4- or 6-digits in length (see above) where each digit can be any value from 0 to 9. The Installer Code cannot be used to program Master Code 1, Master Code 2 or User Access Codes. To program the Installer Code press:
[
ENTER] + [CURRENT INSTALLER CODE] + [281] + new 4- or 6-digit Installer Code
4.3 SYSTEM MASTER CODE (Default: 123456 OR 1234)
The Installer Code can be used to program the System Master Code. With the System Master Code a user can use any arming method and can program any User Access Code, but not the User Code Options. The System Master
Code can be 4 or 6 digits in length (see section 4.1), where each digit can be any digit from 0 to 9. To change the System Master Code press:
[
ENTER] + [INSTALLER CODE] + [301] + new 4- or 6-digit System Master Code
4.4 USER CODE OPTIONS
Sections [302] to [348]: Options [1] to [7]
The User Code Options define which arming methods each user can use to arm or disarm the system. Regardless of these settings, all users can Regular Arm assigned partitions and all users except those with the Arm Only option can disarm an assigned partition, regardless of how it is armed. Select one or more of the options described on the following pages for each User Access Code, where sections [302] to [348] represent User Access Codes 002 to
048. For information on how User Access Codes are programmed, please refer to page 51.
4.4.1 PARTITION 1 ASSIGNMENT
Sections [302] to [348]: User Codes 002 to 048
Option [1] OFF = Deny access to partition 1 Option [1] ON = User code has access to partition 1 (default)
If Partitioned (see page 43), user codes with this option enabled can arm and disarm partition 1.
If the system is not partitioned, you must assign partition 1 to the User Access Code. Otherwise, the User Access Code will be considered disabled.
4.4.2 PARTITION 2 ASSIGNMENT
Sections [302] to [348]: User Codes 002 to 048
Option [2] OFF = Deny access to partition 2 (default) Option [2] ON = User code has access to partition 2
If the system is partitioned (see page 43), user codes with this option enabled can arm and disarm partition
2. If the system is not partitioned, the control panel ignores this option.
SPECTRA SERIES 17
4.4.3 BYPASS PROGRAMMING
Sections [302] to [348]: User Codes 002 to 048
Option [3] OFF = Bypass Programming Disabled Option
User codes with this option enabled can perform Bypass Programming in assigned partitions.
[3]
ON = Bypass Programming Enabled (default)
4.4.4 STAY ARMING
Sections [302] to [348]: User Codes 002 to 048
Option [4] OFF = Stay Arming Disabled Option
User codes with this option enabled can Stay Arm assigned partitions.
[4]
ON = Stay Arming Enabled for selected User Code (default)
4.4.5 FORCE ARMING
Sections [302] to [348]: User Codes 002 to 048
Option [5] OFF = Force Arming Disabled (default) Option [5] ON = Force Arming Enabled for selected User Code
User codes with this option enabled can Force Arm assigned partitions.
4.4.6 ARM ONLY
Sections [302] to [348]: User Codes 002 to 048
Option [6] OFF = Arm Only Disabled (default) Option [6] ON = Arm Only Enabled for selected User Code
The user code with this option enabled can arm assigned partitions, but cannot disarm any partitions. The type of arming is dependent on the other User Code Options selected. Please note that with the Arm Only option, the user can cancel a recently armed system by re-entering the access code before the end of the Exit Delay.
4.4.7 PGM ACTIVATION
Sections [302] to [348]: User Codes 002 to 048
Option Option [7] ON = User Code can activate a PGM only
With option [7] off, entering the access code will arm or disarm according to the programmed User Code Options as well as activate or deactivate a PGM. The appropriate PGM Activation/Deactivation Event must also be programmed (see page 41). With option [7] on, the control panel will ignore all other User Code Options. Therefore, entering the access code will only activate or deactivate the PGM.
[7]
OFF = User Code follows User Code Options and can activate a PGM (default)
4.5 LOCK MASTER CODE
Section [127]: System Options
Option [4] OFF = Lock System Master Code Disabled (default) Option [4] ON = Lock System Master Code Enabled
With this feature enabled, the control panel will lock the System Master Code (001). This means that the System Master Code cannot be deleted, but it can be changed.
4.6 DURESS CODE
Section [127] = System Options
Option [6] OFF = Duress Code Disabled (default) Option [6] ON = User Code 048 becomes a Duress code
With this feature enabled, User Code 048 becomes a Duress Code. When forced to arm or disarm their system, users can enter a Duress Code (User Code 048) to arm or disarm the system which can immediately transmit a silent alert to the Central Station, transmitting the duress report code programmed in section [196].
18 REFERENCE & INSTALLATION MANUAL
PART 5: ZONE PROGRAMMING
The Spectra control panel’s zone assignment depends on where the detection devices are connected (see Table 4).
Tab le 4:
Device connected to which input?
Control Panel
Input 1 = Zone 1 Zone 1 & 6 Zone 1 Zone 1 & 6 Zone 1 Zone 1 & 8 Zone 1 Zone 1 & 8 Input 2 = Zone 2 Zone 2 & 7 Zone 2 Zone 2 & 7 Zone 2 Zone 2 & 9 Zone 2 Zone 2 & 9 Input 3 = Zone 3 Zone 3 & 8 Zone 3 Zone 3 & 8 Zone 3 Zone 3 & 10 Zone 3 Zone 3 & 10 Input 4 = Zone 4 Zone 4 & 9 Zone 4 Zone 4 & 9 Zone 4 Zone 4 & 11 Zone 4 Zone 4 & 11 Input 5 = Zone 5 Zone 5 & 10 Zone 5 Zone 5 & 10 Zone 5 Zone 5 & 12 Zone 5 Zone 5 & 12 Input 6 = N/A N/A N/A N/A Zone 6 Zone 6 & 13 Zone 6 Zone 6 & 13 Input 7 = N/A N/A N/A N/A Zone 7 Zone 7 & 14 Zone 7 Zone 7 & 14
Keypad
Zone 1 = Zone 6 Zone 11 Zone 6 Zone 11 Zone 8 Zone 15 Zone 8 Zone 15 Zone 2 = Zone 7 Zone 12 N/A N/A Zone 9 Zone 16 N/A N/A
Expansion
Input 1 = Zone 8 Zone 13 Zone 7 Zone 12 Zone 10 N/A Zone 9 Zone 16 Input 2 = Zone 9 Zone 14 Zone 8 Zone 13 Zone 11 N/A Zone 10 N/A Input 3 = Zone 10 Zone 15 Zone 9 Zone 14 Zone 12 N/A Zone 11 N/A Input 4 = Zone 11 Zone 16 Zone 10 Zone 15 Zone 13 N/A Zone 12 N/A Input 5 = Zone 12 N/A Zone 11 Zone 16 Zone 14 N/A Zone 13 N/A Input 6 = Zone 13 N/A Zone 12 N/A Zone 15 N/A Zone 14 N/A Input 7 = Zone 14 N/A Zone 13 N/A Zone 16 N/A Zone 15 N/A Input 8 = Zone 15 N/A Zone 14 N/A N/A N/A Zone 16 N/A
1728/EX 1728 1728/EX 1728
With Re-assign Keypad Zone 2 enabled (p. 19)
NO ATZ W ITH AT Z NO ATZ W ITH ATZ NO ATZ W I T H ATZ NO ATZ WITH ATZ
Zone Recognition Table
1738/EX 1738 1738/EX 1738
With Re-assign Keypad Zone 2 enabled (p. 19)
5.1 WHAT IS AN EXPANSION INPUT?
An expansion input allows you to connect modules to the system to increase the number of zones available up to 16 zones. Each hardwired input on a zone expansion bus module or wireless transmitter used by a wireless bus module can be assigned to an expansion input. The expansion inputs can be used in any combination. For example, 5 wireless transmitters and 3 hardwire inputs can be assigned to the expansion inputs. Spectra control panels cannot support more than eight expansion inputs. Refer to the appropriate module’s Instruction Sheet for details.
Do not assign inputs from different modules to the same expansion input.
5.2 REASSIGN KEYPAD ZONE 2
Section [126]: General Options
Option [7] OFF = Reassign Keypad Zone 2 Disabled (default) Option [7] ON = Reassign Keypad Zone 2 Enabled
Reassign Keypad Zone 2 changes the keypad zone into an expansion input. In Table 4 above, the effects of enabling this feature are shown. For example, when option [7] is enabled in control panel 1738, Zone 16 moves to Expansion Input 1 (see Table 5). Then, you are able to use Expansion Input 1
When Reassign Keypad Zone 2 is enabled, the Keypad Tamper Supervision (see page 44) for keypad zone 2 is lost. Keypad Tamper Supervision will
ONLY function on Keypad Zone 1.
Table 5:
1738
WITH ATZ
OFF ON
Zone 15 Zone 15 Zone 16 N/A
N/A Zone 16
Example
SPECTRA SERIES 19
5.3 REASSIGN ZONES TO EXPANSION INPUTS (1728EX & 1728 ONLY)
Section [126]: General Options
Option [8] OFF = Reassign Zones to Expansion Inputs Disabled (default) Option [8] ON = Reassign Zones to Expansion Inputs Enabled
Reassign Zones to Expansion Inputs changes the zone numbering to increase the number of expansion inputs that can be displayed on 10-Zone LED Keypads. In installations that require using mostly the expansion inputs, such as using wireless zones, the 10-Zone LED Keypads may be unable to display some of the zones. In the following table, the effects of enabling this feature and Reassign Keypad Zone 2 (see section 5.2) are shown:
Table 6:
Option [8]: OFF Option [8]: ON
1728/EX 1728 1728/EX 1728 1728/EX 1728
NO ATZ WITH ATZ NO AT Z WI TH ATZ NO ATZ WITH ATZ
Control Panel
Input 1 = Zone 1 Zone 1 & 6 Zone 1 Zone 1 & 3 Zone 1 Zone 1 & 3 Input 2 = Zone 2 Zone 2 & 7 Zone 2 Zone 2 & 4 Zone 2 Zone 2 & 4 Input 3 = Zone 3 Zone 3 & 8 N/A N/A N/A N/A Input 4 = Zone 4 Zone 4 & 9 N/A N/A N/A N/A Input 5 = Zone 5 Zone 5 & 10 N/A N/A N/A N/A
Keypad
Zone 1 = Zone 6 Zone 11 Zone 3 Zone 5 Zone 3 Zone 5 Zone 2 = Zone 7
Expansion
Input 1 = Zone 8 Zone 13 Zone 5 Zone 7 Zone 4 Zone 6 Input 2 = Zone 9 Input 3 = Zone 10 Input 4 = Input 5 = Input 6 = Input 7 = Input 8 =
Zone 11 Zone 16 Zone 8 Zone 10 Zone 7 Zone 9 Zone 12 N/A Zone 9 Zone 11 Zone 8 Zone 10 Zone 13 N/A Zone 10 Zone 12 Zone 9 Zone 11 Zone 14 N/A Zone 11 Zone 13 Zone 10 Zone 12 Zone 15 N/A Zone 12 Zone 14 Zone 11 Zone 13
Zone 12 Zone 4 Zone 6 N/A N/A
Zone 14 Zone 6 Zone 8 Zone 5 Zone 7 Zone 15 Zone 7 Zone 9 Zone 6 Zone 8
Zone Display with 10-Zone LED Keypad
Option [8]: ON and Option [7]: ON (Reassign Keypad Zone 2)
= not displayed on 10-Zone LED Keypads
5.4 ZONE PROGRAMMING
After connecting a hardwired detection device to one of the control panel's or zone expansion bus module’s input terminals or after setting up any wireless transmitters, define the associated zone's parameters. The Zone Parameters define the type of zone, the zone's partition assignment and how the control panel will react when an alarm condition occurs on that zone. These Zone Parameters are programmed into one section as detailed in Figure
5.1 on page 21.
In the 1728EX and 1728, only on-board zones 01 to 04 can be defined a Fire, Delayed Fire or a Keyswitch zone. On-board zone 05 cannot board zones 01 to 07 can be defined a Fire, Delayed Fire or a Keyswitch zone.
20 REFERENCE & INSTALLATION MANUAL
be programmed as such. In the 1738EX and 1738 the on-
Figure 5.1: Spectra Zone Programming
Press the
[
ENTER
]
key
Enter the
[
INSTALLER CODE
]
[001] [002] [003] [004] [005] [006] [007] [008]
= Zone 1 = Zone 2 = Zone 3
= Zone 4
= Zone 5 = Zone 6 = Zone 7 = Zone 8
[009] [010] [011] [012] [013] [014] [015]
[016]
= Zone 09 = Zone 10 = Zone 11 = Zone 12 = Zone 13 = Zone 14 = Zone 15 = Zone 16
Zone Definitions
1 -
Entry Delay 1
2 -
Entry Delay 2
3 -
Follow
4 -
Instant
5 -
24Hr. Burglary
6 -
24Hr. Buzzer
Additional definitions for on-board terminals:
7 -
Keyswitch
8 -
24Hr. Fire
9 -
24Hr. Delayed Fire
Select
one
Key in
3-digit
[
SECTION
Zone Definition
First Digit
Zone Partition
Assignment
Second Digit
Keypads beep twice
Zone Options
Feature Select
Press
[
ENTER
]
]
Select
one
Zone Partition Assignment
1-
Zone Assigned to Partition 1
2-
Zone Assigned to Partition 2
3-
Zone Assigned to Both Partitions
Zone Options
[1]
Auto Zone Shutdown Enabled
[2]
Bypass Enabled
[3]
Stay Zone
[4]
[5]
Zone Alarm Type off off Audible Alarm (steady) off on Audible Alarm (pulsed) on off Silent Alarm on on Generates only a report
[6]
Intellizone
[7]
Delay alarm transmission
[8]
Force Zone
Keyswitch Options
[1]
[2]
off = Maintained
on = Momentary
off = Regular Arm
on = Stay Arm
5.5 ZONE DEFINITIONS
As demonstrated in Figure 5.1, sections [001] to [016] represent zones 1 through 16 respectively, where the first digit in each of these sections represents the zone's definition. Also, refer to Zone Speed on page 25. To disable a zone, clear the contents of the section corresponding to the desired zone by pressing the [ pressing [
5.5.1 ENTRY DELAY 1
ENTER]. There are 9 available Zone Definitions, which are described as follows.
Sections [001] to [016]: Zones 1 to 16, First Digit = 1
When the system is armed and a zone defined with Entry Delay 1 opens, the control panel will generate an alarm after the programmed Entry Delay 1 Timer elapses. This is to provide users with enough time to enter the protected area and disarm the system. To program the Entry Delay 1 Timer, key in the desired 3­digit delay value (000 to 255 seconds, Default = 45 seconds) into section [069]. Entry Delay zones are commonly used at the entry/exit points of the protected area (i.e. front/back door, garage, etc.). Using different Entry Delays (see Entry Delay 2) is useful when, for example, one entry point requires a longer delay than the other entry point or in a partitioned system where each partition may require a different Entry Delay.
FORCE] key 3 times and
SPECTRA SERIES 21
5.5.2 ENTRY DELAY 2
Sections [001] to [016]: Zones 1 to 16, First Digit = 2
Entry Delay 2 zones are identical to the Entry Delay 1 zones (see section 5.5.1), except it uses a separate Entry Delay Timer. To program the Entry Delay 2 Timer, key in the desired 3-digit delay value (000 to 255 seconds, Default = 45 seconds) into section [070].
This timer is also used as the Stay Delay timer (see section 6.2).
5.5.3 FOLLOW ZONES
Sections [001] to [016]: Zones 1 to 16, First Digit = 3
When an armed Follow Zone opens, the control panel will immediately generate an alarm, unless an Entry Delay zone opens first:
• If an armed Follow Zone opens after an Entry Delay zone opens, the control panel waits until the Entry Delay Timer has elapsed before generating an alarm.
• If an armed Follow Zone opens after more than one Entry Delay zone opens, the control panel will wait until the Entry Delay Timer of the zone that opened first has elapsed.
This feature is commonly used when a motion detector is protecting the area occupied by the entry point keypad. This will prevent the motion detector from causing an alarm when a user enters through the entry point to disarm the system.
5.5.4 INSTANT ZONES
Sections [001] to [016]: Zones 1 to 16, First Digit = 4
When an armed Instant Zone opens, the control panel immediately generates an alarm. Instant Zones are commonly used for windows, patio doors, skylights and other perimeter type zones.
5.5.5 24HR. BURGLARY ZONES
Sections [001] to [016]: Zones 1 to 16, First Digit = 5
Whenever a 24Hr. Burglary Zone opens, whether the system is armed or disarmed, the control panel will immediately generate an alarm.
5.5.6 24HR. BUZZER
Sections [001] to [016]: Zones 1 to 16, First Digit = 6
Whenever a 24Hr. Buzzer Zone opens, whether the zone is armed or disarmed, the control panel sets off the keypads’ buzzers to indicate that the zone was breached. The control panel will report the alarm, but will not enable the bell/siren output. Enter any valid access code on the keypad to stop the buzzer. This zone definition is particularly useful when a user wishes to be notified when something such as a safe or locker within the home has been accessed (i.e. a child accessing a valuable collection).
5.6 EXCLUSIVE ZONE DEFINITIONS
The following three zone definitions can only be used for devices connected directly to the control panel’s on-board input terminals. When a zone is programmed as a Keyswitch Zone, the control panel will ignore all other Zone Options. When a zone is programmed as a Standard Fire Zone or Delayed Fire Zone, the control panel will ignore the Zone Options that may have been programmed, except Auto Zone Shutdown. Wireless devices and devices connected to the zone expansion bus modules cannot be programmed with these definitions.
5.6.1 KEYSWITCH ZONE
1728/EX: Sections [001] to [004]: Zones 1 to 4, First Digit = 7 1738/EX: Sections [001] to [007]: Zones 1 to 7, First Digit = 7
Connecting a keyswitch to a zone allows users to arm the system by pressing a button or by turning a switch on or off with a key. Please refer to Keyswitch Connections on page 13 and to Keyswitch Options on page 25.
If the ATZ feature is enabled when using a Keyswitch, the control panel will disable the “doubled zone” (see Zone Doubling on page 25).
22 REFERENCE & INSTALLATION MANUAL
5.6.2 STANDARD 24HR. FIRE ZONE
Fi
24H
1728/EX: Sections [001] to [004]: Zones 1 to 4, First Digit = 8 1738/EX: Sections [001] to [007]: Zones 1 to 7, First Digit = 8
Whenever a Standard 24Hr. Fire Zone opens, whether it is armed or disarmed, the control panel will generate the following:
• The control panel can send the corresponding Alarm Report Code from sections [187] to [190].
• If a tamper/wiring fault occurs on a Fire Zone, the control panel can send a Fire Loop Trouble report code programmed in section [206] to the Central Station. The keypads will display a Fire Loop Trouble in their Trouble Display (see page 50).
• Alarms are always audible regardless of other settings. Fire alarms generate an intermittent (pulsed) bell/siren output signal as shown in Figure 5.3.
For information on how to connect smoke detectors to the control panel, refer to Fire Circuits on page 13.
5.6.3 DELAYED FIRE ZONE
1728/EX: Sections [001] to [004]: Zones 1 to 4, First Digit = 9 1738/EX: Sections [001] to [007]: Zones 1 to 7, First Digit = 9
When a Delayed 24Hr. Fire Zone opens, whether it is armed or disarmed, the control panel will react as shown in Figure 5.2. Delayed 24Hr. Fire Zones are commonly used in residential homes where a smoke detector often generates false alarms (i.e. burning bread, etc.).
gure 5.2: Delayed
Delayed Fire Zone
is triggered
Activate bell/siren output & delay
report transmission for 30 seconds.
Problem
corrected within
30 seconds?
Any key on
keypad pressed
within 30
seconds?
De-activate bell/siren output and
delay report transmission an
additional 90 seconds.
No
Problem
corrected?
END
Alarm Disabled
Yes
No
No
Yes
Yes
Yes
r. Fire Zone
Latch alarm and
transmit report code
If the ATZ feature is enabled when using any type of Fire Zone, the control panel will disable the “doubled zone” (see Zone Doubling on page 25).
Figure 5.3: Bell Output During Fire Alarm
5.7 ZONE PARTITION ASSIGNMENT
Sections [001] to [016]: Zones 1 to 16
The control panel provides the option of partitioning the security system into two completely independent systems. As demonstrated in Figure 5-1 on page 21, sections [001] to [016] represent zones 1 through 16 respectively, where the second digit in each of these sections represents the zone's partition assignment. The zone is assigned to Partition 1 if second digit = 1, Partition 2 if second digit = 2, or both partitions is second digit = 3. For details on Partitioning, refer to page 43.
5.8 ZONE OPTIONS
As demonstrated in Figure 5.1, sections [001] to [016] represent zones 1 through 16 respectively. After entering the first two digits, select one or more of the following Zone Options by using the Multiple Feature Select Programming Method (see page 14):
SPECTRA SERIES 23
5.8.1 AUTO ZONE SHUTDOWN
Sections [001] to [016] = Zones 1 to 16
Option [1] OFF = Auto Zone Shutdown Disabled Option [1] ON = Auto Zone Shutdown Enabled for selected zone (default)
If, in a single armed period, the number of alarms generated by a zone with the Auto Zone Shutdown option enabled exceeds the number defined by the Auto Zone Shutdown Counter, the control panel will no longer generate an alarm for that zone. To program the Auto Zone Shutdown Counter, key in the desired limit (000=Disabled, 001 to 015, Default = 5) into section [089]. The Auto Zone Shutdown Counter resets every time the system is armed.
5.8.2 BYPASS ZONES
Sections [001] to [016] = Zones 1 to 16
Option [2] OFF = Bypass Zone Disabled Option [2] ON = Selected Zone is Bypass Enabled (default)
When a user, utilizes the Bypass Programming feature (see page 53), only zones with the Bypass option enabled can be programmed as bypassed.
Do not program a Fire Zone with the Bypass option, as the control panel will never bypass Fire Zones.
5.8.3 STAY ZONES
Sections [001] to [016]: Zones 1 to 16
Option [3] OFF = Stay Zone Disabled (default) Option [3] ON = Selected Zone is Stay Enabled
Zones with the Stay option enabled will be bypassed when the system is Stay Armed (see page 52).
Do not program a Fire Zone with the Stay option, as the control panel will never bypass Fire Zones when Stay Arming.
5.8.4 ALARM TYPES
Sections [001] to [016]: Zones 1 to 16
[4] OFF / [5] OFF: Audible Steady (default) When the conditions for an alarm have been met, the control panel can transmit the appropriate Zone Alarm report code (see page 34) and provides a steady output for any bells or sirens connected to the control panel’s bell output.
[4] OFF / [5] ON: Audible Pulsed Alarm When the conditions for an alarm have been met, the control panel can transmit the appropriate Zone Alarm report code (see page 34) and provides a pulsed output (see Figure 5-2 on page 22) for any bells or sirens connected to the control panel’s bell output.
[4] ON / [5] OFF: Silent Alarm When the conditions for an alarm are met, the control panel can transmit the appropriate Zone Alarm report code (see page 34) and will not activate the control panel’s bell output. The appropriate
STATUS LED on the keypads will flash to indicate an alarm and the user will still have to disarm the system.
[4] ON / [5] ON: Report Only When the conditions for an alarm have been met, the control panel can transmit the appropriate Zone Alarm report code (see page 34). The system will not have to be disarmed.
5.8.5 INTELLIZONE
Sections [001] to [016]: Zones 1 to 16
Option [6] OFF = Intellizone Disabled (default) Option [6] ON = Intellizone Enabled for Selected Zone This feature reduces the possibility of false alarms. When a zone with the Intellizone option opens, the panel does not immediately generate an alarm. First it triggers the Intellizone Delay Timer. To pr og ra m th e Intellizone Delay Timer, key in the desired 3-digit value (010 to 255 seconds, Default = 48 seconds) into section [084]. If any of the following conditions occur during this period, the panel will generate an alarm:
• During the Intellizone Delay, a second zone has caused an alarm.
• During the Intellizone Delay, the zone in alarm has restored (closed) and re-occurred (opened).
• The zone in alarm remains open for the entire Intellizone Delay.
ARM or
24 REFERENCE & INSTALLATION MANUAL
5.8.6 DELAY BEFORE ALARM REPORT CODE TRANSMISSION
Sections [001] to [016]: Zones 1 to 16
Option [7] OFF = Delay Alarm Transmission Disabled (default) Option [7] ON = Delay Alarm Transmission Enabled for Selected Zone
When an alarm condition occurs on a zone with this option enabled, the control panel enables the bell/ siren output, but does not report the alarm to the central station until the end of the Alarm Before Transmission Delay. To program the Alarm Transmission Delay, key in the desired 3-digit delay value (000 = Disabled, 001 to 255 seconds) into section [080]. During this period, disarming the system disables the bell/siren output and cancels the report code transmission. This feature is commonly used with Entry Delay zones to reduce false alarms created by new users who may not disarm the system in time.
5.8.7 FORCE ZONES
Sections [001] to [016]: Zones 1 to 16
Option [8] OFF = Force Zone Disabled (default) Option [8] ON = Selected Zone is Force Enabled
Any open Force Zones at the time of arming will be considered deactivated by the control panel (see page 53). If during this period a deactivated zone is closed, the control panel will revert that zone to active status. Consequently, the control panel will generate an alarm if the zone is breached.
Do not program a Fire Zone with the Force option, as the control panel will never bypass Fire Zones when Force Arming.
5.8.8 KEYSWITCH OPTIONS
1728/EX: Sections [001] to [004]: Option [1] and [2] 1738/EX: Sections [001] to [007]: Option [1] and [2]
When an on-board zone is programmed as a Keyswitch Zone (see section 5.6.1 on page 22), the control panel will ignore any other Zone Option. The keyswitch can be programmed as a Maintained or Momentary Keyswitch and to Regular or Stay Arm (see section 12.4 on page 52). A Maintained Keyswitch will arm the system when it is set to the Momentary Keyswitch, set the keyswitch to the this sequence will disarm the system. Program the keyswitch with the following:
ON position and will disarm when set to the OFF position. To arm with a
ON position then turn it back to the OFF position. Repeating
Option [1] OFF = Maintained (default) Option [2] OFF = Regular Arming (default) Option [1] ON = Momentary Option [2] ON = Stay Arming
5.9 ZONE SPEED
Sections [050] to [065]: Zones 1 to 16
001 to 255 X 10ms, Default = 600ms The Zone Speed defines how quickly the control panel will respond to an open zone. The control panel will not display an open zone on the keypad or generate an alarm until the programmed Zone Speed has elapsed. All other zone definitions and options do not come into effect until the Zone Speed has elapsed. This feature prevents any momentary glitches from causing an alarm or unnecessary reporting.
If the ATZ feature is enabled (see section 5.11 below), do not set the Zone Speed to less than 50msec. as this may cause false alarms.
5.10 EOL ZONES
Section [132]: Zone Options
Option [4] OFF = Zones do not use EOL resistors (default) Option [4] ON = Zones require EOL resistors
If all detection devices connected to the control panel have input terminals that require 1K end of line resistors, enable option [4] in section [132]. For details on using EOL resistors, refer to Single Zone Inputs and Double Zone Inputs (with ATZ Option only) on page 11.
5.11 ATZ - ZONE DOUBLING (1728 AND 1738 ONLY)
Section [132]: Zone Options
Option [5] OFF = Zone Doubling Disabled (default) Option [5] ON = Zone Doubling Enabled
SPECTRA SERIES 25
Enabling the ATZ feature allows you to install two detection devices per zone input terminal. Each detection device will have its own zone, displaying zone status on the keypad and sending separate alarm codes for each zone. The extra zones are recognized as described in Table 4 on page 19 or in Figure 5-4 below. For more information on how to connect to detection devices, please refer to Double Zone Inputs on page 11.
When a zone is defined as a Keyswitch or a Fire Zone and the ATZ feature is enabled, the control panel will disable the “doubled zone” .
Figure 5.4: Zone Recognition with ATZ enabled
26 REFERENCE & INSTALLATION MANUAL
PART 6: ARMING AND DISARMING OPTIONS
6.1 SWITCH TO STAY ARMING
Section [133] = Partition 1, Section [134] = Partition 2
Option [4] OFF = Switch to Stay Arming Disabled (default) Option [4] ON = Switch to Stay Arming Enabled
If a user Regular arms a partition, but does not exit through (open and close) an Entry Delay zone during the Exit Delay, the control panel can be programmed to switch from Regular Arming to Stay Arming.
6.2 STAY ARMING WITH DELAY
Section [133] = Partition 1, Section [134] = Partition 2
Option [5] OFF = Stay Arming with Delay Disabled (default) Option [5] ON = Stay Arming with Delay Enabled
When a partition is Stay Armed when this feature is enabled, all the zones in the partition, except 24Hr. zones, are associated with the Stay Delay. Therefore, the control panel will not generate an alarm if a zone is breached until the Stay Delay has elapsed. This feature prevents false alarms by allowing users enough time to disarm their system if a zone is accidentally triggered. For example, if a user opens an armed window or crosses an armed detector on the way to the kitchen in the middle of the night, the user will have enough time to disarm the system before the alarm is generated. Each partition’s Stay Delay follows the value programmed in Entry Delay Timer 2 in section [070].
6.3 REGULAR ARMING SWITCHES TO FORCE ARMING*
Section [131]: Arming/Disarming Options
Option [2] OFF = Regular Arming Switches to Force Arming Disabled (default) Option [2] ON = Regular Arming Switches to Force Arming Enabled
With this feature enabled, the control panel will always Force arm instead of Regular arm when a valid User Access Code with the Force Arming Option is entered. In installations where the user must always Force arm when leaving the protected area, this feature allows users to Force arm without pressing the [ User Access Code.
6.4 RESTRICT ARMING ON BATTERY FAIL
Section [130]: Arming/Disarming Options
Option [5] OFF = Permit arming on battery failure (default) Option [5] ON = Restrict arming on battery failure
If this option is enabled, the control panel will not arm the system if the control panel detects that the backup battery is disconnected, that its fuse is blown, or that the battery voltage drops to less than 10.5V. The control panel will not arm the system until all battery trouble conditions are rectified.
6.5 RESTRICT ARMING ON TAMPER FAILURE
Section [130]: Arming/Disarming Options
Option [6] OFF = Permit arming on tamper failure (default) Option [6] ON = Restrict arming on tamper failure
If this option is enabled, the control panel will not arm the system if the control panel detects a tamper trouble on one or more zones. The control panel will not arm the system until all tamper trouble conditions are rectified.
This feature will not function if the Tamper Recognition Options (see page 30) are disabled or whenever the tampered zone is bypassed and the Tamper Bypass Options (see page 30) have been enabled.
FORCE] key before entering their
* Not to be used with UL installations
SPECTRA SERIES 27
6.6 TIMED AUTO-ARMING
Section [133] = Partition 1, [134] = Partition 2
Option [1] OFF = Timed Auto-Arming Disabled (default) Option [1] ON = Timed Auto-Arming Enabled
Each partition can be programmed to arm every day at the time specified by the Auto-Arm Timer. The Auto-Arming Options (see section 6.8) determine the partition's arming method. Any open zones detected when a partition is Auto-Armed will be bypassed regardless of their definition (except 24hr. zones). The control panel will enter a 60­second Exit Delay period before arming the system. At this point, Auto-Arming can be cancelled by entering a valid access code. Once the partition has successfully armed, the control panel can transmit the Timed Auto-Arming report code programmed in section [172].
Example: To automatically arm partition 2 everyday at 6:15PM, enable Timed Auto-Arming for partition 2 by turning on option [1] in section [134]. Then key in 18:15 into section [112].
6.6.1 AUTO-ARM TIMER
Section [111] = Partition 1, [112] = Partition 2
Select the section corresponding to the desired partition and program the time (use the 24-hour clock i.e. 6:30PM = 18:30) that you wish the control panel to attempt to arm the selected partition and/or send the Late to Close report code.
6.7 NO MOVEMENT AUTO-ARMING
Section [133] = Partition 1, [134] = Partition 2
Option [2] OFF = No Movement Auto-Arming Disabled (default) Option [2] ON = No Movement Auto-Arming Enabled
If no movement occurs in a partition's protected area for the period specified by the No Movement Timer (see below), the control panel can automatically arm that partition. The Auto-Arming Option described in section 6.8 of this manual determines the partition's arming method. Any open zones detected when a partition is Auto-Armed will be bypassed regardless of their definition (except 24hr. zones). Upon arming, the control panel will transmit the No Movement report code if programmed in section [172]. Regardless of whether the system was successfully armed or not, the control panel will always transmit the No Movement report code if programmed in section [172]. If No Movement Auto-Arming is disabled, the control panel will still send the No Movement report code at the time specified by the No Movement Timer.
Example: To arm partition 1 whenever there is no movement for a period of 4 hours, enable No Movement Auto­arming for partition 1 by turning on the [2] Option in section [133]. Then in section [075] enter 016 (16x15min. = 240min. = 4 hours).
6.7.1 NO MOVEMENT TIMER
Section [075] = Partition 1, [076] = Partition 2
001 to 255 x15min., Default = disabled Select the section corresponding to the desired partition and program the interval of time without movement you wish the control panel to wait before arming and/or sending the No Movement report code. If No Movement Auto-Arming is disabled, the control panel can still send the No Movement report code when no movement has been detected for the period specified by the No Movement Timer.
6.8 AUTO-ARMING OPTIONS*
Section [133] = Partition 1, [134] = Partition 2
Option [3] OFF = Regular Arming (default) Option [3] ON = Stay Arming
When using Timed Auto-Arming or No Movement Auto-Arming (see section 6.6 and section 6.7), the control panel can Regular or Stay Arm (see page 52) the selected partition.
* Not to be used with UL installations
28 REFERENCE & INSTALLATION MANUAL
6.9 ONE-TOUCH ARMING*
Section [130]: Options [1] to [4]
Option [1] ON = Press & hold the [ Option [2] ON = Press & hold the [ Option [3] ON = Press & hold the [ Option [4] ON = Press & hold the [
The One-touch Arming features allow users to arm the system without having to enter any access codes. To arm the system, press and hold the appropriate key (see above) for approximately 2 seconds. If the system is partitioned (see page 43), you must also press the key corresponding to the partition you wish to arm. For more information on the different arming methods, please refer to page 52.
6.10 EXIT DELAY**
Section [071] = Partition 1, [072] = Partition 2
001 to 255 seconds, Default = 30 seconds After entering the required arming sequence (i.e. User Access code, etc.), the Exit Delay parameter determines the amount of time a user has to leave the protected area before the control panel arms the partition. The Exit Delay applies to all zones in the selected partition. When enabled, the keypad will beep once every second during the Exit Delay and will beep rapidly during the final 10 seconds of the Exit Delay.
6.10.1 BEEP ON EXIT DELAY
Section [130]: Arming/Disarming Options
Option [8] OFF = Beep on Exit Delay Disabled Option [8] ON = Beep on Exit Delay Enabled (default)
ENTER] key for One-touch Regular Arming. STAY] key for One-touch Stay Arming. FORCE] key for One-touch Force Arming. BYP] key for One-touch Bypass Programming.
6.11 BELL SQUAWK ON ARM/DISARM WITH KEYPAD
Section [130]: Arming/Disarming Options
Option [7] OFF = Bell Squawk on Arm/Disarm Disabled (default) Option [7] ON = Bell Squawk on Arm/Disarm Enabled
When this feature is enabled, the bell or siren will squawk once upon arming and twice upon disarming.
6.12 BELL SQUAWK ON ARM/DISARM WITH REMOTE CONTROL
Section [131]: Arming/Disarming Options
Option [3] OFF = Bell Squawk on Arm/Disarm with Remote Control Disabled (default) Option [3] ON = Bell Squawk on Arm/Disarm with Remote Control Enabled
When this feature is enabled, the bell or siren will squawk once upon arming with a remote control and twice upon disarming with a remote control. Must be enabled for UL installations.
6.13 NO EXIT DELAY WHEN ARMING WITH REMOTE CONTROL
Section [131]: Arming/Disarming Options
Option [4] OFF = Provides Exit Delay When Arming with a Remote Control (default) Option [4] ON = No Exit Delay When Arming with a Remote Control
When the option is enabled, the panel cancels the Exit Delay (arms instantly) when a partition is armed with a remote control. When disabled, the Exit Delay timer will start when a partition is armed with a remote control.
6.14 NO EXIT DELAY BEEPS AND NO BELL SQUAWK WHEN STAY ARMING
Section [131]: Arming/Disarming Options
Option [5] OFF = No Exit Delay Beeps and No Bell Squawk When Stay Arming Disabled (default) Option [5] ON = No Exit Delay Beeps and No Bell Squawk When Stay Arming Enabled
With this feature enabled, the control panel will prevent the bell or siren from squawking and the keypads from beeping during the Exit Delay, whenever a partition is Stay Armed.
* Not to be used with UL installations ** Maximum 60 seconds for UL listed systems
SPECTRA SERIES 29
PART 7: ALARM OPTIONS
7.1 BELL CUT-OFF TIMER (5 minutes minimum for CUL installations)
Section [073] = Partition 1, [074] = Partition 2
000 = Disabled, 001 to 255 minutes, Default = 4 min. After an audible alarm, the bell or siren will stop upon disarming of the partition or when the Bell Cut-Off Timer has
elapsed, whichever comes first.
7.2 RECYCLE ALARM
After the Bell Cut-Off Timer and the Recycle Delay have elapsed, the control panel will re-verify the zone status. If there are any open zones, the control panel will generate another alarm. In one armed period, the control panel will repeat this sequence the number of times defined by the Recycle Counter.
7.2.1 RECYCLE ALARM DELAY
Section [090]
000 = disabled, 001 to 255 minutes, Default = disabled The Recycle Delay determines the amount of time after Bell Cut-Off that the control panel will wait before
re-verifying zone status.
7.2.2 RECYCLE COUNTER
Section [091]
000 = disabled, 001 to 255, Default = disabled The Recycle Counter determines the number of times the control panel will re-verify the zone status after
Bell Cut-Off in one armed period.
7.3 TAMPER RECOGNITION
Section [132]: Zone Options
[1] OFF / [2] OFF: Tamper Recognition Disabled (default) If the system is armed or disarmed
not generate an alarm. This option is not permitted on UL systems.
[1] OFF / [2] ON: Trouble Only If the system is armed
Types setting (see page 24). Zone Wiring Failure will appear in the keypads’ Trouble Display (see page 50) and the control panel will transmit the appropriate Zone Tamper report code (see page 34).
[1] ON / [2] OFF: Silent Alarm If the system is armed
Types setting (see page 24). In a disarmed system, it functions the same as the Trouble Only setting, but it will also generate a silent alarm. A silent alarm will not trigger any bells or sirens, but the system will have to be disarmed.
[1] ON / [2] ON: Audible Alarm In an armed system and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm
Types setting (see page 24). In a disarmed system, it functions the same as Trouble Only setting, except it will also generate an audible alarm.
7.3.1 TAMPER BYPASS OPTIONS
Section [132]: Zone Options
Option [3] OFF = Will generate a tamper if detected on a bypassed zone (default) Option [3] ON = Tampers on bypassed zones will be ignored
and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm
If the system is disarmed
and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm
, the control panel will display the zone as open in the keypad display, but will
and a tamper wiring failure occurs on a zone, a Tamper/
With option [3] on, the Tamper Recognition feature follows the zone bypass definition. This means the control panel will ignore any tampers detected on a bypassed zone. With option [3] off, Tamper
30 REFERENCE & INSTALLATION MANUAL
Recognition ignores the bypass definition. This means the control panel will generate an incident as per Tamper Recognition settings if a tamper or wire fault occurs on a bypassed zone.
7.4 KEYPAD PANIC OPTIONS
Section [128]: General Options
Option [1] OFF = Emergency Panic Disabled (default) Option [1] ON = Emergency Panic Enabled Pressing the [1] and [3] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by option [4].
Option [2] OFF = Auxiliary Panic Disabled (default) Option [2] ON = Auxiliary Panic Enabled Pressing the [4] and [6] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by option [5].
Option [3] OFF = Fire Panic Disabled (default) Option [3] ON = Fire Panic Enabled Pressing the [7] and [9] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by option [6].
Option [4] OFF = Emergency Panic is Silent (default) Option [4] ON = Emergency Panic is Audible
Option [5] OFF = Auxiliary Panic is Silent (default) Option [5] ON = Auxiliary Panic is Audible
Option [6] OFF = Fire Panic is Silent (default) Option [6] ON = Fire Panic is Pulsed
Silent alarm
The control panel emits a Confirmation Beep and transmits the appropriate Panic report code if programmed in section [195]. The control panel will not enable the keypad buzzers or the control panel’s alarm).
Audible alarm
Same as silent alarm, except the keypad buzzers and the (disarms) with a valid User Access Code or when the Bell Cut-Off Timer elapses (see page 30).
Fire (pulsed) alarm
Same as audible operation, except that the
:
:
:
Whether the system is partitioned or not, the control panel will report all panic alarms to partition 1.
7.5 PANIC LOCKOUT TIMER
Section [094]
When a panic alarm is activated, the control panel can ignore the disarm signal from a remote control (see the SPC­319 Wireless Bus Module Reference & Installation Manual) for a specified period. This prevents an aggressor from disarming the system by remote control during a panic situation. In section [094] enter a 3-digit value (000 to 255, 000 = disabled) representing the number of seconds that the remote controls will be locked out of the system.
BELL output (no audible
BELL output will activate until a user cancels the alarm
BELL output will be pulsed as shown in Figure 5.3 on page 23.
SPECTRA SERIES 31
PART 8: REPORTING AND DIALER SETTINGS
The following section explains all the features and options that must be programmed in order for your security system to properly report system events to a central station. When an event (e.g. zone in alarm) occurs in the system, the control panel verifies if a report code was programmed in the section corresponding to the event (except Ademco Contact ID “All Codes”). If a report code was programmed, the control panel will dial the central station telephone number defined by the Event Call Direction feature. When the central station answers, the control panel will transmit the System Account Code, followed by the programmed Report Code.
Figure 8.1: Event Reporting
32 REFERENCE & INSTALLATION MANUAL
8.1 REPORTING/DIALER (ENABLE/DISABLE)
Section [135]: Dialer Options
Option [3] OFF = Reporting/Dialer Disabled (default) Option [3] ON = Reporting/Dialer Enabled
8.2 REPORT CODES
A report code is a 1- or 2-digit hexadecimal value consisting of digits from 1 to F. Each section from [160] to [213] represents a set of up to four specific events and each of these events can be programmed with a separate 1- or 2­digit report code.
Only the Ademco Slow, Silent Knight, Sescoa and Pager Formats support 1-digit report codes. To program a 1-digit report code, press the [ vice versa.
When a specific event occurs, the control panel will attempt to transmit the programmed report code to the central station. The method of report code transmission is defined by the Reporting Formats (see page 36) and the Event Call Direction (see page 38). These two items define how and where the report codes are transmitted. If you are using the Ademco Contact ID “All Codes” format, sections [160] to [213] do not have to be programmed. For more information, refer to Reporting Formats (see page 36). The following sub-sections provide a brief description of the events that the control panel can report.
8.2.1 ARMING REPORT CODES
Sections [160] to [171]
A report code can be programmed for each of the 48 User Access Codes. When using an access code to arm a partition, the control panel can send the appropriate report code to the central station, identifying which access code was used to arm the partition.
FORCE] key followed by the desired hexadecimal digit or
8.2.2 SPECIAL ARMING REPORT CODES
Sections [172] and [173]
Whenever the system is armed using one of the special arming features listed below, the control panel can send the appropriate report code to the central station identifying how the system was armed.
Section [172]
TIMED AUTO-ARMING: A partition has armed itself at the programmed time (see page 28).
LATE TO CLOSE: Reports every day at the time specified by the Auto-Arm Timer (see page 28).
NO MOVEMENT: A partition has armed itself after the programmed period without movement (see No
Movement Arming on page 28).
PARTIAL ARMING: A partition was Stay, Instant or Force Armed or armed with Bypassed zones.
Section [173]
ONE-TOUCH ARMING: A partition was armed using a One-touch Arming feature (see page 29).
REMOTE ARMING: A partition was armed using the Winload software.
KEYSWITCH ARMING: A partition was armed using a keyswitch (see page 22)
• Future use
8.2.3 DISARMING REPORT CODES
Sections [174] to [185]
A report code can be programmed for each of the 48 User Access Codes. Whenever an access code is used to disarm an armed partition or a partition in alarm, the control panel can send the appropriate report code to the central station, identifying which access code was used to disarm the partition.
The Disarming and the Special Disarming report codes can be transmitted every time a partition is disarmed or only when a partition is disarmed after an alarm (see Disarming Reporting Options on page 40).
SPECTRA SERIES 33
8.2.4 SPECIAL DISARMING REPORT CODES
Section [186]
Whenever using one of the special disarming features, the control panel can send the report code to the central station, identifying how the system was disarmed.
CANCEL AUTO-ARM: A partition is disarmed during the Timed Auto-Arm's 60-second Exit Delay (see
page 28). Only reports if Disarming Reporting Options (see page 40) are set to always report disarming.
REMOTE D ISARM: S y s t e m i s d i s a r m e d u s i n g t h e W i n l o a d s o f t w a r e .
KEYSWITCH DISARMING: System disarmed using a keyswitch (see page 22).
• Future use
8.2.5 ZONE ALARM REPORT CODES
Sections [187] to [190]
A report code can be programmed for each of the 16 available zones. Whenever a zone generates an alarm, the control panel can send the appropriate report code to the central station, identifying which zone generated an alarm.
8.2.6 ZONE ALARM RESTORE REPORT CODES
Sections [191] to [194]
A report code can be programmed for each of the 16 available zones. The control panel can transmit these report codes to the central station identifying which zone was restored.
A zone is restored when it closes after generating an alarm or once the bell has cut-off after alarm generation. Please refer to Zone Restore Report Options on page 40.
8.2.7 SPECIAL ALARM REPORT CODES
Sections [195] and [196]
Whenever the system generates an alarm due to one of the conditions listed below, the control panel can send the appropriate report code to the central station identifying the type of alarm.
Section [195]
EMERGENCY PANIC: Panic keys [1] and [3] have been pressed (see page 31).
AUXILIARY PANIC: Panic keys [4] and [6] have been pressed (see page 31).
FIRE PANIC: Panic keys [7] & [9] have been pressed (see page 31).
RECENT CLOSING: Reports when an alarm is generated after arming the system within period defined
by the Recent Close Delay (see page 39).
Section [196]
AUTO ZONE SHUTDOWN: A zone communicates more than the programmed number of transmissions
• in a single armed period (see page 24).
DURESS: A Duress access code is keyed in (see page 18).
KEYPAD LOCKOUT: If a consecutive number of invalid codes are entered into a keypad, the control
panel can be set to deny access from all keypads for a specified period.
• Future use
8.2.8 ZONE TAMPER REPORT CODES
Section [197] to [200]
A report code can be programmed for each of the 16 available zones. Whenever a tamper or wire fault occurs on a zone, the control panel can send the appropriate report code to the central station identifying which zone was tampered.
8.2.9 ZONE TAMPER RESTORE REPORT CODES
Sections [201] to [204]
A report code can be programmed for each of the 16 available zones. Whenever a tampered zone is restored, the control panel can send the appropriate report code to the central station identifying which zone has been restored.
If Tamper Recognition (see page 30) is disabled, the control panel will not report the occurrence of any tampers, wire faults or tamper restores.
34 REFERENCE & INSTALLATION MANUAL
8.2.10 SYSTEM TROUBLE REPORT CODES
Section [205] to [207]
Whenever the system generates one of the instances listed below, the control panel can send the appropriate report code to the central station identifying the type of system trouble.
Section [205]
• Future use
AC FAILURE: The control panel has detected a loss of AC power. Transmission of this report code can
be delayed (see Power Failure Report Delay on page 39).
BATTERY FAILURE: backup battery is disconnected or battery voltage is ≤10.5V.
AUXILIARY SUPPLY: Auxiliary power supply has overloaded (current consumption is >1.1A).
Section [206]
BELL OUTPUT OVERLOAD: Bell/siren output has overloaded (see page 10).
BELL OUTPUT DISCONNECTED: Devices connected to the Bell Output have been disconnected.
TIMER LOSS: The control panel has detected a loss in time or clock failure (see page 44)
FIRE LOOP TROUBLE: The control panel has detected a tamper trouble on a fire zone.
Section [207]
WIRELESS LOW BATTERY: The battery voltage of a Liberator or Omnia wireless transmitter (motion
• detector or contact switch) has dropped below recommended limits.
MODULE FAULT: Will report if all keypads connected to the control panel have been disconnected or if a
module with its corresponding supervision option enabled in the control panel (see pages 45 and 46) is disconnected.
PRINTER FAULT: An error has occurred on the Printer Bus Module.
FAIL TO COMMUNICATE: The control panel has failed all attempts to communicate with the central
station. The report code will be transmitted upon the next successful attempt.
8.2.11 SYSTEM TROUBLE RESTORE CODES
Sections [208] to [210]
Whenever the system restores one of the troubles listed in section 8.2.10, the control panel can send the appropriate report code to the central station identifying the type of system trouble restore. If Telephone Line Monitoring is enabled (see page 40), the control panel can also transmit a TLM Restore report code.
8.2.12 SPECIAL REPORTING CODES
Sections [211] to [213]
Whenever the system generates one of the instances listed below, the control panel can send the appropriate report code to the central station identifying the type of system occurrence.
Section [211]
COLD START: The control panel was completely shutdown (no battery, no AC) and then was re-started.
TEST REPORT: A test report has been generated automatically (see page 39).
• Not available
PC EXIT: The control panel has ended communication with WinLoad.
Section [212]
INSTALLER IN: Installer has entered the programming mode.
INSTALLER OUT: Installer has exited the programming mode.
• Future use
• Future use
Section [213]
TX SUPERVISION LOSS: Wireless Transmitter Supervision (see SPC-319 Instruction Sheet) has been
enabled and a transmitter is no longer communicating with the system.
TX SUPERVISION RESTORE: Reports when the above trouble has been restored
• Future use
• Future use
SPECTRA SERIES 35
8.3 CENTRAL STATION TELEPHONE NUMBERS
Section [151] = Phone#1, [152] = Phone#2, [153] = Backup Phone#: Up to 32 digits
The Spectra Control Panels can dial up to 2 different central station telephone numbers. You can enter any digit from 0 to 9 and any special keys or functions (see Table 7) up to a maximum of 32 digits. For more information on how these telephone numbers are used, please refer to Event Call Direction on page 38 and Reporting Formats in section 8.5. After the Maximum Dialing Attempts (see page 39) to one central station telephone number have failed, the control panel will then dial the backup telephone number. If the Alternate Dial Option (see page 39) is enabled, the control panel will dial the programmed backup telephone number after every failed attempt. If no backup telephone number is programmed, the control panel will never report to the backup telephone number. Also refer to Delay Between Dialing Attempts on page 39.
Table 7:
Special Keys for Telephone Numbers
Press Action or Value
[
STAY] *
[
BYP] #
[
MEM] switch from pulse to tone dialing or vice versa
[
TBL] or [TRBL] 4-second pause
[
FORCE] deletes current digit
[
PG] or [FNC1] inserts blank space
8.4 PARTITION ACCOUNT NUMBERS
Section [143] = Partition 1, [144] = Partition 2
All report codes are preceded by a 4-digit or 3-digit Partition Account Number to ensure correct identification in a partitioned system. Partition account numbers can be any hexa-digit from 1 to F. To enter a 3-digit account number, simply press the [ must use 1-digit report codes.
FORCE] key followed by the 3-digit account number. Also, when using 3-digit account numbers, you
8.5 REPORTING FORMATS*
Section [140]: 1st digit = Format for Phone #1, 2nd digit = Format for Phone #2
The Spectra Control Panels can use a number of different reporting formats and each Central Station Telephone Number can be programmed with a different reporting format. The first digit entered into section [140] represents the reporting format used to communicate with Central Station Telephone Number 1, the second digit represents the reporting format used to communicate with Central Station Telephone Number 2. The Backup Telephone Number uses the same reporting format as the last Central Station Telephone Number that was dialed.
Value Entered Reporting Format
1 Ademco Slow (1400Hz, 1900Hz, 10BPS) 2 Silent Knight Fast (1400Hz, 1900Hz, 10BPS) 3 SESCOA (2300Hz, 1800Hz, 20BPS) 4 Ademco Express (DTMF 4+2)
5 (Default) Ademco Contact ID
6 Pager Format
If Hexadecimals (0 to FF) are used to program the report codes, verify that the pager also supports Hexadecimals. If the pager does not support Hexadecimals, use only the digits 0 to 9.
8.5.1 STANDARD PULSE FORMATS
The Spectra Control Panels can use the Ademco slow, Silent Knight and Sescoa standard pulse reporting formats (see Table 8).
Table 8:
Reporting Formats
* UL Note: The installer is required to verify the complete compatibility of the DAC Receiver and formats at least once per year.
36 REFERENCE & INSTALLATION MANUAL
8.5.2 ADEMCO EXPRESS
The Ademco Express is a high-speed reporting format, which will transmit the 2-digit (11 to FF) report codes programmed into sections [160] to [213]. Unlike other Ademco formats, the Ademco Express does not use the Contact ID Report Codes.
8.5.3 ADEMCO CONTACT ID
Ademco Contact ID is a fast communicator format that uses tone reporting instead of pulse reporting. This communicator format also uses a pre-defined list of industry standard messages and report codes that will suit most of your basic installation needs. Please refer to the Contact ID Report Codes List in the Programming Guide for a complete list of these report codes and messages.
8.5.4 CONTACT ID OPTIONS
Section [136]: Dialer Options
Option [3] OFF = Programmable Codes Option [3] ON = All Codes (default)
When using the Programmable Codes format, use the Ademco Contact ID Report Codes List in the Spectra System Programming Guide (version 2.0 or higher) to program the desired report codes into sections [160] to [213]. Enter FF to use the default Contact ID Report Codes. Press the [ enter a 0 value. When using the All Codes format, the control panel will automatically generate Contact ID Report Codes for every event in sections [160] to [213]. Refer to the “All Codes” Ademco Contact ID Report Code List in the Spectra System Programming Guide.
When using the Ademco Contact ID Programmable format, both telephone numbers must use this reporting format.
FORCE] key to
8.5.5 PAGER REPORTING FORMAT
Section [136]: Dialer Options
[6] OFF / [7] OFF: 1 call to the pager/cellular telephone [6] OFF / [7] ON: 2 calls to the pager/cellular telephone [6] ON / [7] OFF: 3 calls to the pager/cellular telephone [6] ON / [7] ON: 4 calls to the pager/cellular telephone
Using this format allows the control panel to transmit report codes to a pager or a cellular telephone. Since the control panel cannot confirm whether the transmission was successful or not, it can be programmed to call the pager or cellular telephone up to four times and transmit the report codes each time. To ensure that the report is received, the control panel transmits the account number, the report code and the # sign four times during each call. Also, refer to the Pager Delay in section 8.6.
8.6 PAGER DELAY
Section [083]
001 to 255 seconds, default = 5 seconds
When using the Pager Reporting Format (see section 8.5.5), the control panel will wait for the Pager Delay period before transmitting the report codes. This is to allow time for the pager system to provide a dial tone or to bypass the “welcome” message before sending data.
SPECTRA SERIES 37
8.7 EVENT CALL DIRECTION
This feature determines where each group of events will be reported. The control panel events are divided into five groups (see above) where each event group can be programmed to dial one or both Central Station Telephone Numbers. When a reportable event occurs in the system, the control panel will verify that one of the two telephone numbers has been enabled. The control panel will begin by dialing the selected telephone number(s). If both numbers were selected it will begin with Central Station Telephone Number 1. After the Maximum Dialing Attempts (see page 39) to one central station telephone number have failed, the control panel will then dial the backup telephone number. If the Alternate Dial Option (see page 39) is enabled, the control panel will dial the programmed backup telephone number after every failed attempt. If no backup telephone number is programmed, the control panel will never report to the backup telephone number. Also, refer to Delay Between Dialing Attempts on page 39.
Example: The system is armed and zone 1 has been breached causing an alarm. If option [3] is off and option [4] is on in section [137], the control panel will attempt to communicate with Central Station Telephone Number 2 in order to transmit the Zone 1 Alarm Report Code programmed in section [187].
8.8 DIALING METHOD
Section [135]: Dialer Options
Option [4] OFF = Pulse Dialing. (Also, refer to Pulse Ratio) Option [4] ON = Tone/DTMF Dialing (default)
8.9 PULSE RATIO
Section [135]: Dialer Options
Option [5] OFF = European Pulse Ratio of 1:2 Option [5] ON = U.S.A. Pulse Ratio of 1:1.5 (default)
When using Pulse dialing, you can select one of two Pulse Ratios. Although most European countries use the 1:2 pulse ratio, the 1:1.5 ratio may provide better results in some cases. The same applies for North American countries. If the 1:1.5 pulse ratio is not providing the desired results, the 1:2 ratio may be used.
8.10 BELL ON COMMUNICATION FAILURE
Section [135]: Dialer Options
Option [6] OFF = Bell On Communication Failure Disabled (default) Option [6] ON = Bell On Communication Failure Enabled
If the control panel fails to communicate with the central station when the system is armed, it will enable the output, setting off any bells or sirens connected to the output.
8.11 DIAL TONE DELAY
Section [136]: Dialer Options
Option [5] OFF = Dialer will continue to dial if no dial tone is present after 4 seconds (default).
38 REFERENCE & INSTALLATION MANUAL
BELL
Option [5] ON = Dialer will hang-up if no dial tone is present after 16 seconds
8.12 MAXIMUM DIALING ATTEMPTS
Section [081]
001 to 016 attempts, Default = 8 attempts
The value programmed in section [081] determines how many times the control panel will re-dial the same Central Station Telephone Number before proceeding to the next number.
8.13 DELAY BETWEEN DIALING ATTEMPTS
Section [082]
000 to 255 seconds, Default = 20 seconds
This delay determines the amount of time the control panel will wait between each dialing attempt.
8.14 ALTERNATE DIAL OPTION
Section [136]: Dialer Options
Option [4] OFF = Alternate Dial Disabled (default) Option [4] ON = Alternate Dial Enabled
With option [4] off, the control panel will dial the backup telephone number programmed in section [153] after all attempts to one Central Station Telephone Number have failed (see section 8.12). With option [4] on, the control panel will dial the backup telephone number after every failed attempt.
8.15 RECENT CLOSE DELAY
Section [085]
000 to 255 seconds, Default = no delay
If after having armed the system, an alarm is generated within the period defined by the Recent Close Delay, the control panel will attempt to transmit the Recent Close report code programmed in section [195].
8.16 AUTO TEST REPORT
Sections [087]
000=disabled, 001 to 255 days, Default = disabled
Section [110]: Time (HH:MM)
The control panel will transmit the Test Report report code programmed into section [211] after the number of days programmed into section [087] has elapsed at the time programmed into section [110]. Use the 24-hour clock to program the time (i.e. 6:30PM = 18:30). The first Test Report will be transmitted within 24 hours after the feature is enabled at the time programmed in [110].
Example: Section [087] = 005 and section [110] = 13:00. The first Test Report will be sent at 1 PM that day and then the report will be sent every 5 days at 1 PM.
8.17 POWER FAILURE REPORT DELAY
Section [086]
001 to 255 minutes, Default = 15 minutes
The control panel will transmit the AC Failure report code programmed in section [205] after the Power Failure Report Delay period has elapsed.
SPECTRA SERIES 39
8.18 DISARM REPORTING OPTIONS
Section [131]: Arming /Disarming Options
Option [1] OFF = Always Report Disarming Option [1] ON = Report Disarming Only After Alarm (default)
With option [1] off, the control panel will send the Disarming report codes (see page 33) to the central station every time the system is disarmed. With option [1] on, the control panel will send the Disarming report codes to the central station when the system is disarmed following an alarm.
8.19 ZONE RESTORE REPORT OPTIONS
Section [132]: Zone Options
Option [6] OFF = Report On Bell Cut-Off (default) Option [6] ON = Report On Zone Closure
With option [6] off, the control panel will send the Zone Alarm Restore report codes (see page 34) to the central station when the zone has returned to normal and the Bell Cut-Off Timer has elapsed (see page 30). With option [6] on, the control panel will send the Zone Alarm Restore report codes to the central station as soon as the zone returns to normal or when the system is disarmed.
8.20 TELEPHONE LINE MONITORING (TLM)
When enabled, the system verifies the existence of a telephone line once every second. A line test failure occurs when the TLM detects less than 3 volts for the period defined by the TLM Fail Timer. If the line test fails, the control panel’s be restored when the control panel detects the telephone line again. Please note that when the dialer detects an incoming call, the TLM test will stop for 1 minute.
STATUS LED flashes and generates one or more conditions as defined by the TLM settings below. These will
Section [135]: Dialer Options
[1] OFF / [2] OFF: TLM Disabled
[1] OFF / [2] ON: Trouble Only
Upon line test failure, a TLM Trouble will appear in the keypads’ Trouble Display (see page 50).
[1] ON / [2] OFF: Alarm If System Armed Upon line test failure, a TLM Trouble will appear in the keypads’ Trouble Display (see page 50) and if the system is armed, the control panel will generate an alarm.
[1] ON / [2] ON: Silent Alarm Becomes Audible Upon line test failure, a TLM Trouble will appear in the keypads’ Trouble Display (see page 50) and causes a silent zone or silent panic alarm to switch to audible.
8.20.1 TLM FAIL TIMER
Section [079]
016 to 255 x 2 seconds, Default = 32 seconds
If TLM does not detect the existence of a telephone line for the duration of this period, the control panel will generate the condition(s) defined by the TLM options (see above).
40 REFERENCE & INSTALLATION MANUAL
PART 9: PROGRAMMABLE OUTPUTS
A PGM is a programmable output that toggles to its opposite state (i.e. a normally open PGM will close) when a specific event has occurred in the system. For example, a PGM can be used to reset smoke detectors, activate bells or strobe lights, open/ close garage doors and much more. When a PGM closes, the control panel supplies a ground to the PGM activating any device or relay connected to it. When a PGM opens, the circuit opens from ground, therefore, cutting power to any devices connected to it.
PGM1
1728EX and 1728: 1738EX and 1738:
page 10.
PGM2
1738EX and 1738 only: PGM2 is a programmable output that can provide up to 1A. PGM2 is designed to be used as a
Strobe Output. For information refer to PGM Strobe Options on page 42. For connections, refer to Alarm Relay and PGMs for 1738EX and 1738 on page 10.
Global PGM
The Global PGM allows you to use the control panel’s PGM Event List to activate PGMs located on a module or LCD keypad. For example, if you enable a module’s “Follows Global PGM” option, the PGM on the module will activate whenever the event programmed in section [124] occurs. Every PGM on every keypad and/or expansion bus module can be programmed to follow the event(s) defined by the Global PGM.
9.1 PGM ACTIVATION EVENT
Sections [120], [122], and [124]
This feature allows you to program the control panel to activate a PGM when a specific event occurs in the system. The PGM will remain in its active state until the programmed PGM Deactivation Event occurs or when the PGM
Delay period elapses (see page 42). For the Event List see the PGM Table in the Spectra 1728EX, 1728, 1738EX and 1738 Programming Guide. PGM2 is available on the 1738EX and 1738 only. To program a PGM Activation
Event:
1) Enter section that represents the desired PGM. PGM1 = [120], PGM2 = [122], Global PGM = [124]
2) Enter the Event Group #.
3) Enter the Sub-Group #.
4) Enter the Partition #
A programmable output that provides A programmable output that provides
01 = Partition 1 02 = Partition 2 99 = Both Partitions
up to 150mA up to 1A.
Refer to
. Refer to PGM for 1728EX and 1728 on page 10.
Alarm Relay and PGMs for 1738EX and 1738 on
The “AC Loss” PGM Event will only occur after the Power Failure Report Delay elapses (see page 39).
9.2 PGM DEACTIVATION EVENT
Sections [121], [123], [125]
After PGM activation, the PGM will return to its normal state (deactivate) when the programmed PGM Deactivation Event occurs. Instead of deactivating the PGM when a specific event occurs, the PGM can deactivate after a programmed period elapses (see PGM Delay). For the Event List see the PGM Table in the Spectra 1728EX, 1728,
1738EX and 1738 Programming Guide. PGM2 is available on the 1738EX and 1738 only. If using the PGM Delay, these sections can be used as a second activation event.
1) Enter section that represents the desired PGM. PGM1 = [121], PGM2 = [123], Global PGM = [125]
2) Enter the Event Group #.
3) Enter the Sub-Group #.
4) Enter the Partition #
01 = Partition 1 02 = Partition 2 99 = Both Partitions
SPECTRA SERIES 41
9.3 PGM DELAY
Section [066] = PGM1, [067] = PGM2, [068] = Global PGM
001 to 255 seconds, 000 = Follows Deactivation Event, Default = 5 seconds
Instead of deactivating the PGM on the occurrence of a specific event, the PGM will deactivate after the period programmed here has elapsed. PGM2 is available on the 1738EX and 1738 only.
If a PGM Delay is programmed, the deactivation event can be used as a second activation event.
9.4 PGM NORMAL STATE
Section [126]: Options [4], [5] and [6]
A PGM toggles to its opposite state (i.e. a normally open PGM will close) when a specific event has occurred in the system. PGM2 is available on the 1738EX and 1738 only. You can program each PGM output to be normally open (N.O.) or normally closed (N.C.) by enabling or disabling options [4], [5] and [6] in section [126].
Option [4] OFF = PGM1 Normally Closed (Default) Option [4] ON = PGM1 Normally Open
Option [5] OFF = PGM2 Normally Closed (Default) Option [5] ON = PGM2 Normally Open
Option [6] OFF = Global PGM Normally Closed (Default) Option [6] ON = Global PGM Normally Open
9.5 PGM2 STROBE OPTIONS (1738EX and 1738 Only)
Section [129]: General Options
Option [1] OFF = PGM2 Output is Steady (Default) Option [1] ON = PGM2 Output is Pulsed (Strobe) With option [1] enabled, PGM2 will flash on and off whenever activated. Otherwise, it will provide a steady output.
Option [2] OFF = Disable PGM2 Pulse When System is Armed (Default) Option [2] ON = Enable PGM2 Pulse When System is Armed Whenever the system is armed, PGM2 will flash once every 30 seconds until the system is disarmed.
Option [3] OFF = Disable PGM2 Pulse on Arm/Disarm (Default) Option [3] ON = Enable PGM2 Pulse on Arm/Disarm Enabled With this option enabled, PGM2 will flash once to indicate the system has been armed and will flash twice to indicate that the system has been disarmed.
9.6 ALARM RELAY OPTIONS (1738EX and 1738 Only)
Section [127]: General Options
Option [7] OFF = Alarm Relay Follows Bell Output (Default) Option [7] ON = Alarm Relay Follows Global PGM
With this option off, the optional Alarm Relay will activate or deactivate whenever the Bell Output activates or deactivates. With the option on, the Alarm Relay will activate or deactivate whenever Global PGM activates or deactivates.
42 REFERENCE & INSTALLATION MANUAL
PART 10: SYSTEM SETTINGS
10.1 HARDWARE RESET
Performing a hardware reset will set all control panel settings to factory default except for the Panel ID and PC Password. Also, the event buffer will not be erased. To perform a power down reset:
1) Make sure the Installer Lock is disabled (see below)
2) Remove battery and AC power from the control panel.
3) Set the
4) Re-connect AC and battery power to the control panel.
5) Wait 10 seconds and remove the jumper.
10.2 INSTALLER LOCK
Section [282]
000 = Disabled, 147 = Lock Enabled, Default = Disabled
Program 147 into section [282] to lock all programming. Performing a hardware reset will not affect the current panel settings. To remove the Installer Lock, enter 000. Please note that four seconds after resetting the control panel the
STATUS LED on the control panel will flash fast for 5 seconds to indicate that the installer lock is enabled.
10.3 KEYPAD LOCKOUT FEATURE
Sections [092] and [093]
If a consecutive number of invalid codes are entered into a keypad, the control panel can be set to deny access from all keypads for a specified period and send the report code programmed in section [196]. Program the number of consecutive invalid codes from 001 to 255 (000 = disabled) into section [092]. Program the duration of the Keypad Lockout from 001 to 255 minutes into section [093]. If 000 is programmed in section [093], the keypads will not be locked-out, but the report code programmed in section [196] will be sent.
RESET jumper to on by placing a jumper on the RESET pins of the control panel.
10.4 BATTERY CHARGE CURRENT
Section [127]: General Options
Option [5] OFF = Battery Charge Current: 350mA (default) Option [5] ON = Battery Charge Current: 700mA (40VA transformer required)
10.5 PARTITIONING
Section [127]: General Options
Option [1] OFF = Partitioning Disabled (default) Option [1] ON = Partitioning Enabled
The Spectra system is equipped with a partitioning feature which can divide the alarm system into two distinct areas identified as Partition 1 and Partition 2. Partitioning can be used in installations where shared security systems are more practical, such as an office/warehouse building. When partitioned, each zone, each User Code (see User
Code Options on page 17) and some of the system's features can be assigned to Partition 1, Partition 2 or both (see Zone Partition Assignment on page 23). If the system is not partitioned, all User Codes and features will be
recognized as belonging to Partition 1.
• Users can only arm partitions to which they have been assigned.
• Only zones assigned to Partition 1 will arm/disarm when Partition 1 is armed or disarmed.
• Only zones assigned to Partition 2 will arm/disarm when Partition 2 is armed or disarmed.
• Zones assigned to both partitions will arm when both partitions are armed and will disarm when at least one disarms.
• The following features can be programmed separately for each partition: Entry/Exit Delay Timer, Auto-Arming Options, Bell Cut-Off Timer, Switch to Stay Arming, PGM Events and Account Numbers.
If the system is not partitioned, all zones, User Codes, and features will be recognized as belonging to partition 1. Zones that have been manually assigned to partition 2 will no longer function.
SPECTRA SERIES 43
10.6 SYSTEM REAL-TIME CLOCK
Section [280]
Program the current time into section [280] using the 24-hour clock (i.e. 8:30PM = 20:30).
10.7 CLOCK ADJUST
Section [088]
000 = Disabled, 001 to 255, Default = Disabled 001 to 127 = + 1 to +127 seconds 128 to 255 = -1 to -127 seconds
If you notice a gain or loss in control panel time, calculate the average gain or loss per day and program the opposite amount in order to automatically correct the time setting every 24 hours.
Example: If a control panel loses 4 minutes per month, this represents an average loss of 8 seconds per day. Therefore, programming 008 (plus 8 seconds) into section [088] would compensate for the 8-second loss.
10.8 KEYPAD TAMPER SUPERVISION
Section [128]: General Options
Option [7] OFF = Keypad 1 Tamper Supervision Disabled (default) Option [7] ON = Keypad 1 Tamper Supervision Enabled
Option [8] OFF = Keypad 2 Tamper Supervision Disabled (default) Option [8] ON = Keypad 2 Tamper Supervision Enabled
The control panel can be programmed to monitor the on-board tamper status of one or two keypads in the system. If Keypad 1 Tamper Supervision is enabled, the control panel will verify the on-board tamper status of a keypad whose Keypad Zone Jumper (J1) is set to on. If Keypad 2 Tamper Supervision is enabled, the control panel will verify the on-board tamper status of a keypad whose Keypad Zone Jumper (J1) is set to off.
Regardless of whether the keypad zones are being used or not, if more than one keypad has the same Keypad Zone Jumper setting, Keypad Tamper Supervision will be lost. For example, if two of the keypads in your system have the keypad zone jumper (J1) set to on, the control panel will not recognize a Keypad 1 Tamper Supervision Failure.
If a keypad tamper occurs, the control panel can transmit the appropriate Zone Tamper report code (see page 34) as originating from the zones specified by the Table 9. If the zone (as specified by Table 9) is enabled, the control panel will report the tamper as originating from the partition where the zone is assigned. If the zone is not enabled, the control panel will send the Zone Tamper report code as originating from partition 1. A Tamper/Zone Wiring Failure will also appear in the keypads’ Trouble Display (see page 50).
Table 9:
Keypad Tamper
Keypad 1 Tamper Supervision = Zone 6 Zone 11 Zone 8 Zone 15 Keypad 2 Tamper Supervision = Zone 7 Zone 12 Zone 9 Zone 16
When Reassign Keypad Zone 2 is enabled (see section 5.2), the Keypad Tamper Supervision for keypad zone 2 is lost. Therefore, Keypad Tamper Supervision will
Zone Tamper Report Code for Keypad Tamper Supervision Failure
1728EX 1728 NO ATZ WITH ATZ
ONLY function on Keypad Zone 1.
1738EX 1738 NO ATZ WITH ATZ
10.9 KEYPAD AUDIBLE TROUBLE WARNING
Section [127]: General Options
Option [3] OFF = Keypad Beep on Trouble Disabled Option [3] ON = Keypad Beep on Trouble Enabled (default)
When enabled, the keypads emit an intermittent beep tone whenever a trouble condition occurs in the system. The intermittent beep tone remains activated until the user enters the Trouble Display by pressing the [ key. The intermittent beeps will re-initialize whenever a new trouble occurs or the trouble restores and re-occurs.
44 REFERENCE & INSTALLATION MANUAL
TBL] or [TRBL]
10.10 CONFIDENTIAL MODE
Section [126] Options [1], [2] and [3]
Option [1] OFF = Confidential Mode Disabled (default) Option [1] ON = Confidential Mode Enabled
Option [2] OFF = Keypads activate when an access code is entered Option [2] ON = Keypads activate when a key is pressed (default)
Option [3] OFF = Confidential Mode Timer is 2 minutes Option [3] ON = Confidential Mode Timer is 5 seconds (default)
If Confidential Mode is enabled and no actions are performed on the keypads for the time defined by the Confidential Mode Timer, all the keypads’ LEDs will be off and LCD screens will show “Paradox Family” until either a key is pressed or an access code is entered. When the system exits Confidential Mode, the keypads will display the system’s status. Confidential Mode is activated by enabling option [1]. Option [2] regulates whether the keypads will be activated at the touch of a key or only when an access code is entered. Option [3] determines the amount of time without action before the system enters Confidential Mode (5 seconds or 2 minutes).
10.11 INSTALLER QUICK FUNCTIONS KEYS
After entering the Installer Code, you can press a key to perform specific actions as described below.
10.11.1 INSTALLER TEST MODE
[ENTER] + [INSTALLER CODE] + [TBL] OR [TRBL] The Installer Test Mode allows you to perform walk tests where the bell or siren will squawk and the keypad will emit a Confirmation Beep to indicate opened zones. To enter this mode, simply enter the Installer Code then press the [ mode, press the [
TBL] key again. The keypad will emit a Rejection Beep.
TBL] or [TRBL] key. The keypad will emit a confirmation beep. To disable this
10.11.2 TEST REPORT
[ENTER] + [INSTALLER CODE] + [MEM] Sends the Test Report report code programmed in section [211] to the central station (see Reporting and Dialer settings on page 32).
10.11.3 CALL WINLOAD SOFTWARE
[ENTER] + [INSTALLER CODE] + [BYP]
Refer to page 49.
10.11.4 CANCEL COMMUNICATION
ENTER] + [INSTALLER CODE] + [STAY]
[
Cancels all communication until the next reportable event.
10.11.5 ANSWER WINLOAD SOFTWARE
[ENTER] + [INSTALLER CODE] + [FORCE]
Refer to page 49.
10.12 4-OUTPUT BUS MODULE SUPERVISION
Section [129]: General Options
Option [7] OFF = 4-Output Bus Option [7] ON = 4-Output Bus
By enabling this option, the control panel will supervise the 4-Output Bus Spectra bus. This means that whenever the 4-Output Bus control panel, the control panel will attempt to transmit the Module Fault report code programmed in section [210] and the Module Loss Failure will appear in the keypads’ Trouble Display (see page 50).
Modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and Digiplex. Modules with the APR3- prefix are compatible with Spectra( versions 2.0 and higher), Digiplex and DigiplexNE.
Module Supervision Disabled (default) Module Supervision Enabled
Module (APR3-PGM4) connected to the
Module is disconnected or is not communicating with the
SPECTRA SERIES 45
10.13 PRINTER BUS MODULE SUPERVISION
Section [129]: General Options
Option [8] OFF = Printer Bus Module Supervision Disabled (default) Option [8] ON = Printer Bus Module Supervision Enabled
By enabling this option, the control panel will supervise the Printer Bus Module (APR3-PRT1) connected to the Spectra bus. This means that whenever the Printer Bus Module is disconnected or is not communicating with the control panel, the control panel will attempt to transmit the Module Fault report code programmed in section [210] and the Module Loss Failure will appear in the keypads’ Trouble Display (see page 50).
Modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and Digiplex. Modules with the APR3- prefix are compatible with Spectra( versions 2.0 and higher), Digiplex and DigiplexNE.
10.14 ZONE EXPANSION BUS MODULE SUPERVISION
Section [129]: General Options
Option [4] OFF = Zone Expansion Bus Module Supervision Disabled (default) Option [4] ON = Zone Expansion Bus Module Supervision Enabled
By enabling this option, the control panel will supervise the 4- or 8-Zone Expansion Bus Module (SPC/APR3-ZX4 or SPC/APR3-ZX8) connected to the Spectra bus. This means that whenever the Zone Expansion Bus Module is disconnected or is not communicating with the control panel, the control panel will attempt to transmit the Module Fault report code programmed in section [210] and the Module Loss Failure will appear in the keypads’ Trouble Display (see page 50).
Modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and Digiplex. Modules with the APR3- prefix are compatible with Spectra( versions 2.0 and higher), Digiplex and DigiplexNE.
10.15 WIRELESS BUS MODULE SUPERVISION
Section [129]: General Options
Option [5] OFF = Wireless Bus Module Supervision Disabled (default) Option [5] ON = Wireless Bus Module Supervision Enabled
By enabling this option, the control panel will supervise the Wireless Bus Module (SPC-319) connected to the Spectra bus. This means that whenever the Wireless Bus Module is disconnected or is not communicating with the control panel, the control panel will attempt to transmit the Module Fault report code programmed in section [210] and the Module Loss Failure will appear in the keypads’ Trouble Display (see page 50).
10.16 WIRELESS TRANSMITTER LOW BATTERY SUPERVISION
Section [129]: General Options
Option [6] OFF = Wireless Transmitter Low Battery Supervision Disabled (default) Option [6] ON = Wireless Transmitter Low Battery Supervision Enabled
When option [6] in section [129] is enabled and the battery voltage of a wireless transmitter (motion detector or contact switch) has dropped below recommended limits, the control panel will attempt to transmit the Wireless Transmitter Low Battery report code programmed in section [210] and the Wireless Transmitter Low Battery Failure will appear in the keypads’ Trouble Display (see page 50).
10.17 WIRELESS TRANSMITTER SUPERVISION OPTIONS
Section [132]: Zone Options
Please note that the Supervision Option on the 900MHz Wireless Bus Module must be enabled (see section 10.15).
[7] OFF / [8] OFF: Supervision Failure Recognition Disabled (default) When a tamper occurs on a wireless transmitter zone in a disarmed system, the control panel will display the zone as open in the keypad display, but will not generate an alarm. When it occurs on in an armed system, the control panel will follow the zone's Alarm Types setting (see page 24). This option is not permitted on UL systems.
46 REFERENCE & INSTALLATION MANUAL
[7] OFF / [8] ON: Trouble Only When a tamper occurs on a wireless transmitter zone in a disarmed system, a Wireless Transmitter Supervision Loss will appear in the keypads’ Trouble Display (see page 50) and the control panel will attempt to transmit the TX Supervision Loss report code programmed in section [213]. When it occurs on in an armed system, the control panel will follow the zone's Alarm Types setting (see page 24).
[7] ON / [8] OFF: Silent Alarm When a tamper occurs on a wireless transmitter zone in a disarmed system, it functions the same as the Trouble Only setting, but it will also generate a silent alarm. A silent alarm will not trigger any bells or sirens, but the system will have to be disarmed. In an armed system, the control panel will follow the zone's Alarm Types setting (see page 24).
[7] ON / [8] ON: Audible Alarm When a tamper occurs on a wireless transmitter zone in a disarmed system, it functions the same as the Trouble Only setting, except it will also generate an audible alarm. In an armed system, the control panel will follow the zone's Alarm Types setting (see page 24).
10.17.1 RESTRICT ARMING ON SUPERVISION LOSS
Section [131]: Arming/Disarming Options
Option [6] OFF = Disabled (default) Option [6] ON = Restrict Arming on Wireless Transmitter Supervision Loss
The control panel will not allow users to arm the system if it receives a Supervision Loss signal. Please note that the Wireless Transmitter Supervision Options (see section 10.17) must be enabled. The control panel will not arm any partition until all Supervision Loss trouble conditions are rectified.
10.17.2 SUPERVISION BYPASS OPTIONS
Section [131]: Arming/Disarming Options
Option [7] OFF = Generate Supervision Loss if detected on a Bypassed Wireless Transmitter Zone
(default)
Option [7] ON = No Supervision Loss if Detected on a Bypassed Wireless Transmitter Zone
When this feature is enabled, the Wireless Transmitter Supervision Options will follow the zone's bypass definition. This means the control panel will not perform any action if a Supervision Loss occurs on a bypassed zone. When this feature is disabled, the Wireless Transmitter Supervision Options will ignore the bypass definition. This means the control panel will generate an incident as per Wireless Transmitter Supervision Options if a supervision loss occurs on a bypassed zone.
10.18 REPROGRAM ALL EXPANSION MODULES
Section [750]
After removing an expansion bus module from the communication bus, the control panel keeps the module’s programmed sections in memory. Therefore, if you add or replace a module or when you have downloaded the contents of the Paradox Memory Key (see section 3.4), you can reprogram the modules with the settings saved in the control panel. To do so, enter section [750] and press [ downloading.
ENTER]. The keypad will emit 2 beeps every second while
SPECTRA SERIES 47
PART 11: SETTINGS FOR WINLOAD SOFTWARE
11.1 PANEL ANSWER OPTIONS
The following two options define how the control panel answers an incoming call from a computer using the WinLoad Software for Windows®.
11.1.1 ANSWERING MACHINE OVERRIDE
Section [077]
000 = Disabled, 010 to 255 seconds, Default = disabled
When using the WinLoad software to communicate remotely with an installation site that uses an answering machine or service, the answering machine override must be programmed. Using the WinLoad software you will call the control panel, hang up, then call back. If the installation site is called back within the programmed delay period, the control panel will override the answering machine or service by picking­up the line after the first ring on the second call. You must wait at least 10 seconds before attempting the second call, otherwise, the control panel will think it is the same call. For details on how to use the WinLoad software, refer to the WinLoad Help Manual.
Example: A security installation is using an answering machine set to answer after three rings. If section [077] has been programmed with 040 (40 seconds) and the second call is made within 40 seconds, the control panel will pick up the line on the first ring. If it takes more than 40 seconds, the control panel will not answer on the first ring and the answering machine will answer after three rings.
11.1.2 NUMBER OF RINGS
Section [078]
000 = disabled, 001 to 015 rings, Default = 8 rings
This value represents the number of rings the control panel will wait before picking-up the line. If the line is not answered after the number of programmed rings, the control panel will answer the call. You must wait at least 10 seconds before attempting the second call or the control panel will think it is the same call.
11.2 PANEL IDENTIFIER
Section [141]
0000 to FFFF
This 4-digit code identifies the control panel to the WinLoad software before initiating communication. The control panel will verify that the Panel Identifier in the WinLoad software is the same. If the codes do not match, the control panel will not establish communication. Therefore, be sure to program the same panel identifier into both the Spectra control panel and the WinLoad software.
11.3 PC PASSWORD
Section [142]
0000 to FFFF
This 4-digit password identifies the PC to the panel before establishing communication. Program the same PC Password into both the Spectra control panel and the WinLoad software. If the passwords do not match, the WinLoad software will not establish communication.
11.4 PC TELEPHONE NUMBER
Section [150]
Up to 32 digits
The control panel will dial this number when trying to initiate communication with a computer using the WinLoad software. You can enter any digit from 0 to 9 and any special keys or functions (see Table 7 on page 36) up to a maximum of 32 digits.
48 REFERENCE & INSTALLATION MANUAL
11.5 CALL WINLOAD SOFTWARE
[ENTER] + [INSTALLER CODE] + [BYP]
The control panel will dial the PC Telephone Number programmed in section [150] in order to communicate with the WinLoad software. The control panel and the WinLoad software will verify that the Panel Identifier and the PC Password match before establishing communication.
11.6 ANSWER WINLOAD SOFTWARE
[ENTER] + [INSTALLER CODE] + [FORCE]
In order to perform on-site upload/download connect your computer directly to the control panel using an ADP-1 line adapter. In the WinLoad software set Dialing Method to Blind Dial. Program the panel telephone number in WinLoad software and follow the instructions on the ADP-1 adapter. When the computer has dialed, press [ by the Installer Code, then press the [
FORCE] key to manually answer the WinLoad software from the control panel.
11.7 AUTO EVENT BUFFER TRANSMISSION
Section [136]: Dialer Options
Option [2] OFF = Auto Event Buffer Transmission Disabled (default) Option [2] ON = Auto Event Buffer Transmission Enabled
When the event buffer reaches 50% capacity, the control panel will make two attempts to establish communication with a PC using the WinLoad software by calling the PC Telephone Number programmed in section [150]. The WinLoad software must be in Wait to Dial mode. When the system establishes communication, it will upload the contents of the event buffer to the WinLoad software. If communication is interrupted before completing transmission or if after two attempts communication is not established, the system will wait until the Event Buffer attains another 50% capacity before attempting to re-communicate with the central station. When the Event Buffer is full, each subsequent new event will erase the oldest event in the buffer.
ENTER] followed
11.8 CALL BACK WINLOAD
Section [136]: Dialer Options
Option [1] OFF = Call Back WinLoad Disabled (default) Option [1] ON = Call Back WinLoad Enabled
For additional security, when a PC using the WinLoad software attempts to communicate with the control panel, the control panel can hang up and call the PC back in order to re-verify identification codes and re-establish communication. When the control panel hangs up, the WinLoad software automatically goes into Wait for Call mode, ready to answer when the control panel calls back. Please note that the PC Telephone Number must be programmed in section [150] in order to use the Call Back feature.
SPECTRA SERIES 49
PART 12: USER OPERATION
12.1 TROUBLE DISPLAY
The Spectra system continuously monitors fourteen possible trouble conditions. When a trouble condition occurs, the [
TBL] key or [TRBL] indicator will illuminate on the LED keypads or “Trouble” will appear on the LCD keypad’s
screen. Press the [ lights corresponding to an existing trouble condition will illuminate on the LED keypads (see Table 10) or the appropriate trouble message will appear on the LCD keypad. Press the [
TBL] or [TRBL] key to switch to the Trouble Display. The [TBL] key or [TRBL] indicator will flash and
CLEAR] key to exit the Trouble Display.
Please note that the keypad can be programmed to emit a has occurred. Pressing the [
TBL] or [TRBL] key will stop the beeping.
Tab le 10:
BEEP every 5 seconds whenever a new trouble condition
Trouble List
LED # Description Details
[1] No/Low Battery Failure The control panel performs a dynamic battery test under load every 60
seconds. This trouble indicates that the back up battery is disconnected or that the battery should be replaced, as it will not provide adequate current in case of AC loss. This trouble will also appear when the control panel is running on battery power and the battery voltage has dropped to 10.5 volts or lower. This means the battery must be recharged or replaced.
[2] Wireless Transmitter
Low Battery
The battery voltage of a wireless transmitter has dropped below recommended limits. If connected to a SPC-319, press [2] to view the zones that are generating this trouble. If connected to an Omnia (OMN­RCV3), the trouble will be displayed as a global trouble. To determine the zones generating the trouble, examine the Low Battery LED indicators on all the transmitters. The batteries should be replaced.
[3] Power Failure Upon power failure, the AC LED on all keypads will turn off. The control
panel can transmit the report code programmed in section [205]. This report code can be delayed by programming a Power Failure Report Delay in section [086]. The AC LED turns back on as soon as power is restored.
[4] Bell Disconnected This trouble occurs when a bell or siren is not connected to the bell output
terminals. If you are not using the
BELL terminals, connect a 1K resistor
across the bell output.
[5] Maximum Bell Current The
BELL output uses a fuseless circuit and will automatically shut down if
the current exceeds 3A. After opening the short or reducing the load, the bell current is restored upon the following alarm generation. This trouble indicator will only appear when a condition has occurred that would activate the bell output (e.g. during an alarm).
[6] Maximum Auxiliary Current The auxiliary output uses a fuseless circuit to protect the power supply
against current overload and automatically shuts down if the current exceeds 1.1A. After opening the short or reducing the load, the panel will restore power to the auxiliary output.
[7] Communicator Report Fail The control panel has failed all attempts to communicate with the central
monitoring station.
[8] Timer Loss The control panel’s internal clock must be re-programmed. To re-program
the timer press the [8] key followed by the current time using the 24-hour clock (i.e. 8:30PM = 20:30).
[9] Tamper/Zone Wiring Fail If the Tamper Recognition options are enabled (see page 30), this trouble
indicates a wiring problem on one or more zones or that the cover has been removed on one or more wireless transmitters. To provide line short recognition the zone connections must have EOL resistors. If you press the [9] key, the keypad will display which zones are in trouble. Enter the Installer Code to clear Tamper troubles.
50 REFERENCE & INSTALLATION MANUAL
LED # Description Details
Telephone Line Monitoring If the Telephone Line Monitoring (TLM) feature is enabled (see section
[10]
[135]), this trouble indicates that the control panel has not detected the
presence of a telephone line for 30 seconds.
[
STAY] or
[11]
Fire Loop Trouble Indicates a wiring problem on a Fire Zone. Press [
that are generating this trouble.
Keypad Fault If the keypad is no longer communicating with the control panel, the [
or [
TRBL] will flash, the [FORCE] key will illuminate (the LCD keypad
FORCE]
[
or [16]
displays “Keypad Fault”) and the keypad will emit four consecutive beeps at 5-second intervals. Press any key on the keypad to terminate the “beeping” sequence. When communication has been restored, the system will revert to previous status.
[
BYP]
or [12]
[MEM]
or [13]
Module Loss
Wireless Transmitter Supervision Loss
A bus module is no longer communicating with the control panel. The module’s supervision option must be enabled [129].
One or more wireless transmitters are no longer communicating with the receiver. If you press the [ are in trouble.
12.2 PROGRAMMING ACCESS CODES
Access Codes are personal identification numbers that allow you to enter certain programming modes, arm or disarm your system as well as activate or deactivate PGMs. The Spectra security system supports the following:
Tab le 10:
Trouble List
STAY] to view the zones
TBL]
MEM] key, the keypad will display which zones
System Master Code arms or disarm partitions using any arming method and can create, modify or delete any User Access Code. Only the System Master Code can modify or delete User Access Codes assigned to both partitions.
Master Code 1 is permanently assigned to partition 1 and can be used to create, modify or delete User Access Codes that are assigned to partition 1.
Master Code 2 is permanently assigned to partition 2 (except when partitioning is disabled, Master Code 2 will be assigned to partition 1) and can be used to create, modify or delete User Access Codes that are assigned to the same partition.
45 User Access Codes (including 1 Duress code)
How Do I Program Access Codes?
1) Press [ENTER]
2) Key in the [
3) Key in 3-digit [
4) Key in new 4- or 6-digit [
[
ENTER] flashes. Return to step 3
SYSTEM MASTER CODE] or [MASTER CODE]
SECTION] (see Table below)
ACCESS CODE]
How Do I Delete Access Codes?
1) Repeat steps 1 to 3 (see above)
2) Press the [
FORCE] key once for each digit in the access code (4 or 6 times) until the keypad emits a
Confirmation Beep
Section User Codes
[001]
[002]
[003]
[004] to [047]
[048]
User Code 001 = System Master Code User Code 002 = Master Code 1 User Code 003 = Master Code 2 User Code 004 to User Code 047 User Code 048 or Duress Code
SPECTRA SERIES 51
12.3 DISARMING & DEACTIVATING AN ALARM
To disarm an already armed system or to deactivate an alarm, simply key in a valid access code. Program a designated entry/exit point, such as the front door or the garage door with an Entry Delay Timer. When these entry/ exit point are opened (breached), it will set off a timer. The system will not generate an alarm until this timer elapses, giving users enough time to enter the premises and disarm the system. Any user can disarm the system, except users have been assigned the Arm Only Option.
How Do I Disarm the System or Deactivate an Alarm?
1) Key in your [ACCESS CODE]*
The arm or alarm indication will turn off and the keypad will emit a Confirmation Beep.
*IF YOU HAVE ACCESS TO BOTH PARTITIONS
Press the key corresponding to the partition you wish to Disarm or to Disarm both partitions, press the [1] key then after the Confirmation Beep press the [2] key.
12.4 REGULAR ARMING
This method, commonly used for day-to-day arming, will arm all the zones in the selected partition. If you make a mistake, the keypad will emit a Rejection Beep. When you have correctly armed the system, the appropriate indication will turn on and the Exit Delay will be initiated. Please note that Regular Arming can also be activated through Auto-Arming, Keyswitch Arming or One-Touch Arming.
How Do I Regular Arm?
1) Green READY indicator must be illuminated. Unless the system is partitioned, in which case all zones in the desired partition must be closed.
2) Key in a valid [
ACCESS CODE]*
*IF YOU HAVE ACCESS TO BOTH PARTITIONS
Press the key corresponding to the partition you wish to arm. To arm both partitions, press the [1] key then after the Confirmation Beep press the [2] key.
12.5 STAY ARMING
This method allows users to remain in the protected area while partially arming the system. For example, when going to sleep at night, entry/exit points like doors and windows can be armed while other zones like motion detectors remain deactivated. Please note that Fire Zones cannot be bypassed.
:
ARM
:
How Do I Stay Arm?
1) All zones in the desired partition (except Stay Zones) must be closed.
2) Press the [
3) Key in a valid [
STAY] key
ACCESS CODE]*
*IF YOU HAVE ACCESS TO BOTH PARTITIONS
Press the key corresponding to the partition you wish to Stay Arm. To Stay Arm both partitions, press the [1] key then after the Confirmation Beep press the [2] key.
If you make a mistake, the keypad will emit a Rejection Beep. When you have correctly Stay Armed the system, the appropriate
ARM or STAY indication appears and the Exit Delay is initiated. Stay Arming can also be activated using
Auto-Arming, Keyswitch Arming or One-Touch Arming. The User Code must have the Stay Arming Option enabled.
12.6 INSTANT ARMING
After Stay Arming the system and during its Exit Delay, press and hold the [STAY] key for 3 seconds. You should hear a Confirmation Beep. This will switch all armed zones to Instant zones.
If you have access to both partitions: To Instant Arm one partition, press [
STAY] + [ACCESS CODE] + Select Partition + [CLEAR] + press & hold [STAY]
To Instant Arm both partitions, press [
52 REFERENCE & INSTALLATION MANUAL
:
STAY] + [ACCESS CODE] + [1] + [2] + press & hold [STAY]
12.7 FORCE ARMING**
Force Arming allows users to rapidly arm the system, without having to wait for all zones in the system to be closed. Force Arming is commonly used when a motion detector is protecting the area occupied by a keypad. Therefore, when arming the system, if the motion detector is set as a Force Zone, the control panel will ignore the zone and allow users to arm the system even if the zone is open. Any open Force Zones at the time of arming will be considered deactivated by the control panel. If during this period a deactivated zone is closed, the control panel will revert that zone to active status, hence, will generate an alarm if breached.
How Do I Force Arm?
1) All zones in the desired partition (except Force Zones) must be closed.
2) Press the [
3) Key in a valid [
FORCE] key
ACCESS CODE]*
*IF YOU HAVE ACCESS TO BOTH PARTITIONS
Press the key corresponding to the partition you wish to Force Arm. To arm both partitions, press the [1] key then after the Confirmation Beep press the [2] key.
If you make a mistake, the keypad will emit a Rejection Beep. When correctly Force Armed, the appropriate arm indication appears and the Exit Delay will initiate. Please note that Force Arming can also be activated using One­Touch Force Arming. Also, note that the User Access Code must have the Force Arming Option enabled.
12.8 MANUAL BYPASS PROGRAMMING
Manual Bypass Programming allows users to program the alarm system to ignore (deactivate) specified zones the next time the system is armed. The Access Code must have the Bypass Programming Option enabled. Please note that Fire Zones cannot be bypassed. Manual Bypass Programming can also be activated using One-Touch Bypass Programming.
How do I Program Bypass Entries?
1) Press the [BYP] key.
2) Key in a valid [
3) Select one or more [
4) Once you have entered the desired bypass entries, press the [
*IF YOU HAVE ACCESS TO BOTH PARTITIONS
Press the key corresponding to the desired partition.
ACCESS CODE]*
ZONES] you wish to bypass
:
ENTER] key to accept these entries.
:
12.8.1 BYPASS RECALL FEATURE
After disarming the system, the control panel will erase the bypass entries. By using the Bypass Recall Feature, you can reinstate the previous bypass entries saved in memory. This eliminates the need to
manually program the bypass entries every time you arm the system. The Access Code must have the Bypass Programming Option enabled.
How Do I Recall Bypass Entries?
1) Press the [BYP] key.
2) Key in your [
3) Press the [
4) Press the [
*IF YOU HAVE ACCESS TO BOTH PARTITIONS
Press the key corresponding to the desired partition.
** Not to be used with UL installations
ACCESS CODE]*
BYP] key. Previously bypassed zones will illuminate. ENTER] key.
:
SPECTRA SERIES 53
12.9 ONE-TOUCH ARMING
One-Touch Arming allows users to arm the system without using an access code. Simply press and hold a key. One­Touch Arming can be used to allow specific individuals like service personnel (i.e. cleaners, maintenance) to arm the system when leaving the protected area, without giving them access to any other alarm system operations.
One-Touch Regular Arming Press and hold the [
One-Touch Force Arming Press and hold the [
One-Touch Bypass Programming Press and hold the [
One-Touch Stay Arming Press and hold the [
Fast Exit - When the system is already Stay Armed:
To Exit and Stay Arm: Press and hold the the Exit Delay period, the system will return to Stay Arming.
To Exit and Regular Arm: Press and hold the of the Exit Delay period, the control panel will switch to Regular Arming.
To Exit and Force Arm: Press and hold the of the Exit Delay period, the control panel will switch to Force Arming.
* If you have access to both partitions after activating a one-touch feature, press the key corresponding to the desired partition. To select both partitions, press the [1] key then after the confirmation beep press the [2] key.
ENTER] key for 3 seconds* to arm all zones in the partition.
FORCE] key for 3 seconds* to bypass any open Force Zones.
BYP] key for 3 seconds* to access Bypass Programming Mode.
STAY] key for 3 seconds* to arm all zones not defined as Stay Zones.
[STAY]
key for 3 seconds*. The system will switch to Exit Delay. At the end of
[
ENTER
]
key for 3 seconds*. The system will switch to Exit Delay. At the end
[FORCE]
key for 3 seconds*. The system will switch to Exit Delay. At the end
12.10 KEYSWITCH ARMING
A keyswitch can be used to arm and disarm the system. Assign the keyswitch to a specific partition and program the keyswitch to Stay or Regular Arm the assigned partition. Also program the keyswitch to function as a Maintained or Momentary keyswitch. To arm the system using a Maintained Keyswitch, set the keyswitch to the disarm the system set the keyswitch to the keyswitch to the
ON position then turn it back to the OFF position. Repeating this sequence will disarm the system.
12.11 PANIC ALARMS
In case of emergency, the Spectra system provides up to three panic alarms. These panic alarms, if programmed, will immediately generate an alarm after pressing and holding two specific keys for two seconds, as described below. Press and hold keys [1] and [3] for a panic alarm. Press and hold keys [4] and [6] for a panic or medical alarm. Press and hold keys [7] and [9] for a panic or fire alarm.
12.12 AUTO-ARMING*
Each partition can be programmed to arm every day at the time specified by the Auto-Arm Timer or for the period specified by the No Movement Timer. The user can program the Auto-Arm Timer by using the System Master Code, Master Code 1 or Master Code 2. Please note that the control panel will enter a 60-second Exit Delay period before
arming the system. At this point, Auto-Arming can be cancelled by entering a valid access code.
12.13 ALARM MEMORY DISPLAY
A record of all alarm situations that occur will be stored in memory. After disarming the system, pressing the [MEM] key will display which zones were in alarm during the alarm period. To exit the Alarm Memory Display, press the
[
CLEAR] key. The control panel will erase the contents of the alarm memory every time the system is armed.
ON position. To
OFF position. To arm the system using a Momentary Keyswitch, set the
* Not to be used with UL installations
54 REFERENCE & INSTALLATION MANUAL
12.14 PROGRAMMING CHIME ZONES
Users can program which zones will be Chime Enabled. A Chime Enabled zone will cause the keypad to emit a rapid intermittent beep tone (
BEEP-BEEP-BEEP-BEEP) advising the user every time it is opened. Each keypad must be
Chime Programmed separately.
10-ZONE LED KEYPAD:
Press and hold any key from [1] to [10] for 3 seconds to activate or deactivate Chiming for zones 1 to 10. For example, press and hold the [1] key to enable chiming on zone 1. If after pressing and holding a key, the keypad emits a confirmation beep, this means the chime feature has been enabled for that zone. If the keypad emits a rejection beep, this means the chime feature has been disabled for the corresponding zone.
16-ZONE LED KEYPAD:
Press and hold the [9] key. Enter the 2-digit (01 to 16) zone number(s). When the corresponding LED is on, the zone is chimed. When the corresponding LED is off, the zone is unchimed. When the desired zones are chimed, press
[
ENTER].
LCD KEYPAD:
Press and hold the [9] key. Enter the 2-digit (01 to 16) zone number(s), or use the arrow keys to scroll through the zones. and when the appropriate zone is displayed, press the [ press [
ENTER].
12.15 KEYPAD MUTING*
Press and hold the [CLEAR] key for 3 seconds to enable or disable keypad muting. When muted, the keypad will only beep when a key is pressed or when the keypad emits a Rejection or Confirmation Beep. All other beep functions are disabled.
FNC1] key. When the desired zones are chimed,
12.16 KEYPAD BACKLIGHT (1686H and 1686V Only)
The illumination level behind the keys can be modified to suit the user’s needs. There are four backlight levels. The
[
MEM] key is used to set the desired level. Each consecutive push of the [MEM] key will increase the backlight level
until the maximum level is reached. After reaching the maximum level, the backlight level will return to the lowest level and the whole process is repeated. To change the backlight level:
How do I Modify The Backlight?
1) Press and hold the [MEM] key for 3 seconds
2) The [
3) Press the [
4) Press [
MEM] key will illuminate
MEM] key to set the desired backlight level
CLEAR] or [ENTER] to exit
* Not to be used with UL installations
SPECTRA SERIES 55
FCC WARNINGS
IMPORTANT INFORMATION
This equipment complies with Part 68 of the FCC rules subpart D and CS-
03. Inside the cover of this equipment is a label that contains, among other information, the FCC registration number of this equipment.
NOTIFICATION TO TELEPHONE COMPANY
Upon request, customer shall notify telephone company of particular line to which the connection will be made, and provide the FCC registration number and the ringer equivalence of the protective circuit.
FCC REGISTRATION NUMBER:5A7CAN-22633 - AL - E RINGER EQUIVALENCE NUMBER:0.1B (U.S. & CANADA) USOC JACK: RJ31X (USA), CA31A (CANADA)
TELEPHONE CONNECTION REQUIREMENTS
Except for telephone company provided ringers, all connections to the telephone network shall be made through standard plugs and telephone company provided jacks, or equivalent, in such a manner as to allow for easy, immediate disconnection of terminal equipment. Standard jacks shall be so arranged that, if plug connected thereto is withdrawn, no interference to operation of equipment at customer's premises which remains connected to telephone network shall occur by reason of such withdrawal.
INCIDENCE OF HARM
Should terminal equipment/protective circuitry cause harm to telephone network, telephone company shall, where practicable, notify customer that temporary disconnection of service may be required; however, where prior notice is not practicable, the telephone company may temporarily discontinue service if action is deemed reasonable in circumstances. In case of temporary discontinuance, telephone company shall promptly notify customer and will be given opportunity to correct the situation.
CHANGES IN TELEPHONE COMPANY EQUIPMENT OR FACILITIES
The telephone company may make changes in its communication facilities, equipment operations or procedures, where such actions are reasonably required and proper in its business. Should any such changes render customer's terminal equipment incompatible with the telephone company facilities, the customer shall be given adequate notice to effect the modifications to maintain uninterrupted service.
GENERAL
This equipment shall not be used on coin telephone lines. Connection to party line service is subject to state tariffs.
RINGER EQUIVALENCE NUMBER (REN)
The ren is useful to determine the quantity of devices that you may connect to your telephone line and still have all of those devices ring when your telephone number is called. In most, but not all areas, sum of the ren's of all devices connected to one line should not exceed five (5.0). To be certain of the number of devices that you may connect to your line, you may want to contact your local telephone company.
EQUIPMENT MAINTENANCE FACILITY
If you experience trouble with this telephone equipment, please contact facility indicated below for information on obtaining service or repairs. The telephone company may ask that you disconnect this equipment from network until problem is corrected or until you are sure that the equipment is not malfunctioning.
FCC PART 15, WARNINGS INFORMATION TO USER
This equipment has been tested and found to comply with the limits for Class B digital devices, pursuant to Part 15 of FCC rules. These limits are designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio frequency energy, and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to equipment intermittently, the user is encouraged to try to correct the interference by one or more of the following measures: (1) re orient or relocate the receiving antenna; (2) increase the separation between the equipment and receiver; (3) connect the equipment to an outlet on a circuit other than the one to which the receiver is connected, or (4) consult the dealer or an experienced radio/tv technician for assistance.
CAUTION:
Changes or modifications not expressly approved by PARADOX SECURITY SYSTEMS could void the user's authority to operate the equipment.
WARRANTY
The Seller warrants its products to be free from defects in materials and workmanship under normal use for a period of one year (except as indicated otherwise). Except as specifically stated herein, all express or implied warranties whatsoever, statutory or otherwise, including without limitation, any implied warranty of merchantability and fitness for a particular purpose, are expressly excluded. Because Seller does not install or connect the products and because the products may be used in conjunction with products not manufactured by Seller. Seller cannot guarantee the performance of the security system. Seller obligation and liability under this warranty is expressly limited to repairing or replacing, at Seller's option, any product not meeting the specifications. In no event shall the Seller be liable to the buyer or any other person for any loss or damages whether direct or indirect or consequential or incidental, including without limitation, any damages for lost profits stolen goods, or claims by any other party, caused by defective goods or otherwise arising from the improper, incorrect or otherwise faulty installation or use of the merchandise sold.
ATTACHMENT LIMITATION NOTICE
The Industry Canada label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements. The Department does not guarantee the equipment will operate to the user's satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
CAUTION: Users should not attempt to make such connections themselves, but should contact the appropriate electrical inspection authority, or electrician, as appropriate.
The Load Number (LN) assigned to each terminal device denotes the percentage of the total load to be connected to a telephone loop which is
56 REFERENCE & INSTALLATION MANUAL
used by the device, to prevent overloading. The termination on a loop may consist of any combination of devices subject only to the requirement that the total of the Load Numbers of all of the devices does not exceed 100.
Industry Canada certification is only applicable to installation of devices which include transformers approved by the Canadian Standards Association (CSA).
RESTRICTIONS CONCERNANT LE RACCORDEMENT DE MATÉRIEL
L'étiquette d'Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme à certaines normes de protection, d'exploitation et de sécurité des réseaux de télécommunications. Le Ministère garantir toutefois pas que le matériel fonctionnera à la satisfaction de l'utilisateur.
Avant d'installer ce matériel, l'utilisateur doit s'assurer qu'il est permis de le raccorder aux installations de l'entreprise locale de télécommunication. De plus, le matériel doit être installé en suivant une méthode acceptable de raccordement. L'abonné ne doit pas oublier qu'il est possible que la conformité aux conditions énoncées ci-dessus n'empêchent pas la dégradation du service dans certaines situations.
Les réparations de matériel homologué doivent être effectuées par un centre de service d'entretien canadien autorisé désigné par le fournisseur. La compagnie de télécommunications peut demander à l'utilisateur de débrancher un appareil à la suite de réparations ou de modifications effectuées par l'utilisateur ou à cause d'un mauvais fonctionnement.
UL AND ULC WARNINGS
UL AND C-UL INSTALLATION NOTES
This equipment is UL listed in accordance with standard UL1023 (Household Burglar -- Alarm Systems Units), standard UL985 (Household Fire Warning Units) and standard UL1635 (Digital Alarm Communicator System Units). This equipment has the capability of being programmed with features not verified for use in UL installations. To stay within these standards, the installer should use the following guidelines when configuring the system:
All components of the system should be UL listed for the intended application.
If the system will be used for “Fire” detection, the installer should refer to NFPA Standards #72, Chapter 2. In addition, once installation is complete, the local fire authority must be notified of the installation.
This equipment must be verified by a qualified technician once every three years.
All keypads must use a tamper switch.
Maximum allowed entry delay is 45 seconds.
Maximum allowed exit delay is 60 seconds.
Minimum 4 minutes for bell cut-off time.
The following features do not comply with UL requirements: Bypass Recall and Auto Trouble Shutdown.
Do not connect the primary indicating device to a relay. The installer must use the bell output.
To comply with UL985, the auxiliary power output should not exceed 200mA. Please refer to Table 2: Current Consumption Table on page 9.
Pour sa propre protection, l'utilisateur doit s'assurer que tous les fils de mise à la terre de la source d'energie électrique, des lignes téléphoniques et des canalisations d'eau métalliques, s'il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales.
AVERTISSEMENT: L'utilisateur ne doit pas tenter de faire ces raccordements lui-même; il doit avoir recours à une service d'inspection des installations électriques, ou à un électricien, selon le cas.
L'indice de charge (IC) assigné à chaque dispositif indique, pour éviter toute surcharge, le pourcentage de la charge totale qui peut être raccordée à un circuit téléphonique bouclé utilisé par ce dispositif. La terminaison du circuit bouclé peut être constituée de n'importe quelle combinaison de dispositifs, pourvu que la somme des indices de charge de l'ensemble des dispositifs ne dépasse pas 100.
La certification d'Industrie Canada s'applique seulement aux installations d'appareils utilisant un transformateur approuvé par l'Association Canadienne de Normalisation (CSA).
RECOMMENDED:
EOL resistor part #2011002000
For 1728/EX, 1738/EX UL Installations: Basler Electric BE156240CAA007 16.5VAC min. 40VA
12vdc 4Ah rechargeable acid/lead or gel cell backup battery (YUASA model #NP7-12 recommended) for residential use. Use a 7Ah battery to comply with fire requirements.
Wheelock 46T-12 siren
All outputs are Class 2 or power-limited, except for the battery terminal.The Class 2 and power-limited fire alarm circuits shall be installed using CL3, CL3R, CL3P, or substitute cable permitted by the National Electrical Code, ANSI/NFPA 70.
For technical support in the US and Canada, call 1-800-791­1919, Monday to Friday, 8 a.m. to 8 p.m. EST. Technical support can also be reached by fax at (450) 491­2313, or via e-mail at support@paradox.ca.
SPECTRA SERIES 57
INDEX
Numerics
24Hr. Buzzer Zone 22 24Hr. Delayed Fire Zone 23 24Hr. Standard Fire Zone 23
A
AC Power 9 Access Code Length 17 Access Code Programming 51 Access Codes 16 Account Numbers 36 Ademco Contact ID 37 Ademco Contact ID Options 37 Ademco Express 37 Adjust Clock 44 Alarm Memory Display 54 Alarm Options 30 Alarm Relay 10 Alarm Relay Options 42 Alarm Report Code Transmission, Delay 25 Alarm Types 24 Alternate Dial Option 39 Answer Upload/Download Software 45 Answer WinLoad Software 49 Answering Machine Override 48 Arm Only 18 Arming and Disarming Options 27 Arming Report Codes 33 ATZ- Zone Doubling 25 Auto Event Buffer Transmission 49 Auto Force Arming 27 Auto Test Report 39 Auto-Arming On No Movement 28 Auto-Arming On Time 28 Auto-Arming Options 28 Auxiliary Power 9
B
Backlight, Keypad 55 Battery Charge Current 43 Battery, Backup 9 Beep On Exit Delay 29 Beep On Trouble 44 Bell Cut-Off Timer 30 Bell on Communication Failure 38 Bell Output Connection 10 Bell Squawk On Arm/Disarm With Keypad 29 Bell Squawk On Arm/disarm with Remote Control 29 Burglary Zones, 24 Hr. 22 Buzzer Zone 22 Bypass Options, Supervision 47 Bypass Programming 53 Bypass Recall Feature 53 Bypass Zones 24
Connecting
Bells or Sirens 10 Double Zone Inputs 11 Fire Zones 13 Keypad Zones 12 Keypads 12 Keyswitches 13 PGMs 10 Single Zone Inputs 11
Telephone Lines 10 Contact ID Options 37 Current Consumption Table 9
D
Data Display Mode 14 Delay Before Alarm Report Code Transmission 25 Delay Between Dialing Attempts 39 Delay Power Failure Report 39 Delay, Pager Report 37 Delayed Fire Zone 23 Dial Tone Delay 38 Dialer settings 32 Dialing Attempts 39 Dialing Method 38 Disarm Reporting Options 40 Disarming 52 Double Zone Inputs 11 Duress Code 18
E
Entry Delay 21 EOL Zones 25 Event Buffer Transmission 49 Event Call Direction 38 Exit Delay 29 Expansion Input 19 Expansion Inputs Reassigned 20
F
Feature Select Programming Method 14 Fire Circuits 13 Fire Zone, Delayed 23 Fire Zone, Standard 24 Hr. 23 Follow Zones 22 Force Arming 53 Force Zones 25
G
Global PGM 41 Ground 8
H
Hardware Reset 43
C
Call Back Feature 49 Call Upload/Download Software 45 Call WinLoad Software 49 Cancel Communication 45 Central Station Telephone Numbers 36 Charge Current 43 Chime Zones 55 Clock Adjust 44 Configuring The LED Keypads 14
58 REFERENCE & INSTALLATION MANUAL
I
Input Speed 25 Installation 7 Installer Code 17 Installer Lock 43 Installer Quick Functions Keys 45 Installer Test Mode 45 Instant Arming 52 Intellizone 24
K
Key. See Memory Card Keypad Audible Trouble Warning 44 Keypad Backlight 55 Keypad Installation 12 Keypad Muting 55 Keypad Panic Options 31 Keypad Tamper Supervision 44 Keypad Zone Connection 12 Keyswitch Arming 54 Keyswitch Connections 13 Keyswitch Options 25 Keyswitch Zone 22
Power 9 Power Failure Report Delay 39 Programmable Output Connections 10 Programmable Outputs 41 Programming Access Codes 51 Programming Chime Zones 55 Programming Methods 13 Programming Using a Keypad 13 Pulse Ratio 38
Q
Quick Arming 29 Quick Functions Keys (Installer) 45
L
Length of Access Codes 17 Location and Mounting 7 Lock Master Code 18 Lock-out 43
M
Manual Bypass Programming 53 Maximum Dialing Attempts 39 Memory Card 16 Memory Display 54 Modify Zone Numbering 20 Mounting 7 Multiple Feature Select Programming Method 14 Muting 55
N
No Arming On Battery Fail 27 No Arming on Supervision Loss 47 No Arming On Tamper Trouble 27 No Audible Feedback Upon Stay Arming 29 No Exit Delay When Arming with Remote Control 29 No Movement Auto-Arming 28 Number of Rings 48
O
One-Touch Arming 29, 54 Options
Alarm 30 Arming and Disarming 27 Auto-Arming 28 Keyswitch 25 User code 17 Zone 23
Override Answering Machine 48
P
Pager Delay 37 Pager Reporting Format 37 Panel Answer Options 48 Panel Identifier 48 Panic Alarms 54 Panic Options 31 Partition Account Numbers 36 Partition Assignment, Zone 23 Partitioning 43 PC Password 48 PC Telephone Number 48 PGM (Control Panel)
Activation Event 41 Deactivation Event 41 PGM Delay 42 Strobe Options 42
PGM Activation, User Code Option 18
R
Real-Time Clock 44 Reassign Keypad Zone 2 19 Reassign Zones to Expansion Inputs 20 Recall Bypass 53 Recent Close Delay 39 Recycle Alarm 30 Regular Arming 52 Regular Arming Switches to Force Arming 27 Report Codes 33 Reporting and Dialer settings 32 Reporting Formats 36 Re-Program All Expansion Modules 47 Reset, Hardware 43 Restrict Arming On Battery Fail 27 Restrict Arming on Supervision Loss 47 Restrict Arming On Tamper Trouble 27 Rings 48
S
Single Zone Inputs 11 Software, Upload/download 13 Special Alarm Report Codes 34 Special Arming Report Codes 33 Special Disarming Report Codes 34 Special Reporting Codes 35 Standard 24Hr. Fire Zone 23 Stay Arming 52 Stay Delay 27 Stay Zones 24 Strobe Options 42 Supervision Bypass Options 47 Supervision Options, Wireless Transmitter 46 Switch to Stay Arming 27 System Master Code 17 System Real-Time Clock 44 System Settings 43 System Trouble Report Codes 35 System Trouble Restore Codes 35
T
Tamper Bypass Options 30 Tamper Recognition 30 Telephone Line Connection 10 Telephone Line Monitoring (TLM) 40 Telephone Number, PC 48 Telephone Numbers 36 Test Report, Automatic 39 Test Report, Manual 45 Timed Auto-Arming 28 Trouble Display 50
U
Upload/Download Software 13
SPECTRA SERIES 59
User Code Options 17 User Operation 50
W
Winload Software 13 Wireless Bus Module Supervision 46 Wireless Transmitter Low Battery Supervision 46 Wireless Transmitter Supervision Options 46
Z
Zone Alarm Report Codes 34 Zone Alarm Restore Report Codes 34 Zone Doubling 25 Zone Options 23 Zone Partition Assignment 23 Zone Programming 19 Zone Restore Report Options 40 Zone Speed 25 Zone Tamper Report Codes 34 Zone Tamper Restore Report Codes 34
60 REFERENCE & INSTALLATION MANUAL